Catalog Thomas Betts
description
Transcript of Catalog Thomas Betts
Product CatalogueLighting, Boxes, Cabinets,
Conduits, Fittings & Accessories for Hazardous and Hostile Areas
Welcome toThomas & Betts
Introduction
2
At Thomas & Betts, our focus is on improving your business
performance by providing practical, reliable electrical
products & services. To connect & protect for life. To solve
everyday problems in the area’s of Wire & Cable Management,
Cable Protection, Power Connection & Control and Safety.
Our extensive engineering, supply chain management
and technical sales support teams are committed to
understanding everything that impacts your ability to
accomplish your business objectives by reducing your total
cost of ownership.
Whether you are designing, installing, operating, maintaining
or owning an offi ce building, off-shore platform, hospital,
or a high speed train, power generating plant, machine
equipment or a manufacturing facility, Thomas & Betts
engineered products fi t and function in your application
while providing superior performance, sustainability, and
value throughout the project life cycle.
All our brands are built upon four product & service
solution platforms. Platforms that address you or your
customers’ critical electrical & lighting needs covering the
protection of data, energy, processes, assets and personal
safety. Beyond hi-performance application characteristics,
Thomas & Betts products, information and services facilitate
and speed up your time critical assembly, installation or
maintenance process.
Thomas & Betts in Europe:
Contents
3
ContentsOil & Gas - Upstream Applications 4-5
Oil & Gas - Midstream Applications 6-7
Oil & Gas - Downstream Applications 8-9
Food & Beverage Applications 10
Chemical & Pharmaceutical Applications 11
World Standards & What They Mean 12-13
Zone Defi nitions - Onshore Gases & Vapours 14-15
Zone Defi nitions - Offshore Gases & Vapours 16
Zone Defi nitions - Dust 17
DTS - Product Marking Guide 18-19
Kopex Ex - Product Marking Guide 20-21
Index of Ingress Protection 22
Photometry 23
Ex Lighting Fittings 24-25
Lighting Fittings - Selection Guide 26-27
Ex Lighting
XFF Range - Ex d 28-29
XFP Range - Ex de 30-31
XEL Range - Ex d 32-33
XEP Range - Ex de 34-35
XF Range - Ex de 36-37
XFB / XFL Range - Ex n 38-39
XDF Range - Ex nA 40-41
EVS Range - Ex de 42-43
EVN Range - Ex n 44-45
EVD Range - Ex t 46-47
ESB Range - Ex de 48-49
Ex Emergency and Escape Lighting
XFF-EM Range - Ex d 50-51
XFP-EM Range - Ex de 52-53
XEL-BAES Range - Escape Lighting - Ex d 54-55
EVS-EM Range - Ex de 56-57
EVS-EMA Range - Ex de 58-59
EVN-EM Range - Ex n 60-61
EVN-EMA Range - Ex n 62-63
EVD-EM Range - Ex t 64-65
EVD-EMA Range - Ex t 66-67
ESB-EM Range - Ex de 68-69
Industrial Lighting 70-71
FF Range 72-73
EL Range 74-75
SF / QF / HF Range 76-77
EVT Range 78-79
EST Range 80-81
FB / FL Range 82-83
HF Range 84-85
Industrial Emergency Lighting
FR-EM / FF-EM Range 86-87
EVT-EM Range 88-89
EVT-EMA Range 90-91
EST-EM Range 92-93
Lighting Accessories & Spare Parts 94-99
Lamps Guide 100-103
Ex Boxes & Enclosures 104-105
Boxes & Enclosures - Selection Guide 106-107
XBL Range - XB100 Junction Boxes - GRP 108-109
XBL Range - Junction Boxes - GRP 110-111
XBL Range - Instrumentation Boxes - GRP 112-113
XBL-A Range - Control Boxes - GRP 114-115
XB Range - Instrumentation Boxes - Aluminium 116-117
XB-A Range - Control Boxes - Aluminium 118-119
XBi Range - Instrumentation Boxes - Stainless Steel 120-121
XBi-A Range - Control Boxes - Stainless Steel 122-123
GUV Range - Junction Boxes - Aluminium 124-125
EFDC / SRC / XMC Range - Control Boxes - Aluminium 126-127
EJB Range - Custom Built Panels - Aluminium 128-129
Box Accessories & Spare Parts 130-131
Conduit Systems 132-133
Conduit Fittings - Selection Guide 134-135
EXB / EXBB Range 136-137
EXBQM / EXPQA Range 138-139
EXLB / EXLT / EXLH / EXBBT / EXLHC Range 140-141
EXSB / EXST / EXSH / EXSBBT / EXSHC Range 142-143
G1 Gland / 90º Elbow Gland 144-145
Group II Gland 146-147
Universal & Universal Swivel Gland 148-149
PA / PAP NPT Range 150-151
PE / PEP ISO Range 152-153
PA-B / PAP-B NPT & ISO Range 154-155
XP Flex Range 156-157
Enlargers, Reducers & Thread Convertors 158-161
Ex d Stopping Plugs 162-163
Ex e Stopping Plugs 164-165
Accessories 166-167
INDEX 168-177
Thomas & Betts Worldwide Industrial Capabilities 178-179
Key of Symbols 180
Thomas & Betts • www.tnb-hazardous.com
4
Thomas & Betts • www.tnb-hazardous.com
Oil & Gas - Upstream Applications
The oil and gas market is split into three sectors Upstream,
Midstream and Downstream. Upstream consists of Exploration
and production both these areas offer very distinct and unique
challenges to people and equipment working within them.
Firstly there are offshore applications such as the drilling rigs
and production platforms; these are always open to extreme
weather conditions so equipment used here needs to be able to
withstand a salty environment. This is achieved through either
manufacturing product from stainless steel as is the
case for the Kopex-Ex conduit glands, and DTS enclosures, or
by ensuring that the product is coated or painted to withstand
marine environments as in the DTS XFF fl uorescent lighting.
Equipment in offshore applications also needs to be
hardwearing and easy to maintain as production downtime
can be extremely costly for example FPSO (Floating Production
Storage and Offl oading) vessel can produce up to 200,000
barrels of crude oil per day at approx $80 to $90 per barrel.
A breakdown would result in the vessel producing a loss of
revenue of over $700,000 and hour.
Industry Overview Approvals / Characteristics
Product Selection Issues• Salt water corrosion (offshore platforms)• Oil and chemical resistance (Drilling rig MUD)• Extreme ambient temperature (High temperature
Middle East / low temperature Russia)• Protection level• Connectivity to other pieces of equipment• Consequence of down time• Approval level required (Ex e, Ex d, etc.)• Approval specification required ATEX, IECEx,
UL, GOST, etc.• Where product will be positioned, e.g. Zone 1 or Zone 2
Oil & Gas - Upstream Applications
5
Thomas & Betts • www.tnb-hazardous.com
EXL Conduit 140 EJB Range 128 XFF Range 28
Related Products
Stopping Plugs 164
This has led to Kopex-Ex conduit systems being used in many
offshore applications to protect critical data and power cables
across these massive vessels, whether it is data cables from
a gas detector or the cable protection on a power transmission
unit, Kopex-Ex offers a whole range of products that are
tested and approved to many of the world standards.
DTS lighting on the other hand offers easy maintenance with
removable gear trays allowing the entire gear tray to be removed
and maintenance to be carried out quickly and safely. In fact
on the XFF Exd luminaries the components such as ballasts and
tubes are standard so the stocking and sourcing of spare parts is
made easy. Again essential to an offshore vessel.
Secondly onshore applications can also be split into exploration
and production. However onshore is more economically viable
than offshore with some wells only producing as few as a dozen
barrels of oil a day. However, they can become extremely
large with wells being networked together to produce up to
a million barrels of oil a day.
This brings with it a whole new series of challenges to be overcome.
Firstly the drilling rigs tend to be mobile with motors and pumps often
mounted on skids for easy transportation. This can lead to issues of
connectivity for which Kopex-Ex have a range of thread converters
in a variety of materials and approvals ready to resolve the problem.
Secondly with so many rigs in a network there is a massive
monitoring operation to be done to ensure that the fl ow of all
the rigs is ongoing and consistent. This is where the DTS range of
instrumentation boxes can offer great fl exibility as they can be
custom made to meet exact specifi cations.
The need to maintain fl ow also leads to the need for motors and
controls on the well heads themselves often referred to as “Christmas
Trees.” These are under high pressure and must be able to withstand
up to 1400 bar this is a critical area and has to be monitored closely
to ensure that pressure do not fl uctuate this is done by the valves
within the wellhead controlled by motors. DTS EJB enclosures can be
custom built to control these valves and at the same time monitor
the pressures and relay it back to the central control point.
6
Oil & Gas - Midstream Applications
Midstream relates to the transportation, storage and partial
processing of crude oil and gas from the wellheads to the refi ning
plants. This brings a different set of challenges to overcome.
This all relates to the fact that what is pumped out of the well
is not pure and often contains a mixture of oil, gas, water
and often sand which fi rstly need to be separated off from each
other before being shipped or piped to a storage facility.
This can be done in a variety of ways depending on the type of oil
or gas that the well is pumping and can often take up to 4 processes
before the commodity is separated out ready for piping or
shipping. These processes require energy and this energy is often
created from the commodity itself by the utilization of the gas.
Once the separating has been completed, the commodity can
then be moved to storage. In the case of an offshore rig this
separating is often done on shore away from the rig then
pumped to the storage depots. In the case of the FPSO vessels
it is all done on board and the oil transferred to tankers at
sea for delivery to storage depots.
Industry Overview Approvals / Characteristics
Product Selection Issues• Salt water corrosion (Tankers)• Extreme ambient temperature (High temperature Middle East / low temperature Russia)• Protection level• Consequence of down time• Approval level required (Ex e, Ex d, etc.)• Approval specification required ATEX, IECEx, UL, GOST etc• Where product will be positioned, e.g. Zone 1 or Zone 2
Thomas & Betts • www.tnb-hazardous.com
Oil & Gas - Midstream Applications
7
EFDC Range 126 EVS Range 42
Related Products
This is also the point when all metering needs to take place
to calculate invoices and taxes today. This is done very
accurately measuring not only the amount of oil produced but
also the density, viscosity, pressure and temperature, and in
the case of gas, the amount of water vapour.
Oil is often pumped direct to the oil refi nery which is where the
down stream operation starts but often needs to go through
a series of pumps to get the required pressure.
With the DTS and Kopex-Ex range of products, Thomas & Betts can
offer a range of products and services to meet the demands of
Midstream Oil and gas markets. The DTS range of lighting products
is manufactured to meet ATEX and IECEx standards. Designed
to be robust to meet the vigors of the environment whether it is on
oil tankers where the XFF product is ideal. To storage depots
where the EVS range of fl uorescents is often preferred. Added to
this all the fl uorescent lighting has been designed with the
installer and maintenance people in mind with removable gear
trays for easy safe installation and maintenance.
DTS also offers a wide range of standard and custom made
instrumentation boxes often used in the monitoring
equipment to relay signals from the sensors back to the central
control systems. As well as a range of standard confi guration
for control boxes including “Emergency Stop” and “On - Off”
to control motors etc. All of these are available in GRP,
aluminum and Stainless steel 316 therefore meeting any
environmental requirement.
Kopex-Ex conduits are used in many applications including to
protect the critical data cables feeding the information from
sensors to the instrumentation boxes as well as being used
on the compressors protecting the wiring where temperatures
can reach over 100ºC.
Thomas & Betts • www.tnb-hazardous.com
EXL Conduit 140 Stopping Plugs 164
8
Oil & Gas - Downstream Applications
The term downstream relates to the processing and delivery of
fi nished carbon related product to the end-user. This covers a whole
range of applications from Refi ning to petrol stations.
There are over 700 refi neries globally all competing to supply
fi nished carbon based products to local and international markets.
The products refi ned are varied including:
• Transportation fuels
LPG, gasoline, jet fuel, diesel, gas oil and bunker fuel.
• Petrochemical feedstocks
LPG, naphtha and aromatics.
• Energy sources
LPG, kerosene, heating oil and fuel oil.
• Specialities
Lubricants, bitumen, coke, solvents and waxes.
• Petrochemical feedstocks
Synthetic fi bres (nylon), plastics (polyethylene, PVC).
Industry Overview Approvals / Characteristics
Product Selection Issues• Continual Movement (CCTV)• Extreme ambient temperature (High temperature
Middle East / low temperature Russia and rail tankers)• Protection level• Consequence of down time• Approval level required (Ex e, Ex d, etc.)• Approval specification required ATEX, IECEx,
UL, GOST, etc.• Where product will be positioned, e.g. Zone 1 or Zone 2
Thomas & Betts • www.tnb-hazardous.com
Oil & Gas - Downstream Applications
9
XF Range 36
Related Products
The refi ning process is in four stages, fi rstly distillation which
separates it into 5 product sectors LPG, Naphtha, Kerosine, Gas,
Oil, and Atmospheric residue, this is done using high
temperature. The higher the temperature the higher the quality
of the product.
The second stage is the upgrading or reforming. This stage
is used to change the product at a molecular level for
example changing the low octane version of Naphtha to high
octane which can be blended into gasoline.
Stages three and four are about treating the product to
remove impurities such as sulphur and blending the refi ned
product into distinct products for the market.
The fi nal stage of the downstream process is delivery to the
market which involves storage and transportation. For example
in the case of aviation fuel this can be shipped direct to
airports by road or rail where it is stored, before transferring
to tanker trunks for the refuelling of aircraft.
All the stages in the downstream operation have different
requirements to ensure safety of personnel and the quality of
the end product. DTS and Kopex-Ex products are both used in
this area whether it is the XF fl oodlight range or EVS
fl uorescent range. They are all designed for easy maintenance.
There is also a range of instrumentation boxes either with
standard confi gurations or custom made to end-user
requirements, all of which are essential within a refi nery where
sensors play a key part on the process to ensure quality.
Kopex-Ex also plays a key part within the downstream market
not just used to protect the sensor cables but also for
security on CCTV all the way through to the cable protection
on rail tankers and tanker trucks.
Thomas & Betts • www.tnb-hazardous.com
EVS Range 42EXL Conduit 140 Stopping Plugs 164
10
Food Manufacture - Explosion Proof (Dust) Beverage Manufacture - Explosion Proof (Vapour)
Food Industry
Thomas & Betts offer a range of products for the food
processing market, including products for use in areas
where stainless steel is preferred as well as areas classed as
hazardous. Thomas & Betts can offer stainless steel
control stations for use on automated food processing and
packaging machines as well as lighting specifi cally designed
for use in dust fi lled atmospheres such as fl our mills or
other places where the risk of explosion is considered to
be extremely high.
Beverage Industry
Thomas & Betts has a range of products designed for use
in all beverage production sectors in the malting,
brewing, wine, spirits or soft drink business. DTS can supply
lighting products to suit the needs of hazardous areas
where explosive gases may occur or in areas where
cleanliness is required.
Food & Beverage Applications
Thomas & Betts • www.tnb-hazardous.com
Pharmaceutical Applications
11
Chemical Engineering - Explosion Proof Pharmaceutical Production - Explosion Proof
Chemical Industry
The chemical industry produces very diverse products,
everything from fertilizers to explosives such as
nitroglycerin. The processes used in this industry mean that
there are lots of applications for the DTS lighting and
box ranges. DTS can offer standard or custom built products,
whether it is for a process control station or for
instrumentation boxes linking sensors back to central
control panels.
Pharmaceutical Industry
The Thomas & Betts range of products and solutions is
ideal for use in the pharmaceutical Industry. Whether
it is upstream in the primary production stage or
downstream in the packing stage. Many of the processes
and applications used in these areas require approvals
to hazardous area standards making stainless steel junction
and control boxes ideal.
Chemical & Pharmaceutical Applications
Thomas & Betts • www.tnb-hazardous.com
12
Standards and what they mean
In this Section we will outline the different Standards used
throughout the world and what it means for products
specifi ed for use in Hazardous Areas. Below is a map of the
world which illustrates the Standards that are generally used in
these regions.
The ATEX Europe Directives 94/9/EC
ATEX requires employers to eliminate or control risks from
dangerous substances and to classify areas where explosive
atmospheres may occur into zones, as laid down in regulations.
ATEX Directives are designed to protect employees, the public
and the environment from accidents owing to explosive
atmospheres and since July 1st 2006 all existing sites, as well as
new sites, must be fully ATEX compliant.
Directive ATEX100a applies to equipment suppliers and
manufacturers and ATEX137 applies to end users. These
directives compliment each other, but have different purposes.
ATEX100A covers both electrical and non-electrical products
intended for use in hazardous areas, including mechanical
equipment. The Directive came into existence in 2003 and
products sold within the European Union designed for use in
hazardous areas must have ATEX certifi cation and bear the
World Standardsand what they mean
ATEX marking on the product or on a certifi cate plate. The
obligation is placed upon the manufacturer or supplier of the
product and the intention is to facilitate free movement of
goods within the EU.
Declaration of Conformance
This has to be issued by the supplier for every order which is
to be installed in a hazardous area. This document has to
show that the equipment supplied complies with the latest
harmonized standard.
UL CSA
Product Approvals
IECEx GOST INMETROATEX
Thomas & Betts • www.tnb-hazardous.com
13
World Standards
IECEx (International Scheme)
The IECEx scheme is an international certifi cate of
conformance for products used in a hazardous area.
This scheme provides:
a) A single certifi cation of conformity for manufacturers to
comply that includes:
i) Testing and assessment of products to a standard
including a full test report.
ii) Ongoing surveillance of manufacturers premises.
b) A fast-track process for countries where regulations still
require the issuing of national Ex certifi cates or approvals.
This scheme is in the process of being adopted by all the
known standards across the world but are all working to
various time scales.
UL (America) & CSA (Canada)
The American and Canadian standards are the only ones to
have different classifi cations and locations. ATEX & IECEx
work to Groups and Zones whereas the NEC & CEC works
to Classes and Divisions, there is no direct comparison
between the two. This means that it is imperative that the two
standards are not inter-changed within an area.
GOST (Russia)
GOST follows similar rules to that of IECEx as far as the
breakdown of the zones and other criteria are concerned.
However, the requirements for this country mean that
separate GOST markings are required on the product.
GOST is divided into GOST (R) which is the standard for Russian
Federation and GOST (K) that cover Kazakhstan.
Electrical materials for use in potentially explosive
atmospheres must conform to two major certifi cation
standards: IEC/CENELEC and NEC
The IEC (International Electrotechnical Commission) standards
are accepted in practically all countries. They are identical to
the European CENELEC standards.
The NEC (National Electrical Code) is mandatory in the
United States. The 1996 version, art. 505, takes up the IEC
designations for gas, temperature classes for materials and
zone defi nition.
Gases and vapours classifi cation
Gases are divided into four groups in the NEC (National
Electrical Code) and three groups for IEC/CENELEC. The groups
display the same hierachy of classifi cation of gases and vapour.
(See table on page 20).
Temperature classifi cation
The IEC and the NEC have also defi ned a temperature
classifi ciation for material used in zones at risk of explosion.
(See table on page 21).
Thomas & Betts • www.tnb-hazardous.com
FOR GASES & VAPOURS ZONE 0 Permanent / Frequent Place in which an explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas, vapour or mist is present continuously or for long periods, or frequently.
ZONE 1 Ocassional Site where an atmosphere consisting of a mixture of air and inflammable substances in the form of gas, vapour or mist is likely to arise occasionally during normal operation.
Zones for Onshore Gases & Vapours
Zone Defi nitions Onshore Gases & Vapours (as per ATEX 60079-10)
14
Thomas & Betts • www.tnb-hazardous.com
SAFETY ZONELow Explosion Risk
ZONE 2 Gas Irregular / Short Duration Place in which an explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas, vapour or mist is not likely to occur in normal operation but, if it does occur, will persist for a short period only.
15
Zones Explained
Thomas & Betts • www.tnb-hazardous.com
16
Zone Defi nitionsOffshore Gases & Vapours (as per ATEX 60079-10)
FOR GASES & VAPOURS ZONE 0 Permanent / Frequent Place in which an explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas, vapour or mist is present continuously or for long periods, or frequently.
SAFETY ZONELow Explosion Risk
ZONE 1 Ocassional Site where an atmosphere consisting of a mixture of air and inflammable substances in the form of gas, vapour or mist is likely to arise occasionally during normal operation.
ZONE 2 Gas Irregular / Short Duration Place in which an explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas, vapour or mist is not likely to occur in normal operation but, if it does occur, will persist for a short period only.
Zones for Offshore Gases & Vapours
Thomas & Betts • www.tnb-hazardous.com
17
Zones Explained
FOR DUST
ZONE 20 Permanent / Frequent Area in which an explosive atmosphere in the form of a cloud of combustible dust in air is present continuously, or for long periods, or frequently.
SAFETY ZONENo Explosion Risk
ZONE 21 Occasional Area in which an explosive atmosphere, in the form of a cloudof combustible dust in air is likely to occur, occasionally, in normal operation, ocassionally.
ZONE 22 Dust Irregular / Short Duration Area in which an explosive atmosphere, in the form of a cloud of combustible dust in air is not likely to occur in normal operation but, if it does occur, will persist for a short period only.
Zone Defi nitions Dust (as per ATEX 60079)
Zones for Dust
Thomas & Betts • www.tnb-hazardous.com
18
DTS - Classifi cation of equipmentfor use in potentially explosive atmospheres
Ex II 2 G Exe IIC T6/ 2 D Extb IIIC T85C IP66
U=415V/50Hz12/0116422
Gases or vapours
Subdivision of gases and vapours
Typicalzones
Temporary behaviour offlammable substances inhazardous places
Flammablesubstances
MethaneDusts
Required marking for installation
equipment equipmentgroup protection level
IIA
IIB
IIC
is present continuously or zone 0 II Gafor long periods or frequently
is likely to occur in normal zone 1 II Gboperation occasionally
is not likely to occur in normalopration but, if it does occur, will zone 2 II Gcpersist for a short period only
is present continuously or for zone 20 III Dafor long periods or frequently
is likely to occur in normal zone 21 III Dboperation occasionally
it is not likely to occur in normaloperation but, if it does occur, zone 22 III Dcwill persist for a short period only
- mines I Ma
- mines I Mb
Dusts
GasesVapours
Apparatus maybe used in group
Dust
IIIA Combustible FlyingsIIIB Non-Conductive DustIIIC Conductive Dust
ammonia ethyl alcohol galsoline acetaldehydemethane cyclohexane n-hexaneethane n-butanepropane
town gas, ethylene ethylene ethyl-etheracrylnitril ethylene glycol
oxide
sulphide ofethinehydrogencarbon(acetylene)
LCIE 11 ATEX 3050 X(Certification Number)
(Gas) (Dust)
(Serial No.)
Classification of hazardous areas European/IEC or NEC classifications
Product stamp detail
XB10-SI
19-21, avenue Henri Baudelet77831 Ozoir-la-Ferriere (France)
0081II
Thomas & Betts • www.tnb-hazardous.com
DTS Product Marking Guide
All applications
Control stations, motors, fuses,switchgear, power electronics
Installation materials, motors, luminaries
Measurement and control, automationtechnology, sensors, actuators
Switch- and control cupboards,analyse-apparatus, computers
Coils of motors or relays, solenoid valves
Transformers, relays, control stations,magnetic contactors
Capacitors, transformers
Product use depending on temperature class (T1 - T6).
See at the top - only for zone 2
Temperature Class (T) / Ignition Temperature
Restrictionfor using apparatus
Requirements Marking
Equipment without
Equipment with
-restriction
special condition Xmay be noted
Ex component,which is notintended to beused aloneand requiresadditionalcertification before
U
being used inhazardous area
-
Ex d
Ex e
Ex i
Ex p
Ex m
Ex o
450º
Ex q
Ex n
60079-0
60079-1
60079-7
60079-11
60079-2
60079-18
60079-6
60079-5
60079-15
General requirements
Flameproof enclosure
Increased safety
Intrinsic safety
Pressurisation
Encapsulation
Oil immersion
Powder filling
‘Non sparking’
For use in zone 0, 1, 2 / for use in zone 1, 2 Ex t 60079-31Dust atmospheres
IIA T1 Acetone 735ºIIA T1 Ammonia 630º
IIB T1 Carbon Monoxide 605ºIIA T1 Bensene 560º
IIC T1 Hydrogen 560ºIIA T1 Methane 537ºIIA T1 Toluene 535ºIIA T1 Styrene 490º
IIA T1 Propane 470ºIIA T1 1-Butene 455º
IIB T1 Butadiene 430º
IIB T2 Ethylene 425ºIIA T2 Butane 372ºIIA T2 Ethanol 363º
IIA T2 Butylalcohol 359ºIIB T2 Dimetylether 350º
IIC T2 Acetylene 305º
IIA T3 Nafta 290ºIIA T3 Hydrogen Sulphide 270º
IIA T3 Cyclohexane 259ºIIA T3 Hexane 233º
IIA T3 Heptane 215ºIIA T3 Kerosene 210º
IIA T3 Dekane 201º
IIB T4 Diethyl Ether 160º
IIC T6 Carbon Disulphide 95º
Application Marking EN/IEC standardType of protection
Protection technique
300º
200º
135º
100º
85º
T1 > 450º
T2 > 300º
T3 > 200º
T4 > 135º
T5 > 100º
T6 > 85º
600º
750º
19
Thomas & Betts • www.tnb-hazardous.com
20
Kopex-Ex - Classifi cation of equipmentfor use in potentially explosive atmospheres
CMPL I M2/II 2GD Exde I Mb Exde IIC Gb Extb IIIC Db
CLI.Div1.ABCD .CLII.Div1.EFG.
Gases or vapours
Subdivision of gases and vapours
Typicalzones
Temporary behaviour offlammable substances inhazardous places
Flammablesubstances
MethaneDusts
Required marking for installation
equipment equipmentgroup protection level
IIA
IIB
IIC
is present continuously or zone 0 II Gafor long periods or frequently
is likely to occur in normal zone 1 II Gboperation occasionally
is not likely to occur in normalopration but, if it does occur, will zone 2 II Gcpersist for a short period only
is present continuously or for zone 20 III Dafor long periods or frequently
is likely to occur in normal zone 21 III Dboperation occasionally
it is not likely to occur in normaloperation but, if it does occur, zone 22 III Dcwill persist for a short period only
- mines I Ma
- mines I Mb
Dusts
GasesVapours
Apparatus maybe used in group
Dust
IIIA Combustible FlyingsIIIB Non-Conductive DustIIIC Conductive Dust
ammonia ethyl alcohol galsoline acetaldehydemethane cyclohexane n-hexaneethane n-butanepropane
town gas, ethylene ethylene ethyl-etheracrylnitril ethylene glycol
oxide
sulphide ofethinehydrogencarbon(acetylene)
(Product stamp detail)
(Class & Divisions)
Classification of hazardous areas European/IEC or NEC classifications
Product stamp detail
CLI (Class I), Div1 Where ignitable concentrations of flammable gases, vapors or liquids are present within the atmosphere under normal operation conditions. CLI (Class I), Div2 Where ignitable concentrations of flammable gases, vapors or liquids arepresent within the atmosphere under abnormal operation conditions.Class I Areas Group A: Acetylene / Group B: Hydrogen / Group C: Propane & Ethylene / Group D: Benzene, Butane & Propane.
CLII (Class II), Div1 Where ignitable concentrations of combustible dusts are present within the atmosphere under normal operation conditions. CLII (Class II), Div2 Where ignitable concentrations of combustible dusts are present within the atmosphere under abnormal operation conditions. Class II Areas Group E: Metal Dust / Group F: Carbon & Charcoal / Group G: Flour, Starch, Wood & Plastic.
Thomas & Betts • www.tnb-hazardous.com
Kopex-Ex Product Marking Guide
IECEx SIRA09.0103 X
All applications
Control stations, motors, fuses,switchgear, power electronics
Installation materials, motors, luminaries
Measurement and control, automationtechnology, sensors, actuators
Switch- and control cupboards,analyse-apparatus, computers
Coils of motors or relays, solenoid valves
Transformers, relays, control stations,magnetic contactors
Capacitors, transformers
Product use depending on temperature class (T1 - T6).
See at the top - only for zone 2
Temperature Class (T) / Ignition Temperature
Restrictionfor using apparatus
Requirements Marking
Equipment without
Equipment with
-restriction
special condition Xmay be noted
Ex component,which is notintended to beused aloneand requiresadditionalcertification before
U
being used inhazardous area
-
Ex d
Ex e
Ex i
Ex p
Ex m
Ex o
450º
Ex q
Ex n
60079-0
60079-1
60079-7
60079-11
60079-2
60079-18
60079-6
60079-5
60079-15
General requirements
Flameproof enclosure
Increased safety
Intrinsic safety
Pressurisation
Encapsulation
Oil immersion
Powder filling
‘Non sparking’
For use in zone 0, 1, 2 / for use in zone 1, 2 Ex t 60079-31Dust atmospheres
IIA T1 Acetone 735ºIIA T1 Ammonia 630º
IIB T1 Carbon Monoxide 605ºIIA T1 Bensene 560º
IIC T1 Hydrogen 560ºIIA T1 Methane 537ºIIA T1 Toluene 535ºIIA T1 Styrene 490º
IIA T1 Propane 470ºIIA T1 1-Butene 455º
IIB T1 Butadiene 430º
IIB T2 Ethylene 425ºIIA T2 Butane 372ºIIA T2 Ethanol 363º
IIA T2 Butylalcohol 359ºIIB T2 Dimetylether 350º
IIC T2 Acetylene 305º
IIA T3 Nafta 290ºIIA T3 Hydrogen Sulphide 270º
IIA T3 Cyclohexane 259ºIIA T3 Hexane 233º
IIA T3 Heptane 215ºIIA T3 Kerosene 210º
IIA T3 Dekane 201º
IIB T4 Diethyl Ether 160º
IIC T6 Carbon Disulphide 95º
Application Marking EN/IEC standardType of protection
Protection technique
(Certification Number)
300º
200º
135º
100º
85º
T1 > 450º
T2 > 300º
T3 > 200º
T4 > 135º
T5 > 100º
T6 > 85º
600º
750º
New Marking - EPL’s (Explosion Protection Levels) The introduction of the EPL’s and changes in the EN 60079 series standard has introduced new marking requirements.
21
Thomas & Betts • www.tnb-hazardous.com
Index of Ingress Protection
22
IPxx suitability ratings are a system for classifying the
degree of protection provided by enclosures of electrical
equipment. The higher the number, the greater the
degree of protection, in accordance with standards
IEC 60529 and EN 60529.
Protection standrards
• Protection against solid bodies
• Protection against liquids
• Protection against impact a per EN 50102 standard
Protection against Solid Bodies Protection against Liquids
0
1
2
03
04
05
6
0
1
2
3
4
5
6
7
8
9
No protection
Protected against solid bodies of 50mm and greater, (e.g. accidental contact with the hand)
Protected against solid bodies of 12.5mm and greater, (e.g. accidental touch by fingers)
Protected against solid bodies of 2.5mm and greater, (e.g. tools and wires)
Protected against solid bodies of 1mm or greater, (e.g. thin tools and fine wires)
Protected against dust - limited ingress (no harmfull deposits)
Totally protected against dust(Dust-tight)
No protection
Protected against vertically falling drops of water (condensation)
Protected against drops of water falling up to 15º from the vertical
Protected against drops of water falling up to 60º from the vertical
Protected against splashing water from all directions
Protection against jets of water from all directions
Protection against powerful jets of water from all directions
The fi rst digit stands for protection against
solid bodies
The second digit stands for protection
against water
IP Classifi cation
Protected against the effects of temporary immersion in water
Protected against the continuous effects of immersion in water havingregard to specific conditions
IP69k Automotive standard DIN40050 signifies resistance to high pressure jets (up to 80bar) from any angle
Index ofIngress Protection
IP 6 77 =
Thomas & Betts • www.tnb-hazardous.com
Example: For a point situated at 60º from the vertical
of a luminaire, the luminous intensity is 27.78 cd in the
lamp’s transverse plane and 26.76 cd in the lamp’s
longitudinal plane (for a 1000 lm fl ux).
Note: the curve ‘integrates’ the lighting fi tting effi ciency, there
is no need to make corrections. However it is neccessary to
multiply the intensity given by the curve by the coeffi cient to
obtain the actual luminous fl ux of the chosen source.
Determination of the illuminance at a given point
A pinhole source of light placed on S at a distance d from a
point P on a surface plane creates an illuminance Ep whose
value is: Ep = where α is the angle forming the
direction Sp from which the luminous intensity comes with the
perpendicular n at P.
This formula is universal and allows the expression of values
of illuminance in horizontal, vertical or any other plane. The
example for a horizontal plane calculation is usually used for
practical reasons. In that case one speaks of a light source
situated at a height h above the plane. The illuminance at the
point P is expressed by the formula: EP =
Photometry
23
Photometric Units and Levels
• Luminous Flux: Symbol F
The amount of light emitted by a source by unit of time:
it’s the fl ow of light. This level is used to rate lamps
photometrically and is epressed in lumen (lm).
• Luminous Intensity: Symbol I
Is the quantity of luminous fl ux in a specifi c direction. The
unit of measurement is the Candela (cd). Values on the
photometric curves are expressed in candelas.
• Illuminance
The quantity of light falling on a unit area, expressed by
the formula: E= F/S, where F is the level of the luminous
fl ux reaching the surface and S is the area of that receiving
surface. The unit is lux (lx) which represents the level
of one lumen falling on a surface of one square metre.
When the surface S is large it is expressed as average
illuminance on the surface. This measurement is important
as it can be measured by a light meter and allow fi ttings
to be controlled.
Photometric Curves
A visual method of showing the luminous intensity distribution
of a lighting fi tting. Values are in candelas (cd). To enable
comparisons to be made for different fi ttings, the curve is
drawn for a 1000 lumen fl ux.
