    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 1

    DACS

    SMPS POWER PLANT

    Model: DACS 48-450

    COMMISIONING MANUAL

  • 8/10/2019 commisioning manual48-450

    2/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 2

    1. ABSTRACT

    DC power plant Commissioning. This document describes the procedure for commissioning of power

    plant.

    2. MAIN SPECIFICATION FOR CABINET

    2.1 MECHANICAL CHARACTERISTICS

    Cabinet DACS 48-450Width 573 mmDepth 600 mm

    Height 1500 mmMax. Number of rectifiers (50A). 9Max. Weight of one module 11 KgMax. Total weight of fullyequipped cabinet

    170 Kg

    2.2 ENVIRONMENTAL CHARACTERISTICS

    Operation temperature : -5C to 55C

    Storage temperature : -5C to +70C

    Relative humidity : 10 to 95% non condensing

    Operating altitude : 0 - 3000 m

    COMMISSIONING MANUALDACS 48-450

  • 8/10/2019 commisioning manual48-450

    3/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 3

    2.3 UPSTEAM CIRCUIT BREAKER TYPE AND CABLE DIAMETER

    DACS 48-450Size and tripping curveCircuit breaker (three phase) 63AMains cable sizeMinimum (mm) 10Maximum (mm) 25

    3. TOOLS AND DOCUMENTS NECESSARY FOR COMMISSIONING

    3.1 Documents needed for commissioning:

    Electrical diagram of system.

    3.2 Test equipments needed for commissioning:

    1 Load Bank Digital Multimeter (DMM) Digital Ammeter

    Note: All measurement tools must be calibrated by external laboratory.

  • 8/10/2019 commisioning manual48-450

    4/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 4

    4. PRELIMINARY CHECKS

    4.1 CONFORMITY WITH THE SPECIFICATION :

    The installation and the connection of the equipment should be checkedbefore all action.

    4.2 INSTALLATION CHECK

    Installation general aspect

    Equipment aspect (no spot, stripe, wrapping, oxidation, edgesmoothing).

    Painting aspect

    Minimum clearance between side and walls: 1 m

    4.3 CABINET CHECK

    1. Check wiring, whether any of the connectors are loose intransportation. Check especially the presence and cross-section of:

    a. The link between 0V bus bar and earth.b. The link between cabinet earth and site earth network.

    2 Check fixing of cabinet.3 In case of false floor, cabinets should be fixed on metallic support

    by 4 points. In case of concrete floor; cabinet is fixed directly on theground by 4 points.

    4 Check for easy opening of doors.

  • 8/10/2019 commisioning manual48-450

    5/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 5

    5. EARTHING GUIDELINES

    1. Two numbers of Earth studs are provided on the topside ofthe power plant with crimping lugs.

    2. Crimp the lugs with proper tools.3. Connect the Earth cable to power plant on any or both Earth

    terminations.4. Use at least 10 Sq. mm. Wires for the termination of earth to

    the power plant.5. Measure the Earth resistance; it should be less than 0.5

    Ohms.6. Proper earth is required to communicate with the remote site

    through RS-485.7. Connect earth to the foundation bolts.8. Separate earth should be used for +Ve grounding.9. Timely watering the earth pit is essential so that its

    resistance will be within limit.10. Use only Copper/Lead Plates and bus bars for earth

    continuity.11. Use at least four earth pits and short it with bus bar to

    achieve good results.12. Improper earth to the power plant may cause failure to the

    power plant due to lightning.

    6. ENERGIESING OF THE POWER PLANT

    1 All disconnecting devices should be in the {{open}} position. Check thatthe mains voltage and frequency is as indicated in the name plate.

    2 Do not install the modules before the mains and battery wirings arecompleted.

    3 For easy accessibility, remove the modules before operate the batteryfuses or disconnecting switches.

    4 Switch ON AC I/P MCB & DC O/P MCB off all the modules.5 A healthy module will indicate DC voltage and current on DSCA by

    pressing UP key on front panel LCD.6 Close all fuse disconnecting switches and load protecting circuits of thepower stations.

    7 Check for proper operation of the system according to technical datasheets.

  • 8/10/2019 commisioning manual48-450

    6/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 6

    7. COMMISSIONNING TESTS

    7.1 Check the measurements on System Display AC Voltage Load Voltage Load Current Battery 1 Current Battery 2 Current Battery 3 Current System Current Battery Status

    7.2 OPERATING CHECKS Float Voltage 54.0V 1% at 27C Charge Voltage 55.2V 1% at 27C Switch OFF mains, the system will change over from mains I/P to battery,

    which will generate alarm of Mains Low with audible alarm. The power cut off or pre alarm when the battery voltage reaches the

    setting threshold Load volt low and Bat disconnect alarm displayed.To achieve this test, replace the battery by the DC power supply anddisconnect all the rectifiers.

    Check FR/FC XX NOT PRE alarm by switching off the I/P O/P MCB ofrectified module.

    Decrease system Float voltage till 44.0 V. Rectifier under voltage operatesand on FR/FC as an alarm red LED DC Fail / DC UV glows. The samealarm is extended to DSA as FR/FC XX FAIL .

    Check Battery X absent by Dialing the non-zero AH capacity in menuwithout connecting batteries to the system.

    Check Batt X Isolated by Dialing the 000 AH capacity in menu when allthe batteries are connected to the system.

    Check ONLY ONE BATT!! by manually isolating the batteries one byone. This alarm appears when only one battery is connected and userwants to isolate it.

    Check Temp X comp fail alarm by shorting or disconnecting the

    external battery temperature-sensing device.

