CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS Sales 1300 NHP NHP | nhp.com.au MOTOR PROTECTION WITH LEADING EDGE TECHNOLOGY, EXPANDABLE PROTECTION AND COMMUNICATION. MOTOR CONTROL

Transcript of CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior...

Page 1: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

CEP7-EELECTRONIC MOTOR PROTECTION RELAYS

Sales 1300 NHP NHP | nhp.com.au

MOTOR PROTECTION WITH LEADING EDGE TECHNOLOGY, EXPANDABLE PROTECTION AND COMMUNICATION.

MOTOR CONTROL

Page 2: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

CEP 7-EDN DeviceNetTM communication module - available for fully adjustable jam / stall protection and thermal warning to indicate imminent overload trip

CEP 7-EPRB Profibus® communication module includes warning for jam trip, overload and underload. Includes device trip and warn status

CEP 7-ETN Ethernet / IP communication module with built-in webserver support for configuration and monitoring

CEP 7-DNCT - hand held programming terminal includes one metre cable to be used with CEP 7-EDN (DeviceNetTM module)

Side mount modules also deliver entry level communication with DeviceNetTM, Profibus® and Ethernet / IP:

FOR FURTHER INFORMATION vIsIT: nhp.com.au/s+s

CEP 7-ERRREMOTE REsET MODULE

CEP 7-EGJGROUND FAULT / JAM PROTECTION AND REMOTE REsET MODULE

CEP 7-EPTPTC THERMIsTOR RELAY AND REMOTE REsET MODULE

CEP 7-EGFGROUND FAULT PROTECTION AND REMOTE REsET MODULE

CEP 7-EJMJAM PROTECTION AND REMOTE REsET MODULE

The new CEP 7 overloads now boast a formidable range of smart add-on modules:

Introduction to CEP 7 electronic overload relays ..........................................................................[3, 4]

CEP 7-ED1 standard electronic overload relays .....................................................................................[5]

Overview of CEP 7-EE features ...........................................................................................................................[6]

CEP 7-EE enhanced electronic overload relays .....................................................................................[7]

CEP 7-E_P pass through electronic overload relays ............................................................................[8]

CEP 7 side mount modules ...................................................................................................................................[9]

CEP 7-CBCT core balance transformers and communication modules ...........................[10]

Accessories ..........................................................................................................................................................[11, 12]

CEP 7 quick reference guide ....................................................................................................................[13, 14]

Dimensions ..........................................................................................................................................................[15, 16]

CEP 7 module technical information ............................................................................................... [17 - 19]

CEP 7-ETN Ethernet Network Communication Module ................................................................[20]

CEP 7-CBCT core balance transformers (technical information) ....................................[21-24]

Trip curves ......................................................................................................................................................................[25]

Technical information ...................................................................................................................................[25, 26]

Contents

• New contactor and overload selection tool

• Calculates full load current of 3-phase motors based on. •kW •Voltage(415,690and1000VAC)

• selection made easy by providing part numbers and product photo.

AVAILABLE FROM THE ITUNES APP STORE NOW!

CONTACTOR SELECT IPHONE APP

2

Page 3: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

Electronic overload relays

CEP 7 comprehensive motor protectionSprecher + Schuh have introduced their new CEP 7, second generation electronic overload protection relays. The new CEP 7 overloads incorporate a greater use of sophisticated electronic control and monitoring. With recent advances in micro electronic technology and the introduction of the ASIC chip set, it has become possible to improve on and add new features to the popular CEP 7 range. The CEP 7 second generation overload now incorporates greater accuracy and versatility whilst providing increased overall protection.

The new CEP 7 incorporates the following improved features:

• Awidersettablecurrentrange(5:1)

• Adjustableclasstripsettings(10,15,20and30)(EEversion)

• Fieldinstallablesidemountmodules(EEversion)

• Anextremelylowpowerconsumptionof150mW

• Robustmountingtocontactor.

Range overview

CEP 7-ED1 basic model

The CEP 7-ED1 is the standard or base model version. The ED1 model is available in the currentrangeof0.1-45A,incorporatesafixedtripclassof10,andissuitedto3phaseoperation. A manual reset function, visible trip indicator and test / reset button are also included.

CEP 7-EE enhanced model

TheenhancedCEP7-EEvariantcoversanoperatingrangeof0.1-800Awithadjustabletripclasssettingsof10,15,20and30(viadipswitchselection).TheEEmodelcanbefurther enhanced by the addition of side mounted plug-in modules.

CEP 7-E_P pass through model

Forcurrentranges1-27Aaversionisavailablethatmountsseparatefromthecontactor.The motor wires pass through CT openings.

Superior phase failure protectionOnboard electronics constantly monitors all motor phases. If the ASIC chip set senses that one or more of the phases is missing during a steady state operation of a fully loaded motor, it will trip in 3 seconds. If a single phase condition is present during starting,theCEP7willtripwithin8seconds(foramotorloadingof>80%).Thesetriptimesaresignificantlyfasterthenconventionalbimetaloverloads.Inaddition,theCEP7relaydetectsa50%phaseimbalanceinthesamewayasaphaseloss.

Rated up to 1000 VACComplies to IEC-60997 for nominal operation voltage of 1000 volts.

27A

45A

90 A

27A

800 A

Dip switch settings (EE version)

ROBUsT MO

U

NT I N G TO CO

NTA

CTOR •

Electronic overload relays for 3 phase motor applications to IEC 60947

CEP 7 ED/EE/E_P x x

PRoDuCT TyPE MoDEL

CuRRENT RANGE oF SINGLE PHASE MoToRS

CuRRENT RANGE oF THREE PHASE MoToRS

CoDE To SuIT CA 7 / CA 6 CoNTACToRS

CEP 7 = 3 phase ED1 = Basic model 3) P =1.0...5.0amps RatedVoltage:690VAC B=CA7-9...23

CEP 7S = 1 phase EE = Enhanced model R=3.2...16amps A=0.1...0.5amps D = CA 7 - 30...43

EE_P = Enhanced pass through 2)

S=5.4...27amps B=0.2...1.0amps E = CA 6 - 60...97

T=9.0...45amps C=1.0...5.0amps F=CA6-115...180

U = 18...90 amps D=3.2...16amps G=CA6-210...420

E=5.4...27amps H = CA 6 - 630...860 4)

F=9.0...45amps

G = 18...90 amps

V = 60...120 amps

RatedVoltage:1000VAC

H=30...150amps

J=40...200amps

K = 60...300 amps

L=100...500amps

M=120...600amps

N = 160...800 amps

Modular in design, clever in application The new CEP 7-EE overloads now offer a formidable range of smart add on modules. Thesesmallsidemountedplug-inmodulesextendtheCEP7capabilitytosomethingmore potent in terms of motor protection. Communication modules are also available.

