IRAN – SOUTH PARS GAS FIELD PHASES 4 & 5 DOC. N. 2017 31 000 E CA HD 70004 PLANT : ONSHORE FACILITIES DOC. N. NC 2017 999 1630 004 Page 1 of 11 This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited. Agip Iran GROUP CABLE SIZING CALCULATION 2 Issue of Approved Final Document J.W.SON T.B.KIM H.M.CHANG 07-08-03 1 Approved For Design J.W.SON T.B.KIM H.M.CHANG 20-12-02 0 Issued for Design J.W.SON T.B.KIM H.M.CHANG 30-07-02 REV. DESCRIPTION BY CHKD APPR DATE

description

SIIZING CABLE

Transcript of CABLE-SIZING

Page 1: CABLE-SIZING

IRAN – SOUTH PARS GAS FIELDPHASES 4 & 5

DOC. N.2017 31 000 E CA HD 70004 PLANT :

ONSHORE FACILITIES

DOC. N.

NC 2017 999 1630 004

Page 1 of 11

This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.

AgipIran

GROUP

CABLE SIZING CALCULATION

2 Issue of Approved Final Document J.W.SON T.B.KIM H.M.CHANG 07-08-03

1 Approved For Design J.W.SON T.B.KIM H.M.CHANG 20-12-02

0 Issued for Design J.W.SON T.B.KIM H.M.CHANG 30-07-02

REV. DESCRIPTION BY CHKD APPR DATE

Page 2: CABLE-SIZING

IRAN - South Pars Gas Field - Phase 4 & 5 Doc. N. NC 2017 120 1630 004 Rev. 2

Page 2 of 11

This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.

TABULAITON OF REVISED PAGES

PAGE Rev.0 Rev.1 Rev.2 PAGE Rev.0 Rev.1 Rev.2

1 X2 X3 X4 X5 X X6 X7 X X8 X 9 X10 X11 X

Page 3: CABLE-SIZING

IRAN - South Pars Gas Field - Phase 4 & 5 Doc. N. NC 2017 120 1630 004 Rev. 2

Page 3 of 11

This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.

CONTENTS

Pages

1. PURPOSE ..................................................................................4

2. STANDARDS AND CODES .......................................................4

3. GENERAL ELECTRICAL DATA ................................................4

4. BASIS OF CALCULATIONS ......................................................6

5. CABLE SIZING CHARTS...........................................................11

Page 4: CABLE-SIZING

IRAN - South Pars Gas Field - Phase 4 & 5 Doc. N. NC 2017 120 1630 004 Rev. 2

Page 4 of 11

This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.

1. PURPOSE

The purpose of this calculation is to verify the cable size selected considering load

current, steady state voltage drop limitation, short circuit current and motor starting

voltage drop limitation for THE SOUTH PARS FIELD DEVELOPMENT PHASES 4&5

ONSHORE FACILITIES PROJECT at ASSALUYEN, IRAN.

2. STANDARDS AND CODES

IEC 183 Guide to the selection of high voltage cables

IEC 287 Calculations of the continuous current rating of cables

IEC 364-5-523 Electrical installation in buildings

– Current-carrying capacities

RP 2017 999 1630 007 Electrical design criteria

RP 2017 999 1630 029 Electrical cables

3. GENERAL ELECTRICAL DATA

3.1 Electrical system voltages

33kV, 50 Hz, 3 phase, neutral earthed by zig-zag transformer

11kV, 50 Hz, 3 phase, neutral resistance earthed

6kV, 50 Hz, 3 phase, neutral resistance earthed

400V, 50 Hz, 3 phase, solidly earthed

230V, 50 Hz, 1 phase, solidly earthed (lighting system)

230V, 50 Hz, 1 phase, isolated from earth (UPS system)

48 VDC, unearthed

3.2 Earthing fault protection : Yes

3.3 Voltage drop : Refer section 4.4.

Page 5: CABLE-SIZING

IRAN - South Pars Gas Field - Phase 4 & 5 Doc. N. NC 2017 120 1630 004 Rev. 2

Page 5 of 11

This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.

3.4 Cables in parallel

Where two or more cables are connected in parallel in the same phase or pole of the

system, measures shall be taken to ensure that the load current is shared equally

between them.

3.5 Cable type

3.5.1 Insulation for power cables shall be:

Cross-linked polyethylene(XLPE) or ethylene propylene rubber(EPR) for HV and LV

cables

3.5.2 Armour

Armour shall mechanically protect the cable and shall be made up of double galvanised

steel tape or steel wire armour. Non magnetic armour shall be used for single core

cables.

3.5.3 Conductor

Conductor shall be stranded. Conductor shall be class 2 for cables for fixed

installations and class 5 for flexible cables feeding mobile equipment.

Cable cores shall be in copper.

3.5.4 Oversheath

Oversheath of cables shall be PVC.

All cables shall be aliphatic hydrocarbon, sunlight resistant, flame retardant and low

density of smoke according to IEC 332 and IEC 1034.

Circuits for safety requirements shall be compulsorily fire resistant. Fire resisting

cables shall withstand to a 1000℃ temperature during 30 minutes (with test

procedure requirement of the IEC 331) and shall continue to conduct electric power

during this period.

Page 6: CABLE-SIZING

IRAN - South Pars Gas Field - Phase 4 & 5 Doc. N. NC 2017 120 1630 004 Rev. 2

Page 6 of 11

This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.

4. BASIS OF CALCULATION

4.1 Basis

A cable selection shall be carried out with respect to the most stringent of the following

criteria.

Admissible steady state cable insulation thermal withstand

Admissible voltage drop (steady state, motor start)

Admissible overcurrent in cable (short-circuit, overload)

4.2 Reference admissible current carrying capacities

For XLPE or EPR core insulation, maximum core temperature is 90℃ and the current

carrying capacities are the following :

4.2.1 LV cables current carrying capacities

(Refer attachment #1)

4.2.2 HV(6kV, 11kV and 33kV) cables current carrying capacities

(Refer attachment #2)

4.3 Admissible current carrying capacities

4.3.1 Rating factor for ambient temperature

Ambient air temperature for SOUTH PARS 4&5 project is 48℃.

KAT = 0.84 interpolated between 45℃ and 50℃.(Refer attachment #3)

Ambient ground temperature for SOUTH PARS 4&5 project is 25℃.

KGT = 0.96 (Refer attachment #4)

4.3.2 Rating factor for Soil thermal resistivity .(Refer attachment #5)

On the basis of IEC-287 9.6.1 the site conditions of soil thermal resistivity is applied as

2.5 K.m/W

For 6kV,11kV and 33kV cables : KSH = 0.70

For 0.4kV cables :

Admissible ampacities are given for 2.5 K.m/W in para. 4.2.1. The cables shall then

be overrated by : KSL = 1.0

Page 7: CABLE-SIZING

IRAN - South Pars Gas Field - Phase 4 & 5 Doc. N. NC 2017 120 1630 004 Rev. 2

Page 7 of 11

This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.

4.3.3 Group rating factor (Influence between cables)

For cables installed in free air :

- HV cables (6kV,11kV and 33kV)

Table 52-E4 of IEC 364-5-523, installation method L – 3 ladders with

vertical spacing between ladder of 300 mm - over 9 touching cables in

single layer formation on each cable ladder. (Attachment #6)

KHA = 0.70

- LV cables (0.4kV)

Table 52-E4 of IEC 364-5-523, installation method L – 3 ladders with

vertical spacing between ladder of 300 mm - over 9 touching cables in

single layer formation on each cable ladder. (Attachment #6)

KLA = 0.70

For buried cables :

- HV cables (6kV,11kV and 33kV) :

Table 52-E2 of IEC 364-5-523

Two layers, 6 cables with horizontal spacing between cables of 150 mm

and vertical spacing between layers of 300 mm ; (Attachment #7)

KHB = 0.62

- LV cables (0.4kV) for motors, feeder power & street lighting :

Table 52-E2 of IEC 364-5-523

Two layers, 5 touching cables with vertical spacing between layers of

300 mm ; (Attachment #7)

KLB = 0.55

4.3.4 Depth of laying

Minimum depth of laying of cable is 0.9m.

The derating factor for different burial depths are ignored.

Page 8: CABLE-SIZING

IRAN - South Pars Gas Field - Phase 4 & 5 Doc. N. NC 2017 120 1630 004 Rev. 2

Page 8 of 11

This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.

4.3.5 Overall admissible ampacity correction factors

4.3.5.1 HV cables (6kV, 11kV and 33kV)

For HV motors & power feeders installed on cable ladder

- K = KAT x KHA = 0.84 x 0.70 = 0.588

For HV motors & power feeders installed underground

- K = KGT x KSH x KHB = 0.96 x 0.70 x 0.62 = 0.417

Corrected current carrying capacities for HV cables : Refer to attachment #8

4.3.5.2 LV cables (0.4kV)

For LV motors & power feeders installed on cable ladder

- K = KAT x KLA = 0.84 x 0.7 = 0.588

For LV motors, power feeders & street lightings installed underground

- K = KGT x KSL x KLB = 0.96 x 1.0 x 0.55 = 0.528

Corrected current carrying capacities for LV cables for motor & power feeder

: Refer to attachment #14, #15, #16 & #17

4.4 Admissible voltage drop

4.4.1 Voltage drop calculation formula

The voltage drop is calculated from the following formula;

- Single-phase voltage drop : Vdrop = 2 × L × I (Ra cosθ + X sinθ )

- Three-phase voltage drop : Vdrop = 3 × L × I (Ra cosθ + X sinθ )

- Motor start voltage drop : Vdrop = 3 × L × ILRC (Ra cosθ LRC+ X sinθ LRC)

where L = feeder length in km

Rc = conductor resistance of cable in D.C. at 90℃(ohm/km)

Ra = conductor resistance of cable in A.C. at 90℃(ohm/km)

X = core inductance (ohm/km)

Page 9: CABLE-SIZING

IRAN - South Pars Gas Field - Phase 4 & 5 Doc. N. NC 2017 120 1630 004 Rev. 2

Page 9 of 11

This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.

I = rated current of electrical consumer to be connected (A)

ILRC = Locked rotor current (A)

cosθ = power factor of electrical consumer to be connected

cosθ LRC= L.R.C power factor

For R and X values, refer to Attachment #9

4.4.2 Voltage drop limitation considered are as follows.

Feeder Voltage Drop

From main switchboards to consumers during normaloperation 5 %

Motor cables at full load 5 %

Motor cables from switchgears to motor terminal duringstarting 15 %

Lighting and small power cables (including AC, DC UPScircuits) between secondary panel and the furthest lightingfixture/small load.

- When secondary panel is located in unit 3 %

- When secondary panel is located near the maindistribution panel in substation 5 %

AC, DC Uninterruptible power supplies main power cablesbetween batteries and main equipment cubicles 1 %

Page 10: CABLE-SIZING

IRAN - South Pars Gas Field - Phase 4 & 5 Doc. N. NC 2017 120 1630 004 Rev. 2

Page 10 of 11

This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.

4.5 Short-circuit current

The minimum conductor size for short circuit current is calculated as follows as

per clause 434-03-03 of IEE WIRING REGULATION 16th edition 1991.

kItS ×

=

S = nominal cross sectional area of conductor in mm²

I = The value of short circuit current in amperes, expressed for a.c. as the

r.m.s value.

k = 143 for HV cables insulated with XLPE

t = duration of short circuit (sec)

0.25 sec (12.5 cycle) for HV circuits

Note 1. 0.25 sec (12.5 cycle) for HV circuit is based on the following

fault clearing time.

Breaker : 5 cycle (0.1 sec)

Instantaneous relay : 1 cycle (0.02 sec)

Safety margin : 6.5 cycle (0.13 sec)

Note 2. 0.1 sec (5 cycle) for fused contactor circuit of HV motor feeder.

Note 3. For the cables routed in classified hazardous area, it shall be

ensured that surface temperature of cables does not exceed

the given temperature class of the hazardous area (T3=200

deg.C) during overcurrent or short circuit fault conditions. This

may be ensured by close consult with cable manufacturer

verifying the temperature propagation speed from the copper

conductor to the outer surface of cables via insulation, armour

and outer sheath in terms of fault clearing time by protective

devices such as fuses or relays.