  • 8/10/2019 commisioning manual48-450

    7/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 7

    8. ALARM TERMINAL BLOCK Connection is made on terminal block Loop ON/OFF characteristics: 100V max. 0.5A

    Alarm on terminal block:

    There are two number of NO, NC potential free contacts provided to extend allfault conditions.

    Contacts definition:

    NO Normally Open NC Normally Close P - Pole

    9. SYSTEM ASSIGNMENT

    9.1 SYSTEM MENU PARAMETERTo go into programming mode press Menu select key.Press UP arrow key and Down arrow key for scrolling the parameters inmenu.The parameters in the Menu are as follows:

    13. Mains High (480V to 470V).14. Mains Low (320V to 340V).15. System over load (100% to 105%)16. System Float V (44.0V to 56.4V)17. System Charge V (44.6V to 57.0V)18. Load Voltage HI (56.0 V to 57.0V)19. Load Voltage Low (45.5 V to 46.5V)20. Bat 1 AH cap (000, 100, 200------ 2000)21. Bat 2 AH cap (000, 100, 200------ 2000)22. Bat 3 AH cap (000, 100, 200------ 2000)23. Bat Disconnect V (44.4V to 45.5V)24. Bat Reconnect V (51.6V to 55.2V)25. No of FR/FCs (1 to 9)26. Edit FR/FC No (1 to 9)

    a) Set Float Volt (44.0V to 56.4V)b) Set Charge Volt (44.6V to 57.0V)c) Set Over Volt (56.0V to 57.0V)d) Set under Volt (44.5V to 45.5V)e) Set over Load (40% to 110%)

  • 8/10/2019 commisioning manual48-450

    8/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 8

    27. Temp comp limit (50.4 to 52.8)9.2 SYSTEM Menu Tree (Flow chart)

    EnterEnter Enter

    Enter Enter

    Enter Enter

    Enter Enter

    Enter Enter

    Enter Enter

    Enter Enter

    Enter Enter

    Enter Enter

    Enter Enter

    Press Menu

    Set value Exit

    Set value Exit

    Mains high

    Mains low

    System overload

    Set value Exit

    System Float V Set value Exit

    System ChargeV

    Set value Exit

    Load voltage hi Set value Exit

    Load voltagelow

    Set value Exit

    Bat 1 AH cap Set value Exit

    Bat 2 AH cap Set value Exit

    Bat 3 AH cap Set value Exit

    Enter password

  • 8/10/2019 commisioning manual48-450

    9/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 9

    Enter Enter

    Enter Enter

    Enter Enter

    Enter

    Enter Enter

    Enter Enter

    Enter Enter

    Enter Enter

    Enter Enter

    Enter Enter

    BatDisconnect

    Set value Exit

    Set value Exit

    Set value Exit

    Bat reconnect

    No of FR/FCs

    Edit FR/FC No(Slot no)

    Set Float Volt Set value Exit

    Set ChargeVolt

    Set value Exit

    Set Over Volt Set value Exit

    Set under Volt Set value Exit

    Set over Load Set value Exit

    Temp complimit

    Set value Exit

  • 8/10/2019 commisioning manual48-450

    10/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 10

    9.3 PARAMETER PROGRAMING PROCEDURE

    While normal working of power plant on display the upper portion shows Systemcurrent ,Load current, System voltage, Battery1 current, Battery2 current,Battery 3 current, Mains voltage.The lower portion of LCD will display status of system and any alarm occurredduring normal working condition.

    To change settings of the parameters in the power plant go into menu.

    System will ask for a password.Using UP & DOWN, arrow keys adjust number 203 on display and press ENTERkey. Now the user can enter into menu.

    Menu AlarmSelect Reset Enter

    SYSTEM CURR 450 AUTO CHARGE

    Menu Alarm

    Select Reset Enter

    DC VOLTS 54.0PASSWORD 203

  • 8/10/2019 commisioning manual48-450

    11/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 11

    1. The first parameter in menu is Mains HI.

    a. Press menu select key. Lower portion of LCD will display the parameterMains HI and the Upper portion will display the present setting.

    b. If Mains HI is not to be changed go to the next parameter using UParrow key.

    c. To change the present setting press ENTER Key.d. Present setting will start blinking.e. Using UP arrow and DOWN arrow key set the new value.f. Press ENTER key to acknowledge the new setting.g. Settable range for this parameter is 470V to 480V and the default value is

    480.

    2. The next parameter in menu after Mains HI is Mains Low.

    a. Press UP arrow key after Mains HI menu. Lower portion of LCD willdisplay the parameter Mains low and the Upper portion will display thepresent setting.

    b. If Mains low is not to be changed go to the next or previous parameterusing UP and DOWN arrow keys.

    c. To change the present setting press ENTER Key.d. Present setting will start blinking.

    e. Using UP and DOWN arrow key set the new value.f. Press ENTER key to acknowledge the new setting.g. Settable range for this parameter is 320V to 340V and the default value is

    320.

    Menu AlarmSelect Reset Enter

    480MAINS HI

  • 8/10/2019 commisioning manual48-450

    12/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 12

    3. The next parameter in menu after Mains low is System over load.

    a. Press UP arrow key after Mains low menu. Lower portion of LCD willdisplay the parameter system over load and the Upper portion willdisplay the present setting.

    b. If system over load is not to be changed go to the next or previousparameter using UP and DOWN arrow keys.

    c. To change the present setting press ENTER Key.d. Present setting will start blinking.e. Using UP and DOWN arrow key set the new value.

    f. Press ENTER key to acknowledge the new setting.g. Settable range for this parameter is 100 to 105% and the default value is

    105%.