CEP 7-EPRB Profibus® communication module

CEP 7-EDN DeviceNetTM communication module

CEP 7-ETN EtherNet / IP communication module

CEP 7-ERR Remoteresetmodule

CEP 7-EJM Jam protection and remote reset module

CEP 7-EPT PTC thermistor relay and remote reset module

CEP 7-EGF Ground fault protection and remote reset module

CEP 7-EGJ Groundfault/jamprotectionandremoteresetmodule

CEP 7-ERID Remoteindicationmodule(workswithanysidemodule1)

CEP 7-EE + EDN DeviceNetTM

CEP 7-EE + EPRB Profibus®

NoTE: 1) Not compatible with communication modules

2) Only available in 3 Phase. Current range options available are C, D and E only. Ratedto1000VACwith1000Vratedinsulationcables

3) Only available in 3Phase.CurrentrangeoptionsavailableareA,B,C,D,EandFonly. 4) Ratedupto690VAC3 4

Page 4: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

CEP 7-ED1 standard electronic overload relays

Electronic overload relays for 3 phase motors to IEC 60947

Manual reset, trip class 10 - standard 0.1…45 amps• 5:1currentadjustmentrange

• Lowpowerconsumption(150mW)

• Selfpowered

• Visibletripindicator

• 1N/Ctripcontactand1N/Oalarmcontact

• DirectmountingtoCA7contactorsuptoCA7-97.

APPRox kw RANGE

CuRRENT SETTING RANGE (A) To SuIT CoNTACToR CAT No.

0.02…0.12 0.1…0.5 CA7-9/12/16/23 CEP 7-ED1AB

0.06…0.25 0.2…1.0 CA7-9/12/16/23 CEP 7-ED1BB

0.25…2.2 1.0…5.0 CA7-9/12/16/23 CEP 7-ED1CB

1.5…7.5 3.2…16 CA7-9/12/16/23 CEP 7-ED1DB

2.2…15 5.4…27 CA7-9/12/16/23 CEP 7-ED1EB

4…22 9.0…45 CA 7 - 30/37/43 CEP 7-ED1FD

Electronic overloads for single phase applications to IEC 60947

same features as above, plus: • Optionaljam/stallandgroundfaultprotectionmodule

• Selectableauto/manualreset.

APPRox kw RANGE

CuRRENT SETTING RANGE (A) To SuIT CoNTACToR CAT No.

- 1.0…5.0 CA7-9/12/16/23 CEP 7S-EEPB

- 3.2…16 CA7-9/12/16/23 CEP 7S-EERB

- 5.4…27 CA7-9/12/16/23 CEP 7S-EESB

- 9.0…45 CA 7 - 30/37/43 CEP 7S-EETD

- 18…90 CA7-60/72/85/97 CEP 7S-EEuE

wiring diagrams

MANuAL RESET CLASS 10

SINGLE PHASE

3 phase CEP 7-ED1/EE/E_P Single phase CEP 7S-EE/E_P

5 6

CEP 7-EPRB

CEP 7-EDN

CEP 7-ETN

overview of CEP 7-EE features

Communication options with add-on modulesAllCEP7-EEversionsfrom0.1-800Acanbefittedwithsideaccessories(1peroverload).Inthecaseoffieldbuscommunicationsidemodules,theyprovidethepossibilitytocontrolthecontactororcollectinputsoverthefieldbusnetwork.Further,itthenbecomes possible to monitor trips, warnings and motor operating parameters.

Profibus® - CEP 7-EPRB

• SupportsDP-V0andDP-V1

• Auto-bandupto12MB/s

DeviceNetTM - CEP 7-EDN

• CanalsobestandaloneprogrammedusingCEP7-DNCTprogrammer

EtherNet/IP - CEP 7-ETN

• Built-inwebserversupportforconfigurationandmonitoring

Allcommunicationmodulesaddthefollowingfeatures:

• Overloadwarning

• Jamtripandwarning

• Overloadwarning

• 2inputs

• 1output

• Diagnostics:

-%thermalutilised

-Averagecurrent%FLA

- Device status

- Trip and warn status

MouLDED PowER CoNNECToRS

TEST BuTToN

MECHANICAL TRIP TEST

TRIP STATuS INDICAToR

CoNTRoL TERMINALS

CoNTACToR CoNNECTING MECHANISM

RESET BuTToN

DIP SwITCHES

FLA SETTING DIAL

LoAD TERMINATIoNS

Page 5: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

7 8

CEP 7-EE enhanced electronic overload relays 1)

Electronic overload relays for 3 phase motors to IEC 60947

Auto / manual reset, trip class 10, 15, 20 or 30 - enhanced 0.1 to 800 amps • 5:1currentadjustmentrange

• DirectmountingtoCA7andCA6contactors

• Selfpowered

• Lowpowerconsumption(150mW)

• 1N/Ctripcontactand1N/Oalarmcontact

• Visibletripindicator

• Selectablemanualreset

• Adjustabletripclass10,15,20and30

• OptionalDeviceNet™communicationmodule

• OptionalProfibus® communication module

• OptionalEtherNet/IPcommunicationmodule

• Optionaljam/stallandremoteresetmodule

• OptionalPTCthermistorrelayandremotereset

• Optionalgroundfaultprotectionandremotereset.

APPRox kw RANGE

CuRRENT SETTING RANGE (A) To SuIT CoNTACToR CAT No.

RatedOperationVoltage:690VoltsAC

0.02…0.12 0.1…0.5 CA7-9/12/16/23 CEP 7-EEAB

0.06…0.25 0.2…1.0 CA7-9/12/16/23 CEP 7-EEBB

0.25…2.2 1.0…5.0 CA7-9/12/16/23 CEP 7-EECB

1.5…7.5 3.2…16 CA7-9/12/16/23 CEP 7-EEDB

2.2…15 5.4…27 CA7-9/12/16/23 CEP 7-EEEB

2.2…15 5.4…27 CA 7 - 30/37/43 CEP 7-EEED

4…22 9.0…45 CA 7 - 30/37/43 CEP 7-EEFD

11…45 18…90 CA7-60/72/85/97 CEP 7-EEGE

25…55 60…120 CA7-60/72/85/97 CEP 7-EEVE

RatedOperationVoltage:1000VoltsAC

18.5…90 30…150 CA6-115/140/180 CEP 7-EEHF

22…1102) 40…200 CA6-115/140/180 CEP 7-EEJF

22…110 40…200 CA6-210/250/300/420 CEP 7-EEJG

37…180 60…300 CA6-210/250/300/420 CEP 7-EEKG

55…300 100…500 CA6-210/250/300/420 CEP 7-EELG

75…385 120…600 CA 6 - 630/860 CEP 7-EEMH

100…510 160…800 CA 6 - 630/860 CEP 7-EENH

CEP 7-EEAB

AuTo / MANuAL RESET CLASS 10, 15, 20 oR 30

CEP 7-EEGE

CEP 7-EEJF

CEP 7-EEJG

CEP 7-EEMH

NoTE: 1) EEversionscanbefittedwithsidemountaccessories-referpages9-10 NoTE: 1) With 1000V rated insulated cables.

CEP 7-E_P pass through electronic overload relays TheCEP7-E_Pversionsprovideadditionalapplicationflexibilityandaredesignedtobemounted separately from the contactor. The motor wires are simply passed through the CT openings in the device and straight to the contactor which reduces the number of connectionpoints.ThismakesthemidealinretrofitapplicationsandwhenusedwithcontactorsotherthanCA7orwherespaceisrestricted.ThePversioncanbefitteddirectlyonto DIN rail to speed up assembly. The EE_P version can also accept any of the side mount accessories including the communication modules; DevicenetTM,Profibus® or Ethernet / IP.

