Catalogue tai sin

40
1 Stranded Plain Annealed Copper Conductor ___________________________________________________ 2 PVC Cables Single Core _________________________________________________________________ 3 PVC/ PVC Cables 1 Core & 2 Cores _______________________________________________________ 4 PVC/ PVC Cables 3 Cores & 4 Cores _______________________________________________________ 5 PVC/ PVC Cables Multi Cores ____________________________________________________________ 6 PVC/ AWA/ PVC Cables Single Core ______________________________________________________ 7 PVC/ SWA/ PVC Cables 2 Cores, 3 Cores & 4 Cores __________________________________________ 8 PVC/ SWA/ PVC Cables - Multi Cores _______________________________________________________ 9 Flexible Cable, Circular Sheathed, Metric Unit - 2 Cores, 3 Cores & 4 Cores _________________________ 10 Flexible Cord, Twin Twisted, Imperial Unit ___________________________________________________ 11 Flexible Cable, Circular Sheathed, Imperial Unit 1 Core, 2 Cores, 3 Cores & 4 Cores _________________ 11 XLPE/ PVC & XLPE/ AWA/ PVC Cables Single Core _________________________________________ 12 XLPE/ PVC & XLPE/ SWA/ PVC Cables - 2 Cores, 3 Cores & 4 Cores _____________________________ 13 XLPE/ PVC & XLPE/ SWA/ PVC Cables Multi Cores _________________________________________ 14 IN-POP & IN-POSP - Multi Cores __________________________________________________________ 15 IN-POP & IN-POSP Single & Multi Pairs ___________________________________________________ 16 IN-PIOP & IN-PIOSP Multi Pairs _________________________________________________________ 17 IN-EOP & IN-EOSP Single & Multi Pairs ___________________________________________________ 18 IN-EIOP & IN-EIOSP Multi Pairs _________________________________________________________ 19 XLPE/ CT/ AWA/ PVC Cables Single Core _________________________________________________ 20 XLPE/ CT/ SWA/ PVC Cables 4 Cores _____________________________________________________ 21 XLPE/ CT/ PVC Cables 3 Cores + 3 Earth ___________________________________________________ 22 Schedule of Installation Methods of Cables ____________________________________________________ 23 Correction Factors _______________________________________________________________________ 26 Current Rating and Voltage Drop (PVC Insulated Cables) ________________________________________ 28 Current Rating and Voltage Drop (XLPE Insulated Cables) _______________________________________ 32 Current Rating and Voltage Drop (Flexible Cables) _____________________________________________ 36 Short Circuit Current for PVC Insulated & XLPE Insulated Cables _________________________________ 37 Short Circuit Ratings _____________________________________________________________________ 38 Additional Technical Information ___________________________________________________________ 39 Conversion Tables of Conductor Size ________________________________________________________ 40

description

Catalogue TaiSin

Transcript of Catalogue tai sin

Page 1: Catalogue tai sin

1

Stranded Plain Annealed Copper Conductor ___________________________________________________ 2

PVC Cables – Single Core _________________________________________________________________ 3

PVC/ PVC Cables – 1 Core & 2 Cores _______________________________________________________ 4

PVC/ PVC Cables – 3 Cores & 4 Cores _______________________________________________________ 5

PVC/ PVC Cables – Multi Cores ____________________________________________________________ 6

PVC/ AWA/ PVC Cables – Single Core ______________________________________________________ 7

PVC/ SWA/ PVC Cables – 2 Cores, 3 Cores & 4 Cores __________________________________________ 8

PVC/ SWA/ PVC Cables - Multi Cores _______________________________________________________ 9

Flexible Cable, Circular Sheathed, Metric Unit - 2 Cores, 3 Cores & 4 Cores _________________________ 10

Flexible Cord, Twin Twisted, Imperial Unit ___________________________________________________ 11

Flexible Cable, Circular Sheathed, Imperial Unit – 1 Core, 2 Cores, 3 Cores & 4 Cores _________________ 11

XLPE/ PVC & XLPE/ AWA/ PVC Cables – Single Core _________________________________________ 12

XLPE/ PVC & XLPE/ SWA/ PVC Cables - 2 Cores, 3 Cores & 4 Cores _____________________________ 13

XLPE/ PVC & XLPE/ SWA/ PVC Cables – Multi Cores _________________________________________ 14

IN-POP & IN-POSP - Multi Cores __________________________________________________________ 15

IN-POP & IN-POSP – Single & Multi Pairs ___________________________________________________ 16

IN-PIOP & IN-PIOSP – Multi Pairs _________________________________________________________ 17

IN-EOP & IN-EOSP – Single & Multi Pairs ___________________________________________________ 18

IN-EIOP & IN-EIOSP – Multi Pairs _________________________________________________________ 19

XLPE/ CT/ AWA/ PVC Cables – Single Core _________________________________________________ 20

XLPE/ CT/ SWA/ PVC Cables – 4 Cores _____________________________________________________ 21

XLPE/ CT/ PVC Cables – 3 Cores + 3 Earth ___________________________________________________ 22

Schedule of Installation Methods of Cables ____________________________________________________ 23

Correction Factors _______________________________________________________________________ 26

Current Rating and Voltage Drop (PVC Insulated Cables) ________________________________________ 28

Current Rating and Voltage Drop (XLPE Insulated Cables) _______________________________________ 32

Current Rating and Voltage Drop (Flexible Cables) _____________________________________________ 36

Short Circuit Current for PVC Insulated & XLPE Insulated Cables _________________________________ 37

Short Circuit Ratings _____________________________________________________________________ 38

Additional Technical Information ___________________________________________________________ 39

Conversion Tables of Conductor Size ________________________________________________________ 40

Page 2: Catalogue tai sin

2

Stranded Plain Annealed Copper Conductor BS 66360 & IEC 60228 Table 1

Nominal

Conductor

Area

No. and

Diameter

of Wire

No. and

Diameter

of Conductor

Maximum

Conductor

Resistance at 200C

Nominal Weight

per km

of Conductor

(mm2) (no./mm) (mm) (Ω/km) (kg/km)

1.0

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

630

800

1000

7/ 0.43

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

61/ 2.85

61/ 3.20

127/ 2.52

127/ 2.85

127/ 3.20

1.29

1.59

2.01

2.55

3.12

4.05

5.10

6.42

7.56

8.90

10.70

12.60

14.21

15.75

17.64

20.25

22.68

25.65

28.80

32.76

37.05

41.60

18.1

12.1

7.41

4.61

3.08

1.83

1.15

0.727

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

9.2

14.0

22.4

36.1

54

90.8

145

229

317

429

620

860

1086

1334

1673

2199

2759

3528

4448

5744

7346

9260

Construction Technical Data

1. Conductor : Plain Annealed Copper

Conductor Stranding : Class 2 stranded circular or compacted conductors

Page 3: Catalogue tai sin

3

PVC Cables SS358 Table 2

Nominal

Conductor

Area

No. and Diameter

Of

Wire

Radial Thickness

Of

Insulation

Mean Overall

Diameter

(Upper Limit)

Approx.

Weight

Minimum Insulation

Resistance

at 700C

(mm2) (no./mm) (mm) (mm) (kg/ km) (mΩ/ km)

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

630

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

61/ 2.85

61/ 3.20

127/ 2.52

0.7

0.8

0.8

0.8

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

2.8

2.8

3.4

4.2

4.8

5.4

6.8

8.0

9.8

11.0

13.0

15.0

17.0

19.0

21.0

23.5

26.5

29.5

33.5

37.0

41.0

22.7

34.0

50.0

70.9

117.5

177.4

279.5

372.0

504.5

710.6

980.8

1216.0

1498.0

1874.0

2444.4

3059.5

3897.0

4940.0

6295.0

0.010

0.009

0.0077

0.0065

0.0065

0.0050

0.0050

0.0040

0.0045

0.0035

0.0035

0.0032

0.0032

0.0032

0.0032

0.0030

0.0028

0.0028

0.0025

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: PVC Compound Type C

3. Colour: Red, Yellow, Blue, Black, Green,

White, or Green/ Yellow

Voltage Uo/U: 450/ 750V

Conductor Stranding: Class 2 stranded circular or compacted

conductors

Operating Temperature: Maximum 700C

Minimum Bending Radius: 3D for D < 10mm

4D for 10mm < D < 25mm

6D for D > 25mm

Page 4: Catalogue tai sin

4

PVC/ PVC Cables IEC 60502 Table 3

Nominal

Conductor

Area

No. and Diameter

of

Wire

Radial Thickness

of

Insulation

Approx.

Overall

Diameter

Approx.

Weight

(mm2) (no./mm) (mm) (mm) (kg/ km)

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

630

800

1000

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

61/ 2.85

61/ 3.20

127/ 2.52

127/ 2.85

127/ 3.20

0.8

0.8

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

2.8

2.8

2.8

3.0

6.3

6.7

7.6

8.2

9.2

10.2

11.9

13.1

14.8

16.6

19.2

20.8

23.0

25.4

28.7

31.7

35.3

39.5

43.2

47.7

53.0

55

70

100

125

175

240

350

460

595

810

1110

1360

1670

2070

2690

3340

4230

5290

6680

8460

10545

2 x 1.5

2 x 2.5

2 x 4

2 x 6

2 x 10

2 x 16

2 x 25 (S)

2 x 35 (S)

2 x 50 (S)

2 x 70 (S)

2 x 95 (S)

2 x 120 (S)

2 x 150 (S)

2 x 185 (S)

2 x 240 (S)

2 x 300 (S)

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

0.8

0.8

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

10.4

11.2

13.1

14.2

16.1

18.2

21.8

24.0

23.0

26.0

30.0

32.0

36.0

40.0

44.0

49.0

145

180

255

285

395

590

900

1160

1260

1700

2310

2880

3520

4290

5570

6970

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: PVC Compound Type A

3. Sheath: PVC Compound Type ST1

4. Colour: Insulation: 1 Core - Black

2 Cores- Red & Black

Sheath: 1 Core – Grey

2 Cores - Black

Voltage Uo/U: 600/ 1000V

Conductor Stranding: Class 2 stranded circular or

compacted conductors

Operating Temperature: Maximum 700C

Minimum Bending Radius: 1 Core –

8D for 1.5mm2 to 1000mm2

2 Cores –

8D for 1.5mm2 to 300mm2

Page 5: Catalogue tai sin

5

PVC/ PVC Cables IEC 60502 Table 4

Nominal

Conductor

Area

No. and

Diameter

of Wire

Radial

Thickness

of Insulation

Approx.

Overall

Diameter

Approx.

Weight

(mm2) (no./mm) (mm) (mm) (kg/ km)

3 x 1.5

3 x 2.5

3 x 4

3 x 6

3 x 10

3 x 16

3 x 25 (S)

3 x 35 (S)

3 x 50 (S)

3 x 70 (S)

3 x 95 (S)

3 x 120 (S)

3 x 150 (S)

3 x 185 (S)

3 x 240 (S)

3 x 300 (S)

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

0.8

0.8

1.0

1.0

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

10.9

11.8

13.8

15.0

17.1

19.3

23.2

25.7

26.0

29.0

34.0

37.0

40.0

45.0

51.2

56.0

165

210

305

370

515

740

1160

1520

1750

2435

3360

4140

5070

6330

8265

10355

4 x 1.5

4 x 2.5

4 x 4

4 x 6

4 x 10

4 x 16

4 x 25

4 x 35

4 x 35 (S)

4 x 50 (S)

4 x 70 (S)

4 x 95 (S)

4 x 120 (S)

4 x 150 (S)

4 x 185 (S)

4 x 240 (S)

4 x 300 (S)

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

0.8

0.8

1.0

1.0

1.0

1.0

1.2

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

11.7

12.8

15.0

16.4

18.6

21.2

25.6

28.4

26.0

29.0

33.0

39.0

42.5

47.0

52.0

58.2

65.0

200

255

375

455

665

930

1465

1920

1740

2320

3215

4400

5440

6675

8360

10870

13650

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: PVC Compound Type A

3. Sheath: PVC Compound Type ST1

3. Colour: Insulation: 3 Cores – Red, Yellow, Blue

4 Cores- Red , Yellow, Blue,

Black

Sheath: Black

Voltage Uo/U: 600/ 1000V

Conductor Stranding: Class 2 stranded circular or

compacted conductors

Operating Temperature: Maximum 700C

Minimum Bending Radius: 8D for 1.5mm2 to 300mm2

PVC/ PVC Cables Table 5

No.

of

Nominal

Conductor

No. and

Diameter

Radial

Thickness

Approx.

Overall

Approx.

Weight

Page 6: Catalogue tai sin

6

Cores Area of Wire of Insulation Diameter

(mm2) (no./mm) (mm) (mm) (kg/ km)

2

3

4

5

7

10

12

19

27

37

48

1.5

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

8.8

9.2

10.0

10.8

11.7

14.8

15.2

17.9

21.4

24.0

27.6

109

129

154

190

240

330

385

560

770

1015

1300

2

3

4

5

7

10

12

19

27

37

48

2.5

7/ 0.67

7/ 0.67

7/ 0.67

7/ 0.67

7/ 0.67

7/ 0.67

7/ 0.67

7/ 0.67

7/ 0.67

7/ 0.67

7/ 0.67

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.7

10.0

10.6

11.5

12.7

13.7

17.4

18.0

21.2

25.4

28.6

33.0

148

171

218

270

340

490

560

820

1135

1560

1930

2

3

4

5

7

10

12

19

27

37

48

4

7/ 0.85

7/ 0.85

7/ 0.85

7/ 0.85

7/ 0.85

7/ 0.85

7/ 0.85

7/ 0.85

7/ 0.85

7/ 0.85

7/ 0.85

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

11.5

12.2

13.3

14.7

16.2

20.6

21.3

25.1

30.4

34.2

39.3

205

252

315

415

535

720

850

1260

1740

2300

2900

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: PVC Compound Type TI1

3. Sheath: PVC Compound Type TM1

3. Colour: Insulation: White with Black numberings

Sheath: Black

Voltage Uo/U: 600/ 1000V

Conductor Stranding: Class 2 stranded circular

Operating Temperature: Maximum 700C

Minimum Bending Radius: 3D for D < 10mm

4D for 10mm < D < 25mm

6D for D > 25mm

Page 7: Catalogue tai sin

7

PVC/ AWA/ PVC Cables BS 6346 Table 6

Nominal

Conductor

Area

No. and

Diameter

of Wire

Radial

Thickness

of Insulation

Approx.