    Menu AlarmSelect Reset Enter

    320MAINS LOW

    Menu Alarm

    Select Reset Enter

    105SYSTEM OVERLOAD

  • 8/10/2019 commisioning manual48-450

    13/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 13

    4. The next parameter in menu after System overload is System float V.

    a. Press UP arrow key after System over load menu. Lower portion of LCDwill display the parameter System float V and the Upper portion willdisplay the present setting.

    b. If System float V is not to be changed go to the next or previousparameter using UP and DOWN arrow keys.

    c. To change the present setting press ENTER Key.d. Present setting will start blinking.e. Using UP and DOWN arrow key set the new value.f. Press ENTER key to acknowledge the new setting.g. Settable range for this parameter is 44.0V to 57.0V and the default value

    is 54.0V.

    5. The next parameter in menu after System float V is System charge V.

    a. Press UP arrow key after System float V menu. Lower portion of LCD willdisplay the parameter System charge V and the Upper portion willdisplay the present setting.

    b. If System charge V is not to be changed go to the next or previousparameter using UP and DOWN arrow keys.

    c. To change the present setting press ENTER Key.d. Present setting will start blinking.e. Using UP and DOWN arrow key set the new value.

    f. Press ENTER key to acknowledge the new setting.g. Settable range for this parameter is 44.0V to 57.0V and the default valueis 55.2V.

    Note: There is a lock (0.6V difference) between system float voltage andsystem charge voltage (always charge voltage > float voltage).

    Menu AlarmSelect Reset Enter

    54.0SYSTEM FLOAT V

  • 8/10/2019 commisioning manual48-450

    14/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 14

    6. The next parameter in menu after System charge V is Load voltage HI.

    a. Press UP arrow key after System charge V menu. Lower portion of LCDwill display the parameter Load voltage HI and the Upper portion willdisplay the present setting.

    b. If Load voltage HI is not to be changed go to the next or previousparameter using UP and DOWN arrow keys.

    c. To change the present setting press ENTER Key.d. Present setting will start blinking.e. Using UP and DOWN arrow key set the new value.f. Press ENTER key to acknowledge the new setting.

    g. Settable range for this parameter is 56.0V to 57.0V and the default valueis 56.1.

    Menu AlarmSelect Reset Enter

    55.2SYSTEM CHARGE V

    Menu AlarmSelect Reset Enter

    56.1LOAD VOLTAGE HI

  • 8/10/2019 commisioning manual48-450

    15/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 15

    7. The next parameter in menu after Load voltage HI is Load voltage low.

    a. Press UP arrow key after Load voltage HI menu. Lower portion of LCDwill display the parameter Load voltage low and the Upper portion willdisplay the present setting.

    b. If Load voltage HI is not to be changed, go to the next or previousparameter using UP and DOWN arrow keys.

    c. To change the present setting press, ENTER Key.d. Present setting will start blinking.e. Using UP and DOWN arrow key set the new value.f. Press ENTER key to acknowledge the new setting.g. Settable range for this parameter is 45.5V to 46.5V and the default value

    is 45.7.

    8. The next parameter in menu after Load voltage low is Bat 1 AH CAP.

    a. Press UP arrow key after Load voltage low menu. Lower portion of LCDwill display the parameter Bat 1 AH CAP and the Upper portion willdisplay the present setting.

    b. If Bat 1 AH CAP is not to be changed go to the next or previousparameter using UP and DOWN arrow keys.c. To change the present setting press ENTER Key.d. Present setting will start blinking.e. Using UP and DOWN arrow key set the new value.

    Menu AlarmSelect Reset Enter

    45.7LOAD VOLTAGE LOW

  • 8/10/2019 commisioning manual48-450

    16/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 16

    f. Press ENTER key to acknowledge the new setting.g. Settable range for this parameter is 000 to 2000 and the default value is

    200.Note: To isolate battery 1 set bat 1 AH cap 000AH.CAUTION: Enter the correct AH capacity of the battery afterreconnecting to the power plant.

    9. The next parameter in menu after Bat 1 AH CAP is Bat 2 AH CAP.

    a. Press UP arrow key after Bat 1 AH CAP menu. Lower portion of LCD willdisplay the parameter Bat 2 AH CAP and the Upper portion will displaythe present setting.

    b. If Bat 2 AH CAP is not to be changed go to the next or previousparameter using UP and DOWN arrow keys.

    c. To change the present setting press ENTER Key.d. Present setting will start blinking.e. Using UP and DOWN arrow key set the new value.f. Press ENTER key to acknowledge the new setting.

    g. Settable range for this parameter is 000 to 2000 and the default value is200.Note: To isolate battery 2 set bat 2 AH cap 000AH.

    CAUTION: Enter the correct AH capacity of the battery after reconnectingto the power plant.

    Menu AlarmSelect Reset Enter

    200BAT 1 AH CAP

  • 8/10/2019 commisioning manual48-450

    17/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 17

    10. The next parameter in menu after Bat 2 AH CAP is Bat 3 AH CAP.

    a. Press UP arrow key after Bat 2 AH CAP menu. Lower portion of LCD willdisplay the parameter Bat 3 AH CAP and the Upper portion will displaythe present setting.

    b. If Bat 3 AH CAP is not to be changed go to the next or previousparameter using UP and DOWN arrow keys.

    c. To change the present setting press ENTER Key.d. Present setting will start blinking.e. Using UP and DOWN arrow key set the new value.f. Press ENTER key to acknowledge the new setting.g. Settable range for this parameter is 000 to 2000 and the default value is

    200.

    Note: To isolate battery 3 set bat 3 AH cap 000AH.CAUTION: Enter the correct AH capacity of the battery after reconnectingto the power plant.