Page 11: CABLE-SIZING

IRAN - South Pars Gas Field - Phase 4 & 5 Doc. N. NC 2017 120 1630 004 Rev. 2

Page 11 of 11

This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.

5. CABLE SIZING CHART

5.1 HV cable sizing chart for power feeder data

5.1.1 For 33kV feeder

Refer to attachment #10

5.1.2 For 11kV feeder

Refer to attachment #11

5.1.3 For 6kV plain feeder

Refer to attachment #12

5.1.4 For 6kV motor feeder

Refer to attachment #13

5.2 LV cable sizing chart

5.2.1 For 400V motor feeder

Refer to attachment #14 & #15

5.2.2 For 400V power feeder

Refer to attachment #16 & #17

5.2.3 For 230VAC power feeder

Refer to attachment #18, #19 & #20

5.2.4 For 230VAC motor feeder

Refer to attachment #21

5.2.5 For 48VDC power feeder

Refer to attachment #22, #23 & #24

Page 12: CABLE-SIZING

Attachment # 1

LV cable current carrying capacities

Multi-core cables

In free air(1) Underground(2)

Nominalconductor

cross-section(sq.mm) 2 cores 3 cores 2 cores 3 cores

1.5 26 23 26 22

2.5 36 32 34 29

4 49 42 44 37

6 63 54 56 46

10 86 75 73 61

16 115 100 95 79

25 149 127 121 101

35 185 157 146 122

50 225 192 173 144

70 289 246 213 178

95 352 298 252 211

120 410 346 287 240

150 473 399 324 271

185 542 456 363 304

240 641 538 419 351

300 741 620 474 396

Note (1) : Reference air temperature 30℃

Reference installation Chart 52-C11 column E of IEC 364-5-523,

with two loaded cores & three loaded cores

(2) : Reference soil temperature 20℃

Reference thermal soil resistivity 2.5 K.m/W

Reference installation Chart 52-C2 column D for two loaded

conductors & Chart 52-C4 Column D of IEC

364-5-523 for three loaded conductors.

Page 13: CABLE-SIZING

Attachment # 2

HV cable current carrying capacities

Allowable current(A) (1)

Nominal Cross-section(sq.mm)

Direct laid in ground Installed in free air on cable trays

3C-35 190 190

3C-50 225 225

3C-70 275 280

3C-95 330 340

3C-120 370 385

3C-150 420 445

3C-185 470 510

3C-240 540 590

1C-300 630 740

Note (1) : Reference soil temperature 20℃

Reference air temperature 30℃

Reference thermal soil resistivity 1 K.m/W

Reference installation Chart 52-C33 of NFC13200 for 3 cores

Cable & Chart 52-C23 of NFC 13200 for

1 core cable

Page 14: CABLE-SIZING

Attachment # 3

Correction factors for ambient air temperature other than 30℃

(Table 52-D1 of IEC 364-5-523)

Insulation

Mineral *Ambienttemperature

(℃) PVC XLPE andEPR

PVC coveredor bare andexposed toloads 70℃

Bare notexposed totouch 105℃

10 1.22 1.15 1.26 1.14

15 1.17 1.12 1.20 1.11

20 1.12 1.08 1.14 1.07

25 1.06 1.04 1.07 1.04

35 0.94 0.96 0.93 0.96

40 0.87 0.91 0.85 0.92

45 0.79 0.87 0.87 0.88

50 0.71 0.82 0.67 0.84

55 0.61 0.76 0.57 0.80

60 0.5 0.71 0.45 0.75

65 - 0.65 - 0.70

70 - 0.58 - 0.65

75 - 0.50 - 0.60

80 - 0.41 - 0.54

85 - - - 0.47

90 - - - 0.40

95 - - - 0.32

* For higher ambient temperatures, consult manufacturer

Page 15: CABLE-SIZING

Attachment # 4

Correction factors for ambient ground temperatures other than 20℃.

(Table 52-D2 of IEC 364-5-523)

InsulationGround temperature (℃)

PVC XLPE and EPR

10 1.10 1.07

15 1.05 1.04

25 0.95 0.96

30 0.89 0.93

35 0.84 0.89

40 0.77 0.85

45 0.71 0.80

50 0.63 0.76

55 0.55 0.71

60 0.45 0.65

65 - 0.60

70 - 0.53

75 - 0.46

80 - 0.38

Attachment # 5

Rating factor for Soil thermal resistivity

(Table 52 GJ of NFC 15-100)

Ground ThermalResistivity (K.m/W) Correction Humidity Soil

0.50 1.21 Very wet soil

������������������������������������������������������������������������������������������

0.70 1.13 Wet soil

0.85 1.05 Normal

1.00 1 Dry soil

���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������

1.20 0.94

1.50 0.86

Clay andlimestone

2.00 0.76

2.50 0.70

3.00 0.65

Very dry soil

Sand������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������

Ashes andSlag

Page 16: CABLE-SIZING

Attachment #6

Correction factors for groups of more than one multicore cable

(Table 52-E4 of IEC364-5-523)

Number of cablesInstallation method

In Table 52-B2 Number of

trays1 2 3 4 6 9

1 1.00 0.85 0.80 0.80 0.80 0.80

2 1.00 0.85 0.80 0.80 0.75 0.75

3 1.00 0.85 0.80 0.75 0.75 0.70

1 1.00 1.00 1.00 1.00 1.00 -

2 1.00 1.00 1.00 0.95 0.95 -

Ladder

supports,

cleats,

etc.

L

3 1.00 1.00 0.95 0.95 0.95 -

Attachment #7

Correction factors for more than one circuit, cables laid directly in the ground

(Table 52-E2 of IEC364-5-523)Cable to cable clearance

Number of

circuits

Nil

(cables

touching)

One cable

diameter0.125 m 0.25 m 0.5 m

2 0.75 0.80 0.85 0.90 0.90

3 0.65 0.60 0.75 0.80 0.85

4 0.6 0.60 0.70 0.75 0.80

5 0.55 0.55 0.65 0.70 0.80

6 0.5 0.55 0.60 0.70 0.80

Page 17: CABLE-SIZING

Attachment #8

REM

ARK

SC

OR

REC

TED

CU

RR

ENT-

CAR

RYI

NG

CAP

ACIT

Y (A

)

79 93 114

137

154

174

195

224

262

UN

DER

GR

OU

ND

(D.F

:0.4

1664

)

CU

RR

ENT-

CAR

RYI

NG

CAP

ACIT

Y (A

)

190

225

275

330

370

420

470

540

630

CO

RR

ECTE

DC

UR

REN

T-C

ARR

YIN

GC

APAC

ITY

(A)

112

132

165

200

226

262

300

347

435

IN F

REE

AIR

(D.F

:0.5

88)

CU

RR

ENT-

CAR

RYI

NG

CAP

ACIT

Y (A

)

190

225

280

340

385

445

510

590

740

CO

RR

ECTE

D C

UR

REN

T C

AR

RYI

NG

CA

PAC

ITIE

S FO

R 6

kV, 1

1kV

& 3

3kV

CA

BLE

CA

BLE

SIZE

(MM

2 )

3C-3

5

3C-5

0

3C-7

0

3C-9

5

3C-1

20

3C-1

50

3C-1

85

3C-2

40

1C-3

00

Page 18: CABLE-SIZING

Attachment # 9

RESISTANCE AND REACTANCE

ResistanceCross-section

(sq.mm)D.C at 20℃

(ohm/km)

D.C at 90℃

(ohm/km)

A.C at 90℃

(ohm/km)

Reactance at50Hz

(ohm/km)

1.5 12.10 15.43 15.43 0.122

2.5 7.41 9.45 9.45 0.116

4 4.61 5.88 5.88 0.110

6 3.08 3.93 3.93 0.100

10 1.83 2.33 2.33 0.094

16 1.15 1.47 1.47 0.0911

25 0.727 0.927 0.927 0.0911

35 0.524 0.668 0.669 0.0911

50 0.387 0.493 0.494 0.0879

70 0.268 0.342 0.344 0.0879

95 0.193 0.246 0.247 0.0879

120 0.153 0.195 0.197 0.0879

150 0.124 0.158 0.160 0.0879

185 0.0991 0.1264 0.1290 0.0879

240 0.0754 0.0961 0.0997 0.0879

Page 19: CABLE-SIZING

Attachment #10

33kV FEEDER

TAG NO. KVA VOLTAGE(KV) F.L.A (A) LENGTH

(M)MAX. FAULT

CURRENT (KA)

MIN. REQ’DCONDUCTOR

SIZE (mm2)

SELECTEDCABLE SIZE

(mm2)

SELECTEDCABLE

AMPACITY(A)

V.D ATFULLLOAD

(%)NOTE(1)

120TR101A 50,000 33 874.8 130 21.986 76.9 4x(3x1C-240) 896 0.02

120TR101B 50,000 33 874.8 150 21.986 76.9 4x(3x1C-240) 896 0.02

120TR101C 50,000 33 874.8 190 21.986 76.9 4x(3x1C-240) 896 0.03

120TR101D 50,000 33 874.8 210 21.986 76.9 4x(3x1C-240) 896 0.03

1TR1111 50,000 33 874.8 50 21.986 76.9 3x(3C-185) 900 0.01

1TR1311 20,000 33 349.9 65 21.986 76.9 3x(1C-300) 435 0.02

1TR1312 20,000 33 349.9 75 21.986 76.9 3x(1C-300) 435 0.02

1TR1211 10,000 33 175.0 1,590 21.986 76.9 3C-185 195 0.23

1TR1212 10,000 33 175.0 1,590 21.986 76.9 3C-185 195 0.23

1TR1213 10,000 33 175.0 1,590 21.986 76.9 3C-185 195 0.23

1TR1216 10,000 33 175.0 1,820 21.986 76.9 3C-120 154 0.28

1TR1217 10,000 33 175.0 1,010 21.986 76.9 3C-95 137 0.19

1TR1218 10,000 33 175.0 1,590 21.986 76.9 3C-185 195 0.23

1TR1214 8,000 33 140.0 1,590 21.986 76.9 3C-185 195 0.23

1TR1219 8,000 33 140.0 1,590 21.986 76.9 3C-185 195 0.23

1TR1215 6,300 33 110.2 1,820 21.986 76.9 3C-120 154 0.28

1TR1220 6,300 33 110.2 1,010 21.986 76.9 3C-95 137 0.19

2TR1311 8,000 33 140.0 1,590 21.986 76.9 3C-120 154 0.25

2TR1312 8,000 33 140.0 1,590 21.986 76.9 3C-120 154 0.25

3TR1311 8,000 33 140.0 1,590 21.986 76.9 3C-120 154 0.25

3TR1312 8,000 33 140.0 1,570 21.986 76.9 3C-120 154 0.24

4TR1311 8,000 33 140.0 1,520 21.986 76.9 3C-120 154 0.23

4TR1312 8,000 33 140.0 1,520 21.986 76.9 3C-120 154 0.23

5TR1311 8,000 33 140.0 1,010 21.986 76.9 3C-120 154 0.16

5TR1312 8,000 33 140.0 1,010 21.986 76.9 3C-120 154 0.16

6TR1311 8,000 33 140.0 1,820 21.986 76.9 3C-120 154 0.28

6TR1312 8,000 33 140.0 1,820 21.986 76.9 3C-120 154 0.28

7TR1311 4,000 33 70.0 3,300 21.986 76.9 3C-95 137 0.40

7TR1312 4,000 33 70.0 3,300 21.986 76.9 3C-95 137 0.40

9TR1311 3,150 33 55.1 750 21.986 76.9 3C-95 137 0.07

9TR1312 3,150 33 55.1 750 21.986 76.9 3C-95 137 0.07

10TR1311 5,000 33 87.5 1,030 21.986 76.9 3C-95 137 0.16

10TR1312 5,000 33 87.5 1,080 21.986 76.9 3C-95 137 0.16

Page 20: CABLE-SIZING

TAG NO. KVA VOLTAGE(KV) F.L.A (A) LENGTH

(M)MAX. FAULT

CURRENT (KA)

