cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

download cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

of 30

Transcript of cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    1/30

    FIRE DETECTION & ALARM SYSTEM

    RAVI SHANKAR SINGH

    (E6S304)

    1

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    2/30

    2

    Why are fire detection and alarm systems

    required?

    Detect fire in the areas.

    Notify building occupants to take evasive action to escape thedangers of a hostile fire.

    Summon organized assistance to initiate or assist in fire controlactivities.

    Initiate automatic fire control & suppression systems & to soundalarm.

    Supervise fire control & suppression systems to assure operationalstatus is maintained Initiate auxiliary functions involving

    environmental, utility & process controls

    Systems may incorporate one or all of these functions

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    3/30

    Block diagram of FDA system

    3

    Input

    Devices

    Output

    Devices

    Control

    Panel

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    4/30

    4

    Input Devices

    Fire Box (Manual Pull Station)

    When shorted trips an alarm (usually fire)

    Installed in the normal exit path

    Types of Fire Box Single Action

    Pull handle once

    Glass Break

    Glass rod or plate is broken

    Double Action

    Lifting of a cover or opening a door

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    5/30

    5

    3.1) Heat detectors

    1. fixed temp type heat detector

    2. rate-of-rise type heat detector

    3.2) Smoke detectors

    1. Photoelectric

    2. Ionization

    3.3) Flame detectors

    1. Ultraviolet light (UV)

    2. Infrared (IR)3.4) Fire-gas detectors

    FIRE DETECTORS

    Input Devices

    Heat Detectors

    Smoke Detector

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    6/30

    6

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    7/30

    Fixed temp. heat detectors

    Detect heat by one or more of 3 primary principles of physics:

    Expansion of heated material

    Melting of heated material Changes in resistance of heated material

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    8/30

    Rate-of-rise heat detectors

    Operate on the principle that the temperature in a room willincrease faster from fire than from atmospheric temperature

    Will initiate an alarm when the rise in temp. exceeds 12-15F (7-8C)

    per minute

    Alarm can be initiated at a temp. far below that required for a fixed-

    temp. device

    Reliable devices, not subject to false activations

    But if not properly installed, they can be activated under non fire

    conditions (eg. detector located too close to doorway and subject to

    extreme fluctuations in temperatures)

    Pneumatic rate-of-rise spot detector

    Pneumatic rate-of-rise line detector

    Thermoelectric detector

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    9/30

    9

    Photoelectric smoke detector

    Uses a photocell coupled with a specific light source.

    Basically smoke entering the smoke detector chamber disruptsthe light beam causing an alarm signal to be initiated

    More sensitive to smoldering fires

    1: optical chamber

    2: cover3: case moulding

    4: Photodiode (detector)

    5: infrared LED

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    10/30

    10

    Circuit of Photoelectric Smoke Detector

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    11/30

    11

    Ionization smoke detector

    Invisible products of combustion enter the chamber

    decreasing the current between theve & +ve plates,

    thereby initiating an alarm signal.

    Generally responds faster to flaming fires versus

    smoldering fires Automatically resets when the atmosphere clears

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    12/30

    Fire-gas detectors

    Monitors levels of carbon dioxide and carbon monoxide

    (common to all fires)

    More discriminating than other detectors can be designed to

    be sensitive only to gases produced by specific types of hostile

    fires and ignores gases produced by friendly fires

    Not many in use very specialized applications

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    13/30

    Combination detectors

    Single device can be designed to have more than 1 function eg.

    heat/smoke, smoke/carbon monoxide detectors

    Different combination make the detectors more versatile and

    more responsive to fire conditions

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    14/30

    14

    S.No PLANT AREA TYPE OF DETECTORS

    1. Main control room, Computer

    room, Electronic cubicle

    room and control rooms inoutlying areas.

    Combination of -

    Ionisation smoke detector

    Optical type smoke detector

    2. Switchgear rooms in main

    Plant and outlying areas,

    battery charger room, record

    and shift-in-charge engineers

    room

    Ionisation type smoke detector.

    3. Office rooms / storage rooms Ionisation type smoke detector

    4. Battery rooms and chemically

    corrosive areas.

    Corrosion resistant, Rate of rise of temperature heat

    detectorwith fixed temperature setting.

    5. Cable gallery Combination of Optical type smoke detectors and Linear

    heat sensorrunning above all HV and LV power cable trays.

    Unless the vertical distance between cable tray is less than

    500 mm in which case alternate trays (in addition to the top

    and bottom trays). The optical smoke detector and LHS

    detectors along with necessary number of interface units in the

    cable gallery will be cross zoned to actuate the water spray

    system

    6. Station building / Plant area Infrared flame detectors (where oil tanks are located), spray

    tanks rate of rise of temp. detectorwith fixed element

    Selection of Detectors for different Area

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    15/30

    15

    7. Coal Conveyors Analogue Linear heat sensor cable, infra red spark / ember

    detectors and manual call points. If water spray system is

    provided the LHS cable and IR detectorwill be cross zoned toactuate the same

    8. Dusty areas in coal handling

    plants like crusher house

    Flame proof manual call points

    9. Junction towers Flame proof heat detectors, flame proof manual call points

    10. Conveyor tunnels Flame proof infrared detectors, flame proof MCPs, LHS

    cables

    11. Hazardous plant areas such

    as fuel oil / lube oil, DG

    houses, H2 generating plantsand hydrogen storage areas.