CEP 7-EE_P Enhanced model

CAT No.CuRRENT SETTING RANGE (A)

CoNTRoL TERMINAL wIRE VARIABLE

CoNTRoL TERMINAL ToRquE VARIABLE TRIP CLASS

RatedOperationVoltage:1000VoltsAC1)

CEP 7-EECP 1.0…5.0 0.5...4mm2 0.55Nm 10-30

CEP 7-EEDP 3.2…16 0.5...4mm2 0.55Nm 10-30

CEP 7-EEEP 5.4…27 0.5...4mm2 0.55Nm 10-30

The pass through version of the CEP 7 permits separate mount of the overload relay.

Motor load side cables simply pass through a window in the overload relay body. The internal current transformers monitor the current flow.

Page 6: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

9 10

CEP 7 side mount modules 1)

ACCESSoRy DESCRIPTIoN To SuIT CAT No.

CEP7-ERR

Remote reset module• ProvisionforresetaftertripfromremotepilotdeviceorCEP7-ERID

CEP7(S)-EE CEP 7-EE_P

CEP7-ERR

CEP 7-EJM

Jam protection and remote reset module• Dipswitchadjustablejamprotection

-Jamsetpoints-150%,200%,300%,or400%FLA

-Tripdelay-0.5,1,2,or4sec.

• ProvisionforresetaftertripfromremotepilotdeviceorCEP7-ERID

CEP7(S)-EE CEP 7-EE_P

CEP7- EJM

CEP 7-EPT

PTC thermistor relay and remote reset module• PTCprotectionandLEDstatusindication

Typeofcontrolunit MarkA Number of sensors 6 Maximumcoldresistanceofsensorchain 1500Ω Tripresistance 3400Ω±150Ω Resetresistance 1600Ω±50Ω Shortcircuittripresistance 25Ω±10Ω Opencircuittripresistance >20,000Ω Maximumvoltageat1T1/1T2(Rptc=4kΩ) <7.5VDC Maximumvoltageat1T1/1T2(Rptc=open) <30VDC PTCresponsetime 500…800ms

• ProvisionforresetaftertripfromremotepilotdeviceorCEP7-ERID

CEP7(S)-EE CEP 7-EE_P

CEP 7-EPT

CEP7-EGF

Ground fault protection and remote reset module 2) 3)

• Dipswitchadjustablegroundfaultprotection

>GFcurrentrangesetpoints -20…100mA -100…500mA -0.2…1.0A -1.0…5.0A

>GFtriplevel20%-100%

• LEDstatusindication

• ProvisionforresetaftertripfromremotepilotdeviceorCEP7-ERID

• MustusewithCEP7-CBCTcurrentsensor

CEP7(S)-EE_ CEP 7-EE_P

CEP 7-EGF

CEP 7-EGJ

Ground fault/jam protection and remote reset module 2) 3)

• Dipswitchadjustablegroundfaultprotectionsameas CEP7-EGFshownabove

• Jamtripwhenthemotorcurrentexceeds400%FLA setting when enabled

• LEDstatusindication

• ProvisionforresetaftertripfromremotepilotdeviceorCEP7-ERID

• MustusewithCEP7-CBCTcurrentsensor

CEP7(S)-EE CEP 7-EE_P

CEP 7-EGJ

NoTE: 1) Sidemountmodulesmusthave24-240V,47-63HzorDCappliedtoterminalsA1andA2forcontrolpower

2) Attention: The CEP 7 overload relay is not a ground fault circuit interruptor for personnel protection

3) Must be used with core balance transformer - refer page 11

CEP 7-CBCT core balance transformers for CEP 7-EGF / EGJGround fault current is sensed by passing all lines carrying current to and from a motor through the window of a special core balance current transformer often called a toroid / ground fault sensor. If all the current to the motor returns throughthelinesinthetoroid,nosignificantcurrentwillbeinducedinthetoroidsecondary.If,however,groundfaultcurrentreturnsviaapathexternaltothetoroid,suchasviatheconduitwalls,acurrentwillbeinducedinthetoroidsecondary.Thiscurrentwillbesensedandamplifiedbysolidstatecircuits.Ifthegroundfaultcurrentislargerthantheselected ground fault trip level of the overload relay, the overload relay will trip.

SENSoR TyPE APPRox. CuRRENT RATING

INSIDE DIAMETER

MAx REC. CABLE SIzE @ 600 V

TyPICAL uSE wITH CoNTACToR SIzE CAT No.

45A 19 mm 10 mm21) CA 7 - 9... CA 7 - 43 CEP 7-CBCT1

90 A 40 mm 35mm21) CA7-9...CA7-85 CEP 7-CBCT2

180 A 64 mm 120mm21) CA 6 - 180 CEP 7-CBCT3

420A 82mm 185mm21) CA6-420 CEP 7-CBCT4

860 A 160 mm 300 mm21) CA 6 - 860 CEP 7-CBCT5

Communication modulesDESCRIPTIoN To SuIT CAT No.

Ethernet / IP communication module Includeswarningforjamtrip,overloadandunderload Inputs/outputs - 2inputs(24VDCrated) - 1outputrelay(B300rated) - status indication LED Monitoring - %thermalutilised - averagecurrent%FLA - device, trip and warn status

CEP7(S)-EE CEP 7-EE_P

CEP 7-ETN

Profibus® communication module Includeswarningforjamtrip,overloadandunderload Inputs/outputs - 2inputs(24VDCrated) - 1outputrelay(B300rated) - status indication LED Monitoring - %thermalutilised - averagecurrent%FLA - device, trip and warn status

CEP7(S)-EE CEP 7-EE_P

CEP 7-EPRB

DeviceNet communication module CEP7(S)-EE CEP 7-EE_P

CEP 7-EDN

DeviceNet™ Hand Held Programmer HMI 2)

Programming terminal includes 1 m communication cable TobeusedwithCEP7-C1/C2/C3andCEP7-EDNmodule

CEP7(S)-EE CEP 7-EE_P

CEP 7-DNCT

NoTE: 1) With a 3 phase system with one cable per phase

2) Can be used on any DeviceNetTMproductornetwork.CompatiblewithCEP7C

Page 7: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

11 12

Accessories

ACCESSoRy DESCRIPTIoN FoR uSE wITH CAT No.

DIN-rail / panel adaptorForseparatemountingofoverloadrelaytobackpanortophatDIN-rail

CEP 7-ED1_B CEP7(S)-EE_B

CEP 7-EPB

CEP7-EE…D CEP 7-EPD

CEP7-EE…E CEP 7-EPE

Current adjustment shieldPreventsinadvertentadjustmentofthecurrentsetting

All CEP 7 CEP 7-BC8

External reset button adaptorProvides a larger “target area” for resetting the overload relay whenusinganexternalresetbutton

All CEP 7 CEP 7-ERA

External reset buttonManual reset pushbutton used for resetting overloads mountedinenclosures.TobeusedwithCEP7-ERA

All CEP 7 D7P-R611

Reset rodTosuitD7externalresetpushbutton(D7P-R611)and CEP7-ERAadaptor

All CEP 7 D7-ATR08

Adjustment cover for external modules All CEP 7 CEP 7-EMC

Remote reset solenoids 24VAC

110VAC

240VAC

24VDC

48VDC

110VDC

All CEP 7

All CEP 7

All CEP 7

All CEP 7

All CEP 7

All CEP 7

CEP 7-EMRJCEP 7-EMRDCEP 7-EMRACEP 7-EMRz24CEP 7-EMRz48CEP 7-EMRz01

1 metre communications cable with micro-connector CEP 7-DNCT CEP 7-CM1

1 metre communications cable with bare leads (includedwiththeCEP7-DNCT)

CEP 7-DNCT CEP 7-BC1

Door / panel mount bezel kit CEP 7-DNCT CEP 7-DNCT - Bz1

ACCESSoRy DESCRIPTIoN FoR uSE wITH CAT No.

