CDT3000 SeriesMulti-Digital Calorie Monitor
OUTLINEThe CDT3000 calorie monitor consists of a pitot tube type flowelement with a built-in temperature sensor and a differential pres-sure instrument equipped with root extraction and calorie calculationfunctions. By inputting an external temperature signal and calculat-ing temperature difference, it indicates and outputs thermal flow andtotalized calorie in addition to flow rate. Applicable pipe size rangesfrom 20 mm to 450 mm.
FEATURES Easy installation by welding a 20 mm, 3/4 inch socket on exist
ing piping for insertion of CDT3000 Simultaneous measurement of both flow and temperature saves
your installation cost Negligible small pressure loss Selectable from wide variety of flow meter ranges suitable for
your applications Applicable for both horizontal and vertical pipes By inputting temperature signal on the fluid feed line it allows
thermal flow measurement and totalized calorie calculation toserve as a calorie monitor for your energy conservation
Easy to read with a large LCD display
STANDARD SPECIFICATIONS Measuring fluid : Water, cold water, hot water Max. pressure : 2 MPa Max. allowable differential pressure
: 700 kPa (bias pressure)Not applicable for vacuum service
Temperature and relative humidityFluid temperature : -10 to 80°C *1
(Use the lining or plastics pipe within itsallowable temperature)
Ambient : -10 to 50°C < 85% RH Storage : -20 to 60°C < 85% RH
Without freezing and condensation *1 When the instrument is used for the services exceeding 70°C,
do not insulate nozzle and differential pressure instrument asthe maximum allowable temperature of sensor is -10 to 70°C.
Pipe size : 20 mm to 450 mm, 3/4" to 18" Applicable pipe : Carbon steel pipe for ordinary piping (JIS
G 3452) for 1 MPa classCarbon steel pipe for pressure service(JIS G 3454 Sch 40) for 2 MPa class
Note : If other pipes than above are used, the calibration is re-quired. Contact us for details.
Accuracy of flow measurement : ±5% F.S. as standard (±10%F.S. for a flow rate of less than30%)
Pressure influence : ±0.5% F.S./MPa Flow measuring range : 10 to 100% F.S. Low cutoff : Less than 7% Built-in temperature sensor : RTD (Resistance Temperature
Detector) Pt 100Ω, 3 wire, JISgrade A
Temperature measuringAccuracy : ±5% F.S.(F.S. =130°C)Range : -10 to 120°CIndication resolution : 0.1°CMeasuring period : 1 s
Materials of wet parts : See "MATERIAL AND OUTLINE DIMEN-SION"
Painting : Melamine resin painting only for indicatorhousing
Painting color for front : Wine red (Munsell 10RP3/8)for rear : Light gray (Munsell N7.5)
Housing enclosure : IP65, equivalent to JIS C0920 Protectedagainst powerful jets except for an airintroduction port at the bottom of housing.
Process connection : R3/4 Male
Installation posture : Perpendicular to front face Power supply : 24 V DC±10% Power consumption : 2 VA or less Specifications of indication parts
Measuring value indication part• 3-1/2 digit LCD : Letter height 18 mm, indication range 0 to
1999Note : Data outside indication range are expressed as FFF
• Bar graph indication with 11 segments• Filter : Selectable from 0, 2, 4, 8, 16 ,32s Moving
average• Flow rate indication interval : 0.5s with sampling period 0.25s• Contents of indication : Changeable from following
(1) to (6) by a key operation(1) Flow rate m3/h(2) Thermal flow MJ/h, 10 MJ/h, 100 MJ/h, GJ/h(3) Temperature difference °C(4) Feed line temperature °C(5) Return line temperature °C(6) Differential pressure kPa
Totalized value indication part *2• 7-1/2 digit LCD : Letter height 5 mm, indication range 0 to
19999999• Counting frequency : 2 Hz or less• Totalized value saving function : Saved automatically in
EEPROM* every 1 hour or by a key operation* Use an external counter preferably because the rewritable
times of EEPROM are 1000000, about 10 years.Use the totalized value on the indicator mainly as a monitor-ing purpose.
• Reset of totalized values : By a key operation• Contents of indication : Changeable from following (1) or (2)
by a key operation(1) Totalized volume : m3 [ 0.001 to 1000](2) Totalized calorie : MJ [ 0.001 to 1000]
LCD back light : Operating 1 minute after a key opera-tion
Required straight runs
Note : D is inside diameter of pipe
Downstream
5D or more
3D or more
Pipe size
32 mm or less
40 mm or more
Upstream
10D or more
5D or more
Mass : Approx. 2 kg
CDT3000 series Calorie Monitor
TG-F1056-2E2 TOKYO KEISO CO., LTD.
Note 1: The inside diameter of pipe size 20 to 32 mm in 1 MPaclass is based on three-way socket JIS B 2301.Please specify the three-way sockets by using optionalcodes if requested.