PhotometryPhotometric Data Explained
lcos α d2
lcos3 α h2
h
P
α
S
n
P
d
100110100
20 10 0 10 20
110
80
70
60
50
40
30
9090
80
70
60
50
40
30
0 . 6 8 H + 0 . 1 0 T
255075
100125150175200
Thomas & Betts • www.tnb-hazardous.com
26
Ex Lighting Range
Ex Lighting Fittings - Selection Guide
Thomas & Betts • www.tnb-hazardous.com
XFP Page 30
XEL Page 32
XEP Page 34
XFF Page 28
XDF Page 40
EVS Page 42
EVN Page 44
XF Page 36
EVD Page 46
ESB Page 48
Prot
ectio
n Ty
peG
asG
roup
sD
ust
Gro
ups
Zo
nes
Ex Lighting Fittings - Selection Guide
27
Ex Emergency & Escape Lighting Range
Thomas & Betts • www.tnb-hazardous.com
XFP-EM Page 52
XEL-BAES Page 54
EVS-EM Page 56
XFF-EM Page 50
EVN-EM Page 60
EVN-EMA Page 62
EVD-EM Page 64
EVS-EMA Page 58
EVD-EMA Page 66
ESB-EM Page 68
Approved to: EN60079-0, 60079-1, 60079-31 EC TYPE Examination Certificate:INERIS 11 ATEX 0051XEx II 2 GEx d IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (All Polycarbonate tubes)Ex d IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass tubes)Ex d IIB T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass versions - XFR140, XFR165, XFF240 and XFF265)Ex II 2 DEx tb IIIC T80°C Db IP66Glow wire test: 960ºC EN60598-2-22Safe operating temperature range: -20°C to +55ºC
Certifi cation & Standards
• Manufactured from marine grade aluminium• All components mounted on slide gear tray for easy installation and maintenance• Standard components used inside body allowing reduced maintenance costs• Available in Glass for paint shop and other spray applications for easy cleaning• Including accessories, cable gland & fixing brackets
Approvals / Characteristics Features
28
XFF RangeTubular fl uorescent fi tting
Thomas & Betts • www.tnb-hazardous.com
EXL Conduit 140
Ex lighting - XFF Range
Wiring Nominal Dimensions (mm)
Type Configuration Rating (W) Current (A) Diffuser A B Weight (kg)
XFR120-0G000 3 Wire 1 x 18 0.15 Polycarbonate 780 565 5.5
XFR136-0G000 3 Wire 1 x PL36 0.2 Polycarbonate 1385 1170 6
XFR140-0G000 3 Wire 1 x 36 0.2 Polycarbonate 1385 1170 9
XFR155-0G000 3 Wire 1 x PL55 0.25 Polycarbonate 1690 1475 6
XFR165-0G000 3 Wire 1 x 58 0.35 Polycarbonate 1690 1475 11
XFF220-0G000 3 Wire 2 x 18 0.3 Polycarbonate 780 565 6.5
XFF236-0G000 3 Wire 2 x PL36 0.4 Polycarbonate 1385 1170 6.5
XFF240-0G000 3 Wire 2 x 36 0.4 Polycarbonate 1385 1170 10
XFF255-0G000 3 Wire 2 x PL55 0.5 Polycarbonate 1690 1475 6.5
XFF265-0G000 3 Wire 2 x 58 0.5 Polycarbonate 1690 1475 12
XFR120V-0G000 3 Wire 1 x 18 0.15 Glass 780 565 7
XFR136V-0G000 3 Wire 1 x PL36 0.2 Glass 1385 1170 8
XFR140V-0G000 3 Wire 1 x 36 0.2 Glass 1385 1170 17
XFR155V-0G000 3 Wire 1 x PL55 0.25 Glass 1690 1475 8
XFR165V-0G000 3 Wire 1 x 58 0.35 Glass 1690 1475 17
XFF220V-0G000 3 Wire 2 x 18 0.3 Glass 780 565 8.5
XFF236V-0G000 3 Wire 2 x PL36 0.4 Glass 1385 1170 8.5
XFF240V-0G000 3 Wire 2 x 36 0.4 Glass 1385 1170 18
XFF255V-0G000 3 Wire 2 x PL55 0.5 Glass 1690 1475 8.5
XFF265V-0G000 3 Wire 2 x 58 0.5 Glass 1690 1475 20
Technical Specifi cations
29
Related Products
Dimensions
Spares & Fixings Accessories see pages 94-99
Stopping Plugs 162
EnclosureEnd caps according to standard: EN1706:EN AC-AISi12(Fe) DF or EN AC-AISi10Mg(a) DF marine grade aluminium Yellow polyurethane paint RAL 1003IP66 / IP67 IEC60529 if installed to manufacturersinstructionsFixingStandard: D023 - 2 Zinc Plated Steel articulated brackets for ceiling mounting
Rated voltagesElectronic ballast:AC/DC 220V-240V, 50-60HzFor other voltages contact SalesPower factorSuperior to 0.98Cable entriesStandard: Two entries 3/4” NPT includedOne 3/4” zinc chromed steel plug and One cable gland - 3/4” NPT Brass for non-armoured cable, diameter 8-10.5mm
Terminal block (plug in terminal block)Up to 10mm² (rigid wire), 6mm² (fl exible wire)Terminals supplied L, N, PELooping possibleLamps (order separately)T8 bi-pin G13 tube, Ø 26 - white industry 4000°KG11 compact fl uorescent PL lampOther optionsStainless steel shock proof kit 304LEnclosure: Offshore and other colours
GUV Range 124 PA NPT Gland 150
Thomas & Betts • www.tnb-hazardous.com
Approvals / Characteristics Features
30
XFP RangeTubular fl uorescent fi tting with
automatic switch off
Approved to: EN60079-0, 60079-1, 60079-7, EN61241-0, 61241-1 EC TYPE Examination Certificate:INERIS 11 ATEX 0052XEx II 2 GEx de IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (All Polycarbonate tubes)Ex de IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass tubes)Ex de IIB T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass versions - XFP140V, XFP165V, XFP240V and XFP265V)Ex II 2 DEx tD IIIC A21 IP6x T80°CGlow wire test: 960ºC EN60598-2-22Safe operating temperature range: -20°C to +55ºC
Certifi cation & Standards
• Manufactured from marine grade aluminium• All components mounted on slide gear tray for easy installation and maintenance• Maintenance in hazardous area is quick and easy with isolation switch for safe maintenance• Standard components used inside body allowing reduced maintenance costs• Available in Glass for paint shop and other spray applications for easy cleaning• Including accessories, cable gland & fixing brackets
Thomas & Betts • www.tnb-hazardous.com
EXL Conduit 140
Ex lighting - XFP Range
Technical Specifi cations
31
Related Products
Dimensions
Spares & Fixings Accessories see pages 94-99
Stopping Plugs 162
EnclosureEnd caps according to standard: EN1706:EN AC-AISi12(Fe) DF or EN AC-AISi10Mg(a) DF marine grade aluminiumYellow polyurethane paint RAL 1003FixingStandard: D023 - 2 Zinc Plated Steel articulated brackets for ceiling mounting
Rated voltagesStandard electronic ballast:AC/DC 220V-240V, 50-60HzFor other voltages contact SalesPower factorSuperior to 0.98Cable entriesStandard: M20 cable entry includedOne cable gland - Nickel Plated Brass ISO M20 for non-armoured cable, diameter 8-13mm
Terminal block (plug in terminal block)Up to 6mm² (rigid wire), 4mm² (fl exible wire)Lamps (order separately)T8 bi-pin G13 tube, Ø 26 - white industry 4000°KG11 compact fl uorescent PL lampOther optionsStainless steel shock proof kit 304LEnclosure: Offshore and other colours
Wiring Nominal Dimensions (mm)
Type Configuration Rating (W) Current (A) Diffuser A B Weight (kg)
XFP120-0G000 3 Wire 1 x 18 0.15 Polycarbonate 780 565 5.5
XFP136-0G000 3 Wire 1 x PL36 0.2 Polycarbonate 1385 1170 6
XFP140-0G000 3 Wire 1 x 36 0.2 Polycarbonate 1385 1170 9
XFP155-0G000 3 Wire 1 x PL55 0.25 Polycarbonate 1690 1475 6
XFP165-0G000 3 Wire 1 x 58 0.35 Polycarbonate 1690 1475 11
XFP220-0G000 3 Wire 2 x 18 0.3 Polycarbonate 780 565 6.5
XFP236-0G000 3 Wire 2 x PL36 0.4 Polycarbonate 1385 1170 6.5
XFP240-0G000 3 Wire 2 x 36 0.4 Polycarbonate 1385 1170 10
XFP255-0G000 3 Wire 2 x PL55 0.5 Polycarbonate 1690 1475 12
XFP265-0G000 3 Wire 2 x 58 0.5 Polycarbonate 1690 1475 12
XFP120V-0G000 3 Wire 1 x 18 0.15 Glass 780 565 7
XFP136V-0G000** 3 Wire 1 x PL36 0.2 Glass 1385 1170 8
XFP140V-0G000 3 Wire 1 x 36 0.2 Glass 1385 1170 17
XFP155V-0G000** 3 Wire 1 x PL55 0.25 Glass 1690 1475 8
XFP165V-0G000 3 Wire 1 x 58 0.35 Glass 1690 1475 17
XFP220V-0G000 3 Wire 2 x 18 0.3 Glass 780 565 8.5
XFP236V-0G000** 3 Wire 2 x PL36 0.4 Glass 1385 1170 8.5
XFP240V-0G000** 3 Wire 2 x 36 0.4 Glass 1385 1170 18
XFP255V-0G000** 3 Wire 2 x PL55 0.5 Glass 1690 1475 18
XFP265V-0G000 3 Wire 2 x 58 0.5 Glass 1690 1475 20
**T5 for gas or T95ºC for dust when supply is 240V AC
GUV Range 124 PA Metric Gland 150
Thomas & Betts • www.tnb-hazardous.com
• Manufactured from marine grade aluminium• All components mounted on the gear tray for easy installation and maintenance• Standard components used inside the body allowing reduced maintenance costs• Available in Glass for paint shop and other spray applications for easy cleaning• Including accessories, cable gland & fixing brackets
Approvals / Characteristics Features
32
XEL RangeMiniature tubular fl uorescent fi tting
Approved to: EN60079-0, 60079-1, 60079-7, 60079-31EC TYPE Examination Certificate:INERIS II ATEX 0051XEx II 2 GEx d IIC T6 GbEx II 2 DEx tb IIIC T80°C Db IP66Glow wire test: 960ºC EN60598-2-22Safe operating temperature range: -20°C to +55ºC
Certifi cation & Standards
Thomas & Betts • www.tnb-hazardous.com
Ex lighting - XEL Range
Technical Specifi cations
33
EnclosureEnd caps according to standard: EN1706:EN AC-AISi12(Fe) DF or EN AC-AISi10Mg(a) DF marine grade aluminiumYellow polyurethane paint RAL 1003FixingStandard: D023 - 2 Zinc Plated Steel articulated brackets for ceiling mounting
Rated voltagesStandard electronic ballast: AC/DC 220-240V, 50-60HzPower factor0.9 with capacitor included in all modelsCable entriesXEL: Two entries 3/4” NPT includedOne 3/4” stopping plug and One cable gland - 3/4” NPT Brass for non-armoured cable, diameter 8-10.5mm
Terminal blockUp to 10mm² (rigid wire), 6mm² (fl exible wire)Terminals supplied for L, N, PE loopingLamps (order separately)T5 bi-pin G5 tubes, Ø 16 coolwhite 4000°KCompact fl uorescent PL lamp with G11 base (18W) or G23 (7W, 9W, 11W)Other optionsStainless steel shockproof kit 304LEnclosure: Offshore and other colours
Dimensions
Wiring Nominal Dimensions (mm)
Type Configuration Rating (W) Current (A) Diffuser A B Weight (kg)
XEL3008-0G000 3 Wire 1 x 8 0.1 Polycarbonate 780 565 5
XEL3009-0G000 3 Wire 1 x PL9 0.1 Polycarbonate 780 565 9
XEL30011-0G000 3 Wire 1 x PL11 0.1 Polycarbonate 780 565 5
XEL120-0G000 3 Wire 1 x PL18 0.1 Polycarbonate 780 565 4.5
XEL220-0G000 3 Wire 2 x PL18 0.1 Polycarbonate 780 565 5
XEL30028-0G000 3 Wire 2 x 8 0.1 Polycarbonate 780 565 5
XEL3008V-0G000 3 Wire 1 x 8 0.1 Glass 780 565 7
XEL3009V-0G000 3 Wire 1 x PL9 0.1 Glass 780 565 9
XEL30011V-0G000 3 Wire 1 x PL11 0.1 Glass 780 565 7
XEL120V-0G000 3 Wire 1 x PL18 0.1 Glass 780 565 6.5
XEL220V-0G000 3 Wire 2 x PL18 0.1 Glass 780 565 7
XEL30028V-0G000 3 Wire 2 x 8 0.1 Glass 780 565 7
EXL Conduit 140
Related Products
Spares & Fixings Accessories see pages 94-99
Stopping Plugs 162 GUV Range 124 PA NPT Gland 150
Thomas & Betts • www.tnb-hazardous.com
Approvals / Characteristics Features
34
Approved to: EN60079-0, 60079-1, 60079-7, EN61241-0, 61241-1EC TYPE Examination Certificate:INERIS II ATEX 0052XEx II 2 GEx de IIC T6 GbEx II 2 DEx tD A21 IP66 T80ºCGlow wire test: 960ºC EN60598-2-22Safe operating temperature range: -20°C to +55ºC
Certifi cation & Standards
Thomas & Betts • www.tnb-hazardous.com
• Manufactured from marine grade aluminium• All components mounted on the gear tray for easy installation and maintenance• Standard components used inside the body allowing reduced maintenance costs• Available in Glass for paint shop and other spray applications for easy cleaning• Maintenance in hazardous area - quick and easy isolation switch for safe maintenance in hazardous area• Including accessories, cable gland & fixing brackets
XEP RangeMiniature tubular fl uorescent fi tting
with automatic switch off
Ex lighting - XEP Range
Technical Specifi cations
35
EnclosureEnd caps according to standard: EN1706:EN AC-AlSi12(Fe) DF or EN AC-AlSi10Mg(a) DF marine grade aluminiumYellow polyurethane paint RAL 1003FixingStandard: D023 - 2 Zinc Plated Steel articulated brackets for ceiling mounting
Rated voltagesStandard electronic ballast: AC/DC 220-240V, 50-60HzPower factorSuperior to 0.98Cable entriesOne M20 cable entry includedOne cable gland - Nickel Plated Brass ISO M20 for non-armoured cable, diameter 8-13mm
Terminal blockUp to 6mm² (rigid wire), 4mm² (fl exible wire)Terminals supplied for L, N, PELamps (oder separately)T5 bi-pin G5 tubes, Ø 16 coolwhite 4000°KCompact fl uorescent PL lamp with G11 base (18W) or G23 (7W, 9W, 11W)Other optionsStainless steel shockproof kit 304L (factory fi tted)Enclosure: Offshore and other colours
Dimensions
Wiring Nominal Dimensions (mm)
Type Configuration Rating (W) Current (A) Diffuser A B Weight (kg)
XEP3008-0G000 3 Wire 1 x 8 0.1 Polycarbonate 780 565 5
XEP3009-0G000 3 Wire 1 x PL9 0.1 Polycarbonate 780 565 5
XEP30011-0G000 3 Wire 1 x PL11 0.1 Polycarbonate 780 565 5
XEP120-0G000 3 Wire 1 x PL18 0.1 Polycarbonate 780 565 4.5
XEP220-0G000 3 Wire 2 x PL18 0.1 Polycarbonate 780 565 5
XEP30028-0G000 3 Wire 2 x 8 0.1 Polycarbonate 780 565 5
XEP3008V-0G000 3 Wire 1 x 8 0.1 Glass 780 565 7
XEP3009V-0G000 3 Wire 1 x PL9 0.1 Glass 780 565 7
XEP30011V-0G000 3 Wire 1 x PL11 0.1 Glass 780 565 7
XEP120V-0G000 3 Wire 1 x PL18 0.1 Glass 780 565 6.5
XEP220V-0G000 3 Wire 2 x PL18 0.1 Glass 780 565 7
XEP30028V-0G000 3 Wire 2 x 8 0.1 Glass 780 565 7
EXL Conduit 140
Related Products
Spares & Fixings Accessories see pages 94-99
Stopping Plugs 162 GUV Range 124 PA Metric Gland 150
Thomas & Betts • www.tnb-hazardous.com
• Compact, lightweight and robust
• Ex e integral juction box: easy connection
• Excellent photometric properties, wide or narrow beam
• Internationally recognised
• Supplied with lamp installed and cable gland
Approvals / Characteristics Features
36
XF RangeFloodlight fi ttings
Approved to: EN60079-0, 60079-1, 60079-7EC TYPE Examination Certificate:LCIE 00 ATEX 6019X / IECEx LCI 11-0062XEx II 2 GEx de IIB T1 to T5 Gb for ≤ -20ºC to ≤ +60ºCdepending on model
Certifi cation & Standards
Thomas & Betts • www.tnb-hazardous.com
EXL Conduit 140
Ex lighting - XF Range
Nominal Temperature Class
Type Mounting Rating (W) Current (A) Version -20ºC to +40ºC -20ºC to +60ºC Weight (kg)
XSF70P-00000 Flat 1 x 70 0.4 HP Sodium T4 T3 17
XSF70G-00000 Pole 1 x 70 0.4 HP Sodium T4 T3 17
XSF150P-00000 Flat 1 x 150 0.8 HP Sodium T4 T3 17
XSF150G-00000 Pole 1 x 150 0.8 HP Sodium T4 T3 17
XSF250P-00000 Flat 1 x 250 1.3 HP Sodium T3 T3 18
XSF250G-00000 Pole 1 x 250 1.3 HP Sodium T3 T3 18
XSF400P-00000 Flat 1 x 400 2.1 HP Sodium T3 T2 20
XSF400G-00000 Pole 1 x 400 2.1 HP Sodium T3 T2 20
XQF250P-00000 Flat 1 x 250 1.3 Metal Halide T3 T2 20
XQF250G-00000 Pole 1 x 250 1.3 Metal Halide T3 T3 18
XQF400P-00000 Flat 1 x 400 2.1 Metal Halide T3 T3 18
XQF400G-00000 Pole 1 x 400 2.1 Metal Halide T3 T2 20
XEF110P-00000 Flat 2 x 55 9.2 Halogen (12V) T5 T5 13
XEF110G-00000 Pole 2 x 55 9.2 Halogen (12V) T5 T5 13
XEF140P-00000 Flat 2 x 70 5.8 Halogen (24V) T5 T5 13
XEF140G-00000 Pole 2 x 70 5.8 Halogen (24V) T5 T5 13
Technical Specifi cations
37
Related Products
EnclosureMarine grade aluminium alloy type according to EN1706:EN AC-AlSi7 Mg 0,6 T6Cataphoretically treated - yellow polyester paint RAL 1003 12mm toughened glass
Rated voltagesVersion HPS/metal halide:Standard: 230V 50Hz ferromagnetic ballast,with capacitorFor other voltages contact SalesPower factor0.85 for version with compensated ballast (Sodium HP and metal halide)Cable entriesStandard: Two entries M20 included One Nickel Plated Brass M20 cable gland withfi xing fl ange for non-armoured cable, Ø 8-13mm and One M20 Nickel Brass plug
Terminal blockUp to 6mm² (rigid wire), 4mm² (fl exible wire)Lamps (Installed)Polished aluminium refl ectorStandard:wide beamFixingStandard:galvanised steel fl at mounting bracket, yellow polyester paint RAL1003Pole mounted: Ø 40 to 60mm
Dimensions
Spares & Fixings Accessories see pages 94-99
Stopping Plugs 164 GUV Range 124
Standard Flat Pole Mounting
PA Metric Gland 150
Thomas & Betts • www.tnb-hazardous.com
• Lightweight and robust for easy installation
• Static or flashing versions available for use in a
variety of applications
• Choice of 5 colours
• 2 or 3 light versions available for traffic signals
• Supplied with single cable gland and lamps installed
Approvals / Characteristics Features
38
XFB / XFL RangeWarning lights and beacons
Approved to: EN60079-0, 60079-15, 60079-31EC TYPE Examination Certificate:Ex II 3 G / DEx nA IIC T5 GcEx tc IIIC T100ºC DC IP6X for ≤ -20ºC to ≤ +60ºC
Certifi cation & Standards
Thomas & Betts • www.tnb-hazardous.com
Type Rating (W) Lamp Version Weight (kg)
XFB30-00000 1 x 28 E27 Halogen 3.5
XFB70-00000 1 x 8 E27 LED 3.5
XFL30P-00000 30 Joules Picots Xenon flash 4
Ex lighting - XFB / XFL Range
Technical Specifi cations
39
EnclosureMarine grade aluminium alloy type EN1706 AC-43100KF-AlSi 10MgYellow polyurethane paint RAL1003Aluminium refl ectorTemperatureAmbient temperature: -20°C to +60°C
Rated voltagesHalogen AC: 230V, 50-60HzLED AC: 100-240V, 50-60HzXenon Flash AC: 230V, 50-60HzCable entriesStandard: Two entries M20 includedOne plug and one cable gland - Nickel ISO M20 for non-armoured cable, diameter 8-13mmTerminal blockUp to 6mm2
Terminals supplied for L, N,P, E.
Lamps (supplied)For xenon fl ash versionsFlashing rate: 45 to 60 - per minuteGlobe3mm thick polycarbonateStandard: RedOption: Green, Orange / Yellow, Blue, Transparent
Dimensions
Related Products
Spares & Fixings Accessories see pages 94-99
EXL Conduit 140 Stopping Plugs 164 GUV Range 124 Thread Convertors 158
Thomas & Betts • www.tnb-hazardous.com
Contact Sales for Mounting Options8
Approvals / Characteristics Features
40
XDF RangeDrilling fl uorescent fi tting
Approved to: EN60079-0, 60079-15EC TYPE Examination Certificate:Ex II 3 G / DEx nA IIC T4 GcEx tc IIIC T135ºC Dc IP6X Temperature range: -20ºC to +60ºC
Certifi cation & Standards
Thomas & Betts • www.tnb-hazardous.com
X
• Vibration resistant lighting system
• Plug in system for fast installation
• Designed to minimise heat build up and overheating
• Corrosion resistant ideal for marine applications
• Hazardous and safe area versions available
Wiring Nominal
Type Configuration Rating (W) Current (A) Diffuser A B Weight (kg)
XDF140-00000 3 Wire 1 x 36 0.20 Polycarbonate 1173 1540 8.5
XDF165-00000 3 Wire 1 x 58 0.35 Polycarbonate 1474 1841 9
Ex lighting - XDF Range
Technical Specifi cations
41
EnclosureEnd caps according to standard: EN1706:EN AC-AISi12(Fe) DF or EN AC-AISi10Mg(a) DF marine grade aluminium Including offshore optionYellow polyurethane paint RAL 1003
Rated voltagesFerromagnetic ballast:230V, 50HzCable entriesStandard: Three M20 cable entriesSupplied with: One plug entry: male - 2 poles & earth - 10Amp - 250VACOne socket entry: female - 2 poles & earth -10 Amp - 250VACOne extendable cable with male plug and female socket (Helical cable) expandable to 5 metre max
Terminal block (plug in terminal block)Up to 6mm² (fl exible wire)Terminals supplied L, N, PELamps (supplied on request)T8 bi-pin G13 tube, Ø 26 - white industry 4000°KFixing2 Brackets for beam clamp fi xing
Dimensions
Related Products
Spares & Fixings Accessories see pages 94-99
EXL Conduit 140 Stopping Plugs 164 GUV Range 124
Thomas & Betts • www.tnb-hazardous.com
264
B
A 80
145
108
145
108
11
155 220
Must be used with XD104RContact Sales for further details
• Easy disconnector for safer maintenance out of zones • Main body constructed of a GRP for high impact strength• Polycarbonate diffuser to resist harsh environments• Automatic switch off upon opening for safe maintenance• All components mounted on hinged and removable gear tray which gives easy access for intallation and maintenance• Including accessories, cable gland & fixing brackets
Approvals / Characteristics Features
42
EVS RangeFluorescent fi tting with easy disconnect
Approved to: EN60079-0, 60079-1, 60079-5, 60079-7, EN61241-1EC TYPE Examination Certificate:LCIE 11 ATEX 3065X IEC Ex LCI 11.0053XEx II 2 GEx de IIC T4 Gb for ≤ -40ºC to ≤ +60ºCEx de IIC T5 Gb for ≤ -40ºC to ≤ +35ºCEx II 2 DEx tD IIIC A21 T85ºC Db IP64Glow wire test: 960ºC EN60598-2-22Safe operating temperature range: -20°C to +50ºC
Certifi cation & Standards
4
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 136 Nylon Stopping Plugs 164
Exe Nylon Gland 166
Ex lighting - EVS Range
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Current (A) A B C Weight (kg)
EVS120-0000 3 Wire Loop 1 x 18 0.09 785 432 400 5.5
EVS120-A000 5 Wire Loop 1 x 18 0.09 785 432 400 5.5
EVS120-B000 5 Wire Through 1 x 18 0.09 785 432 400 5.5
EVS140-0000 3 Wire Loop 1 x 36 0.17 1370 900 700 7.5
EVS140-A000 5 Wire Loop 1 x 36 0.17 1370 900 700 7.5
EVS140-B000 5 Wire Through 1 x 36 0.17 1370 900 700 7.5
EVS165-0000 3 Wire Loop 1 x 58 0.26 1670 900 700 9
EVS165-A000 5 Wire Loop 1 x 58 0.26 1670 900 700 9
EVS165-B000 5 Wire Through 1 x 58 0.26 1670 900 700 9
EVS220-0000 3 Wire Loop 2 x 18 0.17 785 432 400 6.5
EVS220-A000 5 Wire Loop 2 x 18 0.17 785 432 400 6.5
EVS220-B000 5 Wire Through 2 x 18 0.17 785 432 400 6.5
EVS240-0000 3 Wire Loop 2 x 36 0.33 1370 900 700 8.5
EVS240-A000 5 Wire Loop 2 x 36 0.33 1370 900 700 8.5
EVS240-B000 5 Wire Through 2 x 36 0.33 1370 900 700 8.5
EVS265-0000 3 Wire Loop 2 x 58 0.5 1670 900 700 10
EVS265-A000 5 Wire Loop 2 x 58 0.5 1670 900 700 10
EVS265-B000 5 Wire Through 2 x 58 0.5 1670 900 700 10
*EVS... C000 - 3 Wire loop & continuity plate*EVS... E000 - 5 Wire through & 2 continuity plates
Technical Specifi cations
43
Related Products
EnclosureFibreglass reinforced polyester bodyPolycarbonate diffuser EPDM cellular gasketsFixingStandard: V015 - 2 Zinc Plated Steel brackets for ceiling mounting
Rated voltagesStandard: electronic ballast AC 220-240V, 50-60HzDC 220-240VFor other voltages contact SalesPower factorSuperior to 0.98Cable entriesStandard: Three M20 entries includedTwo M20 Nylon plugs and One cable gland - ISO M20 Nylon, diameter 8-13mm for non-armoured cableFor armoured cable - continuity plate option:Nickel Brass cable gland (1 or 2 according to number of plates)
Terminal blockUp to 4mm² (rigid wire), 2.5mm² (fl exible wire)Lamps (order separately)Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
170
137
Dimensions
Spares & Fixings Accessories see pages 94-99
XB100 Range 108
Thomas & Betts • www.tnb-hazardous.com
• Main body constructed of a GRP for high impact strength• Polycarbonate diffuser to resist harsh and corrosive environments• All components mounted on hinged and removable gear tray which gives easy access for installation and maintenenace• Including accessories, cable gland & fixing brackets
Approvals / Characteristics Features
44
EVN RangeFluorescent fi tting with diffuser
Approved to: EN60079-0, 60079-15, EN61241-1EC TYPE Examination Certificate: Under new 94/9/EC self certifiedEx II 3 GEx nr IIC T4 Gb for ≤ -40ºC to ≤ +60ºCEx nr IIC T6 Gb for ≤ -40ºC to ≤ +35ºCEx II 3 DEx tD IIIC A22 T85ºC to T135ºC Db IP6xGlow wire test: 960ºC EN60598-2-22Safe operating temperature range: -20°C to +50ºC
Certifi cation & Standards
4
Thomas & Betts • www.tnb-hazardous.com
Ex lighting - EVN Range
Technical Specifi cations
45
Related Products
EnclosureFibreglass reinforced polyester bodyPolycarbonate diffuser EPDM cellular gasketFixingStandard: V015 - 2 Zinc Plated Steel brackets for ceiling mounting
Rated voltagesStandard: electronic ballast AC 220-240V, 50-60HzDC 220-240VFor other voltages contact SalesPower factorSuperior to 0.98Cable entriesStandard: Three M20 cable entries includedTwo M20 Nylon plugs and One cable gland - ISO M20 Nylon, diameter 8-13mm for non-armoured cableFor armoured cable - continuity plate option: Nickel Brass cable gland (1 or 2 according to number of plates)
Terminal blockUp to 6mm² (rigid wire), 4mm² (fl exible wire)Lamps (order separately)Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
170
137
Dimensions
Spares & Fixings Accessories see pages 94-99
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Current (A) A B C Weight (kg)
EVN120-0000 3 Wire Loop 1 x 18 0.09 785 432 400 4.2
EVN120-A000 5 Wire Loop 1 x 18 0.17 785 432 400 4.2
EVN120-B000 5 Wire Through 1 x 18 0.17 785 432 400 4.2
EVN140-0000 3 Wire Loop 1 x 36 0.17 1370 900 700 6.5
EVN140-A000 5 Wire Loop 1 x 36 0.17 1370 900 700 6.5
EVN140-B000 5 Wire Through 1 x 36 0.17 1370 900 700 6.5
EVN165-0000 3 Wire Loop 1 x 58 0.26 1670 900 700 8
EVN165-A000 5 Wire Loop 1 x 58 0.26 1670 900 700 8
EVN165-B000 5 Wire Through 1 x 58 0.26 1670 900 700 8
EVN220-0000 3 Wire Loop 2 x 18 0.17 785 432 400 4.5
EVN220-A000 5 Wire Loop 2 x 18 0.17 785 432 400 4.5
EVN220-B000 5 Wire Through 2 x 18 0.17 785 432 400 4.5
EVN240-0000 3 Wire Loop 2 x 36 0.33 1370 900 700 6.8
EVN240-A000 5 Wire Loop 2 x 36 0.33 1370 900 700 6.8
EVN240-B000 5 Wire Through 2 x 36 0.33 1370 900 700 6.8
EVN265-0000 3 Wire Loop 2 x 58 0.5 1670 900 700 8.5
EVN265-A000 5 Wire Loop 2 x 58 0.5 1670 900 700 8.5
EVN265-B000 5 Wire Through 2 x 58 0.5 1670 900 700 8.5
*EVN... C000 - 3 Wire loop & continuity plate*EVN... E000 - 5 Wire through & 2 continuity plates
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 138 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
46
EVD RangeFluorescent fi tting
• Main body constructed of a GRP for high impact strength
• Polycarbonate diffuser to resist harsh and
corrosive environments
• All componets mounted on hinged and removable gear tray
which gives easy access for installation and maintenance
• Including accessories, cable gland & fixing brackets
Approvals / Characteristics Features
Approved to: EN60079-0, 60079-31EC TYPE Examination Certificate: Under new 94/9/EC self certifiedLCIE II ATEX 3092XIECEx LCI 11.0064XEx II 2 DEx t IIIC T82ºC (≤ +60ºC) DbEx t IIIC T62ºC (≤ +40ºC) DbGlow wire test: 960ºC EN60598-2-22Safe operating temperature range: -40°C to +60ºC
Certifi cation & Standards
4
Thomas & Betts • www.tnb-hazardous.com
Ex lighting - EVD Range
Technical Specifi cations
47
Related Products
EnclosureFibreglass reinforced polyester bodyPolycarbonate diffuserEPDM cellular gasketFixingStandard: V015 - 2 Zinc Plated Steel brackets for ceiling mounting
Rated voltagesStandard: electronic ballast AC/DC 220-240V, 50-60HzFor other voltages contact SalesPower factorSuperior to 0.98Cable entriesStandard: Three M20 cable entries included Two M20 Nylon plugs andOne cable gland - ISO M20 Nylon, diameter 8-13mm for non-armoured cableFor armoured cable - continuity plate option: Nickel Brass cable gland (1 or 2 according to number of plates)
Terminal blockUp to 6mm² (rigid wire), 4.5mm² (fl exible wire)Terminals supplied for L1, L2, L3, N, PE (1 max 16A)Lamps (order separately)Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
170
137
Dimensions
Spares & Fixings Accessories see pages 94-99
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Current (A) A B C Weight (kg)
EVD120-00J0 3 Wire Loop 1 x 18 0.09 785 432 400 4.2
EVD120-A0J0 5 Wire Loop 1 x 18 0.09 785 432 400 4.2
EVD120-B0J0 5 Wire Through 1 x 18 0.09 785 432 400 4.2
EVD140-00J0 3 Wire Loop 1 x 36 0.17 1370 900 700 6.5
EVD140-A0J0 5 Wire Loop 1 x 36 0.17 1370 900 700 6.5
EVD140-B0J0 5 Wire Through 1 x 36 0.17 1370 900 700 6.5
EVD165-00J0 3 Wire Loop 1 x 58 0.26 1670 900 700 8
EVD165-A0J0 5 Wire Loop 1 x 58 0.26 1670 900 700 8
EVD165-B0J0 5 Wire Through 1 x 58 0.26 1670 900 700 8
EVD220-00J0 3 Wire Loop 2 x 18 0.17 785 432 400 4.5
EVD220-A0J0 5 Wire Loop 2 x 18 0.17 785 432 400 4.5
EVD220-B0J0 5 Wire Through 2 x 18 0.17 785 432 400 4.5
EVD240-00J0 3 Wire Loop 2 x 36 0.33 1370 900 700 6.8
EVD240-A0J0 5 Wire Loop 2 x 36 0.33 1370 900 700 6.8
EVD240-B0J0 5 Wire Through 2 x 36 0.33 1370 900 700 6.8
EVD265-00J0 3 Wire Loop 2 x 58 0.5 1670 900 700 8.5
EVD265-A0J0 5 Wire Loop 2 x 58 0.5 1670 900 700 8.5
EVD265-B0J0 5 Wire Through 2 x 58 0.5 1670 900 700 8.5
*EVD... C0J0 - 3 Wire loop & continuity plate*EVD... E0J0 - 5 Wire through & 2 continuity plates
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 138 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
• Main body made from powder coated steel
• 6mm toughened glass making it perfect
for laboratories
• Automatic switch off upon opening
for safe maintenance
• Including accessories & cable gland
Approvals / Characteristics Features
48
ESB RangeRecessed fl uorescent fi tting
Approved to: EN60079-0, 60079-1, 60079-7EC TYPE Examination Certificate: Under 94/9/EC INERIS II ATEX 0058XEx II 2 GEx de IIC T4 Gb for ≤ -20ºC to ≤ +40ºCGlow wire test: 850°C EN60598-2-22Safe operating temperature range: -20°C to +40ºC
Certifi cation & Standards
5
Thomas & Betts • www.tnb-hazardous.com
Ex lighting - ESB Range
Technical Specifi cations
49
Related Products
EnclosureSteel housing and body painted in white polyester powderpaint RAL 9016 6mm clear toughened glass panel (optional frosted low lumen output) Neoprene gasket
Rated voltagesStandard: electronic ballast AC/DC 220-240V, 50-60HzFor other voltages contact SalesPower factorSuperior to 0.98Cable entriesTwo M20 cable entries includedOne M20 Nylon stopping plug and One cable gland - ISO M20 Nylon, diameter 8-13mm for non-armoured cable
Terminal blockUp to 4mm² (rigid wire), 2.5mm² (fl exible wire)Terminals supplied for L, N, PELamps (order separately)Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k FixingFixing by 4 M6 threaded bolts (not supplied) joined to the main body
Dimensions
Spares & Fixings Accessories see pages 94-99
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Current (A) Glass A B C Weight (kg)
ESB220-0000 3 Wire 2 x 18 0.17 Toughened 753 702 105 12.5
ESB220-A000 3 Wire 2 x 18 0.17 Frosted 753 702 105 12.5
ESB240-0000 3 Wire 2 x 36 0.33 Toughened 1364 1312 105 20
ESB240-A000 3 Wire 2 x 36 0.33 Frosted 1364 1312 105 20
ESB265-0000 3 Wire 2 x 58 0.5 Toughened 1664 1612 105 25
ESB265-A000 3 Wire 2 x 58 0.5 Frosted 1664 1612 105 25
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 138 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
240
240
Approvals / Characteristics Features
50
XFF-EM RangeEmergency tubular fl uorescent fi tting
Approved to: EN60079-0, 60079-1, 60079-31 EC TYPE Examination Certificate:INERIS 11 ATEX 0051XEx II 2 GEx d IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (All Polycarbonate tubes)Ex d IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass tubes)Ex d IIB T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass versions - XFR140EMand XFF240EM)Ex II 2 DEx tb IIIC T80°C Db IP66Glow wire test: 960ºC EN60598-2-22Safe operating temperature range: -10°C to +40ºC
Certifi cation & Standards
• Manufactured from marine grade aluminium• All components mounted on the gear tray for easy installation and maintenance• Standard components used inside the body allowing reduced maintenance costs• Available in Glass for paint shop and other spray applications for easy cleaning• Battery duration 2 hours• Including accessories, cable gland & fixing brackets
Thomas & Betts • www.tnb-hazardous.com
EXL Conduit 140
Ex Emergency lighting - XFF-EM Range
Technical Specifi cations
51
Related Products
EnclosureEnd caps and cover in marine grade aluminium alloy type EN 1706 EN AC-AlSi12(Fe) DF orEN AC-AlSi10 Mg(a) DFYellow polyurethane paint RAL 1003FixingStandard: D023 - 2 Zinc Plated Steel articulated brackets for ceiling mounting
Rated voltagesElectronic ballast:AC/DC 220V-240V, 50-60HzPower factorSuperior to 0.98Cable entriesStandard: Two entries 3/4” NPT includedOne 3/4” zinc chromed steel plug and One cable gland - 3/4” NPT Brass for non-armoured cable, diameter 8-10.5mmBatteryLumen output in emergency mode (1 tube lit)40% for 18W33% for 40W
Terminal block (plug in terminal block)Up to 10mm² (rigid wire), 6mm² (fl exible wire)Supplied L, N, PE terminalsSelect function: Lighting in maintained mode or lighting in non-maintained modeLamps (order seperately)T8 bi-pin G13 tube, Ø 26 - white industry 4000°KG11 compact fl uorescent PL lampOther optionsStainless steel shockproof kit 304LEnclosure: Offshore and other colours
Dimensions
Spares & Fixings Accessories see pages 94-99
Stopping Plugs 162
Wiring Dimensions (mm)
Type Configuration Rating (W) Battery Diffuser A B Weight (kg)
XFR120EM-0G000 3 Wire 1 x 18 2h Polycarbonate 780 565 7.5
XFR140EM-0G000 3 Wire 1 x 36 2h Polycarbonate 1385 1170 9.5
XFF220EM-0G000 3 Wire 2 x 18 2h Polycarbonate 780 565 7.5
XFF240EM-0G000 3 Wire 2 x 36 2h Polycarbonate 1385 1170 9.5
XFR120VEM-0G000 3 Wire 1 x 18 2h Glass 780 565 9.5
XFR140VEM-0G000 3 Wire 1 x 36 2h Glass 1385 1170 9.5
XFF220VEM-0G000 3 Wire 2 x 18 2h Glass 780 565 9.5
XFF240VEM-0G000 3 Wire 2 x 36 2h Glass 1385 1170 9.5
GUV Range 124 PA NPT Gland 150
Thomas & Betts • www.tnb-hazardous.com
Approvals / Characteristics Features
52
Approved to: EN60079-0, 60079-1, 60079-7, 60079-31, EN61241-0, 61241-1 EC TYPE Examination Certificate:INERIS 11 ATEX 0052XEx II 2 GEx de IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (All Polycarbonate tubes)Ex de IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass tubes)Ex de IIB T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass versions - XFP140EM and XFP240EM)Ex II 2 DEx tD IIIC A21 IP6x T80°C Glow wire test: 960ºC EN60598-2-22Safe operating temperature range: -10°C to +40ºC
Certifi cation & Standards
• Manufactured from marine grade aluminium• Maintenance in hazardous area is quick and easy with isolation switch for safe maintenance• All components mounted on the gear tray for easy installation and maintenance• Standard components used inside the body allowing reduced maintenance costs• Available in Glass for paint shop and other spray applications for easy cleaning• Battery duration 2 hours• Including accessories, cable gland & fixing brackets
Thomas & Betts • www.tnb-hazardous.com
XFP-EM RangeEmergency tubular fl uorescent fi tting
with automatic switch off
Ex Emergency lighting - XFP-EM Range
Technical Specifi cations
53
Related Products
Dimensions
EnclosureEnd caps and cover in marine grade aluminium alloy type EN1706:EN AC-AlSi12(Fe) DF orEN AC-AlSi10 Mg(a) DFYellow polyurethane paint RAL 1003FixingStandard: D023 - 2 Zinc Plated Steel articulated brackets for ceiling mounting
Rated voltagesStandard: electronic ballast:AC/DC 220V-240V, 50-60HzPower factorSuperior to 0.98Cable entriesStandard M20 cable entry includedOne cable gland - ISO M20 Nylon, diameter 8-13mm for non-armoured cableBatteryLumen output in emergency mode (1 tube lit)40% for 18W33% for 33WMonitored by one LED
Terminal block (plug in terminal block)Up to 6mm² (rigid wire), 4mm² (fl exible wire)Supplied L, N, PE terminalsSelect function: Lighting in maintained mode or lighting in non-maintained modeLamps (order separately)T8 bi-pin G13 tube, Ø 26 - white industry 4000°KG11 compact fl uorescent PL lampOther optionsStainless steel shockproof kit 304LEnclosure: Offshore and other colours
Wiring Dimensions (mm)
Type Configuration Rating (W) Battery Diffuser A B Weight (kg)
XFP120EM-0G000 3 Wire 1 x 18 2h Polycarbonate 780 565 7.5
XFP120EM-0G000 3 Wire 1 x 36 2h Polycarbonate 1385 1170 7.5
XFP120EM-0G000 3 Wire 2 x 18 2h Polycarbonate 780 565 9.5
XFP120EM-0G000 3 Wire 2 x 36 2h Polycarbonate 1385 1170 9.5
XFP120VEM-0G000 3 Wire 1 x 18 2h Glass 780 565 9.5
XFP120VEM-0G000 3 Wire 1 x 36 2h Glass 1385 1170 11
XFP120VEM-0G000 3 Wire 2 x 18 2h Glass 780 565 9.5
XFP120VEM-0G000 3 Wire 2 x 36 2h Glass 1385 1170 11
Thomas & Betts • www.tnb-hazardous.com
Spares & Fixings Accessories see pages 94-99
Stopping Plugs 162 GUV Range 124 PA Metric Gland 150 EFDC Range 126
Approvals / Characteristics Features
54
XEL-BAES RangeSelf-contained emergency lighting fi tting
Approved to: EN60079-0, 60079-1, 60079-7, 60079-31, EN61241-0, 61241-1EC TYPE Examination Certificate:Models SI & AIINERIS II ATEX 0052XEx II 2 GEx de IIC T6 Gb Ex II 2 DEx tD A21 IP6x T80°CGlow wire test: 960ºC EN60598-2-22Safe operating temperature range: -20°C to +55ºC
Certifi cation & Standards
• Manufactured from marine grade aluminium• All components mounted on the gear tray for easy installation and maintenance• Self contained luminaires with built in automatic facility to give local indication of result, test or control monitoring• Available in Glass for paint shop and other spray applications for easy cleaning• Including accessories, cable gland & fixing brackets
Part No. B019T
Models A & AKINERIS II ATEX 0051XEx II 2 GEx d IIC T6 Gb Ex II 2 DEx tb IIIC T80ºC IP66 Db
Thomas & Betts • www.tnb-hazardous.com
205
Ex Emergency lighting - XEL-BAES Range
Technical Specifi cations
55
EnclosureEnd caps and cover in marine grade aluminium alloy type AS10GY30. Yellow polyurethane paint RAL 1003 (other colour on request) including offshore availableStainless steel screwsRated voltages and emergency functionElectronic ballast: AC/DC 230V, 50HzPower factorSuperior to 0.98
Self test SATISafety lighting with automatic built in systems test the lamps every 7 days and the battery pack every 12 weeks. Results of the test are displayed by yellow and green diodes.