Remote indication and reset module 1)

PanelmountedIP66uses22.5mmfixinghole.Itmustbeusedinconjunctionwithasidemountmoduleandconnectsvia twowirestotheremoteresetterminalsR1andR2.

Indication LEDS Power

Overload

• Trip(solid)

• Warning(flash)

Phase loss

ModulespecificLED-groundfault,PTC,jam

CEP7-ERR

CEP 7-EJM

CEP 7-EPT

CEP7-EGF

CEP 7-EGJ

CEP 7-ERID

NoTE: 1) Must be used with side mount modules. Not compatible with communication modules

works with CEP7-EE overloads from 0.1 to 800 Amps

overload Conditions LED • Trip(RED,solid) • Warning(YELLOW,flash)

Display Status • Modulepower(GREEN,flash) • Modulepower&motorcurrent (GREEN, solid) • Hardwarefault(RED,solid)

Module Fault LED • Groundfaulttrip(RED,oneflash) • Jamtrip(RED,twoflashes) • PTCtrip(RED,threeflashes) • Faultdetected(RED,rapidflash)

Phase Loss LED • Trip(RED,solid)

Remote Reset

IP 66 rated

Installation Dimensions (mm)

Page 8: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

355

300

420

250

210

180

140115

16

23

912

16

23630

860

43

30

37

8597

7260

9

12

500kW

Amps

455540

32

22

18.5

15

250

185

150

132

110

9075

4 5.57.5

11

4

5.5

7.5

11

CuRRENT SETTING RANGE (A)

CEP7-EEJG40...200CEP7-EEKG60...300CEP7-EELG100...500

CuRRENT SETTING RANGE (A)

CEP7-EEHF30...150CEP7-EEJF40...200

CuRRENT SETTING RANGE (A)

CEP7-EEMH120...600

CEP7-EENH160...800

CuRRENT SETTING RANGE (A)

CEP7-EEGE18...90 CEP7-EEVE30...150

CEP 7 quICK REFERENCE GuIDE

Motor protection CEP 7 overload relaysNHP have introduced the new sprecher + schuh CEP 7, second generation electronic overload protection relays. The new CEP 7 overloads incorporate a greater use of sophisticated electronic control and monitoring. The CEP 7 second generation overload now incorporates greater accuracy and versatility whilst providing increased overall protection.

CEP 7-EE

CEP 7-EE CEP 7-EE

CEP 7-EE CEP 7-EE

CEP 7-EDCEP 7-EE

CEP 7

quick Reference GuideCEP 7 sIDE MOUNT MODULEs

• RemoteresetmoduleCEP7-ERR

• Jamprotectionandremoteresetmodule CEP 7-EJM

• PTCthermistorrelayandremotereset module CEP 7-EPT

• GroundfaultprotectionandremoteresetmoduleCEP7-EGF

• Groundfault/jamprotectionandremote reset module CEP 7-EGJ

• Profibus® communication moduleCEP7-EPRB

• DeviceNetTM communication module CEP 7-EDN

• Ethernet/IPcommunicationmodule CEP 7-ETN

• Electronicoverloadsalsoavailablefor single phase applications to IEC 60947. Current settings from 1...90 amps. See page 6.

• ElectronicoverloadsCEP7-E_Ppass through version also available. See page 9.

• ElectronicoverloadsCEP7-C1andCEP7-C2completewithcommunication(DeviceNetTM). Current settings from 0.4...860 amps. See NHP Part-A Catalogue for more details.

Enhanced electronic overload relays for 3 phase motors

standard electronic overload relays for 3 phase motors

CuRRENT SETTING RANGE (A)

CEP7-EEAB0.1...0.5

CEP7-EEBB0.2...1.0

CEP7-EECB1.0...5.0

CEP7-EEDB3.2...16

CEP7-EEEB5.4...27

CEP7-ED1AB0.1...0.5

CEP7-ED1BB0.2...1.0

CEP7-ED1CB1.0...5.0

CEP7-ED1DB3.2...16

CEP7-ED1EB5.4...27

CuRRENT SETTING RANGE (A)

FEATuRES:• Manual reset• Tripclass10• 5:1currentadjustmentrange• self powered• Lowpowerconsumption(150mW)• Direct mounting to CA 7

contactors• 1 N/C trip contact and 1 N/O

alarm contact• visible trip indicator

FEATuRES:• Auto/manualreset• Adjustabletripclass10,15,20and30• 5:1currentadjustmentrange• Selfpowered• Lowpowerconsumption(150mW)• DirectmountingtoCA7contactors• 1N/Ctripcontactand1N/Oalarmcontact• Visibletripindicator• Optionalsidemountmodules

kW

CuRRENT SETTING RANGE (A)

CEP7-EEED5.4...27CEP7-EEFD9.0...45

Amps

CA 6

(10

00 V

AC) CA

7 (690 VAC)

Page 9: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

Dimensions (mm)

CEP 7 MouNTED To CA 7 CoNTACToR (wITH SIDE MouNTED MoDuLE)

A

F

G

B

D

E

K

L

H

C

J

Wire size and torque specifications

1X

2X

0.2...3.3 mm2

0.2...1.3 mm2

0.55 Nm

1X

2X

0.2...2.5 mm2

0.25...1 mm2

0.55 Nm

1X

2X

0.2...2.5 mm2

0.2...1 mm2

0.55 Nm

oVERLoAD Cat. No.

CoNTACToR Cat. No.

mm

A B C D E F G H J K L

CEP 7*-EE_B CA7-9/12/16/23 63 148 85.2 24.5 13.9 35 60 86.5 2 4.5 18

CEP 7*-EE_DCA 7 - 30/37 63 148 101.2 24.5 13.9 35 60 104 2 4.5 18

CA 7 - 43 67.5 148 101.2 24.5 18.4 45 60 107 2 4.5 18

CEP 7*-EE_E CA7-60/72/85/97 90 191.6 120.4 29 23.8 55 100 126 2 5.4 18

CEP7 module technical information

A

F

G

B

D

E

K

L

H

C

J

Wire size and torque specifications

1X

2X

0.2...3.3 mm2

0.2...1.3 mm2

0.55 Nm

1X

2X

0.2...2.5 mm2

0.25...1 mm2

0.55 Nm

1X

2X

0.2...2.5 mm2

0.2...1 mm2

0.55 Nm

• ConnectremoteresetpilotdevicetoterminalsR1andR2.

• DonotapplyexternalvoltagetoR1andR2.Equipmentdamagewilloccur.

• Recommenduseoftwistedpairforremotereset,0.2mm2 minimum.

