Carrier 42 Cet FCU
-
Upload
cantorband8234 -
Category
Documents
-
view
340 -
download
19
Transcript of Carrier 42 Cet FCU
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 1/21
MAXIMIZING PERFORMANCE,
ENERGY
SAVINGS
&
COMFORT
42C/D SERIES
Ducted Chilled Water Fan Coil Unit
With District Cooling Application(200 to 2000 CFM)
42DF
42DE
42CG
42DC
42CE
Turn to the Experts
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 2/21
2
MODEL NUMBER NOMENCLATURE
TABLE OF CONTENTSPage
Model Number Nomenclature……………………………………………………………………………………..……... 2 ‐ 3
Product Features………………………………………………………………………………………………………………………. 4
Technical Data………………………………………………………………………………………………………………….…. 5 – 9
Unit Dimension and Weight……………………………………………………………………………………………...10 – 14
Performance Rating…………………………………………………………………………………………………………..15 – 17
Electrical
Data………………………………………………………………………………………………………………………… 18Wiring Diagram……………………………………………………………………………………………………………………….. 19
Guide Specifications………………………………………………………………………………………………………………… 20
COMPUTER SELECTION
We have made available a computer program to finalize your selections.
Please
contact
your
Carrier
representative
for
a
computer
selection
based
on
your “Quick Selection” plus the design parameters of your application.
4 2 C E T 0 0 3 4 ‐ ‐ 7 0 1 2 5
42 series CISB Code
Fan Coil Unit 25
Model Packing method
CET 1
DC‐
CED ∆T District Development Series
DCD Cooling 0 : 42CET / 42CED
3 : 42DC / 42DCD
Model No.
42CET & CED 42DC & DCD Electrical Characteristic
003 010 7 ‐ 220/240V‐1PH‐50Hz
004 012
005 014
006 016
008 018010 020
012 3 : 3 row coil (42CET)
014 4 : 4 row coil (42CET, CED, DC, DCD)
Std
R : Right Handling
‐ : Left Handling
Not used
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 3/21
3
MODEL NUMBER NOMENCLATURE (cont’)
4 2 D E ‐
0 6 ‐
4 R L 7 2 1 2 5
42 series CISB Code
Fan Coil Unit 25
Packing method
Model 1
CG‐
DE‐
DF‐ Development Series
2 : 42CG, DE/DF
Model No.
42CG 42DE/DF Electrical Characteristic
02 06 7 ‐ 220/240V‐1PH‐50Hz
03 08
04 10
06 12
08 14 4 : 4 row coil (42CG, 42DE, DF)
10 16 6 : 6 row coil (42DE, 42DF)
12 18
20 ‐ : Not used
RR : Right Handling
RL : Left Handling
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 4/21
4
PRODUCT FEATURES
If fan coil terminals are the answer to your job requirements, you can’t afford to pass
over Carrier’s
versatile
and
extensive
range
of
fan
coil
units.
With Carrier’s 42 series fan coil units, you can select furred‐in or cabinet style, in capacities from 200 to
2,000 cfm. Units are ideal for installations in residential, hotels, motels, apartments, offices, hospitals,
schools and other multi‐room buildings.
Carrier room fan coil terminals provide unsurpassed year round comfort, with high cooling performance.
Carrier 42 series terminal requires very little space and is easy to install. Piping, drain and wiring
connections are readily accessible to save installation time and field labor expense.
Forget about expensive ductwork, forget about complex system controls, forget the aggravation and choose
Carrier’s easy to install room fan coil units – in pipe systems. Opt for quiet. Carrier room fan coil units
operate at exceptionally low sound levels. Generous amount of insulation absorbs operating sound and
rugged, rigid construction ensures vibration free operation at all fan speeds.
Carrier room fan coil units are economical. Three speed fans deliver just the right amount of conditioned air
for your comfort needs at any load. And each individual unit can be shut off when not in use. Shaded‐pole
motors deliver peak operating efficiency. In choosing Carrier units, you can match your application with a
wide range of custom‐designed options and accessories.
When you go for Carrier 42 series, the advantages to owner, installer and the room occupants are too great
to ignore.
Carrier 42
series
fan
coils
give
you
design
and
equipment location flexibility• Wide range of popular capacities, 200 – 2000 cfm
• Available up to 8 sizes.
