Characterization of a surface dielectric barrier discharge · The SDBD model (Fig.2) consists of...
Transcript of Characterization of a surface dielectric barrier discharge · The SDBD model (Fig.2) consists of...
-
Characterization of a surface dielectric barrier discharge
A.J.M. Pemen1, F.J.C.M. Beckers
1, E.J.M. van Heesch
1
1Eindhoven University of Technology, Department of Electrical Engineering,
P.O.Box 513, 5600 MB Eindhoven, The Netherlands, email: [email protected]
Abstract: A surface dielectric barrier discharge (SDBD) reactor provides a homogeneous plasma
over a large surface area. This allows surface treatments of foils, textiles or fibers. Here we present
results of a study to characterize the AC and pulsed performance of SDBD with regard to ozone
production, equivalent electrical model, and fast imaging of the plasma development.
Keywords: surface-dielectric barrier discharge, ozone yields, fast imaging.
1. Introduction
Surface Dielectric Barrier Discharges (SDBD) are gen-
erated in a thin layer along along a dielectric surface, at
room temperature and atmospheric pressure [1-4]. SDBD
has a streamer like nature on macroscopic scale. These
streamers move rapidly and have a high density along the
surface, resulting in homogeneous surface treatment.
SDBD reactors are constructed of a dielectric material with
parallel strips (high voltage electrode) at one side, and a
ground plane at the backside (Fig.1).
Fig.1 Example of a SDBD plasma reactor (10x20 cm).
Pulsed and AC operation is possible because any applied
voltage variation dU/dt will result in a displacement cur-
rent in the dielectric barrier which enables discharge cur-
rent to flow. The AC excited plasma consists of small local
discharges which extinguish almost immediately due to
charge accumulation on the dielectric barrier which re-
duces the gap voltage.
For uni-polar ns pulses the SDBD reactor behaves dif-
ferently. The gap voltage is able to exceed the discharge
inception voltage which results in a higher initial electric
field in the gap. The high dU/dt of the pulse slopes results
in a larger discharge current, and in one discharge on the
rising edge and a discharge on the falling edge of the pulse.
Here we present results of a study to characterize the AC
and pulsed performance of SDBD with regard to ozone
production, equivalent electrical model, and fast imaging
of the plasma development.
2. Experimental set-up
The SDBD reactor is constructed of a 1 mm thick Al2O3
plate (10x20 cm). The HV electrodes consist of 20 parallel
platinum strips, printed on top of the dielectric (1 mm wide,
180 mm long, mutual distance 3 mm. A ground plane is
printed at the back. Total capacitance between ground
plane and electrodes is ≈700pF. AC operation was done by
a 22 kHz resonator, with a voltage up to 4 kVrms. Pulsed
operation [5], is performed with pulse voltages up to 7.2
kV (30 ns duration, 20 ns risetime).
We applied ozone measurements to compare chemical
activity of pulsed and AC excited plasma. Uniformly dis-
tributed ambient air is flushed along the SDBD, O3 was
measured by UV absorption (230-290 nm) in the exhaust
of the reactor [6]. An ICCD camera was used to study the
pulsed and AC excited plasma optically (180-800nm,
576x384 pixels, shutter time >5 ns).
Fig.2 Equivalent electrical model for AC SDBD
3. Verification of AC equivalent model
An equivalent electrical model for SDBD is shown in
Fig.2. If an AC voltage (Ue) is applied over the electrodes,
upon reaching the inception voltage, a small, transient
discharge will occur which accumulates charge on the
dielectric surface. The charge causes a voltage drop over
the discharge region, resulting in the quenching of the
discharge so that the electric field drops below the critical
value to maintain the discharge. The voltage over the dis-
charge region Udis increases again when the electrode
Plasma off
Plasma on
Cd
Cg
Ce
Udis
Cd
Cg Udis
Ce
-
voltage increases, resulting in a next discharge. This
process will repeat itself, resulting in a burst of micro
discharges and a nearly constant voltage Udis over the
discharge zone. So the electric charge accumulated on the
dielectric combined with the applied voltage to the elec-
trodes will determine when the voltage in the gap is high
enough to initiate the discharges.