    Menu AlarmSelect Reset Enter

    200BAT 2 AH CAP

    Menu Alarm

    Select Reset Enter

    200BAT 3 AH CAP

  • 8/10/2019 commisioning manual48-450

    18/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 18

    11. The next parameter in menu after Bat 3 AH CAP is Bat Disconnect V.

    a. Press UP arrow key after Bat 3 AH CAP menu. Lower portion of LCD willdisplay the parameter Bat Disconnect V and the Upper portion willdisplay the present setting.

    b. If Bat Disconnect V is not to be changed go to the next or previousparameter using UP and DOWN arrow keys.

    c. To change the present setting press ENTER Key.d. Present setting will start blinking.e. Using UP and DOWN arrow key set the new value.f. Press ENTER key to acknowledge the new setting.g. Settable range for this parameter is 44.4V to 45.5V and the default value

    is 44.4V.

    12. The next parameter in menu after Bat Disconnect V is Bat Reconnect V.

    a. Press UP arrow key after Bat Disconnect V menu. Lower portion of LCDwill display the parameter Bat Reconnect V and the Upper portion willdisplay the present setting.

    b. If Bat Reconnect V is not to be changed go to the next or previousparameter using UP and DOWN arrow keys.

    c. To change the present setting press ENTER Key.d. Present setting will start blinking.e. Using UP and DOWN arrow key set the new value.f. Press ENTER key to acknowledge the new setting.

    Menu AlarmSelect Reset Enter

    44.4BAT DISCONNECT V

  • 8/10/2019 commisioning manual48-450

    19/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 19

    g. Settable range for this parameter is 51.6V to 55.2V and the default valueis 51.6V.

    13. The next parameter in menu after Bat Reconnect V is No of FR/FCs.

    a. Press UP arrow key after Bat Reconnect V menu. Lower portion of LCDwill display the parameter No of FR/FCs and the Upper portion willdisplay the present setting.

    b. If No of FR/FCs is not to be changed go to the next or previousparameter using UP and DOWN arrow keys.

    c. To change the present setting press ENTER Key.

    d. Present setting will start blinking.e. Using UP and DOWN arrow key set the new value.f. Press ENTER key to acknowledge the new setting.NOTE: Always enter the number of FR/FCs switched ON. Other wisethere will be alarm of Mod CONFIG Err or FR/FC?? NOT PRE.

    Menu AlarmSelect Reset Enter

    51.6BAT RECONNECT V

    Menu AlarmSelect Reset Enter

    09No OF FR/FCs

  • 8/10/2019 commisioning manual48-450

    20/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 20

    14. The next parameter in menu after No of FR/FCs is EDT FR/FC No.a. Press UP arrow key after No of FR/FCs menu. Lower portion of LCD will

    display the parameter EDT FR/FC No and the Upper portion will displaythe present setting.

    b. If EDT FR/FC No is not to be changed go to the next or previousparameter using UP and DOWN arrow keys.

    c. To edit the parameters in required module press ENTER Key.d. Last edited module number will start blinking.e. Using UP and DOWN arrow key set the new module is to be edited.f. Press ENTER key.

    The parameters of module, which user can change from system level, are:

    a. SET FLOAT VOLT (44.0V to 57.0V) default is 54.0V.b. SET CHARGE VOLT (44.0V to 57.0V) default is 55.2V.c. SET OVER VOLT (56.0V to 57.0V) default is 57.0V.d. SET UNDER VOLT (45.0V to 46.0V) default is 45.0V.e. SET OVER LOAD (40% to 110%) default is 110%.

    Note: All the above FR/FC parameters are effective only when controller isnot communicating with the module. Controller settings will over ride thelocally generated module parameters.

    a. Set float voltage:

    I. Press menu select display appears SET FLOAT VOLT in lowerportion of the LCD and value from 44.0 to 57.0 in the upper portion.II. Press, ENTER key. Value in upper portion starts blinking.III. Using UP and DOWN arrow key set required float voltage.IV. Press Enter key to acknowledge the program.

    Menu AlarmSelect Reset Enter

    01EDIT FR/FC No

  • 8/10/2019 commisioning manual48-450

    21/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 21

    b. Set Charge voltage:I. If float voltage is not to be set after SET FLOAT VOLT in lower

    portion of the LCD press up arrow key to get SET CHARGE VOLTin the lower portion.

    II. Press ENTER Key. The upper portion will start blinking with currentsetting (from 44.0 to 57.0)

    III. Press, ENTER key. Value in upper portion starts blinking.IV. Using UP and DOWN arrow key set required charge voltage.V. Press Enter key to acknowledge the program.

    c. Set Over voltage:I. If charge voltage is not to be set press UP arrow key after SET

    CHARGE VOLT, the next menu is SET OVER VOLT. Settablerange is from 56.0 to 57.0 in the upper portion.II. Press, ENTER key. Value in upper portion starts blinking.III. Using UP and DOWN arrow key set required over voltage.IV. Press Enter key to acknowledge the program.

    Menu AlarmSelect Reset Enter

    54.0SET FLOAT VOLT

    Menu AlarmSelect Reset Enter

    55.2SET CHARGE VOLT

  • 8/10/2019 commisioning manual48-450

    22/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 22

    d. Set Under voltage:I. If over voltage is not to be set press UP arrow key after SET

    OVER VOLT, the next menu is SET UNDER VOLT. Settablerange is from 45.0 to 46.0 in the upper portion.

    II. Press, ENTER key. Value in upper portion starts blinking.III. Using UP and DOWN arrow key set required under voltage.IV. Press Enter key to acknowledge the program.

    e. Set OVER LOAD:I. If Under voltage is not to be set press UP arrow key after SET

    UNDER VOLT, the next menu is SET OVER LOAD. Settablerange is from 40% to 110% in the upper portion.