• Cabinet or furred‐in units
• Choose from numerous control systems
• Select 3 row coils (42CE), 4 row coils (42CE & DC) and
6 row coils (42DE & DF)
• Accommodates 2 pipe systems
• Fully insulated/low fan speed means quiet operation
• Draw outside air for odor dilution
• Uses only
minimal
space
Select Carrier fan coils for easy, low cost
installation• Easy wiring, piping connections
• Mounting holes, slots speed hanging
• Requires no expensive ductwork
• Ideal for new construction or renovation
Save operating
costs
with
Carrier
fan
coils
• Individual unit shut‐off when not in use
• Efficient, 3 speed centrifugal fans
• Shaded pole motors
• High efficiency heat transfer surface
Carrier fan coils save you service and
maintenance expense• Nationwide Carrier service
• Insulated drain pan
• Easy access to components
• Rugged construction
• Factory leak test for coil
• Cleanable filters
• Long life, heavy duty bearings
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 5/21
5
TECHNICAL DATA
42CET Furred‐in Ceiling FCU with Plenum
3 Rows
at
nominal
CFM
MODEL: 42CETPERFORMANCE
49.942.837.734.125.523.221.918.8KgNet Weight
¾” MPTCondensate Drain
¾” FPTIn‐OutConnections
1.72MPaWorking Pressure
3RowCoil
Permanent Split
CapacitorMotor
Type
Centrifugal Forward‐curved bladesFan Type
23.714.931.923.623.814.811.922.5kPaWater Drop
0.4710.3830.3310.2870.2060.1630.1500.120L/sWater Flow
40.140.839.836.237.836.134.733.4Low
41.742.741.539.340.036.738.236.0Med
44.943.743.941.841.241.340.039.0
dB(A)
High
Noise *
2.041.301.101.020.650.550.440.37AmpMotor nominal current78w
x
375w
x
268w
x
258w
x
275684835WMotor
nominal
power
output
373613036726307227921634312966118749519Btu/hr
10.958.907.716.684.793.803.482.79kWCooling Capacity (Fluid)*
661566472378283236189142L/s
140012001000800600500400300CFMHigh
Nominal
Air Volume
014012010008006005004003
NOTE:
* Based on motor at high speed, standard air and dry coil operation; 8.9˚C water temperature rise; entering air
temperature 24.4˚C DB; 17.2˚C WB; Entering water temperature 5.5˚C.
** Sound measurement
in
accordance
with
Standard
JIS8616
‐2006
(1.5m
below
the
unit
bottom).
Performance AssuranceRated in accordance with
ARI Standard 440‐1998
(50Hz only)
‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 6/21
6
TECHNICAL DATA (cont’)
42CET Furred‐in Ceiling FCU with Plenum
4 Rows
at
nominal
CFM
MODEL: 42CETPERFORMANCE
52.445.139.735.926.524.523.119.9KgNet Weight
¾” MPTCondensate Drain
¾” FPTIn‐OutConnections
1.72 MPaWorking Pressure
4RowCoil
Permanent Split
CapacitorMotor
Type
Centrifugal Forward‐curved bladesFan Type
37.323.825.317.97.422.218.19.8kPaWater Drop
0.5510.4540.3650.3120.2090.1830.1680.124L/sWater Flow
40.140.839.836.237.836.134.733.4Low
41.742.741.539.340.036.738.236.0Med
44.943.743.941.841.241.340.039.0
dB(A)
High
Noise *
2.041.301.101.020.650.550.440.37AmpMotor nominal current78w
x
375w
x
268w
x
258w
x
275684835WMotor
nominal
power
output
437083596228797247371661614603134779792Btu/hr
12.8110.548.447.254.874.283.952.87kWCooling Capacity (Fluid)*
661566472378283236189142L/s
140012001000800600500400300CFMHigh
Nominal
Air Volume
014012010008006005004003
NOTE:
* Based on motor at high speed, standard air and dry coil operation; 8.9˚C water temperature rise; entering air
temperature 24.4˚C DB; 17.2˚C WB; Entering water temperature 5.5˚C.
** Sound measurement
in
accordance
with
Standard
JIS8616
‐2006
(1.5m
below
the
unit
bottom).