The SDBD model (Fig.2) consists of capacitance Cd ,
which represents the capacitance of the plasma layer to the
ground plane, and Cg is the capacitance of the discharge
region. During discharges the voltage Udis over the dis-
charge region remains more or less constant as explained
before, here represented by two zener diodes, with a zener
voltage that is equal to the discharge inception voltage. The
electrodes have a constant capacitance Ce to the ground
plane. Note that a single discharge occurs in the model
instead of several micro discharges. The energy dissipation
of the plasma takes place in the zener diodes.
Fig.3 Measured voltage-charge plot for SDBD (integrated reactor
current [total charge q] vs applied rms-electrode voltage).
The voltage-charge Lissajous plot for a SDBD (Fig.3)
can be corrected for capacitance Ce by substracting its
charge from the total electrode charge. This gives curve
1-2-3-4. At point 1 the displacement current through the
reactor will be zero because dUe/dt is zero. The zero
crossing causes an interruption of the previous negative
discharges because the voltage in the discharges (Ug) de-
creases due to the negative displacement current. Voltage
Ug has to reach the positive inception voltage during period
interval 1→2. Now a conductive channel is introduced by
the discharges, during interval 2→3 and 4→1. These
slopes will correspond therefore to capacitance Cd. The
external current will increase substantially during the
discharge periodes. Between 3 and 4 the voltage Ug has to
swing over again and the slope corresponds to the series
connection of Cd and Cg. Negative discharges will occur
during interval 4→1. The width of the plot corresponds to
twice the magnitude of the required minimum external
applied electrode voltage Ue which is necessary to reach
the discharge inception voltage. The voltage Ug (which is
close to the inception voltage) can be calculated by multi-
plying Ue with ratio Cd/(Cd+Cg), since Cg and Cd act as
capacitive divider during interval 1→2 and 3→4.
Cd depends on the amount of discharges covering the
SDBD surface. Fig.4 shows Cd versus the applied rms
voltage. Capacitance Cd has a lower value for lower volt-
ages, because the surface of the SDBD isn’t completely
covered with discharges. For voltages >3kV (≈225W) the
value of Cd stabilizes. At this point the plasma is visually
homogeneous. Second observation is the lower value of Cd
for negative discharges.
Fig. 4 Capacitance Cd vs. applied rms voltage
Fig.5 (a) Results of ozone measurements. (b) Zoom of plot (a)
4. Results of ozone measurements
Figure 5 shows the measured ozone concentrations for
pulsed and AC excitation as function of the applied energy
density of the plasma (J/L). The plasma power for AC
2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6
200
300
400
500
600
Cd (
pF
)
RMS voltage (kV)
positive cycle (2>3)
negative cycle (4>1)
0 500 1000 1500 20000
50
100
150
200
250
300
30 ns pulses, 2.2-7.2 kV
25 kHz AC, 2-4 kV
Ozo
ne c
once
ntr
ation
(p
pm
)
Plasma energy density (J/L)
0 50 100 150 200 250 3000
25
50
75
100
Ozo
ne
con
ce
ntr
atio
n (
pp
m)
Plasma energy density (J/L)
30 ns pulses, 2.2-7.2 kV
25 kHz AC, 2-4 kV
-
operation is varied by the reactor rms voltage, while for
pulsed operation the pulse repetition rate is used to adjust
the power. Only relative low power levels could be reached
for pulsed operation, because of limited repetition rate and
energy per pulse.
The AC plasma produces little O3 for energy densities
3
kV. In this case, the entire SDBD surface is covered with
discharges. Also, the intensity at 3.8 kV is almost similar to
the intensity at 3.47 kV. Apparently, the energy cannot be
converted into a larger plasma surface coverage, resulting
into more intense or faster repetitive discharges. For pulsed
26 mm
-2 -1.5 -1 -0.5 0 0.5 1 1.5 2100
200
300
400
500
600
700
800
900
1000
1100
Distance (mm)
Avera
ge
Inte
nsity
(au)
2.56kV
3.06kV
3.47kV
3.84kV
-2 -1.5 -1 -0.5 0 0.5 1 1.5 2100
200
300
400
500
600
700
800
900
1000
1100
Distance (mm)
Avera
ge
Inte
nsity
(au)
2.56kV
3.06kV
3.47kV
3.84kV
-2 -1.5 -1 -0.5 0 0.5 1 1.5 20
200
400
600
800
1000
1200
1400
Distance (mm)
Avera
ge
In
ten
sity
(au)
3.57kV
4.21kV
5.90kV
7.19kV
9.80kV
-2 -1.5 -1 -0.5 0 0.5 1 1.5 20
200
400
600
800
1000
1200
1400
Distance (mm)
Avera
ge
In
ten
sity
(au)
3.57kV
4.21kV
5.90kV
7.19kV
9.80kV
-
operation, the intensity increases with increasing pulse
voltage.