MIN. REQ’DCONDUCTOR

SIZE (mm2)

SELECTEDCABLE SIZE

(mm2)

SELECTEDCABLE

AMPACITY(A)

V.D ATFULLLOAD

(%)NOTE(1)

11TR1311 6,300 33 110.2 560 21.986 76.9 3C-95 137 0.11

11TR1312 6,300 33 110.2 590 21.986 76.9 3C-95 137 0.11

12TR1311 5,000 33 87.5 5,950 21.986 76.9 3C-95 137 0.90

12TR1312 5,000 33 87.5 5,950 21.986 76.9 3C-95 137 0.90

Note (1) : POWER FACTOR 0.8

Page 21: CABLE-SIZING

Attachment #11

11kV MOTOR FEEDER

TAG NO.KW

VOLTAGE(KV)

F.L.A (A)NOTE(1)

L.R.CLENGTH

(M)

MAX.FAULT

CURRENT(KA)

MIN. REQ’DCONDUCTORSIZE (mm2)

SELECTEDCABLE SIZE

(mm2)

SELECTEDCABLE

AMPACITY (A)

V.D ATSTARTING

(%)

VOLTAGEDROP AT

STARTING(V)

REMARKS

103 KM 101 3,100 11 206.7 1,033.5 320 6.367 22.26 3C-240 224 0.552 60.75

103 KM 201 3,100 11 206.7 1,033.5 425 6.367 22.26 3C-240 224 0.734 80.69

111 KM 101 5,200 11 346.7 1,733.5 312 10.342 36.16 2x(3C-150) 348 1.006 110.66

111 KM 201 5,200 11 346.7 1,733.5 216 10.342 36.16 2x(3C-150) 348 0.696 76.61

111 KM 301 5,200 11 346.7 1,733.5 264 10.342 36.16 2x(3C-150) 348 0.851 93.63

111 KM 401 5,200 11 346.7 1,733.5 312 10.342 36.16 2x(3C-150) 348 1.006 110.66

111 KM 501 5,200 11 346.7 1,733.5 216 10.371 36.26 2x(3C-150) 348 0.696 76.61

111 KM 601 5,200 11 346.7 1,733.5 264 10.371 36.26 2x(3C-150) 348 0.851 93.63

147 KM 101 A 4,300 11 283.7 1,418.7 270 8.038 28.10 2x(3C-120) 308 0.757 83.28

147 KM 101 B 4,300 11 283.7 1,418.7 260 8.538 29.85 2x(3C-120) 308 0.729 80.20

Page 22: CABLE-SIZING

Attachment #12

6kV PLAIN FEEDERS

TAG NO. KVA VOLTAGE(KV) F.L.A (A) LENGTH (M)

MAX.FAULT

CURRENT(KA)

MIN. REQ’DCONDUCTORSIZE (mm2)

SELECTEDCABLE SIZE

(mm2)

SELECTEDCABLE

AMPACITY(A)

V.D ATFULL

LOAD (%)NOTE(1)

1TR1311 20,000 6 1,924.5 40 22.735 79 5x(3x1C-300) 2,175 0.06

1TR1312 20,000 6 1,924.5 55 22.735 79 5x(3x1C-300) 2,175 0.08

1TR3411 2,000 6 192.5 70 22.735 79 3C-120 226 0.08

1TR3412 2,000 6 192.5 85 22.735 79 3C-120 226 0.10

1TR3413 1,600 6 154.0 90 22.735 79 3C-95 200 0.13

1TR3414 1,600 6 154.0 110 22.735 79 3C-95 200 0.16

1TR3415 2,500 6 240.6 90 21.937 77 3C-185 300 0.10

1TR3416 2,500 6 240.6 85 21.937 77 3C-185 300 0.09

2TR1311 8,000 6 769.8 34 12.791 45 2x(3x1C-300) 870 0.05

2TR1312 8,000 6 769.8 30 12.791 45 2x(3x1C-300) 870 0.04

2TR3411 2,500 6 240.6 40 12.791 45 3C-150 262 0.05

2TR3412 2,500 6 240.6 25 12.791 45 3C-150 262 0.03

2TR3413 630 6 60.6 1,675 21.937 69 3C-70 165 0.96

2TR3414 2,500 6 240.6 40 12.791 45 3C-150 262 0.05

2TR3415 2,500 6 240.6 40 12.791 45 3C-150 262 0.05

2TR3416 400 6 38.5 1,680 21.937 69 3C-70 165 0.61

3TR1311 8,000 6 769.8 34 12.633 44 2x(3x1C-300) 870 0.05

3TR1312 8,000 6 769.8 30 12.633 44 2x(3x1C-300) 870 0.04

3TR3411 2,500 6 240.6 40 12.633 44 3C-150 262 0.05

3TR3412 2,500 6 240.6 25 12.633 44 3C-150 262 0.03

3TR3413 400 6 38.5 1,620 21.937 69 3C-70 165 0.59

3TR3414 2,500 6 240.6 40 12.633 44 3C-150 262 0.05

3TR3415 2,500 6 240.6 40 12.633 44 3C-150 262 0.05

3TR3416 630 6 60.6 1,630 21.937 69 3C-70 165 0.94

4TR1311 8,000 6 769.8 35 12.28 43 2x(3x1C-300) 870 0.05

4TR1312 8,000 6 769.8 35 12.28 43 2x(3x1C-300) 870 0.05

4TR3411 2,000 6 192.5 40 12.28 43 3C-120 226 0.05

4TR3412 2,000 6 192.5 40 12.28 43 3C-120 226 0.05

4TR3413 630 6 60.6 1,520 21.937 69 3C-70 165 0.87

4TR3414 2,000 6 192.5 50 12.28 43 3C-120 226 0.06

4TR3415 2,000 6 192.5 50 12.28 43 3C-120 226 0.06

5TR1311 8,000 6 769.8 53 12.122 42 2x(3x1C-300) 870 0.08

5TR1312 8,000 6 769.8 52 12.122 42 2x(3x1C-300) 870 0.08

5TR3411 2,000 6 192.5 45 12.122 42 3C-120 226 0.05

Page 23: CABLE-SIZING

TAG NO. KVA VOLTAGE(KV) F.L.A (A) LENGTH (M)

MAX.FAULT

CURRENT(KA)

MIN. REQ’DCONDUCTORSIZE (mm2)

SELECTEDCABLE SIZE

(mm2)

SELECTEDCABLE

AMPACITY(A)

V.D ATFULL

LOAD (%)NOTE(1)

5TR3412 2,000 6 192.5 45 12.122 42 3C-120 226 0.05

5TR3413 630 6 60.6 1,100 21.937 69 3C-70 165 0.63

5TR3414 2,000 6 192.5 40 12.122 42 3C-120 226 0.05

5TR3415 2,000 6 192.5 40 12.122 42 3C-120 226 0.05

6TR1311 8,000 6 769.8 34 13.341 47 2x(3x1C-300) 870 0.05

6TR1312 8,000 6 769.8 30 13.341 47 2x(3x1C-300) 870 0.04

6TR3411 1,600 6 154.0 40 13.341 47 3C-95 200 0.06

6TR3412 1,600 6 154.0 25 13.341 47 3C-95 200 0.04

6TR3413 630 6 60.6 1,870 21.937 69 3C-70 165 1.07

6TR3414 1,600 6 154.0 40 13.341 47 3C-95 200 0.06

6TR3415 1,600 6 154.0 40 13.341 47 3C-95 200 0.06

7TR1311 4,000 6 384.9 45 7.596 27 3x(1C-300) 435 0.07

7TR1312 4,000 6 384.9 40 7.596 27 3x(1C-300) 435 0.06

7TR3411 100 6 9.6 35 7.596 27 3C-35 112 0.01

7TR3413 100 6 9.6 3,300 21.937 69 3C-70 165 0.30

8TR3411 1,250 6 120.3 540 22.735 79 3C-95 200 0.61

8TR3412 1,250 6 120.3 545 22.735 79 3C-95 200 0.62

8TR3413 400 6 38.5 540 21.937 69 3C-70 165 0.20

9TR1311 3,150 6 303.1 30 4.848 17 3C-240 347 0.03

9TR1312 3,150 6 303.1 25 4.848 17 3C-240 347 0.03

9TR3411 1,250 6 120.3 40 4.848 17 3C-70 165 0.05

9TR3412 1,250 6 120.3 25 4.848 17 3C-70 165 0.03

9TR3413 630 6 60.6 700 21.937 69 3C-70 165 0.40

9TR3414 800 6 77.0 40 4.848 17 3C-35 112 0.05

9TR3415 800 6 77.0 40 4.848 17 3C-35 112 0.05

10TR1311 5,000 6 481.1 30 8.795 31 2x(3C-150) 524 0.04

10TR1312 5,000 6 481.1 25 8.795 31 2x(3C-150) 524 0.03

10TR3411 2,500 6 240.6 40 8.795 31 3C-150 262 0.05

10TR3412 2,500 6 240.6 25 8.795 31 3C-150 262 0.03

10TR3413 630 6 60.6 1,045 21.937 69 3C-70 165 0.60

10TR3414 2,000 6 192.5 40 8.795 31 3C-120 226 0.05

10TR3415 2,000 6 192.5 40 8.795 31 3C-120 226 0.05

11TR1311 6,300 6 606.2 55 9.895 35 2x(3C-240) 694 0.06

11TR1312 6,300 6 606.2 55 9.895 35 2x(3C-240) 694 0.06

11TR3411 2,000 6 192.5 55 9.895 35 3C-120 226 0.06

11TR3412 2,000 6 192.5 60 9.895 35 3C-120 226 0.07

11TR3413 800 6 77.0 570 21.937 69 3C-70 165 0.42

11TR3414 2,000 6 192.5 45 9.895 35 3C-120 226 0.05

Page 24: CABLE-SIZING

TAG NO. KVA VOLTAGE(KV) F.L.A (A) LENGTH (M)

MAX.FAULT

CURRENT(KA)

MIN. REQ’DCONDUCTORSIZE (mm2)

SELECTEDCABLE SIZE

(mm2)

SELECTEDCABLE

AMPACITY(A)

V.D ATFULL

LOAD (%)NOTE(1)

11TR3415 2,000 6 192.5 45 9.895 35 3C-120 226 0.05

12TR1311 5,000 6 481.1 55 8.287 29 2x(3C-150) 524 0.07

12TR1312 5,000 6 481.1 55 8.287 29 2x(3C-150) 524 0.07

12TR3411 630 6 60.6 65 8.287 29 3C-35 112 0.07

12TR3412 630 6 60.6 65 8.287 29 3C-35 112 0.07

12TR3413 400 6 38.5 5,950 21.937 69 3C-70 165 2.17

131G101A 4,500 6 433 265 21.937 77 2x(3x1C-300) 524 1.09

131G101B 4,500 6 433 265 21.937 77 2x(3x1C-300) 524 1.09

1ES31A - 6 1,250 60 21.937 77 5x(3x1C-300) 1310 0.71

1ES31B - 6 1,250 60 21.937 77 5x(3x1C-300) 1310 0.71

NOTE (1) : POWER FACTOR 0.8

Page 25: CABLE-SIZING

Attachment #13

6kV MOTOR FEEDERS

TAG NO.KW

VOLTAGE(KV)

F.L.A (A)NOTE(1)

L.R.CLENGTH

(M)

MAX. FAULTCURRENT

(KA)

MIN. REQ’DCONDUCTORSIZE (mm2)

SELECTEDCABLE SIZE

(mm2)

SELECTEDCABLE

AMPACITY (A)

V.D ATSTARTING

(%)