Overall

Diameter

Approx.

Weight

(mm2) (no./mm) (mm) (mm) (kg/ km)

50

70

95

120

150

185

240

300

400

500

630

800

1000

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

61/ 2.85

61/ 3.20

127/ 2.52

127/ 2.85

127/ 3.20

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

2.6

2.8

2.8

2.8

3.0

19.1

21.1

23.4

26.3

28.3

30.8

34.1

37.0

42.0

45.6

49.7

55.8

61.0

760

1010

1330

1690

2110

2450

3120

3810

4890

5990

7510

9590

11820

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: PVC Compound Type TI1

3. Bedding: PVC Compound Type TM1

4. Armour: Aluminium Wire

5. Sheath: PVC Compound Type TM1

6. Colour: Insulation: Black

Sheath: Black

Voltage Uo/U: 600/ 1000V

Conductor Stranding: Class 2 stranded circular or

compacted conductors

Operating Temperature: Maximum 700C

Minimum Bending Radius: 6D for 50mm2 to 1000mm2

Page 8: Catalogue tai sin

8

PVC/ SWA/ PVC Cables BS 6346 Table 7

Nominal

Conductor

Area

No. and

Diameter

of Wire

Radial

Thickness

of Insulation

Approx.

Overall

Diameter

Approx.

Weight

(mm2) (no./mm) (mm) (mm) (kg/ km)

2 x 1.5

2 x 2.5

2 x 4

2 x 6

2 x 10

2 x 16

2 x 25

2 x 35

2 x 50 (S)

2 x 70 (S)

2 x 95 (S)

2 x 120 (S)

2 x 150 (S)

2 x 185 (S)

2 x 240 (S)

2 x 300 (S)

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

0.6

0.7

0.8

0.8

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

12.3

13.6

15.1

16.5

20.1

21.9

26.7

29.4

27.4

30.0

34.7

37.2

40.5

45.2

50.0

54.8

270

340

450

550

750

960

1400

1750

1990

2500

2460

4120

4890

6250

7860

9480

3 x 1.5

3 x 2.5

3 x 4

3 x 6

3 x 10

3 x 16

3 x 25

3 x 35

3 x 50 (S)

3 x 70 (S)

3 x 95 (S)

3 x 120 (S)

3 x 150 (S)

3 x 185 (S)

3 x 240 (S)

3 x 300 (S)

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

0.6

0.7

0.8

0.8

1.0

1.0

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

12.8

14.1

15.8

18.0

21.2

23.1

28.2

30.8

30.1

34.2

38.5

41.4

46.3

50.7

56.2

61.6

350

400

520

730

1010

1180

1760

2170

2560

3520

4640

5500

6970

8400

10550

12800

4 x 1.5

4 x 2.5

4 x 4

4 x 6

4 x 10

4 x 16

4 x 25

4 x 35

4 x 35 (S)

4 x 50 (S)

4 x 70 (S)

4 x 95 (S)

4 x 120 (S)

4 x 150 (S)

4 x 185 (S)

4 x 240 (S)

4 x 300 (S)

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

0.6

0.7

0.8

0.8

1.0

1.0

1.2

1.2

1.2

1.4

1.4

1.6

1.6

1.8

2.0

2.2

2.4

13.5

15.0

17.8

19.2

22.8

26.3

30.7

33.7

29.9

34.6

38.4

43.5

48.1

52.4

57.4

64.1

70.4

345

440

710

810

1130

1550

2150

2670

2510

3410

4400

5830

7400

8810

10660

13430

16330

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: PVC Compound Type TI1

3. Bedding: PVC Compound Type TM1 or Lapped PVC Tape 4. Armour: Galvanised Steel Wire

5. Sheath: PVC Compound Type TM1

6. Colour: Insulation: 2 Cores- Red, Black 3 Cores – Red, Yellow, Blue

4 Cores – Red, Yellow, Blue, Black

Sheath: Black

Voltage Uo/U: 600/ 1000V

Conductor Stranding: Class 2 stranded circular or

compacted conductors Operating Temperature: Maximum 700C

Minimum Bending Radius: 6D for 1.5mm2 to 16mm2

8D for 25mm2 and above

PVC/SWA/ PVC Cables BS 6346 Table 8

No. Nominal No. and Radial Approx. Approx.

Page 9: Catalogue tai sin

9

Of

Cores

Conductor

Area

Diameter

of Wire

Thickness

of Insulation

Overall Diameter Weight

(mm2) (no./mm) (mm) (mm) (kg/ km)

5

7

10

12

19

27

37

48

1.5

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

14.3

15.2

19.0

19.4

22.2

26.7

29.2

32.9

357

416

446

716

938

1380

1689

2048

5

7

10

12

19

27

37

48

2.5

7/ 0.67

7/ 0.67

7/ 0.67

7/ 0.67

7/ 0.67

7/ 0.67

7/ 0.67

7/ 0.67

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.7

16.3

18.0

21.9

22.4

26.6

30.7

34.0

39.5

465

557

878

955

1455

1885

2340

3190

5

7

10

12

19

27

37

48

4

7/ 0.85

7/ 0.85

7/ 0.85

7/ 0.85

7/ 0.85

7/ 0.85

7/ 0.85

7/ 0.85

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

19.0

20.5

26.1

26.8

30.5

37.1

40.8

46.0

750

905

1405

1530

2060

3025

3900

4800

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: PVC Compound Type TI1

3. Bedding: PVC Compound Type TM1

or Lapped PVC Tape

4. Armour: Galvanised Steel Wire

5. Sheath: PVC Compound Type TM1

6. Colour: Insulation:White with Black numberings

Sheath: Black

Voltage Uo/U: 600/ 1000V

Conductor Stranding: Class 2 stranded circular or

compacted conductors

Operating Temperature: Maximum 700C

Minimum Bending Radius: 6D for 1.5mm2 to 4mm2

Page 10: Catalogue tai sin

10

Flexible Cable, Circular Sheathed, Metric Unit BS 6500 Table 9.1

Conductor Thickness

of

Insulation

2 Cores

Nominal

Area Construction

Approx.

Overall Diameter

Approx.

Net Weight

(mm2) (no./mm) (mm) (mm) (kg/ km)

0.5

0.75

1.0

1.25

1.5

2.5

4.0

16/ 0.20

24/ 0.20

32/ 0.20

40/ 0.20

30/ 0.25

50/ 0.25

56/ 0.30

0.6

0.6

0.6

0.7

0.7

0.8

0.8

6.1

6.6

6.9

7.6

7.8

9.6

11.0

55

65

75

80

90

135

135

Flexible Cable, Circular Sheathed, Metric Unit BS 6500 Table 9.2

Conductor Thickness

of

Insulation

2 Cores

Nominal

Area Construction

Approx.

Overall Diameter

Approx.

Net Weight

(mm2) (no./mm) (mm) (mm) (kg/ km)

0.5

0.75

1.0

1.25

1.5

2.5

4.0

16/ 0.20

24/ 0.20

32/ 0.20

40/ 0.20

30/ 0.25

50/ 0.25

56/ 0.30

0.6

0.6

0.6

0.7

0.7

0.8

0.8

6.5

6.9

7.3

8.3

8.5

10.4

11.8

60

75

85

100

110

170

215

Flexible Cable, Circular Sheathed, Metric Unit BS 6500 Table 9.3

Conductor Thickness

of

Insulation

2 Cores

Nominal

Area Construction

Approx.

Overall Diameter

Approx.

Net Weight

(mm2) (no./mm) (mm) (mm) (kg/ km)

0.5

0.75

1.0

1.25

1.5

2.5

4.0

16/ 0.20

24/ 0.20

32/ 0.20

40/ 0.20

30/ 0.25

50/ 0.25

56/ 0.30

0.6

0.6

0.6

0.7

0.7

0.8

0.8

7.1

7.6

8.2

-

9.5

11.4

12.9

75

90

110

-

140

205

275

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation : PVC Compound Type TI2

3. Assembly : 2, 3 or 4 Cores are Twisted Together

4. Sheath : PVC Compound Type TM2

Voltage Uo/U: 300/ 500V

Conductor Stranding: Class 5

Operating Temperature: 700

Page 11: Catalogue tai sin

11

Flexible Cord, Twin Twisted Non- Sheated, Imperial Unit BS 2004 Table 10.1

Conductor Thickness

of

Insulation

Twin Twisted

Nominal

Area Construction

Approx.

Overall Diameter

Approx.

Net Weight

(mm2) (no./in) (mm) (mm) (kg/ 100y)

0.41

0.67

1.17

14/ 0.0076

23/ 0.0076

40/ 0.0076

0.64

0.64

0.64

2.1

2.4

2.7

1.7

2.3

3.1

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation : PVC Compound Type TI1

3. Assembly : Two Cores Twisted

Voltage Uo/U: 250/ 440V

Conductor Stranding: Class 5

Operating Temperature: 700

Flexible Cable, Circular Sheathed, Imperial Unit BS 2004 Table 10.2

Conductor Thickness

of

Insulation

1 Core 2 Cores

Nominal

Area Construction

Approx.

Overall Diameter

Approx.

Net Weight

Approx.

Overall Diameter

Approx.

Net Weight

(mm2) (mm) (mm) (mm) (kg/ 100y) (mm) (kg/ 100y)

0.41

0.67

1.17

2.05

3.22

4.74

14/ 0.0076

23/ 0.0076

40/ 0.0076

70/ 0.0076

110/ 0.0076

162/ 0.0076

0.64

0.64

0.64

0.64

0.64

0.76

4.2

4.4

4.8

5.2

5.7

6.4

2.1

2.5

3.2

4.2

5.4

7.3

6.3

6.8

7.5

9.0

10.0

11.3

4.8

6.0

7.5

10.0

12.9

17.4

Flexible Cable, Circular Sheathed, Imperial Unit BS 2004 Table 10.3

Conductor Thickness

of

Insulation

3 Cores 4 Cores

Nominal

Area Construction

Approx.

Overall Diameter

Approx.

Net Weight

Approx.

Overall Diameter

Approx.

Net Weight

(mm2) (mm) (mm) (mm) (kg/ 100y) (mm) (kg/ 100y)

0.41

0.67

1.17

2.05

3.22

4.74

14/ 0.0076

23/ 0.0076

40/ 0.0076

70/ 0.0076

110/ 0.0076

162/ 0.0076

0.64

0.64

0.64

0.64

0.64

0.76

6.6

7.1

7.9

9.5

10.5

12.2

5.6

6.2

8.9

12.7

16.6

22.9

7.2

7.7

9.2

10.3

11.4

13.2

6.2

7.9

10.0

15.4

20.4

28.3

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation : PVC Compound Type TI1

3. Assembly : 1, 2, 3 or 4 Cores Twisted Togeher

4. Sheath: PVC Compound Type T6

Voltage Uo/U: 250/ 440V

Conductor Stranding: Class 5

Operating Temperature: 700

Page 12: Catalogue tai sin

12

XLPE/ PVC & XLPE/ AWA/ PVC Cables IEC 60502 Table 11

Nominal

Conductor

Area

No. and

Diameter

of

Wire

Radial

Thickness

of Insulation

XP XAP

Cable Overall

Diameter

Approx.

Weight

Diameter

Under Armour

Armour Wire

Diameter

Cable Overall

Diameter

Approx.

Weight

(mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)

16

25

35

50

70

95

120

150

185

240

300

400

500

630

800

1000

7/ 1.70

7/ 2.14

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

61/ 2.85

61/ 3.20

127/ 2.52

127/ 2.85

127/ 3.20

0.7

0.9

0.9

1.0

1.1

1.1

1.2

1.4

1.6

1.7

1.8

2.0

2.2

2.4

2.6

2.8

9.6

11.3

12.5

14.0

16.1

18.2

20.0

22.2

24.4

27.5

30.3

33.9

37.6

42.4

47.3

52.4

205

309

412

540

760

1020

1270

1560

1930

2510

3120

3970

4980

6400

8190

10265

-

10.6

11.8

13.3

15.4

17.3

19.1

21.0

23.3

26.1

28.7

32.1

35.7

40.4

45.1

50.1

-

0.9

0.9

1.25

1.25

1.25

1..6

1.60

1.60

1.6

1.6

2.0

2.0

2.0

2.5

2.5

-

16.0

17.2

19.4

21.5

23.4

25.9

27.9

30.1

33.2

35.8

40.9

44.6

49.2

55.7

61.0

-

470

581

800

960

1240

1650

1970

2390

3040

3790

4790

5880

7400

9500

11750

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: XLPE Compound

3. Bedding: PVC Compound Type ST2

4. Armour: Aluminium Wire

5. Sheath: PVC Compound Type ST2

6. Colour: Insulation: Natural

Sheath: Black

Voltage Uo/U: 600/ 1000V

Conductor Stranding: Class 2 stranded circular or compacted

conductors

Operating Temperature: Maximum 900C

Minimum Bending Radius: Unarmoured:

8D for 16mm2 to 1000mm2

Armoured:

10D for 25mm2 to 1000mm2

Page 13: Catalogue tai sin

13

XLPE/ PVC & XLPE/ SWA/ PVC Cables IEC 60502 Table 12

Nominal

Conductor

Area

No. and

Diameter

of

Wire

Radial

Thickness

of Insulation

XP XSP

Cable Overall

Diameter

Approx.

Weight

Diameter

Under Armour

Armour Wire

Diameter

Cable Overall

Diameter

Approx.

