Busbar Protection by GE

download Busbar Protection by GE

of 92

Transcript of Busbar Protection by GE

  • 8/17/2019 Busbar Protection by GE

    1/92

    Fundamentals of Fundamentals of 

    Bus BarBus BarProtectionProtection

    GE Multilin

  • 8/17/2019 Busbar Protection by GE

    2/92

    2

    GE Consumer & IndustrialMultilin

    May 3, 2016

     Outline

    • Bus arrangements• Bus components• Bus protection techniques• CT Saturation• Application Considerations: igh impedance !us di"erentialrela#ing $o% impedance !us di"erential

    rela#ing Special topics

  • 8/17/2019 Busbar Protection by GE

    3/92

    3

    GE Consumer & IndustrialMultilin

    May 3, 2016

    1 2 3 n-1 n

    ZONE 1

     

    - - - -

    •  &istri!ution and lo%er transmission

    'oltage le'els•  (o operating )e*i!ilit#

    •  Fault on the !us trips all circuit !rea+ers

    Single !us , single !rea+er

  • 8/17/2019 Busbar Protection by GE

    4/92

    4

    GE Consumer & IndustrialMultilin

    May 3, 2016

    ZONE 1ZONE 2

    •&istri!ution and lo%er transmission

    'oltage le'els

    •$imited operating )e*i!ilit#

    Multiple !us sections , single!rea+er %ith !us tie

  • 8/17/2019 Busbar Protection by GE

    5/92

    5

    GE Consumer & IndustrialMultilin

    May 3, 2016

    ZONE 1

    ZONE 2

    •Transmission and distri!ution 'oltage le'els•Brea+er maintenance %ithout circuit remo'al

    •Fault on a !us disconnects onl# the circuits

    !eing connected to that !us

    &ou!le !us , single !rea+er %ith!us tie

  • 8/17/2019 Busbar Protection by GE

    6/92

    6

    GE Consumer & IndustrialMultilin

    May 3, 2016

    ZONE 1

    MAIN BUS

    TRANFER BUS

    • -ncreased operating )e*i!ilit#•A !us fault requires tripping all

    !rea+ers

    •Transfer !us for !rea+er maintenance

    Main and transfer !uses

  • 8/17/2019 Busbar Protection by GE

    7/92

    7

    GE Consumer & IndustrialMultilin

    May 3, 2016

    ZONE 1

    ZONE 2

    •.er# high operating )e*i!ilit#•Transfer !us for !rea+er

    maintenance

    &ou!le !us / single !rea+er %0 tra

  • 8/17/2019 Busbar Protection by GE

    8/92

    8

    GE Consumer & IndustrialMultilin

    May 3, 2016

    ZONE 1

    ZONE 2

    •igh operating )e*i!ilit#•$ine protection co'ers !us section !et%een

    t%o CTs

    •Fault on a !us does not distur! the po%er to

    circuits

    &ou!le !us , dou!le !rea+er

  • 8/17/2019 Busbar Protection by GE

    9/92

    9

    GE Consumer & IndustrialMultilin

    May 3, 2016

    ZONE 1

    ZONE 2

    •1sed on higher 'oltage le'els

    •More operating )e*i!ilit#

    •2equires more !rea+ers

    •Middle !us sections co'ered !# line or

    other equipment protection

    Brea+er,and,a,half !us

  • 8/17/2019 Busbar Protection by GE

    10/92

    10

    GE Consumer & IndustrialMultilin

    May 3, 2016

    •igher 'oltage le'els•igh operating )e*i!ilit# %ith minimum

    !rea+ers

    •Separate !us protection not required at

    B1 B2

    TB1

    L1   L2

    L3 L4

    TB1

    2ing !us

  • 8/17/2019 Busbar Protection by GE

    11/92

    11

    GE Consumer & IndustrialMultilin

    May 3, 2016

    Bus components !rea+ers

    SF34 E. 5 . ,S nchro u"  

    $o% .oltage circuit!rea+ers

    BUS 2

    CB 1

    BUS 1

    ISO 1 ISO 2

    ISO 3

    BYPASS

  • 8/17/2019 Busbar Protection by GE

    12/92

    12

    GE Consumer & IndustrialMultilin

    May 3, 2016

    -

    +

    F1aF1c

    Contact Input F1a OnContact Input F1c On

    F1b

       I   S   O   L   A   T   O   R   1

    ISOLATOR 1 OPEN

    7B 7A

    BUS 1

    -

    +

    F1aF1c

    Contact Input F1a OnContact Input F1c On

    F1b

       I   S   O   L   A   T

       O   R   1

    ISOLATOR 1 CLOSED

    7B 7A

    BUS 1

    &isconnect s%itches 5 au*iliar#contacts

    BUS 2

    CB 1

    BUS 1

    ISO 1 ISO 2

    ISO 3

    BYPASS

  • 8/17/2019 Busbar Protection by GE

    13/92

    13

    GE Consumer & IndustrialMultilin

    May 3, 2016

    BUS 2

    CB 1

    BUS 1

    ISO 1 ISO 2

    ISO 3

    BYPASS

    Current Transformers 

    Oil insulated currenttransformer 678+. up to

    9+.;