Standard full scale range (maximum flow rate)when using 1 MPa class, 40 to 450 mm SGP pipe
Note 2: The inside diameter of pipe size 40 to 450 mm in 1 MPaclass is based on Carbon steel pipe for ordinary piping SGPJIS G 3452.
Standard full scale range (maximum flow rate)when using 2 MPa class, 20 to 32 mm three-way socket
Note 3: The inside diameter of pipe size 20 to 32 mm in 2 MPaclass is based on three-way socket with sch40.The three-way sockets are supplied by customers.
Standard full scale range (maximum flow rate)when using 2 MPa class, 40 to 450 mm STPG pipe
Note 4: The inside diameter of pipe size 40 to 450 mm in 2 MPaclass is based on Carbon steel pipe for pressure serviceSTPG (JIS G 3454 Sch 40).
Standard full scale range (maximum flow rate)when using 1 MPa class, 32 to 150 mm PVC lining pipe
Specifications of outputs Current outputs : Selectable from “Not required” or “The
followings”• Contents : Select from “one of (1) to (6) in Measuring
value indication”• Signal : 4 to 20 mA DC• Allowable load resistance : 500 Ω• Accuracy of output : ±0.5% F.S. at 23°C Accuracy of
indication itself• Temperature influence : ±0.03% F.S./ °C for both zero and
span• Response : 1s or less when filter is set as 0
Pulse outputs*2 : Selectable from “Not required” or “Thefollowings”
• Contents : Select from “ (1) or (2) in Totalized valueindication”
• Output type : Photo MOS relay®• Load rating : 30 VDC, 100 mA Max.• Pulse frequency : 2 Hz or less, Synchronized with totalized
value indication• Pulse width : ON 200 to 300 ms
Alarm outputs : Alarm output becomes ON when one offollowings occurs. You can also set to “Notrequired.”
(1) Flow rate indication exceeds 1999.(2) Thermal flow indication exceeds 1999.(3) Temperature difference exceeds 120% of its setting value.(4) Feed line temperature is less than -10°C or more than 120°C.(5) Return line temperature is less than -10°C or more than 120°C.(6) Differential pressure is less than -10% F.S. or more than 110%
F.S.• Output type : Photo MOS relay®• Load rating : 30 VDC, 100 mA Max.• Response : 1s or less to the indication
*2 Select a proper flow range so that normal flow rate becomesbetween 50% and 100% of the full scale range especially at thetotalized flow and pulse output-emphasized measurement. Theaccuracy of flow rate measurement is ±5% of full scale. Accord-ingly in the totalized flow measurement, if the normal flow rate israther low compared to flow range, the accumulated error re-sults in higher.
Standard full scale range (maximum flow rate)when using 1 MPa class, 20 to 32 mm three-way socket
Note 5: Above full scale ranges are based on the flow rate when theflow runs through the inside diameter of the pipe lined withPVC. The pipe consists of a tee joint of the Eslo coat LXmade by Sekisui Chemical Co.Åfs Eslon(R). Its maximumoperating pressure is 1 MPa. If you use the tee joints withthe different inside diameter from above, the extra calibra-tion is required.If your size is different from the one in the standard dimen-sions of D and L of PVC lining pipe described on page 7,consult us.
Pipe size Full scale flow rate m3/h Note 1Inside diameter
mmmm inch Code
20
25
32
3/4
1
1-1/4
05
3
4.5
8.5
10
4
6.5
12
20
6
9
17
(26)
(34)
(43)
Pipe size Full scale flow rate m3/h Note 2Inside diameter
mmmm inch Code
40
50
65
80
100
125
150
200
250
300
350
400
450
1-1/2
2
2-1/2
3
4
5
6
8
10
12
14
16
18
05
9
15
25
35
60
90
130
240
350
500
650
850
1100
10
13
20
35
50
85
130
190
340
500
750
900
1200
1500
20
18
30
50
75
120
190
270
480
720
1000
1300
1700
41.6
52.9
67.9
80.7
105.3
130.8
155.2
204.7
254.2
304.7
339.8
390.6
441.4
Pipe size Full scale flow rate m3/h Note 3Inside
diameter mm
mm inch Code
20
25
32
3/4
1
1-1/4
10
3
4.5
9
20
4
6.5
13
50
6
9
16
21.4
27.2
35.5
Pipe size Full scale flow rate m3/h Note 4Inside
diameter mm
mm inch Code
40
50
65
80
100
125
150
200
250
300
350
400
450
1-1/2
2
2-1/2
3
4
5
6
8
10
12
14
16
18
05
9
15
24
35
55
90
130
230
350
500
600
800
1000
10
12.5
20
34
48
80
130
180
320
500
700
900
1150
1500
20
18
30
48
70
110
180
260
460
700
1000
1250
1660
41.2
52.7
65.9
78.1
102.3
126.6
151.0
199.9
248.8
297.9
333.4
381.0
428.6
Pipe size Full scale flow rate m3/h Note 5Inside
diameter mm
mm inch Code
32
40
50
65
80
100
125
150
1-1/4
1-1/2
2
2-1/2
3
4
5
6
05
5
6.5
11
20
30
50
85
120
10
7
9
16
28
40
75
120
170
20
10
13
22
40
60
100
170
240
29.5
34.7
46.2
59.7
70.9
95.2
119.7
142
Refer to the " STANDARD SETTING LIST(1), (2) " on pages 10 and 11 for the details of Standard full scale range (maxi-mum flow rate), Maximum thermal flow and Multiplier.