Cable entryModel SI & AI: One M20 cable entry includedOne cable gland - Nickel Plated Brass ISO M20, diameter 8-13mm for non-armoured cableModel A & AK: Two entries 3/4” NPT includedOne 3/4” stopping plug andOne cable gland - 3/4” NPT Brass, diameter 8-10.5mm for non-armoured cableBatteryXEL80: Lumen output for 1 hour = 70lm, XEL300: Lumen output for 1 hour = 280lm, XEL3001 and XEL3002: Battery 3h for all markets except France - No NFCTerminal blockModel SI & AI: Up to 6mm² (rigid wire), 4mm² (fl exible wire) Terminals supplied for L, N, PE loopingModel A & AK: Up to 10mm² (rigid wire), 6mm² (fl exible wire) Terminals supplied for L, N, PE loopingLamps (supplied fi tted)XEL 80: emergency lamp: 1 x 6W tube with G5 (70 lumen) lampholder, 2 charge lamp using LEDsXEL 300: emergency lamp: 1 x 8W tube with G5 (280 lumen) lampholder, 2 charge lamp using LEDsFixingStandard: D023 - 2 Zinc Plated Steel articulated brackets for ceiling mounting
Dimensions
Testing Type Switch Type (see diagrams)
Type Function Rating (W) Diffuser Manual Automatic Addressable Unswitched Switch Off Combined Weight (kg)
XEL3001-00000 Large area 1 x 8 Polycarbonate ● – – ● – – 5
XEL3002-00000* Large area 2 x 8 Polycarbonate ● – – ● – – 5
XEL80A-00000 Escape route 1 x 6 Polycarbonate – ● – ● – – 4.7
XEL80AK-00000 Escape route 1 x 6 Polycarbonate – ● – – ● – 4.7
XEL80AI-00000 Escape route 1 x 6 Polycarbonate – ● – – – ● 5.5
XEL80SI-0J000 Escape route 1 x 6 Polycarbonate – – ● – – ● 5.5
XEL300A-00000 Large area 1 x 8 Polycarbonate – ● – ● – – 5
XEL300AK-00000 Large area 1 x 8 Polycarbonate – ● – – ● – 5
XEL300AI-00000 Large area 1 x 8 Polycarbonate – ● – – – ● 5.5
XEL300SI-00000 Large area 1 x 8 Polycarbonate – – ● – – ● 5.5
XEL3001V-00000 Large area 1 x 8 Glass ● – – ● – – 7
XEL3002V-00000* Large area 2 x 8 Glass ● – – ● – – 7
XEL80VA-0J000 Escape route 1 x 6 Glass – ● – ● – – 6.5
XEL80VAK-00000 Escape route 1 x 6 Glass – ● – – ● – 6.5
XEL80VAI-00000 Escape route 1 x 6 Glass – ● – – – ● 7.3
XEL80VSI-0J000 Escape route 1 x 6 Glass – – ● – – ● 7.3
XEL300VA-00000 Large area 1 x 8 Glass – ● – ● – – 7
XEL300VAK-00000 Large area 1 x 8 Glass – ● – – ● – 7
XEL300VAI-00000 Large area 1 x 8 Glass – ● – – – ● 7.5
XEL300VSI-00000 Large area 1 x 8 Glass – – ● – – ● 7.5
*Permanent lighting
SI & AI A & AK265
Thomas & Betts • www.tnb-hazardous.com
Healthy Emergency or Indicator
Lamp Fault
Test inProgress
Fault
UNSWITCHED enclosureCompulsary power socketFitting has to be removedMaintenance must be done in safe area
Enclosure with battery SWITCH OFFNo power socketExternal cut-out requiredMaintenance done in hazardous area
Enclosure with COMBINED battery and supply switch offNo power socketNo external cut-outMaintenance done in hazardous area
Approvals / Characteristics
56
EVS-EM RangeEmergency fl uorescent fi tting with easy disconnect
Features
Approved to: EN60079-0, 60079-1, 60079-5, 60079-7, EN61241-1EC TYPE Examination Certificate:LCIE 11 ATEX 3065X IEC Ex LCI 11.0053XEx II 2 GEx de IIC T4 Gb for ≤ -40ºC to ≤ +60ºCEx de IIC T5 Gb for ≤ -40ºC to ≤ +35ºCEx II 2 DEx tD IIIC A21 T85ºC Db IP64Glow wire test: 960ºC EN60598-2-22Safe operating temperature range: -10°C to +40ºC
Certifi cation & Standards
• Easy disconnector for safer maintenance out of zones• Main body constructed of a GRP for high impact strength• Battery duration 2 hours• All componets mounted on hinged and removable gear tray which gives easy access for installation and maintenance• Automatic switch off upon opening for safe maintenance• Including accessories, cable gland & fixing brackets
4
Thomas & Betts • www.tnb-hazardous.com
Ex Emergency lighting - EVS-EM Range
Technical Specifi cations
57
Related Products
EnclosureFibreglass reinforced polyester bodyPolycarbonate diffuser (protective coating optional) EPDM cellular gasketsFixingStandard: V015 - 2 Zinc Plated Steel brackets for ceiling mounting
Rated voltagesStandard: electronic ballast AC 220-240V, 50-60HzFor other voltages contact SalesBatteryNi-Cad 7.2V 4Ah battery in fl ameproof case(Auto cut out of defective light)Lumen output in emergency mode (1 tube lit): 40% at 18W, 33% at 36WBattery duration: 18W = 2 hours, 36W = 2hoursMonitored by one LEDPower factorSuperior to 0.98Cable entriesStandard: Three M20 cable entries includedTwo M20 Nylon plugs and One cable gland - ISO M20 Nylon, diameter 8-13mm for non-armoured cableFor armoured cable - continuity plate option: Nickel Brass cable gland (1 or 2 according to number of plates)
Terminal blockUp to 4mm² (rigid wire), 2.5mm² (fl exible wire)Select function: Lighting in maintained mode or lighting in non-maintained modeLamps (order separately)Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
170
137
Dimensions
Spares & Fixings Accessories see pages 94-99
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Battery Current (A) A B C Weight (kg)
EVS120EM-0000 3 Wire Loop 1 x 18 2h 0.09 785 432 400 7.5
EVS120EM-A000 5 Wire Loop 1 x 18 2h 0.09 785 432 400 7.5
EVS120EM-B000 5 Wire Through 1 x 18 2h 0.09 785 432 400 7.5
EVS140EM-0000 3 Wire Loop 1 x 36 2h 0.17 1370 900 700 9.5
EVS140EM-A000 5 Wire Loop 1 x 36 2h 0.17 1370 900 700 9.5
EVS140EM-B000 5 Wire Through 1 x 36 2h 0.17 1370 900 700 9.5
EVS220EM-0000 3 Wire Loop 2 x 18 2h 0.17 785 432 400 8.5
EVS220EM-A000 5 Wire Loop 2 x 18 2h 0.17 785 432 400 8.5
EVS220EM-B000 5 Wire Through 2 x 18 2h 0.17 785 432 400 8.5
EVS240EM-0000 3 Wire Loop 2 x 36 2h 0.33 1370 900 700 10.5
EVS240EM-A000 5 Wire Loop 2 x 36 2h 0.33 1370 900 700 10.5
EVS240EM-B000 5 Wire Through 2 x 36 2h 0.33 1370 900 700 10.5
*EVS... EM-C000 - 3 Wire loop & continuity plate*EVS... EM-E000 - 5 Wire through & 2 continuity plates
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 136 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
Approvals / Characteristics
58
EVS-EMA RangeEmergency fl uorescent fi tting with automatic test
Features
Approved to: EN60079-0, 60079-1, 60079-5, 60079-7, EN61241-1EC TYPE Examination Certificate:LCIE 11 ATEX 3065X IEC Ex LCI 11.0053XEx II 2 GEx de IIC T4 Gb for ≤ -40ºC to ≤ +60ºCEx de IIC T5 Gb for ≤ -40ºC to ≤ +35ºCEx II 2 DEx tD IIIC A21 T85ºC Db IP64Glow wire test: 960°C EN605988-2-22Safe operating temperature range: -10°C to +40ºC
Certifi cation & Standards
• Main body constructed of a GRP for high impact strength• Battery duration 3 hours• Automatic testing for preventitive maintenance• Clear LED for visual inspection• Polycarbonate diffuser to resist harsh and corrosive environments• All componets mounted on hinged and removable gear tray• Automatic switch off upon opening for safe maintenance• Including accessories, cable gland & fixing brackets
4
Thomas & Betts • www.tnb-hazardous.com
Ex Emergency lighting - EVS-EMA Range
Technical Specifi cations
59
Related Products
EnclosureFibreglass reinforced polyester bodyPolycarbonate diffuserEPDM cellular gasketsPower factorSuperior to 0.98Cable entriesStandard: Three M20 cable entries includedTwo M20 Nylon plugs and One cable gland - ISO M20 Nylon, diameter 8-13mm for non-armoured cableFixingStandard: V015 - 2 Zinc Plated Steel brackets for ceiling mounting
Rated voltagesStandard: electronic ballast AC/DC 220-240V, 50-60HzFor other voltages contact SalesBatteryNi-Cad 6V 4Ah for 18W / Ni-Cad 6V 7Ah for 36W battery in fl ameproof case(Auto cut out of defective light)Lumen output in emergency mode (1 tube lit): 40%at 18W, 33% at 36WBattery duration: 3h max 36WPreventive maintenance - Self test- Battery charge - daily- Emergency lamp during 1min - weekly- Battery charge capacity during 1hr - quaterly- Clean system test displayBattery charge monitored by 2 LED
Terminal blockUp to 4mm² (rigid wire), 2.5mm² (fl exible wire)Lamps (order separately)Command must be supplied with switch on lineTube G13 bi-pin T8 Ø 26 coolwhite 4000°k
170
137
Dimensions
Spares & Fixings Accessories see pages 94-99
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Battery Current (A) A B C Weight (kg)
EVS120EMA-A000 5 Wire Loop 1 x 18 3h 0.09 785 432 400 7.5
EVS140EMA-A000 5 Wire Loop 1 x 36 3h 0.17 1370 900 700 9.5
EVS140EMA-B000 5 Wire Through 1 x 36 3h 0.17 1370 900 700 9.5
EVS220EMA-A000 5 Wire Loop 2 x 18 3h 0.17 785 432 400 8.5
EVS240EMA-A000 5 Wire Loop 2 x 36 3h 0.33 1370 900 700 10.5
EVS240EMA-B000 5 Wire Through 2 x 36 3h 0.33 1370 900 700 10.5
Healthy(test OK)
Emergency or Indicator
Lamp Fault(must bereplaced)
Test inProgress
(waiting endof test)
Fault(replacebattery)
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 138 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
60
EVN-EM RangeEmergency fl uorescent fi tting
• Main body constructed of a GRP for high impact strength
• Battery duration 2 hours
• All components mounted on hinged and removable
gear tray which gives easy access for installation
and maintenance
• Including accessories, cable gland & fixing brackets
Approvals / Characteristics Features
Approved to: EN60079-0, 60079-15, 61241-1EC TYPE Examination Certificate:Ex II 3 GEx nr IIC T4 Gb for ≤ -40ºC to ≤ +60ºCEx nr IIC T6 Gb for ≤ -40ºC to ≤ +35ºCEx II 3 DEx td IIIC A22 T85ºC to T135ºC Db IP6xGlow wire test: 960°C EN60598-2-22Safe operating temperature range: -10°C to +40ºC
Certifi cation & Standards
4
Thomas & Betts • www.tnb-hazardous.com
Ex Emergency lighting - EVN-EM Range
Technical Specifi cations
61
Related Products
EnclosureFibreglass reinforced polyester bodyPolycarbonate diffuserFixingStandard: V015 - 2 Zinc Plated Steel brackets for ceiling mounting
Rated voltagesStandard: electronic ballast AC/DC 220-240V, 50-60HzFor other voltages contact SalesBatteryNi-Cd 7.2V 4Ah batteryAuto cut-off for defective lightLumen output in emergency mode (1 tube lit)40% at 18W, 33% at 36WMonitored by one LEDPower factorSuperior to 0.98Cable entriesStandard: Three M20 cable entries includedTwo M20 Nylon plugs and One cable gland - ISO M20 Nylon, diameter 8-13mm for non-armoured cableFor non-armoured cable - continuity plate option: Nickel Brass cable gland (1 or 2 according to number of plates)
Terminal blockUp to 4mm² (rigid wire), 2.5mm² (fl exible wire)Select function: Lighting in maintained mode or lighting in non-maintained modeLamps (order separately)Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
170
137
Dimensions
Spares & Fixings Accessories see pages 94-99
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Battery Current (A) A B C Weight (kg)
EVN120EM-0000 3 Wire Loop 1 x 18 2h 0.09 785 432 400 6.5
EVN120EM-A000 5 Wire Loop 1 x 18 2h 0.09 785 432 400 6.5
EVN120EM-B000 5 Wire Through 1 x 18 2h 0.09 785 432 400 6.5
EVN140EM-0000 3 Wire Loop 1 x 36 2h 0.17 1370 900 700 8.5
EVN140EM-A000 5 Wire Loop 1 x 36 2h 0.17 1370 900 700 8.5
EVN140EM-B000 5 Wire Through 1 x 36 2h 0.17 1370 900 700 8.5
EVN220EM-0000 3 Wire Loop 2 x 18 2h 0.17 785 432 400 7.5
EVN220EM-A000 5 Wire Loop 2 x 18 2h 0.17 785 432 400 7.5
EVN220EM-B000 5 Wire Through 2 x 18 2h 0.17 785 432 400 7.5
EVN240EM-0000 3 Wire Loop 2 x 36 2h 0.33 1370 900 700 10.5
EVN240EM-A000 5 Wire Loop 2 x 36 2h 0.33 1370 900 700 10.5
EVN240EM-B000 5 Wire Through 2 x 36 2h 0.33 1370 900 700 10.5
*EVN... EM-C000 - 3 Wire loop & continuity plate*EVN... EM-E000 - 5 Wire through & 2 continuity plates
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 138 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
• Main body constructed of a GRP for high impact strength• Polycarbonate diffuser to resist harsh and corrosive environments• Battery duration 3 hours• Automatic testing for preventive maintenance• Clear LED for easy visual inspection• Including accessories, cable gland & fixing brackets
62
EVN-EMA RangeEmergency fl uorescent fi tting with automatic test
Approvals / Characteristics Features
Approved to: EN60079-0, 60079-15, EN61241-1EC TYPE Examination Certificate: Under new 94/9/EC self certifiedEx II 3 GEx nr IIC T4 Gb for ≤ -40ºC to ≤ +60ºCEx nr IIC T6 Gb for ≤ -40ºC to ≤ +35ºCEx II 3 DEx td IIIC A22 T85ºC to T135ºC Db IP6xGlow wire test: 960°C EN605988-2-22Safe operating temperature range: -10°C to +40ºC
Certifi cation & Standards
4
Thomas & Betts • www.tnb-hazardous.com
Ex Emergency lighting - EVN-EMA Range
Technical Specifi cations
63
Related Products
EnclosureFibreglass reinforced polyester bodyPolycarbonate diffuser (protective coating optional) EPDM cellular gasketPower factorSuperior to 0.98Cable entriesStandard: Three M20 entries includedTwo M20 Nylon plugs and One cable gland - ISO M20 Nylon, diameter 8-13mm for non-armoured cableFixingStandard: V015 - 2 Zinc Plated Steel brackets for ceiling mounting
Rated voltagesStandard: single tube electronic ballast AC 220-240V, 50-60HzFor other voltages contact SalesBatteryNi-Cd 6V 4Ah for 18W /Ni-Cd 6V 7Ah for 36W batteryLumen level in emergency mode (1 tube lit): 40%in 18W, 33% in 36WBattery duration in emergency mode:3 hoursPreventive maintenance - Self test- Battery charge - daily- Emergency lamp during 1min - weekly- Battery charge capacity during 1hr - quaterly- Clean system test displayBattery charge monitored by 2 LED
Terminal blockUp to 6mm² (rigid wire), 4.5mm² (fl exible wire)Separate switch from lineLamps (order separately)Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
170
137
Dimensions
Spares & Fixings Accessories see pages 94-99
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Battery Current (A) A B C Weight (kg)
EVN120EMA-A000 5 Wire Loop 1 x 18 3h 0.09 785 170 432 6.5
EVN140EMA-A000 5 Wire Loop 1 x 36 3h 0.17 1370 170 900 8.5
EVN140EMA-B000 5 Wire Through 1 x 36 3h 0.17 1370 170 900 8.5
EVN220EMA-A000 5 Wire Loop 2 x 18 3h 0.17 785 170 432 7.5
EVN240EMA-A000 5 Wire Loop 2 x 36 3h 0.33 1370 170 900 10.5
EVN240EMA-B000 5 Wire Through 2 x 36 3h 0.33 1370 170 900 10.5
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 136 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
Healthy(test OK)
Emergency or Indicator
Lamp Fault(must bereplaced)
Test inProgress
(waiting endof test)
Fault(replacebattery)
64
EVD-EM RangeEmergency fl uorescent fi tting
Approvals / Characteristics Features
Approved to: EN60079-0, 60079-31EC TYPE Examination Certificate: Under new 94/9/EC self certifiedLCIE II ATEX 3092XIECEx LCI 11.0064XEx t IIIC T82ºC (≤ +60ºC) DbEx t IIIC T62ºC (≤ +40ºC) DbGlow wire test: 960°C EN60598-2-22Safe operating temperature range: -10°C to +40ºC
Certifi cation & Standards
• Main body constructed of a GRP for high impact strength• Polycarbonate diffuser to resist harsh and corrosive environments• All componets mounted on hinged and removable gear tray which gives easy access for installation and maintenance• Battery duration 2 hours• Including accessories, cable gland & fixing brackets
4
Thomas & Betts • www.tnb-hazardous.com
Ex Emergency lighting - EVD-EM Range
Technical Specifi cations
65
Related Products
EnclosureFibreglass reinforced polyester bodyPolycarbonate diffuser (protective coating optional) EPDM cellular gasketFixingStandard: V015 - 2 Zinc Plated Steel brackets for ceiling mounting
Rated voltagesStandard: dual tube electronic ballast AC 220-240V, 50-60HzFor other voltages contact SalesBatteryNi-Cd 7.2V 4Ah batteryLumin level in emergency mode (1 tube lit): 40%at 18W, 33% at 36WBattery duration in emenrgency mode: 2 hoursBattery charge monitored by one LEDPower factorSuperior to 0.98Cable entriesStandard: Three M20 cable entries includedTwo M20 Nylon plugs and One cable gland - ISO M20 Nylon, diameter 8-13mm for non-armoured cableFor armoured cable - continuity plate option: Nickel Brass cable gland (1 or 2 ccording to number of plates)
Terminal blockUp to 4mm² (rigid wire), 2.5mm² (fl exible wire)Terminals supplied for L1, L2, L3, N, PE (1 max 16A)Select function: Lighting in maintained mode or lighting in non-maintained modeLamps (order separately)Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
170
137
Dimensions
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Battery Current (A) A B C Weight (kg)
EVD120EM-00J0 3 Wire Loop 1 x 18 2h 0.09 785 432 400 6.5
EVD120EM-A0J0 5 Wire Loop 1 x 18 2h 0.09 785 432 400 6.5
EVD120EM-B0J0 5 Wire Through 1 x 18 2h 0.09 785 432 400 6.5
EVD140EM-00J0 3 Wire Loop 1 x 36 2h 0.17 1370 900 700 8.5
EVD140EM-A0J0 5 Wire Loop 1 x 36 2h 0.17 1370 900 700 8.5
EVD140EM-B0J0 5 Wire Through 1 x 36 2h 0.17 1370 900 700 8.5
EVD220EM-00J0 3 Wire Loop 2 x 18 2h 0.17 785 432 400 7.5
EVD220EM-A0J0 5 Wire Loop 2 x 18 2h 0.17 785 432 400 7.5
EVD220EM-B0J0 5 Wire Through 2 x 18 2h 0.17 785 432 400 7.5
EVD240EM-00J0 3 Wire Loop 2 x 36 2h 0.33 1370 900 700 10.5
EVD240EM-A0J0 5 Wire Loop 2 x 36 2h 0.33 1370 900 700 10.5
EVD240EM-B0J0 5 Wire Through 2 x 36 2h 0.33 1370 900 700 10.5
*EVD... EM-C0J0 - 3 Wire loop & continuity plate*EVD... EM-E0J0 - 5 Wire through & 2 continuity plates
Thomas & Betts • www.tnb-hazardous.com
Spares & Fixings Accessories see pages 94-99
EXB Conduit 136 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
• Main body constructed of a GRP for high impact strength• Polycarbonate diffuser to resist harsh and corrosive environments• Battery duration 3 hours• All componets mounted on hinged and removable gear tray • Automatic testing for preventive maintenance• Clear LED for easy visual inspection• Including accessories, cable gland & fixing brackets
66
EVD-EMA RangeEmergency fl uorescent fi tting with automatic test
Approvals / Characteristics Features
Approved to: EN60079-0, 60079-31EC TYPE Examination Certificate: Under new 94/9/EC self certifiedLCIE II ATEX 3092XIECEx LCI 11.0064XEx t IIIC T82ºC (≤ +60ºC) DbEx t IIIC T62ºC (≤ +40ºC) DbGlow wire test: 960°C EN60598-2-22Safe operating temperature range: -10°C to +40ºC
Certifi cation & Standards
4
Thomas & Betts • www.tnb-hazardous.com
Ex Emergency lighting - EVD-EMA Range
Technical Specifi cations
67
Related Products
EnclosureFibreglass reinforced polyester bodyPolycarbonate diffuser (protective coating optional) EPDM cellular gasketPower factorSuperior to 0.98Cable entriesStandard: Three M20 cable entries includedTwo M20 Nylon plugs and One cable gland - ISO M20 Nylon, diameter 8-13mmFixingStandard: V015 - 2 Zinc Plated Steel brackets for ceiling mounting
Rated voltagesStandard: electronic ballast AC 220-240V, 50-60HzFor other voltages contact SalesBattery: Ni-Cd batteryLumin level in emergency mode (1 tube lit): 40%at 18W, 33% at 36WBattery duration: 3h max 36WPreventive maintenance - Self test- Battery charge - daily- Emergency lamp during 1min - weekly- Battery charge capacity during 1hr - quaterly- Clean system test displayBattery charge monitored by 2 LED
Terminal blockUp to 4mm² (rigid wire), 2.5mm² (fl exible wire)Terminals supplied for L1, L2, L3, N, PE (1 max 16A)Through wire 16 Amp maxCommand must be supplied with switch on lineLamps (order separately)Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
170
137
Dimensions
Spares & Fixings Accessories see pages 94-99
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Battery Current (A) A B C Weight (kg)
EVD120EMA-A000 5 Wire Loop 1 x 18 3h 0.09 785 432 400 6.5
EVD140EMA-A000 5 Wire Loop 1 x 36 3h 0.17 1370 900 700 8.5
EVD140EMA-B000 5 Wire Through 1 x 36 3h 0.17 1370 900 700 8.5
EVD220EMA-A000 5 Wire Loop 2 x 18 3h 0.17 785 432 400 7.5
EVD240EMA-A000 5 Wire Loop 2 x 36 3h 0.33 1370 900 700 10.5
EVD240EMA-B000 5 Wire Through 2 x 36 3h 0.33 1370 900 700 10.5
Healthy(test OK)
Emergency or Indicator
Lamp Fault(must bereplaced)
Test inProgress
(waiting endof test)
Fault(replacebattery)
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 138 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
• Main body made from powder coated steel• 6mm toughened glass making it perfect for laboratories• Automatic switch off upon opening for safe maintenance• Battery duration 2 hours• Including accessories & cable gland
Approvals / Characteristics Features
68
ESB-EM RangeRecessed emergency fl uorescent fi tting
Approved to: EN60079-0, 60079-1, 60079-7EC TYPE Examination Certificate: Under 94/9/EC INERIS II ATEX 0058XEx II 2 GEx de IIC T4 Gb for ≤ -40ºC to ≤ +60ºCGlow wire test: 850°C EN60598-2-22Safe operating temperature range: -10°C to +40ºC
Certifi cation & Standards
5
Thomas & Betts • www.tnb-hazardous.com
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Battery Current (A) Glass A B C Weight (kg)
ESB240EM-0000 3 Wire 2 x 36 2h 0.33 Toughened 1364 1312 105 22
ESB240EM-A000 3 Wire 2 x 36 2h 0.33 Frosted 1364 1312 105 22
Ex Emergency lighting - ESB-EM Range
Technical Specifi cations
69
Related Products
Dimensions
Spares & Fixings Accessories see pages 94-99
EnclosureSteel housing and body painted in white polyester powderpaint RAL 9016 6mm clear toughened glass panel (optional frosted low lumen output) Neoprene gasket
Rated voltagesConcealed white painted Standard: electronic ballast:AC/DC 220-240V, 50-60HzFor other voltages contact SalesBatteryNi-Cd 6V 7Ah battery in fl ameproof caseLumen level in emergency mode (1 tube lit): 33% Emergency load duration: 2 hoursPower factorSuperior to 0.98Cable entriesStandard: Two M20 cable entries includedOne M20 Nylon plugs and One cable gland - ISO M20 Nylon, diameter 8-13mm
Terminal blockUp to 4mm² (rigid wire), 2.5mm² (fl exible wire)Select function: Lighting in maintained mode or lighting in non-maintained modeLamps (order separately)Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k FixingFixing by 4 M6 threaded bolts (not supplied) joined to the main body
240
240
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 138 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
72
FF RangeWeatherproof tubular fl uorescent fi tting
Approvals / Characteristics Features
• Ingress protection IP66 ideal for wash down areas
• All componets mounted on a removable gear tray which
gives easy access for installation and maintenance
• Including accessories, cable gland & fixing brackets
Thomas & Betts • www.tnb-hazardous.com
Industrial Lighting - FF Range
Technical Specifi cations
73
Related Products
EnclosureReinforced black polycarbonate end capsLEXAN 2034 UV protected extruded polycarbonate tube, thickness 2.5mmTemperatureAmbient temperature: -20°C to +50°CFixingStandard: D023 - 2 Zinc Plated Steel articulated brackets for ceiling mounting
Rated voltagesElectronic ballast: AC/DC 220-240V, 50-60HzPower factorSuperior to 0.98Cable entriesStandard: Two M20 entries includedOne plug and one cable gland - ISO M20 Nylon, diameter 8-13mm
Terminal block (plug in terminal block)Up to 10mm2 (rigid wire), 6mm2 (fl exible wire)Standard: terminals supplied for L, N, PE, looping possibleLamps (order separately)T8 bi-pin G13 tube, Ø 26 - white industry 4000°KG11 compact fl uorescent PL lamp
Dimensions
Spares & Fixings Accessories see pages 94-99
Nominal Dimensions (mm)
Type Diffuser Rating (W) Current (A) A B Weight (kg)
FR120-0G000 Polycarbonate 1 x 18 0.15 780 565 4
FR136-0G000 Polycarbonate 2 x PL36 0.2 1385 1170 4.5
FR140-0G000 Polycarbonate 1 x 36 0.2 1385 1170 7
FR155-0G000 Polycarbonate 1 x PL55 0.35 1690 1475 4.5
FR165-0G000 Polycarbonate 1 x 58 0.35 1690 1475 8
FF220-0G000 Polycarbonate 2 x 18 0.3 780 565 4.5
FF236-0G000 Polycarbonate 2 x PL36 0.4 1385 1170 5
FF240-0G000 Polycarbonate 2 x 36 0.4 1385 1170 7
FF255-0G000 Polycarbonate 2 x PL55 0.7 1690 1475 5
FF265-0G000 Polycarbonate 2 x 58 0.7 1690 1475 9
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 136 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
74
EL RangeWeatherproof miniature tubular fl uorescent fi tting
Approvals / Characteristics Features
• Ingress protection IP66 ideal for wash down areas
• All componets mounted on a removable gear tray which
gives easy access for installation and maintenance
• Small and compact for confined spaces
• Including accessories, cable gland & fixing brackets
Thomas & Betts • www.tnb-hazardous.com
Industrial Lighting - EL Range
Technical Specifi cations
75
Related Products
EnclosureReinforced black polycarbonate end capsLEXAN 2034 UV protected extruded polycarbonate tube, thickness 2.5mmNeoprene gasketTemperatureAmbient temperature: -20°C to +50°CFixingStandard: D023 - 2 Zinc Plated Steel articulated brackets for ceiling mounting
Rated voltagesStandard: Electronic ballast: AC/DC 220 to 240VPower factorSuperior to 0.98Standard: Two M20 entries includedOne plug and one cable gland - ISO M20 Nylon, diameter 8-13mm
Terminal block (plug in terminal block)Up to 10mm2 (rigid wire), 6mm2 (fl exible wire)Standard: terminals supplied for L, N, PE, looping possibleLamps (order separately)T8 bi-pin G13 tube, Ø 26 - white industry 4000°KG11 compact fl uorescent PL lampLamp with G11 base (18W)or G23 (7W, 9W, 11W)
Dimensions
Spares & Fixings Accessories see pages 94-99
Nominal Dimensions (mm)
Type Diffuser Rating (W) Current (A) A B Weight (kg)
EL3008-0G000 Polycarbonate 1 x 8 0.1 780 565 3
EL3009-0G000 Polycarbonate 1 x PL9 0.1 780 565 3
EL30011-0G000 Polycarbonate 1 x PL11 0.1 780 565 3.5
EL120-0G000 Polycarbonate 1 x PL18 0.1 780 565 3.5
EL220-0G000 Polycarbonate 2 x PL18 0.1 780 565 4
EL30028-0G000 Polycarbonate 2 x 8 0.1 780 565 3.5
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 136 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
76
SF / QF / EF RangeWeatherproof fl oodlight fi tting
Approvals / Characteristics Features
• Compact, lightweight and robust ideal for lighting
large areas
• Integral junction box: rapid installation
• Excellent photometric properties, wide or narrow beam
• Including accessories, cable gland & lamps installed
Thomas & Betts • www.tnb-hazardous.com
Industrial Lighting - SF / QF / EF Range
Technical Specifi cations
77
Related Products
Dimensions
Spares & Fixings Accessories see pages 94-99
Standard Flat Pole Mounting
Nominal
Type Rating (W) Current (A) Fixing Weight (kg)
SF70P-00000 1 x 70 HP Sodium 0.4 Flat 17
SF70G-00000 1 x 70 HP Sodium 0.4 Pole 17
SF150P-00000 1 x 150 HP Sodium 0.8 Flat 17
SF150G-00000 1 x 150 HP Sodium 0.8 Pole 17
SF250P-00000 1 x 250 HP Sodium 1.3 Flat 18
SF250G-00000 1 x 250 HP Sodium 1.3 Pole 18
SF400P-00000 1 x 400 HP Sodium 2.1 Flat 20
SF400G-00000 1 x 400 HP Sodium 2.1 Pole 20
QF250P-00000 1 x 250 Metal Halide 1.3 Flat 18
QF250G-00000 1 x 250 Metal Halide 1.3 Pole 18
QF400P-00000 1 x 400 Metal Halide 2.1 Flat 20
QF400G-00000 1 x 400 Metal Halide 2.1 Pole 20
EF110P-00000 2 x 55 Halogen 9.2 Flat 13
EF110G-00000 2 x 55 Halogen 9.2 Pole 13
EF140P-00000 2 x 55 Halogen 5.8 Flat 13
EF140G-00000 2 x 55 Halogen 5.8 Pole 13
EnclosureMarine grade aluminium alloy type according to EN1706:EN AC-AlSi7 Mg 0,6 T6Cataphoretically treated - yellow polyester paint RAL 1003 12mm toughened glassStainless steel screwsTemperatureAmbient temperature: -20°C to +60°C
Rated voltagesStandard: 230V 50Hz ferromagnetic ballast,with capacitorFor other voltages contact SalesPower factor0.85 for version with compensated ballast (Sodium HP and metal halide)Cable entriesStandard: Two M20 entries includedOne M20 nickel chromed brass plug andOne cable gland - Nickel Plated Brass ISO M20 for non-armoured cable, diameter 8-13mm
Terminal blockUp to 6mm² (rigid wire), 4mm² (fl exible wire)Lamps (Installed)Polished aluminium refl ectorStandard:wide beamFixingStandard:galvanised steel fl at mounting bracket, yellow polyester paint RAL1003Pole mounted: Ø 40 to 60mm
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 136 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
• Double central locking: for easy installation
and ingress protection
• Including accessories, cable gland & fixing brackets
78
EVT RangeWeatherproof fl uorescent fi tting with diffuser
Approvals / Characteristics Features
Thomas & Betts • www.tnb-hazardous.com
Industrial Lighting - EVT Range
Technical Specifi cations
79
Related Products
EnclosureFibreglass reinforced polyester bodyPolycarbonate diffuser (protective coating optional) TemperatureAmbient temperature: -20ºC to +50ºCFixingStandard: V015 - 2 Zinc Plated Steel brackets for ceiling mounting
Rated voltagesStandard electronic ballast: AC/DC 220-240V, 50-60HzPower factorSuperior to 0.98Cable entriesStandard: Three M20 cable entries includedTwo M20 Nylon plug andOne cable gland - ISO M20 Nylon, diameter 8-13mm for non-armoured cableFor armoured cable - continuity plate option:Nickel Brass cable gland (1 or 2 according to number of plates)
Terminal blockUp to 6mm² (rigid wire), 4.5mm² (fl exible wire)Standard: Terminals supplied for L, N, PE,looping possibleLamps (order separately)T8 bi-pin G13 tube, Ø 26 - cool white 4000°K
Dimensions
Spares & Fixings Accessories see pages 94-99
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Current (A) A B C Weight (kg)
EVT120-00J0 3 Wire Loop 1 x 18 0.09 785 170 432 4.2
EVT120-A0J0 5 Wire Loop 1 x 18 0.09 785 170 432 4.2
EVT120-B0J0 5 Wire Through 1 x 18 0.09 785 170 432 4.2
EVT140-00J0 3 Wire Loop 1 x 36 0.17 1370 170 900 6.5
EVT140-A0J0 5 Wire Loop 1 x 36 0.17 1370 170 900 6.5
EVT140-B0J0 5 Wire Through 1 x 36 0.17 1370 170 900 6.5
EVT165-00J0 3 Wire Loop 1 x 58 0.26 1670 170 900 8
EVT165-A0J0 5 Wire Loop 1 x 58 0.26 1670 170 900 8
EVT165-B0J0 5 Wire Through 1 x 58 0.26 1670 170 900 8
EVT220-00J0 3 Wire Loop 2 x 18 0.17 785 170 432 4.5
EVT220-A0J0 5 Wire Loop 2 x 18 0.17 785 170 432 4.5
EVT220-B0J0 5 Wire Through 2 x 18 0.17 785 170 432 4.5
EVT240-00J0 3 Wire Loop 2 x 36 0.33 1370 170 900 6.8
EVT240-A0J0 5 Wire Loop 2 x 36 0.33 1370 170 900 6.8
EVT240-B0J0 5 Wire Through 2 x 36 0.33 1370 170 900 6.8
EVT265-00J0 3 Wire Loop 2 x 58 0.5 1670 170 900 8.5
EVT265-A0J0 5 Wire Loop 2 x 58 0.5 1670 170 900 8.5
EVT265-B0J0 5 Wire Through 2 x 58 0.5 1670 170 900 8.5
*EVT... C0J0 - 3 Wire loop & continuity plate*EVT... E0J0 - 5 Wire through & 2 continuity plates
170
137
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 136 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
• Fitting combines photometric qualities, strength
and design
• Easy access to components
• Including accessories, cable gland & fixing brackets
Approvals / Characteristics Features
80
EST RangeWeatherproof recessed fl uorescent fi tting
5
Thomas & Betts • www.tnb-hazardous.com
Industrial Lighting - EST Range
Technical Specifi cations
81
Related Products
EnclosureSteel housing and body painted in white polyester powder paint RAL 9016 (stainless steel 304L on request) 6mm clear toughened glass panel (optional frosted low lumen output) Neoprene gasketTemperatureOperating temperature range: -20°C to +40°C
Rated voltagesStandard: electronic ballast AC 220-240V, 50-60HzDC 220-240VFor other voltages contact SalesPower factorSuperior to 0.98Cable entriesStandard: Two M20 cable entries includedOne M20 Nylon plug andOne cable gland - ISO M20 Nylon, diameter 8-13mm
Terminal blockUp to 4mm² (rigid wire), 2.5mm² (fl exible wire)Lamps (order separately)Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k FixingFixing by 4 M6 threaded bolts (not supplied) joined to the main body
Dimensions
Spares & Fixings Accessories see pages 94-99
240
240
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Glass Current (A) A B C Weight (kg)
EST220-00J0 3 Wire Loop 2 x 18 Toughened 0.17 753 702 105 12.5
EST220-A0J0 3 Wire Loop 2 x 18 Frosted 0.17 753 702 105 12.5
EST240-00J0 3 Wire Loop 2 x 36 Toughened 0.33 1364 1312 105 20
EST240-A0J0 3 Wire Loop 2 x 36 Frosted 0.33 1364 1312 105 20
EST265-00J0 3 Wire Loop 2 x 58 Toughened 0.5 1664 1612 105 25
EST265-A0J0 3 Wire Loop 2 x 58 Frosted 0.5 1664 1612 105 25
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 136 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
• Lightweight and robust for easy installation
• Static or flashing versions available for use in a
variety of applications
• Choice of 5 colours
• 2 or 3 light versions available for traffic signals
• Including accessories, cable gland & lamps installed
Approvals / Characteristics Features
82
FB / FL RangeWeatherproof warning lights and beacons
Thomas & Betts • www.tnb-hazardous.com
Type Rating (W) Lamp Version Weight (kg)
FB30-00000 1 x 28 E27 Halogen 3.5
FB70-00000 1 x 8 E27 LED 3.5
FL30P-00000 30 Joules Picots Xenon flash 4
Industrial Lighting - FB / FL Range
Technical Specifi cations
83
EnclosureMarine grade aluminium alloy type EN1706 AC-43100KF-AlSi 10MgYellow polyurethane paint RAL1003Aluminium refl ectorTemperatureAmbient temperature: -20°C to +60°C
Rated voltagesHalogen AC: 230V, 50-60HzLED AC: 100-240V, 50-60HzXenon Flash AC: 230V, 50-60HzCable entriesStandard: Two entries M20 includedOne plug and one cable gland - Nickel ISO M20 for non-armoured cable, diameter 8-13mmTerminal blockUp to 6mm2
Terminals supplied for L, N, P, E
Lamps (supplied)For xenon fl ash versionsFlashing rate: 45 to 60 - per minuteGlobe3mm thick polycarbonateStandard: RedOption: Green, Orange / Yellow, Blue, Transparent
Dimensions
Thomas & Betts • www.tnb-hazardous.com
Contact Sales for Mounting Options8
Related Products
Spares & Fixings Accessories see pages 94-99
EXB Conduit 136 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
• Lightweight and robust for easy carriage
• Free standing on base plate for stable use
in high winds
• Fully portable (carrying handle)
• Including accessories, cable gland & lamps installed
Approvals / Characteristics Features
84
HF RangePortable fl oodlight
Thomas & Betts • www.tnb-hazardous.com
Nominal
Type Rating (W) Lamp Power Supply (V) Current (A) Weight (kg)
HF55P-00000 55 Halogen H3 12 4.6 6
HF70P-00000 70 Halogen H3 24 2.9 6
Industrial Lighting - HF Range
Technical Specifi cations
85
EnclosureMarine grade aluminium alloy Yellow polyurethane paint RAL1003Globe: 3mm thick transparent polycarbonateTemperatureAmbient temperature: -20°C to +60°C
Cable entriesOne M20 entry includedOne cable gland - ISO M20 Nylon, diameter 8-13mmMetallic cable gland for non-armoured cable or armoured cable on requestTerminal blockUp to 6mm2
Lamps (supplied)70W - 24V iodine lamp - H3 lampholder55W - 12V iodine lamp - H3 lampholderFixingTreated steel support with base plate ref. SA103
Dimensions
Related Products
Spares & Fixings Accessories see pages 94-99
EXL Conduit 140 Stopping Plugs 164 GUV Range 124 PA Gland 150
Thomas & Betts • www.tnb-hazardous.com
86
FR-EM / FF-EM RangeEmergency weatherproof tubular fl uorescent fi tting
Approvals / Characteristics Features
• Ingress protection IP66 ideal for wash down areas
• All componets mounted on hinged and removable gear tray
which gives easy access for installation and maintenance
• Battery 2h duration
• Including accessories, cable gland & fixing brackets
Thomas & Betts • www.tnb-hazardous.com
Industrial Emergency Lighting - FR-EM / FF-EM Range
Technical Specifi cations
87
Related Products
EnclosureReinforced black polycarbonate end capsLEXAN 2034 UV protected extruded polycarbonate tube, thickness 2.5mmTemperatureAmbient temperature: -10°C to +40°CFixingStandard: D023 - 2 Zinc Plated Steel articulated brackets for ceiling mounting
Power FactorSuperior to 0.98Rated voltagesElectronic ballast: AC/DC 220-240V, 50-60HzBatteryNi-Cd battery 7.2V, 4AhLumen output in emergency mode (1 tube lit):40% for 8W, 33% for 36WBattery duration in emergency mode: 2 hoursMonitored by one LEDCable entriesStandard: Two M20 entries includedOne cable gland - ISO M20 Nylon, diameter 8-13mm