Performance AssuranceRated in accordance with
ARI Standard 440‐1998
(50Hz only)
‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 7/21
7
TECHNICAL DATA (cont’)
42CED Furred‐in Ceiling FCU with Plenum (District Cooling Application)
4 Rows
at
nominal
CFM
MODEL: 42CEDPERFORMANCE
52.445.139.735.926.524.523.119.9KgNet Weight
¾” MPTCondensate Drain
¾” FPTIn‐OutConnections
1.72MPaWorking Pressure
4RowCoil
Permanent Split
CapacitorMotor
Type
Centrifugal Forward‐curved bladesFan Type
15.223.313.520.27.722.718.58.8kPaWater Drop
0.2450.2330.1750.1510.0970.0950.0860.060L/sWater Flow
40.140.839.836.237.836.134.733.4Low
41.742.741.539.340.036.738.236.0Med
44.943.743.941.841.241.340.039.0
dB(A)
High
Noise *
2.041.301.101.020.650.550.440.37AmpMotor nominal current78w
x
375w
x
268w
x
258w
x
275684835WMotor
nominal
power
output
310492821722178192101231712044109877609Btu/hr
9.108.276.505.633.613.533.222.23kWCooling Capacity (Fluid)*
661566472378283236189142L/s
140012001000800600500400300CFMHigh
Nominal
Air Volume
014012010008006005004003
NOTE:
* Based on motor at high speed, standard air and dry coil operation; 8.9˚C water temperature rise; entering air
temperature 24.4˚C DB; 17.2˚C WB; Entering water temperature 5.5˚C.
** Sound measurement
in
accordance
with
Standard
JIS8616
‐2006
(1.5m
below
the
unit
bottom).
Performance AssuranceRated in accordance with
ARI Standard 440‐1998
(50Hz only)
‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 8/21
8
TECHNICAL DATA (cont’)
42DC Furred‐in Ceiling FCU with Plenum
4 Rows
at
nominal
CFM
1 1/8”1 1/8”1 1/8”1 1/8”7/8”7/8”In‐Out (Sweat conn.)Connections
7/8”Condensate Drain
MODEL: 42DCPERFORMANCE
1008881797666KgNet Weight
1.72 MPaWorking Pressure
4RowCoil
Permanent Split
CapacitorMotor
Type
Centrifugal Forward‐curved bladesFan Type
30.825.250.529.841.523.8kPaWater Drop
0.80.80.80.60.50.4L/sWater Flow
45.245.347.641.042.440.6Low
49.449.552.844.844.545.5Med
52.151.854.347.647.647.6
dB(A)
High
Noise *
2.39x22.39x22.39x21.15x21.15x22.39AmpMotor nominal current
200x2200x2200x2120x2120x2200WMotor nominal power output
661966107760054467464196931733Btu/hr
19.417.917.613.712.39.3kWCooling Capacity (Fluid)*
943852755661566472L/s
200018001600140012001000CFMHigh
Nominal
Air Volume
020018016014012010
NOTE:
* Based on motor at high speed, standard air and dry coil operation; 8.9˚C water temperature rise; entering air
temperature 24.4˚C DB; 17.2˚C WB; Entering water temperature 5.5˚C.
** Sound measurement
in
accordance
with
Standard
JIS8616
‐2006
(1.5m
below
the
unit
bottom).
Performance AssuranceRated in accordance with
ARI Standard 440‐1998
(50Hz only)
‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 9/21
9
TECHNICAL DATA (cont’)
42DCD Furred‐in Ceiling FCU with Plenum (District Cooling Application)
4 Rows
at
nominal
CFM
1 1/8”1 1/8”1 1/8”1 1/8”7/8”7/8”In‐Out (Sweat conn.)Connections
7/8”Condensate Drain
MODEL: 42DCDPERFORMANCE
1008881797666KgNet Weight
1.72 MPaWorking Pressure
4RowCoil
Permanent Split
CapacitorMotor
Type
Centrifugal Forward‐curved bladesFan Type
30.825.250.529.841.523.8kPaWater Drop
0.80.80.80.60.50.4L/sWater Flow
45.245.347.641.042.440.6Low
49.449.552.844.844.545.5Med
52.151.854.347.647.647.6
dB(A)
High
Noise *
2.39x22.39x22.39x21.15x21.15x22.39AmpMotor nominal current
200x2200x2200x2120x2120x2200WMotor nominal power output
661966107760054467464196931733Btu/hr
19.417.917.613.712.39.3kWCooling Capacity (Fluid)*
943852755661566472L/s
200018001600140012001000CFMHigh
Nominal
Air Volume
020018016014012010
NOTE:
* Based on motor at high speed, standard air and dry coil operation; 8.9˚C water temperature rise; entering air
temperature 24.4˚C DB; 17.2˚C WB; Entering water temperature 5.5˚C.