• Apply24-240V,47-63HzorDCtoterminalsA1andA2forcontrolpower.

• Ratedinsulationvoltage(Ui) 300V

• Ratedoperatingvoltage(Ue) 24-240VAC,50/60Hz 24-240VDC

• Poweratratedoperatingvoltage 24VAC 0.3W (Typical) 120VAC 0.3W 240VAC 0.5W

• Ratedimpulsewithstandvoltage(Uimp) 2.5kV

• Dynamicinhibitonstart.AuniquecircuitwithintheCEP7protectionmodulesmonitors for motor starting inrush current. The circuit inhibits the protection feature during the motor start period and arms the protection function after the inrush current falls to motor rated current. This allows the motor to start and run, avoiding nuisance tripping during the inrush period.

Dimensions (mm)

NoTE: * No letter indicates 3 phase; ‘S’ indicates single phase

oVERLoAD Cat. No.

CoNTACToR Cat. No.

Awidth

BHeight B1 C

Depth D E1 E2 F G H J K M

Without terminal covers

With terminal covers

Reset

CEP 7-EE_F

CA6-115(EI) 120 336.3 418 311.8 152.7 156 36 226.3 12.5 100 145 135 22.3 8-5.6

CA6-140(EI)120 339.8 418 317.8 152.7 156 36 226.3 16 100 145 135 22.3 8-5.6

CA6-180(EI)

CEP 7-EE_GCA6-210EI

155 385.8 487.4 360.8 176.5 180 36 265.5 21 130 180 140 23.5 8-6.5CA6-420EI

CEP 7-EE_HCA 6 - 630 EI

255 552 915 508 269.3 270.7 36 384.1 52.5 226 230 108 109 8 - 13CA 6 - 860 EI

CEP 7 PASS THRouGH oVERLoAD

CEP 7-EEVF MouNTED To CA 6 CoNTACToR

261

Ø 5.6

145

46.4

100

120

12.5

CA6-110]

153.7

151.2

196.2

158.3 RESET BUTTONTRAVEL: 2.5

CEP 7-EE_F...EE_H MouNTED To CA 6 CoNTACToR

15 16

Page 10: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

wiring diagrams

CEP 7-ERR AND CEP 7-EJM wIRING DIAGRAMS

CEP 7-ERR / EJM oPERATIoNAL LED

CEP 7-EJM DIP SwITCH

2R

1R

2A

1A A1

A2

R1

R2Adjustment Settings

Remote Reset

Enable: ISW1 Disable: 0

Jam Protection

Jam Trip Level

Enable: 0

SW 3 SW 4

150% 0 0

200% 0 I

300% I 0

400% I I

SW2 Disable: I

Jam Trip Delay

SW 5 SW 6

0.5 sec I I

1 sec I 0

2 sec 0 I

4 sec 0 0

CEP7-EPT Wiring Diagrams

2R

1R

2TI

1TI

2A

1A A1

A2

R1

R2

IT2IT1 Adjustment Settings 1)

SW1 Manual: I

SW2 Enable: I

Overload Relay and PTC Reset Mode

PTC ProtectionDisable: 0

Automatic: 0

SW3 3 Phase: IOverload Relay Type

1 Phase: 0

• Apply24-240V,47-63HzorDCtoterminals A1andA2forcontrolpower.

• ConnectremoteresetpilotdeviceorCEP7-ERIDto terminals R1andR2.

STATuS LED

steady green - Module is powered up.

2R

1R

2A

1A A1

A2

R1

R2Adjustment Settings

Remote Reset

Enable: ISW1 Disable: 0

Jam Protection

Jam Trip Level

Enable: 0

SW 3 SW 4

150% 0 0

200% 0 I

300% I 0

400% I I

SW2 Disable: I

Jam Trip Delay

SW 5 SW 6

0.5 sec I I

1 sec I 0

2 sec 0 I

4 sec 0 0

CEP7-EPT Wiring Diagrams

2R

1R

2TI

1TI

2A

1A A1

A2

R1

R2

IT2IT1 Adjustment Settings 1)

SW1 Manual: I

SW2 Enable: I

Overload Relay and PTC Reset Mode

PTC ProtectionDisable: 0

Automatic: 0

SW3 3 Phase: IOverload Relay Type

1 Phase: 0

CEP 7-EPT wIRING DIAGRAM

CEP 7-EPT oPERATIoNAL LED

CEP 7-EPT DIP SwITCH

2R

1R

2A

1A A1

A2

R1

R2Adjustment Settings

Remote Reset

Enable: ISW1 Disable: 0

Jam Protection

Jam Trip Level

Enable: 0

SW 3 SW 4

150% 0 0

200% 0 I

300% I 0

400% I I

SW2 Disable: I

Jam Trip Delay

SW 5 SW 6

0.5 sec I I

1 sec I 0

2 sec 0 I

4 sec 0 0

CEP7-EPT Wiring Diagrams

2R

1R

2TI

1TI

2A

1A A1

A2

R1

R2

IT2IT1 Adjustment Settings 1)

SW1 Manual: I

SW2 Enable: I

Overload Relay and PTC Reset Mode

PTC ProtectionDisable: 0

Automatic: 0

SW3 3 Phase: IOverload Relay Type

1 Phase: 0

• Apply24-240V,47-63HzorDCtoterminalsA1andA2forcontrolpower.

• Connectremoteresetpilotdeviceor CEP7-ERIDtoterminalsR1andR2.

• ConnectterminalIT1andIT2to PTC chain.

STATuS LED

steady green - Module is powered up.

Flashing LED - The number of flashes followed by a pause identifiesthespecifictripcodeasfollows:

(1) Flash - overload trip

(2) Flash - phase loss trip

(3) Flash - PTC trip

(4)Flash- PTC open circuit

(5)Flash- PTC short circuit

Fastflash- Impending trip. PTC thermistor fault detected and CEP 7 not yet capable of tripping.

steady red - Hardware fault. Internal hardware fault detected and CEP 7 trip attempted.

2R

1R

2A

1A A1

A2

R1

R2Adjustment Settings

Remote Reset

Enable: ISW1 Disable: 0

Jam Protection

Jam Trip Level

Enable: 0

SW 3 SW 4

150% 0 0

200% 0 I

300% I 0

400% I I

SW2 Disable: I

Jam Trip Delay

SW 5 SW 6

0.5 sec I I

1 sec I 0

2 sec 0 I

4 sec 0 0

CEP7-EPT Wiring Diagrams

2R

1R

2TI

1TI

2A

1A A1

A2

R1

R2

IT2IT1 Adjustment Settings 1)

SW1 Manual: I

SW2 Enable: I

Overload Relay and PTC Reset Mode

PTC ProtectionDisable: 0

Automatic: 0

SW3 3 Phase: IOverload Relay Type

1 Phase: 0

wiring diagrams

CEP 7-EGF AND CEP 7-EGJ wIRING DIAGRAMS

CEP 7-EGF oPERATIoNAL LED

CEP 7-EGF DIP SwITCH

2A

1A A1

A2

R1R2

S1

S2

2R

1R

2S

1S

Adjustment Settings

SW1 Manual: I

SW 2 SW30 00 II 0I I

SW 4 SW 6SW 50 0

00

0 I00IIII

0

0

II I

I

III00

0

20...100 m A100...500 mA0.2...1.0 A1.0...5.0 A

Overload Relay Reset Mode

Ground Fault Current Range

Ground Fault Trip Level

Automatic: 0

SW7 3 Phase: I Overload Relay Type

1Phase: 0

SW8 Not Used

Disable/Off20 % Max GF Current35 % Max GF Current50 % Max GF Current65 % Max GF Current80 % Max GF Current90 % Max GF Current100 % Max GF Current