VOLTAGEDROP AT

STARTING (V)REMARKS

101 PM 101 A 1,160 6 131.7 658.6 398 12.791 44.72 3C-95 137 1.025 61.53

101 PM 101 B 1,160 6 131.7 658.6 402 12.791 44.72 3C-95 137 1.036 62.15

101 PM 201 A 1,160 6 131.7 658.6 298 12.791 44.72 3C-95 137 0.768 46.07

101 PM 201 B 1,160 6 131.7 658.6 302 12.791 44.72 3C-95 137 0.778 46.69

101 PM 301 A 1,160 6 131.7 658.6 298 12.633 44.17 3C-95 137 0.768 46.07

101 PM 301 B 1,160 6 131.7 658.6 302 12.633 44.17 3C-95 137 0.778 46.69

101 PM 401 A 1,160 6 131.7 658.6 398 12.633 44.17 3C-95 137 1.025 61.53

101 PM 401 B 1,160 6 131.7 658.6 402 12.633 44.17 3C-95 137 1.036 62.15

102 PM 102 A 250 6 31.7 158.6 351 12.122 26.81 3C-35 79 0.358 21.51

102 PM 102 B 250 6 31.7 158.6 345 12.122 26.81 3C-35 79 0.352 21.14

102 PM 102 C 250 6 31.7 158.6 340 12.122 26.81 3C-35 79 0.347 20.83

103 PM 101 A 220 6 26.1 130.3 270 12.122 26.81 3C-35 79 0.226 13.59

103 PM 101 B 220 6 26.1 130.3 235 12.122 26.81 3C-35 79 0.197 11.83

103 PM 103 A 220 6 26.1 130.3 261 12.122 26.81 3C-35 79 0.219 13.13

103 PM 103 B 220 6 26.1 130.3 265 12.122 26.81 3C-35 79 0.222 13.34

103 PM 108 320 6 35.0 174.9 257 12.122 26.81 3C-35 79 0.289 17.36

103 PM 201 A 220 6 26.1 130.3 195 12.122 26.81 3C-35 79 0.164 9.81

103 PM 201 B 220 6 26.1 130.3 200 12.122 26.81 3C-35 79 0.168 10.07

103 PM 203 A 220 6 26.1 130.3 186 12.122 26.81 3C-35 79 0.156 9.36

103 PM 203 B 220 6 26.1 130.3 190 12.122 26.81 3C-35 79 0.159 9.56

103 PM 208 320 6 35.0 174.9 182 12.122 26.81 3C-35 79 0.205 12.30

104 KM 101 A 390 6 43.8 218.8 432 12.791 28.29 3C-35 79 0.609 36.51

104 KM 101 B 390 6 43.8 218.8 432 12.791 28.29 3C-35 79 0.609 36.51

104 KM 201 A 390 6 43.8 218.8 332 12.791 28.29 3C-35 79 0.468 28.06

104 KM 201 B 390 6 43.8 218.8 332 12.791 28.29 3C-35 79 0.468 28.06

104 KM 301 A 390 6 43.8 218.8 332 12.633 27.94 3C-35 79 0.468 28.06

104 KM 301 B 390 6 43.8 218.8 342 12.633 27.94 3C-35 79 0.482 28.91

104 KM 401 A 390 6 43.8 218.8 432 12.633 27.94 3C-35 79 0.609 36.51

104 KM 401 B 390 6 43.8 218.8 442 12.633 27.94 3C-35 79 0.623 37.36

106 XM 150 530 6 59.0 295.1 339 12.28 27.16 3C-35 79 0.644 38.65

106 XM 250 530 6 59.0 295.1 315 12.28 27.16 3C-35 79 0.599 35.92

106 XM 350 530 6 59.0 295.1 291 12.28 27.16 3C-35 79 0.553 33.18

106 XM 450 530 6 59.0 295.1 267 12.28 27.16 3C-35 79 0.507 30.44

106 XM 550 530 6 59.0 295.1 243 12.28 27.16 3C-35 79 0.462 27.71

Page 26: CABLE-SIZING

TAG NO.KW

VOLTAGE(KV)

F.L.A (A)NOTE(1)

L.R.CLENGTH

(M)

MAX. FAULTCURRENT

(KA)

MIN. REQ’DCONDUCTORSIZE (mm2)

SELECTEDCABLE SIZE

(mm2)

SELECTEDCABLE

AMPACITY (A)

V.D ATSTARTING

(%)

VOLTAGEDROP AT

STARTING (V)REMARKS

106 XM 650 530 6 59.0 295.1 219 12.28 27.16 3C-35 79 0.416 24.97

108 KM 201 A 580 6 68.0 340.2 529 12.28 27.16 3C-35 79 1.159 69.53

108 KM 201 B 580 6 68.0 340.2 594 12.28 27.16 3C-35 79 1.301 78.07

108 KM 201 C 580 6 68.0 340.2 596 12.28 27.16 3C-35 79 1.306 78.34

108 KM 202 A 190 6 21.2 105.8 653 12.28 27.16 3C-35 79 0.445 26.69

108 KM 202 B 190 6 21.2 105.8 655 12.28 27.16 3C-35 79 0.446 26.77

108 KM 301 A 580 6 68.0 340.2 721 12.28 27.16 3C-35 79 1.579 94.77

108 KM 301 B 580 6 68.0 340.2 719 12.28 27.16 3C-35 79 1.575 94.50

108 KM 301 C 580 6 68.0 340.2 717 12.28 27.16 3C-35 79 1.571 94.24

108 KM 302 A 190 6 21.2 105.8 780 12.28 27.16 3C-35 79 0.531 31.88

108 KM 302 B 190 6 21.2 105.8 778 12.28 27.16 3C-35 79 0.530 31.80

116 KM 101 A 190 6 21.5 107.3 311 8.795 19.45 3C-35 79 0.215 12.89

116 KM 101 B 190 6 21.5 107.3 311 8.795 19.45 3C-35 79 0.215 12.89

116 KM 201 A 190 6 21.5 107.3 311 8.795 19.45 3C-35 79 0.215 12.89

116 KM 201 B 190 6 21.5 107.3 311 8.795 19.45 3C-35 79 0.215 12.89

116 PM 111 A 250 6 27.6 138.0 252 8.795 19.45 3C-35 79 0.224 13.43

116 PM 111 B 250 6 27.6 138.0 252 8.795 19.45 3C-35 79 0.224 13.43

116 PM 211 A 250 6 27.6 138.0 252 8.795 19.45 3C-35 79 0.224 13.43

116 PM 211 B 250 6 27.6 138.0 252 8.795 19.45 3C-35 79 0.224 13.43

120 PM 101 A 450 6 51.2 255.9 235 21.973 48.59 3C-50 93 0.321 19.26

120 PM 101 B 450 6 51.2 255.9 245 21.973 48.59 3C-50 93 0.335 20.08

120 PM 101 C 450 6 51.2 255.9 190 21.973 48.59 3C-50 93 0.260 15.57

120 PM 101 D 450 6 51.2 255.9 255 21.973 48.59 3C-50 93 0.348 20.90

121 KM 101 A 370 6 40.9 204.3 390 22.735 50.28 3C-70 114 0.356 21.38

121 KM 101 B 370 6 40.9 204.3 395 22.735 50.28 3C-70 114 0.361 21.66

121 KM 101 C 370 6 40.9 204.3 435 22.735 50.28 3C-70 114 0.398 23.85

121 KM 101 D 370 6 40.9 204.3 440 22.735 50.28 3C-70 114 0.402 24.13

121 KM 101 E 370 6 40.9 204.3 480 22.735 50.28 3C-70 114 0.439 26.32

121 KM 101 F 370 6 40.9 204.3 480 22.735 50.28 3C-70 114 0.439 26.32

121 PM 103 A 961 6 103.7 518.4 360 22.735 50.28 3C-70 114 0.835 50.08

121 PM 103 B 961 6 103.7 518.4 330 22.735 50.28 3C-70 114 0.765 45.91

121 PM 103 C 961 6 103.7 518.4 345 22.735 50.28 3C-70 114 0.800 47.99

123 KM 101 A 1,200 6 129.8 649.0 275 22.735 79.49 3C-95 137 0.698 41.89

123 KM 101 B 1,200 6 129.8 649.0 275 22.735 79.49 3C-95 137 0.698 41.89

123 KM 101 C 1,200 6 129.8 649.0 280 22.735 79.49 3C-95 137 0.711 42.65

125 PM 101 A 1,050 6 109.6 548.2 170 7.596 26.56 3C-70 114 0.417 25.01

125 PM 101 B 1,050 6 109.6 548.2 180 7.596 26.56 3C-70 114 0.441 26.48

125 PM 101 C 1,050 6 109.6 548.2 190 7.596 26.56 3C-70 114 0.466 27.95

Page 27: CABLE-SIZING

TAG NO.KW

VOLTAGE(KV)

F.L.A (A)NOTE(1)

L.R.CLENGTH

(M)

MAX. FAULTCURRENT

(KA)

MIN. REQ’DCONDUCTORSIZE (mm2)

SELECTEDCABLE SIZE

(mm2)

SELECTEDCABLE

AMPACITY (A)

V.D ATSTARTING

(%)

VOLTAGEDROP AT

STARTING (V)REMARKS

125 PM 101 D 1,050 6 109.6 548.2 200 7.596 26.56 3C-70 114 0.490 29.42

125 PM 102 A 600 6 66.9 334.4 70 12.122 26.81 3C-35 79 0.151 9.04

125 PM 102 B 600 6 66.9 334.4 70 12.122 26.81 3C-35 79 0.151 9.04

125 PM 102 C 600 6 66.9 334.4 70 12.122 26.81 3C-35 79 0.151 9.04

130 PM 102 A 405 6 45.1 225.5 540 21.973 48.59 3C-50 93 0.650 39.01

130 PM 104 A 612 6 72.2 360.8 500 21.973 48.59 3C-50 93 0.963 57.79

130 PM 106 A 258 6 28.7 143.7 5,950 21.973 48.59 3C-50 93 4.563 273.80

132 KM 101 A 960 6 105.1 525.4 200 22.735 50.28 3C-95 137 0.411 24.67

132 KM 101 B 960 6 105.1 525.4 205 22.735 50.28 3C-95 137 0.421 25.28

143 PM 103 A 1,210 6 134.9 674.5 530 16.955 59.28 3C-120 154 1.295 77.72

143 PM 103 B 1,210 6 134.9 674.5 520 16.955 59.28 3C-120 154 1.271 76.26

143 PM 103 C 1,210 6 134.9 674.5 510 16.955 59.28 3C-120 154 1.246 74.79

147 KM 102 A 380 6 42.3 211.6 204 13.341 29.50 3C-35 79 0.278 16.68

147 KM 102 B 380 6 42.3 211.6 204 13.341 29.50 3C-35 79 0.278 16.68

147 PM 101 A 485 6 53.6 268.1 486 13.341 29.50 3C-35 79 0.839 50.34

147 PM 101 B 485 6 53.6 268.1 491 13.341 29.50 3C-35 79 0.848 50.86

147 PM 101 C 485 6 53.6 268.1 496 13.341 29.50 3C-35 79 0.856 51.38

147 PM 103 A 485 6 53.6 268.1 569 13.341 29.50 3C-35 79 0.982 58.94

147 PM 103 B 485 6 53.6 268.1 574 13.341 29.50 3C-35 79 0.991 59.46

147 PM 103 C 485 6 53.6 268.1 579 13.341 29.50 3C-35 79 1.000 59.98

148 PM 101 A 597 6 66.0 330.0 327 13.341 29.50 3C-35 79 0.695 41.70

148 PM 101 B 597 6 66.0 330.0 332 13.341 29.50 3C-35 79 0.706 42.33

148 PM 101 C 597 6 66.0 330.0 337 13.341 29.50 3C-35 79 0.716 42.97

148 PM 103 A 597 6 66.0 330.0 410 13.341 29.50 3C-35 79 0.871 52.28

148 PM 103 B 597 6 66.0 330.0 415 13.341 29.50 3C-35 79 0.882 52.92

148 PM 103 C 597 6 66.0 330.0 420 13.341 29.50 3C-35 79 0.893 53.55

Page 28: CABLE-SIZING

Attachment #14

CABLE SELECTION TABLE FOR 400V MOTOR FEEDER(CABLE LADDER) REVISION : 2 DATE : 07 Aug. '03

**NOTE1. MOTOR VOLTAGE : 400 V (3 PHASE)2. ALLOWABLE VOLTAGE DROP: 5 % (UNDER NORMAL RUNNING CONDITION)

3. VALUE OF R & X : REFER TO ATTACHMENT #9 V x ALLOWABLE VOLTAGE DROP x 1000

4. DERATED FACTOR : 0.588 5. MAX. CABLE LENGTH[m] =

√3 x FLC x (Rcosθ + Xsinθ)