CDT3000 series Calorie Monitor
TG-F1056-2E TOKYO KEISO CO., LTD. 3
MATERIAL AND OUTLINE DIMENSION
Feed line temperature sensor inputPower supply and signal output
CDT32
CDT34
(23)
72(1
5.5)
21 24
93
(0.5)93
(184)
(84) (100) l
R3/4
35
1 3 8 3 2 4 5 6 7
3
(41) (47)
(55)
(199
)
(127
)72
(105.5)
(84)
(66.5)
R3/4
l
1
8
3 3
2
4
5
6
7
1
2
3
4
5
6
7
8
No. Part name MaterialIndicatorDiaphragmBodyO-ringDrain hole sealIsolation valveValve shaftShaft O-ringVent valveCap nutFittingsO-ringPitot tubeTemperature sensor
Lead wire
Aluminum alloySUS 316LSUS 316Fluorocarbon rubberAlumina ceramicsSCS 14SUS 316NBRSUS 316SCS 13SCS 14NBRSUS 316SUS 316
PTFE insulated and fluorocarbon rubber sheathed
Pipesizemm
Standard "I" length mm*3 *4
*3 For SGP and STPG pipes*4 For PVC lining pipe
20 25 32 40 50 65 80 100 125 150 200 250 300 350 400 450
30 32 42 63 69 79 88 102 117 133 98 113 128 135 151 166
65 70 76 88 98 116 131 148
Note : The above length "I" of pitot tube is our standard size. When your sizes of pipe and socket are different from ours, check your sizes with "L" and "D" in the drawing on page 7 and consult us if necessary.
CDT3000 series Calorie Monitor
TG-F1056-2E4 TOKYO KEISO CO., LTD.
INDICATION PART
INTERCONNECTION
Measuring value indication part
Bar graph meter indication
Indicated in proportion to set value
Operation monitor
SET
ADJ.
H/C
Blinking during set mode
Remains ON while zero adjustment is enabled
Cooling or heating monitorDuring heating : ONDuring cooling : OFF
MODE key DOWN key UP key ENTER key
Totalized value indication part
Measuring unit monitorAlarm output monitor
Pulse output monitor
m3/h
MJ/h
°C ('T)
°C (TS)
°C (TR)
m3
MJ
Flow rate
Thermal flow
Temperature difference
Feed line temperature
Return line temperature
Totalized volume
Totalized calorie
The measured values of thermal flow, totalized volume and calorie are indicated in the following units and multipliers as specified.
Thermal flowTotal volumeTotal calorie
Flow rate, temperature difference, feed and return line temperature are indicated in fixed units.
0.001 m3
0.001 MJ0.01 m3
0.01 MJ0.1 m3
0.1 MJ
MJ/hm3
MJ
10 MJ/h10 m3
10 MJ
100 MJ/h100 m3
100 MJ
GJ/h1000 m3
1000 MJ
Applicable multi-core cable with shield
Outside diameter : ø4 to 8 mmCore wire cross section : 0.3 to 0.5 mm2 stranded
Terminalblock
Power supply 124 V DC ±10%
Receivinginstrument
Power supply 230 V DC, 100 mA or less
Load
Load
Shielded wire Power supply 330 V DC, 100 mA or less
Feed line RTDPt 100 Ω, 3 wire, JIS grade A
Return line RTDBuilt-in and pre-wired in Pitot tube before shipment
Note : RTD stands for resistance temperature detector Since the pulse and alarm are output by photo MOS relay®, the external power sources are acceptable as shown above power sources 1, 2, 3.
+ - + - + -
a1
COM
a2
A
B
b
A
B
b
POWER24 V DC
ANA. OUT4 to 20 m A DC
NC
OUT1PulseOUT2Alarm
TS
Pt100
TR
Pt100
+ -
+ -
+ -
+ -
CDT3000 series Calorie Monitor
TG-F1056-2E TOKYO KEISO CO., LTD. 5
*5 Insert “/ ” between each optional code if more than one options are involved.You are requested to see the option item list on the next chapter to check if your requirements are available or not.