Ground Fault Sensor (CEP 7-CBCT) Control Wiring

Motor

L2 L3L1

GroundFault

Sensor

CEP 7Overload Relay

with Side Mount Module

S1 S2

SW8 Enable: I Jam Protection

Disable: 0

Adjustment Settings

SW1 Manual: I

SW 2 SW30 00 II 0I I

SW 4 SW 6SW 50 0

00

0 I00IIII

0

0

II I

I

III00

0

20...100 mA100...500 mA0.2...1.0 A1.0...5.0 A

Overload Relay Reset Mode

Ground Fault Current Range

Ground Fault Trip Level

Automatic: 0

SW7 3 Phase: I Overload Relay Type

1Phase: 0

Disable/Off20 % Max GF Curren t35 % Max GF Curren t50 % Max GF Curren t65 % Max GF Curren t80 % Max GF Curren t90 % Max GF Current100 % Max GF Current

• Apply24-240V,47-63HzorDCtoterminalsA1andA2forcontrolpower.

• ConnectremoteresetpilotdeviceorCEP7-ERIDtoterminalsR1andR2.

• Connectcurrentsensortoterminal S1andS2.

STATuS LED:

steady green - Module is powered up.

Flashing LED - The number of flashes followed by a pauseidentifiesthespecifictripcodeasfollows:

(1) Flash - overload trip

(2) Flash - phase loss trip

(3) Flash - ground fault trip

Fastflash- Impending trip ground fault detected and CEP 7 not yet capable of tripping.

steady red - Hardware fault. Internal hardware fault detected and CEP 7 trip attempted.

2A

1A A1

A2

R1R2

S1

S2

2R

1R

2S

1S

Adjustment Settings

SW1 Manual: I

SW 2 SW30 00 II 0I I

SW 4 SW 6SW 50 0

00

0 I00IIII

0

0

II I

I

III00

0

20...100 m A100...500 mA0.2...1.0 A1.0...5.0 A

Overload Relay Reset Mode

Ground Fault Current Range

Ground Fault Trip Level

Automatic: 0

SW7 3 Phase: I Overload Relay Type

1Phase: 0

SW8 Not Used

Disable/Off20 % Max GF Current35 % Max GF Current50 % Max GF Current65 % Max GF Current80 % Max GF Current90 % Max GF Current100 % Max GF Current

Ground Fault Sensor (CEP 7-CBCT) Control Wiring

Motor

L2 L3L1

GroundFault

Sensor

CEP 7Overload Relay

with Side Mount Module

S1 S2

SW8 Enable: I Jam Protection

Disable: 0

Adjustment Settings

SW1 Manual: I

SW 2 SW30 00 II 0I I

SW 4 SW 6SW 50 0

00

0 I00IIII

0

0

II I

I

III00

0

20...100 mA100...500 mA0.2...1.0 A1.0...5.0 A

Overload Relay Reset Mode

Ground Fault Current Range

Ground Fault Trip Level

Automatic: 0

SW7 3 Phase: I Overload Relay Type

1Phase: 0

Disable/Off20 % Max GF Curren t35 % Max GF Curren t50 % Max GF Curren t65 % Max GF Curren t80 % Max GF Curren t90 % Max GF Current100 % Max GF Current

CEP 7-EGF AND CEP 7-EGJ INSTALLATIoN

CEP 7-EGJ oPERATIoNAL LED

CEP 7-EGJ DIP SwITCH

2A

1A A1

A2

R1R2

S1

S2

2R

1R

2S

1S

Adjustment Settings

SW1 Manual: I

SW 2 SW30 00 II 0I I

SW 4 SW 6SW 50 0

00

0 I00IIII

0

0

II I

I

III00

0

20...100 m A100...500 mA0.2...1.0 A1.0...5.0 A

Overload Relay Reset Mode

Ground Fault Current Range

Ground Fault Trip Level

Automatic: 0

SW7 3 Phase: I Overload Relay Type

1Phase: 0

SW8 Not Used

Disable/Off20 % Max GF Current35 % Max GF Current50 % Max GF Current65 % Max GF Current80 % Max GF Current90 % Max GF Current100 % Max GF Current

Ground Fault Sensor (CEP 7-CBCT) Control Wiring

Motor

L2 L3L1

GroundFault

Sensor

CEP 7Overload Relay

with Side Mount Module

S1 S2

SW8 Enable: I Jam Protection

Disable: 0

Adjustment Settings

SW1 Manual: I

SW 2 SW30 00 II 0I I

SW 4 SW 6SW 50 0

00

0 I00IIII

0

0

II I

I

III00

0

20...100 mA100...500 mA0.2...1.0 A1.0...5.0 A

Overload Relay Reset Mode

Ground Fault Current Range

Ground Fault Trip Level

Automatic: 0

SW7 3 Phase: I Overload Relay Type

1Phase: 0

Disable/Off20 % Max GF Curren t35 % Max GF Curren t50 % Max GF Curren t65 % Max GF Curren t80 % Max GF Curren t90 % Max GF Current100 % Max GF Current

STATuS LED:

steady green - Module is powered up.

Flashing LED - The number of flashes followed by a pauseidentifiesthespecifictripcodeasfollows:

(1) Flash - overload trip

(2) Flash - phase loss trip

(3) Flash - ground fault trip

(4)Flash-jamtrip

Fastflash- Impending trip ground fault detected and CEP 7 not yet capable of tripping.

steady red - Hardware fault. Internal hardware fault detected and CEP 7 trip attempted.

2A

1A A1

A2

R1R2

S1

S2

2R

1R

2S

1S

Adjustment Settings

SW1 Manual: I

SW 2 SW30 00 II 0I I

SW 4 SW 6SW 50 0

00

0 I00IIII

0

0

II I

I

III00

0

20...100 m A100...500 mA0.2...1.0 A1.0...5.0 A

Overload Relay Reset Mode

Ground Fault Current Range

Ground Fault Trip Level

Automatic: 0

SW7 3 Phase: I Overload Relay Type

1Phase: 0

SW8 Not Used

Disable/Off20 % Max GF Current35 % Max GF Current50 % Max GF Current65 % Max GF Current80 % Max GF Current90 % Max GF Current100 % Max GF Current

Ground Fault Sensor (CEP 7-CBCT) Control Wiring

Motor

L2 L3L1

GroundFault

Sensor

CEP 7Overload Relay

with Side Mount Module

S1 S2

SW8 Enable: I Jam Protection

Disable: 0

Adjustment Settings

SW1 Manual: I

SW 2 SW30 00 II 0I I

SW 4 SW 6SW 50 0

00

0 I00IIII

0

0

II I

I

III00

0

20...100 mA100...500 mA0.2...1.0 A1.0...5.0 A

Overload Relay Reset Mode

Ground Fault Current Range

Ground Fault Trip Level

Automatic: 0

SW7 3 Phase: I Overload Relay Type

1Phase: 0

Disable/Off20 % Max GF Curren t35 % Max GF Curren t50 % Max GF Curren t65 % Max GF Curren t80 % Max GF Curren t90 % Max GF Current100 % Max GF Current

NoTE: 1) The delay between the occurrence of a PTC out-of-range fault and a trip of the CEP 7 varies, but is generally described byoneofthefollowing:

• 500ms±250ms,typical; - <6seconds,foraPTCout-of-rangefaultpresentatpower-upofthesidemountmodule. - UndernoconditionsshouldaPTCtriptakelongerthan6seconds.17 18

Page 11: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

wiring diagrams

CEP 7-EDN DEVICENETTM MoDuLE CEP 7-EPRB PRoFIBuS® MoDuLE

CEP 7-ETN ETHERNET / IP MoDuLE

CEP7-ETN Ethernet Network Communication Module ConnectstothenetworkviaRJ45(Cat5)connector.