* INSTALLATION CONDITION : AMBIENT TEMP. : 48 ℃

MAX. ALLOWABLE TEMP. OF CONDUCTOR : 90 ℃

SPECIFICATION XLPE/PVC/DSTA/PVC (3CORE)SIZE 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 2x150 2x185 2x240

CABLE RESISTANCE[ohm/km] 15.4300 9.4500 5.8800 3.9300 2.3300 1.4700 0.9270 0.6690 0.4940 0.3430 0.2470 0.1970 0.1600 0.1290 0.0997 0.0800 0.0645 0.0499REACTANCE[ohm/km] 0.1220 0.1160 0.1100 0.1000 0.0940 0.0911 0.0911 0.0911 0.0879 0.0879 0.0879 0.0879 0.0879 0.0879 0.0879 0.0440 0.0440 0.0440IMPEDANCE [ohm/km] 15.430 9.451 5.881 3.931 2.332 1.473 0.931 0.675 0.502 0.354 0.262 0.216 0.183 0.156 0.133 0.091 0.078 0.066

AMPACITY[A] 23 32 42 54 75 100 127 157 192 246 298 346 399 456 538 798 912 1076DERATED AMPACITY[A] 13.524 18.816 24.696 31.752 44.100 58.800 74.676 92.316 112.896 144.648 175.224 203.448 234.612 268.128 316.344 469.224 536.256 632.688

MOTOR MAXIMUM ALLOWABLE CABLE LENGTH kW EFF. P.F FLC[A] [M]

0.37 0.80 0.70 0.95 1,808 2,887 4,290 7,130 11,067 16,959 22,702 29,635 39,977 51,377 60,337 69,279 79,100 91,338 138,558 158,200 182,677 0.55 0.80 0.70 1.42 1,216 1,942 2,886 4,797 7,445 11,409 15,272 19,936 26,894 34,563 40,591 46,606 53,213 61,446 93,212 106,426 122,892 0.75 0.80 0.70 1.93 892 1,424 2,116 3,518 5,460 8,367 11,199 14,620 19,722 25,346 29,766 34,178 39,023 45,060 68,355 78,045 90,121

1.1 0.90 0.73 2.42 685 1,094 1,627 2,707 4,209 6,466 8,678 11,358 15,390 19,877 23,436 27,014 30,978 35,965 54,029 61,956 71,930 1.5 0.85 0.74 3.44 474 758 1,127 1,877 2,919 4,489 6,030 7,899 10,720 13,868 16,372 18,897 21,702 25,242 37,794 43,403 50,484 2.2 0.90 0.76 4.64 343 548 815 1,358 2,114 3,257 4,382 5,750 7,826 10,158 12,025 13,917 16,030 18,715 27,833 32,059 37,431

4 0.87 0.84 7.90 183 292 436 728 1,138 1,765 2,391 3,159 4,352 5,728 6,856 8,027 9,366 11,120 16,053 18,732 22,240 5.5 0.85 0.85 10.99 130 208 310 518 810 1,257 1,704 2,254 3,111 4,101 4,916 5,765 6,739 8,019 11,529 13,477 16,038 7.5 0.85 0.87 14.64 95 153 227 380 596 926 1,258 1,667 2,308 3,055 3,673 4,321 5,070 6,064 8,643 10,141 12,128 11 0.86 0.86 21.47 105 157 262 410 638 865 1,145 1,583 2,091 2,510 2,948 3,453 4,119 5,896 6,905 8,237 15 0.89 0.89 27.33 119 200 313 488 663 881 1,223 1,625 1,961 2,315 2,727 3,280 4,630 5,455 6,559

18.5 0.88 0.89 34.09 160 251 391 532 706 981 1,303 1,572 1,856 2,187 2,629 3,712 4,373 5,259 22 0.92 0.88 39.22 141 220 343 466 618 857 1,136 1,369 1,613 1,896 2,274 3,225 3,792 4,547 30 0.90 0.89 54.06 158 246 335 445 619 822 992 1,171 1,379 1,658 2,341 2,758 3,316 37 0.92 0.90 64.50 205 279 371 516 687 830 982 1,159 1,398 1,964 2,319 2,796 45 0.92 0.90 78.44 229 305 424 565 683 807 953 1,150 1,615 1,907 2,299 55 0.91 0.87 100.27 243 337 446 536 631 740 885 1,262 1,480 1,771 75 0.92 0.89 132.21 253 336 405 479 564 678 957 1,128 1,356 90 0.94 0.90 153.55 289 349 412 487 587 825 974 1,175

110 0.94 0.90 187.67 285 337 398 481 675 797 961 132 0.90 0.93 227.63 280 333 406 560 666 811 150 0.90 0.93 258.67 293 357 493 586 714

NO

T A

PPLIC

AB

LE

Page 29: CABLE-SIZING

Attachment #15

CABLE SELECTION TABLE FOR 400V MOTOR FEEDER(TRENCH) REVISION : 2 DATE : 07 Aug. '03

**NOTE1. MOTOR VOLTAGE : 400 V (3 PHASE)2. ALLOWABLE VOLTAGE DROP: 5 % (UNDER NORMAL RUNNING CONDITION)

3. VALUE OF R & X : REFER TO ATTACHMENT #9 V x ALLOWABLE VOLTAGE DROP x 1000

4. DERATED FACTOR : 0.528 5. MAX. CABLE LENGTH[m] =

√3 x FLC x (Rcosθ + Xsinθ)

* INSTALLATION CONDITION : AMBIENT TEMP. : 48 ℃

MAX. ALLOWABLE TEMP. OF CONDUCTOR : 90 ℃

SPECIFICATION XLPE/PVC/DSTA/PVC (3CORE)SIZE 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 2x150 2x185 2x240

CABLE RESISTANCE[ohm/km] 15.4300 9.4500 5.8800 3.9300 2.3300 1.4700 0.9270 0.6690 0.4940 0.3430 0.2470 0.1970 0.1600 0.1290 0.0997 0.0800 0.0645 0.0499REACTANCE[ohm/km] 0.1220 0.1160 0.1100 0.1000 0.0940 0.0911 0.0911 0.0911 0.0879 0.0879 0.0879 0.0879 0.0879 0.0879 0.0879 0.0440 0.0440 0.0440IMPEDANCE [ohm/km] 15.430 9.451 5.881 3.931 2.332 1.473 0.931 0.675 0.502 0.354 0.262 0.216 0.183 0.156 0.133 0.091 0.078 0.066

AMPACITY[A] 22 29 37 46 61 79 101 122 144 178 211 240 271 304 351 542 608 702DERATED AMPACITY[A] 11.616 15.312 19.536 24.288 32.208 41.712 53.328 64.416 76.032 93.984 111.408 126.720 143.088 160.512 185.328 286.176 321.024 370.656

MOTOR MAXIMUM ALLOWABLE CABLE LENGTH kW EFF. P.F FLC[A] [M]

0.37 0.80 0.70 0.95 1,808 2,887 4,290 7,130 11,067 16,959 22,702 29,635 39,977 51,377 60,337 69,279 79,100 91,338 138,558 158,200 182,677 0.55 0.80 0.70 1.42 1,216 1,942 2,886 4,797 7,445 11,409 15,272 19,936 26,894 34,563 40,591 46,606 53,213 61,446 93,212 106,426 122,892 0.75 0.80 0.70 1.93 892 1,424 2,116 3,518 5,460 8,367 11,199 14,620 19,722 25,346 29,766 34,178 39,023 45,060 68,355 78,045 90,121

1.1 0.90 0.73 2.42 685 1,094 1,627 2,707 4,209 6,466 8,678 11,358 15,390 19,877 23,436 27,014 30,978 35,965 54,029 61,956 71,930 1.5 0.85 0.74 3.44 474 758 1,127 1,877 2,919 4,489 6,030 7,899 10,720 13,868 16,372 18,897 21,702 25,242 37,794 43,403 50,484 2.2 0.90 0.76 4.64 343 548 815 1,358 2,114 3,257 4,382 5,750 7,826 10,158 12,025 13,917 16,030 18,715 27,833 32,059 37,431

4 0.87 0.84 7.90 183 292 436 728 1,138 1,765 2,391 3,159 4,352 5,728 6,856 8,027 9,366 11,120 16,053 18,732 22,240 5.5 0.85 0.85 10.99 130 208 310 518 810 1,257 1,704 2,254 3,111 4,101 4,916 5,765 6,739 8,019 11,529 13,477 16,038 7.5 0.85 0.87 14.64 95 153 227 380 596 926 1,258 1,667 2,308 3,055 3,673 4,321 5,070 6,064 8,643 10,141 12,128 11 0.86 0.86 21.47 157 262 410 638 865 1,145 1,583 2,091 2,510 2,948 3,453 4,119 5,896 6,905 8,237 15 0.89 0.89 27.33 200 313 488 663 881 1,223 1,625 1,961 2,315 2,727 3,280 4,630 5,455 6,559

18.5 0.88 0.89 34.09 251 391 532 706 981 1,303 1,572 1,856 2,187 2,629 3,712 4,373 5,259 22 0.92 0.88 39.22 220 343 466 618 857 1,136 1,369 1,613 1,896 2,274 3,225 3,792 4,547 30 0.90 0.89 54.06 335 445 619 822 992 1,171 1,379 1,658 2,341 2,758 3,316 37 0.92 0.90 64.50 371 516 687 830 982 1,159 1,398 1,964 2,319 2,796 45 0.92 0.90 78.44 424 565 683 807 953 1,150 1,615 1,907 2,299 55 0.91 0.87 100.27 446 536 631 740 885 1,262 1,480 1,771 75 0.92 0.89 132.21 479 564 678 957 1,128 1,356 90 0.94 0.90 153.55 487 587 825 974 1,175

110 0.94 0.90 187.67 675 797 961 132 0.90 0.93 227.63 560 666 811 150 0.90 0.93 258.67 493 586 714

NO

T A

PPLIC

AB

LE

Page 30: CABLE-SIZING

Attachment #16

CABLE SELECTION TABLE FOR 400V POWER FEEDER(CABLE LADDER) REVISION : 2 DATE : 07 Aug. '03

**NOTE1. MOTOR VOLTAGE : 400 V (3 PHASE)2. ALLOWABLE VOLTAGE DROP: 5 % (UNDER NORMAL RUNNING CONDITION)

3. VALUE OF R & X : REFER TO ATTACHMENT #9 V x ALLOWABLE VOLTAGE DROP x 1000

4. DERATED FACTOR : 0.588 5. MAX. CABLE LENGTH[m] =

√3 x FLC x (Rcosθ + Xsinθ)

* INSTALLATION CONDITION : AMBIENT TEMP. : 48 ℃

MAX. ALLOWABLE TEMP. OF CONDUCTOR : 90 ℃

SPECIFICATION XLPE/PVC/DSTA/PVC (3CORE+NEUTRAL)SIZE 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 1C-185 1C-240 1C-300

CABLE RESISTANCE[ohm/km] 15.4300 9.4500 5.8800 3.9300 2.3300 1.4700 0.9270 0.6690 0.4940 0.3430 0.2470 0.1970 0.1600 0.1290 0.0997 0.1280 0.0987 0.0799REACTANCE[ohm/km] 0.1220 0.1160 0.1100 0.1000 0.0940 0.0911 0.0911 0.0911 0.0879 0.0879 0.0879 0.0879 0.0879 0.0879 0.0879 0.0973 0.0942 0.0911IMPEDANCE [ohm/km] 15.4305 9.4507 5.8810 3.9313 2.3319 1.4728 0.9315 0.6752 0.5018 0.3541 0.2622 0.2157 0.1826 0.1561 0.1329 0.1608 0.1364 0.1212

AMPACITY[A] 23 32 42 54 75 100 127 157 192 246 298 346 399 456 538 509 604 699DERATED AMPACITY[A] 13.52 18.82 24.70 31.75 44.10 58.80 74.68 92.32 112.90 144.65 175.22 203.45 234.61 268.13 316.34 299.29 355.15 411.01