Weight

(mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)

2 x 1.5

2 x 2.5

2 x 4

2 x 6

2 x 10

2 x 16

2 x 25

2 x 35

2 x 50 (S)

2 x 70 (S)

2 x 95 (S)

2 x 120 (S)

2 x 150 (S)

2 x 185 (S)

2 x 240 (S)

2 x 300 (S)

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

0.7

0.7

0.7

0.7

0.7

0.7

0.9

0.9

1.0

1.1

1.1

1.2

1.4

1.6

1.7

1.8

10.0

10.8

11.9

13.0

14.9

17.0

20.4

22.7

21.0

24.0

26.9

29.9

33.4

37.1

45.0

50.0

130

165

210

270

390

450

820

1065

1140

1560

2130

2640

3270

4040

5150

6560

8.5

9.3

10.4

11.5

13.4

15.5

18.9

21.2

19.2

22.3

25.3

28.1

30.9

36.0

41.6

47.4

0.9

0.9

0.9

0.9

1.25

1.25

1.6

1.6

1.6

1.6

2.0

2.0

2.0

2.0

2.5

2.5

13.9

14.7

15.8

16.9

19.5

21.6

25.7

28.0

26.0

29.5

33.5

36.5

39.5

45.0

52.0

58.0

350

400

475

560

810

980

1410

1930

1880

2420

3360

3980

4730

6245

8720

9390

3 x 1.5

3 x 2.5

3 x 4

3 x 6

3 x 10

3 x 16

3 x 25

3 x 35

3 x 50 (S)

3 x 70 (S)

3 x 95 (S)

3 x 120 (S)

3 x 150 (S)

3 x 185 (S)

3 x 240 (S)

3 x 300 (S)

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

0.7

0.7

0.7

0.7

0.7

0.7

0.9

0.9

1.0

1.1

1.1

1.2

1.4

1.6

1.7

1.8

10.5

11.4

12.5

13.8

15.8

18.0

21.7

24.2

25.0

29.0

32.0

36.5

39.0

44.0

49.0

55.0

150

195

255

330

490

700

1000

1300

1600

2240

3050

3800

4640

5870

7670

9460

9.0

9.9

11.0

12.3

14.3

16.5

20.2

23.0

23.0

27.0

30.1

34.4

37.5

41.3

46.4

52.0

0.9

0.9

0.9

0.9

1.25

1.25

1.6

1.6

1.6

2.0

2.0

2.0

2.5

2.5

2.5

2.5

14.4

15.3

16.4

17.7

20.4

22.6

27.0

29.8

30.0

35.0

38.5

43.0

47.5

51.5

57.0

36.0

390

450

540

745

950

1250

1840

2280

2550

3500

4500

5700

6800

8200

10300

12500

4 x 1.5

4 x 2.5

4 x 4

4 x 6

4 x 10

4 x 16

4 x 25

4 x 35

4 x 35 (S)

4 x 50 (S)

4 x 70 (S)

4 x 95 (S)

4 x 120 (S)

4 x 150 (S)

4 x 185 (S)

4 x 240 (S)

4 x 300 (S)

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

0.7

0.7

0.7

0.7

0.7

0.7

0.9

0.9

0.9

1.0

1.1

1.1

1.2

1.4

1.6

1.7

1.8

11.3

12.3

13.6

15.0

17.2

19.7

23.9

26.6

25.0

28.5

32.0

37.0

42.0

46.0

50.0

55.0

36.0

175

225

305

405

600

870

1325

1760

1600

2200

3050

4070

5195

6350

7890

10400

12810

10.0

10.8

12.1

13.5

15.7

18.2

22.4

15.1

24.0

26.8

30.6

34.4

36.0

38.3

46.4

51.0

56.6

0.9

0.9

0.9

1.25

1.25

1.6

1.6

1.6

1.6

1.6

2.0

2.0

2.5

2.5

2.5

2.5

2.5

15.4

16.2

17.5

19.6

21.8

25.0

29.2

32.1

31.0

34.0

39.0

43.0

46.0

48.5

57.0

62.0

68.0

430

505

710

855

1120

1600

2160

2750

2500

3100

4400

5610

7400

8300

10400

13000

15900

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: XLPE Compound 3. Bedding: PVC Compound Type ST2 or Lapped PVC Tape

4. Armour: Galvanised Steel Wire

5. Sheath: PVC Compound Type ST2 6. Colour: Insulation: 2 Cores - Red, Black

3 Cores – Red, Yellow, Blue

4 Cores – Red, Yellow, Blue, Black Sheath: Black

Voltage Uo/U: 600/ 1000V

Conductor Stranding: Class 2 stranded circular or compacted conductors

Operating Temperature: Maximum 900C

Minimum Bending Radius: Unarmoured: 6D for 1.5mm2 to 300mm2

Armoured:

8D for 1.5mm2 to 300mm2

Page 14: Catalogue tai sin

14

XLPE/ PVC & XLPE/ SWA/ PVC Cables IEC 60502 Table 13

No.

of

Cores

Nominal

Conductor

Area

No. and

Diameter

of Wire

Radial

Thickness

of Insulation

XP XSP

Cable

Overall

Diameter

Approx.

Weight

Diameter

Under

Armour

Armour

Wire

Diameter

Cable

Overall

Diameter

Approx.

Weight

(mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)

5

7

12

19

37

1.5

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

0.7

0.7

0.7

0.7

0.7

11.9

12.9

16.5

19.4

25.4

214.5

235.5

391.1

522.0

981.0

10.5

11.5

15.1

17.7

23.3

0.9

0.9

1.25

1.25

1.6

15.9

16.9

21.2

23.8

30.1

493.9

560.7

903.9

1167.8

1872.0

5

7

12

19

37

2.5

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

0.7

0.7

0.7

0.7

0.7

13.1

14.1

18.4

21.4

18.4

280.4

317.5

500.0

737.0

1327.0

11.7

12.7

16.8

19.8

27.0

0.9

0.9

1.25

1.6

1.6

17.1

18.1

22.9

26.6

33.8

586.8

676.1

1095.8

1593.2

2361.0

5

7

12

19

37

4

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

0.7

0.7

0.7

0.7

0.7

14.5

16.0

20.6

24.1

32.2

381.6

470.0

709.0

1051.0

1989.0

13.1

14.3

18.6

22.0

30.1

1.25

1.25

1.25

1.6

1.6

19.2

20.4

24.7

28.8

36.9

823.0

906.0

1293.0

1904.0

2919.0

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: XLPE Compound

3. Bedding: PVC Compound Type ST2 or

Lapped PVC Tape

4. Armour: Galvanised Steel Wire

5. Sheath: PVC Compound Type ST2

6. Colour: Insulation:White with Black numberings

Sheath: Black

Voltage Uo/U: 600/ 1000V

Conductor Stranding: Class 2 stranded circular

Operating Temperature: Maximum 900C

Minimum Bending Radius: Unarmoured:

6D for 1.5mm2 to 4mm2

Armoured:

8D for 1.5mm2 to 4mm2

Page 15: Catalogue tai sin

15

IN-POP & IN-POSP Cables Table 14

SIZE IN-POP IN-POSP

Nominal

Conductor

Area

No. and

Diameter

of Wire

Radial

Thickness

of Insulation

Unarmoured Armoured

Cable Overall

Diameter

Approx.

Weight

Diameter

Under Armour

Armour Wire

Diameter

Cable Overall

Diameter

Approx.

Weight

(mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)

2C x 0.5

3C x 0.5

4C x 0.5

6C x 0.5

10C x 0.5

20C x 0.5

40C x 0.5

80C x 0.5

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

7.0

7.3

7.9

9.3

11.9

14.9

20.1

26.3

60

68

78

110

170

295

510

950

7.0

7.3

7.9

9.3

11.9

14.9

20.1

26.3

0.90

0.90

0.90

0.90

0.90

1.25

1.60

1.60

11.4

11.7

12.3

13.9

16.7

20.6

26.7

33.3

250

265

290

360

490

800

1300

2050

2C x 0.75

3C x 0.75

4C x 0.75

6C x 0.75

10C x 0.75

20C x 0.75

40C x 0.75

80C x 0.75

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

7.3

7.7

8.3

9.9

12.7

16.0

21.7

28.5

65

78

92

128

200

355

640

1185

7.3

7.7

8.3

9.9

12.7

16.0

21.7

28.5

0.90

0.90

0.90

0.90

0.90

1.25

1.60

1.60

11.7

12.1

12.9

14.5

17.5

21.7

28.5

35.7

260

280

320

400

550

905

1500

2420

2C x 1.5

3C x 1.5

4C x 1.5

6C x 1.5

10C x 1.5

20C x 1.5

40C x 1.5

80C x 1.5

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

8.3

8.9

9.7

11.7

14.7

18.7

24.6

33.6

90

115

140

200

315

560

1040

1970

8.3

8.9

9.7

11.7

14.7

18.7

24.6

33.6

0.90

0.90

0.90

0.90

1.25

1.60

1.60

2.00

12.9

13.5

14.3

16.3

20.4

25.3

31.6

41.8

310

360

400

515

820

1340

2090

3690 Pair configurations are available upon request

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: PVC Compound Type TI1

3. Lay Up: Cores are stranded in Reverse Layer

Technique forming a Concentric Cable

4. Wrap film: Polyster Binder Tape

5. Collective: Aluminium/ Polyster Tape, with a Tinned

Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm)

6. Bedding : PVC Compound Type TM1

(optional)

7. Armouring: Galvanised Steel Wire

(optional)

Reference standards: BS 5308 Part 2

Voltage Uo/U: 300/ 500V

Conductor Stranding: Class 2 and 5

Operating Temperature: 700C

Testing Voltage: 1KV/ 1 Minute

8. Sheath: PVC Compound Type TM1

9. Colour: Insulation: Yellow with Black numberings

or refer to colour code

Sheath: Black

Page 16: Catalogue tai sin

16

IN-POP & IN-POSP Cables Table 15

SIZE IN-POP IN-POSP

Nominal

Conductor

Area

No. and

Diameter

of Wire

Radial

Thickness

of Insulation

Unarmoured Armoured

Cable Overall

Diameter

Approx.

Weight

Diameter

Under Armour

Armour Wire

Diameter

Cable Overall

Diameter

Approx.

Weight

(mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)

1P x 0.5

2P(Quad) x 0.5

5P x 0.5

10P x 0.5

15P x 0.5

20P x 0.5

30P x 0.5

50P x 0.5

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

7.0

7.9

13.1

17.2

19.8

22.3

26.9

33.9

60

78

185

310

430

540

780

1240

7.0

7.9

13.1

17.2

19.8

22.3

26.9

33.9

0.90

0.90

0.90

1.25

1.60

1.60

1.60

2.00

11.4

12.3

17.9

22.9

26.4

29.1

33.9

42.1

250

290

540

905

1270

1490

1960

3000

1P x 0.75

2P(Quad) x 0.75

5P x 0.75

10P x 0.75

15P x 0.75

20P x 0.75

30P x 0.75

50P x 0.75

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

7.3

8.3

14.3

18.7

21.4

24.5

29.5

37.4

68

92

230

390

530

690

1010

1610

7.3

8.3

14.3

18.7

21.4

24.5

29.5

37.4

0.90

0.90

1.25

1.60

1.60

1.60

2.00

2.00

11.7

12.9

19.8

25.3

28.2

31.3

37.5

45.8

260

325

710

1170

1460

1750

2560

3550

1P x 1.5

2P(Quad) x 1.5

5P x 1.5

10P x 1.5

15P x 1.5

20P x 1.5

30P x 1.5

50P x 1.5

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

8.3

9.7

16.4

21.6

25.2

28.5

34.3

43.6

90

142

330

580

860

1090

1600

2570

8.3

9.7

16.4

21.6

25.2

28.5

34.3

43.6

0.90

0.90

1.25

1.60

1.60

1.60

2.00

2.50

12.9

14.3

22.1

28.4

32.2

35.7

42.5

53.4

310

410

900

1510

1950

2330

3400

5320 Pair configurations are available upon request

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: PVC Compound Type TI1

3. Lay Up: Cores are paired, pairs are twisted in

Reverse Layer Technique forming a

Concentric Cable

4. Wrap Film: Polyster Binder Tape

5. Collective: Aluminium/ Polyster Tape, with a Tinned

Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm)

6. Bedding : PVC Compound Type TM1

(optional)

7. Armouring: Galvanised Steel Wire

(optional)

Reference standards: BS 5308 Part 2

Voltage Uo/U: 300/ 500V

Conductor Stranding: Class 2 and 5

Operating Temperature: 700C

Testing Voltage: 1KV/ 1 Minute

8. Sheath: PVC Compound Type TM1

9. Colour: Insulation:White and Black numberings

or refer to colour code

Sheath: Black

Page 17: Catalogue tai sin

17

IN-POP & IN-POSP Cables Table 16

SIZE IN-PIOP IN-PIOSP

Nominal

Conductor

Area

No. and

Diameter

of Wire

Radial

Thickness

of Insulation

Unarmoured Armoured

Cable Overall

Diameter

Approx.

Weight

Diameter

Under Armour

Armour Wire

Diameter

Cable Overall

Diameter

Approx.

Weight

(mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)

2P x 0.5

5P x 0.5

10P x 0.5

15P x 0.5

20P x 0.5

30P x 0.5

50P x 0.5

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

12.0

15.2

21.1

24.5

27.3

32.3

41.7

135

240

410

590

750

1090

1780

12.0

15.2

21.1

24.5

27.3

32.3

41.7

0.90

1.25

1.60

1.60

1.60

2.00

2.50

16.8

20.9

27.9

31.3

34.3

40.5

51.5

470

770

1320

1640

1910

2740

4400

2P x 0.75

5P x 0.75

10P x 0.75

15P x 0.75

20P x 0.75

30P x 0.75

50P x 0.75

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

12.8

16.3

22.7

26.4

29.8

35.5

45.0

155

275

480

700

900

1310

2060

12.8

16.3

22.7

26.4

29.8

35.5

45.0

0.90

1.25

1.60

1.60

2.00

2.00

2.50

17.6

22.0

29.5

33.4

37.8

43.9

55.0

505

850

1450

1830

2430

3190

4970

2P x 1.5

5P x 1.5

10P x 1.5

15P x 1.5

20P x 1.5

30P x 1.5

50P x 1.5

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

14.7

18.8

26.5

30.8

34.4

41.0

52.2

215

400

740

1060

1340

1970

3130

14.7

18.8

26.5

30.8

34.4

41.0

52.2

1.25

1.60

1.60

2.00

2.00

2.50

2.50

20.4

25.4

33.5

38.8

42.6

50.8

62.6

730

1200

1860

2660

3100

4550

6420

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: PVC Compound Type TI1

3. Lay Up: Cores are paired, pairs are twisted in Reverse

Layer Technique forming a

Concentric Cable

4. Individual: Aluminium/ Polyester Tape, with a Tinned

Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm)

5. Wrap Film: Polyster Binder Tape

6. Collective: Aluminium/ Polyster Tape, with a Tinned

Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm)

7. Bedding : PVC Compound Type TM1

(optional)

Reference standards: BS 5308 Part 2

Voltage Uo/U: 300/ 500V

Conductor Stranding: Class 2 and 5

Operating Temperature: 700C

Testing Voltage: 1KV/ 1 Minute

8. Armouring: Galvanised Steel Wire

(optional)

9. Sheath: PVC Compound Type TM110. Colour:

10. Colour: Insulation: White and Black numberings

or refer to colour code

Sheath: Black

Page 18: Catalogue tai sin

18

IN-EOP & IN-EOSP Cables Table 17

SIZE IN-EOP IN-EOSP

Nominal

Conductor

Area

No. and

Diameter

of Wire

Radial

Thickness

of Insulation

Unarmoured Armoured

Cable Overall

Diameter

Approx.