SupportsI/Oandexplicitmessagingfordataaccessbyprogrammableautomatic controller.

ContainspredefinedControlLogixstyletagsfordirectsoftwareaccess.

Includes an integrated web server to allow users to read information and configureparametersviaacomputerwebbrowserfromremotelocations.

UsesaSimpleMailTransferProtocol(SMTP)servertosende-mailortextmessages in the event of a warning or trip condition.

EtherNet /IP Communications

TCP Connection 150

CIP Connection 48

CIP Unconnected Messages 128

I/OPacketRates 500/s

ExplicitPacketRates 500/s

SpeedDuplex(Half/Full) 10/100

Duplicate IP Detection Yes

ElectricalPowER SuPPLy RATINGS

RatedSupplyVoltage 24VDC

RatedOperationRange 20.4...26.4VDC

RatedSupplyCurrent 0.1A

MaximumSurgeCurrentatPower-up 2.5A

MaximumPowerConsumption 2.5...2.7WouTPuT RELAy RATINGS

Terminal OUT A 13/14

Type of Contacts FormASPST-NO

RatedThermalCurrent 5A

RatedInsulationVoltage 300V AC

RatedOperatingVoltage 240VAC

RatedOperatingCurrent

3A(@120VAC)

1.5A(@240VAC)

0.25A(@110VDC)

0.1A(@220VDC)

Minimum Operating Current 10mA(@5VDC)

RatingDesignation B300

UtilizationCategoryAC -15

ResistiveLoadRating(p.f.1.0)5A,250VDC

5A,30VDC

InductiveLoadRating

(p.f.=0.4),(L/R=7ms)

2A,250VAC

2A,30VDC

ShortCircuitCurrentRating 1000 A

RecommendedControlCircuitFuse KTK-R-6(6A,600V)

offers Integrated web and E-mail ServerView the status and events of your overload relay on the web at

anytime, anywhere!

The CEP7-ETN contains a web server to allow users to read informationandconfigureparametersviatheweb.

Usesasimplemailtransferprotocol(SMTP)servertosendemailortextmessagesintheeventofawarningortripcondition.

19 20

Page 12: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

CEP 7-CBCT Core balance transformers

Control wiring installation

CEP 7-CBCT GRouND FAuLT TRIP DATA

• The control wiring must be a twisted pair

• Linesinexcessofonemetrelongmustbeashieldedpairwiththeshieldconnectedtogroundatonlyonepoint

Important: the shield, if present, of the twisted pair must be connected to earth ground at the sensor, with no connection made at the overload relay

• Maximumlengthis30metresfortheshieldedcable

• Sensorfastenertorque2.94-3.39Nm

• CEP7-CBCT lead wires should be twisted before termination by applying one twist per inch

CEP 7 oVERLoAD RELAy wITH CEP 7-EGF oR CEP 7-EGJ (CEP 7-EE)

Motor

L2 L3L1

S1 S2

Attention:thegroundfaultprotectionsystemisintendedforequipmentuseonly.Thissystemisnotagroundfaultcircuit interrupter for personnel protection.

Ground fault trip delayThe delay between the occurrence of a ground fault and a trip of the CEP 7 varies, but is generally described by one of thefollowing:

<6seconds,foragroundfaultpresentatpowerupofthesidemountmodule

<30seconds,iftheprotectioninhibithasnotbeencleared.Undernoconditionsshouldagroundfaulttriptakelongerthan 31 seconds

Power cable installation

1 Allpowercables,includingtheneutralwhenused,mustpassthroughthesensorwindow.Theequipmentgroundconductor(theconductorusedtocarrythenon-currentcarryingmetalpartsofequipment)mustnotpassthroughthe sensor window.

2 The power cables, going through the sensor window, must be straight, tightly bundled, centred in the window, and perpendiculartothesensorforalengthequaltoorgreaterthansixtimesthecablebundlediameter(includinginsulation)fromthesensor(seeFigure1).

3 Allotherconductorswithavailablefaultcurrentsinexcessof1,000Ashouldbeplacedadistanceequaltoorgreaterthansixtimesthecablebundlediameter(includinginsulation)fromthesensor(seeFigure2).

4 The power cables of the branch circuit, to be protected by the overload relay, must not be grounded on the load side of the ground fault sensor.

5 Ifthepowercablesareenclosedinaconductingjacket,thejacketmustbegroundedonthelinesideofthesensor.Thejacketmustnotpassthroughthesensorwindow,butmustbecutatthewindowandjoinedwithaconductorthat passes outside the sensor window.

6 The power system must be solidly grounded or grounded through an impedance at the source, as long as the impedance allows for a magnitude of current to flow that is within the operational range of the overload relay.

CEP 7 oVERLoAD RELAy wITH CEP 7-EGF oR CEP 7-EGJ (CEP 7-EE)

Attention:Topreventelectricalshock,disconnectfrompowersourcebeforeinstallingorservicing.Installinasuitableenclosure,keepfreefromcontaminants.

Do not apply power to a system with power cables going through the sensor unless the sensor is connected to the overload relay. Operation without a low impedence connection to the secondary windings may result in damage to the sensor.

Figure 1 Figure 2

21 22

Page 13: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

Locating phase conductors in the sensor window

• Firmlysecuretheconductorsinthecentreofthesensorwindowsothattheycannotbemovedaccidentallyorunder fault conditions

• Maintain as large a distance as possible between the bundled conductors and the wall of the sensor window

• Forapplicationshavingonecableperphase,arrangetheconductorsperFigureA

• Forapplicationshavingtwocablesperphase,arrangetheconductorsperFigureB.Aspacer,havingthesamediameter as the conductors being used, should be used to separate the phase conductors

Single cable per phase Two cables per phase

B erugiFA erugiF

spacerA

B C

C

B B

A

A

C

Attention:Thegroundfaultprotectionsystemisintendedforequipmentuseonly.Thissystemisnotagroundfaultcircuit interrupter for personnel protection.

An ideal core-balanced ground fault toroid responds only to the sum of the currents flowing through the sensor window, however, an actual core balanced transformer may saturate if the phase currents are too large. This results ingroundfaultsensoroutputevenifthesumofthephasecurrentsiszero.Saturationcanbeminimisedbychoosingagroundfaultsensorwithadequatecoresizeandsymmetricallylocatingthephaseconductorsinthecentreofthesensor window as shown above.