    Gas 6SF3; insulatedcurrent transformer

    Bushing t#pe

    6medium 'oltages%itchgear;

  • 8/17/2019 Busbar Protection by GE

    14/92

    14

    GE Consumer & IndustrialMultilin

    May 3, 2016

    Protection 2equirements

    igh !us fault currents due to large num!er ofcircuits connected:• CT saturation often !ecomes a pro!lem as CTs ma# not !e

    su

  • 8/17/2019 Busbar Protection by GE

    15/92

    15

    GE Consumer & IndustrialMultilin

    May 3, 2016

    Bus Protection Techniques

    • -nterloc+ing schemes• O'ercurrent 6>unrestrained? or

    >un!iased?; di"erential

    • O'ercurrent percent 6>restrained? or>!iased?; di"erential

    • $inear couplers

    • igh,impedance !us di"erential schemes

    • $o%,impedance !us di"erential schemes

  • 8/17/2019 Busbar Protection by GE

    16/92

  • 8/17/2019 Busbar Protection by GE

    17/92

    17GE Consumer & Industrial

    Multilin

    May 3, 2016

    O'ercurrent 6unrestrained;&i"erential

    • &i"erential signal formed!# summation of allcurrents feeding the !us

    • CT ratio matching ma# !erequired

    • On e*ternal faults4saturated CTs #ieldspurious di"erentialcurrent

    • Time dela# used to cope%ith CT saturation

    • -nstantaneous di"erentialOC function useful onintegrated microprocessor,!ased rela#s

    51

  • 8/17/2019 Busbar Protection by GE

    18/92

    18GE Consumer & Industrial

    Multilin

    May 3, 2016

    59

    $inear Couplers

    ZC = 2 – 20 - typi!" #i" i$p%&!'%

    ()* p%+ 1000A$p, = 0.00)  / 0

    -f @9 A

    0 ! 10 ! 10 ! 0 ! 20 !

    2000 A

    0 !

    E*ternalFault

  • 8/17/2019 Busbar Protection by GE

    19/92

    19GE Consumer & Industrial

    Multilin

    May 3, 2016

    59

    $inearCouplersEsec@ -primDm , secondar# 'oltage on rela# terminals-2@ -primDm 062 C;  / minimum operating current

     %here4-prim / primar# current in each circuit

    Dm / liner coupler mutual reactance 68. per Amps @H I8  J

    3K ;2 / rela# tap impedance

     

    C / sum of all linear coupler self impedances-f @9 A

    0 ! 10 ! 10 ! 0 ! 20 !

    0 !

    -nternal BusFault

  • 8/17/2019 Busbar Protection by GE

    20/92

    20GE Consumer & Industrial

    Multilin

    May 3, 2016

    • Fast4 secure and pro'en

    • 2equire dedicated air gap CTs4 %hich ma# not!e used for an# other protection

    • Cannot !e easil# applied to reconLgura!le!uses

    • The scheme uses a simple 'oltage detector /it does not pro'ide !eneLts of amicroprocessor,!ased rela# 6eIgIoscillograph#4 !rea+er failure protection4other functions;

    $inearCouplers

  • 8/17/2019 Busbar Protection by GE

    21/92

    21GE Consumer & Industrial

    Multilin

    May 3, 2016

    igh -mpedance &i"erential• Operating signal created !#

    connecting all CT secondaries in

    parallelo CTs must all ha'e the same ratio

    o Must ha'e dedicated CTs

    • O'er'oltage element operateson 'oltage de'eloped acrossresistor connected in secondar#

    circuito 2equires 'aristors or AC

    shorting rela#s to limit energ#during faults

    • Accurac# dependent onsecondar# circuit resistance

    o 1suall# requires larger CTca!les to reduce errors ⇒ highercost

    Cannot easily be alied to re!on"#urablebuses and o$ers no ad%an!ed un!tionality

    )4

  • 8/17/2019 Busbar Protection by GE

    22/92

    22GE Consumer & Industrial

    Multilin

    May 3, 2016

    Percent &i"erential

    • Percent characteristicused to cope %ith CTsaturation and othererrors

    • 2estraining signal can

    !e formed in a num!erof %a#s

    • (o dedicated CTsneeded

    • 1sed for protection ofre,conLgura!le !usespossi!le

    51"7

    n DIF   I  I  I  I    +++=   ...21

    n RES   I  I  I  I    +++=   ...21   ( )n RES    I  I  I  I    ...,,,max 21=

  • 8/17/2019 Busbar Protection by GE

    23/92

    23GE Consumer & Industrial

    Multilin

    May 3, 2016

    $o% -mpedance Percent&i"erential• -ndi'idual currents sampled !# protection and summateddigitall#

    o CT ratio matching done internall# 6no au*iliar# CTs;

    o &edicated CTs not necessar#

    • Additional algorithms impro'e securit# of percent di"erentialcharacteristic during CT saturation

