24. Circuit Breaker Circuit Breaker Protection from overload in electrical circuits.
Circuit Breaker Selection 1
Transcript of Circuit Breaker Selection 1
-
8/12/2019 Circuit Breaker Selection 1
1/28
Circuit Breaker Selection
(Section 10.5)
-
8/12/2019 Circuit Breaker Selection 1
2/28
AC Circuit Breakers
A circuit breaker is a mechanical switch capable
of interrupting fault currents and of reclosing.
Classified as low voltage circuit breakers (< 1500
V) OR power circuit breakers (>1500 V)
Different types depending on the medium in
which the arc is elongated (air, oil, SF6, vacuum..)
-
8/12/2019 Circuit Breaker Selection 1
3/28
AC Circuit Breakers
-
8/12/2019 Circuit Breaker Selection 1
4/28
Reclosing of circuit breakers
Most faults are temporary and self clearing.
It is assumed that whatever caused the fault
has disintegrated.
In EHV systems the standard practice is to
reclose only once.
Multiple shot reclosing in EHV systems maylead to transient stability problems
-
8/12/2019 Circuit Breaker Selection 1
5/28
Circuit breaker selection
Modern circuit breaker standards are based onsymmetrical interrupting current.
Only the symmetrical fault current at the point of
location is calculated and a circuit breaker withsymmetrical interrupting capability equal to the
calculated current is chosen.
Can handle asymmetrical fault current if dc offset is
not too large Power circuit breakers with a 2 cycle interrupting
time are designed to handle asymmetrical currents
up to 1.4 times the symmetrical interrupting
capability
-
8/12/2019 Circuit Breaker Selection 1
6/28
Fault current components
-
8/12/2019 Circuit Breaker Selection 1
7/28
Fault current components
-
8/12/2019 Circuit Breaker Selection 1
8/28
Fault current components
SubtransientPeriod
Steady StatePeriod
TransientPeriod
-
8/12/2019 Circuit Breaker Selection 1
9/28
Fault current calculation
Period Fault Current Generator
Reactance
Synchronous
Motor
Reactance
Induction
Motor
reactance
( 50 hp)
Subtranient
period
Subtransient
currentOR
Asymmetrical
current
XdG Xdsm Xdsm
Transient
period
Transient
current
OR
Symmetrical
current
XdG Xdsm
= 1.5Xdsm
Xdsm
= ???Xdsm
-
8/12/2019 Circuit Breaker Selection 1
10/28
-
8/12/2019 Circuit Breaker Selection 1
11/28
E/X method for circuit breaker
selection
If X/R is > 15, the DC offset may not have
decayed sufficiently and a method for
correcting the calculated fault current to
account for the DC and AC time constants
needs to be applied.
If X/R is unknown, the calculated fault current
should not be more than 80% of the breakers
interrupting capability.
-
8/12/2019 Circuit Breaker Selection 1
12/28
Application Guide for AC High Voltage Circuit
Breakers rated on a Symmetrical Current Basis
-
8/12/2019 Circuit Breaker Selection 1
13/28
Application Guide for AC High Voltage Circuit
Breakers rated on a Symmetrical Current Basis
-
8/12/2019 Circuit Breaker Selection 1
14/28
Voltage ratings
Rated maximum voltage: Designated the maximum
rms line-line operating voltage.
Rated low frequency withstand voltage: The
maximum rms line to line voltage the circuitbreaker can withstand without insulation damage.
Rated impulse withstand voltage: The maximum
crest voltage of a voltage pulse with standard riseand delay times that the breaker insulation can
withstand.
-
8/12/2019 Circuit Breaker Selection 1
15/28
Voltage ratings
Rated voltage range factor K: The range of
voltage for which the symmetrical interrupting
capability times the operating voltage is
constant.
-
8/12/2019 Circuit Breaker Selection 1
16/28
Current ratings
Rated continuous current: The maximum rmscurrent that the breaker can carry continuouslywhile closed without heating.
Rated short circuit current: The maximum rmssymmetrical current that the breaker can safelyinterrupt at rated maximum voltage.
Rated momentary current: The maximum rmsasymmetrical current that the breaker canwithstand while closed without damage.
-
8/12/2019 Circuit Breaker Selection 1
17/28
Current ratings
Rated interrupting time: The time in cycles from
the instant the trip coil is energized to the
instant the fault current is cleared.
Rated interrupting MVA: For a three phase
circuit breaker, this is 3times the rated
maximum voltage in kV times the rated short
circuit current in kA.
-
8/12/2019 Circuit Breaker Selection 1
18/28
Symmetrical interrupting capability of
a 69 kV class breaker
-
8/12/2019 Circuit Breaker Selection 1
19/28
Symmetrical interrupting capability of
a 69 kV class breaker
Symmetrical interrupting current increases
from rated short circuit current I = 19 kA at
rated maximum voltage Vmax= 72.5 kV to Imax=
KI = (1.21)(19) = 23 kA at an operating voltage
of Vmin= (
) =
72.5
1.21= 60 kV.
For any operating voltage V between Vmin
and
Vmaxthe symmetrical interrupting current is(72.5)(19)
-
8/12/2019 Circuit Breaker Selection 1
20/28
Symmetrical interrupting capability of
a 69 kV class breaker
For any operating voltage V below Vmin the
symmetrical interrupting current remains
constant at Imax= KI = 23 kA
-
8/12/2019 Circuit Breaker Selection 1
21/28
Example 1
The calculated symmetrical fault is 17 kA at a
three phase bus where the operating voltage
voltage is 64 kV. The X/R ratio at the is unknown.
Select a circuit breaker from the given tables forthis bus.
-
8/12/2019 Circuit Breaker Selection 1
22/28
Example 1
Consider the next highest available standardvoltage from the table. Therefore consider a 69kV class breaker.
At 64 kV, the symmetrical interrupting capabilityof the breaker is
(72.5)(19)
64= 21.5 kA
If X/R is unknown, the calculated fault current
should not be more than 80% of the breakersinterrupting capability. We need to do thischeck
-
8/12/2019 Circuit Breaker Selection 1
23/28
Example 1
Calculated fault current = 17 kA
Breakers interrupting capability = 21.5 kA
Therefore
17
21.5= 79.1 % < 80%
So the calculated fault current is not more than
80% of the breakers interrupting capabilitytherefore the chosen 69 kV class breaker issuitable for the application.
-
8/12/2019 Circuit Breaker Selection 1
24/28
Example 2
A 69 kV circuit breaker has a voltage range factor
K of 1.21, a continuous current rating of 1.2 kA
and a short circuit current rating of 19 kA at a
maximum rated voltage of 72.5 kV. Determinethe maximum symmetrical interrupting
capability of the breaker and determine the
voltage range at which the symmetricalinterrupting current is lower than the maximum
symmetrical interrupting current
-
8/12/2019 Circuit Breaker Selection 1
25/28
Example 2
Maximum symmetrical interrupting capability
= K x rated short circuit current
= 1.21(19)
= 23 kA
Vmin= (
) =
72.5
1.21= 60 kV.
Therefore the voltage range at which the
symmetrical interrupting current is lower than themaximum symmetrical interrupting current is 60 kV
72.5 kV
-
8/12/2019 Circuit Breaker Selection 1
26/28
Tutorial Exercises
-
8/12/2019 Circuit Breaker Selection 1
27/28
Tutorial Exercises
-
8/12/2019 Circuit Breaker Selection 1
28/28
Tutorial Exercises