Dimensions (mm)

CEP 7-CBCT 1

45.3

23.1

Ø 19.1

Ø 44.5

63.550.8

3.2 4

12.7

CEP 7-CBCT 2 AND 3

11.8

3.2

Ø D

5.3

E

F B

A

C44.5

CAT No.mm

A B C Ø D E F

CEP 7-CBCT 2 96 89 48.3 39.6 54.6 69.9

CEP 7-CBCT 3 122.4 115.9 59.7 63.5 54.1 96

CEP 7-CBCT 4

56.2

74.4

123.2 96.7

11.8 146.8

143.5

5.5

74.93.2

82.6

23 24

Page 14: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

NoTE: 1)Performancecriteria1requirestheDUTtoexperiencenodegradationorlossofperformance

2)Environment2

NoTE: 1) Typical reset time for CEP 7 Second Generation devices set to “automatic reset” mode is 120seconds

Technical information

CoNTRoL CIRCuIT

Rated insulation voltage - uI [V] 690 AC

Rated insulation strength - uimp [kV] 6 AC

Rated operation voltage - ue [V] 690AC(IEC)/690AC(UL/CSA)

Rated operation current - ue

12...120V [A] 220...240V [A] AC-15 380...480V [A] 500...600V [A]

3/21)1.5/1.50.75/0.75

0.6 / 0.6 24V [A] DC-13 110 V [A] atL/R15ms 220V [A] 440 V [A]

1.1 / 1.10.4 / 0.40.2/0.2

0.08 / 0.08

Thermal current - Ithe [A]Contact reliability [kV]Screw terminal cross sectionTerminal screw One conductor [mm2] Flexiblewithwire Torque [Nm] end ferrule Two conductors [mm2] Torque [Nm]

517V,5mA

M31x(0.5...2.5)

0.552x(0.25...1.5)

0.55

One conductor [mm2] Coursestranded Torque [Nm] / solid Two conductors [mm2] Torque [Nm]

1x(0.5...4)0.55

2x(0.22...2.5)0.55

One conductor [mm2] Stranded Torque [Nm] / solid Two conductors [mm2] Torque [Nm]

1x(0.2...5.3)0.55

2x(0.2...3.3)0.55

Pozidrivescrewdriversize 1

Slottedscrewdriversize [mm] 0.6x3.5

ENVIRoNMENTAL RATINGS

Ambient temperature Storage [°C] Operating [°C]

-40...+85-20...+60

Humidity Operating [%] Damp Heat

5...95,non-condensingperIEC68-2-3andIEC68-2-30

Vibration(perIEC68-2-6) [G] 3

Shock (perIEC68-2-27) [G] 30

Maximum altitude [m] 2000

Pollution environment Pollution degree 3

Degree of protection IP20

Type of relay Ambient compensated, time delay, phase loss standard

Nature of relay Solid stateTrip ratingTrip class Type ED Type EE

120%FLA10

10,15,20,30Reset mode Type ED Type EE

ManualManual or automatic

Trip curves 1)

1000

1000

100

100

10

10

Tim

e (s

econ

ds)

Tim

e (s

econ

ds)

FLA multiple

FLA multiple

TRIP ClASS 15

TRIP ClASS 30

1

1

0.1

0.1

1

1

10

10

1000

1000

100

100

10

10

Tim

e (s

econ

ds)

Tim

e (s

econ

ds)

FLA multiple

FLA multiple

TRIP ClASS 10

TRIP ClASS 20

1

1

0.1

0.1

1

1

10

10

TRIP CuRVE LEGEND

Cold tripHot trip

Technical information

ELECTRoMAGNETIC CoMPATIBILITy

Electrostatic discharge immunity Testlevel [kV]

Performance level

8kVairdischarge6kVcontactdischarge

1 1)2)RF immunity Test level [V/m] Performance level

10 V/m1 1)2)

Electrical fast transient burst immunity Test level [V/m] Performance level

4kV1 1)2)

Surge immunity Test level [V/m]

Performance level

2kV(L-E)1kV(L-L)

1 1)2)

GENERAL

Standards UL,508,CSAC22.2No.14,NEMA(CD2-1993

Part4,EN60947-4-1,EN60947-5-1)Approvals CE,C-Tick,CSA,UL,Atex(pending)

25 26

Page 15: CEP7-E ELECTRONIC MOTOR PROTECTION RELAYS · The motor wires pass through CT openings. Superior phase failure protection Onboard electronics constantly monitors all motor phases.

NHP Electrical Engineering Products Pty LtdA.B.N.84004304812

NSPRECHEP7C©CopyrightNHP2011

AUSTRAlIAnhp.com.au

SALES 1300 NHP NHP

VICToRIAMelbourne 43-67RiverStreet Richmond VIC3121 Tel+61394292999

laverton 104-106 William Angliss Drive Laverton North VIC3026 Tel+61393682901

Albury / Wodonga 847RamsdenDrive Albury NSW2640 Tel+61260490600

Dandenong 40-42CyberLoop Dandenong South VIC3175 Tel +61 3 8773 6400

TASMANIAHobart 2/65AlbertStreet Moonah TAS 7009 Tel+61362289575

launceston 3/13-17 Merino Street Kings Meadows TAS7249 Tel+61363452600

NEW SoUTH WAlESSydney 30-34 Day Street North Silverwater NSW2128 Tel+61297483444

Newcastle 575MaitlandRoad MayfieldWest NSW2304 Tel+61249602220

Wollongong 34IndustrialRoad Unanderra NSW2526 Tel+61242725763

ACTCanberra 1/187 Gladstone Street Fyshwick ACT2609 Tel+61262809888

WESTERN AUSTRAlIAPerth 38 Belmont Ave Rivervale WA 6103 Tel+61892771777

NoRTHERN TERRIToRyDarwin 3 Steele Street Winnellie NT0820 Tel+61889472666

QUEENSlANDBrisbane 16RiverviewPlace Murarrie QLD4172 Tel +61 7 3909 4999

Townsville 5LeylandStreet Garbutt QLD 4814 Tel +61 7 4779 0700

Rockhampton 14RobisonStreet QLD 4701 Tel+61749272277

Toowoomba Cnr Carroll Street and Struan Court QLD4350 Tel +61 7 4634 4799

Cairns 2/1BrampClose Portsmith QLD 4870 Tel+61740356888

SoUTH AUSTRAlIAAdelaide 36-38CroydonRoad Keswick SA5035 Tel+61882979055

NEW ZEAlANDnhp-nz.com

SALES 0800 NHP NHP

POBox62-009 Mount Wellington Auckland1641 New Zealand

Auckland 118aCarbineRoad Mt Wellington 1060 Tel+6492761967

Hamilton 78RostrevorStreet Hamilton3204 Tel+6478490257

Napier 126TaradaleRd Onekawa4110 Tel+6468436928

New Plymouth 2DeanPlace Waiwhakaiho4312 Tel 0800 NHP NHP

Wellington 52VictoriaStreet LowerHutt5010 Tel+6445700634

Christchurch 85GassonStreet Sydenham8023 Tel +64 3 377 4407