Circuit Breaker Selection 1

download Circuit Breaker Selection 1

of 28

Transcript of Circuit Breaker Selection 1

  • 8/12/2019 Circuit Breaker Selection 1

    1/28

    Circuit Breaker Selection

    (Section 10.5)

  • 8/12/2019 Circuit Breaker Selection 1

    2/28

    AC Circuit Breakers

    A circuit breaker is a mechanical switch capable

    of interrupting fault currents and of reclosing.

    Classified as low voltage circuit breakers (< 1500

    V) OR power circuit breakers (>1500 V)

    Different types depending on the medium in

    which the arc is elongated (air, oil, SF6, vacuum..)

  • 8/12/2019 Circuit Breaker Selection 1

    3/28

    AC Circuit Breakers

  • 8/12/2019 Circuit Breaker Selection 1

    4/28

    Reclosing of circuit breakers

    Most faults are temporary and self clearing.

    It is assumed that whatever caused the fault

    has disintegrated.

    In EHV systems the standard practice is to

    reclose only once.

    Multiple shot reclosing in EHV systems maylead to transient stability problems

  • 8/12/2019 Circuit Breaker Selection 1

    5/28

    Circuit breaker selection

    Modern circuit breaker standards are based onsymmetrical interrupting current.

    Only the symmetrical fault current at the point of

    location is calculated and a circuit breaker withsymmetrical interrupting capability equal to the

    calculated current is chosen.

    Can handle asymmetrical fault current if dc offset is

    not too large Power circuit breakers with a 2 cycle interrupting

    time are designed to handle asymmetrical currents

    up to 1.4 times the symmetrical interrupting

    capability

  • 8/12/2019 Circuit Breaker Selection 1

    6/28

    Fault current components

  • 8/12/2019 Circuit Breaker Selection 1

    7/28

    Fault current components

  • 8/12/2019 Circuit Breaker Selection 1

    8/28

    Fault current components

    SubtransientPeriod

    Steady StatePeriod

    TransientPeriod

  • 8/12/2019 Circuit Breaker Selection 1

    9/28

    Fault current calculation

    Period Fault Current Generator

    Reactance

    Synchronous

    Motor

    Reactance

    Induction

    Motor

    reactance

    ( 50 hp)

    Subtranient

    period

    Subtransient

    currentOR

    Asymmetrical

    current

    XdG Xdsm Xdsm

    Transient

    period

    Transient

    current

    OR

    Symmetrical

    current

    XdG Xdsm

    = 1.5Xdsm

    Xdsm

    = ???Xdsm

  • 8/12/2019 Circuit Breaker Selection 1

    10/28

  • 8/12/2019 Circuit Breaker Selection 1

    11/28

    E/X method for circuit breaker

    selection

    If X/R is > 15, the DC offset may not have

    decayed sufficiently and a method for

    correcting the calculated fault current to

    account for the DC and AC time constants

    needs to be applied.

    If X/R is unknown, the calculated fault current

    should not be more than 80% of the breakers

    interrupting capability.

  • 8/12/2019 Circuit Breaker Selection 1

    12/28

    Application Guide for AC High Voltage Circuit

    Breakers rated on a Symmetrical Current Basis

  • 8/12/2019 Circuit Breaker Selection 1

    13/28

    Application Guide for AC High Voltage Circuit

    Breakers rated on a Symmetrical Current Basis

  • 8/12/2019 Circuit Breaker Selection 1

    14/28

    Voltage ratings

    Rated maximum voltage: Designated the maximum

    rms line-line operating voltage.

    Rated low frequency withstand voltage: The

    maximum rms line to line voltage the circuitbreaker can withstand without insulation damage.

    Rated impulse withstand voltage: The maximum

    crest voltage of a voltage pulse with standard riseand delay times that the breaker insulation can

    withstand.

  • 8/12/2019 Circuit Breaker Selection 1

    15/28

    Voltage ratings

    Rated voltage range factor K: The range of

    voltage for which the symmetrical interrupting

    capability times the operating voltage is

    constant.