Weight

Diameter

Under Armour

Armour Wire

Diameter

Cable Overall

Diameter

Approx.

Weight

(mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)

1P x 0.5

2P(Quad) x 0.5

5P x 0.5

10P x 0.5

15P x 0.5

20P x 0.5

30P x 0.5

50P x 0.5

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

7.0

7.9

13.1

17.2

19.8

22.3

26.9

33.9

56

70

170

280

385

480

690

1080

7.0

7.9

13.1

17.2

19.8

22.3

26.9

33.9

0.90

0.90

0.90

1.25

1.60

1.60

1.60

2.00

11.4

12.3

17.9

22.9

26.4

29.1

33.9

42.1

230

270

500

830

1150

1360

1750

2730

1P x 0.75

2P(Quad) x 0.75

5P x 0.75

10P x 0.75

15P x 0.75

20P x 0.75

30P x 0.75

50P x 0.75

7/ 0.43

7/ 0.43

7/ 0.43

7/ 0.43

7/ 0.43

7/ 0.43

7/ 0.43

7/ 0.43

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

7.4

8.4

14.2

18.4

21.3

24.4

29.0

37.3

68

95

230

385

540

705

995

1630

7.4

8.4

14.2

18.4

21.3

24.4

29.0

37.3

0.90

0.90

1.25

1.25

1.60

1.60

1.60

2.00

11.8

13.0

19.7

24.3

28.1

31.2

36.2

45.7

250

310

680

980

1380

1650

2150

3430

1P x 1.5

2P(Quad) x 1.5

5P x 1.5

10P x 1.5

15P x 1.5

20P x 1.5

30P x 1.5

50P x 1.5

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

8.3

9.7

16.4

21.6

25.2

28.5

34.3

43.6

85

132

315

550

790

1000

1460

2340

8.3

9.7

16.4

21.6

25.2

28.5

34.3

43.6

0.90

0.90

1.25

1.60

1.60

1.60

2.00

2.50

12.9

14.3

22.1

28.4

32.2

35.7

42.5

53.4

290

380

840

1410

1790

2150

3100

4920 Pair configurations are available upon request

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: PVC Compound Type TI1

3. Lay Up: Cores are paired, pairs are twisted in Reverse

Layer Technique forming a Concentric Cable

4. Wrap Film: Polyster Binder Tape

5. Collective: Aluminium/ Polyster Tape, with a Tinned

Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm)

6. Bedding : Polyethylene Compound Type 03

(optional)

7. Armouring: Galvanised Steel Wire

(optional)

Reference standards: BS 5308 Part 1

Voltage Uo/U: 300/ 500V

Conductor Stranding: Class 2 and 5

Operating Temperature: 650C

Testing Voltage: 1KV/ 1 Minute

8. Sheath: PVC Compound Type TM1

9. Colour: Insulation: White and Black numberings

or refer to colour code

Sheat: Black

Page 19: Catalogue tai sin

19

IN-EOP & IN-EOSP Cables Table 18

SIZE IN-EOP IN-EOSP

Nominal

Conductor

Area

No. and

Diameter

of Wire

Radial

Thickness

of Insulation

Unarmoured Armoured

Cable Overall

Diameter

Approx.

Weight

Diameter

Under Armour

Armour Wire

Diameter

Cable Overall

Diameter

Approx.

Weight

(mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)

2P x 0.5

5P x 0.5

10P x 0.5

15P x 0.5

20P x 0.5

30P x 0.5

50P x 0.5

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

16/ 0.2

0.6

0.6

0.6

0.6

0.6

0.6

0.6

12.0

15.2

21.1

24.5

27.3

32.3

41.7

130

230

400

560

690

990

1610

12.0

15.2

21.1

24.5

27.3

32.3

41.7

0.90

1.25

1.60

1.60

1.60

2.00

2.50

16.8

20.9

27.9

31.3

34.3

40.5

51.5

430

720

1240

1530

1770

2550

4080

2P x 0.75

5P x 0.75

10P x 0.75

15P x 0.75

20P x 0.75

30P x 0.75

50P x 0.75

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

24/ 0.2

0.6

0.6

0.6

0.6

0.6

0.6

0.6

12.8

16.3

22.7

26.4

29.8

35.5

45.0

155

285

500

720

930

1350

2130

12.8

16.3

22.7

26.4

29.8

35.5

45.0

0.90

1.25

1.60

1.60

2.00

2.00

2.50

17.6

21.9

29.4

33.2

37.8

43.8

54.9

480

800

1400

1760

2350

3060

4800

2P x 1.5

5P x 1.5

10P x 1.5

15P x 1.5

20P x 1.5

30P x 1.5

50P x 1.5

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

7/ 0.53

0.6

0.6

0.6

0.6

0.6

0.6

0.6

14.7

18.8

26.5

30.8

34.4

41.0

52.2

210

380

690

990

1240

1820

2890

14.7

18.8

26.5

30.8

34.4

41.0

52.2

1.25

1.60

1.60

2.00

2.00

2.50

2.50

20.4

25.4

33.5

38.8

42.6

50.8

62.6

670

1110

1750

2460

2910

4250

6040

Pair configurations are available upon request

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: Polyethylene Compound Type 03

3. Lay Up: Cores are paired, pairs are twisted in

Reverse Layer Technique forming

a Concentric Cable

4. Individual: Aluminium/ Polyester Tape, with a Tinned

Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm)

5. Wrap Film: Polyster Binder Tape

6. Collective: Aluminium/ Polyster Tape, with a Tinned

Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm)

7. Bedding : Polyethylene Compound Type 03

(optional)

Reference standards: BS 5308 Part 1

Voltage Uo/U: 300/ 500V

Conductor Stranding: Class 2 and 5

Operating Temperature: 650C

Testing Voltage: 1KV/ 1 Minute

8. Armouring: Galvanised Steel Wire

(optional)

9. Sheath: PVC Compound Type TM1

10. Colour: Insulation:White and Black numberings

or refer to colour code

Sheat: Black

Page 20: Catalogue tai sin

20

XLPE/ CT/ AWA/ PVC Cables IEC 60502 Table 19

Nominal

Conductor

Area

No. and

Diameter

of Wire

Radial

Thickness

of Insulation

Approximate Diameter

Approx.

Weight Under

Screen

Over

Bedding

Over

Armour

Over

All

(mm2) (no./mm) (mm) (mm) (mm) (mm) (mm) (kg/ km)

70

95

120

150

185

240

300

400

500

630

800

1000

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

61/ 2.85

61/ 3.20

127/ 2.52

127/ 2. 85

127/ 3.20

1.1

1.1

1.2

1.4

1.6

1.7

1.8

2.0

2.2

2.4

2.6

2.8

15.2

17.1

19.0

21.0

23.2

26.1

28.7

32.5

36.0

40.4

45.5

50.4

17.6

19.5

20.8

22.8

25.0

27.9

30.5

34.3

37.8

42.2

47.3

52.2

20.1

22.0

24.0

26.0

28.2

31.1

33.7

38.3

41..8

46.2

52.3

57.2

23.9

25.8

27.8

29.8

32.0

35.1

37.9

42.7

46.4

51.0

57.5

62.4

1400

1700

2000

2400

2800

3500

4200

5400

6500

8200

10400

13000

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: XLPE Compound

3. Bedding: PVC Compound Type ST2 or

Lapped PVC Tape

4. Screen: Copper Tape

5. Armour: Aluminium Wire

6. Sheath: PVC Compound Type ST2

7. Colour: Insulation: Natural

Sheath: Black

Voltage Uo/U: 600/ 1000V

Conductor Stranding: Class 2 stranded circular or

compacted conductors

Operating Temperature: Maximum 900C

Minimum Bending Radius: 12D for 70mm2 to 1000mm2

Page 21: Catalogue tai sin

21

XLPE/ CT/ SWA/ PVC Cables IEC 60502 Table 20

Nominal

Conductor

Area

No. and

Diameter

of Wire

Radial

Thickness

of Insulation

Approximate Diameter

Approx.

Weight Under

Screen

Over

Bedding

Over

Armour

Over

All

(mm2) (no./mm) (mm) (mm) (mm) (mm) (mm) (kg/ km)

4 x 1.5

4 x 2.5

4 x 4

4 x 6

4 x 10

4 x 16

4 x 25

4 x 35 (S)

4 x 50 (S)

4 x 70 (S)

4 x 95 (S)

4 x 120 (S)

4 x 150 (S)

4 x 185 (S)

4 x 240 (S)

4 x 300 (S)

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

0.7

0.7

0.7

0.7

0.7

0.7

0.9

0.9

1.0

1.1

1.1

1.2

1.4

1.6

1.7

1.8

9.7

10.7

12.0

13.4

15.6

18.1

22.3

25.0

27.8

31.6

35.4

39.0

42.0

47.8

54.0

58.0

12.1

13.1

14.4

15.8

18.0

20.5

24.1

26.8

29.6

33.4

37.2

40.8

43.8

49.6

55.8

59.8

13.9

14.9

16.2

18.3

20.5

23.7

27.3

30.0

32.8

37.4

41.2

45.8

48.8

54.6

60.8

64.8

17.7

18.7

20.0

22.1

24.3

27.5

31.1

33.8

37.0

42.0

46.0

51.0

54.2

60.4

67.0

71.4

640

730

870

1180

1490

2070

2790

2940

3500

5000

6300

8200

9600

11500

14400

17200

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: XLPE Compound

3. Bedding: PVC Compound Type ST2 or

Lapped PVC Tape

4. Screen: Copper Tape

5. Armour: Galvanised Steel Wire

6. Sheath: PVC Compound Type ST2

7. Colour: Insulation: Red, Yellow, Blue, Green/ Yellow

Sheath: Black

Voltage Uo/U: 600/ 1000V

Conductor Stranding: Class 2 stranded circular or

compacted conductors

Operating Temperature: Maximum 900C

Minimum Bending Radius: 12D for 1.5mm2 to 300mm2

Page 22: Catalogue tai sin

22

XLPE/ CT/ PVC Cables IEC 60502 Table 21

Nominal

Conductor

Area

No. and

Diameter

of Wire

Combined

Earth

Size

Radial

Thickness

of Insulation

Radial

Thickness

of Sheath

Unarmoured

Cable Overall

Diameter

Approx.

Weight

(mm2) (no./mm) (mm) (mm) (mm) (mm) (kg/ km)

3 x 1.5

3 x 2.5

3 x 4

3 x 6

3 x 10

3 x 16

3 x 25

3 x 35

3 x 50 (S)

3 x 70 (S)

3 x 95 (S)

3 x 120 (S)

3 x 150 (S)

3 x 185 (S)

3 x 240 (S)

3 x 300 (S)

7/ 0.53

7/ 0.67

7/ 0.85

7/ 1.04

7/ 1.35

7/ 1.70

7/ 2.14

7/ 2.52

19/ 1.78

19/ 2.14

19/ 2.52

37/ 2.03

37/ 2.25

37/ 2.52

61/ 2.25

61/ 2.52

4.5 (3 x 1.5)

4.5 (3 x 1.5)

4.5 (3 x 1.5)

7.5 (3 x 2.5)

12 (3 x 4)

18 (3 x 6)

30 (3 x 10)

30 (3 x 10)

30 (3 x 10)

48 (3 x 16)

48 (3 x 16)

75 (3 x 25)

75 (3 x 25)

105 (3 x 35

150 (3 x 50)

150 (3 x 50)

0.7

0.7

0.7

0.7

0.7

0.7

0.9

0.9

1.0

1.1

1.1

1.2

1.4

1.6

1.7

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.9

2.0

2.2

2.3

2.5

2.6

2.8

3.0

13.6

14.8

15.8

16.9

18.6

20.8

24.0

25.6

31.1

34.6

39.3

44.0

49.0

54.0

61.0

67.0

325

380

440

550

750

1000

1470

1890

2300

3200

4200

5400

6400

7900

10200

1230

Construction Technical Data

1. Conductor : Plain Annealed Copper

2. Insulation: XLPE Compound

3. Screen: Copper Tape

4. Sheath: PVC Compound Type ST2

5. Colour: Insulation: Red, Yellow, Blue,

Green/ Yellow (x3)

Sheath: Black

Voltage Uo/U: 600/ 1000V

Conductor Stranding: Class 2

Operating Temperature: Maximum 900C for XLPE

Maximum 1100C for XLEVA

Minimum Bending Radius: 10D for unarmoured cable

Page 23: Catalogue tai sin

23

Schedule of Installation Methods of Cables (Including Reference Method) Technical Table 1.1

Installation Method Examples

Appropriate Reference Methoad For

Determining Current- Carrying Capacity Description

OPEN AND CLIPPED DIRECT:

Sheathed cables clipped direct to or lying on

a non- metallic surface

Method 1

CABLES EMBEDDED DIRECT IN BUILDING MATERIALS:

Sheathed cables embedded directly in

masonry, brickwork, concrete, plaster or the

like (other than thermally insulating

materials)

Method 1

IN CONDUIT:

Single core non- sheathed cables in metallic

or non- metallic conduit on a wall or ceiling

Method 3

Single core non- sheathed cables in

metallic or non- metallic conduit in a

thermally insulating ceiling, the conduit

being in contact with a thermally conductive

surface on one side

Method 4

Multi core cables having non- metallic

sheath, in metallic or non- metallic conduit

on a wall or ceiling

Method 3

The wall is assumed to consist of an outer weatherproof skin, thermal insulation and an inner skin of plasterboard of wood- like material

having a coefficient of heat transfer not less than 10 W/m2K. The conduit is fixed so as to be close to, but not necessarily touching, the

inner skin. Heat from the cables is assumed ti escape through the inner skin only.