    • namic !us replica allo%s application to reconLgura!le !useso &one digitall# %ith logic to add0remo'e current inputs from

    di"erential computation

    o S%itching of CT secondar# circuits not required

    • $o% secondar# !urdens

    • Additional functionalit# a'aila!le

    o &igital oscillograph# and monitoring of each circuit connected to!us Kone

    o Time,stamped e'ent recording

    o Brea+er failure protection

  • 8/17/2019 Busbar Protection by GE

    24/92

    24GE Consumer & Industrial

    Multilin

    May 3, 2016

    &igital &i"erential AlgorithmGoals• -mpro'e the main di"erential algorithm operationo Better Lltering

    o Faster response

    o Better restraint techniques

    o S%itching transient !loc+ing

    • Pro'ide d#namic !us replica for reconLgura!le !us !ars• &ependa!l# detect CT saturation in a fast and relia!le

    manner4 especiall# for e*ternal faults

    • -mplement additional securit# to the main di"erentialalgorithm to pre'ent incorrect operation

    oE*ternal faults %ith CT saturationo CT secondar# circuit trou!le 6eIgI short circuits;

  • 8/17/2019 Busbar Protection by GE

    25/92

    25GE Consumer & Industrial

    Multilin

    May 3, 2016

    $o% -mpedance &i"erential6&istri!uted;

    • &ata Acquisition 1nits

    6&A1s; installed in !a#s• Central Processing 1nit

    6CP1; processes all datafrom &A1s

    • Communications !et%een

    &A1s and CP1 o'er L!erusing proprietar# protocol

    • Sampling s#nchronisation!et%een &A1s is required

    • Percei'ed less relia!le

    6more hard%are needed;• &i

  • 8/17/2019 Busbar Protection by GE

    26/92

    26GE Consumer & Industrial

    Multilin

    May 3, 2016

    $o% -mpedance &i"erential6CentraliKed;

    • All currents applied to asingle central processor

    • (o communications4e*ternal samplings#nchronisation necessar#

    • Percei'ed more relia!le6less hard%are needed;

    • =ell suited to !oth ne%and retroLt applicationsI

    52 52 52

    CU

    copp$% 

  • 8/17/2019 Busbar Protection by GE

    27/92

    27GE Consumer & Industrial

    Multilin

    May 3, 2016

    CT Saturation

  • 8/17/2019 Busbar Protection by GE

    28/92

    28GE Consumer & Industrial

    Multilin

    May 3, 2016

    CT Saturation Concepts

    • CT saturation depends on a num!er of factorso Ph#sical CT characteristics 6siKe4 rating4 %inding

    resistance4 saturation 'oltage;

    o Connected CT secondar# !urden 6%ires rela#s;

    o Primar# current magnitude4 &C o"set 6s#stem D02;

    o 2esidual )u* in CT core• Actual CT secondar# currents ma# not !eha'e in the same

    manner as the ratio 6scaled primar#; current during faults

    • End result is spurious di"erential current appearing in thesummation of the secondar# currents %hich ma# cause

    di"erential elements to operate if additional securit# isnot applied

  • 8/17/2019 Busbar Protection by GE

    29/92

    29GE Consumer & Industrial

    Multilin

    May 3, 2016

    CT Saturation

    (at'o Cu%%$nt C) Cu%%$nt

    (at'o Cu% %$nt C) Cu% %$nt

    (o &C O"set

    • =a'eform remainsfairl# s#mmetrical

    =ith &C O"set

    • =a'eform starts o"!eing as#mmetrical4then s#mmetrical instead# state

  • 8/17/2019 Busbar Protection by GE

    30/92

    30GE Consumer & Industrial

    Multilin

    May 3, 2016

    E*ternal Fault 5 -deal CTs

    • Fault starts at t

    • Stead#,state fault conditions occur at t

    t0

    t1

    -deal CTs ha'e no saturation or mismatcherrors thus produce no di"erential current

  • 8/17/2019 Busbar Protection by GE

    31/92

    31GE Consumer & Industrial

    Multilin

    May 3, 2016

    E*ternal Fault 5 Actual CTs

    • Fault starts at t

    • Stead#,state fault conditions occur at t

    t0

    t1

    Actual CTs do introduce errors4 producing somedi"erential current 6%ithout CT saturation;

  • 8/17/2019 Busbar Protection by GE

    32/92

    32GE Consumer & Industrial

    MultilinMay 3, 2016

    E*ternal Fault %ith CTSaturation

    • Fault starts at t4 CT !egins to saturate at t

    • CT full# saturated at t

    t0

    t1

    t2

    CT saturation causes increasing di"erentialcurrent that ma# enter the di"erential

    element operate regionI

  • 8/17/2019 Busbar Protection by GE

    33/92

    33GE Consumer & Industrial

    MultilinMay 3, 2016

    Some Methods of Securing Bus&i"erential• Bloc+ the !us di"erential for a period of time 6intentional dela#;

    o -ncreases securit# as !us Kone %ill not trip %hen CT saturation ispresent

    o Pre'ents high,speed clearance for internal faults %ith CT saturationor e'ol'ing faults