  • 8/12/2019 Circuit Breaker Selection 1

    16/28

    Current ratings

    Rated continuous current: The maximum rmscurrent that the breaker can carry continuouslywhile closed without heating.

    Rated short circuit current: The maximum rmssymmetrical current that the breaker can safelyinterrupt at rated maximum voltage.

    Rated momentary current: The maximum rmsasymmetrical current that the breaker canwithstand while closed without damage.

  • 8/12/2019 Circuit Breaker Selection 1

    17/28

    Current ratings

    Rated interrupting time: The time in cycles from

    the instant the trip coil is energized to the

    instant the fault current is cleared.

    Rated interrupting MVA: For a three phase

    circuit breaker, this is 3times the rated

    maximum voltage in kV times the rated short

    circuit current in kA.

  • 8/12/2019 Circuit Breaker Selection 1

    18/28

    Symmetrical interrupting capability of

    a 69 kV class breaker

  • 8/12/2019 Circuit Breaker Selection 1

    19/28

    Symmetrical interrupting capability of

    a 69 kV class breaker

    Symmetrical interrupting current increases

    from rated short circuit current I = 19 kA at

    rated maximum voltage Vmax= 72.5 kV to Imax=

    KI = (1.21)(19) = 23 kA at an operating voltage

    of Vmin= (

    ) =

    72.5

    1.21= 60 kV.

    For any operating voltage V between Vmin

    and

    Vmaxthe symmetrical interrupting current is(72.5)(19)

  • 8/12/2019 Circuit Breaker Selection 1

    20/28

    Symmetrical interrupting capability of

    a 69 kV class breaker

    For any operating voltage V below Vmin the

    symmetrical interrupting current remains

    constant at Imax= KI = 23 kA

  • 8/12/2019 Circuit Breaker Selection 1

    21/28

    Example 1

    The calculated symmetrical fault is 17 kA at a

    three phase bus where the operating voltage

    voltage is 64 kV. The X/R ratio at the is unknown.

    Select a circuit breaker from the given tables forthis bus.

  • 8/12/2019 Circuit Breaker Selection 1

    22/28

    Example 1

    Consider the next highest available standardvoltage from the table. Therefore consider a 69kV class breaker.

    At 64 kV, the symmetrical interrupting capabilityof the breaker is

    (72.5)(19)

    64= 21.5 kA

    If X/R is unknown, the calculated fault current

    should not be more than 80% of the breakersinterrupting capability. We need to do thischeck

  • 8/12/2019 Circuit Breaker Selection 1

    23/28

    Example 1

    Calculated fault current = 17 kA

    Breakers interrupting capability = 21.5 kA

    Therefore

    17

    21.5= 79.1 % < 80%

    So the calculated fault current is not more than

    80% of the breakers interrupting capabilitytherefore the chosen 69 kV class breaker issuitable for the application.

  • 8/12/2019 Circuit Breaker Selection 1

    24/28

    Example 2

    A 69 kV circuit breaker has a voltage range factor

    K of 1.21, a continuous current rating of 1.2 kA

    and a short circuit current rating of 19 kA at a

    maximum rated voltage of 72.5 kV. Determinethe maximum symmetrical interrupting

    capability of the breaker and determine the

    voltage range at which the symmetricalinterrupting current is lower than the maximum

    symmetrical interrupting current

  • 8/12/2019 Circuit Breaker Selection 1

    25/28

    Example 2

    Maximum symmetrical interrupting capability

    = K x rated short circuit current

    = 1.21(19)

    = 23 kA

    Vmin= (

    ) =

    72.5

    1.21= 60 kV.

    Therefore the voltage range at which the

    symmetrical interrupting current is lower than themaximum symmetrical interrupting current is 60 kV

    72.5 kV

  • 8/12/2019 Circuit Breaker Selection 1

    26/28

    Tutorial Exercises

  • 8/12/2019 Circuit Breaker Selection 1

    27/28

    Tutorial Exercises

  • 8/12/2019 Circuit Breaker Selection 1

    28/28

    Tutorial Exercises