Page 24: Catalogue tai sin

24

Schedule of Installation Methods of Cables (Including Reference Method) Technical Table 1.2

Installation Method Examples

Appropriate Reference Methoad For

Determining Current- Carrying Capacity Description

ON TRAYS:

Sheathed cables on a perforated cable tray,

bunched and unenclosed. A pertorated cable

tray is considerd as a tray in which the holes

occupy at least 30% of the surface area

Method 11

IN FREE AIR, ON CLEATS, BRACKETS OR A LADDER:

Sheathed single- core cables in free air (any

supporting metalwork under the cables

occupying less than 10% of the plan area

Two of three cables vertically one above the

other, minimum distance between cable

surfaces equal to the overall cable diameter

(De); distance from the wall not less than

0.5De

Two or three cables horizontally, with

spacings as above

Three cables in trefoil, distance between

wall and surface of nearest cable 0.5De or

nearest cables 0.75De

Method 12

Sheathed multicore cables on ladder or

brackets, separation greater than 2De

Sheathed multicore cables in free air

distance between wall and cable surface not

less than 0.3De

Any supporting metalwork under the cables

occupying less than 10% of the plan area

Method 13

Cables suspended from or incorporating a

catenary wire

Method 12 or 13,

as appropriate

Page 25: Catalogue tai sin

25

Schedule of Installation Methods of Cables (Including Reference Method) Technical Table 1.3

Installation Method

Examples

Appropriate Reference Methoad For

Determining Current- Carrying

Capacity Description

CABLES IN TRENCHES:

Cables in enclosed trench

450mm wide by 300mm deep

(minimum dimentions)

including 100mm cover

Two signle- core cables

with surfaces

sepaeerated by a

minimum og one cable

diameter

Method 18

Use rating factors

in Technical Table 3

Three single-core

cables in trefoil and

touching throughout

Multicore cables or

groups of single-core

cables with surfaces

separated by a

minimum of 50mm

Cables in enclosed trench

450mm wide by 600mm deep

(minimum dimentions)

including 100mm cover

Single-core cables arranged

in flat groups of two or three

on the vertical trench wall

with surfaces separated by

one diameter with a

minimum distance of 50mm

between groups. Multicore

cables installed with surfaces

separated by a minimum of

75mm. All cables spaced at

least 25mm from the

trenched wall

Method 19

Use rating factors

in Technical Table 3

Cables in enclosed trench

600mm wide by 760mm deep

(minimum dimentions)

including 100mm cover

Single-core cables arranged

in groups of two or three in

flat formation with the

surfaces sepaerated by one

diameter or in trefoil

formation with cables

touching

Method 20

Use rating factors

in Technical Table 3

Groups separated by a

minimum* of 50mm either

horizontally or vertically.

Multi caor cables installed

with surfaces separated by a

minimum* of 75mm either

horizontally or vertically. All

cables spaced at least 25mm

from the trench wall

Larger spacing to be used where practicable

Page 26: Catalogue tai sin

26

Correction Factors For Groups of More than One Circuit Of Single-core Cables, or More than One Multicore Cable Technical Table 2

Reference Methods

of Installation

Correction Factor (C9)

Number of Circuits of Multi-Core Cables

2 3 4 5 6 7 8 9 10 12 14 16 18 20 Enclosed (Method 3 or 4) or

bunched and clipped direct to a

non- metallic surface (Method 1) 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.39 0.38

Single layer clipped to a non-metallic

surface (Method 1)

Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 - - - - - -

Spaced * 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 Single layer multi

core on a perforated

metal cable tray,

vertical or

horizontal

(Method 11)

Touching 0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72 0.71 0.70 - - - -

Spaced * 0.91 0.89 0.88 0.87 0.87 - - - - - - - - -

Single layer single

core on a perforated

metal cable tray, touching (Method 11)

Horizontal 0.90 0.85 - - - - - - - - - - - -

Vertical 0.85 - - - - - - - - - - - - -

Single layer multi core touching on

ladder supports 0.86 0.82 0.80 0.79 0.78 0.78 0.78 0.77 - - - - - -

Space means a clearance between adjacent surfaces of at least one cable diameter (De). Where the horizontal clearance between adjacent cables exceeds 2 De, no

correction factor need be applied.

Notes: 1) The factors in the table are applicable to groups of cables all of one size. The value of current derived from application of the appropriate factors is the

maximum continuous current to be carried by any of the cables in the group.

2) If, due to known operating conditions, a cable is expected to carry not more than 30% of it’s grouped rating, it may be ignored for the purposed of obtaining the rating factor for the rest of the group.

For example, a group of N loaded cables would normally require a group reduction factor of Cg applied to the tabulated It. However, if M cables in the

group carry loads which are not greater than 0.3Cglt amperes, the other cables can be sized by using the group rating factor corresponding to (N-M) cables.

3) Factors are given for single layer of cables and do not apply when cables are installed in more than one layer touching each other.

4) For circuits having more than one cable in parallel per phase, each set of three conductors should be considered as a circuit for the purpose of this table.

Correction Factors for Cables installed in Enclosed Trenches Technical Table 3

Conductor

cross-

sectional

area

mm2

Installation Method 18 Installation Method 19 Installation Method 20

2

1-core

cables, or 1

3- or

4- core

cables

3

1-core

cables,

or 2

2-core

cables

4

1-core

cables, or 2

3- or

4- core

cables

6

1-core

cables,

4

2- core

cables, or 3

3- or

4- core

cables

6

1-core

cables,

4

2- core

cables, or 3

3- or

4- core

cables

8

1-core

cables, or 4

3- or

4- core

cables

12

1-core

cables,

8

2- core

cables, or 6

3- or

4- core

cables

12

1-core

cables,

8

2- core

cables, or 6

3- or

4- core

cables

18

1-core

cables,

12

2- core

cables, or 9

3- or

4- core

cables

24

1-core

cables,

16

2- core

cables, or

12

3- or

4- core

cables

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

630

0.93

0.92

0.91

0.91

0.90

0.89

0.88

0.87

0.86

0.85

0.84

0.83

0.82

0.81

0.80

0.78

0.77

0.90

0.89

0.88

0.87

0.86

0.85

0.84

0.82

0.81

0.80

0.78

0.77

0.76

0.74

0.73

0.72

0.71

0.87

0.86

0.85

0.84

0.82

0.81

0.79

0.78

0.76

0.75

0.74

0.73

0.71

0.69

0.67

0.66

0.65

0.82

0.81

0.80

0.78

0.76

0.75

0.74

0.72

0.70

0.69

0.67

0.65

0.63

0.62

0.59

0.58

0.56

0.86

0.86

0.85

0.83

0.81

0.80

0.78

0.77

0.75

0.73

0.72

0.70

0.69

0.68

0.66

0.64

0.63

0.83

0.82

0.80

0.78

0.76

0.74

0.73

0.72

0.70

0.68

0.67

0.65

0.63

0.62

0.60

0.58

0.57

0.76

0.75

0.74

0.71

0.69

0.68

0.66

0.64

0.63

0.61

0.59

0.58

0.56

0.54

0.52

0.51

0.49

0.81

0.80

0.78

0.76

0.74

0.72

0.71

0.70

0.68

0.66

0.64

0.63

0.61

0.59

0.57

0.56

0.54

0.74

0.73

0.72

0.70

0.67

0.66

0.64

0.62

0.60

0.58

0.57

0.55

0.53

0.52

0.50

0.48

0.47

0.69

0.68

0.66

0.64

0.62

0.60

0.59

0.57

0.55

0.53

0.51

0.49

0.48

0.46

0.44

0.43

0.41 The correction factors tabulated above relate to the disposition of cables illustrated in terms 18 to 20 of Technical Table 1.3 and are applicable to the

current- carrying capacities for Reference Methods 12 or 13 of Technical Table 1.2.

When cables having different conductor operating temperatures are grouped together the current rating shall be based on the lowest operating temperature

of any cable in the group.

Page 27: Catalogue tai sin

27

Technical Data Rating Factors for Other Temperature conditions Technical Table 4

Table A: Rating Factors for Other Ambient Air Temperature (PVC Insulated)

Ambient

Temperature 25

0C 30

0C 35

0C 40

0C 45

0C 50

0C 55

0C 60

0C 65

0C 70

0C

Rating Factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50 0.35 -

Table B: Rating Factors for Other Ground Temperature (PVC Insulated)

Ambient Temperature 100C 15

0C 20

0C 25

0C 30

0C 35

0C 40

0C 45

0C 50

0C

Rating Factor 1.04 1.00 0.95 0.90 0.85 0.80 0.73 0.67 0.60

Table C: Rating Factors for Other Ambient Air Temperature (XLPE Insulated)

Ambient

Temperature 25

0C 30

0C 35

0C 40

0C 45

0C 50

0C 55

0C 60

0C 65

0C 70

0C 75

0C 80

0C 85

0C

Rating Factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.50 0.41 0.29

Table D: Rating Factors for Other Ground Temperature (XLPE Insulated)

Ambient Temperature 150C 20

0C 25

0C 30

0C 35

0C 40

0C 45

0C 50

0C

Rating Factor 1.00 0.97 0.93 0.89 0.86 0.82 0.77 0.73

Table E: Rating factors for Other Ambient Air Temperature (PVC Insulated)

Ambient Temperature 300C 35

0C 40

0C 45

0C 50

0C 55

0C 60

0C 65

0C 70

0C

PVC cords, non-heat

resisting 1.00 0.96 0.92

0.87

0.71 0.50 - - -

PVC cords, heat resisting

1.00 - - - 1.00 0.96 0.83 0.67 0.47

Table F: Group Rating Factors for Cables Installation

Group Rating Factors Numbers of Circuits

2 3 4 5 6 7 8 9 10 11 12

1

For circuits of 2 Single-core

cables laid flat touching

horizontal formation, laid direct

in ground

0.79 0.68

0.62 0.57 0.54 0.52 0.50 0.48 0.47 0.46 0.45

2

For circuits of 3 Single-core

cables in trefoil touching, laid

direct in the ground

0.78 0.66 0.61 0.56 0.53 0.50 0.49 0.47 0.46 0.44 0.43

Number of Cables in a Group

2 3 4 5 6 7 8 9 10 11 12

3

For twin of

multicore

cables in

horizontal

formation, laid

direct in ground

Spaced

0.15m 0.87 0.78 0.74 0.70 0.68 0.66 0.64 0.63 0.62 0.61 0.60

Spaced

0.30m 0.91 0.84 0.81 0.78 0.77 0.75 0.75 0.74 0.73 0.73 0.72

Numbers of Ducts in a Group

2 3 4 5 6 7 8 9 10 11 12

4

For twin multicore cables in

single-way ducts horizontal

formation spaced 0.30m apart

0.93 0.88 0.85 0.83 0.82 0.81 0.80 0.79 0.79 0.78 0.78

Page 28: Catalogue tai sin

28

Current- Carrying Capacities (Amp) PVC & PVC/ PVC Cables Technical Table 5.1

Conductor

cross-

sectional

area

Reference Method 4

(Enclosed in conduit in

thermally insulating

wall etc)

Reference Method 3

(Enclosed in conduit on

a wall or in trunking

etc)

Reference Method 1

(‘Clipped direct’)

Reference Method 11

(on a perforated cable

tray horizontal of

vertical)

Reference Method 12 (free air)

Horizontal

flat spaced,

Vertical

flat spaced,

2 cables,

single-

phase

ac or dc

3 or 4

cables

3- phase

ac

2 cables,

single-

phase

ac or dc

3 or 4

cables

3- phase

ac

2 cables,

single-

phase

ac or dc

3 or 4

cables

3- phase

ac

2 cables,

single-

phase

ac or dc

or flat and

touching

3 cables,

3-phase

ac

flat and

touching

2 cables,

single- phase

ac or dc or

3 cables

or

trefoil

2 cables,

single-

phase

ac or dc

or

3 cables

3- phase

ac

3 cables,

trefoil

3-phase

ac

3-phase

ac

mm2 Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp

BS

600

4

1

1.5

2.5

4

6

10

16

25

35

11

14.5

19.5

26

34

46

61

80

99

10.5

13.5

18

24

31

42

56

73

89

13.5

17.5

24

32

41

57

76

101

125

12

15.5

21

28

36

50

68

89

110

15.5

20

27

37

47

65

87

114

141

14

18

25

33

43

59

79

104

129

-

-

-

-

-

-

-

126

156

-

-

-

-

-

-

-

112

141

-

-

-

-

-

-

-

146

181

-

-

-

-

-

-

-

130

162

-

-

-

-

-

-

-

110

137

BS

634

6

50

70

95

120

150

185

240

300

400

500

630

800

1000

119

151

182

210

240

273

320

367

-

-

-

-

-

108

136

164

188

216

245

286

328

-

-

-

-

-

151

192

232

269

300

341

400

458

546

626

720

-

-

134

171

207

239

262

296

346

394

467

533

611

-

-

182

234

284

330

381

436

515

594

694

792

904

1030

1154

167

214

261

303

349

400

472

545

634

723

826

943

1058

191

246

300

349

404

463

549

635

732

835

953

1086

1216

172

223

273

318

369

424

504

584

679

778

892

1020

1149

219

281

341

396

456

521

615

709

852

982

1138

1265

1420

197

254

311

362

419

480

569

659

795

920

1070

1188

1337

167

216

264

304

356

409

485

561

656

749

855

971

1079

* With or without protective conductor

Note: Rating factors for ambient temperature other than 300c please refer Table A

Group Rating Factor please refer to Table 2 Voltage Drop (Per Amp Meter) PVC & PVC/ PVC Cables Technical Table 5.2

Conductor

Cross-

sectional

area

2

cables

dc

2 cables- single- phase ac 3 or 4 cables- three- phase ac

Reference Methods

3 & 4 (Enclosed in

conduit etc in or on

a wall)