** Sound measurement
in
accordance
with
Standard
JIS8616
‐2006
(1.5m
below
the
unit
bottom).
Performance AssuranceRated in accordance with
ARI Standard 440‐1998
(50Hz only)
‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 10/21
10
UNIT DIMENSIONS AND WEIGHT
42CET/CED Furred
‐in
Ceiling
FCU
with
Plenum
52.449.9184020101876014
45.142.8160017701636012
39.737.7136015301396010
35.934.1124014101276008
26.525.59201090956006
24.523.2800970836005
23.121.9720890756004
19.918.8600770636003
4 Rows3 RowsCBA
WEIGHT (kg)DIMENSIONS
(mm)MODEL
42CET/CED
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 11/21
11
UNIT DIMENSIONS AND WEIGHT (cont’)
42CG Furred‐in Ceiling FCU with Plenum
11130517115715462681546208312
9730517116713242781324188010
80305171155991267991152408
76305171122879233879134606
57279146114768281657121904
5427914694657260546106703
442791469854626543596502
GFEDCBA
WEIGHT
(kg)
DIMENSIONS (mm)UNIT SIZE
42CG
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 12/21
12
UNIT DIMENSIONS AND WEIGHT (cont’)
42DC/DCD Furred
‐in
ceiling
FCU
with
Plenum
100147913721270121911941422020
88137812701168117810921321018
811251114310419919651194016
79112410169148648381067014
76997889787737711940012
68870762660610584813010
FEDCBAWEIGHT (kg)
DIMENSION (mm)UNIT SIZE
42DC/DCD
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 13/21
13
UNIT DIMENSIONS AND WEIGHT (cont’)
42DE Furred
‐in
ceiling
FCU
with
Plenum
110203121912192031219162620
105203111811182031118152418
98203991991203991139716
90203837837203837127014
83203737737203737114312
75203610610203610101610
7020350850820350891408
6120338138120338178706
FEDCBAWEIGHT
(kg)DIMENSIONS
(mm)UNIT SIZE
42DE
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 14/21
14
UNIT DIMENSIONS AND WEIGHT (cont’)
42DF Furred
‐in
ceiling
FCU
with
Plenum
117203121912192221181162620
113203111811182221078152418
104216991991222953139716
98203864864222826127014
90216737737222699114312
80203610610222572101610
7620350850822247091408
7121635638122234378706
FEDCBAWEIGHT
(kg)DIMENSIONS
(mm)UNIT SIZE
42DF
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 15/21
15
PERFORMANCE RATING
42CET (3‐ROWS)
42CET (4‐ROWS)
10.40.13512.914.12.363.13150Medium
14.80.16313.514.92.943.80199
50
High
005
4.80.08812.413.31.532.0591Low
8.30.12013.314.52.182.83142Medium
11.90.15013.915.42.773.48194
50
High
004
9.80.07011.812.71.251.7372Low
16.30.10012.713.81.742.33108Medium
22.50.12013.314.62.142.79141
50
High
003
31.90.33113.615.25.897.71408
50
High
010
11.00.18912.413.53.224.39194Low
19.00.25513.214.64.485.94295Medium23.60.28713.615.15.146.68352
50High
008
13.70.15012.613.82.573.48159Low
18.90.18113.114.53.184.22208Medium
23.80.20613.515.03.684.79251
50
High
006
6.00.09912.213.11.702.30100Low
13.60.34013.014.35.977.99385Low
17.20.39113.314.86.919.10464Medium
23.70.47113.915.68.5310.95610
50
High
014
9.30.29213.214.55.156.79336Low
12.30.34213.615.16.147.95422Medium
14.90.38313.915.66.998.90500
50
High
012
15.20.22012.513.73.745.11230Low
22.10.27013.014.44.666.27302Medium
WBDBSensibleTotal
Water
Pressure
(kPa)
Water Flow
(L/s)
Air off FCU
(°C)
Capacity
(kW)Air Flow
(L/s)
ESP
Pa
SpeedModel
42CET
16.4400.07910.811.42.182.92143Medium