Coding example 1 : No option is selected.With horizontal installation, Pipe size 50 mm, 1 MPa class and flow range code “10”“CDT3210-050-10AL-A”
Coding example 2 : All possible options are selected.With vertical installation, Pipe size 100 mm, 1 MPa class, flow range code “05”, A welding socket for flowmeter installationattached, Degreasing required, A feed line temperature sensor attached, and A welding socket for temperature sensor wellattached.“CDT3410-100-05AL-A/CFS/DEGPT3/PTS”
Coding example 3 : Piping specifications are different from the ones in above model code.With horizontal installation, Pipe size 80 mm, Pipe material SUS 304TPD, 1MPa class, flow range code “20”, A feed linetemperature sensor attached, and A welding socket for temperature sensor well attached.“CDT3210-080-20AL-A/PT2/PTS/Z”
When piping specifications for example, are different from the ones in model code as shown in the Coding example 3, your requirements fallinto the additional functions. Likewise if the sockets or three-way sockets provided by customers require different length of Pitot tube from ourstandard, it also falls into the additional functions.Accordingly, the last letter of model code other than the contents in above will be “/Z”.
MODEL CODE Please specify also INITIAL PAREMETER SETTING CODE on page 9
Blank
/Z
Carbon steel pipe for pressure service STPG (JIS G 3454 Sch 40)
Description RemarksInstall-ationtype
Horizontal type
Vertical type
1 MPa class
2 MPa class
20 mm
25 mm
32 mm
40 mm
50 mm
65 mm
80 mm
100 mm
125 mm
150 mm
200 mm
250 mm
300 mm
350 mm
400 mm
450 mm
Standard (See TYPICAL INSTALLATION METHODS on page 7)
Carbon steel pipe for ordinary piping SGP JIS G 3452Pressure rating
Pipe size Nominal diameter for installation pipe
Full scale range Flow rate range Select a code from the table "STANDARD FULL SCALE RANGE."
Indicator type
Application
Version
Fixed code
For liquid
Version symbol
2
4
CDT3 0
10
20
-
-020
-025
-032
-040
-050
-065
-080
-100
-125
-150
-200
-250
-300
-350
-400
-450
-
-05
-10
-20
-50
A
A
L
L
-A
-A
/
Option *5
Additional functions
/CFT
/CFS
/DEG
/PL
/PT1
/PT2
/PT3
/PTS
Three-way socket for flow-meter installation (CFTW)Welding socket for flow-meter installation (CFSW)
Degreasing (Standard)
PVC lining pipe
Feed line temperature sensor for 20 to 40 mmFeed line temperature sensor for 50 to 80 mmFeed line temperature sensor for 100 to 450 mmWelding socket fortemperature sensor well
Not provided
Provided
Applicable for 1 MPa class, 20 to 32 mm measuring pipe size. Only the material of FCMB is available.Nominal size 3/4 inch. Only the material of SS 400 is available.
Material of O-ring : NBR The procedure and grade of degreasing comply with Tokyo Keiso's standard. Applicable for all measuring pipe sizes.
Inform us L, D dimensions in the drawing on page 7.
RTD Pt100 Ω, 3 wire, JIS grade A with a protecting tees.
RTD Pt100 Ω, 3 wire, JIS grade A with a protection well of its connection size R1/2 inchRTD Pt100 Ω, 3 wire, JIS grade A with a protection well of its connection size R1/2 inchNominal size 1/2 inch. Only the material of SS 400 is available. Applicable for nominal sizes 50 to 450 mm of measuring pipe.No need to specify if your requirements are described by using above coding.Other requirements including specifications of pipe and the length of pitot tube other than above.
CDT3000 series Calorie Monitor
TG-F1056-2E6 TOKYO KEISO CO., LTD.
OPTION
See following option item list to check if your requirements are available or not.
Option item list for SGP and STPG pipes
Optional fittings for flowmeter installation
Optional feed line temperature sensor and its connection fittings
20
25
32
40
50
65
80
100
125
150
200
250
300
350
400
450
Thr
ee-w
ay
sock
et
Pipe sizemm
Standard installationmethod of flowmeter
Option
For installation of flowmeter
A feed line temperature sensor and its connection fittings
SG
P, S
TP
G p
ipes
3/43/43/4
113/4
1-1/41-1/43/4
3/4 inch socket
3/4 inch socket
3/4 inch socket
CFT (Size 20 mm)
CFT (Size 25 mm)
CFT (Size 32 mm)
CFS (3/4 inch Socket)
CFS (3/4 inch Socket)
CFS (3/4 inch Socket)
PT1 (Protection tees with 20 mm in size)
PT1 (Protection tees with 25 mm in size)
PT1 (Protection tees with 32 mm in size)
PT1 (Protection tees with 40 mm in size)
PT2 (Protection well connection size R1/2)
PTS (1/2 inch socket for protection well connection)PT3 (Protection well
connection size R1/2)
Remarks
The three-way sockets (CFT) for flow-meter installation are available only for 1 MPa class and material of FCMB.The three-way sockets (CFT) for 2 MPa class and other materials than FCMB are supplied by customers.