Terminal block (plug in terminal block)Up to 10mm2 (rigid wire), 6mm2 (fl exible wire)Standard: terminals supplied for L, N, PE Lamps (order separately)T8 bi-pin G13 tube, Ø 26 - white industry 4000°KG11 compact fl uorescent PL lamp
Dimensions
Spares & Fixings Accessories see pages 94-99
Wiring Nominal Dimensions (mm)
Type Confi guration Diffuser Rating (W) Current (A) Battery A B Weight (kg)
FR120EM-0G000 3 Wire loop Polycarbonate 1 x 18 0.15 2h 780 565 8
FR140EM-0G000 3 Wire loop Polycarbonate 1 x 36 0.2 2h 1385 1170 8
FF220EM-0G000 3 Wire loop Polycarbonate 2 x 18 0.2 2h 780 565 8
FF240EM-0G000 3 Wire loop Polycarbonate 2 x PL36 0.35 2h 1385 1170 8
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 136 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
• Double central locking: for easy installation
and ingress protection
• Battery duration 2 hours
• Including accessories, cable gland & fixing brackets
88
EVT-EM RangeEmergency weatherproof fl uorescent fi tting with diffuser
Approvals / Characteristics Features
Thomas & Betts • www.tnb-hazardous.com
Industrial Emergency Lighting - EVT-EM Range
Technical Specifi cations
89
Related Products
Dimensions
Spares & Fixings Accessories see pages 94-99
EnclosureFibreglass reinforced polyester bodyPolycarbonate diffuserTemperatureAmbient temperature: -10ºC to +40ºCFixingStandard: V015 - 2 Zinc Plated Steel brackets for ceiling mounting
Rated voltagesElectronic ballast: AC/DC 220-240V, 50-60HzBatteryNi-Cd 7.2V battery 4AhLumen level in emergency mode (1 tube lit):40% for 18W, 33% for 36WBattery duration in emergency mode:2 hoursBattery charge monitored by LEDPower factor0.98 with electronic ballastCable entriesStandard: Three M20 cable entries includedTwo M20 Nylon plugs andOne cable gland - ISO M20 Nylon, diameter 8-13mm for non-armoured cableFor armoured cable - continuity plate option:Nickel Brass cable gland (1 and 2 according to number of plates)
Terminal block (plug in terminal block)Up to 6mm² (rigid wire), 4mm² (fl exible wire)Select function: Lighting in maintained mode or lighting in non-maintained modeLamps (order separately)T8 bi-pin G13 tube, Ø 26 - cool white 4000°K
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Battery Current (A) A B C Weight (kg)
EVT120EM-00J0 3 Wire Loop 1 x 18 2h 0.09 785 170 432 6.5
EVT120EM-A0J0 5 Wire Loop 1 x 18 2h 0.09 785 170 432 6.5
EVT120EM-B0J0 5 Wire Through 1 x 18 2h 0.09 785 170 432 6.5
EVT140EM-00J0 3 Wire Loop 1 x 36 2h 0.17 1370 170 900 8.5
EVT140EM-A0J0 5 Wire Loop 1 x 36 2h 0.17 1370 170 900 8.5
EVT140EM-B0J0 5 Wire Through 1 x 36 2h 0.17 1370 170 900 8.5
EVT220EM-00J0 3 Wire Loop 2 x 18 2h 0.17 785 170 432 7.5
EVT220EM-A0J0 5 Wire Loop 2 x 18 2h 0.17 785 170 432 7.5
EVT220EM-B0J0 5 Wire Through 2 x 18 2h 0.17 785 170 432 7.5
EVT240EM-00J0 3 Wire Loop 2 x 36 2h 0.33 1370 170 900 10.5
EVT240EM-A0J0 5 Wire Loop 2 x 36 2h 0.33 1370 170 900 10.5
EVT240EM-B0J0 5 Wire Through 2 x 36 2h 0.33 1370 170 900 10.5
*EVT... EM-C0J0 - 3 Wire loop & continuity plate*EVT... EM-E0J0 - 5 Wire through & 2 continuity plates
170
137
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 136 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
• Double central locking: for easy installation
and ingress protection
• Battery life 3 hours with battery charge monitor
• Including accessories, cable gland & fixing brackets
90
EVT-EMA RangeEmergency weatherproof fl uorescent fi tting with diffuser
Approvals / Characteristics Features
Thomas & Betts • www.tnb-hazardous.com
Industrial Emergency Lighting - EVT-EMA Range
Technical Specifi cations
91
Related Products
Dimensions
Spares & Fixings Accessories see pages 94-99
Wiring Battery 3h+ Nominal Dimensions (mm)
Type Confi guration Rating (W) Auto Test Current (A) A B C Weight (kg)
EVT120EMA-A0J0 5 Wire Loop 1 x 18 3h 0.09 785 170 432 6.5
EVT140EMA-A0J0 5 Wire Loop 1 x 36 3h 0.17 1370 170 900 8.5
EVT140EMA-B0J0 5 Wire Through 1 x 36 3h 0.17 1370 170 900 8.5
EVT220EMA-A0J0 5 Wire Loop 2 x 18 3h 0.17 785 170 432 7.5
EVT240EMA-A0J0 5 Wire Loop 2 x 36 3h 0.33 1370 170 900 10.5
EVT240EMA-B0J0 5 Wire Through 2 x 36 3h 0.33 1370 170 900 10.5
170
137
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 136 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
EnclosureFibreglass reinforced polyester bodyPolycarbonate diffuserPower factorSuperior to 0.98Cable entriesStandard: Three M20 cable entries includedTwo M20 Nylon plugs and One cable gland - ISO M20 Nylon, diameter 8-13mm for non-armoured cableFixingStandard: V015 - 2 Zinc Plated Steel brackets for ceiling mounting
Rated voltagesElectronic ballast: AC/DC 220-240V, 50-60HzFor other voltages contact SalesBatteryNi-Cad 6V 4Ah for 18W / Ni-Cad 6V 7Ah for 36W Battery in fl ameproof case (Auto cut out of defective light)Lumen output in emergency mode (1 tube lit): 40% at 18W, 33% at 36WBattery duration: 3h max 36WPreventive maintenance - Self test- Battery charge - daily- Emergency lamp during 1min - weekly- Battery charge capacity during 1hr - quaterly- Clean system test displayBattery charge monitored by 2 LED
Terminal blockUp to 4mm² (rigid wire), 2.5mm² (fl exible wire)Command must be supplied with switch on lineLamps (order separately)Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
Healthy(test OK)
Emergency or Indicator
Lamp Fault
Test inProgress
(waiting end
Fault(replacebattery)
• Fitting combines photometric qualities, strength
and design
• Easy access to components
• Battery duration 2 hours
• Including accessories & cable gland
Approvals / Characteristics Features
92
EST-EM RangeEmergency weatherproof recessed fl uorescent fi tting
5
Thomas & Betts • www.tnb-hazardous.com
Industrial Emergency Lighting - EST-EM Range
Technical Specifi cations
93
Related Products
Dimensions
Spares & Fixings Accessories see pages 94-99
EnclosureSteel housing and body painted in white polyester powder paint RAL 90166mm clear toughened glass panel (optional frosted low lumen output) Neoprene gasketTemperatureOperating temperature range:-10°C to +40°C
Rated voltagesElectronic ballast:Standard: AC/DC 220-240V, 50-60HzFor other voltages contact SalesBattery: Ni-Cd 6V 7Ah batteryLumen level in emergency mode (1 tube lit): 33% Emergency load duration: 2 hoursBattery charge monitored by LEDPower factorSuperior to 0.98Cable entriesStandard: Two M20 cable entries includedOne M20 Nylon plug andOne cable gland - ISO M20 Nylon, diameter 8-13mm
Terminal blockUp to 4mm² (rigid wire), 2.5mm² (fl exible wire)Terminals for L, N, PE terminal 1 and terminal 2Select function: Lighting in maintained mode or lighting in non-maintained modeLamps (order separately)Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
240
240
Wiring Nominal Dimensions (mm)
Type Confi guration Rating (W) Battery Current (A) Glass A B C Weight (kg)
EST240EM-00J0 3 Wire Loop 2 x 36 2h 0.33 Toughened 1364 1312 105 22
EST240EM-A0J0 3 Wire Loop 2 x 36 2h 0.33 Frosted 1364 1312 105 22
Thomas & Betts • www.tnb-hazardous.com
EXB Conduit 138 Nylon Stopping Plugs 164
Exe Nylon Gland 166XB100 Range 108
Fixing Accessories
94
,602 Ø 8.5
Fixing Accessories for EV Fluorescent Light Fitting Range
3 5
Ø11
35 35
Ø8
R
55
35 3
2 Ø 113
Fixing Accessories for XFF / XFR / XFP / XEL / XEP / XFF-EM / XFP-EM Range
Fixing Accessories for DTS lighting fi ttings
U-bolt for pole mountingfor 1”1/4
D025: zinc plated steel
BracketStandard D023: zinc plated steel
D024: stainless steel
fl 9
20 30
60¡maxi
30
2
10070
2 x fl 9
fl 36fl 20
M 8
18
25
M8
100
41ø9
~70α
25 ø9
25160200
2 oblong holes18x9
Hinged bracketV023: plastic coated
HookV024: zinc plated steel
Fixing bracket and fl ange for ø 1”1/4 and 1”1/2
V018: zinc plated steel (V015 - 2”)V021: stainless steel (V022 - 2”)
BracketsStandard V015: zinc plated steel
V016: stainless steel
Mounting bracket clipV014: stainless steel
Thomas & Betts • www.tnb-hazardous.com
Spare Parts
Accessories & Spare Parts
95
Spare Parts for EV Fluorescent Light Fitting Range
005003
002
004008009
007002
004
001
Spare Parts for DTS lighting fi ttings
EVS RangeType Specifications
V001 Transparent diffuser
V002 Gasket
V004 Complete gear tray*
V005 XIN switch
V006 Exe terminal block
V008 G13 bi-pin lampholder
EVN / EVD RangeType Specifications
V001 Transparent diffuser
V002 Gasket
V004 Complete gear tray*
V005 XIN switch
V006N Terminal block
V007N Electronic ballast*
V008N Bi-pin lampholder
ESB / ESB-EM RangeType Specifications
Z001 Transparent frame
V003 Box cover
V005 XIN switch
V006 Exe terminal block
V007 Electronic ballast Exd* (ESB)
V012A Electronic ballast Exd* (ESB-EMA)
V008 G13 bi-pin lampholder
Spare Parts for ESB / ESB-EM Range
*Defi ne type, rating and operating voltage
*Defi ne type, rating and operating voltage
005
003
007
008
001
Thomas & Betts • www.tnb-hazardous.com
P
96
Spare Parts
Spare Parts for XFF / XFR Range
XFF / XFR RangeType Specifications
D001 Tube (+ D002, + D003, +D011)
D003 Gasket
D004 Slide for gear tray
D005 Sliding gear tray*
D006 Connector
D007 Starter socket
Type Specifications
D008 Starter
D009 Ballast*
D009E Electronic ballast
D010 Lamp holder
D010PL G11 lampholder for PL
*Specify rating plus voltage
Spare Parts for DTS lighting fi ttings
Spare Parts for XFP Range
XFP RangeType Specifications
D001P Tube (+ D002, + D003, +D011)
D003 Gasket
D004 Slide for gear tray
D005 Sliding gear tray*
D006 Connector
D007 Starter socket
Type Specifications
D008 Starter
D009 Ballast*
D009E Electronic ballast
D010 Lamp holder
D010PL G11 lampholder for PL
*Specify rating plus voltage
Type Specifications
D017 Box gasket
D018 Box cover
D019 Screw for box cover
D020 Terminal block
D021 Switch
D022 Interlock
Thomas & Betts • www.tnb-hazardous.com
Accessories & Spare Parts
97
Spare Parts
Spare Parts for DTS lighting fi ttings
*Specify rating plus voltage
Thomas & Betts • www.tnb-hazardous.com
Spare Parts for XEL / XEP Range
*Specify rating plus voltage
XEL
XEP
Spare Parts for XF Range
XF RangeType Specifications
P001 Closing screw
P002 Sealed front glass
P004 Gasket
P006 Lamp*
P007 Lampholder E40
P008 Reflector
P009 Ballast 230 / 240V (150, 250, 400W)*
P010 Ballast 120V (400W)
Type Specifications
P012 Starter
P015 Safety support cable
P017 Mounting bracket
P018 Support screw
P019 Terminal block 2 x 6
P021 Earthing terminal
P022 Box gasket
P023 Box cover
XEL / XEP RangeType Specifications
B001 Tube (+ D002, + D003, + D011)
D003 Gasket
B004 Slide for gear tray
M005.1 Sliding gear tray - XEL300/8*
M005.2 Sliding gear tray - XEL300/28*
M005.3 Sliding gear tray - XEL30011
M005.4 Sliding gear tray - XEL120*
Type Specifications
M005.5 Sliding gear tray - XEL220*
D006 Connector
D007 Starter socket
D008 Starter
D009 Ballast
D010 Lampholder
D010PL G11 lampholder for PL lamps
Type Specifications
D017 Box gasket
D018 Box cover
D019 Screw for box cover
D20 Terminal block
D021 Switch
D022 Interlock
Type Specifications
P025 Cover screw
P026 Cable gland
P030 Ex through wiring connector
E006 Optic
E007 70W iodine lamp
E008 Gear tray support
E009 Attachment for optic
98
Spare Parts
Spare Parts for XFF-EM / XFP-EM Range
*Specify rating plus voltage
Spare Parts for DTS lighting fi ttings
Spare Parts for EV Range
EV RangeType Specifications
D002 Cover
D003 Gasket
D004 Slide for gear tray
D005 Sliding gear tray*
D006 Connector
D007 Starter socket
Type Specifications
D008 Starter
D009 Ballast*
D009E Electronic ballast
D010 Lamp holder
D010PL G11 lampholder for PL
D011 Chain
*Specify rating plus voltage
XFF-EM RangeType Specifications
D001 Tube (+ D002, + D003, +D011)
D003 Gasket
D004 Slide for gear tray
D005 Sliding gear tray*
D006 Connector
D007 Starter socket
Type Specifications
D008 Starter
D009 Ballast*
D009E Electronic ballast
D010 Lamp holder
D010PL G11 lampholder for PL
XFP-EM RangeType Specifications
D001P Tube (+ D002, + D003, + D011)
D003 Gasket
D004 Slide for gear tray
D005 Sliding gear tray*
D006 Connector
D007 Starter socket
Type Specifications
D008 Starter
D009 Ballast*
D009E Electronic ballast
D010 Lamp holder
D010PL G11 lampholder for PL
D017 Box gasket
Type Specifications
D018 Box cover
D019 Screw for box cover
D020 Terminal block
D021 Switch
D022 Interlock
Thomas & Betts • www.tnb-hazardous.com
Spare Parts for XDF Range
XDF RangeType Specifications
XF001 Gear cover
FF002 Cover fixing screw
FF003 Cover gasket
FF004 Starter switch
FF005 Starter socket
FF006 Ballast 120VAC - 50Hz
FF007 Ballast 120VAC - 60Hz
FF008 Ballast 208/220VAC - 50Hz
FF009 Ballast 208/220VAC - 60Hz
Type Specifications
FF010 Ballast 240VAC - 50Hz
FF011 Ballast 240VAC - 60Hz
XFF012 Lamp holder
XFF013 Body
FF014 Mounting brackets
FF015 Beam mounting brackets
FF016 Stainless steel tube support bracket
FF017 Bi pin tube
Type Specifications
FF018 Fixing screws
FF019 Connecting terminals
FF020 Earthing terminal
FF021 Lamp cover
FF022 M20 cable gland
FF023 3 pole 10A male connector
FF024 3 pole 10A female connector
FF025 Protective cap
99
Accessories & Spare Parts
Spare Parts
Spare Parts for DTS lighting fi ttings
Spare Parts for XEL-BAES Range - XEL / XEP
XFF / XFR RangeType Specifications
B001 Tube (+ D002, + D003, + D011)
B001P Tube (+ D002, + D003, + D011)
D003 Gasket
B004 Sliding gear tray
B005B Gear tray - XEL80A
B006 Gear tray - XEL300
B006L Gear tray - XEL300/1
B007 Gear tray - XEL300/2
Type Specifications
B008B Batteries - XEL80
B009A Batteries - XEL300A
B010B Gear tray - XEL80AK / AI
B011 Gear tray - XEL300AK
B013 Gear tray - XEL300A
B013K Gear tray - XEL300AK
B014B Gear tray - XEL80SI*
B015 Gear tray - XEL300SI*
*Specify address number
Type Specifications
B016 Kit - XEL80K
B017 Kit - XEL300K
D017 Box gasket
D018 Box cover
D019 Screw for box cover
D20 Terminal block
D021B Switch
D022 Interlock
Thomas & Betts • www.tnb-hazardous.com
001002
003
004
005006007
012
012
013
014
015
014015
016
008009010011
019
017
020
022023024
025
018
003
002
021
XEP
XEL
Compact fluorescent lampsSpecifications: PN Power (W) Flux (lm) Cap Lighting equipment Reference
PL7W 7 400 G23 Miniature XEL / XEP...
PL9W 9 600 G23 Weatherproof miniature EL...
PL11W 11 900 G23 Fluorescent XFR / XFF / XFP
PL18W 18 1200 2 G11
PL36W 36 2900 2 G11
PL55W 55 4800 2 G11
LED lampsSpecifications: Power (W) Flux (lm) Cap Lighting equipment Reference
8 345 E27 Beacon XFB
12 806 E27 Weatherproof beacon FB
E27
CRI: 80 - Lm/W: 55
Colour temperature: 3000K
Average life: 25,000 hours
Integral electronic ballast
For Part Number - Contact Sales
100
Lamps Guide
Bi-pin T8/T12 fluorescent tubesSpecifications: PN Power (W) Flux (lm) Cap Lighting equipment Reference
TL18W 18 1250 G13 Fluorescent EVS...
TL36W 36 3350 G13 Fluorescent XFR / XFF / XFP...
TL58W 58 5200 G13 Fluorescent EVN...
Fluorescent EVD...
Weatherproof fluorescent EVT... FR/FF
Guide to Lamps for use in DTS lighting fi ttings
Miniature T5 fluorescent tubesSpecifications: PN Power (W) Flux (lm) Cap Lighting equipment Reference
TL8W 8 430 G5 Miniature XEL / XEP...
Weatherproof miniature EL...
BAES range XEL BAES...
G5 - ø 15mm
CRI: 60 > 85 - Lm/W: 51 > 59
Colour temperature:
2700K > 4100K
Average life: 6,000 hours
Electronic ballast or inverter
G13 - ø 26mm or ø 38mm
CRI: > 80 - Lm/W: 65 > 93
Colour temperature:
2700K > 6500K
Average life: 6,000 > 10,000 hours
Standard or electronic ballast
Thomas & Betts • www.tnb-hazardous.com
Halogen lampsSpecifications: Power (W) Flux (lm) Cap Lighting equipment Reference
28 345 E27 Beacon XFB
70 1200 E27 Wellglass EVX / EVH
140 3000 E27 Weatherproof beacon FB
CRI: 100 - Lm/W: 10 > 17
Colour temperature:
2700K
Average life: 1,000 hours
For Part Number - Contact Sales
G23 or G11
CRI: 85 > 90 - Lm/W: 57 > 87
Colour temperature:
2700K > 4000K
Average life: 20,000 hours
Standard or electronic ballast,
inverter
101
Lamps Guide
High pressure sodium tubular lampsSpecifications: NP Power (W) Flux (lm) Cap Lighting equipment Reference
P00670SHP 70 6000 E40 Ex d floodlight XSF...
P006150SHP 150 45000 E40 Weatherproof floodlight SF...
P006250SHP 250 28000 E40
P006400SHP 400 48000 E40
Guide to Lamps for use in DTS lighting fi ttings
Metal halide tubular lampsSpecifications: NP Power (W) Flux (lm) Cap Lighting equipment Reference
P006250IM 250 20000 E40 Ex d floodlight XQF...
P006400IM 400 42000 E40 Weatherproof floodlight QF...
Halogen lampsSpecifications: NP Power (W) Flux (lm) Cap Lighting equipment Reference
S00755W 55 1350 H3 Ex d floodlight XEF / XHF...
S00770W 70 1770 H3 Weatherproof floodlight EF / HF...
H3
CRI: 100 - Lm/W: 25
Colour temperature:
3000K
Average life: 1,000 hours
CRI: 65 - Lm/W: 68 > 76
Colour temperature:
4300K > 4600K
Average life: 3,000 > 6,000 hours
Mimimum starting temperature: -25ºC
Time to full power: 5 > 10mm
With control gear and ignitor
CRI: NS - Lm/W: 100 > 120
Colour temperature: 2100K
Average life: 15,000 > 20,000 hours
Mimimum starting temperature: -30ºC
Time to full power: 1 > 10mm
With control gear and ignitor
Metal halide egg-shaped lampsSpecifications: Power (W) Flux (lm) Cap Lighting equipment Reference
250 12700 E40 Ex d wellglass EVX
400 22000 E40
250 12700 E40
400 22000 E40
High pressure sodium egg-shaped lampsSpecifications: Power (W) Flux (lm) Cap Lighting equipment Reference
70 6300 E27 Ex d wellglass EVX / EVH Na...
150 17000 E40
250 31100 E40
400 55500 E40
CRI: NS - Lm/W: 80 > 125
Colour temperature:
2000K > 2200K
Average life:
34,000 hours
Mimimum starting temperature: -25ºC
Time to full power: 1 > 10mm
With control gear and ignitor
For Part Number - Contact Sales
Thomas & Betts • www.tnb-hazardous.com
CRI: 33 > 49 - Lm/W: 50 > 60
Colour temperature:
3900K > 4300K
Average life: 15,000 > 20,000 hours
Mimimum starting temperature: -25ºC
Time to full power: 5 > 10mm
With control gear
For Part Number - Contact Sales
EVH 100 (Halogen) EVX 100 (Halogen)
EVX Range - Halogen Dimensions (mm)
Type Rating (W) Lamps Nominal (A) A/A’ B Tº Class Weight in (kg)
EVX100-00000 70 E27 Halogen 0.45 250/283 150 T4 2.9
EVX200-00000 140 E27 Halogen 0.90 313/346 170 T3 3.5
EVX300-00000 250 E27 Mixed light 1.30 410/463 220 T3 7.2
*EVH version, remove X and add H, e.g. EVH120-00000
102
EnclosureBody in marine grade aluminium alloy (CU<0.05%) Yellow polyurethane paint RAL1003Borosilicate glass globeGalvanised steel protection grillIngress rating: IP65 (EN60529), neoprene ingress gasketStainless steel screwsTemperatureAmbient temperature range:-20°C to +60°C Surface temperature classifi cation: T4 to T3 (gas)
Rated voltagesHP Sodium metal halide Standard: 230V 50Hz compensated, wirewound ballastPower factor0.85 (HP Sodium and metal halide)Cable entriesEVH: four 3/4” NPT entries - fi tted 2 plugsEVX: four 3/4” NPT entries - fi tted 2 plugsTerminal blockUp to 6mm² (rigid wire), 4mm² (fl exible wire)
LampsNot suppliedFixingCeiling screw M8 (EVX)Suspension ring (EVH)Spare part: 30º angle wall mounting arm (R018)
EC TYPE Examination Certificate:IECEx CES 07.0004CESI 12 ATEX 006GOST RII 2 GDEx d IIC T...ºC GbEx tb IIIC T...ºC Db IP66
Lamps Guide
EV Range - Wellglass, Lantern or High Bay FIttings
EVX / EVH Range
Thomas & Betts • www.tnb-hazardous.com
EVH Na (HP Sodium) EVX Na (HP Sodium) EVH Im (Metal Halide) EVX Im (Metal Halide)
Lamps Guide
103
EnclosureBody in marine grade aluminium alloy (CU<0.05%) Yellow polyurethane paint RAL1003Borosilicate glass globeGalvanised steel protection grillIngress rating: IP65 (EN60529), neoprene ingress gasketStainless steel screwsTemperatureAmbient temperature range:-20°C to +60°C Surface temperature classifi cation: T4 to T3 (gas)
Rated voltagesHP Sodium metal halide Standard: 230V 50Hz compensated, wirewound ballastPower factor0.85 (HP Sodium and metal halide)Cable entriesEVH: four 3/4” NPT entries - fi tted 2 plugsEVX: four 3/4” NPT entries - fi tted 2 plugsVariants: Other options available on requestTerminal blockUp to 6mm² (rigid wire), 4mm² (fl exible wire)
LampsNot suppliedFixingCeiling screw M8 (EVX)Suspension ring (EVH)Spare part: 30º angle wall mounting arm (R018)
EC TYPE Examination Certificate:IECEx CES 07.0004CESI 12 ATEX 006GOST RII 2 GDEx d IIC T...ºC GbEx tb IIIC T...ºC Db IP66
EV Range - Wellglass, Lantern or High Bay FIttings
EVXNa / EVXlm / EVHNa / EVHlm Range
EVXNa Range - HP Sodium Dimensions (mm)
Type Rating (W) Lamps Nominal (A) A/A’ B TºC Class Weight in (kg)
EVXNa20-00000 70 E27 Egg shaped 0.40 470/500 200 T4 6.5
EVXNa30-00000 150 E40 Egg shaped 0.80 600/633 220 T3 9.7
EVXNa40-00000 250 E40 Egg shaped 1.30 600/633 220 T3 9.7
EVXNa50-00000 400 E40 Egg shaped 2.10 630/670 270 T3 12
*EVH version, remove X and add H, e.g. EVHNa120-00000
EVXlm Range - Metal Halide Dimensions (mm)
Type Rating (W) Lamps Nominal (A) A/A’ B TºC Class Weight in (kg)
EVXlm40-00000 250 E40 Egg shaped 1.30 600/633 220 T3 9.7
EVXlm50-00000 400 E40 Egg shaped 2.10 630/670 270 T3 12
*EVH version, remove X and add H, e.g. EVHlm120-00000
Thomas & Betts • www.tnb-hazardous.com
Ex Boxes & EnclosuresEx Boxes & Enclosures
26104
Thomas & Betts • www.tnb-hazardous.com
Prot
ectio
n Ty
pe
106
Ex Boxes & Enclosures Range
Ex Boxes & Enclosures - Selection Guide
Thomas & Betts • www.tnb-hazardous.com
XBL InstrumentBoxes Page 112
XBInstrumentBoxes Page 116
XB-AControlBoxes Page 118
XBL Junction Boxes Page 108
XBi-AControlBoxes Page 122
XBiInstrumentBoxes Page 120
Gas
Gro
ups
Dus
tG
roup
Zo
nes
XBL-AControlBoxes Page 114
Ex Boxes & Enclosures - Selection Guide
107
Thomas & Betts • www.tnb-hazardous.com
EFDCControlBoxes Page 126
GUVJunction Boxes Page 124
EJBCustom Built Panel Page 128
SRCControlBoxes Page 126
XMCControlBoxes Page 126
• External mounting points allowing for junction boxes to be mounted without the need for the removal of lid• Robust design• Manufactured from anti static GRP so eliminating any chance of static build up• Supplied complete with terminals and glands so all
on site combinations are covered
Approvals / Characteristics Features
108
XBL RangeXB100 Junction boxes
Certifi cation & StandardsApproved to: EN60079-0, 60079-7, 60079-11, EN61241-0, 61241-1EC TYPE Examination Certificate: Under 94/9/ECLCIE 11 ATEX 3049X / IECEx LCI 11.0045XEx II 2 G / II 2 DEx e II T6 to T5Ex tD A21 IP66 T85ºC to T100ºCT6: -20ºC to 40ºCT5: -20ºC to 55ºCGlow wire test: 960ºC EN60598-2-22
Thomas & Betts • www.tnb-hazardous.com
XFF Range 28 EVS Range 42 Exe Nylon Gland 166
Ex Boxes & Enclosures - XBL Range
Technical Specifi cations
109
Related Products
Dimensions
Stopping Plugs 164
AVERTISSEMENT- NE PAS OUVRIR SOUS TENSIONWARNING- DO NOT OPEN WHILE ENERGIZED
32
121
121
R3.2
100
100
75.5
No. of Glands Plug No. of Terminal Plate Bonding
Type Entries Material Gland Size Thread Size Provided Connectors Type Section Conncetion Conductors
XB100-6BV 4 Poly M20a 8-13mm 1 x M20 6 4 x Grey 6mm2 bridge x2 Screw/Screw –
2 x 6mm2 bridge x2 Screw/Screw –
XB100-6BR 4 Poly M20a 8-13mm 1 x M20 6 4 x Grey 4mm2 bridge Spring/Spring –
2 x 4mm2 bridge Spring/Spring –
XB100-10BV 4 Poly 3 x M20a 8-13mm 1 x M20 6 4 x Grey 10mm2 bridge x2 Screw/Screw –
1 x M32 17-25mm 2 x 10mm2 bridge x2 Screw/Screw –
XB100A-6BV 4 Nickel Plated Brass M20T6* 6-12mm Int. 1 x M20 6 4 x Grey 6mm2 bridge x2 Screw/Screw Yes
8.5-16mm Ext. 2 x 6mm2 bridge x2 Screw/Screw
XB100A-6BR 4 Nickel Plated Brass M20T6* 6-12mm Int. 1 x M20 6 4 x Grey 4mm2 bridge x2 Spring/Spring Yes
8.5-16mm Ext. 2 x 4mm2 bridge x2 Spring/Spring
XB100A-10BV 4 Nickel Plated Brass 3 x M20T6* 6-12mm Int. 1 x M20 6 4 x Grey 10mm2 bridge x2 Screw/Screw Yes
8.5-16mm Ext.
1 x M32T8* 12-21mm Int. 2 x 10mm2 bridge x2 Screw/Screw
16-27.5mm Ext.
*For reinforced cable EGFA
Thomas & Betts • www.tnb-hazardous.com
Approvals / Characteristics Features
110
XBL RangeJunction boxes
Certifi cation & Standards
• Robust design• Manufactured from anti static GRP so eliminating any chance of static build up• Supplied complete with terminals and glands so all on site combinations are covered
Approved to: EN60079-0, 60079-7, 60079-11, EN61241-0, 61241-1EC TYPE Examination Certificate: Under 94/9/ECLCIE 11 ATEX 3049X / IECEx LCI 11.0045XEx II 2 G / II 2 DEx e II T6 to T5Ex ia IIC T6Ex tD A21 IP66 T85ºC to T100ºCT6: -20ºC to 40ºCT5: -20ºC to 55ºCGlow wire test: 960ºC EN60598-2-22
Thomas & Betts • www.tnb-hazardous.com
EJB Range 128 EVS Range 42 Exe Nylon Gland 166
Ex Boxes & Enclosures - XBL Range
Glands Plug No. of Terminal Plate Bonding
Type No. of Entries Material Gland Size Thread Size Provided Connectors Section Connection Conductors
XBL28-25BR 6 Poly M20a 8-13mm 1 x M20 3 8 x 2, 5mm2 deck Spring/Spring –
XBL26-25R 4 Poly M20a 8-13mm 1 x M20 3 4 x 2, 5mm2 deck Spring/Spring –
Technical Specifi cations
111
Related Products
Dimensions
Stopping Plugs 164
110
75
25
75.5
AVERTISSEMENT- NE PAS OUVRIR SOUS TENSIONWARNING- DO NOT OPEN WHILE ENERGIZED
25
81
81
R6.5
75.5
XB10-SI Boxes for connecting SI Sensors (for Instrumentation Box Zone 0 Products)
Dimensions
No. of Glands Plug No. of Terminal Plate Bonding
Type Entries Material Gland Size Thread Size Provided Connectors Colour Section Connection Conductors
XB10-SI 3 Poly (Blue) M16b 6-10mm 1 x M16 6 4 x Blue 2.5mm2 Screw/Screw –
2 x V/J 2.5mm2 Screw/Screw –
XB10A-SI 3 Poly (Blue) M16b 8-13mm 1 x M16 6 4 x Blue 2.5mm2 Screw/Screw Yes
Nickel Plated Brass M20T6* 6-12mm Int. 2 x V/J 2.5mm2 Screw/Screw
8.5-16mm Ext.
*For reinforced cable EGFA
Type Connection Nominal Section Maximum Intensity
XB10-SI Rigid 0.5 - 6mm2 21A
Semi Rigid 0.5 - 4mm2
XB10A-SI Flexible 0.5 - 4mm2 21A
Flexible Tip 0.5 - 2.5mm2
Thomas & Betts • www.tnb-hazardous.com
112
XBL RangeInstrumentation boxes
• Robust design• Manufactured from ant static GRP so eliminating any chance of static build up• Can be supplied complete with terminals and glands so
all on site combinations are covered
Approvals / Characteristics Features
Certifi cation & StandardsApproved to: EN60079-0, 60079-1, 60079-7, 60079-11, EN61241-0, 61241-1EC TYPE Examination Certificate: Under 94/9/EC LCIE 11 ATEX 3049X / IECEx LCI 11.0045XEx II 2 G / DEx e or ia or eia IIC T6, T5 or T4Ex tD A21 IP66 T85ºC, T100ºC or T135ºCT4: ≤ -20ºC to ≤ +90ºCT5: ≤ -20ºC to ≤ +55ºCT6: ≤ -20ºC to ≤ +40ºCLCIE 11 ATEX 3035 U / IECEx LCI 11.0028UEx e IIEx tD A21 IP66Glow wire test: 960°C EN60598-2-22
Thomas & Betts • www.tnb-hazardous.com
Ex Boxes & Enclosures - XBL Range
Technical Specifi cations
113
Related Products
Dimensions
EnclosureGlass fi bre reinforced polyester with graphite fi nish (R<1G Ohm)Stainless steel unlosable screwsOptional hinges
Rated voltagesDependent on the components fi tted in the box (eg:with terminal block: Un max = 500V)Cable entriesISO entries and threadsNylon cable glands for non-armoured cableNickel chromed brass cable glands for non-armoured cableNickel chromed brass PE series cable glands for armoured cable PEP series with brass continuity plate on XBL
Terminal block Equipment of the terminal lock wire any type of certifi ed Exe or Exia terminals. The maximum number of terminal blocks per box isdependent on the certifi cationStainless steel external earthOther options available upon request
Maximum number of terminals
Dimensions (mm) size (in mm2) / In Max (in A) Weight in
Type Material A B C D E 2.5/21 4/28 6/36 10/50 16/66 35/109 70/167 70/95/100 120/234 185/307 240/350 (kg)
XBL15 Poly 122 120 91 106 82 13 11 8 6 – – – – – – – 0.8
XBL20 Poly 110 75 75 98 45 11 (Min) 9 (Min) – – – – – – – – – 0.4
XBL25 Poly 220 120 91 204 82 33 28 21 16 – – – – – – – 1.1
XBL35 Poly 360 160 91 340 110 60 50 38 30 25 – – – – – – 2.2
XBL40 Poly 405 400 121 380 355 204 171 129 68 58 21 – – – – – 5.6
XBL45 Poly 400 250 121 380 200 136 114 86 34 29 21 – – – – – 3.7
XBL55 Poly 400 250 161 380 200 136 114 86 34 29 21 17 – – – – 4.8
XBL65 Poly 600 250 121 580 200 216 180 136 54 45 34 – – – – – 5.2
XBL75 Poly 405 605 252 370 570 312 261 130 104 86 32 25 19 6 5 5 7.2
For mounting ø 06.5
Thomas & Betts • www.tnb-hazardous.com
EJB Range 128 EVS Range 42 Exe Nylon Gland 166Stopping Plugs 164
For full details and design service contact Sales
• Wide variety of sizes and functions available as standard products for speed of supply and custom
built to meet the end users exact requirements• All manufactured with approved components• Manufactured from anti static GRP so eliminating any chance of static build up
Approvals / Characteristics Features
114
XBL-A RangeStandard control boxes
Certifi cation & StandardsApproved to: EN60079-0, 60079-1, 60079-7, 60079-11, EN61241-0, 61241-1EC TYPE Examination Certificate: Under 94/9/EC LCIE 11 ATEX 3049X / IECEx LCI 11.0045XEx II 2 G / DEx de or e or ia or eia IIC T6, T5 or T4Ex tD A21 IP66 T85ºC, T100ºC or T135ºCT4: ≤ -20ºC to ≤ +90ºCT5: ≤ -20ºC to ≤ +55ºCT6: ≤ -20ºC to ≤ +40ºCGlow wire test: 960ºC EN60598-2-22
Thomas & Betts • www.tnb-hazardous.com
Ex Boxes & Enclosures - XBL-A Range
Technical Specifi cations
115
Related Products
Dimensions
EnclosureXBL-A: Glass fi bre reinforced polyester with graphite fi nish (R< 1 Gohm)Stainless steel unlosable screws Optional hingesProtection class: ITechnical CharacteristicsAC: U = 415V max. I = 1,75A or U = 240V, I = 3A orU = 120V, I = 6A DC: U = 415V max. I = 0,165A or U = 250V, I = 0,27A or U = 125V, I = 0,55A
Cable entriesEntries and threads ISO Nylon cable glands for non-armoured cableNickel chromed brass PE series cable glands for non- armoured cable Nickel chromed brass PEP cable glands for armoured cable with brass continuity plate on XBL-A
ComponentsDrilling on request Full range indicator lamp with LED Voltage of use 24V-254V AC/DCPush button (green, red, black, yellow or blue) 1 contact (3 contacts maximum)Emergency stop 1 contact (3 contacts maximum) Rotary switch 2 or 3 positions (2 contacts maximum) Anmeter Ex e: direct 1A or with CT/1Amp. max.
For Accessories see page 130
XBL: 122 x 120 x 91 (mm) XBL: 220 x 120 x 91 (mm)
1 Function 2 Functions Ammeter 3 Functions 4 Functions Ammeter
Type 21A 21FA 21VA 215A 215VA 22A 23A AMP 26A 38A 41A 43A 22AMP 38AMP
Push Button Green 1 NO ● – – – – ● ● – ● ● ● ● ● ●
Emergency Stop PB Push/Pull 1 NC – ● – – – – – – ● – – – – –
Emergency Stop PB Push/Pull 1 NC with Key 455 – – ● – – – – – – – – – – –
Switch 0-1, 2NO – – – ● – – – – – ● – – – ●
Switch with Key 0-1, 1 NO – – – – ● – – – – – – – – –
Push Button Red 1 NC – – – – – ● – – – ● ● ● ● ●
Green Indicator Lamp – – – – – – ● – ● – ● ● – –
Red Indicator Lamp – – – – – – – – – – – ● – –
Ammeter TC/IA Graduate – – – – – – – ● – – – – ● ●Scale 0-In-3In dilo IN= to be indicated
Front Plug – – – – – – – – – – – – ● –
*Add function to complete part number, e.g. XBL21A
**Second cablegland impossible
M6
M20 x 1,5M6
M6
M20 x 1,5M20 x 1,5
**Second cablegland impossible
M6M20 x 1,5
3 x ø22.5
XB300 / XBL15 XB400 / XBL25XB300 / XBL15with ammeter
XB400 / XBL25with ammeter
Visu 50x50
3x ø22.5
Visu 50x50 104
80
80
214
80
214
104
80
ø22.5
Standard Confi gurations
Thomas & Betts • www.tnb-hazardous.com
EJB Range 128 EVS Range 42 Exe Nylon Gland 166Stopping Plugs 164
116
• Robust design and paint finish ideal for marine application
• Can be supplied complete with terminals and glands
so all on site combinations are covered
Approvals / Characteristics Features
Approved to: EN60079-0, 60079-1, 60079-7, 60079-11, EN61241-0, 61241-1EC TYPE Examination Certificate: Under 94/9/EC LCIE 11 ATEX 3051X / IECEx LCI 11.0046XEx II 2 G / DEx e or ia or eia IIC T6, T5 or T4Ex tD A21 IP66 T85ºC, T100ºC to T135ºCT4: ≤ -20ºC to ≤ +90ºCT5: ≤ -20ºC to ≤ +55ºCT6: ≤ -20ºC to ≤ +40ºCLCIE 11 ATEX 3046 U / IECEx LCI 11.0043UEx e II Ex tD A21 IP66
Certifi cation & Standards
XB RangeInstrumentation boxes
Thomas & Betts • www.tnb-hazardous.com
Maximum number of terminals
Dimensions (mm) size (in mm2) / In Max (in A) Weight in
Type Material A B C D E 2.5/21 4/28 6/36 10/50 16/66 35/109 70/167 70/95/100 120/234 185/307 240/350 (kg)
XB300 Alu 122 120 91 106 82 13 11 8 6 – – – – – – – 1.0
XB400 Alu 220 120 91 204 82 33 27 21 16 – – – – – – – 1.4
XB510 Alu 160 160 91 140 110 20 17 13 10 – – – – – – – 1.5
XB520 Alu 260 160 91 240 110 40 33 25 20 – – – – – – – 2.0
XB570 Alu 202 232 111 180 180 56 46 36 14 11 9 – – – – – 2.4
XB700 Alu 360 160 91 340 110 61 50 38 30 – – – – – – – 2.5
XB710 Alu 330 230 111 310 180 108 90 68 54 22 17 15 – – – – 3.4
XB750 Alu 403 312 141 382 262 204 171 129 51 42 21 16 – – – – 6.7
XB950 Alu 600 230 111 580 260 216 180 134 54 45 33 – 19 6 5 5 7.0
XB960 Alu 600 600 202 555 525 432 360 204 162 135 132 39 20 11 9 9 26.0
EJB Range 128 EVS Range 42 Exe Nylon Gland 166
Ex Boxes & Enclosures - XB Range
Technical Specifi cations
117
Related Products
EnclosureAluminium ALSi 12, yellow polyurethane paintRAL 1003 (other colours available on request)Stainless steel unlosable screwsOptional hingesRated voltagesDependent on the components fi tted in the box (eg:with terminal block: Un max = 500V)
Cable entriesISO entries and threadsNylon cable glands for non-armoured cableNickel chromed brass cable glands for non-armoured cableNickel chromed brass PE series cable glands for armoured cable PEP series with brass continuity plate on XBL
Terminal block Equipment of the terminal lock wire any type of certifi ed Exe or Exia terminals. The maximum number of terminal blocks per box is dependent on the certifi cationStainless steel external earthOther options available upon request
Dimensions
Stopping Plugs 164
For mounting ø 06.5
Thomas & Betts • www.tnb-hazardous.com
For full details and design service contact Sales
• Wide variety of sizes and functions available as standard products for speed of supply and custom
built to meet the end users exact requirements• All manufactured with approved components allowing
peace of mind• Manufactured from aluminium ideal for marine applications
Approvals / Characteristics Features
118
XB-A RangeStandard control boxes
Certifi cation & StandardsApproved to: EN60079-0, 60079-1, 60079-7, 60079-11, EN61241-0, 61241-1EC TYPE Examination Certificate: Under 94/9/EC LCIE 11 ATEX 3051X / IECEx LCI 11.0046XEx II 2 G / DEx de or e or ia or eia IIC T6, T5 or T4Ex tD A21 IP66 T85ºC, T100ºC to T135ºCT4: ≤ -20ºC to ≤ +90ºCT5: ≤ -20ºC to ≤ +55ºCT6: ≤ -20ºC to ≤ +40ºC
Thomas & Betts • www.tnb-hazardous.com
Exe Nylon Gland 166
Ex Boxes & Enclosures - XB-A Range
Technical Specifi cations
119
Related Products
EnclosureXB-A: Aluminium ALSi 12, yellow polyurethane paint RAL1003 (other colours on request)Stainless steel unlosable screws Optional hingesProtection class: ITechnical CharacteristicsAC: U = 415V max. I = 1,75A or U = 240V, I = 3A orU = 120V, I = 6A DC: U = 415V max. I = 0,165A or U = 250V, I = 0,27A or U = 125V, I = 0,55A
Cable entriesEntries and threads ISO Nylon cable glands for non-armoured cableNickel chromed brass PE series cable glands for non- armoured cable Nickel chromed brass PEP cable glands for armoured cable with brass continuity plate on XBL-A
ComponentsDrilling on request Full range indicator lamp with LED Voltage of use 24V-254V AC/DCPush button (green, red, black, yellow or blue) 1 contact (3 contacts maximum)Emergency stop 1 contact (3 contacts maximum) Rotary switch 2 or 3 positions (2 contacts maximum) Anmeter Ex e: direct 1A or with CT/1Amp. max.