    II. Press, ENTER key. Value in upper portion starts blinking.III. Using UP and DOWN arrow key set required overload inpercentage.

    IV. Press Enter key to acknowledge the program.V. Default value is 110%

    Menu AlarmSelect Reset Enter

    56.0SET OVER VOLT

    Menu AlarmSelect Reset Enter

    45.0SET UNDER VOLT

  • 8/10/2019 commisioning manual48-450

    23/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 23

    15. The next parameter in menu after No of FR/FCs is EDT FR/FC No.

    a. Press UP arrow key after No of FR/FCs menu. Lower portion of LCD willdisplay the parameter EDT FR/FC No and the Upper portion will displaythe present setting.

    b. If EDT FR/FC No is not to be changed, go to the next or previousparameter using UP and DOWN arrow keys.

    c. To edit the parameters in required module press ENTER Key.d. Last edited module number will start blinking.e. Using UP and DOWN arrow key set the new module to be edited.f. Press ENTER key.

    Menu AlarmSelect Reset Enter

    110%SET OVER LOAD

  • 8/10/2019 commisioning manual48-450

    24/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 24

    9.4 SYSTEM IDENTIFICATION MENU(TO FACILITATE RS 485)

    9.4.1 SYSTEM Menu Tree (Flow chart)

    Enter Enter Enter

    EnterEnter Enter

    Enter Enter

    Enter Enter

    Enter Enter Enter

    Enter Enter

    Enter Enter Enter

    Enter Enter

    Enter Enter Enter

    Press Enter &Down arrow

    Set first byte Set second byte

    Set value

    Set third byte

    Hand shake byte

    System make Exit Set fourth byte

    Date ofcommisning

    Set month Exit

    Batt 1 make Exit

    Exit

    Date of

    commisning

    Set year ExitSet month

    Set year

    Set value

    Batt 2 make Exit

    Date ofcommisnin

    Set year ExitSet month

    Set value

    Batt 2 make Exit

    Date ofcommissioning

    Set year ExitSet month

    Set value

  • 8/10/2019 commisioning manual48-450

    25/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 25

    8.4.2 SYSTEM IDENTITY PROGRAMMINGThis programming is to be done while installing the power plant and batteries.

    To change settings in system identity programming menu press ENTER &DOWN arrow key at a time and while releasing first ENTER & then DOWN arrowkeys.

    1. The first parameter in this menu is HAND SHAKE BYTE.

    a. Press Enter & Down arrow keys simultaneously. Lower portion of LCD willdisplay the parameter HAND SHAKE BYTE and the Upper portion willdisplay the present setting.

    b. If Mains HI is not to be changed, go to the next parameter using UParrow key.

    c. To change the present setting press, ENTER Key.

    d. First byte will start blinking.e. Using UP arrow and DOWN arrow key set first byte and press Enter key.f. Second byte will start blinking.g. Using UP arrow and DOWN arrow key set second byte and press Enter

    key.h. Third byte will start blinking.i. Using UP arrow and DOWN arrow key set third byte and press Enter key.

    j. Fourth byte will start blinking.k. Using UP arrow and DOWN arrow key set fourth byte.l. Press ENTER key to acknowledge the new setting.m. Settable range for every byte is 00 to FF.

    Note: First four bytes of RS 485 remote monitoring system data and powerplant should be always same otherwise there will be communication error.

    Menu AlarmSelect Reset Enter

    FF FF FF FFHAND SHAKE BYTE

  • 8/10/2019 commisioning manual48-450

    26/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 26

    2. The next parameter in this menu after HAND SHAKE BYTE is SystemMAKE. In this menu user has to give the identity number to identify thepower plant make from remote computer.

    a. Press UP arrow keys after HAND SHAKE BYTE Lower portion of LCDwill display the parameter SYSTEM MAKE and the Upper portion willdisplay the present setting.

    b. If SYSTEM MAKE is not to be changed, go to the next parameter usingUP arrow key.

    c. To change the present setting press, ENTER Key.d. The present value will start blinking.e. Using UP arrow and DOWN arrow key set new setting.f. Press ENTER key to acknowledge the new setting.g. Settable range for every byte is 00 to FF.

    3. The next parameter in this menu after SYSTEM MAKE is DATE OFCOMMISIONN. In this menu user has to set the month and year ofcommissioning of power plant.

    a. Press UP arrow keys after SYSTEM MAKE Lower portion of LCD willdisplay the parameter DATE OF COMMISIONN and the Upper portionwill display the present setting.

    b. If DATE OF COMMISIONN is not to be changed, go to the nextparameter using UP arrow key.

    c. To change the present setting press, ENTER Key.

    d. The last month setting entered will start blinking.e. Using UP arrow and DOWN arrow key set new setting. Press ENTER key.f. The last year-entered setting will start blinking.g. Using UP arrow and DOWN arrow key set new setting. (MM YY)h. Press ENTER key to acknowledge the new setting.

    Menu AlarmSelect Reset Enter

    FFSYSTEM MAKE

  • 8/10/2019 commisioning manual48-450

    27/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 27

    4. The next parameter in this menu after power plant DATE OF

    COMMISIONN is BATT 1 MAKE. In this menu user has to give theidentity number to identify the Battery 1 make connected to power plantfrom remote computer.

    a. Press UP arrow keys after DATE OF COMMISIONN Lower portion ofLCD will display the parameter BATT 1 MAKE and the Upper portion willdisplay the present setting.

    b. If BATT 1 MAKE is not to be changed, go to the next parameter usingUP arrow key.

    c. To change the present setting press, ENTER Key.

    d. The present value will start blinking.e. Using UP arrow and DOWN arrow key set new setting.f. Press ENTER key to acknowledge the new setting.g. Settable range for every byte is 00 to FF.