    Flame proof rate of rise of temperature detector with fixed

    element and flame proof MCP

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    16/30

    16

    Audible Output Devices An audible alarm signal lets people know

    the alarm system has been activated

    Devices may be mounted inside or outside

    based on level of protection required May consist of:

    Sirens

    Bells

    Buzzers

    Horns

    Voice Drivers

    Output Devices

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    17/30

    17

    Visual Output Devices

    A visual signal lets users know the status ofthe alarm system if activated

    Visual devices may be mounted inside oroutside

    May consist of...

    Strobe lights LEDs

    On / Off site printer

    Output Devices

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    18/30

    1

    8

    Criteria to determine layout of the fire detectors

    The design, construction and operational features of all types of

    detectors shall be in accordance with relevant standards.

    The number of fire detectors to be installed is governed by

    total area to be protected

    type of building construction

    air movement & air velocity

    ceiling obstructions

    concentration of equipment in the area covered

    sensitivity required

    Area is divided into zones to be protected

    The zones of individual detectors should overlap and no blind zone

    should be left.

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    19/30

    19

    Areas above false ceiling and below false flooring shall be

    considered as separate zones.

    Under ideal conditions of smooth ceiling and average room size, one

    detector is recommended to protect the area.

    Ionisation type detectors should be located where the largest

    combustible gas concentration can be expected.

    In the air conditioned areas both ionisation and optical type smoke

    detectors are used.

    Detectors must always installed at the highest point of the ceiling

    and minimum coverage indicated by manufacture shall be

    considered.

    The number of detectors and their location should be so selected that

    complete coverage is obtained

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    20/30

    2

    0

    Initial quantity estimation of smoke / heat detectors

    35 to 40 sq.m per detector for general application.

    20 to 25 sq.m per detector for main control room, electronic

    cubicle room, computer room, etc., in view of high valve

    concentration

    The exact requirement shall calculated based on relevant

    IS/NFPA standard

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    21/30

    TYPES OF FIRE DETECTION SYSTEM

    A. Conventional FDA System

    B. -P Based Addressable FDA System

    2

    1

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    22/30

    CONVENTIONAL FIRE DETECTION AND ALARM SYSTEM

    Conventional fire sensors and manual call points shall provide for continuous

    surveillance the area.

    Main fire alarm panel shall derive signals from the zone indicating panels and

    audible and visual annunciation shall be provided in the event of fire. Repeater panel shall be located in security house / fire station to alert fire

    fighting / security personnel.

    Fire detectors shall be selected depending on the type of fire expected in a

    particular area.

    22

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    23/30

    2

    3

    All the fire alarm circuits shall be of modular design using

    electronic printed card circuits to facilitate easy replacement.

    The system design shall be such that operation / resetting of

    alarms for one zone / detector will not block availability of alarm

    for any other zone.

    the alarm / system resetting shall be by common push button andnot by individual switches for different zones / detectors.

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    24/30

    24

    Addressable Fire Detection & Alarm

    System

    It is an automatic fire detection & alarm system consists of firedetectors & manual call points positioned in Zones/ loop through

    out a building(Area).

    These are wired to control & indicating equipment which shows

    the location of alarm call, & actuates audible alarm sounders.

    Industrial/ Non Industrial Buildings

    Institutional Buildings

    Residential Apartments Hotel & Hospitals

    All Industries

    Mall & Multi Storied Complexes

    Offices & Control Rooms

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    25/30

    25

    Addressable -P based FDA system

    Addressable I/P devices

    Addressable O/P devices

    Control panel

    Constant power supply

    Emergency Battery supply

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    26/30

    2

    6

    Microprocessor Based control Panel

    Processor(CPU)

    Adequate number of loop modules for detector loops

    A coloured VDU monitor with keyboard

    Output modules for alarm

    Output control & interlocks

    Communication modules for interfacing

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    27/30

    27

    Continuous supervision of the detector connecting lines, individual

    detector performance / operation and disconnection / removal of

    detectors.

    Discrimination between a real fire and false fire conditions by

    incorporating signal verification and other features.

    Individual detector addressing capability.

    Detection of over / under sensitive detectors and automatic calibration

    by increasing or decreasing their sensitivity levels based on

    environmental conditions like air movement, fumes, humidity, etc.

    Pre-alarm in case of any detector / detectors requiring maintenance.

    Facility shall be provided for alteration programme according to needs.

    BENEFITS OF -P BASED ADDRESSABLE FDA

    SYSTEM

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    28/30

    CLEARANCE AND APPROVALS

    All detectors and sensors shall be approved by any of the

    following bodies as applicable :

    A. Under writers Laboratories (UL) USA

    B. Fire Officers Committee (FOC) UK

    C. Any other internationally recognised body acceptable to

    Purchaser / Consultant. Approval certificates shall be

    furnished with the bid.

    28

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    29/30

    The Contractor shall be solely responsible for obtaining the

    required approval and clearance for the different components

    and systems of the fire detection and alarm system from the

    following authorities as applicable.

    A. Tariff Advisory Committee (TAC) of the Insurance Association of

    India.

    B. Dept. of Atomic Energy (DAE) Certification of safety from

    radioactivity.

    C. Central Building Research Institute (CBRL), Roorkee

    D. Central Mining Research Station (CMRS), Dhanbad.

    E. Local Fire Authority.

    29

  • 7/27/2019 cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01.ppt

    30/30

    SOME APPLICABLE STANDARDS

    Code of practice for selection, installation & maintenance of

    automatic fire alarm & detection system-IS-2189,BS-5839

    PART1,ANSI-NFPA-72,FOC RULES

    Code of practice for fire safety of buildings - IS-1646

    Smoke detectors for use in automatic fire alarm system-IS-11360,

    BS-5445 PART-7, ANSI-UL268

    3

    0