Scaling and normalizing the various profiles shows that
they are nearly similar for AC and pulsed operation, and
for the various voltage levels (Fig.9). No significant dif-
ference in streamer length or scaled intensity near the high
voltage electrode strip is observed. A persistent mechanism
controls the expansion of the streamers. Presumably the
interacting E field around the strips and the electron fronts
in the head of the streamers from opposite side determine
the expansion of the discharges. Note that Fig.9 gives the
scaled profile for only a limited set of voltage levels.
However, profiles at other voltages are similar.
Fig. 9 Scaled and normalized intensity profiles for both AC and
pulsed operation
Conclusions
An equivalent electrical model is introduced to describe
the AC behavior of a SDBD. The parameters of the model
can be determined from a lissajous plot of the total charge
applied to the SDBD (integral of the measured current) and
the applied rms-voltage. The value for Cd (dielectric sur-
face capacitance) depends on the plasma coverage of the
reactor. The value stabilizes if the applied voltage is large
enough to create homogeneous plasma coverage.
The chemical efficiency of a SDBD plasma for AC or
pulsed operation was compared by measuring ozone con-
centrations in the exhaust of the reactor. Although com-
parison of the pulsed and AC excited plasmas ability to
produce ozone proved to be difficult, it is evident that a
pulsed exited plasma is more efficient in producing ozone.
High speed images showed that, for pulsed operation, the
plasma is already very homogeneous during one single
shot. The plasma profile along the dielectric surface of the
SDBD appeared to be similar for pulsed and AC excited
plasma at different voltage/energy levels. A persistent
mechanism controls the expansion of the streamers.
References
[1] M. Simor et.al. Atmosperic-pressure plasma treatment
of polyester nonwoven fabrics for electrodeless plating,
Surface and Coatings Techn. 172 (2003) 1-6.
[2] L. Cernakova et.al., Surface modification of polypropy
lene non-woven fabrics by atmospheric-pressure
plasma activation followed by acrylic acid grafting,
Plasma Chem.& Plasma Proc., Vol.25, No.4, August
2005
[3] D. Korzec et.al., Insulated surface discharge for
metastables driven processing at atmospheric pressure,
Surface and Coatings Techn. 169-170, (2003),
228-232.
[4] T. Hoder et.al., Investigation of the coplanar barrier
discharge in synthetic air at atmosperic pressure by
cross-correlation spectroscopy, J.Phys.D, Appl.Phys,
41 (2008) 035212.
[5] A. J. M. Pemen, I. V. Grekhov, E. J. M. van Heesch, K.
Yan, S. A. Nair, S. V. Korotkov. Pulsed corona
generation using a diode-based pulsed power generator.
Review of Scientific Instruments, Vol. 74, No.74, 2003
[6] E.J.M. van Heesch, G.J.J. Winands, A.J.M. Pemen,
Evaluation of pulsed streamer corona experiments to
determine the O radical yield, J.Phys.D, Appl.Phys 41
(2008) 234015.
-2 -1.5 -1 -0.5 0 0.5 1 1.5 20
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
Distance (mm)
Scale
d A
ve
rag
e I
nte
nsity
AC: 2.56kV
AC: 3.47kV
Pulse: 5.90kV
-2 -1.5 -1 -0.5 0 0.5 1 1.5 20
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
Distance (mm)
Scale
d A
ve
rag
e I
nte
nsity
AC: 2.56kV
AC: 3.47kV
Pulse: 5.90kV