Dimensions
Stopping Plugs 164EJB Range 128 EVS Range 42
Standard Confi gurations
XB: 122 x 120 x 91 (mm) XB: 220 x 120 x 91 (mm)
1 Function 2 Functions Ammeter 3 Functions 4 Functions Ammeter
Type 21A 21FA 21VA 215A 215VA 22A 23A AMP 26A 38A 41A 43A 22AMP 38AMP
Push Button Green 1 NO ● – – – – ● ● – ● ● ● ● ● ●
Emergency Stop PB Push/Pull 1 NC – ● – – – – – – ● – – – – –
Emergency Stop PB Push/Pull 1 NC with Key 455 – – ● – – – – – – – – – – –
Switch 0-1, 2NO – – – ● – – – – – ● – – – ●
Switch with Key 0-1, 1NO – – – – ● – – – – – – – – –
Push Button Red 1 NC – – – – – ● – – – ● ● ● ● ●
Green Indicator Lamp – – – – – – ● – ● – ● ● – –
Red Indicator Lamp – – – – – – – – – – – ● – –
Ammeter TC/IA Graduate – – – – – – – ● – – – – ● ●Scale 0-In-3In dilo IN= to be indicated
Front Plug – – – – – – – – – – – – ● –
*Add function to complete part number, e.g. XBL21A
**Second cablegland impossible
M6
M20 x 1,5M6
M6
M20 x 1,5M20 x 1,5
**Second cablegland impossible
M6M20 x 1,5
3 x ø22.5
XB300 / XBL15 XB400 / XBL25XB300 / XBL15with ammeter
XB400 / XBL25with ammeter
Visu 50x50
3x ø22.5
Visu 50x50 104
80
80
214
80
214
104
80
ø22.5
Thomas & Betts • www.tnb-hazardous.com
For Accessories see page 130
• Robust design• Manufactured from stainless steel 316 so ideal for offshore applications• Can be supplied complete with terminals and glands so all on site combinations are covered
Approvals / Characteristics Features
120
XBi RangeInstrumentation boxes
Certifi cation & StandardsApproved to: EN60079-0, 60079-1, 60079-7, 60079-11, EN61241-0, 61241-1EC TYPE Examination Certificate: Under 94/9/EC LCIE 11 ATEX 3050X / IECEx LCI 11.0044XEx II 2 G / DEx e or ia or eia IIC T6, T5 or T4Ex tD A21 IP66 T85ºC, T100ºC or T135ºCT4: ≤ -20ºC to ≤ +90ºCT5: ≤ -20ºC to ≤ +55ºCT6: ≤ -20ºC to ≤ +40ºCLCIE 11 ATEX 3045 U / IECEx LCI 11.0041UEx e IIEx tD A21 IP66
Thomas & Betts • www.tnb-hazardous.com
Maximum number of terminals
Dimensions (mm) size (in mm2) / In Max (in A) Weight in
Type Material A B C D E 2.5/21 4/28 6/36 10/50 16/66 35/109 70/167 70/95/100 120/234 185/307 240/350 (kg)
XBi100 Inox 100 100 61 60 60 9 (Min) 8 (Min) – – – – – – – – – 0.8
XBi150 Inox 150 150 81 110 110 19 16 12 10 – – – – – – – 0.4
XBi200 Inox 200 100 61 160 110 29 (Min) 24 (Min) – – – – – – – – – 1.1
XBi300 Inox 300 200 81 260 160 98 80 60 25 – – – – – – – 2.2
XBi400 Inox 400 300 161 360 260 138 116 86 70 56 21 17 – – – – 5.6
XBi500 Inox 500 400 161 460 360 356 296 224 135 87 46 14 11 – – – 3.7
XBi600 Inox 600 200 121 560 360 218 182 136 55 45 34 – – – – – 4.8
Exe Nylon Gland 166
Ex Boxes & Enclosures - XBi Range
Technical Specifi cations
121
Related Products
Dimensions
Stopping Plugs 164
Enclosure316L stainless steel,1.25mm thickStainless steel unlosable screwsOptional hinges
Rated voltagesDependent on the components fi tted in the box (eg:with terminal block: Un max = 500V)Cable entriesISO entries and threadsNylon cable glands for non-armoured cableNickel chromed brass cable glands for non-armoured cableNickel chromed brass PE series cable glands for armoured cable PEP series with brass continuity plate on XBL
Terminal block Equipment of the terminal lock wire any type of certifi ed Exe or Exia terminals. The maximum number of terminal blocks per box isdependent on the certifi cationStainless steel external earthOther options available upon request
A
D
E B
C
EJB Range 128 EVS Range 42
Thomas & Betts • www.tnb-hazardous.com
For full details and design service contact Sales
• Robust design• Manufactured from stainless steel 316 so ideal for offshore applications• Can be supplied complete with terminals and glands so all onsite combinations are covered
Approvals / Characteristics Features
122
XBi-A RangeStandard control boxes
Certifi cation & StandardsApproved to: EN60079-0, 60079-1, 60079-7, 60079-11, EN61241-0, 61241-1EC TYPE Examination Certificate: Under 94/9/EC LCIE 11 ATEX 3050 / IECEx LCI 11.0044Ex II 2 G / DEx de or e or ia or eia IIC T6, T5 or T4Ex tD A21 IP66 T85ºC, T100ºC or T135ºCEx de IIC T6, T5 or T4 IP66T4: ≤ -20ºC to ≤ +90ºCT5: ≤ -20ºC to ≤ +55ºCT6: ≤ -20ºC to ≤ +40ºCGlow wire test: 960°C EN60598-2-22
Thomas & Betts • www.tnb-hazardous.com
EJB Range 128 EVS Range 42 Exe Nylon Gland 166
Ex Boxes & Enclosures - XBi-A Range
Technical Specifi cations
123
Related Products
Dimensions
Stopping Plugs 164
EnclosureXBi-A (upon request): 316L stainless steel, 1.25mm thickStainless steel unlosable screwsProtection class: ITechnical CharacteristicsAC: U = 415V max. I = 1,75A or U = 240V, I = 3A orU = 120V, I = 6A DC: U = 415V max. I = 0,165A or U = 250V, I = 0,27A or U = 125V, I = 0,55A
Cable entriesEntries and threads ISO Nylon cable glands for non-armoured cableNickel chromed brass PE series cable glands for non- armoured cable Nickel chromed brass PEP cable glands for armoured cable with brass continuity plate on XBL-A
ComponentsDrilling on request Full range indicator lamp with LED Voltage of use 24V-254V AC/DCPush button (green, red, black, yellow or blue) 1 contact (3 contacts maximum)Emergency stop 1 contact (3 contacts maximum) Rotary switch 2 or 3 positions (2 contacts maximum) Anmeter Ex e: direct 1A or with CT/1Amp. max.
60
60 160
4x
3x ø22.5
Label
XBi100 XBi200
ø20.5
ø22.5 ø20.560
Standard Confi gurations
XBi: 100 x 100 x 61 (mm) XBi: 200 x 100 x 61 (mm)
1 Function 2 Functions 3 Functions 4 Functions
Type 21A 21FA 21VA 215A 215VA 22A 23A 26A 38A 41A 43A
Push Button Green 1 NO ● – – – – ● ● ● ● ● ●
Emergency Stop PB Push/Pull 1NC – ● – – – – – ● – – –
Emergency Stop PB Push/Pull 1NC with Key 455 – – ● – – – – – – – –
Switch 0-1, 2NO – – – ● – – – – ● – –
Switch with Key 0-1, 1NO – – – – ● – – – – – –
Push Button Red 1 NC – – – – – ● – – ● ● ●
Green Indicator Lamp – – – – – – ● ● – ● ●
Red Indicator Lamp – – – – – – – – – – ●
Ammeter TC/IA Graduate – – – – – – – – – – –Scale 0-In-3In dilo IN= to be indicated
Front Plug – – – – – – – – – – –
*Add function to complete part number, e.g. XBL21A
Thomas & Betts • www.tnb-hazardous.com
For Accessories see page 130
• External mounting points allowing for junction boxes to be mounted without the need for the removal of the lid• Robust design in cast aluminium• Supplied complete with terminals and glands so onsite combinations are covered
Approvals / Characteristics Features
124
GUV RangeAluminium junction boxes
Approved to: EN60079-0, 60079-1EC TYPE Examination Certificate:LCIE 00 ATEX 6022 / IECEx in progressEx II 2 GEx d IIC T6 to T4LCIE 00 ATEX 6022T6: ≤ -20°C to ≤ +40°CT5: ≤ -20°C to ≤ +55°CT4: ≤ -20°C to ≤ +60°C
Certifi cation & Standards
Thomas & Betts • www.tnb-hazardous.com
EXL Conduit 142 XFF Range 28
Ex Boxes & Enclosures - GUV Range
Technical Specifi cations
125
Related Products
EnclosureAluminium alloy body EN 1706 AC - 43100KF - AISI 10MgYellow polyurethane paint RAL1003Stainless steel screws
Cable entriesStandard:Two to four 3/4” NPT entries, accordingto modelOptions: 1” NPT entry on GUV36Metric entries upon request
TerminalsGUV26: 4 terminals up to 6mm2 supplied on request4 interconnected earthing terminals (M4 clampingscrews) (1 terminal per earth)GUV36: terminals supplied on request, maximumnumber 8 x 25mm2 terminals or 6 x 35mm2
terminals
Dimensions
Stopping Plugs 164
Type Number of entries Number of terminals (optional) Weight (Kg)
GUVC26-00000 2 -c- 4 x 2.5 to 6mm2 0.6
GUVC36-00000 2 -c- Max 8 x 25mm2 or 6 x 35mm2 1.6
GUVL26-00000 2 i- 4 x 2.5 to 6mm2 0.6
GUVL36-00000 2 i- Max 8 x 25mm2 or 6 x 35mm2 1.6
GUVT26-00000 3 T 4 x 2.5 to 6mm2 0.6
GUVT36-00000 3 T Max 8 x 25mm2 or 6 x 35mm2 1.7
GUVX26-00000 4 X 4 x 2.5 to 6mm2 0.7
GUVX36-00000 4 X Max 8 x 25mm2 or 6 x 35mm2 1.8
Thomas & Betts • www.tnb-hazardous.com
PA Gland 152
• Ex d approved allowing it to be used in more
sensitive applications
• Manufactured from cast aluminium and machined to
ensure flame paths are correct
Approvals / Characteristics Features
126
EFDC / SRC / XMC RangeControl stations
Certifi cation & StandardsApproved to: EN60079-0, 60079-1EC TYPE Examination Certificate:LCIE 00 ATEX 6022 / IECEx in progressEx II 2 GEx d IIC T6 to T4Type (without light): EFDC, SRCT6: ≤ -20°C to ≤ +40°CT5: ≤ -20°C to ≤ +55°CT4: ≤ -20°C to ≤ +60°CType (with light): EFDC, SRCT6: ≤ -20°C to ≤ +40°C
Thomas & Betts • www.tnb-hazardous.com
SRC / EFDC(enclosure size 1)
SRC / EFDC(enclosure size 2)
XMC 36(enclosure size 3)
166137
140
3/4343/4
3/4
ø6.5
ø765
23
195
124112
105
3/4
3/4
58
150
M6M6
Type SRC Rotary Switch Unit 215 415 330 340 215V
16A 2NO ● – – – ●
32A 3NO Lockable – – ● – –
40A 3NO Lockable – – – ● –
With Key 455 – – – – ●
16A 4 NO – ● – – –
EXL Conduit 142
Ex Boxes & Enclosures - EFDC / SRC / XMC Range
Technical Specifi cations
127
Related Products
EnclosureBody in marine grade aluminium alloyEN1706 AC - 43100KF - AISI 10MgPolyurethane paint: yellow RAL1003 except EFDC21G (red paint RAL3001)Stainless steel screwsPower supplyMaximum operating power: 400 Vac max for the indicator lamps6 A max for the push buttons40 A max for the rotary switchesFor indicator and potentiometer: please enquire
Cable entriesStandard: Two 3/4”NPT one being equipped with onezinc chromed steel plugOption:T wo 1” NPT (or ISO M32) on control stationssizes 2 and 3Recommendation: For Zone I and explosion proof IIC Compound cable gland is required
Terminal blockDirect connection to the component
Dimensions
For Accessories see page 130
Stopping Plugs 164 PA Gland 152 XFF Range 28
Type EFDC 21 25 41 43 44 22 40 42 38 23 21F 21V 21G 21P 24 23A 39 37 36
Green Push Button NO+NC ● – ● ● ● ● ● – ● ● – – – – – – – – –
2 x Green Push button NO+NF – – – – – – – ● – – – – – – – – – – –
Push/Pull Emergency Button NO+NF – ● – – – – – – – – ● – – – – – – – –
Emergency Key Operated Push Button 455 NO+NF – – – – – – – – – – – ● – – – – – – –
Break Glass Automatic Cut-off NO+NC – – – – – – – – – – – – ● – – – – – –
Potentiometer Driver – – – – – – – – – – – – – ● – – – – –
Green Indicator Light – ● ● ● ● – – – – ● – – – – ● ● ● ● –
Push Button Red NO+NC – – ● ● ● ● ● – ● – – – – – – – – – –
2 x Push Button Red NO+NC – – – – – – – ● – – – – – – – – – – –
Indicator Light Red 230V – – – ● – – – – – – – – – – – ● ● – –
Push Button Black NO+NC – – – – ● – ● – – – – – – – – – – – –
Rotary Switch Unit 2x16A – – – – – – – – ● – – – – – – – ● ● –
2 x Rotary Switch Unit 2x16A – – – – – – – – – – – – – – – – – – ●
Type XMC
XMC36 1 display diameter 80 with base plate - no equipment
*Add function to complete part number, e.g. EDFC21, SRC215, XMC36
Thomas & Betts • www.tnb-hazardous.com
• Robust construction
• Wide variety of sizes
• Large choice of electrical components
• Customised to user’s specification
Approvals / Characteristics Features
128
EJB RangeCustom built panels
Approved to: EN60079-0, 60079-1EC TYPE Examination Certificate:INERIS 11 ATEX 0050XEx II 2 GEx d IIB T5 or T6 GbEx II 2 (1) GEx d (ia IIC Ga, or ib, or ib IIC, or ia Ga) IIB T6 GbSafe operating temperature range: -20ºC to +40ºCIECEx Summer 2012: Contact Sales for more information onZones 21 and 22
Certifi cation & Standards
Thomas & Betts • www.tnb-hazardous.com
EXL Conduit 142 GUV Range 124
Ex Boxes & Enclosures - EJB Range
Technical Specifi cations
129
Related Products
EnclosureMarine grade aluminium alloy type EN 1706 AC - 43100KF - AISI 10Mg Yellow polyurethane paint RAL1003 (alternatives on request) Stainless steel external earth Stainless steel screws Hinged door if command buttons are on the panel (except EJB0)Cable entriesNPT or ISO entries and threads as requested Brass, nickel chromed brass or stainless steel cable gland for non armoured cableBrass, nickel chromed brass or stainless steel cable gland for armoured cableRecommendation: For Zone I and explosion group IIB Compound cable gland is required (except EJB0)
Switches and IndicatorsOn request Rotary switches: 1 to X positions two-way, spring return, layout on request (eg : 3NO + 1NC, 1 NO / Position...) Push buttons: Colours: green, red, black, yellow, blue Mechanical reactivation Contacts: maximum 6 contacts as specifi ed, NO or NC Indicator lamps: Colours: green, red, white, yellow, blue, power supply not exceeding 400V LEDs Potentiometer: please advise: value in Ohms, power in W, Number of turns, linear or logarithmic For all components: legends as requested Isolating switch/circuit-breaker: up to 800A Meters behind visual display: ammeter, voltmeter or others upon request
Fixing4 threaded holes on the back plate (see table) Frame or supporting feet on request
Dimensions
For Accessories see page 130
Stopping Plugs 162
GxH
External Internal Fixing / Mounting Internal Plate
Type A B C D E F G H L (mm) Weight (kg)
EJB0 200 145 130 145 90 90 140 85 M6 138 x 85 4
EJB1 302 190 170 225 115 130 200 100 M6 215 x 110 8
EJB2 295 230 165 225 165 132 185 130 M6 220 x 160 9
EJB4 410 300 167 340 220 127 290 190 M8 320 x 210 16
EJB5 475 295 220 390 207 179 335 178 M8 380 x 200 18
EJB8 625 360 250 525 260 195 480 210 M8 510 x 250 33
EJB11 595 505 275 485 395 207 436 335 M10 470 x 380 55
EJB12 805 435 315 690 345 246 605 262 M12 675 x 325 75
EJB13 832 612 323 720 435 252 628 405 M12 790 x 470 92
PA Gland 152
Thomas & Betts • www.tnb-hazardous.com
Box Accessories
130
Complete Units for DTS control stations and boxes
(SRC - EFDC Mod 1 & 2 or EJB as specified)
Type Function
BPN10 Push button Black NO+NC
BPR10 Push button Red NO+NC
BPV10 Push button green NO+NC
REA20 Reset button (customised for EJB ranges)
BCP30 Simple emergency stop push button NO+NC
BCP40 Push/Pull button Emergency Stop NO+NC
BCP50 Push button, unlockable by key N° 455
PRC10 Rotary switch 2x16A 0-1 2NO
PRC20 Rotary switch operated by key No 455 2x 16A 0-1 2NO
PRC30 Rotary switch 2x16A 1-2 NO+NC
PRC40 Rotary switch 2x16A 1-0-2 NO-0-NC
PRC50 Rotary switch 2x16A 0-1-2-0-NO-NO
PRC60 Rotary switch 4x16A 0-1 4NO
PRC70 Lockable rotary switch 3x25A 3NO
VAV10 Indicator lamp 230V - Green
VAR10 Indicator lamp 230V - Red
VAC10 Indicator lamp 230V - White
VAJ10 Indicator lamp 230V - Yellow
VAB10 Indicator lamp 230V - Blue
OptionsRotary Switch Options:- Spring return (40A max for SRC) - Confi guration on request (eg : 3NO+1NF, 1 NO/Position...)Push button options:- Colours: Green, Red, Black,Amber, Blue- Contacts (model 1 & EJB):Max 3 contacts according to request NO or NC - Contacts (model 2): Max 6 contacts according to request NO or NCIndicator Lamp Options:- Power supply up to 400V- LEDFor all products:Legends as requested
Spare Components for Control Panels & Enclosures
Components for Control Station
Spare Parts for the complete units
(EFDC / SRC or EJB as specified)
Type Function
BP01 Contacts NO+NC for push button switches
PR01 Rotary switch unit 2x16A 0-1 2NO
PR02 Rotary switch unit 2x16A 1-2 NO+NC
PR03 Rotary switch unit 2x16A 1-0-2 NO-0-NC
PR04 Rotary switch unit 2x16A 0-1-2-0-NO-NO
PR05 Rotary switch unit 4x16A 0-1 4NO
PR06 Rotary switch unit 3x25A 0-1 3NO
PR07 Rotary switch top
PR07V Key operated switch top
BP02 Cap for push switch Green
BP03 Cap for push switch Red
BP04 Cap for push switch Black
BP05 Cap for mushroom push/pull switch
BP05V Cap for key operated mushroom push switch
DE01 Indicator lamp lens Green
DE02 Indicator lamp lens Red
DE03 Indicator lamp lensWhite
DE04 Indicator lamp lens Amber
DE05 Indicator lamp lens Blue
DE10 Lamp holder for BA9S lamp
OptionsRotary Switch Options:- Spring return (40A max for SRC) - Confi guration on request (eg : 3NO+1NF, 1 NO/Position...)
For all products:- Legends as requested
Thomas & Betts • www.tnb-hazardous.com
Accessories & Spare Parts
131
Polyester / Aluminium Plug & Socket (Safe Disconnect)
DPX / DRX/ RPX / PPX Range
Socket Plug Nominal Power Cable Dimensions (mm) Weight (kg)
Type DRX Type DPX Poles Current (A) Supply (V) Gland A B ø C D E F G ø d AI A0 BI B0 Y Socket Plug
116E250 116E250 IP+N+PE 20 200/250 M20 125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180 0.3 0.16
216X24 216X24 2P 20 24 M20 125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180 0.3 0.16
216E24 216E24 2P+PE 20 24 M20 125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180 0.3 0.16
216E250 216E250 2P+PE 20 200/250 M20 125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180 0.3 0.16
216E415 216E415 2P+PE 20 380/450 M20 125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180 0.3 0.16
316E250 316E250 3P+PE 20 200/250 M20 125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180 0.3 0.16
316E415 316E415 3P+PE 20 380/450 M20 125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180 0.3 0.16
416E250 416E250 3P+N+PE 20 200/250 M20 125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180 0.3 0.16
416E415 416E415 3P+N+PE 20 380/450 M20 125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180 0.3 0.16
132E250 132E250 IP+N+PE 32 200/250 M25 145 68 13-19 138 132 84 107 70 6 214 229 162 171 200 0.46 0.24
232X24 232X24 2P 32 24 M25 145 68 13-19 138 132 84 107 70 6 214 229 162 171 200 0.46 0.24
232E24 232E24 2P+PE 32 24 M25 145 68 13-19 138 132 84 107 70 6 214 229 162 171 200 0.46 0.24
232E250 232E250 2P+PE 32 200/250 M25 145 68 13-19 138 132 84 107 70 6 214 229 162 171 200 0.46 0.24
232E415 232E415 2P+PE 32 380/450 M25 145 68 13-19 138 132 84 107 70 6 214 229 162 171 200 0.46 0.24
332E250 332E250 3P+PE 32 200/250 M25 145 68 13-19 138 132 84 107 70 6 214 229 162 171 200 0.46 0.24
332E415 332E415 3P+PE 32 380/450 M25 145 68 13-19 138 132 84 107 70 6 214 229 162 171 200 0.46 0.24
432E250 432E250 3P+N+PE 32 200/250 M25 145 68 13-19 138 132 84 107 70 6 214 229 162 171 200 0.46 0.24
432E415 432E415 3P+N+PE 32 380/450 M25 145 68 13-19 138 132 84 107 70 6 214 229 162 171 200 0.46 0.24
163E250 163E250 IP+N+PE 63 200/250 M32 152 83 17-25 165 162 89 122 88 6.5 233 259 184 199 236 0.64 0.42
263X24 263X24 2P 63 24 M32 152 83 17-25 165 162 89 122 88 6.5 233 259 184 199 236 0.64 0.42
363E415 363E415 3P+PE 63 380/450 M32 152 83 17-25 165 162 89 122 88 6.5 233 259 184 199 236 0.64 0.42
463E415 463E415 3P+N+PE 63 380/450 M32 152 83 17-25 165 162 89 122 88 6.5 233 259 184 199 236 0.64 0.42
Plug
Wall socket (30°)
Wall socket RPX Fitting plugged in to/unplugged from wall socket (30°)
D
CØ d
E
G
B
A
ø
Socket Plug Nominal Power Cable DImensions (mm) Weight (kg)
Type RPX Type PPX Poles Current (A) Supply (V) Gland A B ø C D E F G ø d AI A0 BI B0 Y Socket Plug
1125E250 1125E250 IP+N+T 125 200/250 M50 220 146 27-41 378 175 221 – 174 9.5 513 – 175 – – 8.0 2.6
3125E415 3125E415 3P+T 125 380/450 M50 220 146 27-41 378 175 221 – 174 9.5 513 – 175 – – 8.0 2.6
4125E415 4125E415 3P+N+T 125 380/450 M50 220 146 27-41 378 175 221 – 174 9.5 513 – 175 – – 8.0 2.6
Approved to: IEC 60079-0, 60079-1, 60079-7, 61241-0, 61241-1 60309-1, 60309-4EC TYPE Examination Certificate: under new directive 94/9/EC20A versions: LCIE 99 ATEX 6027X, IECEx LCI09.005X, ≤ -40°C to ≤ +60°C T5 T90ºC, ≤ -40°C to ≤ +40°C T6 T70ºC32A versions: LCIE 05 ATEX 6149, IECEx LCI09.0006, ≤ -40°C to ≤ +60°C T4 T98ºC, ≤ -40°C to ≤ +40°C T6 T78ºC63A versions: LCIE 05 ATEX 6150, IECEx LCI09.0007, ≤ -40°C to ≤ +60°C T4 T107ºC, ≤ -40°C to ≤ +40°C T5 T87ºC125A versions: LCIE 04 ATEX 6038, IECEx LCI09.0015, ≤ -40°C to ≤ +60°C T5 T90ºC, ≤ -40°C to ≤ +50°C T6 T80ºCATEX II 2 G / D, IP6x Exd e II C tDA21 Ingress protection: IP66/67 (PBT), IP65 (aluminium)
Thomas & Betts • www.tnb-hazardous.com
134
Conduit / Fitting Range
Conduit Fittings - Selection Guide
Thomas & Betts • www.tnb-hazardous.com
EXBB BraidNylon Conduit Page 136
Group 1 Gland Page 144
Group 1 90ºElbow Gland Page 144
EXB Nylon Conduit Page 136
Group 1 Universal Swivel Fitting Page 148
Group IIGland Page 146
Group 1 Univeral Fitting Page 148
XP Flex Page 156
Prot
ectio
n Ty
peG
asG
roup
Dus
tG
roup
Zo
nes
1DIV
2DIVI
2DIV
1DIV
For use with Liquid Tight Conduits
Conduit Fittings - Selection Guide
135
Thomas & Betts • www.tnb-hazardous.com
Standard Stopping Plugs Page 162
TamperproofStopping Plugs Page 162
Hex HeadStoppingPlugs Page 164
Thread Convertors Page 158
Nylon StoppingPlugs Page 164
Coupler Page 166
Dome HeadStopping Plugs Page 164
• Anti-static Nylon conduit
• Approved for use in Ex e applications for
Zones 1, 2, 21 & 22
Approvals / Characteristics Features
136
EXB / EXBB RangeNon-metallic nylon conduit
EC TYPE Examination Certificate:ATEX: Baseefa 08 ATEX 0003XIECEx: IECEx BAS08.0001XGOST R: POCC GB.ГБ05.B03850INMETRO: TÜV 11.0091Temperature: -20°C to 80ºCRTI 110ºC to EN60079-0Special Characteristics: EXB: Surface resistivity 106ΩEXBB: Screening level 60dB at 1MHz
Certifi cation & Standards
Thomas & Betts • www.tnb-hazardous.com
EXPQM Fitting 140
Non-Metallic Nylon Conduit - EXB / EXBB Range
Technical Specifi cations
137
Related Products
For Accessories see page 166
EXBQM Fitting 140
British Conduit Size (mm) 16 20 28 34 42 54
Coil Lengths (m) 10/30/50 10/30/50 10/30/50 10/30/50 10/30/50 10/30/50
Minimum Bore (mm) 11.15 16.45 21.5 27.5 35.2 46.2
Type Outside Diameter (mm) 16.5 21.20 28.35 34.5 42.4 54.3
Anti-Static Nylon 12 (Stainless Steel) EXBB03* EXBB04* EXBB05* EXBB06* EXBB07* EXBB08*
*Add coil length to complete part number, e.g. 10 metres = EXBB0510
British Conduit Size (mm) 16 20 28 34 42 54
Coil Lengths (m) 10/30/50 10/30/50 10/30/50 10/30/50 10/30/50 10/30/50
Minimum Bore (mm) 11.15 16.45 21.5 27.5 35.2 46.2
Type Outside Diameter (mm) 16.5 21.20 28.35 34.5 42.4 54.3
Anti-Static Nylon 12 (Black) EXB03* EXB04* EXB05* EXB06* EXB07* EXB08*
*Add coil length to complete part number, e.g. 10 metres = EXB0510
EXB Anti-Static Conduit
EXBB Overbraided Conduit
Thomas & Betts • www.tnb-hazardous.com
• Manufactured in Nickel Plated Brass
• Approved for use in Ex e applications for
Zones 1, 2, 21 & 22
Approvals / Characteristics Features
138
EXBQM / EXPQA RangeNylon conduit fi ttings
EC TYPE Examination Certificate:ATEX: Baseefa 08 ATEX 0003XIECEx: IECEx BAS08.0001XGOST R: POCC GB.ГБ05.B03850INMETRO: TÜV 11.0091Temperature: -20°C to 80ºC
Certifi cation & Standards
Thomas & Betts • www.tnb-hazardous.com
EXPQM Straight Male Conduit Fitting
Non-Metallic Nylon Fittings - EXPQM / EXBQA Range
Technical Specifi cations
139
Related Products
For Accessories see page 166
British Conduit Size (mm) 16 20 28 34 42 54
Metric Thread Size (mm) 20 20 25 32 40 50
Type NPT Thread Size (inch) 1/2 1/2 3/4 1 11/4 11/2
Metric - Nickel Plated Brass EXPQM0304 EXPQM0404 EXPQM0505 EXPQM0606 EXPQM0707 EXPQM0808
NPT Thread - Nickel Plated Brass EXPQA0304 EXPQA0404 EXPQA5305 EXPQA0606 EXPQA0707 EXPQA0808
*For use with EXB Nylon Conduit see pages 140-141
British Conduit Size (mm) 16 20 28 34 42 54
Metric Thread Size (mm) 20 20 25 32 40 50
Type NPT Thread Size (inch) 1/2 1/2 3/4 1 11/4 11/2
Metric - Nickel Plated Brass EXBQM0304 EXBQM0404 EXBQM0505 EXBQM0606 EXBQM0707 EXBQM0808
NPT Thread - Nickel Plated Brass EXBQA0304 EXBQA0404 EXBQA5305 EXBQA0606 EXBQA0707 EXBQA0808
*For use with EXBB Nylon Conduit see pages 140-141
EXBQM Straight Male Conduit Fitting
Locknuts 166 Sealing 166Washers
EXB Range 138 EXBB Range 138
Thomas & Betts • www.tnb-hazardous.com
140
General Oil Resistant - Galzanised Steel Core with a general purpose oil resistant coating
Low Fire Hazard - Galzanised Steel Core with a LFH coating
Certification Standard: IEC 61386Static Temp: -25°C to +105°CFlexing Temp: -5°C to +105°C
Special Characteristics: Flame retardant PVC covering
Flame Propogation:
Flame dies in less than 30 seconds after ignition source
is removed
Certifi cation & Characteristics
Certification Standard: IEC 61386 LUL Fully Compliant (E1042A6)MOD to NES 518: Issue 3 DEF STAN 61-12 (Part 31) Issue 1
Static Temp: -25°C to +90°CFlexing Temp: -5°C to +90°CSpecial Characteristics: Limited Fire Hazard, zero halogen (BS6425 Pt 1)
Flame Propogation:
Flame dies in less than 30 seconds after ignition source is removed
Certifi cation & Characteristics
High Temperature - Galvanised Steel Core with a high temperature resistant coating
Low Fire Hazard with EMC Protection - Galvanised Steel Core with a galvanised steel EMC shield and LFH Covering
Certification Standard: IEC 61386Static Temp: -50°C to +130°CFlexing Temp: -5°C to +90°C
Special Characteristics: Flame resistance: UL94 V2Chemical and oil resistant
Flame Propogation:
Flame dies in less than 30 seconds after ignition source is removed
Certifi cation & Characteristics
Certifi cation & Characteristics
High Temperature Highly Flexible - Galvanised Steel Core with a high temperature, highly fl exible coating
Certification Standard: IEC 61386Static Temp: -65°C to +150°CFlexing Temp: -45°C to +135°C
Special Characteristics: High FlexibilityHigh Temperature
Flame Propogation:
Flame dies in less than 30 seconds after ignition source is removed
Certifi cation & Characteristics
Certification Standard: IEC 61386MOD to NES 518: Issue 3 DEF STAN 61-12 (Part 31) Issue 1 Static Temp: -25°C to +90°C
Flexing Temp: -5°C to +90°CSpecial Characteristics: Limited Fire Hazard coveringEMC Screening level: 60db at 1MHz Braided
Flame Propogation:
Flame dies in less than 30 seconds after ignition source is removed
Thomas & Betts • www.tnb-hazardous.com
Liquid Tight Conduit - EXLB / EXLT / EXLH / EXBBT / EXLHC Range
141
Related Products
Universal 150Gland
90º Elbow 146Gland
Group II 148Gland
Group I & II 146Gland
British Conduit Size (mm) 16 20 25 32 40 50 63
US Trade Sizes (inch) 3/8 1/2 3/4 1 1 1/4 1 1/2 2
Inside Diameter (mm) 12.5 16.0 21.0 26.4 35.3 40.4 51.6
Type Coil Lengths (m) 10/30 10/30 10/30 10/20 10/20 10/20 10/20
General Oil Resistant (Black) EXLB03* EXLB04* EXLB05* EXLB06* EXLB07* EXLB08* EXLB09*
*Add coil length to complete part number, e.g. 10 metres = EXLB0510
Technical Specifi cations
British Conduit Size (mm) 16 20 25 32 40 50 63
US Trade Sizes (inch) 3/8 1/2 3/4 1 1 1/4 1 1/2 2
Inside Diameter (mm) 12.5 16.0 21.0 26.4 35.3 40.4 51.6
Type Coil Lengths (m) 10/30 10/30 10/30 10/20 10/20 10/20 10/20
Low Fire Hazard with EMC (Black) EXBBT03* EXBBT04* EXBBT05* EXBBT06* EXBBT07* EXBBT08* EXBBT09*
*Add coil length to complete part number, e.g. 10 metres = EXBBT0510
British Conduit Size (mm) 16 20 25 32 40 50 63
US Trade Sizes (inch) 3/8 1/2 3/4 1 1 1/4 1 1/2 2
Inside Diameter (mm) 12.5 16.0 21.0 26.4 35.3 40.4 51.6
Type Coil Lengths (m) 10/30 10/30 10/30 10/20 10/20 10/20 10/20
Low Fire Hazard (Black) EXLT03* EXLT04* EXLT05* EXLT06* EXLT07* EXLT08* EXLT09*
*Add coil length to complete part number, e.g. 10 metres = EXLT0510
British Conduit Size (mm) 16 20 25 32 40 50 63
US Trade Sizes (inch) 3/8 1/2 3/4 1 1 1/4 1 1/2 2
Inside Diameter (mm) 12.5 16.0 21.0 26.4 35.3 40.4 51.6
Type Coil Lengths (m) 10/30 10/30 10/30 10/20 10/20 10/20 10/20
High Temperature Highly Flexible (Black) EXLHC03* EXLHC04* EXLHC05* EXLHC06* EXLHC07* EXLHC08* EXLHC09*
*Add coil length to complete part number, e.g. 10 metres = EXLHC0510
British Conduit Size (mm) 16 20 25 32 40 50 63
US Trade Sizes (inch) 3/8 1/2 3/4 1 1 1/4 1 1/2 2
Inside Diameter (mm) 12.5 16.0 21.0 26.4 35.3 40.4 51.6
Type Coil Lengths (m) 10/30 10/30 10/30 10/20 10/20 10/20 10/20
High Temperature (Black) EXLH03* EXLH04* EXLH05* EXLH06* EXLH07* - -
High Temperature (Blue) EXLLH03* EXLLH04* EXLLH05* EXLLH06* EXLLH07* - -
*Add coil length to complete part number, e.g. 10 metres = EXLH0510
Thomas & Betts • www.tnb-hazardous.com
142
General Oil Resistant - Stainless Steel 316 Core with a general purpose oil resistant coating
Low Fire Hazard - Stainless Steel Core with a LFH coating
Certification Standard: IEC 61386Static Temp: -25°C to +105°CFlexing Temp: -5°C to +105°C
Special Characteristics: Flame retardant PVC covering
Flame Propogation:
Flame dies in less than 30 seconds after ignition source
is removed
Certifi cation & Characteristics
Certification Standard: IEC 61386 LUL Fully Compliant (E1042A6)MOD to NES 518: Issue 3 DEF STAN 61-12 (Part 31) Issue 1
Static Temp: -25°C to +90°CFlexing Temp: -5°C to +90°CSpecial Characteristics: Limited Fire Hazard, zero halogen (BS6425 Pt 1)
Flame Propogation:
Flame dies in less than 30 seconds after ignition source is removed
Certifi cation & Characteristics
High Temperature - Stainless Steel Core with a high temperature resistant coating
Low Fire Hazard with EMC Protection - Stainless Steel Core with a galvanised steel EMC shield and LFH Covering
Certification Standard: IEC 61386Static Temp: -50°C to +130°CFlexing Temp: -5°C to +130°C
Special Characteristics: Flame resistance: UL94 V2Chemical and oil resistant
Flame Propogation:
Flame dies in less than 30 seconds after ignition source is removed
Certifi cation & Characteristics
Certifi cation & Characteristics
High Temperature Highly Flexible - Stainless Steel Core with a high temperature, highly fl exible coating
Certification Standard: IEC 61386Static Temp: -65°C to +150°CFlexing Temp: -45°C to +135°C
Special Characteristics: High FlexibilityHigh Temperature
Flame Propogation:
Flame dies in less than 30 seconds after ignition source is removed
Certifi cation & Characteristics
Certification Standard: IEC 61386, UL full compliantMOD to NES 518: Issue 3 DEF STAN 61-12 (Part 31) Issue 1 Static Temp: -25°C to +90°C
Flexing Temp: -5°C to +90°CSpecial Characteristics: Zero halogen (BS6425 pt1) Limited Fire Hazard covering EMC Screening level: 60db at 1MHz Braided
Flame Propogation:
Flame dies in less than 30 seconds after ignition source is removed
Thomas & Betts • www.tnb-hazardous.com
Related Products
Universal 150Gland
90º Elbow 146Gland
Group II 148Gland
Group I & II 146Gland
Liquid Tight Conduit - EXSB / EXST / EXSH / EXSBBT / EXSHC Range
143
British Conduit Size (mm) 16 20 25 32 40 50 63
US Trade Sizes (inch) 3/8 1/2 3/4 1 1 1/4 1 1/2 2
Inside Diameter (mm) 12.5 16.0 21.0 26.4 35.3 40.4 51.6
Type Coil Lengths (m) 10/30 10/30 10/30 10/20 10/20 10/20 10/20
General Oil Resistant (Black) EXSB03* EXSB04* EXSB05* EXSB06* EXSB07* EXSB08* EXSB09*
*Add coil length to complete part number, e.g. 10 metres = EXLB0510
Technical Specifi cations
British Conduit Size (mm) 16 20 25 32 40 50 63
US Trade Sizes (inch) 3/8 1/2 3/4 1 1 1/4 1 1/2 2
Inside Diameter (mm) 12.5 16.0 21.0 26.4 35.3 40.4 51.6
Type Coil Lengths (m) 10/30 10/30 10/30 10/20 10/20 10/20 10/20
Low Fire Hazard with EMC (Black) EXSBBT03* EXSBBT04* EXSBBT05* EXSBBT06* EXSBBT07* EXSBBT08* EXSBBT09*
*Add coil length to complete part number, e.g. 10 metres = EXLBBT0510
British Conduit Size (mm) 16 20 25 32 40 50 63
US Trade Sizes (inch) 3/8 1/2 3/4 1 1 1/4 1 1/2 2
Inside Diameter (mm) 12.5 16.0 21.0 26.4 35.3 40.4 51.6
Type Coil Lengths (m) 10/30 10/30 10/30 10/20 10/20 10/20 10/20
Low Fire Hazard (Black) EXST03* EXST04* EXST05* EXST06* EXST07* EXST08* EXST09*
*Add coil length to complete part number, e.g. 10 metres = EXLT0510
British Conduit Size (mm) 16 20 25 32 40 50 63
US Trade Sizes (inch) 3/8 1/2 3/4 1 1 1/4 1 1/2 2
Inside Diameter (mm) 12.5 16.0 21.0 26.4 35.3 40.4 51.6
Type Coil Lengths (m) 10/30 10/30 10/30 10/20 10/20 10/20 10/20
High Temperature Highly Flexible (Black) EXSHC03* EXSHC04* EXSHC05* EXSHC06* EXSHC07* EXSHC08* EXSHC09*
*Add coil length to complete part number, e.g. 10 metres = EXLHC0510
British Conduit Size (mm) 16 20 25 32 40 50 63
US Trade Sizes (inch) 3/8 1/2 3/4 1 1 1/4 1 1/2 2
Inside Diameter (mm) 12.5 16.0 21.0 26.4 35.3 40.4 51.6
Type Coil Lengths (m) 10/30 10/30 10/30 10/20 10/20 10/20 10/20
High Temperature (Black) EXSH03* EXSH04* EXSH05* EXSH06* EXSH07* - -
High Temperature (Blue) EXSLLH03* EXSLLH04* EXSLLH05* EXSLLH06* EXSLLH07* - -
*Add coil length to complete part number, e.g. 10 metres = EXLH0510
Thomas & Betts • www.tnb-hazardous.com
• Constructed from either Brass or Stainless Steel
with an epoxy resin barrier the Group I Flameproof
Gland is a high specification product, ideal for all
hazardous area applications
Approvals / Characteristics Features
G1 Gland / 90º Elbow
Liquid tight hazardous area fl ameproof glands
EC TYPE Examination Certificate:ATEX: Sira 09 ATEX 1231XIECEx: IECEx SIR09.0103XCSA: CSA File No: 2310045GOST R: POCC GB.ГБ05.B03850INMETRO: TÜV 11.0339XEx de I MbEx de IIC GbEx tb IIIC DbClass I DIv 2 ABCDClass II Div 1 EFGTemperature: -60ºC to +130ºC
Certifi cation & Standards
144
1DIV
2DIV
I
Thomas & Betts • www.tnb-hazardous.com
General Oil Resistant 140
High Temperature Conduit 142
Low Fire Flexible Conduit 142
Sealing 166Washers
145
Liquid Tight Hazardous Area Flameproof G1 Gland
British Conduit Size (mm) 16 20 25 32 40 50 63
Metric Thread Size (mm) 20 20 25 32 40 50 63
Type NPT Thread Size (inch) 1/2 1/2 3/4 1 11/4 11/2 2
Metric - Brass HAM0304E HAM0404E HAM0505E HAM0606E HAM0707E HAM0808E HAM0909E
Metric - Nickel Plated HAMM0304E HAMM0404E HAMM0505E HAMM0606E HAMM0707E HAMM0808E HAMM0909E
NPT Thread - Brass HAA0304E HAA0404E HAA0505E HAA0606E HAA0707E HAA0808E HAA0909E
NPT Thread - Nickel Plated HAAM0304E HAAM0404E HAAM0505E HAAM0606E HAAM0707E HAAM0808E HAAM0909E
See pages 140-143 for suitable conduits *Stainless Steel available but elbow is Nickel Plated Brass **Elbow supplied is for liquid tight conduit only
British Conduit Size (mm) 16 20 25 32 40 50 63
Metric Thread Size (mm) 20 20 25 32 40 50 63
Type NPT Thread Size (inch) 1/2 1/2 3/4 1 11/4 11/2 2
Metric - Brass HAM0304G1 HAM0404G1 HAM0505G1 HAM0606G1 HAM0707G1 HAM0808G1 HAM0909G1
Metric - Nickel Plated HAMM0304G1 HAMM0404G1 HAMM0505G1 HAMM0606G1 HAMM0707G1 HAMM0808G1 HAMM0909G1
Metric - Stainless Steel HAMS0304G1 HAMS0404G1 HAMS0505G1 HAMS0606G1 HAMS0707G1 HAMS0808G1 HAMS0909G1
NPT Thread - Brass HAA0304G1 HAA0404G1 HAA0505G1 HAA0606G1 HAA0707G1 HAA0808G1 HAA0909G1
NPT Thread - Nickel Plated HAAM0304G1 HAAM0404G1 HAAM0505G1 HAAM0606G1 HAAM0707G1 HAAM0808G1 HAAM0909G1
NPT Thread - Stainless Steel HAAS0304G1 HAAS0404G1 HAAS0505G1 HAAS0606G1 HAAS0707G1 HAAS0808G1 HAAS0909G1
See pages 140-143 for suitable conduits
Related Products
Technical Specifi cationsATEX Flameproof G1 Gland
ATEX Flameproof 90º Elbow Gland
For Accessories see page 166
Thomas & Betts • www.tnb-hazardous.com
• Constructed from either Brass or Stainless Steel
with an epoxy resin barrier the Group II Flameproof
Gland is a high specification product, ideal for all
hazardous area applications
Approvals / Characteristics Features
Group II Gland
Liquid tight hazardous area fl ameproof gland
EC TYPE Examination Certificate:Baseefa 06 ATEX 0256XIECEx BAS06.0059XEx d IICEx e IIEx tD A21Temperature: -60ºC to +80ºC
Certifi cation & Standards
146
Thomas & Betts • www.tnb-hazardous.com
147
Liquid Tight Hazardous Area Flameproof Group II Gland
British Conduit Size (mm) 16 20 25 32 40 50 63
Metric Thread Size (mm) 20 20 25 32 40 50 63
Type NPT Thread Size (inch) 1/2 1/2 3/4 1 11/4 11/2 2
Metric - Brass HAM0304 HAM0404 HAM0505 HAM0606 HAM0707 HAM0808 HAM0909
Metric - Nickel Plated HAMM0304 HAMM0404 HAMM0505 HAMM0606 HAMM0707 HAMM0808 HAMM0909
Metric - Stainless Steel HAMS0304 HAMS0404 HAMS0505 HAMS0606 HAMS0707 HAMS0808 HAMS0909
NPT Thread - Brass HAA0304 HAA0404 HAA0505 HAA0606 HAA0707 HAA0808 HAA0909
NPT Thread - Nickel Plated HAAM0304 HAAM0404 HAAM0505 HAAM0606 HAAM0707 HAAM0808 HAAM0909
NPT Thread - Stainless Steel HAAS0304 HAAS0404 HAAS0505 HAAS0606 HAAS0707 HAAS0808 HAAS0909
See pages 140-143 for suitable conduits
Related Products
Technical Specifi cationsATEX Flameproof Group II Gland
For Accessories see page 166
Thomas & Betts • www.tnb-hazardous.com
General Oil Resistant 140
High Temperature Conduit 142
Low Fire Flexible Conduit 140
Sealing 166Washers
• Constructed from either Brass or Stainless Steel with
an epoxy resin barrier
• The Group I Universal Flameproof Gland is a high specification
product, ideal for all hazardous area applications
Approvals / Characteristics Features
Universal Gland & Universal Swivel Gland
Liquid tight hazardous area fl ameproof glands
EC TYPE Examination Certificate:ATEX: Sira 09 ATEX 1231XIECEx: IECEx SIR09.0103XCSA: CSA File No: 2310045GOST R: POCC GB.ГБ05.B03850INMETRO: TÜV 11.0339XEx de I MbEx de IIC GbEx tb IIIC DbClass I DIv 1 BCD (Rigid conduit only)Class I Div 2 ABCDClass II Div 1 ABCDTemperature: -60ºC to +130ºC
Certifi cation & Standards
1DIV
2DIV
I
148
1DIV
Thomas & Betts • www.tnb-hazardous.com
149
Liquid Tight Hazardous Areas Flameproof Universal Gland
Metric Thread Size (mm) 20 20 25 32 40 50 63
Type NPT Thread Size (inch) 3/8 1/2 3/4 1 11/4 11/2 2
Metric - Brass HAM0304U/SW HAM0404U/SW HAM0505U/SW HAM0606U/SW HAM0707U/SW HAM0808U/SW HAM0909U/SW
Metric - Nickel Plated HAMM0304U/SW HAMM0404U/SW HAMM0505U/SW HAMM0606U/SW HAMM0707U/SW HAMM0808U/SW HAMM0909U/SW
NPT Thread - Brass HAA0304U/SW HAA0404U/SW HAA0505U/SW HAA0606U/SW HAA0707U/SW HAA0808U/SW HAA0909U/SW
NPT Thread - Nickel Plated HAAM0304U/SW HAAM0404U/SW HAAM0505U/SW HAAM0606U/SW HAAM0707U/SW HAAM0808U/SW HAAM0909U/SW
Metric Thread Size (mm) 20 20 25 32 40 50 63
Type NPT Thread Size (inch) 3/8 1/2 3/4 1 11/4 11/2 2
Metric - Brass HAM0304U HAM0404U HAM0505U HAM0606U HAM0707U HAM0808U HAM0909U
Metric - Nickel Plated HAMM0304U HAMM0404U HAMM0505U HAMM0606U HAMM0707U HAMM0808U HAMM0909U
Metric - Stainless Steel HAMS0304U HAMS0404U HAMS0505U HAMS0606U HAMS0707U HAMS0808U HAMS0909U
NPT Thread - Brass HAA0304U HAA0404U HAA0505U HAA0606U HAA0707U HAA0808U HAA0909U
NPT Thread - Nickel Plated HAAM0304U HAAM0404U HAAM0505U HAAM0606U HAAM0707U HAAM0808U HAAM0909U
NPT Thread - Stainless Steel HAAS0304U HAAS0404U HAAS0505U HAAS0606U HAAS0707U HAAS0808U HAAS0909U
For use with all conduits including Rigid
HAA 03 04 U
Thread B = 1/2” NPTThread A = 3/8” NPT
THREAD B THREAD A THREAD B THREAD A
HAM 03 04 U
Thread A = M16 Thread B = M20
Technical Specifi cationsDimensions
Universal Gland
Universal Swivel Gland
Flameproof GlandConstructed from either brass or stainless steel, with an epoxy resin barrier, the Group I Flameproof Universal Gland is a high quality, high specifi cation product, ideal for Ex I & II 2 GD gas and dust, Exde IIC and Exe II applications, Extb II applications.