FEEDER MAXIMUM ALLOWABLE CABLE LENGTH kW EFF. P.F FLC[A] [M]

0.5 1.00 1.00 0.72 1,693 2,721 4,071 6,867 10,884 17,259 23,916 32,388 46,646 64,775 81,216 99,997 124,027 160,477 124,996 162,103 200,244 0.75 1.00 1.00 1.08 1,129 1,814 2,714 4,578 7,256 11,506 15,944 21,592 31,097 43,184 54,144 66,665 82,685 106,984 83,331 108,068 133,496 1.0 1.00 1.00 1.44 847 1,361 2,036 3,433 5,442 8,630 11,958 16,194 23,323 32,388 40,608 49,999 62,014 80,238 62,498 81,051 100,122 1.5 1.00 1.00 2.17 564 907 1,357 2,289 3,628 5,753 7,972 10,796 15,549 21,592 27,072 33,332 41,342 53,492 41,665 54,034 66,748

2 1.00 1.00 2.89 423 680 1,018 1,717 2,721 4,315 5,979 8,097 11,661 16,194 20,304 24,999 31,007 40,119 31,249 40,526 50,061 4 1.00 1.00 5.77 212 340 509 858 1,361 2,157 2,989 4,048 5,831 8,097 10,152 12,500 15,503 20,060 15,625 20,263 25,031 5 1.00 1.00 7.22 169 272 407 687 1,088 1,726 2,392 3,239 4,665 6,478 8,122 10,000 12,403 16,048 12,500 16,210 20,024

7.5 1.00 1.00 10.83 113 181 271 458 726 1,151 1,594 2,159 3,110 4,318 5,414 6,666 8,268 10,698 8,333 10,807 13,350 10 1.00 1.00 14.43 85 136 204 343 544 863 1,196 1,619 2,332 3,239 4,061 5,000 6,201 8,024 6,250 8,105 10,012 15 1.00 1.00 21.65 91 136 229 363 575 797 1,080 1,555 2,159 2,707 3,333 4,134 5,349 4,167 5,403 6,675 20 1.00 1.00 28.87 102 172 272 431 598 810 1,166 1,619 2,030 2,500 3,101 4,012 3,125 4,053 5,006 25 1.00 1.00 36.09 137 218 345 478 648 933 1,296 1,624 2,000 2,481 3,210 2,500 3,242 4,005 30 1.00 1.00 43.30 114 181 288 399 540 777 1,080 1,354 1,667 2,067 2,675 2,083 2,702 3,337 40 1.00 1.00 57.74 136 216 299 405 583 810 1,015 1,250 1,550 2,006 1,562 2,026 2,503 50 1.00 1.00 72.17 173 239 324 466 648 812 1,000 1,240 1,605 1,250 1,621 2,002 75 1.00 1.00 108.26 216 311 432 541 667 827 1,070 833 1,081 1,335 90 1.00 1.00 129.91 259 360 451 556 689 892 694 901 1,112

100 1.00 1.00 144.34 233 324 406 500 620 802 625 811 1,001 120 1.00 1.00 173.21 270 338 417 517 669 521 675 834 150 1.00 1.00 216.51 333 413 535 417 540 667 200 1.00 1.00 288.68 401 312 405 501

NO

T A

PPLIC

AB

LE

Page 31: CABLE-SIZING

Attachment #17

CABLE SELECTION TABLE FOR 400V POWER FEEDER(TRENCH) REVISION : 2 DATE : 07 Aug. '03

**NOTE1. MOTOR VOLTAGE : 400 V (3 PHASE)2. ALLOWABLE VOLTAGE DROP: 5 % (UNDER NORMAL RUNNING CONDITION)

3. VALUE OF R & X : REFER TO ATTACHMENT #9 V x ALLOWABLE VOLTAGE DROP x 1000

4. DERATED FACTOR : 0.528 5. MAX. CABLE LENGTH[m] =

√3 x FLC x (Rcosθ + Xsinθ)

* INSTALLATION CONDITION : AMBIENT TEMP. : 48 ℃

MAX. ALLOWABLE TEMP. OF CONDUCTOR : 90 ℃

SPECIFICATION XLPE/PVC/DSTA/PVC (3CORE+NEUTRAL)SIZE 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 1C-185 1C-240 1C-300

CABLE RESISTANCE[ohm/km] 15.4300 9.4500 5.8800 3.9300 2.3300 1.4700 0.9270 0.6690 0.4940 0.3430 0.2470 0.1970 0.1600 0.1290 0.0997 0.1280 0.0987 0.0799REACTANCE[ohm/km] 0.1220 0.1160 0.1100 0.1000 0.0940 0.0911 0.0911 0.0911 0.0879 0.0879 0.0879 0.0879 0.0879 0.0879 0.0879 0.0973 0.0942 0.0911IMPEDANCE [ohm/km] 15.4305 9.4507 5.8810 3.9313 2.3319 1.4728 0.9315 0.6752 0.5018 0.3541 0.2622 0.2157 0.1826 0.1561 0.1329 0.1608 0.1364 0.1212

AMPACITY[A] 22 29 37 46 61 79 101 122 144 178 211 240 271 304 351 363 419 474DERATED AMPACITY[A] 11.62 15.31 19.54 24.29 32.21 41.71 53.33 64.42 76.03 93.98 111.41 126.72 143.09 160.51 185.33 191.66 221.23 250.27

FEEDER MAXIMUM ALLOWABLE CABLE LENGTH kW EFF. P.F FLC[A] [M]

0.5 1.00 1.00 0.72 1,693 2,721 4,071 6,867 10,884 17,259 23,916 32,388 46,646 64,775 81,216 99,997 124,027 160,477 124,996 162,103 200,244 0.75 1.00 1.00 1.08 1,129 1,814 2,714 4,578 7,256 11,506 15,944 21,592 31,097 43,184 54,144 66,665 82,685 106,984 83,331 108,068 133,496 1.0 1.00 1.00 1.44 847 1,361 2,036 3,433 5,442 8,630 11,958 16,194 23,323 32,388 40,608 49,999 62,014 80,238 62,498 81,051 100,122 1.5 1.00 1.00 2.17 564 907 1,357 2,289 3,628 5,753 7,972 10,796 15,549 21,592 27,072 33,332 41,342 53,492 41,665 54,034 66,748

2 1.00 1.00 2.89 423 680 1,018 1,717 2,721 4,315 5,979 8,097 11,661 16,194 20,304 24,999 31,007 40,119 31,249 40,526 50,061 4 1.00 1.00 5.77 212 340 509 858 1,361 2,157 2,989 4,048 5,831 8,097 10,152 12,500 15,503 20,060 15,625 20,263 25,031 5 1.00 1.00 7.22 169 272 407 687 1,088 1,726 2,392 3,239 4,665 6,478 8,122 10,000 12,403 16,048 12,500 16,210 20,024

7.5 1.00 1.00 10.83 113 181 271 458 726 1,151 1,594 2,159 3,110 4,318 5,414 6,666 8,268 10,698 8,333 10,807 13,350 10 1.00 1.00 14.43 85 136 204 343 544 863 1,196 1,619 2,332 3,239 4,061 5,000 6,201 8,024 6,250 8,105 10,012 15 1.00 1.00 21.65 136 229 363 575 797 1,080 1,555 2,159 2,707 3,333 4,134 5,349 4,167 5,403 6,675 20 1.00 1.00 28.87 172 272 431 598 810 1,166 1,619 2,030 2,500 3,101 4,012 3,125 4,053 5,006 25 1.00 1.00 36.09 218 345 478 648 933 1,296 1,624 2,000 2,481 3,210 2,500 3,242 4,005 30 1.00 1.00 43.30 288 399 540 777 1,080 1,354 1,667 2,067 2,675 2,083 2,702 3,337 40 1.00 1.00 57.74 299 405 583 810 1,015 1,250 1,550 2,006 1,562 2,026 2,503 50 1.00 1.00 72.17 324 466 648 812 1,000 1,240 1,605 1,250 1,621 2,002 75 1.00 1.00 108.26 432 541 667 827 1,070 833 1,081 1,335 90 1.00 1.00 129.91 556 689 892 694 901 1,112

100 1.00 1.00 144.34 620 802 625 811 1,001 120 1.00 1.00 173.21 669 521 675 834 150 1.00 1.00 216.51 540 667 200 1.00 1.00 288.68

NO

T A

PPLIC

AB

LE

Page 32: CABLE-SIZING

Attachment #18

CABLE SELECTION TABLE FOR 230VAC POWER FEEDER(CABLE LADDER) REVISION : 2

South Pars Phase 4&5 Project (32002011) DATE : 07 Aug. '03

**NOTE1. VOLTAGE : 230 V (1 PHASE)2. ALLOWABLE VOLTAGE DROP 1 % (UPS POWER SUPPLIES MAIN POWER CABLES BETWEEN BATTERIES AND MAIN EQUIPMENT CUBICLES)

3. VALUE OF R & X REFER TO ATTACHMENT #9 V x ALLOWABLE VOLTAGE DROP x 1000

4. DERATED FACTOR 0.588 5. MAX. CABLE LENGTH[m] =

2 x FLC x (Rcosθ + Xsinθ)

* INSTALLATION CONDITION AMBIENT TEMP. : 48 ℃

MAX. ALLOWABLE TEMP. OF CONDUCTOR : 90 ℃

SPECIFICATION XLPE/PVC/DSTA/PVC (2CORE+EARTH)SIZE 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240

CABLE RESISTANCE[ohm/km] 15.4300 9.4500 5.8800 3.9300 2.3300 1.4700 0.9270 0.6690 0.4940 0.3420 0.2470 0.1960 0.1600 0.1280 0.0987REACTANCE[ohm/km] 0.1220 0.0932 0.0875 0.0837 0.0785 0.0761 0.0768 0.0743 0.0739 0.0726 0.0708 0.0705 0.0709 0.0712 0.0703IMPEDANCE [ohm/km] 15.4305 9.4505 5.8807 3.9309 2.3313 1.4720 0.9302 0.6731 0.4995 0.3496 0.2569 0.2083 0.1750 0.1465 0.1212

AMPACITY[A] 26 34 44 56 73 95 121 146 173 213 252 287 324 363 419DERATED AMPACITY[A] 15.29 19.99 25.87 32.93 42.92 55.86 71.15 85.85 101.72 125.24 148.18 168.76 190.51 213.44 246.37

FEEDER MAXIMUM ALLOWABLE CABLE LENGTH kVA kW EFF. P.F FLC[A] [M]

0.1 0.10 1.00 1.00 0.31 396 636 952 1,605 2,545 4,035 5,591 7,572 10,937 15,144 19,085 23,379 29,223 37,899 0.2 0.20 1.00 1.00 0.61 198 318 476 803 1,272 2,018 2,796 3,786 5,469 7,572 9,542 11,689 14,612 18,949 0.3 0.30 1.00 1.00 0.92 132 212 317 535 848 1,345 1,864 2,524 3,646 5,048 6,362 7,793 9,741 12,633 0.4 0.40 1.00 1.00 1.23 99 159 238 401 636 1,009 1,398 1,893 2,734 3,786 4,771 5,845 7,306 9,475 0.5 0.50 1.00 1.00 1.54 79 127 190 321 509 807 1,118 1,514 2,187 3,029 3,817 4,676 5,845 7,580 0.6 0.60 1.00 1.00 1.84 66 106 159 268 424 673 932 1,262 1,823 2,524 3,181 3,896 4,871 6,316 0.8 0.80 1.00 1.00 2.46 49 80 119 201 318 504 699 947 1,367 1,893 2,386 2,922 3,653 4,737 1.0 1.00 1.00 1.00 3.07 40 64 95 161 254 404 559 757 1,094 1,514 1,908 2,338 2,922 3,790 1.1 1.10 1.00 1.00 3.38 36 58 87 146 231 367 508 688 994 1,377 1,735 2,125 2,657 3,445 1.2 1.20 1.00 1.00 3.69 33 53 79 134 212 336 466 631 911 1,262 1,590 1,948 2,435 3,158 1.5 1.50 1.00 1.00 4.61 26 42 63 107 170 269 373 505 729 1,010 1,272 1,559 1,948 2,527 2.0 2.00 1.00 1.00 6.15 20 32 48 80 127 202 280 379 547 757 954 1,169 1,461 1,895 3.0 3.00 1.00 1.00 9.22 13 21 32 54 85 135 186 252 365 505 636 779 974 1,263 5.0 5.00 1.00 1.00 15.37 8 13 19 32 51 81 112 151 219 303 382 468 584 758