22.7170.09511.412.22.693.53188
50
High
005
7.2930.05110.410.81.411.9188Low
12.7040.07111.211.81.992.62135Medium
18.5320.08611.8312.72.523.22183
50
High
004
2.5110.03710.911.21.071.3969Low
6.5460.05011.612.21.471.87103Medium
8.7880.06012.112.91.802.23133
50
High
003
13.4510.17512.113.05.166.50385
50
High
010
9.7440.10011.011.82.763.73187Low
16.6490.13511.712.73.835.03281Medium
20.1760.15112.013.24.365.63332
50
High
008
4.4840.07111.912.72.092.64153Low
6.1870.08612.313.32.563.19198Medium
7.7420.09712.613.72.953.61237
50
High
006
9.2960.05810.110.51.572.1596Low
8.6680.18011.712.65.126.69370Low10.8500.20412.013.05.897.59442Medium
15.2140.24512.413.67.239.10576
50
High
014
14.5570.17111.111.84.786.35323Low
18.7710.19911.512.45.687.41402Medium
23.2850.22311.812.86.438.27472
50
High
012
6.7250.11711.111.73.314.34221Low
9.5650.14311.512.24.115.31287Medium
WBDBSensibleTotal
Water
Pressure
(kPa)
Water Flow
(L/s)
Air off FCU
(°C)
Capacity
(kW)Air Flow
(L/s)
ESP
(Pa)Speed
Model
42CET
NOTE: Air Conditions: EDB/EWB 27/19°C Water Conditions: EWT/LWT 7.2/12.8˚C ∆T: 5.6˚C
NOTE: Air Conditions: EDB/EWB 27/19°C Water Conditions: EWT/LWT 7.2/12.8˚C ∆T: 5.6˚C
‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 16/21
16
PERFORMANCE RATING (cont’)
16.4400.07910.811.42.182.92143Medium
22.7170.09511.412.22.693.53188
50
High
005
7.2930.05110.410.81.411.9188Low
12.7040.07111.211.81.992.62135Medium
18.5320.08611.8312.72.523.22183
50
High
004
2.5110.03710.911.21.071.3969Low
6.5460.05011.612.21.471.87103Medium
8.7880.06012.112.91.802.23133
50
High
003
13.4510.17512.113.05.166.5385
50
High
010
9.7440.10011.011.82.763.73187Low
16.6490.13511.712.73.835.03281Medium
20.1760.15112.013.24.365.63332
50
High
008
4.4840.07111.912.72.092.64153Low
6.1870.08612.313.32.563.19198Medium
7.7420.09712.613.72.953.61237
50
High
006
9.2960.05810.110.51.572.1596Low
8.6680.18011.712.65.126.69370Low
10.8500.20412.013.05.897.59442Medium
15.2140.24512.413.67.239.10576
50
High
014
14.5570.17111.111.84.786.35323Low
18.7710.19911.512.45.687.41402Medium
23.2850.22311.812.86.438.27472
50
High
012
6.7250.11711.111.73.314.34221Low
9.5650.14311.512.24.115.31287Medium
WBDBSensibleTotal
Water
Pressure(kPa)
Water Flow
(L/s)
Air off FCU
(°C)
Capacity
(kW)Air Flow
(L/s)
ESP
PaSpeedModel
42CED
42CED (4‐ROWS) – District Cooling Application
NOTE: Air Conditions: EDB/EWB 23.9/17.2°C Water Conditions: EWT/LWT 5.5/14.4˚C ∆T: 8.9˚C
‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 17/21
17
PERFORMANCE RATING (cont’)
42DC (4‐ROWS)
42DCD (4‐ROWS) – District Cooling Applications
NOTE: Air Conditions: EDB/EWB 27/19°C Water Conditions: EWT/LWT 7.2/12.8˚C ∆T: 5.6˚C
NOTE: Air
Conditions:
EDB/EWB
23.9/17.2°C Water
Conditions:
EWT/LWT
5.5/14.4˚C ∆
T:
8.9˚C
22.7770.50612.513.58.811.8531Medium
29.7710.58913.114.210.513.7671
50
High
014
21.8800.36611.912.66.28.5352Low
32.9990.46412.713.78.110.8500Medium
41.4580.52913.214.49.512.3613
50
High
012
12.3750.28112.012.84.86.5277Low
19.8770.36212.913.96.48.4401Medium
23.7630.40213.314.47.39.3470
50
High
010
30.8470.83613.114.214.919.4947
50
High
020
14.4070.56412.112.99.713.1563Low
20.9830.69812.913.912.416.2772Medium
25.1680.77213.314.413.917.9901
50
High
018