Related Products
For Accessories see page 166
Thomas & Betts • www.tnb-hazardous.com
General Oil Resistant 140
High Temperature Conduit 142
Low Fire Flexible Conduit 140
Sealing 166Washers
• Solid brass cable gland
• Single compression for non-armoured cable (PA)
• Double compression for armoured cable (PAP)
Approvals / Characteristics Features
PA / PAP NPT Range
Cable glands
150
Thomas & Betts • www.tnb-hazardous.com
Approved to: EN60079-0, 60079-1, 60079-7, EN61241-0, EN61421-1EC TYPE Examination Certificate:INERIS 06 ATEX 0014XEx II 2 GD / I M2Ex d IIC / Ex e II / Ex d I / Ex e IEx tD A21 IP66/68Temperature: -40ºC to +100ºC
Certifi cation & Standards
151
PA / PAP NPT Range
Technical Specifi cationsDimensions
GlandMarine grade brassOption: nickel chromed brass and stainless steelIngress rating IP66 (EN 60529), neoprene compression gasket
ThreadsNPT threads, for size see tableOptions: ISO threadsSleeve
Sealing 166Washers
Related Products
For Accessories see page 166
ø Min-Max
External Dimension (mm) Weight
PN Type (mm) D E F L (kg)
PA18L PA1-8 1/2” 5.5-8 41 32 35 18 0.15
PA110L PA1-10 1/2” 8-10.5 41 32 35 18 0.15
PA113L PA1-13 1/2” 10.5-13 41 32 35 18 0.15
PA210L PA2-10 3/4” 8-10.5 41 32 35 18 0.15
PA213L PA2-13 3/4” 10.5-13 41 32 35 18 0.15
PA215L PA2-15 3/4” 13-15.5 41 36 39 18 0.20
PA218L PA2-18 3/4” 15.5-18 41 36 39 18 0.20
PA318L PA3-18 1” 15-18 52 45 49 22 0.38
PA321L PA3-21 1” 18-21 52 45 49 22 0.38
PA324L PA3-24 1” 21-24 52 45 49 22 0.38
PA424L PA4-24 1,1/4” 21-24 53 50 55 22 0.42
PA427L PA4-27 1,1/4” 24-27 53 50 55 22 0.42
PA430L PA4-30 1,1/4” 27-30 53 50 55 22 0.42
PA533L PA5-33 1,1/2” 30-33 53 57 62 22 0.52
PA536L PA5-36 1,1/2” 33-36 53 57 62 22 0.52
PA639L PA6-39 2” 36-39 53 67 73 22 0.75
PA642L PA6-42 2” 39-42 53 67 73 22 0.75
PA645L PA6-45 2” 42-45 53 67 73 22 0.75
PA748L PA7-48 2,1/2” 45-48 53 80 88 27 1.20
PA751L PA7-51 2,1/2” 48-51 53 80 88 27 1.20
ø Min-Max
Internal External Dimension (mm) Weight
PN Type (mm) (mm) D E F L (kg)
PAP18L PAP1-8 1/2” 5,5-8 10-15 65 32 35 18 0,22
PAP110L PAP1-10 1/2” 8-10.5 10-15 65 32 35 18 0.22
PAP113L PAP1-13 1/2” 10.5-13 14-19 65 32 35 18 0.22
PAP210L PAP2-10 3/4” 8-10.5 10-15 65 32 35 18 0.22
PAP213L PAP2-13 3/4” 10.5-13 15-20 65 32 35 18 0.22
PAP215L PAP2-15 3/4” 13-15.5 15-20 65 36 39 18 0.29
PAP218L PAP2-18 3/4” 15.5-18 19-24 65 36 39 18 0.29
PAP318L PAP3-18 1” 15-18 20-26 82 45 49 22 0.50
PAP321L PAP3-21 1” 18-21 20-26 82 45 49 22 0.50
PAP324L PAP3-24 1” 21-24 25-31 82 45 49 22 0.50
PAP424L PAP4-24 1,1/4” 21-24 26-32 83 50 55 22 0.55
PAP427L PAP4-27 1,1/4” 24-27 26-32 83 50 55 22 0.55
PAP430L PAP4-30 1,1/4” 27-30 31-37 83 50 55 22 0.55
PAP533L PAP5-33 1,1/2” 30-33 36-43 83 57 62 22 0.70
PAP536L PAP5-36 1,1/2” 33-36 36-43 83 57 62 22 0.70
PAP639L PAP6-39 2” 36-39 42-48 83 67 73 22 0.85
PAP642L PAP6-42 2” 39-42 42-48 83 67 73 22 0.85
PAP645L PAP6-45 2” 42-45 47-53 83 67 73 22 0.85
PAP748L PAP7-48 2,1/2” 45-48 52-58 83 80 88 27 1.45
PAP751L PAP7-51 2,1/2” 48-51 52-58 83 80 88 27 1.45
XB-A Range 118 GUV Range 124Locknuts 166
Thomas & Betts • www.tnb-hazardous.com
• Nickel chromed brass cable gland
• Single compression for non-armoured cable (PE)
• Double compression for armoured cable (PEP)
Approvals / Characteristics Features
PE / PEP ISO Range
Cable glands
152
Thomas & Betts • www.tnb-hazardous.com
Approved to: EN60079-0, 60079-1, 60079-7, EN61241-0, EN61421-1EC TYPE Examination Certificate:LCIE 97 ATEX 6008X / IECEx LCI 05.0004XEx II 2 GDEx d IIC / Ex e II / Ex tDEx tD A21 IP66/68Temperature: -60ºC to +80ºC or -40ºC to 100ºC
Certifi cation & Standards
153
PE / PEP ISO Range
Technical Specifi cationsDimensions
GlandNickel chrome brassOption: stainless steelIngress rating IP68 10 bar (EN 60529), neoprene compression gasket
ThreadsNPT threads, for size see tableOptions: Clamping moduleLead sheaf earthing washerShroud
Related Products
For Accessories see page 166
ø Min-Max
External Dimension (mm)
Type (mm) E F D L Weight (kg)
PEM20T4 4-8.5 15 24 20 15 0.056
PEM20T5 6-12 19 24 22 15 0.038
PEM20T6 8.5-15 24 24 25 15 0.045
PEM25T6 8.5-16 24 30 25 15 0.055
PEM25T7 12-20.5 30 30 27 15 0.070
PEM32T7 12-21 30 36 27 15 0.100
PEM32T8 16-27.5 41 41 34 15 0.150
PEM40T9 21-33 48 48 36 15 0.210
PEM50T10 27-41 55 55 39 16 0.285
PEM63T11 33-48 64 67 41 17 0.400
PEM75T12 40-56 72 80 43 18 0.570
ø Min-Max
Internal External Dimension (mm)
Type (mm) (mm) E F D L Weight (kg)
PEPM20T5 4-8.5 6-12 19 24 36 15 0.080
PEPM20T6 6-12 8.5-16 24 24 42 15 0.090
PEPM20T7 8.5-15.5 12-21 30 30 46 15 0.123
PEPM25T7 8.5-16 12-21 30 30 46 15 0.170
PEPM25T8 12-21 16-27.5 41 41 56 15 0.270
PEPM32T8 12-21 16-27.5 41 41 56 15 0.310
PEPM32T9 16-27.5 21-33 48 48 63 15 0.400
PEPM40T10 21-33 27-41 55 55 68 15 0.540
PEPM50T11 27-41 33-48 64 64 74 16 0.735
PEPM63T12 33-48 40-56 72 72 77 17 0.996
PEPM75T13 40-55 47-65 85 85 85 18 1.590
Sealing 166Washers
XB-A Range 118 GUV Range 124Locknuts 166
Thomas & Betts • www.tnb-hazardous.com
• Solid Brass Nickel cable gland
• Single compression for non-armoured cable (PA-B)
• Double compression for armoured cable (PAP-B)
• Accessories included - compound kit and different
rings to cover multi-cable sizes
Approvals / Characteristics Features
PA-B / PAP-B NPT & ISO Range
Barrier compound cable glands
154
Thomas & Betts • www.tnb-hazardous.com
Approved to: EN60079-0, 60079-1, 60079-7, EN61241-0, EN61421-1EC TYPE Examination Certificate:INERIS 06 ATEX 0014XEx II 2 GD / I M2Ex d IIC / Ex e II / Ex d I / Exe IEx tD A21 IP66/68Temperature: -40ºC to 100ºC
Certifi cation & Standards
PA-B / PAP-B NPT & ISO Range
155
ø Min-Max
External Dimension (mm)
Type (mm) D E F L Weight (kg)
PA1B-1/2NPT 5,5-8 40 32 35 18 0,156
8-10.5 40 32 35 18 0.156
10.5-13 40 32 35 18 0.156
PA2B-3/4NPT 8-10.5 40 36 39 18 0.20
10.5-13 40 36 39 18 0.20
13-15.5 40 36 39 18 0.20
15.5-18 40 36 39 18 0.20
PA3B-1NPT 15-18 52 45 49 22 0.38
18-21 52 45 49 22 0.38
21-24 52 45 49 22 0.38
PA4B-1,1/4NPT 21-24 52 50 55 22 0.421
24-27 52 50 55 22 0.421
27-30 52 50 55 22 0.421
PA5B-1,1/2NPT 30-33 52 57 62 22 0.537
33-36 52 57 62 22 0.537
PA6B-2NPT 36-39 52 67 72 22 0.75
39-42 52 67 72 22 0.75
42-45 52 67 72 22 0.75
PA7B-2,1/2NPT 45-48 52 80 88 27 1.20
48-51 52 80 88 27 1.20
51-54 52 80 88 27 1.20
ø Min-Max
Internal External Dimension (mm)
Type (mm) (mm) D E F L Weight (kg)
PAP1B-1/2NPT 5,5-8 10-15 64 32 35 18 0,228
8-10.5 10-15 64 32 35 18 0.228
10.5-13 14-19 64 32 35 18 0.228
PAP2B-3/4NPT 8-10.5 10-15 65 32 35 18 0.22
10.5-13 15-20 65 32 35 18 0.22
13-15.5 15-20 64 36 39 18 0.29
15.5-18 19-24 64 36 39 18 0.29
PAP3B-1NPT 15-18 20-26 83 45 49 22 0.50
18-21 20-26 83 45 49 22 0.50
21-24 25-31 83 45 49 22 0.50
PAP4B-1,1/4NPT 21-24 26-32 83 50 55 22 0.576
24-27 26-32 83 50 55 22 0.576
27-30 31-37 83 50 55 22 0.576
PAP5B-1,1/2NPT 30-33 36-43 83 57 62 22 0.730
33-36 36-43 83 57 62 22 0.730
PAP6B-2NPT 36-39 42-48 83 67 73 22 0.961
39-42 42-48 83 67 73 22 0.961
42-45 47-53 83 67 73 22 0.961
PAP7B-2,1/2NPT 45-48 52-58 83 80 88 27 1.45
48-51 52-58 83 80 88 27 1.45
51-54 52-58 83 80 88 27 1.45
Technical Specifi cationsDimensions
ø Min-Max
External Dimension (mm)
Type (mm) D E F L Weight (kg)
PA1B-M20 5,5-8 40 32 35 18 0,156
8-10.5 40 32 35 18 0.156
10.5-13 40 32 35 18 0.156
PA2B-M25 8-10.5 40 36 39 18 0.20
10.5-13 40 36 39 18 0.20
13-15.5 40 36 39 18 0.20
15.5-18 40 36 39 18 0.20
PA3B-M32 15-18 52 45 49 22 0.38
18-21 52 45 49 22 0.38
21-24 52 45 49 22 0.38
PA4B-M40 21-24 52 50 55 22 0.421
24-27 52 50 55 22 0.421
27-30 52 50 55 22 0.421
PA5B-M50 30-33 52 57 62 22 0.537
33-36 52 57 62 22 0.537
PA6B-M63 36-39 52 67 72 22 0.75
39-42 52 67 72 22 0.75
42-45 52 67 72 22 0.75
PA7B-M75 45-48 52 80 88 27 1.20
48-51 52 80 88 27 1.20
51-54 52 80 88 27 1.20
ø Min-Max
Internal External Dimension (mm)
Type (mm) (mm) D E F L Weight (kg)
PAP1B-M20 5,5-8 10-15 64 32 35 18 0,228
8-10.5 10-15 64 32 35 18 0.228
10.5-13 14-19 64 32 35 18 0.228
PAP2B-M25 8-10.5 10-15 65 32 35 18 0.22
10.5-13 15-20 65 32 35 18 0.22
13-15.5 15-20 64 36 39 18 0.29
15.5-18 19-24 64 36 39 18 0.29
PAP3B-M32 15-18 20-26 83 45 49 22 0.50
18-21 20-26 83 45 49 22 0.50
21-24 25-31 83 45 49 22 0.50
PAP4B-M40 21-24 26-32 83 50 55 22 0.576
24-27 26-32 83 50 55 22 0.576
27-30 31-37 83 50 55 22 0.576
PAP5B-M50 30-33 36-43 83 57 62 22 0.730
33-36 36-43 83 57 62 22 0.730
PAP6B-M63 36-39 42-48 83 67 73 22 0.961
39-42 42-48 83 67 73 22 0.961
42-45 47-53 83 67 73 22 0.961
PAP7B-M75 45-48 52-58 83 80 88 27 1.45
48-51 52-58 83 80 88 27 1.45
51-54 52-58 83 80 88 27 1.45
Thomas & Betts • www.tnb-hazardous.com
• UL Listed for use in hazardous and wet locations
• Corrosion-resistant - ideal for washdown areas
• Flexible bronze construction with arc-resistant inner
sleeve and brass fittings
• Terminated with two threaded female end fittings
and male close nipples
• No bonding jumper required
156
1DIV
2DIV
I
1DIV
Approvals / Characteristics Features
XP Flex™ RangeExplosion-proof fl exible couplings
UL Listed and CSA Certified for Hazardous Locations:0.5” and 0.75” Hub Sizes: Class I Div 1 & 2 ABCD; Class II Div 1 EFG, Class III1” Hub Size: Class I Div 1 & 2 CD; Class II Div 1 EFG, Class IIIUL Listed 886
Certifi cation & Standards
Thomas & Betts • www.tnb-hazardous.com
Explosion-Proof Flexible Couplings - XP Flex™ Range
Dimensions (mm)
Reference Thread Type (inch) Flexible Length (mm) A B
XPLFL16 1/2” NPT 150 39.1 36.6
XPLFL18 1/2” NPT 200 39.1 36.6
XPLFL110 1/2” NPT 250 39.1 36.6
XPLFL112 1/2” NPT 300 39.1 36.6
XPLFL115 1/2” NPT 380 39.1 36.6
XPLFL118 1/2” NPT 460 39.1 36.6
XPLFL124 1/2” NPT 610 39.1 36.6
XPLFL212 3/4” NPT 300 40.6 47.5
XPLFL215 3/4” NPT 380 40.6 47.5
XPLFL218 3/4” NPT 460 40.6 47.5
XPLFL224 3/4” NPT 610 40.6 47.5
XPLFL236 3/4” NPT 915 40.6 47.5
XPLFL318 1” NPT 460 50.08 58.7
157
Explosion-Proof and Dust- Ignition-Proof for Use in Hazardous LocationsWith their fl exible design, T&B® XP FlexTM Couplings make it easy to achieve tight bends in conduit systems in confi ned spaces - or to connect stationary equipment to equipment that moves or vibrates. Their explosion-proof and corrosion-resistant construction mean you can use them with confi dence in hazardous and wet locations.
Technical Specifi cationsDimensions
FlexibleLength
AB
NPTThreads
Enlargers, Reducers & Thread Convertors 160
Sealing 166Washers
Related Products
Locknuts 166
Thomas & Betts • www.tnb-hazardous.com
• Adaptors and Reducers provide a method of
matching threadforms on hazardous approved
equipment whilst ensuring the integrity and approval
of the installation is maintained
Approvals / Characteristics Features
Thread ConvertorsEnlargers, reducers & convertors
Certification Standard: ATEX: Baseefa07 ATEX 0247X, IECEx: IECEx BAS07.0090XGOST R: POCC GB.ГБ05.B03850INMETRO: TÜV 11.0339XClass I Div1 ABCD, Class II Div1 EFG (does not include M16 & 3/8”NPT or unplated brass products)Approved to UL 1203Approved to CSA C22.2 No.60079-04Approved to C22.2 No.60079-1
Certifi cation & Standards
158
1DIV
I 1DIV
Thomas & Betts • www.tnb-hazardous.com
Male
External Metric Female Internal Thread
Thread M16 M20 M25 M32 M40 M50 M63 M75
M16 EX/M16-M20/E EX/M16-M25/E
M20 EX/M20-M16/R EX/M20-M25/E EX/M20-M32/E
M25 EX/M25-M16/R EX/M25-M20/R EX/M25-M32/E EX/M25-M40/E
M32 EX/M32-M16/R EX/M32-M20/R EX/M32-M25/R EX/M32-M40/E EX/M32-M50/E
M40 EX/M40-M16/R EX/M40-M20/R EX/M40-M25/R EX/M40-M32/R EX/M40-M50/E EX/M40-M63/E
M50 EX/M50-M16/R EX/M50-M20/R EX/M50-M25/R EX/M50-M32/R EX/M50-M40/R EX/M50-M63/E EX/M50-M75/E
M63 EX/M63-M16/R EX/M63-M20/R EX/M63-M25/R EX/M63-M32/R EX/M63-M40/R EX/M63-M50/R EX/M63-M75/E
M75 EX/M75-M16/R EX/M75-M20/R EX/M75-M25/R EX/M75-M32/R EX/M75-M40/R EX/M75-M50/R EX/M75-M63/R
PG9 EX/PG9-M16/TC EX/PG9-M20/TC
PG11 EX/PG11-M16/TC EX/PG11-M20/TC
PG13 EX/PG13-M16/TC EX/PG13-M20/TC
PG16 EX/PG16-M16/TC EX/PG16-M20/TC EX/PG16-M25/TC
PG21 EX/PG21-M16/TC EX/PG21-M20/TC EX/PG21-M25/TC EX/PG21-M32/TC
PG29 EX/PG29-M16/TC EX/PG29-M20/TC EX/PG29-M25/TC EX/PG29-M32/TC EX/PG29-M40/TC
PG36 EX/PG36-M16/TC EX/PG36-M20/TC EX/PG36-M25/TC EX/PG36-M32/TC EX/PG36-M40/TC EX/PG36-M50/TC
PG42 EX/PG42-M16/TC EX/PG42-M20/TC EX/PG42-M25/TC EX/PG42-M32/TC EX/PG42-M40/TC EX/PG42-M50/TC EX/PG42-M63/TC
PG48 EX/PG48-M16/TC EX/PG48-M20/TC EX/PG48-M25/TC EX/PG48-M32/TC EX/PG48-M40/TC EX/PG48-M50/TC EX/PG48-M63/TC
NPT 3/8 EX/038-M16/TC
NPT 1/2 EX/050-M16/TC EX/050-M20/TC EX/050-M25/TC
NPT 3/4 EX/075-M16/TC EX/075-M20/TC EX/075-M25/TC EX/075-M32/TC
NPT 1 EX/100-M16/TC EX/100-M20/TC EX/100-M25/TC EX/100-M32/TC EX/100-M40/TC
NPT 1 1/4 EX/125-M16/TC EX/125-M20/TC EX/125-M25/TC EX/125-M32/TC EX/125-M40/TC EX/125-M50/TC
NPT 1 1/2 EX/150-M16/TC EX/150-M20/TC EX/150-M25/TC EX/150-M32/TC EX/150-M40/TC EX/150-M50/TC EX/150-M63/TC
NPT 2 EX/200-M16/TC EX/200-M20/TC EX/200-M25/TC EX/200-M32/TC EX/200-M40/TC EX/200-M50/TC EX/200-M63/TC
NPT 2 1/2 EX/250-M16/TC EX/250-M20/TC EX/250-M25/TC EX/250-M32/TC EX/250-M40/TC EX/250-M50/TC
NPT 3 EX/300-M16/TC EX/300-M20/TC EX/300-M25/TC EX/300-M32/TC EX/300-M40/TC EX/300-M50/TC EX/300-M75/TC
*For Nickel Plated Brass version, add N to the reference, e.g. EXN/M20-M16/R**For Stainless Steel 316 version, add S to the reference, e.g. EXS/M20-M16/R
Enlargers, Reducers & Thread Convertors
159
Metric - Technical Specifi cation
Connector Description:EX - BrassEXN - Nickel Plated BrassEXS - Stainless Steel 316
Enlargers (/E) are used where the thread size of the Female side of the device is larger than the male side.Reducers (/R) are used where the thread size of the female side of device is smaller than the male side.Thread Converters (/TC) are used where a conversion is required between thread types, e.g. Metric to PG.
Our comprehensive range of Adaptors and Reducers provide a method of matching threadforms on hazardous area approved equipment whilst ensuring the integrity and approval of the installation is maintained.
Manufactured in the UK, this new range of converters meets the latest ATEX / IECEx & CSA / UL standards. This means that all the standards are marked on the product around the main body. This allows for them to be seen easily once installed, a key component of the new standard.
Kopex’s Enlargers, Reducers and thread converters are designed for hazardous area applications and are certifi ed to protection concepts Exd “Flameproof” and Exe “Increased Safety” for use in Zone 1, 2, 2.1, 2.2 applications. Under NEC Class I Div1 ABCD Class II Div1 EFG.
EFDC Range 126 XB100 Range 108
Related Products
GUV Range 124 PA Gland 152
Thomas & Betts • www.tnb-hazardous.com
160
Male
External NPT Female Internal Thread
Thread NPT 1/2 NPT 3/4 NPT 1 NPT 1 1/4 NPT 1 1/2 NPT 2 NPT 2 1/2 NPT 3
M16 EX/M16-050/TC
M20 EX/M20-050/TC EX/M20-075/TC
M25 EX/M25-050/TC EX/M25-075/TC EX/M25-100/TC
M32 EX/M32-050/TC EX/M32-075/TC EX/M32-100/TC EX/M32-125/TC
M40 EX/M40-050/TC EX/M40-075/TC EX/M40-100/TC EX/M40-125/TC EX/M40-150/TC
M50 EX/M50-050/TC EX/M50-075/TC EX/M50-100/TC EX/M50-125/TC EX/M50-150/TC EX/M50-200/TC
M63 EX/M63-050/TC EX/M63-075/TC EX/M63-100/TC EX/M63-125/TC EX/M63-150/TC EX/M63-200/TC
M75 EX/M75-050/TC EX/M75-075/TC EX/M75-100/TC EX/M75-125/TC EX/M75-150/TC EX/M75-200/TC
PG9 EX/PG9-050/TC
PG11 EX/PG11-050/TC
PG13 EX/PG13-050/TC
PG16 EX/PG16-050/TC EX/PG16-075/TC
PG21 EX/PG21-050/TC EX/PG21-075/TC EX/PG21-100/TC
PG29 EX/PG29-050/TC EX/PG29-075/TC EX/PG29-100/TC EX/PG29-125/TC EX/PG29-150/TC
PG36 EX/PG36-050/TC EX/PG36-075/TC EX/PG36-100/TC EX/PG36-125/TC EX/PG36-150/TC
PG42 EX/PG42-050/TC EX/PG42-075/TC EX/PG42-100/TC EX/PG42-125/TC EX/PG42-150/TC EX/PG42-200/TC
PG48 EX/PG48-050/TC EX/PG48-075/TC EX/PG48-100/TC EX/PG48-125/TC EX/PG48-150/TC EX/PG48-200/TC
NPT 1/2 EX/050-075/E
NPT 3/4 EX/075-050/R EX/075-100/E
NPT 1 EX/100-050/R EX/100-075/R EX/100-125/E
NPT 1 1/4 EX/125-050/R EX/125-075/R EX/125-100/R EX/125-150/E
NPT 1 1/2 EX/150-050/R EX/150-075/R EX/150-100/R EX/150-125/R EX/150-200/E
NPT 2 EX/200-050/R EX/200-075/R EX/200-100/R EX/200-125/R X/200-150/R
NPT 2 1/2 EX/250-050/R EX/250-075/R EX/250-100/R EX/250-125/R EX/250-150/R EX/250-200/R EX/250-300/E
NPT 3 EX/300-050/R EX/300-075/R EX/300-100/R EX/300-125/R EX/300-150/R EX/300-200/R EX/300-250/R
*For Nickel Plated Brass version, add N to the reference, e.g. EXN/M20-M16/R**For Stainless Steel 316 version, add S to the reference, e.g. EXS/M20-M16/R
NPT - Technical Specifi cation
Thomas & Betts • www.tnb-hazardous.com
Male
External PG Female Internal Thread
Thread PG9 PG11 PG13 PG16 PG21 PG29 PG36 PG42 PG48
M16 EX/M16-PG9/TC EX/M16-PG11/TC EX/M16-PG13/TC
M20 EX/M20-PG9/TC EX/M20-PG11/TC EX/M20-PG13/TC EX/M20-PG16/TC
M25 EX/M25-PG9/TC EX/M25-PG11/TC EX/M25-PG13/TC EX/M25-PG16/TC EX/M25-PG21/TC
M32 EX/M32-PG9/TC EX/M32-PG11/TC EX/M32-PG13/TC EX/M32-PG16/TC EX/M32-PG21/TC EX/M32-PG29/TC
M40 EX/M40-PG9/TC EX/M40-PG11/TC EX/M40-PG13/TC EX/M40-PG16/TC EX/M40-PG21/TC EX/M40-PG29/TC EX/M40-PG36/TC
M50 EX/M50-PG9/TC EX/M50-PG11/TC EX/M50-PG13/TC EX/M50-PG16/TC EX/M50-PG21/TC EX/M50-PG29/TC EX/M50-PG36/TC EX/M50-PG42/TC
M63 EX/M63-PG9/TC EX/M63-PG11/TC EX/M63-PG13/TC EX/M63-PG16/TC EX/M63-PG21/TC EX/M63-PG29/TC EX/M63-PG36/TC EX/M63-PG42/TC EX/M63-PG48/TC
M75 EX/M75-PG9/TC EX/M75-PG11/TC EX/M75-PG13/TC EX/M75-PG16/TC EX/M75-PG21/TC EX/M75-PG29/TC EX/M75-PG36/TC EX/M75-PG42/TC EX/M75-PG48/TC
PG11 EX/PG11-PG9/R
PG13 EX/PG13-PG9/R EX/PG13-PG11/R
PG16 EX/PG16-PG9/R EX/PG16-PG11/R EX/PG16-PG13/R EX/P16-PG21/E
PG21 EX/PG21-PG9/R EX/PG21-PG11/R EX/PG21-PG13/R EX/PG21-PG16/R EX/PG21-PG29/E
PG29 EX/PG29-PG9/R EX/PG29-PG11/R EX/PG29-PG13/R EX/PG29-PG16/R EX/PG29-PG21/R EX/PG29-PG36/E
PG36 EX/PG36-PG9/R EX/PG36-PG11/R EX/PG36-PG13/R EX/PG36-PG16/R EX/PG36-PG21/R EX/PG36-PG29/R EX/PG36-PG48/E
PG42 EX/PG42-PG9/R EX/PG42-PG11/R EX/PG42-PG13/R EX/PG42-PG16/R EX/PG42-PG21/R EX/PG42-PG29/R EX/PG42-PG36/R EX/PG42-PG48/E
PG48 EX/PG48-PG9/R EX/PG48-PG11/R EX/PG48-PG13/R EX/PG48-PG16/R EX/PG48-PG21/R EX/PG48-PG29/R EX/PG48-PG36/R EX/PG48-PG42/R
NPT 1/2 EX/050-PG9/TC EX/050-PG11/TC EX/050-PG13/TC EX/050-PG16/TC
NPT 3/4 EX/075-PG9/TC EX/075-PG11/TC EX/075-PG13/TC EX/075-PG16/TC EX/075-PG21/TC
NPT 1 EX/100-PG9/TC EX/100-PG11/TC EX/100-PG13/TC EX/100-PG16/TC EX/100-PG21/TC EX/100-PG29/TC
NPT 1 1/4 EX/125-PG9/TC EX/125-PG11/TC EX/125-PG13/TC EX/125-PG16/TC EX/125-PG21/TC EX/125-PG29/TC EX/125-PG36/TC
NPT 1 1/2 EX/150-PG9/TC EX/150-PG11/TC EX/150-PG13/TC EX/150-PG16/TC EX/150-PG21/TC EX/150-PG29/TC EX/150-PG36/TC EX/150-PG42/TC
NPT 2 EX/200-PG9/TC EX/200-PG11/TC EX/200-PG13/TC EX/200-PG16/TC EX/200-PG21/TC EX/200-PG29/TC EX/200-PG36/TC EX/200-PG42/TC EX/200-PG48/TC
*For Nickel Plated Brass version, add N to the reference, e.g. EXN/M20-M16/R**For Stainless Steel 316 version, add S to the reference, e.g. EXS/M20-M16/R
Enlargers, Reducers & Thread Convertors
161
PG - Technical Specifi cation
Connector Description:EX - BrassEXN - Nickel Plated BrassEXS - Stainless Steel 316
Enlargers (/E) are used where the thread size of the Female side of the device is larger than the male side.Reducers (/R) are used where the thread size of the female side of device is smaller than the male side.Thread Converters (/TC) are used where a conversion is required between thread types, e.g. Metric to PG.
Our comprehensive range of Adaptors and Reducers provide a method of matching threadforms on hazardous area approved equipment whilst ensuring the integrity and approval of the installation is maintained.
Manufactured in the UK, this new range of converters meets the latest ATEX / IECEx & CSA / UL standards. This means that all the standards are marked on the product around the main body. This allows for them to be seen easily once installed, a key component of the new standard.
Kopex’s Enlargers, Reducers and thread converters are designed for hazardous area applications and are certifi ed to protection concepts Exd “Flameproof” and Exe “Increased Safety” for use in Zone 1, 2, 2.1, 2.2 applications. Under NEC Class I Div1 ABCD Class II Div1 EFG.