10.0 10.00 1.00 1.00 30.74 10 16 25 40 56 76 109 151 191 234 292 379 15.0 15.00 1.00 1.00 46.12 17 27 37 50 73 101 127 156 195 253 20.0 20.00 1.00 1.00 61.49 20 28 38 55 76 95 117 146 189 25.0 25.00 1.00 1.00 76.86 22 30 44 61 76 94 117 152 30.0 30.00 1.00 1.00 92.23 25 36 50 64 78 97 126 40.0 40.00 1.00 1.00 122.98 27 38 48 58 73 95

NO

T A

PPLIC

AB

LE

Page 33: CABLE-SIZING

Attachment #19

CABLE SELECTION TABLE FOR 230VAC POWER FEEDER(TRENCH) REVISION : 2

South Pars Phase 4&5 Project (32002011) DATE : 07 Aug. '03

**NOTE1. VOLTAGE : 230 V (1 PHASE)2. ALLOWABLE VOLTAGE DROP 3 % (WHEN SECONDARY PANEL IS LOCATED IN UNIT)

3. VALUE OF R & X REFER TO ATTACHMENT #9 V x ALLOWABLE VOLTAGE DROP x 1000

4. DERATED FACTOR 0.528 5. MAX. CABLE LENGTH[m] =

2 x FLC x (Rcosθ + Xsinθ)

* INSTALLATION CONDITION AMBIENT TEMP. : 48 ℃

MAX. ALLOWABLE TEMP. OF CONDUCTOR : 90 ℃

SPECIFICATION XLPE/PVC/DSTA/PVC (2CORE+EARTH)SIZE 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240

CABLE RESISTANCE[ohm/km] 15.4300 9.4500 5.8800 3.9300 2.3300 1.4700 0.9270 0.6690 0.4940 0.3420 0.2470 0.1960 0.1600 0.1280 0.0987REACTANCE[ohm/km] 0.1220 0.0932 0.0875 0.0837 0.0785 0.0761 0.0768 0.0743 0.0739 0.0726 0.0708 0.0705 0.0709 0.0712 0.0703IMPEDANCE [ohm/km] 15.4305 9.4505 5.8807 3.9309 2.3313 1.4720 0.9302 0.6731 0.4995 0.3496 0.2569 0.2083 0.1750 0.1465 0.1212

AMPACITY[A] 26 34 44 56 73 95 121 146 173 213 252 287 324 363 419DERATED AMPACITY[A] 13.73 17.95 23.23 29.57 38.54 50.16 63.89 77.09 91.34 112.46 133.06 151.54 171.07 191.66 221.23

FEEDER MAXIMUM ALLOWABLE CABLE LENGTH kVA kW EFF. P.F FLC[A] [M]

0.1 0.10 1.00 1.00 0.31 1,187 1,908 2,855 4,816 7,634 12,105 16,774 22,716 32,812 45,432 57,254 70,136 87,670 113,696 0.2 0.20 1.00 1.00 0.61 594 954 1,428 2,408 3,817 6,053 8,387 11,358 16,406 22,716 28,627 35,068 43,835 56,848 0.3 0.30 1.00 1.00 0.92 396 636 952 1,605 2,545 4,035 5,591 7,572 10,937 15,144 19,085 23,379 29,223 37,899 0.4 0.40 1.00 1.00 1.23 297 477 714 1,204 1,908 3,026 4,193 5,679 8,203 11,358 14,314 17,534 21,918 28,424 0.5 0.50 1.00 1.00 1.54 237 382 571 963 1,527 2,421 3,355 4,543 6,562 9,086 11,451 14,027 17,534 22,739 0.6 0.60 1.00 1.00 1.84 198 318 476 803 1,272 2,018 2,796 3,786 5,469 7,572 9,542 11,689 14,612 18,949 0.8 0.80 1.00 1.00 2.46 148 239 357 602 954 1,513 2,097 2,840 4,102 5,679 7,157 8,767 10,959 14,212 1.0 1.00 1.00 1.00 3.07 119 191 286 482 763 1,211 1,677 2,272 3,281 4,543 5,725 7,014 8,767 11,370 1.1 1.10 1.00 1.00 3.38 108 173 260 438 694 1,100 1,525 2,065 2,983 4,130 5,205 6,376 7,970 10,336 1.2 1.20 1.00 1.00 3.69 99 159 238 401 636 1,009 1,398 1,893 2,734 3,786 4,771 5,845 7,306 9,475 1.5 1.50 1.00 1.00 4.61 79 127 190 321 509 807 1,118 1,514 2,187 3,029 3,817 4,676 5,845 7,580 2.0 2.00 1.00 1.00 6.15 59 95 143 241 382 605 839 1,136 1,641 2,272 2,863 3,507 4,384 5,685 3.0 3.00 1.00 1.00 9.22 40 64 95 161 254 404 559 757 1,094 1,514 1,908 2,338 2,922 3,790 5.0 5.00 1.00 1.00 15.37 24 38 57 96 153 242 335 454 656 909 1,145 1,403 1,753 2,274

10.0 10.00 1.00 1.00 30.74 48 76 121 168 227 328 454 573 701 877 1,137 15.0 15.00 1.00 1.00 46.12 51 81 112 151 219 303 382 468 584 758 20.0 20.00 1.00 1.00 61.49 61 84 114 164 227 286 351 438 568 25.0 25.00 1.00 1.00 76.86 67 91 131 182 229 281 351 455 30.0 30.00 1.00 1.00 92.23 109 151 191 234 292 379 40.0 40.00 1.00 1.00 122.98 114 143 175 219 284

NO

T A

PPLIC

AB

LE

Page 34: CABLE-SIZING

Attachment #20

CABLE SELECTION TABLE FOR 230VAC POWER FEEDER(TRENCH) REVISION : 2

South Pars Phase 4&5 Project (32002011) DATE : 07 Aug. '03

**NOTE1. VOLTAGE : 230 V (1 PHASE)2. ALLOWABLE VOLTAGE DROP 5 % (WHEN SECONDARY PANEL IS LOCATED NEAR MAIN DISTRIBUTION PANEL IN SUBSTATION)

3. VALUE OF R & X REFER TO ATTACHMENT #9 V x ALLOWABLE VOLTAGE DROP x 1000

4. DERATED FACTOR 0.528 5. MAX. CABLE LENGTH[m] =

2 x FLC x (Rcosθ + Xsinθ)

* INSTALLATION CONDITION AMBIENT TEMP. : 48 ℃

MAX. ALLOWABLE TEMP. OF CONDUCTOR : 90 ℃

SPECIFICATION XLPE/PVC/DSTA/PVC (2CORE+EARTH)SIZE 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240

CABLE RESISTANCE[ohm/km] 15.4300 9.4500 5.8800 3.9300 2.3300 1.4700 0.9270 0.6690 0.4940 0.3420 0.2470 0.1960 0.1600 0.1280 0.0987REACTANCE[ohm/km] 0.1220 0.0932 0.0875 0.0837 0.0785 0.0761 0.0768 0.0743 0.0739 0.0726 0.0708 0.0705 0.0709 0.0712 0.0703IMPEDANCE [ohm/km] 15.4305 9.4505 5.8807 3.9309 2.3313 1.4720 0.9302 0.6731 0.4995 0.3496 0.2569 0.2083 0.1750 0.1465 0.1212

AMPACITY[A] 26 34 44 56 73 95 121 146 173 213 252 287 324 363 419DERATED AMPACITY[A] 13.73 17.95 23.23 29.57 38.54 50.16 63.89 77.09 91.34 112.46 133.06 151.54 171.07 191.66 221.23

FEEDER MAXIMUM ALLOWABLE CABLE LENGTH kVA kW EFF. P.F FLC[A] [M]

0.1 0.10 1.00 1.00 0.31 1,979 3,181 4,759 8,027 12,723 20,176 27,957 37,860 54,687 75,721 95,423 116,894 146,117 189,493 0.2 0.20 1.00 1.00 0.61 990 1,590 2,380 4,014 6,362 10,088 13,978 18,930 27,344 37,860 47,712 58,447 73,058 94,747 0.3 0.30 1.00 1.00 0.92 660 1,060 1,586 2,676 4,241 6,725 9,319 12,620 18,229 25,240 31,808 38,965 48,706 63,164 0.4 0.40 1.00 1.00 1.23 495 795 1,190 2,007 3,181 5,044 6,989 9,465 13,672 18,930 23,856 29,223 36,529 47,373 0.5 0.50 1.00 1.00 1.54 396 636 952 1,605 2,545 4,035 5,591 7,572 10,937 15,144 19,085 23,379 29,223 37,899 0.6 0.60 1.00 1.00 1.84 330 530 793 1,338 2,121 3,363 4,659 6,310 9,115 12,620 15,904 19,482 24,353 31,582 0.8 0.80 1.00 1.00 2.46 247 398 595 1,003 1,590 2,522 3,495 4,733 6,836 9,465 11,928 14,612 18,265 23,687 1.0 1.00 1.00 1.00 3.07 198 318 476 803 1,272 2,018 2,796 3,786 5,469 7,572 9,542 11,689 14,612 18,949 1.1 1.10 1.00 1.00 3.38 180 289 433 730 1,157 1,834 2,542 3,442 4,972 6,884 8,675 10,627 13,283 17,227 1.2 1.20 1.00 1.00 3.69 165 265 397 669 1,060 1,681 2,330 3,155 4,557 6,310 7,952 9,741 12,176 15,791 1.5 1.50 1.00 1.00 4.61 132 212 317 535 848 1,345 1,864 2,524 3,646 5,048 6,362 7,793 9,741 12,633 2.0 2.00 1.00 1.00 6.15 99 159 238 401 636 1,009 1,398 1,893 2,734 3,786 4,771 5,845 7,306 9,475 3.0 3.00 1.00 1.00 9.22 66 106 159 268 424 673 932 1,262 1,823 2,524 3,181 3,896 4,871 6,316 5.0 5.00 1.00 1.00 15.37 40 64 95 161 254 404 559 757 1,094 1,514 1,908 2,338 2,922 3,790

10.0 10.00 1.00 1.00 30.74 80 127 202 280 379 547 757 954 1,169 1,461 1,895 15.0 15.00 1.00 1.00 46.12 85 135 186 252 365 505 636 779 974 1,263 20.0 20.00 1.00 1.00 61.49 101 140 189 273 379 477 584 731 947 25.0 25.00 1.00 1.00 76.86 112 151 219 303 382 468 584 758 30.0 30.00 1.00 1.00 92.23 182 252 318 390 487 632 40.0 40.00 1.00 1.00 122.98 189 239 292 365 474

NO

T A

PPLIC

AB

LE

Page 35: CABLE-SIZING

Attachment #21

CABLE SELECTION TABLE FOR 230VAC MOTOR FEEDER(TRENCH) REVISION : 2 DATE : 07 Aug. '03

**NOTE1. VOLTAGE : 230 V (1 PHASE)2. ALLOWABLE VOLTAGE DROP 5 %

3. VALUE OF R & X REFER TO ATTACHMENT #9 V x ALLOWABLE VOLTAGE DROP x 1000

4. DERATED FACTOR 0.528 5. MAX. CABLE LENGTH[m] =

2 x FLC x (Rcosθ + Xsinθ)