28.7850.55812.213.19.613.0560Low
42.3550.68813.014.012.216.0767Medium
50.4850.75813.314.613.617.6894
50
High
016
15.3940.40911.812.56.99.5392Low
17.0380.59811.812.610.113.9575Low
24.7790.74312.613.613.017.3790Medium
WBDBSensibleTotal
Water
Pressure
(kPa)
Water Flow
(L/s)
Air off FCU
(°C)
Capacity
(kW)Air Flow
(L/s)
ESP
PaSpeed
Model
42DC
17.7550.23612.213.07.18.8531Medium
23.3750.27512.613.68.410.2671
50
High
014
8.2800.16012.012.74.86.0352Low
12.5240.20312.713.66.37.6500Medium
16.0210.23213.014.17.38.6613
50
High
012
24.6600.14111.312.04.05.3277Low
39.2470.18212.013.05.46.8422Medium
46.9580.20312.413.46.17.5470
50
High
010
34.7030.40812.313.412.215.2947
50
High
020
28.6950.28411.412.28.110.6563Low
41.8170.35212.013.010.313.1772Medium
49.7380.38912.313.411.614.5901
50
High
018
23.9430.26811.812.67.79.9559Low
34.5840.33012.413.49.912.3767Medium
41.1600.36312.713.811.013.5894
50
High
016
12.1360.19111.612.35.67.1391Low
18.9510.29111.412.18.310.8575Low
28.1870.36212.012.910.613.5790Medium
WBDBSensibleTotal
Water
Pressure
(kPa)
Water Flow
(L/s)
Air off FCU
(°C)
Capacity
(kW)Air Flow
(L/s)
ESP
PaSpeed
Model
42DCD
‐ ‐ For other design conditions, please apply the selection program to finalize your applications ‐ ‐
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 18/21
18
ELECTRICAL DATA
NOTE:
1.) Total motor amps and watts shown for units with 2 motors (size 10 and 12)
2.) Motor name plate amps may vary.
42CG MOTOR DATA
NOTE:
1.) Total motor amps and watts shown for units with 2 motors (size 12 to 20)
2.) Motor name
plate
amps
may
vary.
220/240‐1‐50V‐Ph‐HzPower Supply
1.551.180.800.690.560.420.42AmpMotor nominal current
2802481521501188787WattsMotor nominal power output
56647237828318914294ℓ/s
12001000800600400300200CFMHighNominal Air Volume
12100806040302
MODEL: 42CGPERFORMANCE
4.504.504.352.402.202.401.501.23AmpMotor nominal current
950960920490445500295250WattsMotor nominal power output
220/240‐1‐50V‐Ph‐HzPower Supply
943850755661566472378283ℓ/s
200018001600140012001000800600CFMHighNominal Air Volume
2018161412100806
MODEL: 42DE, DFPERFORMANCE
42DE, DF MOTOR DATA
220/240‐1‐50V‐Ph‐HzPower Supply
MODEL: 42CED/CET
PERFORMANCE
2.041.301.101.020.650.550.440.37AmpMotor nominal current
78w x 375w x 268w x 258w x 275684835WMotor nominal power output
661566472378283236189142L/s
140012001000800600500400300CFMHigh
Nominal
Air Volume
014012010008006005004003
42CED/CET MOTOR DATA
220/240‐1‐50V‐Ph‐HzPower Supply
MODEL: 42DC/DCDPERFORMANCE
2.39x22.39x22.39x21.15x21.15x22.39AmpMotor nominal current
200x2200x2200x2120x2120x2200WMotor nominal power output
943852755661566472L/s
200018001600140012001000CFMHigh
Nominal
Air Volume
020018016014012010
42DC/DCD MOTOR DATA
NOTE: Motor name plate amps may vary.
NOTE: Motor name plate amps may vary.
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 19/21
19
WIRING DIAGRAM
42CET/CED Wiring Diagram
42DC/DCD Wiring Diagram
NOTE: 1. CAUTION – DISCONNECT POWER BEFORE SERVICING.
2. USE 14 AWG, 75˚C MIN, COPPER CONDUCTOR.
3. MOTOR(S) THERMALLY PROTECTED.
4. PROVIDE DISCONNECT MEANS & OVERCURRENT PROTECTION AS REQUIRED.
5. 002 TO 006 ARE SINGLE MOTOR; 008 TO 012 ARE DOUBLE MOTORS & 014 IS THREE FAN MOTORS.