    Menu AlarmSelect Reset Enter

    05 06DATE OF COMMISIONN

    Menu AlarmSelect Reset Enter

    FFBATT 1 MAKE

  • 8/10/2019 commisioning manual48-450

    28/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 28

    5. The next parameter in this menu after BATT 1 MAKE is DATE OFCOMMISIONN of battery 1. In this menu user has to set the month andyear of commissioning of Battery1 connected to power plant.

    a. Press UP arrow keys after BATT 1 MAKE Lower portion of LCD willdisplay the parameter DATE OF COMMISIONN and the Upper portionwill display the present setting.

    b. If DATE OF COMMISIONN is not to be changed, go to the nextparameter using UP arrow key.

    c. To change the present setting press, ENTER Key.d. The last month setting entered will start blinking.e. Using UP arrow and DOWN arrow key set new setting. Press ENTER key.

    f. The last year-entered setting will start blinking.g. Using UP arrow and DOWN arrow key set new setting. (MM YY)h. Press ENTER key to acknowledge the new setting.

    6. The next parameter in this menu after Battery1 DATE OF COMMISIONNis BATT 2 MAKE. In this menu user has to give the identity number toidentify the Battery 2 make connected to power plant from remotecomputer.

    a. Press UP arrow keys after DATE OF COMMISIONN Lower portion ofLCD will display the parameter BATT 2 MAKE and the Upper portion willdisplay the present setting.

    Menu AlarmSelect Reset Enter

    12 06DATE OF COMMISIONN

  • 8/10/2019 commisioning manual48-450

    29/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 29

    b. If BATT 2 MAKE is not to be changed, go to the next parameter usingUP arrow key.

    c. To change the present setting press, ENTER Key.d. The present value will start blinking.e. Using UP arrow and DOWN arrow key set new setting.f. Press ENTER key to acknowledge the new setting.g. Settable range for every byte is 00 to FF.

    7. The next parameter in this menu after BATT 2 MAKE is DATE OFCOMMISIONN of battery 2. In this menu user has to set the month andyear of commissioning of Battery1 connected to power plant.

    a. Press UP arrow keys after BATT 2 MAKE Lower portion of LCD willdisplay the parameter DATE OF COMMISIONN and the Upper portionwill display the present setting.

    b. If DATE OF COMMISIONN is not to be changed, go to the nextparameter using UP arrow key.

    c. To change the present setting press, ENTER Key.d. The last month setting entered will start blinking.e. Using UP arrow and DOWN arrow key set new setting. Press ENTER key.f. The last year-entered setting will start blinking.g. Using UP arrow and DOWN arrow key set new setting.h. Press ENTER key to acknowledge the new setting.

    Menu AlarmSelect Reset Enter

    FFBATT 2 MAKE

  • 8/10/2019 commisioning manual48-450

    30/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 30

    8. The next parameter in this menu after Battery2 DATE OF COMMISIONNis BATT 3 MAKE. In this menu user has to give the identity number to

    identify the Battery 3 make connected to power plant from remotecomputer.

    a. Press UP arrow keys after DATE OF COMMISIONN Lower portion ofLCD will display the parameter BATT 3 MAKE and the Upper portion willdisplay the present setting.

    b. If BATT 3 MAKE is not to be changed, go to the next parameter usingUP arrow key.

    c. To change the present setting press, ENTER Key.d. The present value will start blinking.

    e. Using UP arrow and DOWN arrow key set new setting.f. Press ENTER key to acknowledge the new setting.g. Settable range for every byte is 00 to FF.

    Menu AlarmSelect Reset Enter

    12 06DATE OF COMMISIONN

    Menu Alarm

    Select Reset Enter

    FFBATT 3 MAKE

  • 8/10/2019 commisioning manual48-450

    31/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 31

    9. The next parameter in this menu after BATT 3 MAKE is DATE OFCOMMISIONN of battery 3. In this menu user has to set the month andyear of commissioning of Battery3 connected to power plant.

    a. Press UP arrow keys after BATT 3 MAKE Lower portion of LCD willdisplay the parameter DATE OF COMMISIONN and the Upper portionwill display the present setting.

    b. If DATE OF COMMISIONN is not to be changed, go to the nextparameter using UP arrow key.

    c. To change the present setting press, ENTER Key.d. The last month setting entered will start blinking.e. Using UP arrow and DOWN arrow key set new setting. Press ENTER key.f. The last year-entered setting will start blinking.

    g. Using UP arrow and DOWN arrow key set new setting.h. Press ENTER key to acknowledge the new setting.

    Menu AlarmSelect Reset Enter

    12 06DATE OF COMMISIONN

  • 8/10/2019 commisioning manual48-450

    32/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 32

    10. SYSTEM STATUS AND ALARM INDICATIONSThe upper portion of the LCD always keeps on scrolling system voltages andcurrents i.e. MAINS VOLT XXX , SYSTEM VOLT XX.X , SYSTEM CURRXXX , BATT 1 CURR XXX , BATT 2 CURR XXX , BATT 3 CURR XXX , andLOAD CURR XXX (XXX is the actual value).In normal working condition, scrolling of parameters may be stopped to observecontinuously any one parameter by pressing ENTER key. When scrolling isstopped, there is * sign after the parameter.