Reference Methods 1

& 11 (Clipped direct

or on trays, touching)

Reference Methods

12

(space *)

Reference Methods

3 & 4 (Enclosed in

conduit etc in or on

a wall)

Reference Methods

1, 11& 12

(in trefoil)

Reference Methods

1 & 11 (flat

touching)

Reference Methods

12

(Flat spaced*)

mm2 mV mV mV mV mV mV mV mV

1

1.5 2.5

4

6 10

16

44

29 18

11

7.3 4.4

2.8

44

29 18

11

7.3 4.4

2.8

44

29 18

11

7.3 4.4

2.8

44

29 18

11

7.3 4.4

2.8

38

25 15

9.5

6.4 3.8

2.4

38

25 15

9.5

6.4 3.8

2.4

38

25 15

9.5

6.4 3.8

2.4

38

25 15

9.5

6.4 3.8

2.4 r x z r x z r x z r x z r x z r x z r x z

25

35

50

70

95

120

150

185

240

300

400

500

630

800

1000

1.75

1.25

0.93

0.63

0.46

0.36

0.29

0.23

0.180

0.145

0.105

0.086

0.068

0.053

0.042

1.80

1.30

0.95

0.65

0.49

0.39

0.31

0.25

0.195

0.160

0.130

0.110

0.094

-

-

0.33

0.31

0.30

0.29

0.28

0.27

0.27

0.27

0.26

0.26

0.26

0.26

0.25

-

-

1.80

1.30

1.00

0.72

0.56

0.47

0.41

0.37

0.33

0.31

29

0.28

0.27

-

-

1.75

1.25

0.93

0.63

0.47

0.37

0.30

0.24

0.185

0.150

0.120

0.098

0.081

0.068

0.059

0.20

0.195

0.190

0.185

0.180

0.175

0.175

0.170

0.165

0.165

0.160

0.155

0.155

0.150

0.150

1.75

1.25

0.95

0.66

0.50

0.41

0.34

0.29

0.25

0.22

0.20

0.185

0.175

0.165

0.160

1.75

1.25

0.93

0.63

0.47

0.37

0.29

0.24

0.185

0.150

0.115

0.093

0.076

0.061

0.050

0.29

0.28

0.28

0.27

0.27

0.26

0.26

0.26

0.25

0.25

0.25

0.24

0.24

0.24

0.24

1.80

1.30

0.97

0.69

0.54

0.45

0.39

0.35

0.31

0.29

0.27

0.26

0.25

0.25

0.24

1.50

1.10

0.81

0.56

0.42

0.33

0.27

0.22

0.17

0.14

0.12

0.10

0.08

-

-

0.29

0.27

0.26

0.25

0.24

0.23

0.23

0.23

0.23

0.23

0.22

0.22

0.22

-

-

1.55

1.10

0.85

0.61

0.48

0.41

0.36

0.32

0.29

0.27

0.25

0.25

0.24

-

-

1.50

1.10

0.80

0.55

0.41

0.32

0.26

0.21

0.160

0.130

0.150

0.086

0.072

0.060

0.052

0.175

0.170

0.165

0.160

0.155

0.150

0.150

0.145

0.145

0.140

0.140

0.135

0.135

0.130

0.130

1.50

1.10

0.82

0.57

0.43

0.36

0.30

0.26

0.22

0.190

0.175

0.160

0.150

0.145

0.140

1.50

1.10

0.80

0.55

0.41

0.32

0.26

0.21

0.160

0.130

0.150

0.086

0.072

0.060

0.052

0.25

0.24

0.24

0.24

0.23

0.23

0.23

0.22

0.22

0.22

0.21

0.21

0.21

0.21

0.20

1.55

1.10

0.84

0.60

0.47

0.40

0.34

0.31

0.27

0.25

0.24

0.23

0.22

0.22

0.21

1.50

1.10

0.80

0.55

0.40

0.32

0.26

0.21

0.160

0.130

0.100

0.081

0.066

0.053

0.044

0.32

0.32

0.32

0.31

0.31

0.30

0.30

0.30

0.29

0.29

0.29

0.29

0.28

0.28

0.28

1.55

1.15

0.86

0.63

0.51

0.44

0.40

0.36

0.34

0.32

0.31

0.30

0.29

0.29

0.28

Note: r = conductor resistance at operating temperature

z = impedance, x = reactance

Page 29: Catalogue tai sin

29

Current- Crying Capacities (Amp) PVC/ PVC Cables Technical Table 6.1

Conductor

cross- sectional

area

Reference Methods 4

(Enclosed in an

insulated wall etc)

Reference Methods 3

(Enclosed in conduit on a wall

or ceiling, or in trunking)

Reference Method 1

(Clipped direct)

Reference Method 11

(on a perforated cable tray), or

Reference Method 13 ( free air)

1

2-core cable*

single-phase

ac or dc

1

2-core cable*

or 1

4-core cable

3-phase ac

1

2-core cable*

single-phase

ac or dc

1

2-core cable*

or 1

4-core cable

3-phase ac

1

2-core cable*

single-phase

ac or dc

1

2-core cable*

or 1

4-core cable

3-phase ac

1

2-core cable*

single-phase

ac or dc

1

2-core cable*

or 1

4-core cable

3-phase ac

mm2 Amp Amp Amp Amp Amp Amp Amp Amp

1

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

11

14

18.5

25

32

43

57

75

92

110

139

167

192

219

248

291

334

-

10

13

17.5

23

29

39

52

68

83

99

125

150

172

196

223

261

298

-

13

16.5

23

30

38

52

69

90

111

133

168

201

232

258

294

344

394

470

11.5

15

20

27

34

46

62

80

99

118

149

179

206

225

255

297

339

402

15

19.5

27

36

46

63

85

112

138

168

213

258

299

344

392

461

530

634

13.5

17.5

24

32

41

57

76

96

119

144

184

223

259

299

341

403

464

557

17

22

30

40

51

70

94

119

148

180

232

282

328

379

434

514

593

715

14.5

18.5

25

34

43

60

80

101

126

153

196

238

276

319

364

430

497

597

* With or without protective conductor

Note: Rating factors for ambient temperature other than 300c please refer Table A

Group Rating Factor please refer to Table 2

Voltage Drop (Per Amp Meter) PVC/ PVC Cables Technical Table 6.2

Conductor

cross- sectional 2-core cable ac

2-core cable

single-phase ac

3 or 4-core cable

3-phase ac

mm2 mV mV mV

1

1.5

2.5

4

6

10

16

44

29

18

11

7.3

4.4

2.8

44

29

18

11

7.3

4.4

2.8

38

25

15

9.5

6.4

3.8

2.4

r x z r x z

25

35

50

70

95

120

150

185

240

300

400

1.75

1.25

0.93

0.63

0.46

0.36

0.29

0.23

0.180

0.145

0.105

1.75

1.25

0.93

0.63

0.47

0.38

0.30

0.25

0.190

0.155

0.115

0.170

0.165

0.165

0.160

0.155

0.155

0.155

0.150

0.150

0.145

0.145

1.75

1.25

0.94

0.65

0.50

0.41

0.34

0.29

0.24

0.21

0.185

1.50

1.10

0.80

0.55

0.41

0.33

0.26

0.21

0.165

0.135

0.100

0.145

0.145

0.140

0.140

0.135

0.135

0.130

0.130

0.130

0.130

0.125

1.50

1.10

0.81

0.57

0.43

0.35

0.29

0.25

0.21

0.185

0.160

Note: r = conductor resistance at operating temperature

z = impedance, x = reactance

Page 30: Catalogue tai sin

30

Current- Crying Capacities (Amp) PVC/ AWA/ PVC Cables Technical Table 7.1

Conductor

cross-

sectional

area

Reference Methods 1

(Clipped direct)

Reference Methods 11

(on perforated cable

tray)

Reference Methods 12 (free air)

Direct in

ground

In Single Way

Ducts

2 cables

single-

phase

ac or dc

3 or 4

cables

3-phase

ac

2 cables

single-

phase

ac flat &

touching

3 or 4

cables

3-phase

flat &

touching

3 or 4 cables

3-phase ac

2 cables dc

spaced

2

cables

flat

touch-

ing

3

cables

trefoil

touch-

ing

2

cables

duct

touch-

ing

3

cables

trefoil

touch-

ing

Horizontal

flat

spaced

Vertical

flat

spaced

3 cables

trefoils

Hori-

zontal

Verti-

cal

mm2 Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp

50

70 95

120

150 185

240

300 400

500

630 800

1000

193

245 296

342

393 447

525

594 687

763

843 919

975

179

225 269

309

352 399

465

515 575

622

669 710

737

205

259 313

360

413 469

550

624 723

805

891 976

1041

189

238 285

327

373 422

492

547 618

673

228 777

808

230

286 338

385

436 490

566

616 674

721

771 824

872

212

263 313

357

405 456

528

578 632

676

723 772

816

181

231 280

324

373 425

501

567 657

731

809 886

945

229

294 357

415

479 548

648

748 885

1035

1218 1441

1685

216

279 340

396

458 525

622

719 851

997

1174 1390

1627

238

292 349

396

443 497

571

640 708

780

856 895

939

203

248 297

337

376 423

485

542 600

660

721 756

797

216

262 308

341

375 414

463

509 545

585

632 662

703

199

241 282

311

342 375

419

459 489

523

563 587

621

Note: Rating factors for ambient temperature other than 300c please refer Table A

Rating factors for ambient temperature other than 150c please refer Table B

Group Rating Factor please refer to Table F & Table 2

Voltage Drop (Per Amp Meter) PVC/AWA/ PVC Cables Technical Table 7.2

Conduc-

tor

cross-

sectional

area

2

cable

s dc

2 cables-single-phase ac 3 or 4 cables-three-phase ac Direct in ground

Single Way

Ducts

Reference

Methods 1 & 11

(Touching)

Reference

Methods 12

(space*)

Reference

Methods 1, 11 &

12 (in trefoil

touching)

Reference

Methods 1 & 11

(Flat touching)

Reference

Methods 12

(flat spaced*)

2

cables

flat

touch-

ing

3 cables

trefoil

touch-

ing

2 cables

flat

touch-

ing

3

cable

s

trefoi

l

touch

-ing

mm2 mV mV mV mV mV mV mV mV mV mV r x z r x z r x z r x z r x z

50

70

95

120

150

185

240

300

400

500

630

800

1000

0.93

0.63

0.46

0.36

0.29

0.23

0.180

0.145

0.105

0.086

0.068

0.053

0.042

0.93

0.64

0.48

0.39

0.31

0.26

0.20

0.160

0.140

0.120

0.105

0.094

0.095

0.22

0.21

0.20

0.195

0.19

0.19

0.180

0.180

0.175

0.170

0.165

0.160

0.155

0.95

0.68

0.52

0.43

0.37

0.32

0.27

0.24

0.22

0.21

0.195

0.185

0.185

0.92

0.66

0.51

0.42

0.34

0.29

0.23

0.190

0.180

0.165

0.150

0.145

0.140

0.30

0.29

0.28

0.28

0.27

0.27

0.26

0.26

0.24

0.23

0.22

0.21

0.190

0.97

0.72

0.58

0.50

0.44

0.39

0.35

0.32

0.30

0.29

0.27

0.25

0.24

0.80

0.56

0.42

0.33

0.27

0.22

0.175

0.140

0.120

0.105

0.091

0.082

0.079

0.19

0.18

0.175

0.17

0.165

0.16

0.160

0.155

0.130

0.145

0.145

0.140

0.135

0.82

0.58

0.45

0.37

0.32

0.27

0.23

0.21

0.195

0.180

0.170

0.160

0.155

0.79

0.57

0.44

0.36

0.30

0.25

0.20

0.165

0.160

0.145

0.135

0.125

0.125

0.26

0.25

0.25

0.24

0.24

0.23

0.23

0.22

0.21

0.20

0.195

0.180

0.165

0.84

0.62

0.50

0.43

0.38

0.34

0.30

0.28

0.26

0.25

0.23

0.22

0.21

0.79

0.59

0.47

0.40

0.34

0.29

0.24

0.20

0.21

0.190

0.175

0.170

0.165

0.34

0.32

0.31

0.30

0.30

0.29

0.28

0.28

0.25

0.24

0.22

0.195

0.170

0.86

0.68

0.57

0.50

0.45

0.41

0.37

0.34

0.32

0.30

0.28

0.26

0.24

0.97

0.67

0.50

0.42

0.36

0.31

0.26

0.23

0.22

0.20

0.19

-

-

0.82

0.58

0.44

0.36

0.31

0.27

0.23

0.20

0.19

0.18

0.16

-

-

1.00

0.76

0.61

0.54

0.48

0.44

0.40

0.37

0.34

0.32

0.30

-

-

0.88

0.66

0.53

0.47

0.42

0.38

0.34

0.32

0.30

0.28

0.26

-

-

Note: r = conductor resistance at operating temperature; z = impedance; x = reactance

Page 31: Catalogue tai sin

31

Current- Crying Capacities (Amp) PVC/ SWA/ PVC Cables Technical Table 8.1

Conductor

cross- sectional

area

Reference Methods 1

(Clipped direct)

Reference Methods 11

(on a perforated horizontal cable

tray or Reference Methods 13

(free air) Direct in Ground In Single Way Ducts

1

2-core cable

single-phase

ac or dc

1

3- or 4-

cable

3- phase ac

or dc

1

2-core cable

single-phase

ac or dc

1

3- or 4-

cable

3- phase ac

or dc 2 cores 3 or 4 cores 2 cores 3 or 4 cores

mm2 Amp Amp Amp Amp Amp Amp Amp Amp

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

21

28

38

49

67

89

118

145

175

222

269

310

356

405

476

547

621

18

25

33

42

58

77

102

125

151

192

231

267

306

348

409

469

540

22

31

41

53

72

97

128

157

190

241

291

336

386

439

516

592

683

19

26

35

45

62

83

110

135

163

207

251

290

332

378

445

510

590

32

41

55

69

92

119

158

190

225

277

332

377

422

478

551

616

693

27

35

47

59

78

101

132

159

188

233

279

317

355

401

462

517

580

26

34

45

57

76

98

129

154

183

225

271

309

346

393

455

510

574

22

29

38

48

64

83

107

126

153

190

228

260

292

331

382

428

490

Note: Rating factors for ambient temperature other than 300c please refer Table A