The optional protection tees (PT1) are available only for 1 MPa class and ma-terial of FCMB.Consult us for the protection tees for 2 MPa class and other materials than FCMB.The sockets for flowmeter installation (CFS) and sockets for protection well connection (PTS) are available only for the material SS400. Those materi-als other than SS400 are supplied by customers.
Note : Consult Tokyo Keiso Co., Ltd. for such specifications as PVC lining pipe, piping specifications designated by customers, feed line temperature sensor (resistance temperature detector, RTD) and its protection well.
Three-way socket for flowmeter installation (Model : CFTW)Option code : CFT
Sizemm
Dimensions of three-way socket
Applicable pipe size : 20 to 32 mmApplicable piping class : 1 MPaApplicable material : FCMB
Welding socket for flowmeter installation (Model : CFSW) Option code : CFS
Applicable pipe size : 40 to 450 mmApplicable piping class : 1 MPa, 2 MPaApplicable material : SS400
Rc3/4
B 2-d
AA
20
25
32
d A B
Rc3/4
Rc1
Rc1-1/4
33
35
36
33
36
4139
Rp3/4
Ø34
.5
Feed line temperature sensor and its protection tees (Option code : PT1 for 20 to 40 mm)
Extension wirePTFE insulated and fluorocarbon resin sheathed
Heat shrinkable tubeSilicone rubber
SheathSUS304
G1/4
Resistance temperature detector (RTD)
Temperature sensor : RTD Pt 100Ω, 3 wire, JIS grade A
Applicable pipe size : 20 to 40 mmApplicable piping class : 1 MPaApplicable material of protection tees : FCMB
Protection wellSUS304
G1/4
Protection teesFCMB
Dimensions of protection teesSizemm
5 30 20 10
2000 (150)
(59)
ø6.
4
A
2-d
(B)
A
20
25
32
40
d A B
Rc3/4
Rc1
Rc1-1/4
Rc1-1/2
28
30
33
34
50
51
53
55
CDT3000 series Calorie Monitor
TG-F1056-2E TOKYO KEISO CO., LTD. 7
Feed line temperature sensor and its protection well (Option code : PT2 for 50 to 80 mm, PT3 for 100 to 450 mm)
Extension wirePTFE insulated and fluoro-carbon resin sheathed
Heat shrinkabletubeSilicone rubber
SheathSUS304
Resistancetemperaturedetector(RTD)
Temperature sensor : RTD Pt 100 Ω, 3 wire, JIS grade A
Applicable pipe size : 50 to 450 mmApplicable piping class : 1 MPa, 2 MPaApplicable material : SS 400
Tube fitting Ø6.4SUS316
ProtectionwellSUS304
Welding socket for above protection well(Option code : PTS for 50 to 450 mm)
5 30 20
2000
10PT2: (150) PT3: (170)
ø6.
4
HE
X 2
2.2
R1/2
ø7
ø10
12 19
3PT2: (75) PT3: (100)
PT2: (106) PT3: (131)
Rp1/2
37
ø28OPTION PVC LINING
Option code : PL for 32 to 150 mm
The full scale ranges are based on the flow rate when the flowruns through the inside diameter of the pipe lined with PVC. Thepipe consists of a tee joint of the Eslo coat LX made by SekisuiChemical Co.’s Eslon®.If you use the tee joints with the different inside diameter fromabove, the extra calibration is required.For further consultation inform us of the dimension “D” in thefollowing drawing.
When the main pipe size is between 32 mm and 150 mm, provideeither one of the following tee joint and bushing assembly tomake the connection size 20 mm:— tee joint with 25 mm in branch line + A bushing with 25 mm x20 mm— tee joint with larger than 25 mm in branch line + One or morebushings in series to make the final connection size 20 mmFor further consultation inform us of the dimension “L” in thefollowing drawing.
Without these dimensions Tokyo Keiso Co., Ltd makesthem comply with our standard practice as shown in the followingtable. The full scale flow rate will be set as the values in the tableon page 2.
Consult Tokyo Keiso Co., Ltd. for the additional equipment suchas the feed line temperature sensor (RTD) and protection well forits installation or else.
STANDARD ACCESSORY Protection cover for indicator
Avoid installing this instrument at the places exposed to directsunlight or rain as much as possible. If it is inevitable, providewith a protection cover above indicator.
OTHER PIPES Other types of piping configuration are also available. Feel free to contact Tokyo Keiso Co., Ltd. Inform us your piping
specifications and following L and D dimensions.
TYPICAL INSTALLATION METHODS Install the flowmeter on the three-way socket for the pipe sizes
from 20 to 32 mm as shown in the following drawing.Weld a socket on the straight pipe and install the flowmeter onthe socket for the pipe sizes 40 mm or more.You can install the flowmeter either on horizontal or vertical pipefor model CDT32.