Related Products
Thomas & Betts • www.tnb-hazardous.com
EFDC Range 126 XB100 Range 108GUV Range 124 PA Gland 152
• For use in potentially explosive atmospheres
• Manufactured from either Brass, Nickel Plated Brass
or Stainless Steel
Approvals / Characteristics Features
Standard Ex d Stopping Plug & Tamperproof Ex d Stopping Plug
Exd stopping plugs
EC TYPE Examination Certificate:ATEX: Baseefa 08 ATEX 6324IECEx: IECEx BAS08.0109XGOST R: POCC GB.ГБ05.B03850INMETRO: TÜV 11.0093UL 1203 (Nickel Plated Brass and Stainless Steel only)Ex d IEx d IICClass I Div 1 ABCDClass II Div 1 EFGTemperature: -60ºC to +130ºC
Certifi cation & Standards
1DIV
I 1DIV
162
Thomas & Betts • www.tnb-hazardous.com
163
Ex d Stopping Plugs
NPT Thread Size (inch) 3/8 1/2 3/4 1 1 1/4 1 1/2 2
Type Metric Thread Size (mm) 16 20 25 32 40 50 63
NPT Thread - Brass EX/038/SP EX/050/SP EX/075/SP EX/100/SP EX/125/SP EX/150/SP EX/200/SP
Metric - Brass EX/M16/SP EX/M20/SP EX/M25/SP EX/M32/SP EX/M40/SP EX/M50/SP EX/M63/SP
NPT Thread - Nickel Plated Brass EXN/038/SP EXN/050/SP EXN/075/SP EXN/100/SP EXN/125/SP EXN/150/SP EXN/200/SP
Metric - Nickel Plated Brass EXN/M16/SP EXN/M20/SP EXN/M25/SP EXN/M32/SP EXN/M40/SP EXN/M50/SP EXN/M63/SP
NPT Thread - Stainless Steel EXS/038/SP EXS/050/SP EXS/075/SP EXS/100/SP EXS/125/SP EXS/150/SP EXS/200/SP
Metric - Stainless Steel EXS/M16/SP EXS/M20/SP EXS/M25/SP EXS/M32/SP EXS/M40/SP EXS/M50/SP EXS/M63/SP
*Does not include M16 & 3/8 NPT or Unplated Brass products
NPT Thread Size (inch) 3/8 1/2 3/4 1 1 1/4 1 1/2 2
Type Metric Thread Size (mm) 16 20 25 32 40 50 63
NPT Thread - Brass EX/038/TSP EX/050/TSP EX/075/TSP EX/100/TSP EX/125/TSP EX/150/TSP EX/200/TSP
Metric - Brass EX/M16/TSP EX/M20/TSP EX/M25/TSP EX/M32/TSP EX/M40/TSP EX/M50/TSP EX/M63/TSP
NPT Thread - Nickel Plated Brass EXN/038/TSP EXN/050/TSP EXN/075/TSP EXN/100/TSP EXN/125/TSP EXN/150/TSP EXN/200/TSP
Metric - Nickel Plated Brass EXN/M16/TSP EXN/M20/TSP EXN/M25/TSP EXN/M32/TSP EXN/M40/TSP EXN/M50/TSP EXN/M63/TSP
NPT Thread - Stainless Steel EXS/038/TSP EXS/050/TSP EXS/075/TSP EXS/100/TSP EXS/125/TSP EXS/150/TSP EXS/200/TSP
Metric - Stainless Steel EXS/M16/TSP EXS/M20/TSP EXS/M25/TSP EXS/M32/TSP EXS/M40/TSP EXS/M50/TSP EXS/M63/TSP
*Does not include M16 & 3/8 NPT or Unplated Brass products
Related Products
Technical Specifi cationsStandard Exd Stopping Plug
Tamperproof Exd Stopping Plug
XFF Range 28 GUV Range 124EJB Range 128 XEL Range 32
Thomas & Betts • www.tnb-hazardous.com
• For use in potentially explosive atmospheres
• Hex Head and Dome Head stopping plugs manufactured
from either Brass, Nickel Plated Brass or Stainless Steel
• Nylon Stopping Plug manufactured in Nylon only
Approvals / Characteristics Features
Hex Head Ex e Stopping Plug / Dome Head Ex e & Nylon Stopping Plug
Ex e & nylon stopping plugs
Hex Head Exe Stopping Plug & Dome Head Stopping PlugEC TYPE Examination Certificate:ATEX: Baseefa 08 ATEX 0325XIECEx: IECEx BAS08.0108XGOST R: POCC GB.ГБ05.B03850INMETRO: TÜV 11.0090UL 1203 (Nickel Plated Brass and Stainless Steel only)Ex d IEx e II Ex tDTemperature: -60ºC to +80ºC
Certifi cation & Standards
164
Nylon Stopping PlugEC TYPE Examination Certificate:Sira 00 ATEX 1074XLCIE 98 ATEX 0001U
Thomas & Betts • www.tnb-hazardous.com
165
Ex e & Nylon Stopping Plugs
Type Metric Thread Size (mm) 16 20 25 32 40 50 63
Metric - Brass EX/M16/HSP EX/M20/HSP EX/M25/HSP EX/M32/HSP EX/M40/HSP EX/M50/HSP EX/M63/HSP
Metric - Nickel Plated Brass EXN/M16/HSP EXN/M20/HSP EXN/M25/HSP EXN/M32/HSP EXN/M40/HSP EXN/M50/HSP EXN/M63/HSP
Metric - Stainless Steel EXS/M16/HSP EXS/M20/HSP EXS/M25/HSP EXS/M32/HSP EXS/M40/HSP EXS/M50/HSP EXS/M63/HSP
*Does not include M16 & 3/8 NPT or Unplated Brass products
Related Products
Technical Specifi cationsHex Head Exe Stopping Plug
Type Metric Thread Size (mm) 16 20 25 32 40 50 63
Metric - Brass EX/M16/DSP EX/M20/DSP EX/M25/DSP EX/M32/DSP EX/M40/DSP EX/M50/DSP EX/M63/DSP
Metric - Nickel Plated Brass EXN/M16/DSP EXN/M20/DSP EXN/M25/DSP EXN/M32/DSP EXN/M40/DSP EXN/M50/DSP EXN/M63/DSP
Metric - Stainless Steel EXS/M16/DSP EXS/M20/DSP EXS/M25/DSP EXS/M32/DSP EXS/M40/DSP EXS/M50/DSP EXS/M63/DSP
*Products supplied with sealing washers and ‘O’ rings **Does not include M16 & 3/8 NPT or Unplated Brass products
Dome Head Exe Stopping Plug
XFF Range 28 GUV Range 124XB Range 116 EVS Range 42
Type Metric Thread Size (mm) 16 20 25 32 40 50 63
Metric - Nylon (supplied without locknut) BEM16POLY BEM20POLY BEM25POLY BEM32POLY BEM40POLY BEM50POLY BEM63POLY
Nylon Stopping Plug ( only)
Thomas & Betts • www.tnb-hazardous.com
166
Ex e Nylon Gland - Group II, Zones 1, 2, 21 and 22
Coupler - Female to Female thread couplers for use in both Exd and Exe applications
Certification Standard: LCIE 97 ATEX 6007X
Certifi cation & Standards
Certification Standard: Baseefa 08 ATEX 0359U
IECEx BAS08.0121U
TÜV11.0158U
Temperature: -60°C to +200°C
Certifi cation & Standards
Hex Locknut - for Metric Threads and NPT Threads (Nickel Plated Brass only)
Sealing Joint Washer - for use with all ATEX and IECEx approved products (Nylon only)
Certification Standard: Nylon Metric approved for use
with all ATEX / IECEx products
Certifi cation & Standards
Earth Tag - to be used to create an earthing bond on an enclosure, when a cable gland is used
Accessories
Thomas & Betts • www.tnb-hazardous.com
Cable Glands, Sealing Washers & Locknuts - Accessories
167
Metric Thread Size (mm) 12 16a 16b 20a 20b 25 32 40 50 63
Type Cable Diameter (mm) 3,5-6 5-8 6-10 8-13 10-15 13-19 17-25 23-32 25-38 34-40
Ex e Nylon Gland PCM12 PCM16A PCM16B PCM20A PCM20B PCM25 PCM32 PCM40 PCM50 PCM63
Ex i Nylon Gland (Blue) PCM12i PCM16iA PCM16iB PCM20iA PCM20iB PCM25i PCM32i PCM40i PCM50i PCM63i
Technical Specifi cations
Metric Thread Size (mm) 16 20 25 32 40 50 63 75
Type PG Thread Size 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2
Metric - Brass EX/M16/C EX/M20/C EX/M25/C EX/M32/C EX/M40/C EX/M50/C EX/M63/C EX/M75/C
NPT Thread - Brass EX/038/C EX/050/C EX/075/C EX/100/C EX/125/C EX/150/C EX/200/C EX/250/P
Metric - Nickel Plated Brass EXN/M16/C EXN/M20/C EXN/M25/C EXN/M32/C EXN/M40/C EXN/M50/C EXN/M63/C EXN/M75/C
NPT Thread - Nickel Plated Brass EXN/038/C EXN/050/C EXN/075/C EXN/100/C EXN/125/C EXN/150/C EXN/200/C EXN/250/P
Metric - Stainless Steel EXS/M16/C EXS/M20/C EXS/M25/C EXS/M32/C EXS/M40/C EXS/M50/C EXS/M63/C EXS/M75/C
NPT Thread - Stainless Steel EXS/038/C EXS/050/C EXS/075/C EXS/100/C EXS/125/C EXS/150/C EXS/200/C EXS/250/P
Metric Thread Size (mm) 16 20 25 32 40 50 63 75
Type PG Thread Size 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2
Metric - Stainless Steel - MXWH04 MXWH05 MXWH06 MXWH07 MXWH08 - -
Metric - Brass WHMB03 WHMB04 WHMB05 WHMB06 WHMB07 WHMB08 - -
Metric - Nickel Plated Brass WHMM03 WHMM04 WHMM05 WHMM06 WHMM07 WHMM08 WHMM09 -
NPT Thread - Nickel Plated Brass - WHAM04 WHAM05 WHAM06 WHAM07 WHAM08 WHAM09 -
Metric Thread Size (mm) 16 20 25 32 40 50 63 75
PG Thread Size 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2
Outside Diameter (mm) 22 26 34.3 41.5 52 66.5 84.5 -
Type Thickness (mm) 1.6 1.6 1.7 1.7 2 2 2 -
Metric - Nylon (ATEX / IECEx approved) EXFM03 EXFM04 EXFM05 EXFM06 EXFM07 EXFM08 EXFM09 -
Metric - Fibre EXFM03F EXFM04F EXFM05F EXFM06F EXFM07F EXFM08F - -
Metric Thread Size (mm) 16 20 25 32 40 50 63 75
Type PG Thread Size 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2
Earth Tag - Brass EX/M16/TAG EX/M20/TAG EX/M25/TAG EX/M32/TAG EX/M40/TAG EX/M53/TAG EX/M63/TAG EX/M75/TAG
EFDC Range 126 XB100 Range 108
Related Products
GUV Range 124 PA Gland 152
Thomas & Betts • www.tnb-hazardous.com
168
Index
Thomas & Betts • www.tnb-hazardous.com
B004 97
B005B 99
B006 99
B006L 99
B007 99
B008B 99
B009A 99
B010B 99
B011 99
B013 99
B013K 99
B014B 99
B015 99
B016 99
B017 99
BCP30 130
BCP40 130
BCP50 130
BP01 130
BP02 130
BP03 130
BP04 130
BP05 130
BP05V 130
BPN10 130
BPR10 130
BPV10 130
D002 96
D003 96
D004 96
D005 96
D006 96
D007 96
D008 96
D009 96
D010 96
D010PL 96
D011 96
D017 96
D018 96
D019 96
D020 96
D021 96
D021B 99
D022 96
D023 94
D024 94
D09E 96
DE01 130
DE02 130
DE03 130
DE04 130
DE05 130
DE10 130
E006 97
E007 97
E008 97
E009 97
EF110G-00000 77
EF110P-00000 77
EF140G-00000 77
EF140P-00000 77
EFDC21 127
EFDC21F 127
EFDC21G 127
EFDC21P 127
EFDC21V 127
EFDC22 127
EFDC23 127
EFDC23A 127
EFDC24 127
EFDC25 127
EFDC36 127
EFDC37 127
EFDC38 127
EFDC39 127
EFDC40 127
EFDC41 127
EFDC42 127
EFDC43 127
EFDC44 127
EJB0 129
EJB1 129
EJB11 129
EJB12 129
EJB13 129
EJB2 129
EJB4 129
EJB5 129
EJB8 129
EL120-0G000 75
EL220-0G000 75
EL30011-0G000 75
EL30028-0G000 75
EL3008-0G000 75
EL3009-0G000 75
ESB220-0000 49
ESB220-A000 49
ESB240-0000 49
ESB240-A000 49
ESB240EM-0000 69
ESB240EM-A000 69
ESB265-0000 49
ESB265-A000 49
EST220-00J0 81
EST220-A0J0 81
EST240-00J0 81
EST240-A0J0 81
EST240EM-00J0 93
EST240EM-A0J0 93
EST265-00J0 81
EST265-A0J0 81
EVD120-00J0 47
EVD120-A0J0 47
EVD120-B0J0 47
EVD120EM-00J0 65
EVD120EM-A0J0 65
EVD120EMA-A000 67
EVD120EM-B0J0 65
EVD140-00J0 47
EVD140-A0J0 47
EVD140-B0J0 47
EVD140EM-00J0 65
EVD140EM-A0J0 65
EVD140EMA-A000 67
EVD140EMA-B000 67
EVD140EM-B0J0 65
EVD165-00J0 47
EVD165-A0J0 47
EVD165-B0J0 47
EVD220-00J0 47
EVD220-A0J0 47
EVD220-B0J0 47
EVD220EM-00J0 65
EVD220EM-A0J0 65
EVD220EMA-A000 67
EVD220EM-B0J0 65
EVD240-00J0 47
EVD240-A0J0 47
EVD240-B0J0 47
EVD240EM-00J0 65
EVD240EM-A0J0 65
EVD240EMA-A000 67
EVD240EMA-B000 67
EVD240EM-B0J0 65
EVD265-00J0 47
EVD265-A0J0 47
EVD265-B0J0 47
EVN120-0000 45
EVN120-A000 45
EVN120-B000 45
EVN120EM-0000 61
EVN120EM-A000 61
EVN120EMA-A000 63
EVN120EM-B000 61
EVN140-0000 45
EVN140-A000 45
EVN140-B000 45
EVN140EM-0000 61
EVN140EM-A000 61
EVN140EMA-A000 63
EVN140EMA-B000 63
EVN140EM-B000 61
EVN165-0000 45
EVN165-A000 45
EVN165-B000 45
EVN220-0000 45
EVN220-A000 45
EVN220-B000 45
EVN220EM-0000 61
EVN220EM-A000 61
EVN220EMA-A000 63
EVN220EM-B000 61
EVN240-0000 45
EVN240-A000 45
EVN240-B000 45
EVN240EM-0000 61
EVN240EM-A000 61
EVN240EMA-A000 63
EVN240EMA-B000 63
EVN240EM-B000 61
EVN265-0000 45
EVN265-A000 45
EVN265-B000 45
EVS120-0000 43
EVS120-A000 43
EVS120-B000 43
EVS120EM-0000 57
EVS120EM-A000 57
EVS120EM-B000 57
EVS120EMEA-0000 59
EVS120EMEA-A000 59
EVS120EMEA-B000 59
EVS140-0000 43
EVS140-A000 43
EVS140-B000 43
EVS140EM-0000 57
EVS140EM-A000 57
EVS140EM-B000 57
EVS140EMEA-0000 59
EVS140EMEA-A000 59
EVS140EMEA-B000 59
EVS165-0000 43
EVS165-A000 43
EVS165-B000 43
EVS220-0000 43
EVS220-A000 43
EVS220-B000 43
EVS220EM-0000 57
EVS220EM-A000 57
EVS220EM-B000 57
EVS220EMA-0000 59
EVS220EMA-A000 59
EVS220EMA-B000 59
EVS240-0000 43
EVS240-A000 43
EVS240-B000 43
EVS240EM-0000 57
EVS240EM-A000 57
EVS240EM-B000 57
EVS240EMA-0000 59
EVS240EMA-A000 59
EVS240EMA-B000 59
EVS265-0000 43
EVS265-A000 43
EVS265-B000 43
EVT120-00J0 79
EVT120-A0J0 79
EVT120-B0J0 79
EVT120EM-00J0 89
EVT120EM-A0J0 89
EVT120EMA-A0J0 91
EVT120EM-B0J0 89
EVT140-00J0 79
EVT140-A0J0 79
EVT140-B0J0 79
EVT140EM-00J0 89
EVT140EM-A0J0 89
EVT140EMA-A0J0 91
EVT140EMA-B0J0 91
Part No. Page Part No. Page Part No. Page Part No. Page Part No. Page
Index
169
Thomas & Betts • www.tnb-hazardous.com
EVT140EM-B0J0 89
EVT165-00J0 79
EVT165-A0J0 79
EVT165-B0J0 79
EVT220-00J0 79
EVT220-A0J0 79
EVT220-B0J0 79
EVT220EM-00J0 89
EVT220EM-A0J0 89
EVT220EMA-A0J0 91
EVT220EM-B0J0 89
EVT240-00J0 79
EVT240-A0J0 79
EVT240-B0J0 79
EVT240EM-00J0 89
EVT240EM-A0J0 89
EVT240EMA-A0J0 91
EVT240EMA-B0J0 91
EVT240EM-B0J0 89
EVT265-00J0 79
EVT265-A0J0 79
EVT265-B0J0 79
EVX100-00000 102
EVX200-00000 102
EVX300-00000 102
EVXlm40-00000 103
EVXlm40-00000 103
EVXNa20-00000 103
EVXNa30-00000 103
EVXNa40-00000 103
EVXNa50-00000 103
EX/038/SP 163
EX/038/TSP 163
EX/038-M16/TC 159
EX/050/SP 163
EX/050/TSP 163
EX/050-075/E 160
EX/050-M16/TC 159
EX/050-M20/TC 159
EX/050-M25/TC 159
EX/050-PG11/TC 161
EX/050-PG13/TC 161
EX/050-PG16/TC 161
EX/050-PG9/TC 161
EX/075/SP 163
EX/075/TSP 163
EX/075-050/R 160
EX/075-100/E 160
EX/075-M16/TC 159
EX/075-M20/TC 159
EX/075-M25/TC 159
EX/075-M32/TC 159
EX/075-PG11/TC 161
EX/075-PG13/TC 161
EX/075-PG16/TC 161
EX/075-PG21/TC 161
EX/075-PG9/TC 161
EX/100/SP 163
EX/100/TSP 163
EX/100-050/R 160
EX/100-075/R 160
EX/100-125/E 160
EX/100-M16/TC 159
EX/100-M20/TC 159
EX/100-M25/TC 159
EX/100-M32/TC 159
EX/100-M40/TC 159
EX/100-PG11/TC 161
EX/100-PG13/TC 161
EX/100-PG16/TC 161
EX/100-PG21/TC 161
EX/100-PG29/TC 161
EX/100-PG9/TC 161
EX/125/SP 163
EX/125/TSP 163
EX/125-050/R 160
EX/125-075/R 160
EX/125-100/R 160
EX/125-150/E 160
EX/125-M16/TC 159
EX/125-M20/TC 159
EX/125-M25/TC 159
EX/125-M32/TC 159
EX/125-M40/TC 159
EX/125-M50/TC 159
EX/125-PG11/TC 161
EX/125-PG13/TC 161
EX/125-PG16/TC 161
EX/125-PG21/TC 161
EX/125-PG29/TC 161
EX/125-PG36/TC 161
EX/125-PG9/TC 161
EX/150/SP 163
EX/150/TSP 163
EX/150-050/R 160
EX/150-075/R 160
EX/150-100/R 160
EX/150-125/R 160
EX/150-200/E 160
EX/150-M16/TC 159
EX/150-M20/TC 159
EX/150-M25/TC 159
EX/150-M32/TC 159
EX/150-M40/TC 159
EX/150-M50/TC 159
EX/150-M63/TC 159
EX/150-PG11/TC 161
EX/150-PG13/TC 161
EX/150-PG16/TC 161
EX/150-PG21/TC 161
EX/150-PG29/TC 161
EX/150-PG36/TC 161
EX/150-PG42/TC 161
EX/150-PG9/TC 161
EX/200/SP 163
EX/200/TSP 163
EX/200-050/R 160
EX/200-075/R 160
EX/200-100/R 160
EX/200-125/R 160
EX/200-150/R 160
EX/200-M16/TC 159
EX/200-M20/TC 159
EX/200-M25/TC 159
EX/200-M32/TC 159
EX/200-M40/TC 159
EX/200-M50/TC 159
EX/200-M63/TC 159
EX/200-PG11/TC 161
EX/200-PG13/TC 161
EX/200-PG16/TC 161
EX/200-PG21/TC 161
EX/200-PG29/TC 161
EX/200-PG36/TC 161
EX/200-PG42/TC 161
EX/200-PG48/TC 161
EX/200-PG9/TC 161
EX/250-M50/TC 159
EX/300-M50/TC 159
EX/M16/C 167
EX/M16/DSP 165
EX/M16/HSP 165
EX/M16/SP 163
EX/M16/TAG 167
EX/M16/TSP 163
EX/M16-038/TC 160
EX/M16-050/TC 160
EX/M16-M20/E 159
EX/M16-M25/E 159
EX/M16-PG11/TC 161
EX/M16-PG13/TC 161
EX/M16-PG9/TC 161
EX/M20/C 167
EX/M20/DSP 165
EX/M20/HSP 165
EX/M20/SP 163
EX/M20/TAG 167
EX/M20/TSP 163
EX/M20-050/TC 160
EX/M20-075/TC 160
EX/M20-M16/R 159
EX/M20-M25/E 159
EX/M20-M32/E 159
EX/M20-PG11/TC 161
EX/M20-PG13/TC 161
EX/M20-PG16/TC 161
EX/M20-PG9/TC 161
EX/M25/C 167
EX/M25/DSP 165
EX/M25/HSP 165
EX/M25/SP 163
EX/M25/TAG 167
EX/M25/TSP 163
EX/M25-050/TC 160
EX/M25-075/TC 160
EX/M25-100/TC 160
EX/M25-M16/R 159
EX/M25-M20/R 159
EX/M25-M32/E 159
EX/M25-M40/E 159
EX/M25-PG11/TC 161
EX/M25-PG13/TC 161
EX/M25-PG16/TC 161
EX/M25-PG21/TC 161
EX/M25-PG9/TC 161
EX/M32/C 167
EX/M32/DSP 165
EX/M32/HSP 165
EX/M32/SP 163
EX/M32/TAG 167
EX/M32/TSP 163
EX/M32-050/TC 160
EX/M32-075/TC 160
EX/M32-100/TC 160
EX/M32-125/TC 160
EX/M32-M16/R 159
EX/M32-M20/R 159
EX/M32-M25/R 159
EX/M32-M40/E 159
EX/M32-M50/E 159
EX/M32-PG11/TC 161
EX/M32-PG13/TC 161
EX/M32-PG16/TC 161
EX/M32-PG21/TC 161
EX/M32-PG29/TC 161
EX/M32-PG9/TC 161
EX/M40/C 167
EX/M40/DSP 165
EX/M40/HSP 165
EX/M40/SP 163
EX/M40/TAG 167
EX/M40/TSP 163
EX/M40-050/TC 160
EX/M40-075/TC 160
EX/M40-100/TC 160
EX/M40-125/TC 160
EX/M40-150/TC 160
EX/M40-M16/R 159
EX/M40-M20/R 159
EX/M40-M25/R 159
EX/M40-M32/R 159
EX/M40-M50/E 159
EX/M40-M63/E 159
EX/M40-PG11/TC 161
EX/M40-PG13/TC 161
EX/M40-PG16/TC 161
EX/M40-PG21/TC 161
EX/M40-PG29/TC 161
EX/M40-PG36/TC 161
EX/M40-PG9/TC 161
EX/M50/C 167
EX/M50/DSP 165
EX/M50/HSP 165
EX/M50/SP 163
EX/M50/TAG 167
EX/M50/TSP 163
EX/M50-050/TC 160
EX/M50-075/TC 160
EX/M50-100/TC 160
EX/M50-125/TC 160
Part No. Page Part No. Page Part No. Page Part No. Page Part No. Page
170
Index
Thomas & Betts • www.tnb-hazardous.com
EX/M50-150/TC 160
EX/M50-200/TC 160
EX/M50-M16/R 159
EX/M50-M20/R 159
EX/M50-M25/R 159
EX/M50-M32/R 159
EX/M50-M40/R 159
EX/M50-M63/E 159
EX/M50-M75/E 159
EX/M50-PG11/TC 161
EX/M50-PG13/TC 161
EX/M50-PG16/TC 161
EX/M50-PG21/TC 161
EX/M50-PG29/TC 161
EX/M50-PG36/TC 161
EX/M50-PG42/TC 161
EX/M50-PG9/TC 161
EX/M63/C 167
EX/M63/DSP 165
EX/M63/HSP 165
EX/M63/SP 163
EX/M63/TAG 167
EX/M63/TSP 163
EX/M63-050/TC 160
EX/M63-075/TC 160
EX/M63-100/TC 160
EX/M63-125/TC 160
EX/M63-150/TC 160
EX/M63-200/TC 160
EX/M63-M16/R 159
EX/M63-M20/R 159
EX/M63-M25/R 159
EX/M63-M32/R 159
EX/M63-M40/R 159
EX/M63-M50/R 159
EX/M63-M75/E 159
EX/M63-PG11/TC 161
EX/M63-PG13/TC 161
EX/M63-PG16/TC 161
EX/M63-PG21/TC 161
EX/M63-PG29/TC 161
EX/M63-PG36/TC 161
EX/M63-PG42/TC 161
EX/M63-PG48/TC 161
EX/M63-PG9/TC 161
EX/M75/C 167
EX/M75/TAG 167
EX/M75-050/TC 160
EX/M75-075/TC 160
EX/M75-100/TC 160
EX/M75-125/TC 160
EX/M75-150/TC 160
EX/M75-200/TC 160
EX/M75-M16/R 159
EX/M75-M20/R 159
EX/M75-M25/R 159
EX/M75-M32/R 159
EX/M75-M40/R 159
EX/M75-M50/R 159
EX/M75-M63/R 159
EX/M75-PG11/TC 161
EX/M75-PG13/TC 161
EX/M75-PG16/TC 161
EX/M75-PG21/TC 161
EX/M75-PG29/TC 161
EX/M75-PG36/TC 161
EX/M75-PG42/TC 161
EX/M75-PG48/TC 161
EX/M75-PG9/TC 161
EX/PG11/DSP 165
EX/PG11/HSP 165
EX/PG11/SP 163
EX/PG11/TSP 163
EX/PG11-050/TC 160
EX/PG11-M16/TC 159
EX/PG11-M20/TC 159
EX/PG11-PG9/R 161
EX/PG13/DSP 165
EX/PG13/HSP 165
EX/PG13/SP 163
EX/PG13/TSP 163
EX/PG13-050/TC 160
EX/PG13-M16/TC 159
EX/PG13-M20/TC 159
EX/PG13-PG11/R 161
EX/PG13-PG9/R 161
EX/PG16/DSP 165
EX/PG16/HSP 165
EX/PG16/SP 163
EX/PG16/TSP 163
EX/PG16-050/TC 160
EX/PG16-075/TC 160
EX/PG16-M16/TC 159
EX/PG16-M20/TC 159
EX/PG16-M25/TC 159
EX/PG16-PG11/R 161
EX/PG16-PG13/R 161
EX/PG16-PG21/E 161
EX/PG16-PG9/R 161
EX/PG21/DSP 165
EX/PG21/HSP 165
EX/PG21/SP 163
EX/PG21/TSP 163
EX/PG21-075/TC 160
EX/PG21-100/TC 160
EX/PG21-M16/TC 159
EX/PG21-M20/TC 159
EX/PG21-M25/TC 159
EX/PG21-M32/TC 159
EX/PG21-PG11/R 161
EX/PG21-PG13/R 161
EX/PG21-PG16/R 161
EX/PG21-PG29/E 161
EX/PG21-PG9/R 161
EX/PG29/DSP 165
EX/PG29/HSP 165
EX/PG29/SP 163
EX/PG29/TSP 163
EX/PG29-050/TC 160
EX/PG29-075/TC 160
EX/PG29-100/TC 160
EX/PG29-125/TC 160
EX/PG29-150/TC 160
EX/PG29-M16/TC 159
EX/PG29-M20/TC 159
EX/PG29-M25/TC 159
EX/PG29-M32/TC 159
EX/PG29-M40/TC 159
EX/PG29-PG11/R 161
EX/PG29-PG13/R 161
EX/PG29-PG16/R 161
EX/PG29-PG21/R 161
EX/PG29-PG36/E 161
EX/PG29-PG9/R 161
EX/PG36/DSP 165
EX/PG36/HSP 165
EX/PG36/SP 163
EX/PG36/TSP 163
EX/PG36-050/TC 160
EX/PG36-075/TC 160
EX/PG36-100/TC 160
EX/PG36-125/TC 160
EX/PG36-150/TC 160
EX/PG36-M16/TC 159
EX/PG36-M20/TC 159
EX/PG36-M25/TC 159
EX/PG36-M32/TC 159
EX/PG36-M40/TC 159
EX/PG36-M50/TC 159
EX/PG36-PG11/R 161
EX/PG36-PG13/R 161
EX/PG36-PG16/R 161
EX/PG36-PG21/R 161
EX/PG36-PG29/R 161
EX/PG36-PG48/E 161
EX/PG36-PG9/R 161
EX/PG42/DSP 165
EX/PG42/HSP 165
EX/PG42/SP 163
EX/PG42/TSP 163
EX/PG42-050/TC 160
EX/PG42-075/TC 160
EX/PG42-100/TC 160
EX/PG42-125/TC 160
EX/PG42-150/TC 160
EX/PG42-200/TC 160
EX/PG42-M16/TC 159
EX/PG42-M20/TC 159
EX/PG42-M25/TC 159
EX/PG42-M32/TC 159
EX/PG42-M40/TC 159
EX/PG42-M50/TC 159
EX/PG42-M63/TC 159
EX/PG42-PG11/R 161
EX/PG42-PG13/R 161
EX/PG42-PG16/R 161
EX/PG42-PG21/R 161
EX/PG42-PG29/R 161
EX/PG42-PG36/R 161
EX/PG42-PG48/E 161
EX/PG42-PG9/R 161
EX/PG48/DSP 165
EX/PG48/HSP 165
EX/PG48/SP 163
EX/PG48/TSP 163
EX/PG48-050/TC 160
EX/PG48-075/TC 160
EX/PG48-100/TC 160
EX/PG48-125/TC 160
EX/PG48-150/TC 160
EX/PG48-200/TC 160
EX/PG48-M16/TC 159
EX/PG48-M20/TC 159
EX/PG48-M25/TC 159
EX/PG48-M32/TC 159
EX/PG48-M40/TC 159
EX/PG48-M50/TC 159
EX/PG48-M63/TC 159
EX/PG48-PG11/R 161
EX/PG48-PG13/R 161
EX/PG48-PG16/R 161
EX/PG48-PG21/R 161
EX/PG48-PG29/R 161
EX/PG48-PG36/R 161
EX/PG48-PG42/R 161
EX/PG48-PG9/R 161
EX/PG9/DSP 165
EX/PG9/HSP 165
EX/PG9/SP 163
EX/PG9/TSP 163
EX/PG9-050/TC 160
EX/PG9-M16/TC 159
EX/PG9-M20/TC 159
EX-8160 167
EX-8240 167
EX-8560 167
EX-8640 167
EX-8720 167
EX-8800 167
EXB0310 137
EXB0330 137
EXB0350 137
EXB0410 137
EXB0430 137
EXB0450 137
EXB0510 137
EXB0530 137
EXB0550 137
EXB0610 137
EXB0630 137
EXB0650 137
EXB0710 137
EXB0730 137
EXB0750 137
EXB0810 137
EXB0830 137
EXB0850 137
EXBB0310 137
EXBB0410 137
EXBB0430 137
Part No. Page Part No. Page Part No. Page Part No. Page Part No. Page
Index
171
Thomas & Betts • www.tnb-hazardous.com
EXBB0450 137
EXBB0510 137
EXBB0530 137
EXBB0550 137
EXBB0610 137
EXBB0630 137
EXBB0650 137
EXBB0710 137
EXBB0810 137
EXBBT0110 141
EXBBT0130 141
EXBBT0210 141
EXBBT0230 141
EXBBT0310 141
EXBBT0330 141
EXBBT0410 141
EXBBT0430 141
EXBBT0450 141
EXBBT0510 141
EXBBT0530 141
EXBBT0550 141
EXBBT0610 141
EXBBT0630 141
EXBBT0710 141
EXBBT0720 141
EXBBT0810 141
EXBBT0820 141
EXBBT0910 141
EXBBT0920 141
EXBQA0304 139
EXBQA0404 139
EXBQA0505 139
EXBQA0606 139
EXBQA0707 139
EXBQA0808 139
EXBQM0303 139
EXBQM0404 139
EXBQM0505 139
EXBQM0606 139
EXBQM0707 139
EXBQM0808 139
EXFM03 167
EXFM03F 167
EXFM04 167
EXFM04F 167
EXFM05 167
EXFM05F 167
EXFM06 167
EXFM06F 167
EXFM07 167
EXFM07F 167
EXFM08 167
EXFM08F 167
EXLB0110 141
EXLB0130 141
EXLB0210 141
EXLB0230 141
EXLB0310 141
EXLB0330 141
EXLB0410 141
EXLB0430 141
EXLB0450 141
EXLB0510 141
EXLB0530 141
EXLB0550 141
EXLB0610 141
EXLB0630 141
EXLB0710 141
EXLB0720 141
EXLB0810 141
EXLB0820 141
EXLB0910 141
EXLB0920 141
EXLH0310 141
EXLH0330 141
EXLH0410 141
EXLH0430 141
EXLH0510 141
EXLH0530 141
EXLH0610 141
EXLH0620 141
EXLH0710 141
EXLH0720 141
EXLH0810 141
EXLH0820 141
EXLH0910 141
EXLH0920 141
EXLHC0310 141
EXLHC0330 141
EXLHC0410 141
EXLHC0430 141
EXLHC0510 141
EXLHC0530 141
EXLHC0610 141
EXLHC0630 141
EXLHC0710 141
EXLHC0810 141
EXLHC0820 141
EXLHC0910 141
EXLLH0310 141
EXLLH0330 141
EXLLH0410 141
EXLLH0430 141
EXLLH0510 141
EXLLH0530 141
EXLLH0610 141
EXLLH0620 141
EXLLH0710 141
EXLLH0720 141
EXLLH0810 141
EXLLH0820 141
EXLLH0910 141
EXLLH0920 141
EXLT0310 141
EXLT0330 141
EXLT0410 141
EXLT0430 141
EXLT0510 141
EXLT0530 141
EXLT0610 141
EXLT0620 141
EXLT0710 141
EXLT0720 141
EXLT0810 141
EXLT0820 141
EXLT0910 141
EXLT0920 141
EXLT0930 141
EX-M16 165
EX-M20 165
EX-M25 165
EX-M32 165
EX-M40 165
EX-M50 165
EX-M63 165
EXN/038/SP 163
EXN/038/TSP 163
EXN/038-M16/TC 159
EXN/050/SP 163
EXN/050/TSP 163
EXN/050-075/E 160
EXN/050-M16/TC 159
EXN/050-M20/TC 159
EXN/050-M25/TC 159
EXN/050-PG11/TC 161
EXN/050-PG13/TC 161
EXN/050-PG16/TC 161
EXN/050-PG9/TC 161
EXN/075/SP 163
EXN/075/TSP 163
EXN/075-050/R 160
EXN/075-100/E 160
EXN/075-M16/TC 159
EXN/075-M20/TC 159
EXN/075-M25/TC 159
EXN/075-M32/TC 159
EXN/075-PG11/TC 161
EXN/075-PG13/TC 161
EXN/075-PG16/TC 161
EXN/075-PG21/TC 161
EXN/075-PG9/TC 161
EXN/100/SP 163
EXN/100/TSP 163
EXN/100-050/R 160
EXN/100-075/R 160
EXN/100-125/E 160
EXN/100-M16/TC 159
EXN/100-M20/TC 159
EXN/100-M25/TC 159
EXN/100-M32/TC 159
EXN/100-M40/TC 159
EXN/100-PG11/TC 161
EXN/100-PG13/TC 161
EXN/100-PG16/TC 161
EXN/100-PG21/TC 161
EXN/100-PG29/TC 161
EXN/100-PG9/TC 161
EXN/125/SP 163
EXN/125/TSP 163
EXN/125-050/R 160
EXN/125-075/R 160
EXN/125-100/R 160
EXN/125-150/E 160
EXN/125-M16/TC 159
EXN/125-M20/TC 159
EXN/125-M25/TC 159
EXN/125-M32/TC 159
EXN/125-M40/TC 159
EXN/125-M50/TC 159
EXN/125-PG11/TC 161
EXN/125-PG13/TC 161
EXN/125-PG16/TC 161
EXN/125-PG21/TC 161
EXN/125-PG29/TC 161
EXN/125-PG36/TC 161
EXN/125-PG9/TC 161
EXN/150/SP 163
EXN/150/TSP 163
EXN/150-050/R 160
EXN/150-075/R 160
EXN/150-100/R 160
EXN/150-125/R 160
EXN/150-200/E 160
EXN/150-M16/TC 159
EXN/150-M20/TC 159
EXN/150-M25/TC 159
EXN/150-M32/TC 159
EXN/150-M40/TC 159
EXN/150-M50/TC 159
EXN/150-M63/TC 159
EXN/150-PG11/TC 161
EXN/150-PG13/TC 161
EXN/150-PG16/TC 161
EXN/150-PG21/TC 161
EXN/150-PG29/TC 161
EXN/150-PG36/TC 161
EXN/150-PG42/TC 161
EXN/150-PG9/TC 161
EXN/200/SP 163
EXN/200/TSP 163
EXN/200-050/R 160
EXN/200-075/R 160
EXN/200-100/R 160
EXN/200-125/R 160
EXN/200-150/R 160
EXN/200-M16/TC 159
EXN/200-M20/TC 159
EXN/200-M25/TC 159
EXN/200-M32/TC 159
EXN/200-M40/TC 159
EXN/200-M50/TC 159
EXN/200-M63/TC 159
EXN/200-PG11/TC 161
EXN/200-PG13/TC 161
EXN/200-PG16/TC 161
EXN/200-PG21/TC 161
EXN/200-PG29/TC 161
EXN/200-PG36/TC 161
EXN/200-PG42/TC 161
EXN/200-PG48/TC 161
Part No. Page Part No. Page Part No. Page Part No. Page Part No. Page
172
Index
Thomas & Betts • www.tnb-hazardous.com
EXN/200-PG9/TC 161
EXN/250-M50/TC 159
EXN/300-M50/TC 159
EXN/M16/C 167
EXN/M16/DSP 165
EXN/M16/HSP 165
EXN/M16/SP 163
EXN/M16/TSP 163
EXN/M16-038/TC 160
EXN/M16-050/TC 160
EXN/M16-M20/E 159
EXN/M16-M25/E 159
EXN/M16-PG11/TC 161
EXN/M16-PG13/TC 161
EXN/M16-PG9/TC 161
EXN/M20/C 167
EXN/M20/DSP 165
EXN/M20/HSP 165
EXN/M20/SP 163
EXN/M20/TSP 163
EXN/M20-050/TC 160
EXN/M20-075/TC 160
EXN/M20-M16/R 159
EXN/M20-M25/E 159
EXN/M20-M32/E 159
EXN/M20-PG11/TC 161
EXN/M20-PG13/TC 161
EXN/M20-PG16/TC 161
EXN/M20-PG9/TC 161
EXN/M25/C 167
EXN/M25/DSP 165
EXN/M25/HSP 165
EXN/M25/SP 163
EXN/M25/TSP 163
EXN/M25-050/TC 160
EXN/M25-075/TC 160
EXN/M25-100/TC 160
EXN/M25-M16/R 159
EXN/M25-M20/R 159
EXN/M25-M32/E 159
EXN/M25-M40/E 159
EXN/M25-PG11/TC 161
EXN/M25-PG13/TC 161
EXN/M25-PG16/TC 161
EXN/M25-PG21/TC 161
EXN/M25-PG9/TC 161
EXN/M32/C 167
EXN/M32/DSP 165
EXN/M32/HSP 165
EXN/M32/SP 163
EXN/M32/TSP 163
EXN/M32-050/TC 160
EXN/M32-075/TC 160
EXN/M32-100/TC 160
EXN/M32-125/TC 160
EXN/M32-M16/R 159
EXN/M32-M20/R 159
EXN/M32-M25/R 159
EXN/M32-M40/E 159
EXN/M32-M50/E 159
EXN/M32-PG11/TC 161
EXN/M32-PG13/TC 161
EXN/M32-PG16/TC 161
EXN/M32-PG21/TC 161
EXN/M32-PG29/TC 161
EXN/M32-PG9/TC 161
EXN/M40/C 167
EXN/M40/DSP 165
EXN/M40/HSP 165
EXN/M40/SP 163
EXN/M40/TSP 163
EXN/M40-050/TC 160
EXN/M40-075/TC 160
EXN/M40-100/TC 160
EXN/M40-125/TC 160
EXN/M40-150/TC 160
EXN/M40-M16/R 159
EXN/M40-M20/R 159
EXN/M40-M25/R 159
EXN/M40-M32/R 159
EXN/M40-M50/E 159
EXN/M40-M63/E 159
EXN/M40-PG11/TC 161
EXN/M40-PG13/TC 161
EXN/M40-PG16/TC 161
EXN/M40-PG21/TC 161
EXN/M40-PG29/TC 161
EXN/M40-PG36/TC 161
EXN/M40-PG9/TC 161
EXN/M50/C 167
EXN/M50/DSP 165
EXN/M50/HSP 165
EXN/M50/SP 163
EXN/M50/TSP 163
EXN/M50-050/TC 160
EXN/M50-075/TC 160
EXN/M50-100/TC 160
EXN/M50-125/TC 160
EXN/M50-150/TC 160
EXN/M50-200/TC 160
EXN/M50-M16/R 159
EXN/M50-M20/R 159
EXN/M50-M25/R 159
EXN/M50-M32/R 159
EXN/M50-M40/R 159
EXN/M50-M63/E 159
EXN/M50-M75/E 159
EXN/M50-PG11/TC 161
EXN/M50-PG13/TC 161
EXN/M50-PG16/TC 161
EXN/M50-PG21/TC 161
EXN/M50-PG29/TC 161
EXN/M50-PG36/TC 161
EXN/M50-PG42/TC 161
EXN/M50-PG9/TC 161
EXN/M63/C 167