6. SNAP APART CAREFULLY AT HINGLE TO SEPARATE COVER FROM THE CONTROL BOX.
NOTE: 1. CAUTION – DISCONNECT POWER BEFORE SERVICING.
2. USE 14 AWG, 75˚C MIN, COPPER CONDUCTOR.
3. MOTOR(S) THERMALLY
PROTECTED.
4. PROVIDE DISCONNECT MEANS & OVERCURRENT PROTECTION AS REQUIRED.
5. UNIT 42DC012 AND ABOVE HAVE 2 FAN MOTORS.
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 20/21
20
GUIDE SPECIFICATIONS
HVAC Guide Specifications
Size range: 200 to 1400 Nominal Cfm
Part 1 – GENERAL
1.1 System Description
Horizontal, room fan coil unit with furred‐in,
above ceiling for ducting, or with cabinet for
exposed ceiling installations.
1.2 Quality Assurance
Unit shall be tested in accordance with ARI
Standard 440. Each coil shall be factory tested
for
leakage
at
400
psig
air
pressure
with
coil
submerge in water, insulation and adhesive
shall meet NFPA‐90A requirements for flame
spread and smoke generation. All equipment
wiring shall comply with NEC requirements.
Factory is ISO‐9001 certified.
1.3 Delivery storage and handling
Each unit shall be individually packaged from
point of manufacture. Unit shall be handled
and stored in accordance with the
manufacturer’s instructions.
Part 2 ‐ PRODUCTS
Equipment2.1 General
Factory assembled, horizontal, blow‐thru type
fan coil for furred‐in, exposed ceiling or ducted
installations. Unit shall be complete with water
coil(s), fan(s), motor(s), drain pan, filters and all
required wiring, collars for ducted units.
2.2 42CET, CED Furred‐in Units
Base 42CET, CED unit with factory installed
plenum section and cleanable filter as shown
on equipment drawings. The plenum shall be
rear air return. Shall enclose the fan/motor
assemblies, and shall be lined with PU
insulation 18kg/m³ density. Unit shall have a
removable panel to provide access to
fan/motor assemblies and unit identification
label.
2.3 Fans
Direct driven, double width fan wheels with
forward
curved
blades
shall
be
statically
and
dynamically balanced. Scrolls shall be
constructed of galvanized steel. Fan wheels
shall be constructed of galvanized steel.
2.4 Coils
Drain pan covers entire length & width of coil
till the headers.
Standard base unit shall be equipped with a 3‐
row, 4‐row or 6‐row coil for installation in a 2‐
pipe system. Coils shall have 3/8‐in (or ½”)
copper
tubes,
aluminium fins
bonded
to
the
tubes by mechanical expansion. Each coil shall
have a manual air vent and threaded or sweat
connections field piping.
2.5 Operating Characteristics
A one coil unit installed in a 2‐pipe system shall
be capable of providing cooling as determined
by the operating mode of the central water
supply system.
2.6 Electrical Requirements
Standard unit shall operate on 220/240v, single
phase, 50Hz electric power. All internal wiring
shall be in flexible conduit.
2.7 Motor(s)
Fan motors shall be 3‐speed, 220/240v, single
phase, 50Hz, permanent split capacitor type,
with sleeve type bearings and oversized oil
reservoirs to ensure lubrication.
The fan motor(s) shall be equipped with
integral automatic temperature reset for motor
protection.
7/26/2019 Carrier 42 Cet FCU
http://slidepdf.com/reader/full/carrier-42-cet-fcu 21/21
Manufacturer reserves the right to discontinue, or change at anytime, specifications or designs without notice and without incurring obligations.
42CD‐H08‐1PD
Carrier International Sdn Bhd, Malaysia
Turn to the Experts
As the world leader in heating, ventilation and air conditioning, Carrier is committed to continually improving the
quality of comfort we provide to our customers. But our level of responsibility extends well beyond…
Carrier Corporation has identified six specific areas which directly impact how we, as a world manufacturer,
balance our customers’ needs for comfort with the environment’s needs for responsible consumption.
These symbols graphically represent our six areas of concentration and will serve as visual reminders of the
importance of managing our finite resources.
Each of us at Carrier Corporation believes that, for generations to come, success will not only be measured by the
quality of our products and systems, but also by how we have improved the quality of life.