Rc3/4
øD
L
Bushing(R1Rc 3/4)
to 32mm
Pipesizemm
Dimensions based on ourstandard practices
Applicable pipe size : 32 to 150 mmApplicable piping class : 1 MP
øD
L
D L
32
40
50
65
80
100
125
150
29.5
34.7
46.2
59.7
70.9
95.2
119.7
142
62.5
65.5
71.5
80.5
88.5
103.5
117.5
130.5
Protection cover made of polypropylene
Pipe size CDT32For horizontal and vertical piping
CDT34For horizontal piping
Three-waysocket
Straight pipe
Socket
20 to 32mm
40 to 450mm
CDT3000 series Calorie Monitor
TG-F1056-2E8 TOKYO KEISO CO., LTD.
FLOW MEASUREMENT CONFIGURATION
Install the CDT3000 on return line. The CDT3000 installed on feed line gives a calculation error and results in wrong measurement.
PARAMETER SETTING AND ADJUSTMENT
The key operation on the front panel enables the setting changes.• Mode change : Selectable from “Automatic change-over cooling or heating”, “Cooling fixed mode”, “Heating fixed mode”• Low cut-off of flow rate : Can be set at any value between 0 to 100% F.S. (Standard setting : 7%)• Indication filter : Selectable from 0, 2, 4, 8, 16, 32 seconds in moving average. Applicable for flow rate/thermal flow, feed
and return temperature.(Standard setting : 4 seconds for flow rate/thermal flow, 4 seconds for feed and return temperature)
• Maximum temperature difference : Can be set at any value between 0.5 to 80.0°C. (Standard setting : 20°C)• Zero adjustment : Available for flow rate/differential pressure, temperature difference.
Current output : Flow ratePulse output : CalorieAlarm output : Measuring error
Flow rate measurement : QReturn line measured temperature : TR
Power supply : 24 V DCFeed line temperature
Heat source
Feed line
Return line
Heat duty
Feed line temperature sensorPt 100 Ω, 3 wire, JIS grade AFeed line measured temperature : TS
Automatic change-over from heating to cooling mode and vice versa
From heating to cooling mode
Conversion coefficient : Calorie is calculated and indicated as k= 4.186 MJ/°Cm3.
Conversion coefficient : Calorie is calculated and indicated as k= 4.123 MJ/°Cm3.
Conversion coefficient : Calorie is calculated and indicated as k= 4.186 MJ/°Cm3.
Conversion coefficient : Calorie is calculated and indicated as k= 4.123 MJ/°Cm3.
Feed line temperature °C*6
From cooling to heating mode
10 20 25 30 40
The thermal flow is determined by the following equation.Thermal flow F = Q TS—TR k = Q T k [MJ/h]
Flow rate : Q [m3/h] : Measured by CDT3000Feed line temperature : TS [°C] : Measured by a RTD supplied by customersReturn line temperature : TR [°C] : Measured by CDT3000Calorie conversion coefficient : k [MJ/°Cm3] : At cooling mode 4.186/ At heating mode 4.123
Note : When T 0.5°C, the thermal flow automatically becomes 0 MJ/h due to the low cut-off function of temperature difference.
*6 Operation at 25°C or lower is cooling mode, and 30°C or higher is heating mode according to our standard practice. The different specifiedvalues override these values. At start up just after the installation of CDT3000 when feed line temperature is between 25 to 30°C, the thermal flow is calculated and indicated as k= 4.186 MJ/°Cm3.Even at this stage, when T0.5°C, the thermal flow becomes 0 MJ/h due to the low cut-off function.
CDT3000 series Calorie Monitor
TG-F1056-2E TOKYO KEISO CO., LTD. 9
INITIAL PARAMETER SETTING CODE (Please specify also MODEL CODE on page 5)
*7 Setting of Temperature at cooling and heating mode, Current output required or not, Pulse output required or not, No alarm output designation, Back light required or not can not be set by the indication key operation. However, if current output or pulse output is added, the output items can be also changed by indication key operation.*8 Align the flowmeter in the same flow direction as indicated. The change of flow direction after start-up requires the stoppage of liquid flow.*9 Designate the values of full scale range and maximum thermal flow if other than standard ranges are required , referring to the "INDICATION SETTING LIST" while selecting code "Z".*10 If you have any other special setting requirements other than above, feel free to contact us
Parameters in shaded area are set initially as standard.
Description Setting range
Full scale range
Maximum thermal flow
Thermal flow multipliers
Standard
Designate values *9
Standard
Designate the values *9
Standard
MJ/h
10 MJ/h
100 MJ/h
GJ/h
Standard
Designate it between the values indicated on the right
Standard
Designate it between the values indicated on the right
Standard
Designate it between the values indicated on the right
Not required
Flow rate (Standard)
Thermal flow
Temperature difference
Feed line temperature
Return line temperature
Differential pressure
Not required
Totalized volume
Totalized calorie (Standard)
Bottom to top
Left to right (Standard)
Right to left
Top to bottom
Version symbol
Not required
Fixed operation mode
Low cut-off value
Differential pressure filter
Feed line temperature filter
Return line temperature filter
Back light *7
OUT 2 (No alarm output) *7
Others *10
See "STANDARD SETTING LIST(1), (2)."