    • Change settings of the percent di"erential characteristic

    6usuall# Slope ;o -mpro'es securit# of di"erential element !# increasing the amount

    of spurious di"erential current needed to incorrectl# trip

    o &i

  • 8/17/2019 Busbar Protection by GE

    34/92

    34GE Consumer & Industrial

    MultilinMay 3, 2016

    igh,

    -mpedance

    Bus&i"erential

  • 8/17/2019 Busbar Protection by GE

    35/92

    35GE Consumer & Industrial

    MultilinMay 3, 2016

    igh -mpedance .oltage,operated 2ela#

    E*ternal Fault• 59 element set abo%e ma' ossible %olta#ede%eloed a!ross relay durin# e'ternal ault !ausin#(orst !ase C) saturation• *or internal aults+ e'tremely ,i#, %olta#es -(ell

    abo%e 59 element i!.u/ (ill de%elo a!ross relay 

  • 8/17/2019 Busbar Protection by GE

    36/92

    36GE Consumer & Industrial

    MultilinMay 3, 2016

    igh -mpedance .oltageOperated 2ela# 2atio matching %ith

    Multi,ratio CTs• li!ation o ,i#, imedan!e di$erential relays(it, C)s o di$erent ratios but ratio mat!,in# tas isossible+ but !ould lead to %olta#e ma#ni"!ation

    • olta#e de%eloed a!ross ull (indin# o taed C)does not e'!eed C) ratin#+ terminal blo!.s+ et!

  • 8/17/2019 Busbar Protection by GE

    37/92

    37GE Consumer & Industrial

    MultilinMay 3, 2016

    igh -mpedance .oltageOperated 2ela# 2atio matching %ith

    Multi,ratio CTs• se o au'iliary C)s to obtain !orre!t ratio mat!,in#is also ossible+ but t,ese C)s must be able to deli%erenou#, %olta#e ne!essary to rodu!e relay oerationor internal aults

  • 8/17/2019 Busbar Protection by GE

    38/92

    38GE Consumer & Industrial

    MultilinMay 3, 2016

    Electromechanical igh-mpedance Bus &i"erential

    2ela#s• Single phase rela#s• igh,speed

    • igh impedance 'oltage sensing

    • igh seismic -OC unit 

    P ! d i h - d B

  • 8/17/2019 Busbar Protection by GE

    39/92

    39GE Consumer & Industrial

    MultilinMay 3, 2016

    Op$%at'n* t'+$, 20 30+. / I 15K

    µP ,!ased igh,-mpedance Bus&i"erential Protection 2ela#s

  • 8/17/2019 Busbar Protection by GE

    40/92

    40GE Consumer & Industrial

    MultilinMay 3, 2016

    2ST @   , sta!iliKing resistor to limit thecurrent through the rela#4 and force it tothe lo%er impedance CT %indingsIMO. / Metal O*ide .aristor to limit the'oltage to .olts93 / latching contact pre'enting theresistors from o'erheating after the fault is

    detected

    igh -mpedance Module for&igital 2ela#s

    i h - d M d l

  • 8/17/2019 Busbar Protection by GE

    41/92

    41GE Consumer & Industrial

    MultilinMay 3, 2016

    igh,-mpedance Module

    O'ercurrent 2ela#

  • 8/17/2019 Busbar Protection by GE

    42/92

    42GE Consumer & Industrial

    MultilinMay 3, 2016

    • Fast4 secure and pro'en

    • 2equires dedicated CTs4 prefera!l# %ith the sameCT ratio and using full tap

    • Can !e applied to small !uses

    • &epending on !us internal and e*ternal faultcurrents4 high impedance !us di" ma# not pro'ideadequate settings for !oth sensiti'it# and securit#

    • Cannot !e easil# applied to reconLgura!le !uses

    • 2equire 'oltage limiting 'aristor capa!le ofa!sor!ing signiLcant energ#

    • Ma# require au*iliar# CTs• &o not pro'ide full !eneLts of microprocessor,

    !ased rela# s#stem 6eIgI metering4 monitoring4oscillograph#4 etcI;

    igh -mpedance Bus Protection ,Summar#

  • 8/17/2019 Busbar Protection by GE

    43/92

    43GE Consumer & Industrial

    MultilinMay 3, 2016

    $o%,

    -mpedance

    Bus&i"erential

  • 8/17/2019 Busbar Protection by GE

    44/92

    44GE Consumer & Industrial

    MultilinMay 3, 2016

    µP,!ased $o%,-mpedance 2ela#s

    • (o need for dedicated CTs

    • -nternal CT ratio mismatch compensation

    • Ad'anced algorithms supplement percent diferential

     protection function ma+ing the rela# 'er# secure

    • namic !us replica 6!us image; principle is used in

    protection of reconLgura!le !us !ars4 eliminating the

    need for s%itching ph#sicall# secondar# current

    circuits

    • -ntegrated Brea+er Failure 6BF; function can pro'ide

    optimal tripping strateg# depending on the actualconLguration of a !us !ar

  • 8/17/2019 Busbar Protection by GE

    45/92

    45GE Consumer & Industrial

    MultilinMay 3, 2016

    • 1p to Current -nputs• ones

    • one @ Phase A• one @ Phase B• one 7 @ Phase C• one @ (ot used

    • &i"erent CT 2atioCapa!ilit# for EachCircuit

    • $argest CT Primar# isBase in 2ela#

    ,9 CircuitApplications

    Small Bus Applications

  • 8/17/2019 Busbar Protection by GE

    46/92

    46GE Consumer & Industrial

    MultilinMay 3, 2016

    • 2ela# , Current -nputs

    • ones• one @ Phase A 6 currents;• one @ Phase B 6 currents;• one 7 @ (ot used• one @ (ot used