    Again to put into scrolling mode press, ENTER key. Scrolling will start and *sign will disappear.The status and any alarm occurred in system is displayed on the lower portion ofthe LCD. If there is any fault occurred in the system then it will go on scrolling the

    massages.10.1 SYSTEM STATUS

    1. When individual battery current is less than 3% of the AH capacity i.e. fullycharged then the system will be in Auto float mode

    Menu AlarmSelect Reset Enter

    SYSTEM CURR 450 * AUTO CHARGE

    Menu AlarmSelect Reset Enter

    BATT 1 CURR 003 AUTO FLOAT

  • 8/10/2019 commisioning manual48-450

    33/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 33

    2. When any battery current is more than 5% of the AH capacity i.e. Batteryin discharged condition then the system will be in Auto charge mode.

    3. When Mains AC is in specified limits and system is working on Mains AC

    voltage then there is a status of POWER MAINS.

    4. When Mains AC is in out of specified limits and system is working onstand by Generator AC source then there is a status of POWER STANDBY.

    Menu AlarmSelect Reset Enter

    BATT 1 CURR 020 AUTO CHARGE

    Menu AlarmSelect Reset Enter

    BATT 1 CURR 040POWER MAINS

    Menu AlarmSelect Reset Enter

    BATT 1 CURR 040POWER STAND BY

  • 8/10/2019 commisioning manual48-450

    34/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 34

    5. When Mains ac is out of specified limits then system will change over tobattery. At this time, there is an alarm of LOAD ON BATT.

    6. To monitor the individual module Voltage and current press UP Arrow key.One by one it will display FR/FC Voltage and current of the number ofmodules present in the system in scrolling manner and will restore to thesystem display after releasing the Key. Also it will show the version Noand software Check sum value of the individual FR/FC module.

    Menu AlarmSelect Reset Enter

    BATT 1 CURR 040LOAD ON BATTERY

    Menu AlarmSelect Reset Enter

    54.0 V 50.1AFR/FC 1 1-DOE9

  • 8/10/2019 commisioning manual48-450

    35/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 35

    7. To monitor the Version No and Check sum value of the system press Alarm reset and Down arrow Key simultaneously.

    8. To observe the temperature of the battery temperature compensationsensors press down arrow key in normal working condition. Firsttemperature is of battery1 second is of battery2 and third is of battery3.

    9. To observe the ID of system press alarm reset and ENTER keysimultaneously. The ID of the system is settable from 00 to 0F. To changeID inset Jumper on the DSA mother board on different position to achievethe required ID(Useful in RS-485 communications.)

    Menu AlarmSelect Reset Enter

    BATT 1 CURR 02028 27 C 25 C 28 C

    Menu AlarmSelect Reset Enter

    CHECK SUM 2FDAVERSION NO. 001

  • 8/10/2019 commisioning manual48-450

    36/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 36

    Mother Board view

    10. To observe that whether modules are communicating to the system or notpress ENTER and UP arrow Key. The COM STATUS will be a 01FF Ifall nine modules are working and communicating with DSCA. Here 1 is for9 th module (1 if ON and 0 if OFF). Next F in COM status stands for

    Menu AlarmSelect Reset Enter

    BATT 1 CURR 020PWR PLANT ID 0F

    DSA MOTHER BOARD

    Jumper to change ID

    B a t

    t M o n

    i t o r c a r d s l o t

    A C D C C a r

    d s l o t

    P F C B T C B o a r d

    c a b l e

    Control connector

    Ac connector

    Curr sense Con

    C o m m u n

    i c a t

    i o n

    c a b l e

  • 8/10/2019 commisioning manual48-450

    37/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 37

    module no 5 to 8. This value will change from 0 to F as per the modulecondition (ON or OFF). Next F in COM status stands for module no 1 to4. This value will change from 0 to F as per the module condition (ON orOFF). The details to identify which module is not communicating withDSCA is given in the table below.

    Mod8

    Mod7

    Mod6

    Mod5

    HEXCODE

    Mod4

    Mod3

    Mod2

    Mod1

    HEXCODE

    OFF OFF OFF OFF 0 OFF OFF OFF OFF 0OFF OFF OFF ON 1 OFF OFF OFF ON 1OFF OFF ON OFF 2 OFF OFF ON OFF 2OFF OFF ON ON 3 OFF OFF ON ON 3

    OFF ON OFF OFF 4 OFF ON OFF OFF 4OFF ON OFF ON 5 OFF ON OFF ON 5OFF ON ON OFF 6 OFF ON ON OFF 6OFF ON ON ON 7 OFF ON ON ON 7ON OFF OFF OFF 8 ON OFF OFF OFF 8ON OFF OFF ON 9 ON OFF OFF ON 9ON OFF ON OFF A ON OFF ON OFF AON OFF ON ON B ON OFF ON ON B

    ON ON OFF OFF C ON ON OFF OFF CON ON OFF ON D ON ON OFF ON DON ON ON OFF E ON ON ON OFF EON ON ON ON F ON ON ON ON F

    Menu AlarmSelect Reset Enter

    SYSTEM CURR 107COM STATUS 01FF

  • 8/10/2019 commisioning manual48-450

    38/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 38

    When all 9 modules are working and communicating with the DSCA then there is01FF in COM status.

    11. To load the default setting (Factory settings) press, ENTER and MenuSelect Key there will be a message of DEFAULT LOADED and systemwill follow factory settings.

    10.2 SYSTEM ALARMS

    1. When Mains AC is within the specified limits and still battery is dischargingthen there is an alarm of AC OK BATT DISC.