See "INDICATION SETTING LIST."
See "STANDARD SETTING LIST(1), (2)."
See "INDICATION SETTING LIST."
See "STANDARD SETTING LIST(1), (2)."
See "INDICATION SETTING LIST."
Setting of temperature at cooling mode *7
25°C15 to 24°C only integer
30°C31 to 40°C only integer
20°C21 to 60°C only integer
Outputted to indication range 0 to 100% F.S.
Outputted to indication range 0 to 100% F.S.
Outputted to maximum set temperature difference
Outputted to -10 to 120°COutputted to -10 to 120°COutputted to differential pressure range
100 c/h or more and less than 1000 c/h
100 c/h or more and less than 1000 c/h
Cooling or heating mode
Between 0 to 50% only integer
0s, 2s, 4s (Standard), 8s, 16s, 32s
0s, 2s, 4s (Standard), 8s, 16s, 32s
0s, 2s, 4s (Standard), 8s, 16s, 32s
Invalid
Designate if any
Blank
Setting of temperature at heating mode *7
Setting of maximum temperature difference
Current output *7
OUT 1 Output (pulse output) *7
Flow direction *8
Version
Other special setting
CDT3 - - -A
1
Z1
Z
1
2
3
4
5
-25
-30
20
-0
-1
-2
-3
-4
-5
-6
0
1
2
1
6
7
8-A
/Z
CDT3000 series Calorie Monitor
TG-F1056-2E10 TOKYO KEISO CO., LTD.
STANDARD SETTING LIST (1)
INDICATION SETTING LIST
0.2 to 1.999 m3/h
2 to 19.99 m3/h
20 to 199.9 m3/h
200 to 1999 m3/h
0.200 to 1.999
2.00 to 19.99
20.0 to 199.9
200 to 1999
Full scale range(Maximum flow rate)
Indication rangeand decimal place
Indicationunit
only m3/h
Note : You can not set full scale range of 2000 m3/h or more.
0.2 to 1.999 MJ/h
2 to 19.99 MJ/h
20 to 199.9 MJ/h
200 to 1999 MJ/h
2000 to 19990 MJ/h
20000 to 199900 MJ/h
200000 to 1999000 MJ/h
0.200 to 1.999
2.00 to 19.99
20.0 to 199.9
200 to 1999
200 to 1999
200 to 1999
200 to 1999
Maximum thermal flow range
Indication range and decimal place
Indication unit and multipliers
Thermal flow multiplier code
Note : You can not set maximum thermal flow range of 2000 GJ/h or more.
MJ/h
MJ/h
MJ/h
MJ/h
10 MJ/h
100 MJ/h
GJ/h
2
3
4 5
Standard full scale range (maximum flow rate) and Maximum thermal flow indication setting list when using 1 MPa class, 20 to 32 mm three-way socket and 40 to 450 mm SGP pipe
1 MPa classFlow rate range code : 05
Pipe sizemm
Pipe inside dia-meter
Full scale range (maximum flow rate)
Maximumthermal flow
Indication value
Indicationunit
Indication value
Indicationunit
Flow rate range code : 10Full scale range (maximum flow rate)
Maximumthermal flow
Indication value
Indicationunit
Indication value
Indicationunit
Full scale range (maximum flow rate)
Maximumthermal flow
Indication value
Indicationunit
Indication value
Indicationunit
Flow rate range code : 20
20
25
32
40
50
65
80
100
125
150
200
250
300
350
400
450
26
34
43
41.6
52.9
67.9
80.7
105.3
130.8
155.2
204.7
254.2
304.7
339.8
390.6
441.4
3.00
4.50
8.50
9.00
15.00
25.0
35.0
60.0
90.0
130.0
240
350
500
650
850
1100
m3/hfixed
m3/hfixed
m3/hfixed
260
380
720
760
1300
210
300
510
760
1100
210
300
420
550
720
930
MJ/h
MJ/h
MJ/h
MJ/h
MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
4.00
6.50
12.00
13.00
20.0
35.0
50.0
85.0
130.0
190.0
340
500
750
900
1200
1500
340
550
1100
1100
1700
300
420
720
1100
1600
290
420
630
760
1100
1300
6.00
9.00
17.00
18.00
30.0
50.0
75.0
120.0
190.0
270
480
720
1000
1300
1700
510
760
1500
1600
260
420
630
1100
1600
230
410
610
840
1100
1500
CDT310--05AL-A CDT310--10AL-A CDT310--20AL-A
MJ/h
MJ/h
MJ/h
MJ/h
MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
MJ/h
MJ/h
MJ/h
MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
Standard full scale range (maximum flow rate) and Maximum thermal flow indication setting list when using 2 MPa class, 20 to 32 mm three-way socket and 40 to 450 mm STPG pipe