* INSTALLATION CONDITION AMBIENT TEMP. : 48 ℃

MAX. ALLOWABLE TEMP. OF CONDUCTOR : 90 ℃

SPECIFICATION XLPE/PVC/STA/PVC (1CORE+NEUTRAL)SIZE 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240

CABLE RESISTANCE[ohm/km] 15.4300 9.4500 5.8800 3.9300 2.3300 1.4700 0.9270 0.6690 0.4940 0.3420 0.2470 0.1960 0.1600 0.1280 0.0987REACTANCE[ohm/km] 0.1220 0.0932 0.0875 0.0837 0.0785 0.0761 0.0768 0.0743 0.0739 0.0726 0.0708 0.0705 0.0709 0.0712 0.0703IMPEDANCE [ohm/km] 15.4305 9.4505 5.8807 3.9309 2.3313 1.4720 0.9302 0.6731 0.4995 0.3496 0.2569 0.2083 0.1750 0.1465 0.1212

AMPACITY[A] 26 34 44 56 73 95 121 146 173 213 252 287 324 363 419DERATED AMPACITY[A] 13.73 17.95 23.23 29.57 38.54 50.16 63.89 77.09 91.34 112.46 133.06 151.54 171.07 191.66 221.23

FEEDER MAXIMUM ALLOWABLE CABLE LENGTH HP kW EFF. P.F FLC[A] [M}

1/6 0.125 0.51 0.49 2.20 561 894 1,322 2,183 3,357 5,064 6,720 8,602 11,410 14,402 16,699 18,746 21,046 23,932 1/4 0.188 0.54 0.52 2.90 397 633 937 1,551 2,391 3,621 4,820 6,196 8,267 10,496 12,229 13,792 15,566 17,803 1/3 0.250 0.54 0.56 3.60 297 475 704 1,166 1,802 2,741 3,662 4,727 6,347 8,109 9,498 10,767 12,223 14,071 1/2 0.375 0.60 0.56 4.90 219 349 517 857 1,324 2,014 2,690 3,473 4,663 5,957 6,978 7,911 8,980 10,338

NO

T A

PPLIC

AB

LE

Page 36: CABLE-SIZING

Attachment #22

CABLE SELECTION TABLE FOR 48VDC POWER FEEDER REVISION : 2

South Pars Phase 4&5 Project (32002011) DATE : 07 Aug. '03

**NOTE1. VOLTAGE : 48 VDC2. ALLOWABLE VOLTAGE DROP 1 % (UPS POWER SUPPLIES MAIN POWER CABLES BETWEEN BATTERIES AND MAIN EQUIPMENT CUBICLES)

3. VALUE OF R & X REFER TO ATTACHMENT #9 V x ALLOWABLE VOLTAGE DROP x 1000

4. DERATED FACTOR 0.588 5. MAX. CABLE LENGTH[m] =

2 x FLC x R

* INSTALLATION CONDITION AMBIENT TEMP. : 48 ℃

MAX. ALLOWABLE TEMP. OF CONDUCTOR : 90 ℃

SPECIFICATION XLPE/PVC/STA/PVC (2C)SIZE 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240

CABLE RESISTANCE[ohm/km] 15.4300 9.4485 5.8782 3.9273 2.3334 1.4664 0.9270 0.6682 0.4935 0.3417 0.2461 0.1951 0.1581 0.1264 0.0961

AMPACITY[A] 26 34 44 56 73 95 121 146 173 213 252 287 324 363 419DERATED AMPACITY[A] 15.29 19.99 25.87 32.93 42.92 55.86 71.15 85.85 101.72 125.24 148.18 168.76 190.51 213.44 246.37

FEEDER MAXIMUM ALLOWABLE CABLE LENGTH kVA kW EFF. P.F FLC[A] [M]

0.1 0.10 1.00 1.00 2.08 12 20 29 49 79 124 172 233 337 468 590 729 912 1,198 0.2 0.20 1.00 1.00 4.17 6 10 15 25 39 62 86 117 169 234 295 364 456 599 0.3 0.30 1.00 1.00 6.25 4 7 10 16 26 41 57 78 112 156 197 243 304 399 0.4 0.40 1.00 1.00 8.33 3 5 7 12 20 31 43 58 84 117 148 182 228 300 0.5 0.50 1.00 1.00 10.42 2 4 6 10 16 25 34 47 67 94 118 146 182 240 0.6 0.60 1.00 1.00 12.50 2 3 5 8 13 21 29 39 56 78 98 121 152 200 0.8 0.80 1.00 1.00 16.67 2 2 4 6 10 16 22 29 42 59 74 91 114 150 1.0 1.00 1.00 1.00 20.83 2 3 5 8 12 17 23 34 47 59 73 91 120 1.1 1.10 1.00 1.00 22.92 2 3 4 7 11 16 21 31 43 54 66 83 109 1.2 1.20 1.00 1.00 25.00 2 2 4 7 10 14 19 28 39 49 61 76 100 1.5 1.50 1.00 1.00 31.25 2 3 5 8 11 16 22 31 39 49 61 80 2.0 2.00 1.00 1.00 41.67 2 4 6 9 12 17 23 30 36 46 60 3.0 3.00 1.00 1.00 62.50 4 6 8 11 16 20 24 30 40 5.0 5.00 1.00 1.00 104.17 7 9 12 15 18 24

10.0 10.00 1.00 1.00 208.33 9 12 15.0 15.00 1.00 1.00 312.5020.0 20.00 1.00 1.00 416.6725.0 25.00 1.00 1.00 520.8330.0 30.00 1.00 1.00 625.0040.0 40.00 1.00 1.00 833.33

NO

T A

PPLIC

AB

LE

Page 37: CABLE-SIZING

Attachment #23

CABLE SELECTION TABLE FOR 48VDC POWER FEEDER(TRENCH) REVISION : 2

South Pars Phase 4&5 Project (32002011) DATE : 07 Aug. '03

**NOTE1. VOLTAGE : 48 VDC2. ALLOWABLE VOLTAGE DROP 3 % (WHEN SECONDARY PANEL IS LOCATED IN UNIT)

3. VALUE OF R & X REFER TO ATTACHMENT #9 V x ALLOWABLE VOLTAGE DROP x 1000

4. DERATED FACTOR 0.528 5. MAX. CABLE LENGTH[m] =

2 x FLC x R

* INSTALLATION CONDITION AMBIENT TEMP. : 48 ℃

MAX. ALLOWABLE TEMP. OF CONDUCTOR : 90 ℃

SPECIFICATION XLPE/PVC/STA/PVC (2C)SIZE 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240

CABLE RESISTANCE[ohm/km] 15.4300 9.4485 5.8782 3.9273 2.3334 1.4664 0.9270 0.6682 0.4935 0.3417 0.2461 0.1951 0.1581 0.1264 0.0961

AMPACITY[A] 26 34 44 56 73 95 121 146 173 213 252 287 324 363 419DERATED AMPACITY[A] 13.73 17.95 23.23 29.57 38.54 50.16 63.89 77.09 91.34 112.46 133.06 151.54 171.07 191.66 221.23

FEEDER MAXIMUM ALLOWABLE CABLE LENGTH kVA kW EFF. P.F FLC[A] [M]

0.1 0.10 1.00 1.00 2.08 37 59 88 148 236 373 517 700 1,011 1,404 1,771 2,186 2,735 3,595 0.2 0.20 1.00 1.00 4.17 18 29 44 74 118 186 259 350 506 702 886 1,093 1,367 1,797 0.3 0.30 1.00 1.00 6.25 12 20 29 49 79 124 172 233 337 468 590 729 912 1,198 0.4 0.40 1.00 1.00 8.33 9 15 22 37 59 93 129 175 253 351 443 546 684 899 0.5 0.50 1.00 1.00 10.42 7 12 18 30 47 75 103 140 202 281 354 437 547 719 0.6 0.60 1.00 1.00 12.50 6 10 15 25 39 62 86 117 169 234 295 364 456 599 0.8 0.80 1.00 1.00 16.67 5 7 11 19 29 47 65 88 126 176 221 273 342 449 1.0 1.00 1.00 1.00 20.83 6 9 15 24 37 52 70 101 140 177 219 273 359 1.1 1.10 1.00 1.00 22.92 5 8 13 21 34 47 64 92 128 161 199 249 327 1.2 1.20 1.00 1.00 25.00 7 12 20 31 43 58 84 117 148 182 228 300 1.5 1.50 1.00 1.00 31.25 10 16 25 34 47 67 94 118 146 182 240 2.0 2.00 1.00 1.00 41.67 12 19 26 35 51 70 89 109 137 180 3.0 3.00 1.00 1.00 62.50 12 17 23 34 47 59 73 91 120 5.0 5.00 1.00 1.00 104.17 20 28 35 44 55 72

10.0 10.00 1.00 1.00 208.33 36 15.0 15.00 1.00 1.00 312.5020.0 20.00 1.00 1.00 416.6725.0 25.00 1.00 1.00 520.8330.0 30.00 1.00 1.00 625.0040.0 40.00 1.00 1.00 833.33

NO

T A

PPLIC

AB

LE

Page 38: CABLE-SIZING

Attachment #24

CABLE SELECTION TABLE FOR 48VDC POWER FEEDER(TRENCH) REVISION : 2

South Pars Phase 4&5 Project (32002011) DATE : 07 Aug. '03

**NOTE1. VOLTAGE : 48 VDC2. ALLOWABLE VOLTAGE DROP 5 % (WHEN SECONDARY PANEL IS LOCATED NEAR MAIN DISTRIBUTION PANEL IN SUBSTATION)

3. VALUE OF R & X REFER TO ATTACHMENT #9 V x ALLOWABLE VOLTAGE DROP x 1000

4. DERATED FACTOR 0.528 5. MAX. CABLE LENGTH[m] =

2 x FLC x R

* INSTALLATION CONDITION AMBIENT TEMP. : 48 ℃

MAX. ALLOWABLE TEMP. OF CONDUCTOR : 90 ℃

SPECIFICATION XLPE/PVC/STA/PVC (2C)SIZE 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240

CABLE RESISTANCE[ohm/km] 15.4300 9.4485 5.8782 3.9273 2.3334 1.4664 0.9270 0.6682 0.4935 0.3417 0.2461 0.1951 0.1581 0.1264 0.0961

AMPACITY[A] 26 34 44 56 73 95 121 146 173 213 252 287 324 363 419DERATED AMPACITY[A] 13.73 17.95 23.23 29.57 38.54 50.16 63.89 77.09 91.34 112.46 133.06 151.54 171.07 191.66 221.23

FEEDER MAXIMUM ALLOWABLE CABLE LENGTH kVA kW EFF. P.F FLC[A] [M]

0.1 0.10 1.00 1.00 2.08 61 98 147 247 393 621 862 1,167 1,686 2,341 2,952 3,643 4,558 5,991 0.2 0.20 1.00 1.00 4.17 30 49 73 123 196 311 431 584 843 1,170 1,476 1,821 2,279 2,996 0.3 0.30 1.00 1.00 6.25 20 33 49 82 131 207 287 389 562 780 984 1,214 1,519 1,997 0.4 0.40 1.00 1.00 8.33 15 24 37 62 98 155 216 292 421 585 738 911 1,140 1,498 0.5 0.50 1.00 1.00 10.42 12 20 29 49 79 124 172 233 337 468 590 729 912 1,198 0.6 0.60 1.00 1.00 12.50 10 16 24 41 65 104 144 195 281 390 492 607 760 999 0.8 0.80 1.00 1.00 16.67 8 12 18 31 49 78 108 146 211 293 369 455 570 749 1.0 1.00 1.00 1.00 20.83 10 15 25 39 62 86 117 169 234 295 364 456 599 1.1 1.10 1.00 1.00 22.92 9 13 22 36 56 78 106 153 213 268 331 414 545 1.2 1.20 1.00 1.00 25.00 12 21 33 52 72 97 140 195 246 304 380 499 1.5 1.50 1.00 1.00 31.25 16 26 41 57 78 112 156 197 243 304 399 2.0 2.00 1.00 1.00 41.67 20 31 43 58 84 117 148 182 228 300 3.0 3.00 1.00 1.00 62.50 21 29 39 56 78 98 121 152 200 5.0 5.00 1.00 1.00 104.17 34 47 59 73 91 120

10.0 10.00 1.00 1.00 208.33 60 15.0 15.00 1.00 1.00 312.5020.0 20.00 1.00 1.00 416.6725.0 25.00 1.00 1.00 520.8330.0 30.00 1.00 1.00 625.0040.0 40.00 1.00 1.00 833.33