    C12

    C11

    • &i"erent CT 2atio Capa!ilit# for Each Circuit• $argest CT Primar# is Base in 2ela#

    • 2ela# , Current -nputs

    • ones• one @ (ot used• one @ (ot used• one 7 @ Phase C 6 currents;• one @ (ot used

    , CircuitApplications

    Medium to $arge BusApplications

  • 8/17/2019 Busbar Protection by GE

    47/92

    47GE Consumer & Industrial

    MultilinMay 3, 2016

    $arge Bus Applications

    56B p7!,% A

    56B p7!,% B

    56B p7!,% C

    L#8i +%"!y

    (,9it7 ,t!t:,;

    #pti#'!" BF

    $ B A li ti

  • 8/17/2019 Busbar Protection by GE

    48/92

    48GE Consumer & Industrial

    MultilinMay 3, 2016

    $arge Bus Applications*or buses (it, u to 24 !ir!uits

  • 8/17/2019 Busbar Protection by GE

    49/92

  • 8/17/2019 Busbar Protection by GE

    50/92

    50GE Consumer & Industrial

    MultilinMay 3, 2016

    &eLnitions of 2estraint Signals

    +a'+u+ o&6

    *$o+$t%'ca7 a8$%a*$6

    .ca7$ .u+ o&6

    .u+ o&6n R   iiiii   ++++=   ...321

    ( )n R   iiiin

    i   ++++=   ...1

    321

    ( )n R

      iiii Maxi   ,...,,, 321=

    nn R

      iiiii   ⋅⋅⋅⋅=   ...321

  • 8/17/2019 Busbar Protection by GE

    51/92

    51GE Consumer & Industrial

    MultilinMay 3, 2016

    >Sum Of? 'sI >Ma* Of? 2estraintMethods

    >Sum Of? Approach• ore restraint on e'ternal

    aults less sensiti%e or internalaults

    • :;!aled aroa!,ta.es into a!!ount number o!onne!ted !ir!uits and mayin!rease sensiti%ity

    • rea.oint settin#s or t,eer!ent di$erential!,ara!teristi! more di?!ult toset

    >Ma* Of? Approach• @ess restraint on e'ternal aults

    more sensiti%e or internal aults

    • rea.oint settin#s or t,eer!ent di$erential!,ara!teristi! easier to set

    • etter ,andles situation (,ereone C) may saturate !omletely-99A sloe settin#s ossible/

  • 8/17/2019 Busbar Protection by GE

    52/92

    52GE Consumer & Industrial

    MultilinMay 3, 2016

    Bus &i"erential Adapti'eApproach

                     9                 '                 &                 &             $             %             $             n

                    t                 '             a                 7

    %$.t%a'n'n*

    R%8i#' 1

    :7o; 9'&&$%$nt'a7

    cu%%$nt.<

    R%8i#' 2

    :='*= 9'&& $%$nt'a7

    cu%%$nt.<

  • 8/17/2019 Busbar Protection by GE

    53/92

    53GE Consumer & Industrial

    MultilinMay 3, 2016

    Bus &i"erential Adapti'e $ogic&iagram

    DIFL

    DIR

    SAT

    DIF

     OR

    AND

     O

    R56B BIASED OP

    AND

  • 8/17/2019 Busbar Protection by GE

    54/92

    54GE Consumer & Industrial

    MultilinMay 3, 2016

    Phase Comparison Principle• -nternal Faults: ll ault -:lar#e>/ !urrents are

    aro'imately in ,ase

    • E*ternal Faults: =ne ault -:lar#e>/ !urrent (ill be outo ,ase

    • (o .oltages are required or needed

    S$cona%> Cu%%$nt o&Fau7t$ C'%cu't

    :S$8$%$ C) Satu%at'on<

  • 8/17/2019 Busbar Protection by GE

    55/92

    55GE Consumer & Industrial

    MultilinMay 3, 2016

    Phase Comparison PrincipleContinuedQ

    BLOC=

    OPERATE

    BLOC=

      

     

     

     

     

    −   p D

     p

     I  I 

     I real 

       

      

     

    −   p D

     p

     I  I 

     I imag 

     I  p

     I  D

    - I  p

    E>t%+'!" F!:"t C#'&iti#',

    OPERATE

    BLOC=

    BLOC=

      

     

     

     

     

    −   p D p

     I  I 

     I real 

       

      

     