2 MPa class20 to 32 mm Flow rate range code : 1040 to 450 mm Flow rate range code : 05
Pipe sizemm
Pipe inside dia-meter
Full scale range (maximum flow rate)
Maximumthermal flow
Indication value
Indicationunit
Indication value
Indicationunit
Full scale range (maximum flow rate)
Maximumthermal flow
Indication value
Indicationunit
Indication value
Indicationunit
Full scale range (maximum flow rate)
Maximumthermal flow
Indication value
Indicationunit
Indication value
Indicationunit
20 to 32 mm Flow rate range code : 2040 to 450 mm Flow rate range code : 10
20 to 32 mm Flow rate range code : 5040 to 450 mm Flow rate range code : 20
20
25
32
40
50
65
80
100
125
150
200
250
300
350
400
450
21.4
27.2
35.5
41.2
52.7
65.9
78.1
102.3
126.6
151
199.9
248.8
297.9
333.4
381
428.6
3.00
4.50
9.00
9.00
15.00
24.0
35.0
55.0
90.0
130.0
230
350
500
600
800
1000
m3/hfixed
m3/hfixed
m3/hfixed
260
380
760
760
1300
210
300
470
760
1100
200
300
420
510
670
840
MJ/h
MJ/h
MJ/h
MJ/h
MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
4.00
6.50
13.00
12.50
20.0
34.0
48.0
80.0
130.0
180.0
320
500
700
900
1150
1500
340
550
1100
1100
1700
290
410
670
1100
1600
270
420
590
760
1000
1300
6.00
9.00
16.00
18.00
30.0
48.0
70.0
110.0
180.0
260
460
700
1000
1250
1650
510
760
1400
1600
260
410
590
1000
1600
220
390
590
840
1100
1400
CDT320--10AL-ACDT320--05AL-A
CDT320--20AL-ACDT320--10AL-A
CDT320--50AL-ACDT320--20AL-A
MJ/h
MJ/h
MJ/h
MJ/h
MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
MJ/h
MJ/h
MJ/h
MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
100 MJ/h
CDT3000 series Calorie Monitor
TG-F1056-2E TOKYO KEISO CO., LTD. 11
Head Office : Shiba Toho Building, 1 – 7 – 24 Shibakoen, Minato-ku, Tokyo 105 – 8558
Tel : +81-3 – 3431 – 1625 (KEY) ; Fax : +81-3 – 3433 – 4922
e-mail : [email protected] ; URL : http://www.tokyokeiso.co.jp
* Specification is subject to change without notice.
STANDARD SETTING LIST (2)
Standard full scale range (maximum flow rate) and Maximum thermal flow indication setting list when using 1 MPa class, 32 to 150 mm lining pipe
Standard multipliers for totalization list
PVC liningpipe Flow rate range code : 05
Pipe sizemm
Pipe inside dia-meter
Full scale range (maximum flow rate)
Maximumthermal flow
Indication value
Indicationunit
Indication value
Indicationunit
Flow rate range code : 10Full scale range (maximum flow rate)
Maximumthermal flow
Indication value
Indicationunit
Indication value
Indicationunit
Flow rate range code : 20Full scale range (maximum flow rate)
Maximumthermal flow
Indication value
Indicationunit
Indication value
Indicationunit
Full scale range(maximum flow rate) m3/h Multipliers for totalized flow
Maximum thermal flow range MJ/h
Multipliers for total-ized flow Maximum count number range
1000c/h to 1999c/h(Not recommended)
1 to 9.99
10 to 99.9
100 to 999
1000 to 1999
100 to 999
1000 to 9990
10000 to 99900
100000 to 999000
1000000 to 1999000
100c/h to 999c/h
0.01 m3
0.1 m3
1 m3 (Indicated as m3)
10 m3
1 MJ (Indicated as MJ)
10 MJ
100 MJ
1000 MJ
1000 MJ
32
40
50
65
80
100
125
150
29.5
34.7
46.2
59.7
70.9
95.2
119.7
142
5.00
6.50
11.00
20.0
30.0
50.0
85.0
120.0
m3/hfixed
m3/hfixed
m3/hfixed
420
550
930
1700
260
420
720
1100
MJ/h
MJ/h
MJ/h
MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
MJ/h
MJ/h
MJ/h
MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
MJ/h
MJ/h
MJ/h
MJ/h
10 MJ/h
10 MJ/h
10 MJ/h
100 MJ/h
7.00
9.00
16.00
28.0
40.0
75.0
120.0
170.0
590
760
1400
240
340
630
1100
1500
10.00
13.00
22.0
40.0
60.0
100.0
170.0
240
840
1100
1900
340
510
840
1500
210
CDT310--05AL-A/PL CDT310--10AL-A/PL CDT310--20AL-A/PL