    Menu Alarm

    Select Reset Enter

    BATT 1 CURR 040 AC OK BATT DISC

    Menu AlarmSelect Reset Enter

    SYSTEM CURR 107DEFAULT LOADED

  • 8/10/2019 commisioning manual48-450

    39/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 39

    2. When Stage 2 surge arrestor fails due to lightning then there is an alarmof STAGE II FAIL.

    3. When the system current more than the preset percentage entered in themenu then there is an alarm of SYSTEM OVER LOAD. This alarmappears as per the total number of working modules in the system. The

    settable range in the menu is 100% to 105% of the system workingcapacity.

    Menu AlarmSelect Reset Enter

    BATT 1 CURR 040STAGE II FAIL

    Menu AlarmSelect Reset Enter

    SYSTEM CURR 472SYSTEM OVER LOAD

  • 8/10/2019 commisioning manual48-450

    40/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 40

    4. When the number of working module preset in the system more than thenumber of module entered in the Menu then there is an alarm of FR/FCCONFIG ERR. This alarm will disappear only when correct number ofworking modules entered in Menu.

    5. Due to any reason, if module is failed and on module, there is an alarm ofFR/FC FAIL then there is an alarm of FR/FC XX FAIL on system (XXstands for number of module).

    6. Due to any reason, if module is not communicating with system orswitching OFF any module, creates an alarm of FR/FC XX NOT PRE(XX stands for number of module). If the module is identified then it willshow the respective number or it will show FR/FC ?? NOT PRE. If themodule number is unknown, check number of FR/FC entered in menu.

    Menu AlarmSelect Reset Enter

    SYSTEM CURR 100FR/FC CONFIG ERR

    Menu AlarmSelect Reset Enter

    SYSTEM CURR 100FR/FC XX FAIL

  • 8/10/2019 commisioning manual48-450

    41/46

  • 8/10/2019 commisioning manual48-450

    42/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 42

    9. When Mains AC voltage is less than the Mains low cut OFF voltage set inthe menu then there is an alarm of MAINS LOW. During the alarm the

    mains supply of the modules are isolated due to which modules are inOFF condition. When Mains AC voltage restores back with in the specifiedlimit (Hysterisis of 10V is given operate and release levels) there is a delayof 10sec (approx) to turn ON the modules.

    10. If some how the system voltage increases beyond the LOAD VOLT HIvalue then there is an alarm of LOAD VOLT HIGH. This alarm is PRE

    WARN alarm for battery disconnection.

    Menu AlarmSelect Reset Enter

    MAINS VOLT 490MAINS HIGH

    Menu AlarmSelect Reset Enter

    MAINS VOLT 310MAINS LOW

  • 8/10/2019 commisioning manual48-450

    43/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 43

    11. If Mains AC voltage is out of specified limit then the system works onbattery and battery starts discharging. When the battery voltage reachesbelow the LOAD VOLT LOW value set in the menu then there is an alarm

    of LOAD VOLT LOW. This alarm is PRE WARN indication beforebattery disconnection voltage.

    12. When battery is discharged below LOAD VOLT LOW condition and whenthe battery voltage reaches below the BAT DISCONNECT V value set inthe menu then there is an alarm of BATT DISCONNECT. This alarmdisconnects all the batteries (through DC contactors) connected to thesystem. Now battery will reconnect only when the system voltage rises

    above the BAT RECONNECT V set in Menu.

    Menu AlarmSelect Reset Enter

    SYSTEM VOLT 45.5LOAD VOLT LOW

    Menu AlarmSelect Reset Enter

    SYSTEM VOLT 56.1

    LOAD VOLT HIGH

  • 8/10/2019 commisioning manual48-450

    44/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 44

    13. The system is having facility to monitor Battery room temperature. Thesystem corrects the DC voltage in 72mV per degree centigrade law. At

    27 C there is no correction but as temperature increases system voltagedecreases and wise versa. 55.8V is the lock where further decrease intemperature will not cause any correction. Menu contains Settable rangefor lock in lower side where there is decrease in temperature. When thesensor is short or is open then there is an alarm of TEMP. X COMP.FAIL (X stands for battery number i.e. 1 or 2 or 3).

    NOTE: The system has provision to monitor temperature of each batterywith separate probes. When any of the sensors is open or short creates, anAlarm. Among all three temperatures, correction in system voltage is madeaccording to highest temperature.

    14. When programming 000AH isolates battery then the respective batterygets isolated and an alarm of BATT X ISOLATED (X stands for batterynumber i.e. 1 or 2 or 3) generated.

    Menu AlarmSelect Reset Enter

    SYSTEM VOLT 44.4

    BATT DISCONNECT

    Menu AlarmSelect Reset Enter

    SYSTEM VOLT 55.8TEMP. X COMP. FAIL

  • 8/10/2019 commisioning manual48-450

    45/46

    DACSSMPS Power plant division

    DACS Revision No. Revision Date Issue no. Issue Date Page No.

    SMPS CS 00 20.06.07 00 20.06.07 45

    15. If any battery does not connected to battery terminal and user hasselected other than 000AH for same battery then there is an alarm ofBATTERY X ABSENT (X stands for battery number i.e. 1 or 2 or 3).

    NOTE: Whenever any of the above alarm operates there is an audible aswell as visual alarm. Buzzer is used as audio alarm whereas alarm isvisualized on LCD display. To cut OFF audio alarm press alarm reset key.Whenever audio alarm is cut OFF visual alarm remains continuously untilthe alarm is rectified.

    Menu AlarmSelect Reset Enter

    SYSTEM VOLT 54.0BATT X ISOLATED

    Menu AlarmSelect Reset Enter

    SYSTEM VOLT 54.0BATTERY X ABSENT

  • 8/10/2019 commisioning manual48-450

    46/46

    DACSSMPS Power plant division

    END OF DOCUMENT