    −   p D

     p

     I  I 

     I imag 

     I  p

     I  D

    - I  p

    I't%+'!" F!:"t C#'&iti#',

    OPERATE

    OPERATE

  • 8/17/2019 Busbar Protection by GE

    56/92

    56GE Consumer & Industrial

    MultilinMay 3, 2016

    CT Saturation

    • *ault starts at t0+ C) be#ins to saturate at t1

    • C) ully saturated at t2

    t0

    t1

    t2

    i

  • 8/17/2019 Busbar Protection by GE

    57/92

    57GE Consumer & Industrial

    MultilinMay 3, 2016

    CT Saturation &etector StateMachine NORMAL

    SAT := 0

    EXTERNAL

    FAULT

    SAT := 1

    EXTERNAL

    FAULT & CTSATURATION

    SAT := 1

    The differential

    characteritic

    entered

    The differential!

    retrainin" tra#ect$r%

    $t $f the differential

    characteritic f$r

    certain 'eri$d $f ti(e

    atrati$n

    c$nditi$n

    The differential

    crrent )el$* the

    firt l$'e f$r

    certain 'eri$d $f 

    ti(e

    C S i

  • 8/17/2019 Busbar Protection by GE

    58/92

    58GE Consumer & Industrial

    MultilinMay 3, 2016

    CT Saturation &etectorOperating Principles

    • The 9B SAT )ag WILL NOT  !e set duringinternal faults4 regardless of %hether or notan# of the CTs saturateI

    • The 9B SAT )ag WILL !e set duringe*ternal faults4 regardless of %hether or notan# of the CTs saturateI

    • B# design4 the 9B SAT )ag WILL force the

    rela# to use the additional 9B &-2 phasecomparison for 2egion The Saturation &etector =-$$ (OT Bloc+ theOperation of the &i"erential Element / it %illonl# Force ,out,of, Operation

    CT S i &

  • 8/17/2019 Busbar Protection by GE

    59/92

    59GE Consumer & Industrial

    MultilinMay 3, 2016

    CT Saturation &etector ,E*amples• The oscillograph# records on the ne*t t%o slides %ere

    captured from a B7 rela# under test on a real,time digital

    po%er s#stem simulator• First slide sho%s an e*ternal fault %ith deep CT saturation

    6RI8 msec of good CT performance;

    o SAT saturation detector )ag asserts prior to B-ASE& PP!us di"erential pic+up

    o &-2 directional )ag does not assert 6one current )o%sout of Kone;4 so e'en though !us di"erential pic+s up4 notrip results

    • Second slide sho%s an internal fault %ith mild CT saturation

    o B-ASE& PP and B-ASE& OP !oth assert !efore &-2

    assertso CT saturation does not !loc+ !us di"erential

    • More e*amples a'aila!le 6COMT2A&E Lles; upon request

    CT S t ti E l

  • 8/17/2019 Busbar Protection by GE

    60/92

    60GE Consumer & Industrial

    MultilinMay 3, 2016

    )=$ bu. 9'&&$%$nt'a

    p%ot$ct'on $$+$ntp'c?. up 9u$ to =$a8>

    C) .atu%at'on

    )=$ C) .atu%at'on &a*

    '. .$t .a&$> b$&o%$ t=$p'c?up &a*

    )=$9'%$ct'ona &a*

    '. not .$t

    )=$ $$+$nt9o$. not

    +aop$%at$

    #$.p't$ =$a8> C).atu%at'on t=$$t$%na7 &au7t cu%%$nt'. .$$n 'n t=$oppo.'t$ '%$ct'on

    CT Saturation E*ample /E*ternal Fault

    0.06 0.07 0.08 0.09 0.1 0.11 0.12-200

    -150

    -100

    -50

    0

    50

    100

    150

    200

    time, sec

     c u r r e n t , A

    @1 +.

    CT S t ti - t l F lt

  • 8/17/2019 Busbar Protection by GE

    61/92

    61GE Consumer & Industrial

    MultilinMay 3, 2016

    )=$ bu. 9'&&$%$nt'ap%ot$ct'on $$+$ntp'c?. up

    )=$ .atu%at'on&a* '. not .$t - no

    9'%$ct'ona

    9$c'.'on %$u'%$9

    )=$ $$+$ntop$%at$. 'n

    10+.

    )=$9'%$ct'ona

    &a* '. .$t

    A t=$ &aut cu%%$nt.a%$ .$$n 'n on$

    9'%$ct'on

    CT Saturation / -nternal FaultE*ample

    A l i $ - d

  • 8/17/2019 Busbar Protection by GE

    62/92

    62GE Consumer & Industrial

    MultilinMay 3, 2016

    Appl#ing $o%,-mpedance&i"erential 2ela#s for Bus!ar

    ProtectionBasic Topics• ConLgure ph#sical CT -nputs

    • ConLgure Bus one and namic Bus

    2eplica• Calculating Bus &i"erential Element settings

    Ad'anced Topics

    • -solator s%itch monitoring for

    reconLgura!le !uses• &i"erential one CT Trou!le

    • -ntegrated Brea+er Failure protection

    C L i CT - t

  • 8/17/2019 Busbar Protection by GE

    63/92

    63GE Consumer & Industrial

    MultilinMay 3, 2016

    ConLguring CT -nputs

    •For each connected CT circuit enter Primar#rating and select Secondar# ratingI

    • Each 7,phase !an+ of CT inputs must !eassigned to a Signal Source that is used todeLne the Bus one and namic Bus 2eplica