Rating factors for ambient temperature other than 150c please refer Table B

Group Rating Factor please refer to Table F & Table 2

Voltage Drop (Per Amp Meter) PVC/AWA/ PVC Cables Technical Table 8.2

Conductor

cross- sectional

area 2- core cable ac 2- core cable single-phase ac

3- or 4-

cable 3- phase ac

Direct in Ground

In Single

Way Ducts

2- cores

3- or 4-

cores

2 -

cores

3- or 4-

cores

mm2 mV mV mV mV mV mV mV

1.5

2.5

4

6

10

16

29

18

11

7.3

4.4

2.8

29

18

11

7.3

4.4

2.8

25

15

9.5

6.4

3.8

2.4

29

18

11

7.3

4.4

2.8

25

15

9.5

6.4

3.8

2.4

29

18

11

7.3

4.4

2.8

25

15

9.5

6.4

3.8

2.4

r x z r x z

25

35

50

70

95

120

150

185

240

300

400

1.75

1.25

0.93

0.63

0.46

0.36

0.29

0.23

0.18

0.145

0.105

1.75

1.25

0.93

0.63

0.47

0.38

0.3

0.25

0.19

0.155

0.115

0.17

0.165

0.165

0.16

0.155

0.155

0.155

0.15

0.15

0.145

0.145

1.75

1.25

0.94

0.65

0.5

0.41

0.34

0.29

0.24

0.21

0.185

1.5

1.1

0.8

0.55

0.41

0.33

0.26

0.21

0.165

0.135

0.1

0.145

0.145

0.14

0.14

0.135

0.135

0.13

0.13

0.13

0.13

0.125

1.5

1.1

0.81

0.57

0.43

0.35

0.29

0.25

0.21

0.185

0.16

1.7

1.3

0.94

0.66

0.49

0.4

0.34

0.29

0.24

0.21

0.19

1.5

1.1

0.82

0.57

0.42

0.35

0.29

0.25

0.21

0.18

0.17

1.7

1.3

0.94

0.66

0.49

0.4

0.34

0.29

0.24

0.21

0.19

1.5

1.1

0.82

0.57

0.42

0.35

0.29

0.25

0.21

0.18

0.17

Note: r = conductor resistance at operating temperature

z = impedance, x = reactance

Page 32: Catalogue tai sin

32

Current- Crying Capacities (Amp) XLPE/ PVC Cables Technical Table 9.1

Size of

Conductor

Reference Methods 4

(Enclosed in an

insulated wall etc)

Reference Methods 3

(Enclosed in conduit on a wall

or ceiling, or in trunking)

Reference Method 1

(Clipped direct)

Reference Method

11 (on a perforated

cable tray,

horizontal or

vertical)

Reference

Method 12

( free air)

2 cables

1-phase

ac or dc

3 or 4

cables

3-phase ac

2 cables

1-phase

ac or dc

3 or 4

cables

3-phase ac

2 cables

1-phase

ac or dc flat &

touching

3 or 4

cables

3-phase ac flat

& touching or

trefoil

2 cables

1-phase

ac or dc

flat &

touching

3 or 4

cables

3-phase

ac flat &

touching

or

trefoil

3 cables

trefoil

3-phase ac

1 2 3 4 5 6 7 8 9 10

mm2 A A A A A A A A A

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

630

800

1000

18

24

33

43

58

76

100

124

149

189

228

263

300

341

400

459

-

-

-

-

-

17

23

30

39

53

70

91

111

135

170

205

235

270

306

358

410

-

-

-

-

-

22

30

40

51

71

95

126

156

189

240

290

336

375

426

500

573

683

783

900

-

-

19

26

35

45

63

85

111

138

168

214

259

299

328

370

433

493

584

666

764

-

-

25

34

46

59

81

109

143

176

228

293

355

413

476

545

644

743

868

990

1130

1288

1443

23

31

41

54

74

99

130

161

209

268

326

379

436

500

590

681

793

904

1033

1179

1323

-

-

-

-

-

-

158

195

293

308

375

436

505

579

686

794

915

1044

1191

1358

1520

-

-

-

-

-

-

140

176

215

279

341

398

461

530

630

730

849

973

1115

1275

1436

-

-

-

-

-

-

138

171

209

270

330

385

445

511

606

701

820

936

1069

1214

1349

Note: Rating factors for ambient temperature other than 300c please refer Table C

Rating factors for ambient temperature other than 150c please refer Table D

Group Rating Factor please refer to Table 2

Voltage Drop (Per Amp Per Meter) XLPE/ PVC Cables Technical Table 9.2

Size of

Conductor

2 cables

dc

2 Cables, 1-phase ac 3 or 4 Cables, 3-phase ac

Reference Methods 3&4

(Enclosed in conduit

etc, in or on a wall)

Reference Methods 1 &

11 (clipped direct or on

trays touching)

Reference Methods 3&4

(Enclosed in conduit etc,

in or on a wall)

Reference Methods

1, 11 & 12

(in trefoil)

Reference Methods

1 & 11

(flat & touching)

1 2 3 4 5 6 7

mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m

1.5 2.5

4

6 10

16

31 19

12

7.9 4.7

2.9

31 19

12

7.9 4.7

2.9

31 19

12

7.9 4.7

2.9

27 16

10

6.8 4.0

2.5

27 16

10

6.8 4.0

2.5

27 16

10

6.8 4.0

2.5

r x z r x Z r x z r x z r x Z

25 35

50

70 95

120

150 185

240

300

400

500

630 800

1000

1.85 1.35

0.99

0.68 0.49

0.39

0.32 0.25

0.19

0.155

0.12

0.093

0.072 0.056

0.045

1.85 1.35

1.00

0.70 0.51

0.41

0.33 0.27

0.21

0.175

0.14

0.12

0.10 -

-

0.31 0.29

0.29

0.28 0.28

0.27

0.26 0.26

0.26

0.26

0.25

0.25

0.25 0.25

-

1.90 1.35

1.05

0.75 0.58

0.48

0.43 0.37

0.33

0.31

0.29

0.28

0.27 -

-

1.85 1.35

0.99

0.68 0.49

0.39

0.32 0.26

0.20

0.16

0.13

0.105

0.086 0.072

0.063

0.19 0.18

0.18

0.175 0.170

0.165

0.165 0.165

0.160

0.160

0.155

0.155

0.155 0.150

0.150

1.85 1.35

1.00

0.71 0.52

0.43

0.36 0.30

0.25

0.22

0.20

0.185

0.175 0.170

0.165

1.60 1.15

0.87

0.60 0.44

0.35

0.29 0.23

0.185

0.15

0.125

0.100

0.088 -

-

0.27 0.25

0.25

0.24 0.23

0.23

0.23 0.23

0.22

0.22

0.22

0.22

0.21 -

-

1.65 1.15

0.90

0.65 0.50

0.42

0.37 0.32

0.29

0.27

0.25

0.24

0.23 -

-

1.60 1.15

0.86

0.59 0.43

0.34

0.28 0.22

0.17

0.14

0.11

0.09

0.074 0.062

0.055

0.165 0.155

0.155

0.150 0.145

0.140

0.140 0.140

0.140

0.140

0.135

0.135

0.135 0.130

0.130

1.60 1.15

0.87

0.61 0.45

0.37

0.31 0.26

0.22

0.195

0.175

0.160

0.150 0.145

0.140

1.60 1.15

0.86

0.59 0.43

0.34

0.28 0.22

0.17

0.135

0.110

0.088

0.071 0.059

0.050

0.19 0.18

0.18

0.175 0.170

0.165

0.165 0.165

0.165

0.160

0.160

0.160

0.160 0.155

0.150

1.60 1.15

0.87

0.62 0.46

0.38

0.32 0.28

0.24

0.21

0.195

0.180

0.170 0.165

0.165

Note: r = conductor resistance at operating temperature

z = impedance, x = reactance

Page 33: Catalogue tai sin

33

Current- Crying Capacities (Amp) XLPE/ PVC Cables Technical Table 10.1

Size of

Conductor

Reference Methods 4

(Enclosed in conduit and in

insulated wall etc)

Reference Methods 3

(Enclosed in conduit on a wall

or ceiling, or in trunking)

Reference Method 1

(Clipped direct)

Reference Method 11 (on a

perforated cable tray, or

Reference Method 13 (free air)

1

2-core cable

single-phase

ac or dc

1

3- or 4-

cable

3-phase ac

1

2-core cable

single-phase

ac or dc

1

3- or 4-

cable

3-phase ac

1

2-core cable

single-phase

ac or dc

1

3- or 4-

cable

3-phase ac

1

2-core cable

single-phase

ac or dc

1

3- or 4-

cable

3-phase ac

1 2 3 4 5 6 7 8 9

mm2 A A A A A A A A

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

18.5

25

33

42

57

76

99

121

145

183

220

253

290

329

386

442

-

16.5

22

30

38

51

68

89

109

130

164

197

227

259

295

346

396

-

22

30

40

51

69

91

119

146

175

221

265

305

334

384

459

532

625

19.5

26

35

44

60

50

105

128

154

194

233

268

300

340

398

455

536

24

33

45

58

80

107

138

171

209

269

328

382

441

506

599

693

803

22

30

40

52

71

96

119

147

179

229

278

322

371

424

500

576

667

26

36

49

63

86

115

149

185

225

289

352

410

473

542

641

741

865

23

32

42

54

75

100

127

158

192

246

298

346

399

456

538

621

741

Note: Rating factors for ambient temperature other than 300c please refer Table C

Rating factors for ambient temperature other than 150c please refer Table D

Group Rating Factor please refer to Table 2

Voltage Drop (Per Amp Per Meter) XLPE/ PVC Cables Technical Table 10.2

Size of Conductor 2-core cable dc

2-core cable

single-phase ac

3- or 4-

Cable

3-phase ac

1 2 3 4

mm2 mV/A/m mV/A/m mV/A/m

1.5

2.5

4

6

10

16

31

19

12

7.9

4.7

2.9

31

19

12

7.9

4.7

2.9

27

16

10

6.8

4.0

2.5

r x z r x Z

25

35

50

70

95

120

150

185

240

300

400

1.85

1.35

0.98

0.67

0.49

0.39

0.31

0.25

0.195

0.155

0.120

1.85

1.35

0.99

0.67

0.50

0.40

0.32

0.26

0.20

0.16

0.13

0.16

0.155

0.155

0.150

0.150

0.145

0.145

0.145

0.140

0.140

0.140

1.9

1.35

1.00

0.69

0.52

0.42

0.35

0.29

0.24

0.21

0.19

1.6

1.15

0.86

0.59

0.43

0.34

0.28

0.22

0.175

0.140

0.115

0.14

0.135

0.135

0.130

0.130

0.130

0.125

0.125

0.125

0.120

0.120

1.65

1.15

0.87

0.60

0.45

0.37

0.30

0.26

0.21

0.185

0.165

Note: r = conductor resistance at operating temperature

z = impedance, x = reactance

Page 34: Catalogue tai sin

34

Current- Crying Capacities (Amp) XLPE/ AWA/ PVC Cables Technical Table 11.1

Size of

Conductor

Reference Methods 1

(clipped direct)

Reference Method 11

(on a perforated cable tray)

Reference

Method 12

( free air) In single-way ducts Laid direct in ground

2 cables

1-phase

ac or dc

flat &

touching

3 or 4

cables

3-phase ac

flat &

touching

2 cables

1-phase

ac or dc

flat &

touching

3 or 4

cables

3-phase ac

flat &

touching

3 cables

3-phase ac

trefoil

touching

2 cables

1-phase

ac or dc

ducts

touching

3 cables

3-phase

ac

trefoil

ducts

touching

2 cables

1-phase

ac or dc

touching

3 cables

3-phase ac

trefoil

touching

1 2 3 4 5 6 7 8 9 10

mm2 A A A A A A A A A

50

70

95

120

150

185

240

300

400

500

630

800

1000

237

303

367

425

488

557

656

755

853

962

1082

1170

1261

220

277

333

383

437

496

579

662

717

791

861

904

961

253

322

382

449

516

587

689

792

899

1016

1146

1246

1345

232

293

352

405

462

524

612

700

767

851

935

987

1055

222

285

346

402

463

529

625

720

815

918

1027

1119

1214

255

310

365

410

445

485

550

610

640

690

750

828

919

235

280

330

370

405

440

500

550

580

620

670

735

811

257

340

405

460

510

580

670

750

830

910

1000

1117

1254

235

290

345

390

435

490

560

630

700

770

840

931

1038

Note: Rating factors for ambient temperature other than 300c please refer Table C

Rating factors for ambient temperature other than 150c please refer Table D

Group Rating Factor please refer to Table F & Table 2

Voltage Drop (Per Amp Per Meter) XLPE/AWA/PVC Cables Technical Table 11.2

Size of

Conductor

2 cables

dc

2 Cables,

1-phase ac

3 or 4 Cables,

3-phase ac

2 Cables,

1-phase ac

3 or 4 Cables, 3-phase

ac, touching

Reference Methods 1 &

11 (touching)

Reference Methods 1, 11

& 12 (in trefoil touching)

Reference Methods 1 &

11 (flat & touching)