EXN/M63/DSP 165
EXN/M63/HSP 165
EXN/M63/SP 163
EXN/M63/TSP 163
EXN/M63-050/TC 160
EXN/M63-075/TC 160
EXN/M63-100/TC 160
EXN/M63-125/TC 160
EXN/M63-150/TC 160
EXN/M63-200/TC 160
EXN/M63-M16/R 159
EXN/M63-M20/R 159
EXN/M63-M25/R 159
EXN/M63-M32/R 159
EXN/M63-M40/R 159
EXN/M63-M50/R 159
EXN/M63-M75/E 159
EXN/M63-PG11/TC 161
EXN/M63-PG13/TC 161
EXN/M63-PG16/TC 161
EXN/M63-PG21/TC 161
EXN/M63-PG29/TC 161
EXN/M63-PG36/TC 161
EXN/M63-PG42/TC 161
EXN/M63-PG48/TC 161
EXN/M63-PG9/TC 161
EXN/M75-050/TC 160
EXN/M75-075/TC 160
EXN/M75-100/TC 160
EXN/M75-125/TC 160
EXN/M75-150/TC 160
EXN/M75-200/TC 160
EXN/M75-M16/R 159
EXN/M75-M20/R 159
EXN/M75-M25/R 159
EXN/M75-M32/R 159
EXN/M75-M40/R 159
EXN/M75-M50/R 159
EXN/M75-M63/R 159
EXN/M75-PG11/TC 161
EXN/M75-PG13/TC 161
EXN/M75-PG16/TC 161
EXN/M75-PG21/TC 161
EXN/M75-PG29/TC 161
EXN/M75-PG36/TC 161
EXN/M75-PG42/TC 161
EXN/M75-PG48/TC 161
EXN/M75-PG9/TC 161
EXN/PG11/DSP 165
EXN/PG11/HSP 165
EXN/PG11/SP 163
EXN/PG11/TSP 163
EXN/PG11-050/TC 160
EXN/PG11-M16/TC 159
EXN/PG11-M20/TC 159
EXN/PG11-PG9/R 161
EXN/PG13/DSP 165
EXN/PG13/HSP 165
EXN/PG13/SP 163
EXN/PG13/TSP 163
EXN/PG13-050/TC 160
EXN/PG13-M16/TC 159
EXN/PG13-M20/TC 159
EXN/PG13-PG11/R 161
EXN/PG13-PG9/R 161
EXN/PG16/DSP 165
EXN/PG16/HSP 165
EXN/PG16/SP 163
EXN/PG16/TSP 163
EXN/PG16-050/TC 160
EXN/PG16-075/TC 160
EXN/PG16-M16/TC 159
EXN/PG16-M20/TC 159
EXN/PG16-M25/TC 159
EXN/PG16-PG11/R 161
EXN/PG16-PG13/R 161
EXN/PG16-PG21/E 161
EXN/PG16-PG9/R 161
EXN/PG21/DSP 165
EXN/PG21/HSP 165
EXN/PG21/SP 163
EXN/PG21/TSP 163
EXN/PG21-075/TC 160
EXN/PG21-100/TC 160
EXN/PG21-M16/TC 159
EXN/PG21-M20/TC 159
EXN/PG21-M25/TC 159
EXN/PG21-M32/TC 159
EXN/PG21-PG11/R 161
EXN/PG21-PG13/R 161
EXN/PG21-PG16/R 161
EXN/PG21-PG29/E 161
EXN/PG21-PG9/R 161
EXN/PG29/DSP 165
EXN/PG29/HSP 165
EXN/PG29/SP 163
EXN/PG29/TSP 163
EXN/PG29-050/TC 160
EXN/PG29-075/TC 160
EXN/PG29-100/TC 160
EXN/PG29-125/TC 160
EXN/PG29-150/TC 160
EXN/PG29-M16/TC 159
EXN/PG29-M20/TC 159
EXN/PG29-M25/TC 159
EXN/PG29-M32/TC 159
EXN/PG29-M40/TC 159
EXN/PG29-PG11/R 161
EXN/PG29-PG13/R 161
EXN/PG29-PG16/R 161
EXN/PG29-PG21/R 161
EXN/PG29-PG36/E 161
EXN/PG29-PG9/R 161
EXN/PG36/DSP 165
EXN/PG36/HSP 165
EXN/PG36/SP 163
EXN/PG36/TSP 163
EXN/PG36-050/TC 160
EXN/PG36-075/TC 160
EXN/PG36-100/TC 160
EXN/PG36-125/TC 160
EXN/PG36-150/TC 160
EXN/PG36-M16/TC 159
EXN/PG36-M20/TC 159
Part No. Page Part No. Page Part No. Page Part No. Page Part No. Page
Index
173
Thomas & Betts • www.tnb-hazardous.com
EXN/PG36-M25/TC 159
EXN/PG36-M32/TC 159
EXN/PG36-M40/TC 159
EXN/PG36-M50/TC 159
EXN/PG36-PG11/R 161
EXN/PG36-PG13/R 161
EXN/PG36-PG16/R 161
EXN/PG36-PG21/R 161
EXN/PG36-PG29/R 161
EXN/PG36-PG48/E 161
EXN/PG36-PG9/R 161
EXN/PG42/DSP 165
EXN/PG42/HSP 165
EXN/PG42/SP 163
EXN/PG42/TSP 163
EXN/PG42-050/TC 160
EXN/PG42-075/TC 160
EXN/PG42-100/TC 160
EXN/PG42-125/TC 160
EXN/PG42-150/TC 160
EXN/PG42-200/TC 160
EXN/PG42-M16/TC 159
EXN/PG42-M20/TC 159
EXN/PG42-M25/TC 159
EXN/PG42-M32/TC 159
EXN/PG42-M40/TC 159
EXN/PG42-M50/TC 159
EXN/PG42-M63/TC 159
EXN/PG42-PG11/R 161
EXN/PG42-PG13/R 161
EXN/PG42-PG16/R 161
EXN/PG42-PG21/R 161
EXN/PG42-PG29/R 161
EXN/PG42-PG36/R 161
EXN/PG42-PG48/E 161
EXN/PG42-PG9/R 161
EXN/PG48/DSP 165
EXN/PG48/HSP 165
EXN/PG48/SP 163
EXN/PG48/TSP 163
EXN/PG48-050/TC 160
EXN/PG48-075/TC 160
EXN/PG48-100/TC 160
EXN/PG48-125/TC 160
EXN/PG48-150/TC 160
EXN/PG48-200/TC 160
EXN/PG48-M16/TC 159
EXN/PG48-M20/TC 159
EXN/PG48-M25/TC 159
EXN/PG48-M32/TC 159
EXN/PG48-M40/TC 159
EXN/PG48-M50/TC 159
EXN/PG48-M63/TC 159
EXN/PG48-PG11/R 161
EXN/PG48-PG13/R 161
EXN/PG48-PG16/R 161
EXN/PG48-PG21/R 161
EXN/PG48-PG29/R 161
EXN/PG48-PG36/R 161
EXN/PG48-PG42/R 161
EXN/PG48-PG9/R 161
EXN/PG9/DSP 165
EXN/PG9/HSP 165
EXN/PG9/SP 163
EXN/PG9/TSP 163
EXN/PG9-050/TC 160
EXN/PG9-M16/TC 159
EXN/PG9-M20/TC 159
EXPQA0303 139
EXPQA0404 139
EXPQA0505 139
EXPQA0606 139
EXPQA0707 139
EXPQA0808 139
EXPQM0303 139
EXPQM0404 139
EXPQM0505 139
EXPQM0606 139
EXPQM0707 139
EXPQM0808 139
EXS/038/SP 163
EXS/038/TSP 163
EXS/038-M16/TC 159
EXS/050/SP 163
EXS/050/TSP 163
EXS/050-075/E 160
EXS/050-M16/TC 159
EXS/050-M20/TC 159
EXS/050-M25/TC 159
EXS/050-PG11/TC 161
EXS/050-PG13/TC 161
EXS/050-PG16/TC 161
EXS/050-PG9/TC 161
EXS/075/SP 163
EXS/075/TSP 163
EXS/075-050/R 160
EXS/075-100/E 160
EXS/075-M16/TC 159
EXS/075-M20/TC 159
EXS/075-M25/TC 159
EXS/075-M32/TC 159
EXS/075-PG11/TC 161
EXS/075-PG13/TC 161
EXS/075-PG16/TC 161
EXS/075-PG21/TC 161
EXS/075-PG9/TC 161
EXS/100/SP 163
EXS/100/TSP 163
EXS/100-050/R 160
EXS/100-075/R 160
EXS/100-125/E 160
EXS/100-M16/TC 159
EXS/100-M20/TC 159
EXS/100-M25/TC 159
EXS/100-M32/TC 159
EXS/100-M40/TC 159
EXS/100-PG11/TC 161
EXS/100-PG13/TC 161
EXS/100-PG16/TC 161
EXS/100-PG21/TC 161
EXS/100-PG29/TC 161
EXS/100-PG9/TC 161
EXS/125/SP 163
EXS/125/TSP 163
EXS/125-050/R 160
EXS/125-075/R 160
EXS/125-100/R 160
EXS/125-150/E 160
EXS/125-M16/TC 159
EXS/125-M20/TC 159
EXS/125-M25/TC 159
EXS/125-M32/TC 159
EXS/125-M40/TC 159
EXS/125-M50/TC 159
EXS/125-PG11/TC 161
EXS/125-PG13/TC 161
EXS/125-PG16/TC 161
EXS/125-PG21/TC 161
EXS/125-PG29/TC 161
EXS/125-PG36/TC 161
EXS/125-PG9/TC 161
EXS/150/SP 163
EXS/150/TSP 163
EXS/150-050/R 160
EXS/150-075/R 160
EXS/150-100/R 160
EXS/150-125/R 160
EXS/150-200/E 160
EXS/150-M16/TC 159
EXS/150-M20/TC 159
EXS/150-M25/TC 159
EXS/150-M32/TC 159
EXS/150-M40/TC 159
EXS/150-M50/TC 159
EXS/150-M63/TC 159
EXS/150-PG11/TC 161
EXS/150-PG13/TC 161
EXS/150-PG16/TC 161
EXS/150-PG21/TC 161
EXS/150-PG29/TC 161
EXS/150-PG36/TC 161
EXS/150-PG42/TC 161
EXS/150-PG9/TC 161
EXS/200/SP 163
EXS/200/TSP 163
EXS/200-050/R 160
EXS/200-075/R 160
EXS/200-100/R 160
EXS/200-125/R 160
EXS/200-150/R 160
EXS/200-M16/TC 159
EXS/200-M20/TC 159
EXS/200-M25/TC 159
EXS/200-M32/TC 159
EXS/200-M40/TC 159
EXS/200-M50/TC 159
EXS/200-M63/TC 159
EXS/200-PG11/TC 161
EXS/200-PG13/TC 161
EXS/200-PG16/TC 161
EXS/200-PG21/TC 161
EXS/200-PG29/TC 161
EXS/200-PG36/TC 161
EXS/200-PG42/TC 161
EXS/200-PG48/TC 161
EXS/200-PG9/TC 161
EXS/250-M50/TC 159
EXS/300-M50/TC 159
EXS/M16/C 167
EXS/M16/DSP 165
EXS/M16/HSP 165
EXS/M16/SP 163
EXS/M16/TSP 163
EXS/M16-038/TC 160
EXS/M16-050/TC 160
EXS/M16-M20/E 159
EXS/M16-M25/E 159
EXS/M16-PG11/TC 161
EXS/M16-PG13/TC 161
EXS/M16-PG9/TC 161
EXS/M20/C 167
EXS/M20/DSP 165
EXS/M20/HSP 165
EXS/M20/SP 163
EXS/M20/TSP 163
EXS/M20-050/TC 160
EXS/M20-075/TC 160
EXS/M20-M16/R 159
EXS/M20-M25/E 159
EXS/M20-M32/E 159
EXS/M20-PG11/TC 161
EXS/M20-PG13/TC 161
EXS/M20-PG16/TC 161
EXS/M20-PG9/TC 161
EXS/M25/C 167
EXS/M25/DSP 165
EXS/M25/HSP 165
EXS/M25/SP 163
EXS/M25/TSP 163
EXS/M25-050/TC 160
EXS/M25-075/TC 160
EXS/M25-100/TC 160
EXS/M25-M16/R 159
EXS/M25-M20/R 159
EXS/M25-M32/E 159
EXS/M25-M40/E 159
EXS/M25-PG11/TC 161
EXS/M25-PG13/TC 161
EXS/M25-PG16/TC 161
EXS/M25-PG21/TC 161
EXS/M25-PG9/TC 161
EXS/M32/C 167
EXS/M32/DSP 165
EXS/M32/HSP 165
EXS/M32/SP 163
EXS/M32/TSP 163
EXS/M32-050/TC 160
EXS/M32-075/TC 160
EXS/M32-100/TC 160
EXS/M32-125/TC 160
Part No. Page Part No. Page Part No. Page Part No. Page Part No. Page
174
Index
Thomas & Betts • www.tnb-hazardous.com
EXS/M32-M16/R 159
EXS/M32-M20/R 159
EXS/M32-M25/R 159
EXS/M32-M40/E 159
EXS/M32-M50/E 159
EXS/M32-PG11/TC 161
EXS/M32-PG13/TC 161
EXS/M32-PG16/TC 161
EXS/M32-PG21/TC 161
EXS/M32-PG29/TC 161
EXS/M32-PG9/TC 161
EXS/M40/C 167
EXS/M40/DSP 165
EXS/M40/HSP 165
EXS/M40/SP 163
EXS/M40/TSP 163
EXS/M40-050/TC 160
EXS/M40-075/TC 160
EXS/M40-100/TC 160
EXS/M40-125/TC 160
EXS/M40-150/TC 160
EXS/M40-M16/R 159
EXS/M40-M20/R 159
EXS/M40-M25/R 159
EXS/M40-M32/R 159
EXS/M40-M50/E 159
EXS/M40-M63/E 159
EXS/M40-PG11/TC 161
EXS/M40-PG13/TC 161
EXS/M40-PG16/TC 161
EXS/M40-PG21/TC 161
EXS/M40-PG29/TC 161
EXS/M40-PG36/TC 161
EXS/M40-PG9/TC 161
EXS/M50/C 167
EXS/M50/DSP 165
EXS/M50/HSP 165
EXS/M50/SP 163
EXS/M50/TSP 163
EXS/M50-050/TC 160
EXS/M50-075/TC 160
EXS/M50-100/TC 160
EXS/M50-125/TC 160
EXS/M50-150/TC 160
EXS/M50-200/TC 160
EXS/M50-M16/R 159
EXS/M50-M20/R 159
EXS/M50-M25/R 159
EXS/M50-M32/R 159
EXS/M50-M40/R 159
EXS/M50-M63/E 159
EXS/M50-M75/E 159
EXS/M50-PG11/TC 161
EXS/M50-PG13/TC 161
EXS/M50-PG16/TC 161
EXS/M50-PG21/TC 161
EXS/M50-PG29/TC 161
EXS/M50-PG36/TC 161
EXS/M50-PG42/TC 161
EXS/M50-PG9/TC 161
EXS/M63/C 167
EXS/M63/DSP 165
EXS/M63/HSP 165
EXS/M63/SP 163
EXS/M63/TSP 163
EXS/M63-050/TC 160
EXS/M63-075/TC 160
EXS/M63-100/TC 160
EXS/M63-125/TC 160
EXS/M63-150/TC 160
EXS/M63-200/TC 160
EXS/M63-M16/R 159
EXS/M63-M20/R 159
EXS/M63-M25/R 159
EXS/M63-M32/R 159
EXS/M63-M40/R 159
EXS/M63-M50/R 159
EXS/M63-M75/E 159
EXS/M63-PG11/TC 161
EXS/M63-PG13/TC 161
EXS/M63-PG16/TC 161
EXS/M63-PG21/TC 161
EXS/M63-PG29/TC 161
EXS/M63-PG36/TC 161
EXS/M63-PG42/TC 161
EXS/M63-PG48/TC 161
EXS/M63-PG9/TC 161
EXS/M75-050/TC 160
EXS/M75-075/TC 160
EXS/M75-100/TC 160
EXS/M75-125/TC 160
EXS/M75-150/TC 160
EXS/M75-200/TC 160
EXS/M75-M16/R 159
EXS/M75-M20/R 159
EXS/M75-M25/R 159
EXS/M75-M32/R 159
EXS/M75-M40/R 159
EXS/M75-M50/R 159
EXS/M75-M63/R 159
EXS/M75-PG11/TC 161
EXS/M75-PG13/TC 161
EXS/M75-PG16/TC 161
EXS/M75-PG21/TC 161
EXS/M75-PG29/TC 161
EXS/M75-PG36/TC 161
EXS/M75-PG42/TC 161
EXS/M75-PG48/TC 161
EXS/M75-PG9/TC 161
EXS/PG11/DSP 165
EXS/PG11/HSP 165
EXS/PG11/SP 163
EXS/PG11/TSP 163
EXS/PG11-050/TC 160
EXS/PG11-M16/TC 159
EXS/PG11-M20/TC 159
EXS/PG11-PG9/R 161
EXS/PG13/DSP 165
EXS/PG13/HSP 165
EXS/PG13/SP 163
EXS/PG13/TSP 163
EXS/PG13-050/TC 160
EXS/PG13-M16/TC 159
EXS/PG13-M20/TC 159
EXS/PG13-PG11/R 161
EXS/PG13-PG9/R 161
EXS/PG16/DSP 165
EXS/PG16/HSP 165
EXS/PG16/SP 163
EXS/PG16/TSP 163
EXS/PG16-050/TC 160
EXS/PG16-075/TC 160
EXS/PG16-M16/TC 159
EXS/PG16-M20/TC 159
EXS/PG16-M25/TC 159
EXS/PG16-PG11/R 161
EXS/PG16-PG13/R 161
EXS/PG16-PG21/E 161
EXS/PG16-PG9/R 161
EXS/PG21/DSP 165
EXS/PG21/HSP 165
EXS/PG21/SP 163
EXS/PG21/TSP 163
EXS/PG21-075/TC 160
EXS/PG21-100/TC 160
EXS/PG21-M16/TC 159
EXS/PG21-M20/TC 159
EXS/PG21-M25/TC 159
EXS/PG21-M32/TC 159
EXS/PG21-PG11/R 161
EXS/PG21-PG13/R 161
EXS/PG21-PG16/R 161
EXS/PG21-PG29/E 161
EXS/PG21-PG9/R 161
EXS/PG29/DSP 165
EXS/PG29/HSP 165
EXS/PG29/SP 163
EXS/PG29/TSP 163
EXS/PG29-050/TC 160
EXS/PG29-075/TC 160
EXS/PG29-100/TC 160
EXS/PG29-125/TC 160
EXS/PG29-150/TC 160
EXS/PG29-M16/TC 159
EXS/PG29-M20/TC 159
EXS/PG29-M25/TC 159
EXS/PG29-M32/TC 159
EXS/PG29-M40/TC 159
EXS/PG29-PG11/R 161
EXS/PG29-PG13/R 161
EXS/PG29-PG16/R 161
EXS/PG29-PG21/R 161
EXS/PG29-PG36/E 161
EXS/PG29-PG9/R 161
EXS/PG36/DSP 165
EXS/PG36/HSP 165
EXS/PG36/SP 163
EXS/PG36/TSP 163
EXS/PG36-050/TC 160
EXS/PG36-075/TC 160
EXS/PG36-100/TC 160
EXS/PG36-125/TC 160
EXS/PG36-150/TC 160
EXS/PG36-M16/TC 159
EXS/PG36-M20/TC 159
EXS/PG36-M25/TC 159
EXS/PG36-M32/TC 159
EXS/PG36-M40/TC 159
EXS/PG36-M50/TC 159
EXS/PG36-PG11/R 161
EXS/PG36-PG13/R 161
EXS/PG36-PG16/R 161
EXS/PG36-PG21/R 161
EXS/PG36-PG29/R 161
EXS/PG36-PG48/E 161
EXS/PG36-PG9/R 161
EXS/PG42/DSP 165
EXS/PG42/HSP 165
EXS/PG42/SP 163
EXS/PG42/TSP 163
EXS/PG42-050/TC 160
EXS/PG42-075/TC 160
EXS/PG42-100/TC 160
EXS/PG42-125/TC 160
EXS/PG42-150/TC 160
EXS/PG42-200/TC 160
EXS/PG42-M16/TC 159
EXS/PG42-M20/TC 159
EXS/PG42-M25/TC 159
EXS/PG42-M32/TC 159
EXS/PG42-M40/TC 159
EXS/PG42-M50/TC 159
EXS/PG42-M63/TC 159
EXS/PG42-PG11/R 161
EXS/PG42-PG13/R 161
EXS/PG42-PG16/R 161
EXS/PG42-PG21/R 161
EXS/PG42-PG29/R 161
EXS/PG42-PG36/R 161
EXS/PG42-PG48/E 161
EXS/PG42-PG9/R 161
EXS/PG48/DSP 165
EXS/PG48/HSP 165
EXS/PG48/SP 163
EXS/PG48/TSP 163
EXS/PG48-050/TC 160
EXS/PG48-075/TC 160
EXS/PG48-100/TC 160
EXS/PG48-125/TC 160
EXS/PG48-150/TC 160
EXS/PG48-200/TC 160
EXS/PG48-M16/TC 159
EXS/PG48-M20/TC 159
EXS/PG48-M25/TC 159
EXS/PG48-M32/TC 159
EXS/PG48-M40/TC 159
EXS/PG48-M50/TC 159
EXS/PG48-M63/TC 159
EXS/PG48-PG11/R 161
EXS/PG48-PG13/R 161
Part No. Page Part No. Page Part No. Page Part No. Page Part No. Page
Index
175
Thomas & Betts • www.tnb-hazardous.com
EXS/PG48-PG16/R 161
EXS/PG48-PG21/R 161
EXS/PG48-PG29/R 161
EXS/PG48-PG36/R 161
EXS/PG48-PG42/R 161
EXS/PG48-PG9/R 161
EXS/PG9/DSP 165
EXS/PG9/HSP 165
EXS/PG9/SP 163
EXS/PG9/TSP 163
EXS/PG9-050/TC 160
EXS/PG9-M16/TC 159
EXS/PG9-M20/TC 159
EXSB0310 143
EXSB0330 143
EXSB0410 143
EXSB0430 143
EXSB0510 143
EXSB0530 143
EXSB0610 143
EXSB0620 143
EXSB0630 143
EXSB0710 143
EXSB0720 143
EXSB0730 143
EXSB0810 143
EXSB0820 143
EXSB0910 143
EXSB0920 143
EXSH0310 143
EXSH0330 143
EXSH0410 143
EXSH0430 143
EXSH0510 143
EXSH0530 143
EXSH0610 143
EXSH0620 143
EXSH0710 143
EXSH0720 143
EXSH0810 143
EXSH0820 143
EXSH0910 143
EXSH0920 143
EXSHC0310 143
EXSHC0330 143
EXSHC0410 143
EXSHC0430 143
EXSHC0510 143
EXSHC0530 143
EXSHC0610 143
EXSHC0630 143
EXSHC0710 143
EXSHC0810 143
EXSHC0910 143
EXST0310 143
EXST0330 143
EXST0410 143
EXST0430 143
EXST0510 143
EXST0530 143
EXST0610 143
EXST0620 143
EXST0710 143
EXST0720 143
EXST0810 143
EXST0820 143
EXST0910 143
EXST0920 143
FB30-00000 83
FB70-00000 83
FF002 99
FF003 99
FF004 99
FF005 99
FF006 99
FF007 99
FF008 99
FF009 99
FF010 99
FF011 99
FF014 99
FF015 99
FF016 99
FF017 99
FF018 99
FF019 99
FF020 99
FF021 99
FF022 99
FF023 99
FF024 99
FF025 99
FF220-0G000 73
FF220EM-0G000 87
FF220VEM-0G000 87
FF236-0G000 73
FF240-0G000 73
FF240EM-0G000 87
FF240VEM-0G000 87
FF255-0G000 73
FF265-0G000 73
FL30P-00000 83
FR120-0G000 73
FR120EM-0G000 87
FR120VEM-0G000 87
FR136-0G000 73
FR140-0G000 73
FR140EM-0G000 87
FR140VEM-0G000 87
FR155-0G000 73
FR165-0G000 73
GUVC26-00000 125
GUVC36-00000 125
GUVL26-00000 125
GUVL36-00000 125
GUVT26-00000 125
GUVT36-00000 125
GUVX26-00000 125
GUVX36-00000 125
HAA0304 147
HAA0304E 145
HAA0304G1 145
HAA0304U 149
HAA0304U/SW 149
HAA0404 147
HAA0404E 145
HAA0404G1 145
HAA0404U 149
HAA0404U/SW 149
HAA0505 147
HAA0505E 145
HAA0505G1 145
HAA0505U 149
HAA0505U/SW 149
HAA0606 147
HAA0606E 145
HAA0606G1 145
HAA0606U 149
HAA0606U/SW 149
HAA0707 147
HAA0707E 145
HAA0707G1 145
HAA0707U 149
HAA0707U/SW 149
HAA0808 147
HAA0808E 145
HAA0808G1 145
HAA0808U 149
HAA0808U/SW 149
HAA0909 147
HAA0909E 145
HAA0909G1 145
HAA0909U 149
HAA0909U/SW 149
HAAM0304 147
HAAM0304E 145
HAAM0304G1 145
HAAM0304U 149
HAAM0304U/SW 149
HAAM0404 147
HAAM0404E 145
HAAM0404G1 145
HAAM0404U 149
HAAM0404U/SW 149
HAAM0505 147
HAAM0505E 145
HAAM0505G1 145
HAAM0505U 149
HAAM0505U/SW 149
HAAM0606 147
HAAM0606E 145
HAAM0606G1 145
HAAM0606U 149
HAAM0606U/SW 149
HAAM0707 147
HAAM0707E 145
HAAM0707G1 145
HAAM0707U 149
HAAM0707U/SW 149
HAAM0808 147
HAAM0808E 145
HAAM0808G1 145
HAAM0808U 149
HAAM0808U/SW 149
HAAM0909 147
HAAM0909E 145
HAAM0909G1 145
HAAM0909U 149
HAAM0909U/SW 149
HAAS0304G1 145
HAAS0304U 149
HAAS0304U/SW 149
HAAS0404 147
HAAS0404G1 145
HAAS0404U 149
HAAS0404U/SW 149
HAAS0505 147
HAAS0505G1 145
HAAS0505U 149
HAAS0505U/SW 149
HAAS0606 147
HAAS0606G1 145
HAAS0606U 149
HAAS0606U/SW 149
HAAS0707 147
HAAS0707G1 145
HAAS0707U 149
HAAS0707U/SW 149
HAAS0808 147
HAAS0808G1 145
HAAS0808U 149
HAAS0808U/SW 149
HAAS0909 147
HAAS0909G1 145
HAAS0909U 149
HAAS0909U/SW 149
HAM0304 147
HAM0304E 145
HAM0304G1 145
HAM0304U 149
HAM0304U/SW 149
HAM0404 147
HAM0404E 145
HAM0404G1 145
HAM0404U 149
HAM0404U/SW 149
HAM0505 147
HAM0505E 145
HAM0505G1 145
HAM0505U 149
HAM0505U/SW 149
HAM0606 147
HAM0606E 145
HAM0606G1 145
HAM0606U 149
HAM0606U/SW 149
HAM0707 147
HAM0707E 145
HAM0707G1 145
HAM0707U 149
Part No. Page Part No. Page Part No. Page Part No. Page Part No. Page
176
Index
Thomas & Betts • www.tnb-hazardous.com
HAM0707U/SW 149
HAM0808 147
HAM0808E 145
HAM0808G1 145
HAM0808U 149
HAM0808U/SW 149
HAM0909 147
HAM0909E 145
HAM0909G1 145
HAM0909U 149
HAM0909U/SW 149
HAMM0304 147
HAMM0304E 145
HAMM0304G1 145
HAMM0304U 149
HAMM0304U/SW 149
HAMM0404 147
HAMM0404E 145
HAMM0404G1 145
HAMM0404U 149
HAMM0404U/SW 149
HAMM0505 147
HAMM0505E 145
HAMM0505G1 145
HAMM0505U 149
HAMM0505U/SW 149
HAMM0606 147
HAMM0606E 145
HAMM0606G1 145
HAMM0606U 149
HAMM0606U/SW 149
HAMM0707 147
HAMM0707E 145
HAMM0707G1 145
HAMM0707U 149
HAMM0707U/SW 149
HAMM0808 147
HAMM0808E 145
HAMM0808G1 145
HAMM0808U 149
HAMM0808U/SW 149
HAMM0909 147
HAMM0909E 145
HAMM0909G1 145
HAMM0909U 149
HAMM0909U/SW 149
HAMS0304G1 145
HAMS0304U 149
HAMS0304U/SW 149
HAMS0404 147
HAMS0404G1 145
HAMS0404U 149
HAMS0404U/SW 149
HAMS0505 147
HAMS0505G1 145
HAMS0505U 149
HAMS0505U/SW 149
HAMS0606 147
HAMS0606G1 145
HAMS0606U 149
HAMS0606U/SW 149
HAMS0707 147
HAMS0707G1 145
HAMS0707U 149
HAMS0707U/SW 149
HAMS0808 147
HAMS0808G1 145
HAMS0808U 149
HAMS0808U/SW 149
HAMS0909 147
HAMS0909G1 145
HAMS0909U 149
HAMS0909U/SW 149
HF55P-00000 85
HF70P-00000 85
M005.1 97
M005.2 97
M005.3 97
M005.4 97
M005.5 97
P001 97
P002 97
P004 97
P006 97
P007 97
P008 97
P009 97
P010 97
P012 97
P015 97
P017 97
P018 97
P019 97
P021 97
P022 97
P023 97
P025 97
P026 97
P030 97
PA1-10 1/2” 151
PA1-13 1/2” 151
PA1-8 1/2” 151
PA1B 1/2” 155
PA1B M20 155
PA2-10 3/4” 151
PA2-13 3/4” 151
PA2-15 3/4” 151
PA2-18 3/4” 151
PA2B 3/4” 155
PA2B M25 155
PA3-18 1” 151
PA3-21 1” 151
PA3-24 1” 151
PA3B 1” 155
PA3B M32 155
PA4-24 1,1/4” 151
PA4-27 1,1/4” 151
PA4-30 1,1/4” 151
PA4B 1,1/4” 155
PA4B M40 155
PA5-33 1,1/2” 151
PA5-36 1,1/2” 151
PA5B 1, 1/ 155
PA5B M50 155
PA6-39 2” 151
PA6-42 2” 151
PA6-45 2” 151
PA6B 2” 155
PA6B M63 155
PA7-48 2,1/2” 151
PA7-51 2,1/2” 151
PA7B 2,1/2” 155
PA7B 2,1/2” 155
PA7B M75 155
PAP1-10 1/2” 151
PAP1-13 1/2” 151
PAP1-8 1/2” 151
PAP1B 1/2” 155
PAP1B M20 155
PAP2-10 3/4” 151
PAP2-13 3/4” 151
PAP2-15 3/4” 151
PAP2-18 3/4” 151
PAP2B 3/4” 155
PAP2B M25 155
PAP3-18 1” 151
PAP3-21 1” 151
PAP3-24 1” 151
PAP3B 1” 155
PAP3B M32 155
PAP4-24 1,1/4” 151
PAP4-27 1,1/4” 151
PAP4-30 1,1/4” 151
PAP4B 1,1/4” 155
PAP4B M40 155
PAP5-33 1,1/2” 151
PAP5-36 1,1/2” 151
PAP5B 1, 1/ 155
PAP5B M50 155
PAP6-39 2” 151
PAP6-42 2” 151
PAP6-45 2” 151
PAP6B 2” 155
PAP6B M63 155
PAP7-48 2,1/2” 151
PAP7-51 2,1/2” 151
PAP7B 2,1/2” 155
PAP7B M75 155
PEM20T4 153
PEM20T5 153
PEM20T6 153
PEM25T6 153
PEM25T7 153
PEM32T7 153
PEM32T8 153
PEM40T9 153
PEM50T10 153
PEM63T11 153
PEM75T12 153
PEPM20T5 153
PEPM20T6 153
PEPM20T7 153
PEPM25T7 153
PEPM25T8 153
PEPM32T8 153
PEPM32T9 153
PEPM40T10 153
PEPM50T11 153
PEPM63T12 153
PEPM75T13 153
PR01 130
PR02 130
PR03 130
PR04 130
PR05 130
PR06 130
PR07 130
PR07V 130
PRC10 130
PRC20 130
PRC30 130
PRC40 130
PRC50 130
PRC60 130
PRC70 130
QF250G-00000 77
QF250P-00000 77
QF400G-00000 77
QF400P-00000 77
REA20 130
SF150G-00000 77
SF150P-00000 77
SF250G-00000 77
SF250P-00000 77
SF400G-00000 77
SF400P-00000 77
SF70G-00000 77
SF70P-00000 77
SRC215 127
SRC215V 127
SRC330 127
SRC340 127
SRC415 127
V001 95
V002 95
V004 95
V005 95
V006 95
V006N 95
V007N 95
V008 95
V008N 95
V009 95
V012 95
V012A 95
V014 94
V015 94
V016 94
V018 94
V021 94
Part No. Page Part No. Page Part No. Page Part No. Page Part No. Page
Index
177
Thomas & Betts • www.tnb-hazardous.com
V023 94
V024 94
VAB10 130
VAC10 130
VAJ10 130
VAR10 130
VAV10 130
WHMB03 167
WHMB04 167
WHMB05 167
WHMB06 167
WHMB07 167
WHMB08 167
XB100-10BV 109
XB100-6BR 109
XB100-6BV 109
XB100A-10BV 109
XB100A-6BR 109
XB100A-6BV 109
XB10A-SI 111
XB10A-SI 111
XB10-SI 111
XB10-SI 111
XB150 121
XB215VA 119
XB21A 119
XB21FA 119
XB21VA 119
XB22A 119
XB22AMP 119
XB23A 119
XB26A 119
XB300 117
XB38A 119
XB38AMP 119
XB400 117
XB41A 119
XB43A 119
XB510 117
XB520 117
XB570 117
XB700 117
XB710 117
XB750 117
XB950 117
XB960 117
XBAMP 119
XBI100 121
XBI200 121
XBI215VA 123
XBI21A 123
XBI21FA 123
XBI21VA 123
XBI22A 123
XBI22AMP 123
XBI23A 123
XBI26A 123
XBI300 121
XBI38A 123
XBI38AMP 123
XBI400 121
XBI41A 123
XBI43A 123
XBI500 121
XBI600 121
XBIAMP 123
XBL15 113
XBL20 113
XBL215VA 115
XBL21A 115
XBL21FA 115
XBL21VA 115
XBL22A 115
XBL22AMP 115
XBL23A 115
XBL25 113
XBL26-25R 111
XBL26A 115
XBL28-25BR 111
XBL35 113
XBL38A 115
XBL38AMP 115
XBL40 113
XBL41A 115
XBL43A 115
XBL45 113
XBL55 113
XBL65 113
XBL75 113
XBLAMP 115
XDF140-00000 41
XDF165-00000 41
XEF110G-00000 37
XEF110P-00000 37
XEF140G-00000 37
XEF140P-00000 37
XEL120-0G000 33
XEL120V-0G000 33
XEL220-0G000 33
XEL220V-0G000 33
XEL3001-00000 55
XEL30011-0G000 33
XEL30011V-0G000 33
XEL3001V-00000 55
XEL3002-00000 55
XEL30028-0G000 33
XEL30028V-0G000 33
XEL3002V-00000 55
XEL3008-0G000 33
XEL3008V-0G000 33
XEL3009-0G000 33
XEL3009V-0G000 33
XEL300A-00000 55
XEL300AI-00000 55
XEL300AIV-00000 55
XEL300AK-00000 55
XEL300AKV-00000 55
XEL300AV-00000 55
XEL300SI-00000 55
XEL300SIV-00000 55
XEL80A-00000 55
XEL80AI-00000 55
XEL80AIV-00000 55
XEL80AK-00000 55
XEL80AKV-00000 55
XEL80AV-0J000 55
XEL80SI-0J000 55
XEL80SIV-0J000 55
XEP120-0G000 35
XEP120V-0G000 35
XEP220-0G000 35
XEP220V-0G000 35
XEP30011-0G000 35
XEP30011V-0G000 35
XEP30028-0G000 35
XEP30028V-0G000 35
XEP3008-0G000 35
XEP3008V-0G000 35
XEP3009-0G000 35
XEP3009V-0G000 35
XF001 99
XFB30-00000 39
XFB70-00000 39
XFF012 99
XFF013 99
XFF220-0G000 29
XFF220EM-0G000 51
XFF220V-0G000 29
XFF220VEM-0G000 51
XFF236-0G000 29
XFF236V-0G000 29
XFF240-0G000 29
XFF240EM-0G000 51
XFF240V-0G000 29
XFF240VEM-0G000 51
XFF255-0G000 29
XFF255V-0G000 29
XFF265-0G000 29
XFF265V-0G000 29
XFL30P-00000 39
XFP120-0G000 31
XFP120EM-0G000 53
XFP120V EM-0G000 53
XFP120V-0G000 31
XFP136-0G000 31
XFP136V-0G000 31
XFP140-0GG000 31
XFP140EM-0G000 53
XFP140V EM-0G000 53
XFP140V-0G000 31
XFP155-0G000 31
XFP155V-0G000 31
XFP165-0G000 31
XFP165V-0G000 31
XFP220-0G000 31
XFP220EM-0G000 53
XFP220V EM-0G000 53
XFP220V-0G000 31
XFP236-0G000 31
XFP236V-0G000 31
XFP240-0G000 31
XFP240EM-0G000 53
XFP240V EM-0G000 53
XFP240V-0G000 31
XFP255-0G0000 31
XFP255V-0G000 31
XFP265-0G000 31
XFP265V-0G000 31
XFR120-0G000 29
XFR120EM-0G000 51
XFR120V-0G000 29
XFR120VEM-0G000 51
XFR136-0G000 29
XFR136V-0G000 29
XFR140-0G000 29
XFR140EM-0G000 51
XFR140V-0G000 29
XFR140VEM-0G000 51
XFR155-0G000 29
XFR155V-0G000 29
XFR165-0G000 29
XFR165V-0G000 29
XMC36 127
XPLFL110 157
XPLFL112 157
XPLFL115 157
XPLFL118 157
XPLFL124 157
XPLFL16 157
XPLFL18 157
XPLFL212 157
XPLFL215 157
XPLFL218 157
XPLFL224 157
XPLFL236 157
XPLFL318 157
XQF250G-00000 37
XQF250P-00000 37
XQF400G-00000 37
XQF400P-00000 37
XSF150G-00000 37
XSF150P-00000 37
XSF250G-00000 37
XSF250P-00000 37
XSF400G-00000 37
XSF400P-00000 37
XSF70G-00000 37
XSF70P-00000 37
Z001 95
Part No. Page Part No. Page Part No. Page Part No. Page Part No. Page
USA & Canada
178
Thomas & Betts WorldwideIndustrial Capabilities
Thomas & Betts CorporationWorld Headquarters
8155 T&B BoulevardMemphis, TN 38125T 901.252.8000I www.tnb-europe.com
Kopex InternationalUK Head Offi ce
Station Road, Coleshill, Birmingham, B46 1HTT +44 (0) 1675 468 213F +44 (0) 1675 468 280I www.kopex-ex.com
Thomas & BettsEMEA European Centre
200 Chaussee de Waterloo B-1640 Rhode-St-GeneseBelgiumT +32 (0) 2 359 82 00F +44 (0) 2 359 82 01E [email protected]
Thomas & BettsAsia (Singapore) Pte Ltd
10 Ang Mo kio Street 65, #06-07 TechpointSingapore 569059T +65 6720 8828F +65 6720 8780E [email protected]
DTSInternational Call Centre
Z.I. Parc d’Activités de la Gare19 à 21 avenue Henri BeaudeletB.P. 27 - 77831 Ozoir Cedex FranceT +33 (0) 1 64 40 27 26F +33 (0) 1 64 40 20 11E [email protected] www.dtselec.fr
T&B Headquarters
Thomas & Betts • www.tnb-hazardous.com
Europe, Middle East, Asia
Thomas & Betts - Industrial Capabilities
Thomas & Betts • www.tnb-hazardous.com
179
Battery LED Signals SATI
IP 54 IP 56 IP 64 IP 66 IP 67
Healthy(test OK)
Emergency orIndicator
Lamp Fault(must bereplaced)
Test inProgress
(waiting end of test)
Fault(replacebattery)
Healthy Emergency orIndicator
Lamp Fault
Test inProgress
Fault
Thomas & Betts • www.tnb-hazardous.com
Key of Symbols
DTS & Kopex Ex Symbols
Key of Symbols
Market Segments
Product Characteristics
Group I Group II Class I Class II Division 1 Division 2 IK 09 IK 10
Utilities /Power
Food &Beverage
Marine &Shipbuilding
Onshore &Offshore
Chemical &Pharmaceutical
Mining
Ex e Ex d Ex n Ex de Ex tb Ex tDEx t Ex tc
Zone 0 Zone 1 Zone 2 Zone 20 Zone 21 Zone 22
Gas IIB Gas IIC Dust IIIC Dust A21
67665654 64
Ex nA Ex ia Ex eia
180
The content of the Thomas & Betts catalogue has been carefully checked for accuracy at the time of print. However, Thomas & Betts doesn’t give any warranty of any kind, express or implied, in this respect and shall not be liable for any loss or damage that may result from any use or as a consequence of any inaccuracies in or any omissions from the information which it may contain.
Copyright Thomas & Betts 2011. Copyright in these pages is owned by Thomas & Betts except where otherwise indicated. No part of this publication may be reproduced, copied or transmitted in any form or by any means, without our prior written permission. Images, trade marks, brands, designs and technology are also protected by other intellectual prop-erty rights and may not be reproduced or appropriated in any manner without written permission of their respective owners. Thomas & Betts reserves the right to change and improve any product specifi cations or other mentions in the catalogue at its own discretion and at any time. These conditions of use are governed by the laws of the Netherlands and the courts of Amsterdam shall have exclusive jurisdiction in any dispute.
Thomas and Betts manufacture and design a wide range of electrical equipment for hazardousand hostile environments to ensure the safety of the personnel working in them. The extensive range covers Kopex-Ex metallic and non metallic conduit and fi ttings and the DTS range of lighting junction and control boxes. These products are approved to a wide range of hazardous area standards including ATEX, IECEx, UL, CSA, GOST and Inmetro.
DTSThomas & Betts Sales Offi ce
19/21 Avenue Henri BeaudeletBP2777330 Ozoir la FerrièreFranceT +33 (0) 1 64 40 27 26E [email protected]
Kopex InternationalThomas & Betts Sales Offi ce
Station Road, Coleshill Birmingham, B46 1HTT +44 (0) 1675 468 213E [email protected]
Thomas & BettsEuropean Head Offi ce
Benelux BVBAWaterloose Steenweg 200B-1640 Sint-Genesius-RodeBelgiumT +32 (0) 56 78 35 35E [email protected]
LIT-
140G
BR 0
6/12