    ;ome relays de"ne 1 u as t,ema'imum rimary !urrent o all o t,eC)s !onne!ted in t,e #i%en us Bone

    P 1 it C t & L iti

  • 8/17/2019 Busbar Protection by GE

    64/92

    64GE Consumer & Industrial

    MultilinMay 3, 2016

    Per,1nit Current &eLnition ,E*ample

    CurrentChannel

    Primar#

    Secondar#

    one

    CT,

    F 3200 A

    CT,

    F A 8 A

    CT,7

    F7 A A

    CT,

    F 7 A A

    CT,8

    F8 A 8 A

    CT,F3 5000 8 A

    • For one 4 pIuI @ 7 AP

    • For one 4 pIuI @ 8 AP

  • 8/17/2019 Busbar Protection by GE

    65/92

    C L i th B &i" ti l

  • 8/17/2019 Busbar Protection by GE

    66/92

    66GE Consumer & Industrial

    MultilinMay 3, 2016

    ConLguring the Bus &i"erentialone

    I ConLgure the ph#sical CT -nputso CT Primar# and Secondar# 'alues

    o Both 8 A and A inputs are supported !# the 12 hard%are

    o 2atio compensation done automaticall# for CT ratiodi"erences up to 7:

    I ConLgure AC Signal Sources

    7I ConLgure Bus one %ith namic Bus 2eplica

    Bus one settings deLnes the !oundaries of

    the &i"erential Protection and CT Trou!leMonitoringI

    & l P t &i" ti l

  • 8/17/2019 Busbar Protection by GE

    67/92

    67GE Consumer & Industrial

    MultilinMay 3, 2016

    &ual Percent &i"erentialCharacteristic

    i87B+%!?p#i't

    L#9

    B+%!?p#i't

    L#9 S"#p%

    i87 S"#p%

    i87 S%t

    (U'+%,t+!i'%&

    Mi' Pi?:p

  • 8/17/2019 Busbar Protection by GE

    68/92

    Calculating Bus &i"erential

  • 8/17/2019 Busbar Protection by GE

    69/92

    69GE Consumer & Industrial

    MultilinMay 3, 2016

    Calculating Bus &i"erentialSettings / Minimum Pic+up

    • &eLnes the minimum di"erential current requiredfor operation of the Bus one &i"erential element

    • Must !e set a!o'e ma*imum lea+age current not

    Koned o" in the !us di"erential Kone• Ma# also !e set a!o'e ma*imum load conditions

    for added securit# in case of CT trou!le4 !ut!etter alternati'es e*ist

  • 8/17/2019 Busbar Protection by GE

    70/92

    Calculating Bus &i"erential

  • 8/17/2019 Busbar Protection by GE

    71/92

    71GE Consumer & Industrial

    MultilinMay 3, 2016

    Calculating Bus &i"erentialSettings / $o% Brea+point

    • &eLnes the upper limit to restraint currents that %ill!e !iased according to the $o% Slope setting

    • Should !e set to !e a!o'e the ma*imum load !utnot more than the ma*imum current %here the CTs

    still operate linearl# 6including residual )u*;• Assumption is that the CTs %ill !e operating linearl#

    6no signiLcant saturation e"ects up to 9 residual)u*; up to the $o% Brea+point setting

    Calculating Bus &i"erential

  • 8/17/2019 Busbar Protection by GE

    72/92

    72GE Consumer & Industrial

    MultilinMay 3, 2016

    Calculating Bus &i"erentialSettings / igh Brea+point

    • &eLnes the minimum restraint currents that %ill !e!iased according to the igh Slope setting

    • Should !e set to !e !elo% the minimum current

    %here the %ea+est CT %ill saturate %ith noresidual )u*

    • Assumption is that the CTs %ill !e operatinglinearl# 6no signiLcant saturation e"ects up to 9residual )u*; up to the $o% Brea+point setting

    Calculating Bus &i"erential

  • 8/17/2019 Busbar Protection by GE

    73/92

    73GE Consumer & Industrial

    MultilinMay 3, 2016

    Calculating Bus &i"erentialSettings / igh Slope

    • &eLnes the percent !ias for the restraint currents-2EST≥igh Brea+point

    • Setting determines the sta!ilit# of the di"erentialelement for high current e*ternal faults

    • Traditionall#4 should !e set high enough toaccommodate the spurious di"erential currentresulting from saturation of the CTs during hea'#e*ternal faults

    • Setting can !e rela*ed in fa'our of sensiti'it# andspeed as the rela# detects CT saturation and applies

    the directional principle to pre'ent maloperation•  2ange: 8 to in I increments

  • 8/17/2019 Busbar Protection by GE

    74/92

  • 8/17/2019 Busbar Protection by GE

    75/92

  • 8/17/2019 Busbar Protection by GE

    76/92

    2econLgura!le Buses

  • 8/17/2019 Busbar Protection by GE

    77/92

    77GE Consumer & Industrial

    MultilinMay 3, 2016

    NO() BUS

    SOU) BUS

    C)-7

    C)-"

    B-7

    B-5

    B-

    C)-5

    C)-

    S-5

    S-

    B-C)-

    S-3

    S-

    B-3C)-3

    S-1

    S-2

    B-2C)-2C)-1

    B-1

    C-1 C-2 C-

    C-3 C-5

    %ot$ct'n* %$-con&'*u%ab7$ bu.$.