In

ducts

In

ground

In

ducts

In

ground

1 2 3 4 5 6 7 8 9

mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m

r x z r x z r x z

50

70

95

120

150

185

240

300

400

500

630

800

1000

0.98

0.67

0.49

0.39

0.31

0.25

0.195

0.155

0.115

0.093

0.073

0.056

0.045

0.99

0.68

0.51

0.41

0.33

0.27

0.21

0.17

0.145

0.125

0.105

0.09

0.092

0.21

0.20

0.195

0.190

0.185

0.185

0.180

0.175

0.170

0.170

0.165

0.160

0.155

1

0.71

0.55

0.45

0.38

0.33

0.28

0.25

0.22

0.21

0.195

0.190

0.180

0.86

0.59

0.44

0.35

0.29

0.23

0.18

0.145

0.125

0.105

0.092

0.086

0.080

0.18

0.17

0.17

0.165

0.160

0.160

0.155

0.150

0.150

0.145

0.145

0.140

0.135

0.87

0.62

0.47

0.39

0.33

0.28

0.24

0.21

0.195

0.180

0.170

0.165

0.155

0.84

0.6

0.46

0.38

0.31

0.26

0.21

0.17

0.160

0.145

0.135

0.130

0.125

0.25

0.25

0.24

0.24

0.23

0.23

0.22

0.22

0.21

0.20

0.195

0.180

0.170

0.88

0.65

0.52

0.44

0.39

0.34

0.30

0.28

0.27

0.25

0.24

0.23

0.21

1.10

0.80

0.65

0.55

0.50

0.45

0.40

0.37

0.35

0.33

0.30

0.28

0.26

0.99

0.70

0.53

0.43

0.37

0.31

0.26

0.24

0.21

0.20

0.19

0.18

0.17

0.93

0.70

0.56

0.48

0.43

0.39

0.35

0.32

0.30

0.28

0.26

0.24

0.22

0.86

0.61

0.46

0.37

0.32

0.27

0.23

0.21

0.19

0.18

0.17

0.16

0.15

Note: r = conductor resistance at operating temperature

z = impedance, x = reactance

Page 35: Catalogue tai sin

35

Current- Crying Capacities (Amp) XLPE/ SWA/ PVC Cables Technical Table 12.1

Size of

Conductor

Reference Methods 1

(clipped direct)

Reference Method 11 (on a

perforated cable tray, or

Reference Method 13 (free air) In single-way ducts Laid direct in ground

1

2-core cable

single-phase

ac or dc

1

3- or 4-

cable

3-phase ac

1

2-core cable

single-phase

ac or dc

1

3- or 4-

cable

3-phase ac

1

2-core cable

single-phase

ac or dc

1

3- or 4-

cable

3-phase ac

1

2-core cable

single-phase

ac or dc

1

3- or 4-

cable

3-phase ac

1 2 3 4 5 6 7 8 9

mm2 A A A A A A A A

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

27

36

49

62

85

110

146

180

219

279

338

392

451

515

607

698

787

23

31

42

53

73

94

124

154

187

238

289

335

386

441

520

599

673

29

39

52

66

90

115

152

188

228

291

354

410

472

539

636

732

847

25

33

44

56

78

99

131

162

197

251

304

353

406

463

546

628

728

-

-

-

-

-

115

145

175

210

260

310

355

400

455

520

590

660

23

30

40

50

65

94

125

150

175

215

260

300

335

380

440

495

560

-

-

-

-

-

140

180

215

255

315

380

430

480

540

630

700

790

28

36

48

60

80

115

150

180

215

265

315

360

405

460

530

590

670

Note: Rating factors for ambient temperature other than 300c please refer Table C

Rating factors for ambient temperature other than 150c please refer Table D

Group Rating Factor please refer to Table F & Table 2

Voltage Drop (Per Amp Per Meter) XLPE/SWA/PVC Cables Technical Table 12.2

Size of

Conductor

2 cables

dc

2 Cables,

1-phase ac

3 or 4 Cables,

3-phase ac

2 Cables,

1-phase ac

3 or 4 Cables,

3-phase ac

In

ducts

In

ground

In

ducts

In

ground

1 2 3 4 5 6 7 8

mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m

1.5

2.5

4

6

10

16

31

19

12

7.9

4.7

2.9

31

19

12

7.9

4.7

2.9

27

16

10

6.8

4.0

2.5

31

19

12

7.9

4.7

2.9

31

19

12

7.9

4.7

2.9

25

15

9.5

6.4

3.8

2.4

25

15

9.5

6.4

3.8

2.4 r x z r x z

25

35

50

70

95

120

150

185

240

300

400

1.85

1.35

0.98

0.67

0.49

0.39

0.31

0.25

0.195

0.155

0.120

1.85

1.35

0.99

0.67

0.50

0.40

0.32

0.26

0.20

0.16

0.13

0.16

0.155

0.155

0.150

0.150

0.145

0.145

0.145

0.140

0.140

0.140

1.9

1.35

1.00

0.69

0.52

0.42

0.35

0.29

0.24

0.21

0.19

1.6

1.15

0.86

0.59

0.43

0.34

0.28

0.22

0.175

0.140

0.115

0.14

0.135

0.135

0.130

0.130

0.130

0.125

0.125

0.125

0.120

0.120

1.65

1.15

0.87

0.60

0.45

0.37

0.30

0.26

0.21

0.185

0.165

1.9

1.35

1.00

0.69

0.52

0.42

0.35

0.29

0.24

0.21

0.19

1.9

1.35

1.00

0.69

0.52

0.42

0.35

0.29

0.24

0.21

0.19

1.6

1.2

0.87

0.61

0.45

0.36

0.30

0.25

0.21

0.19

0.18

1.6

1.2

0.87

0.61

0.45

0.36

0.30

0.25

0.21

0.19

0.18

Note: r = conductor resistance at operating temperature

z = impedance, x = reactance

Page 36: Catalogue tai sin

36

Technical Data Flexible Cord, Imperial Sizes Technical Table 13.1

Conductor Current Rating Volt Drop PER 100FT

Maximum Weigh

supportable by twin

flexible cord

Nominal

Area Construction

1 or 3 phase

ac or dc

dc or

1 phase ac 3 phase ac

in2 No./in Amp V V lb

0.0006

0.0010

0.0017

0.0030

0.0048

0.0070

14/ 0.0076

23/ 0.0076

40/ 0.0076

70/ 0.0076

110/ 0.0076

162/ 0.0076

3

6

13

18

24

31

8.9

11

14

12

9.6

8.4

7.7

9.4

12

10

8.3

7.3

3

5

10

10

10

10

Note: Rating factors for ambient temperature other than 300c please refer Table E

Technical Data Flexible Cord Metric Sizes Technical Table 13.2

Conductor Current Rating Volt Drop per 100FT

Maximum Weigh

supportable by twin

flexible cord

Nominal

Area Construction

1 or 3 phase

ac or dc

dc or

1 phase ac 3 phase ac

mm2 No./mm Amp mV/m mV/m kg

0.50

0.75

1.00

1.25

1.50

2.50

4.00

16/ 0.2

24/ 0.2

32/ 0.2

40/ 0.2

30/ 0.25

50/ 0.25

56/ 0.3

3

6

10

13

15

20

25

83

56

43

35

31

18

11

72

48

37

29

26

16

9.6

2

3

5

5

5

5

5

Note: Rating factors for ambient temperature other than 300c please refer Table E

Page 37: Catalogue tai sin

37

Allowable Short Circuit Currents For PVC Insulated Cables Technical Table

14.1 S

ho

rt c

ircu

it c

urr

ent

(KA

)

100.0

90.0

80.0

70.0

60.0

50.0

40.0

30.0

20.0

10.0

9.0

8.0

7.0

6.0

5.0

4.0

3.0

2.0

1.0

16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 10000

Conductor: Copper

Insulation: PVC

Curves based on formula:

l = (0.115A÷ t )

Where:

l – Short circuit current (KA)

A- Conductor area (mm2)

t – Time of short circuit

(seconds)

Conductor Size (mm2)

Allowable Short Circuit Currents For XLPE Insulated Cables Technical Table 14.2

Sh

ort

cir

cuit

cu

rren

t (K

A)

100.0

90.0

80.0

70.0

60.0

50.0

40.0

30.0

20.0

10.0

9.0

8.0

7.0

6.0

5.0

4.0

3.0

2.0

1.0

16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 10000

Conductor: Copper

Insulation: PVC

Curves based on formula:

l = (0.115A÷ t )

Where:

l – Short circuit current (KA)

A- Conductor area (mm2)

t – Time of short circuit (seconds)

Conductor Size (mm2)

Page 38: Catalogue tai sin

38

Short Circuit ratings for power cables Technical Table 14.3

Cross- Sectional

Area

Short Circuit

Rating

for 1 second

Short Circuit

Rating

for 3 seconds

Another important factor for the determination of the conductor size is the maximum

allowable current during a short circuit when the maximum allowable current during a short circuit when the maximum allowable conductor temperature is higher than

during normal operation.

The maximum permissible short circuit current of XLPE cables up to 1Kv with copper conductors can be calculated with the formula:

Kt

Slk

Where l = Short Circuit rating (KA)

S = Conductor Area (sq mm)

t = Duration of Short Circuit (sec)

mm2 KA KA

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

630

800

1000

0.2145

0.3575

0.5720

0.8580

1.4300

2.2880

3.5750

5.0050

7.1500

10.0100

13.5850

17.1600

21.4500

26.4550

34.3200

42.9000

57.2000

71.5000

90.0900

114.4000

143.0000

0.1238

0.2064

0.3302

0.4954

0.8256

1.3210

2.0640

2.8896

4.1281

5.7793

7.8433

9.9073

12.3842

15.2738

19.8147

24.7683

33.0244

41.2805

52.0135

66.0489

82.5611

The above rating is calculated using the following formula:

t

Sl

143.0

Where l = Short Circuit rating (KA)

S = Conductor Area (sq mm) t = Duration of Short Circuit (sec)

Copper Conductor Technical Table 14.3

Cu

rren

t in

Kil

oa

mp

ers

Duration of Short circuit in Seconds

The values of fault current given in the graph are based on the cable being fully loaded at the start of the short circuit (conductor temperature 900c), and a final conductor

temperature of 2500c, and it should be ensured that the accessories associated with the cable are also capable of operation at these values of fault current.

Page 39: Catalogue tai sin

39

IN-POP, IN-POSP IN-PIOP, IN-PIOSP & IN-EOP, IN-EOSP IN-EIOP, IN-EIOSP Technical Table 15

1 . Test Voltage: 1000 Vr.m.s. for 1 minute between each conductor in turn and all other connected together

2 . Maximum DC Conductor Resistance at 200c

Conductor Size Multi-cores Multi-pairs

0.5 mm2

0.75 mm2

1.0 mm2

1.5 mm2

39.0

26.0

18.1

12.1

39.7

26.5

18.4

12.3

3. Minimum Insulation Resistance at 200c

PE Insulated PVC Insulated

Individual Conductor (between) each conductor and

Remaining bunched conductors/ screen and/ or armour

5000MΩ.km 25 MΩ.km

Individual Screens (between screens) 1 MΩ.km 1 MΩ.km

4. Maximum Mutual Capacitance at 1 KHz (pF/m)

Cable Type Conductor Size 0.5 mm2 1.0 mm2 1.5 mm2

PE Insulated Cables without individual pair screen 75 pF/m 75 pF/m 85 pF/m

PE Insulated All cables with individual pair screen, 1 and 2 pair cables collective screen 115 pF/m 115 pF/m 120 pF/m

PVC Insulated Pairs 250pF/m

5. Maximum Capacitance Between Any Core or Screen

PVC Insulated cables: 450 pF/m

6. Maximum Capacitance Unbalance at 1 KHz

PE Insulated cables: 250pF/ 250m

7. Maximum L/R Ratio (For Adjacent Cores)

Conductor Size Multi-cores

0.5 mm2

0.75 mm2

1.0 mm2

1.5 mm2

25 µH/Ω

25 µH/Ω

25 µH/Ω

40 µH/Ω

Maximum Conductor Resistance Technical Table 16 Electrical Characteristics Technical Table 16

Cross Section Area (S) Conductor for Fixied Wiring Class 1

(solid), Class 2 (stranded) Conductor Resistance Temperature Correction Factors

mm2 Temp0C Factor

0.50

0.75

1.00

1.50

2.50

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

630

800

1000

36.0

24.5

18.1

12.1

7.41

4.61

3.08

1.83

1.15

0.727

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

30

35

40

45

50

55

60

65

70

75

80

85

90

0.961

0.965

0.969

0.972

0.976

0.980

0.984

0.988

0.992

0.996

1.000

1.004

1.008

1.012

1.016

1.020

1.039

1.059

1.079

1.098

1.118

1.138

1.157

1.177

1.196

1.216

1.236

1.255

1.275

Page 40: Catalogue tai sin

40

(mm2 – CM – AWG/ MCM) Technical Table 18

Cross- sectional Area Conductor Size Cross- sectional Area Conductor Size

(mm2) (CM) (AWG/ MCM) (mm2) (CM) (AWG/ MCM)

0.324

0.519

0.653

0.823

*1.0

1.04

1.31

*1.5

1.65

2.08

*2.5

2.63

3.31

*4.0

4.17

5.261

*6.0

6.631

8.367

*10.0

10.55

13.3

*16.3

16.77

21.15

*25.0

26.67

33.62

*35.0

42.41

*50.0

53.49

67.43

*70.0

85.01

*95.0

640

1020

1290

1620

1974

2050

2580

2960

3260

4110

4934

5180

6530

7894

8230

10380

11841

13090

16510

19735

20820

26240

31576

33090

41740

49338

52620

66360

69073

83690

98675

105600

133100

138145

167800

187483

22

20

19

18

-

17

16

-

15

14

-

13

12

-

11

10

-

9

8

-

7

6

-

5

4

-

3

2

-

1

-

1/0

2/0

-

3/0

-

107.2

*120

127

*150

152

177

*185

203

228

*240

253

279

300

304

329

355

380

*400

405

456

*500

507

557

608

*630

633

659

709

760

*800

811

861

887

912

963

*1000

010

211600

236820

250000

296025

300000

350000

365098

400000

450000

473640

5000000

550000

592050

600000

650000

700000

750000

789400

800000

900000

986750

1000000

1000100

1000200

1243305

1250000

1300000

1400000

1500000

1578800

1600000

1700000

1750000

1800000

1900000

1973500

2000000

4/0

-

-250

-

300

350

-

400

450

-

500

550

-

600

650

700

750

-

850

900

-

1000

1100

1200

-

1250

1300

1400

1500

-

1600

1700

1750

1800

1900

-

2000

Note: * British standard

*127 mm2 and larger is rounded off and not actual. CM area is actual Conversion factors: mm2 x 1973.5 = CM x 0.0005067 = mm2.

AWG - America Wire Gauge. A standard measurement of the size of a conductor: 4/0 & smaller.

CM (Circular Mil) used to define cross-sectional areas of conductors. Area of circle 171000 inches in diameter. MCM – 1000 circular mils.