    2econLgura!le Buses

    2econLgura!le Buses

  • 8/17/2019 Busbar Protection by GE

    78/92

    78GE Consumer & Industrial

    MultilinMay 3, 2016

    NO() BUS

    SOU) BUS

    C)-7

    C)-"

    B-7

    B-5

    B-

    C)-5

    C)-

    S-5

    S-

    B-C)-

    S-3

    S-

    B-3C)-3

    S-1

    S-2

    B-2C)-2C)-1

    B-1

    C-1 C-2 C-

    C-3 C-5

    %ot$ct'n* %$-con&'*u%ab7$ bu.$.

    2econLgura!le Buses

    2econLgura!le Buses

  • 8/17/2019 Busbar Protection by GE

    79/92

    79GE Consumer & Industrial

    MultilinMay 3, 2016

    NO() BUS

    SOU) BUS

    C)-"

    B-5

    B-

    C)-5

    C)-

    S-5

    S-

    B-C)-

    S-3

    S-

    B-3C)-3

    S-1

    S-2

    B-2C)-2

    C)-1

    B-1

    C-1 C-2 C-

    C-3 C-5

    C)-7

    B-7

    %ot$ct'n* %$-con&'*u%ab7$ bu.$.

    2econLgura!le Buses

  • 8/17/2019 Busbar Protection by GE

    80/92

    -solator / T#pical Open0Closed

  • 8/17/2019 Busbar Protection by GE

    81/92

    81GE Consumer & Industrial

    MultilinMay 3, 2016

    -solator / T#pical Open0ClosedConnections

    S%itch Status $ogic and

  • 8/17/2019 Busbar Protection by GE

    82/92

    82GE Consumer & Industrial

    MultilinMay 3, 2016

    -solatorOpenAu*iliar#Contact

    -solatorClosedAu*iliar#Contact

    -solatorPosition

    Alarm Bloc+S%itching

    O" On C$OSE& (o (o

    O" O"   $AST .A$-& After timedela#untilac+no%ledged

    1ntil -solator

    Position is'alid

    On On C$OSE&

    On O"   OPE( (o (o

    (OTE: -solator monitoring function ma# !e a !uilt,in featureor user,programma!le in lo% impedance !us di"erentialdigital rela#s

    S c S a us og c a danamic Bus 2eplica

    &i"erential one CT Trou!le

  • 8/17/2019 Busbar Protection by GE

    83/92

    83GE Consumer & Industrial

    MultilinMay 3, 2016

    &i"erential one CT Trou!le

    • Each Bus &i"erential one ma# a dedicated CTTrou!le Monitor

    • &eLnite time dela# o'ercurrent element operatingon the Kone di"erential current4 !ased on theconLgured namic Bus 2eplica

    • Three strategies to deal %ith CT pro!lems:

    I Trip the !us Kone as the pro!lem %ith a CT %illli+el# e'ol'e into a !us fault an#%a#

    I &o not trip the !us4 raise an alarm and tr# tocorrect the pro!lem manuall#

    7I S%itch to setting group %ith 9B minimumpic+up setting a!o'e the ma*imum loadcurrentI

    &i"erential one CT Trou!le

  • 8/17/2019 Busbar Protection by GE

    84/92

    84GE Consumer & Industrial

    MultilinMay 3, 2016

    • Strategies and 7 can !eaccomplished !#: 1sing under'oltage super'ision to ride through

    the period from the !eginning of the pro!lem%ith a CT until declaring a CT trou!le condition

    1sing an e*ternal chec+ Kone to super'ise the9B function

    1sing CT Trou!le to pre'ent the Bus &i"erentialtripping 6;

    1sing setting groups to increase the pic+up

    'alue for the 9B function 67;

    &i"erential one CT Trou!le

    &i"erential one CT Trou!le /

  • 8/17/2019 Busbar Protection by GE

    85/92

    85GE Consumer & Industrial

    MultilinMay 3, 2016

    &i"erential one CT Trou!le /Strateg# V E*ample

    • CT Trou!le operand is used to rise an alarm

    • The 9B trip is inhi!ited after CT Trou!le elementoperates

    • The rela# ma# misoperate if an e*ternal fault

    occurs after CT trou!le !ut !efore the CT trou!lecondition is declared 6dou!le,contingenc#;

    56B #p%+!t%,

    U'&%+@#"t!8% #'&iti#'

    CT O

    E*ample Architecture for $arge

  • 8/17/2019 Busbar Protection by GE

    86/92

    86GE Consumer & Industrial

    Multilin

    May 3, 2016

    E*ample Architecture for $argeBus!ars

    &ual 6redundant; L!er%ith 7msec deli'er#time !et%een

    neigh!ouring -E&sI 1pto 9 rela#s in the ring

    Phase A C si#nals andtri !onta!ts

    Phase B C si#nals andtri !onta!ts

    Phase C C si#nals andtri !onta!ts

    &igital -nputs orisolator monitorin# and*

    E*ample Architecture / namic

  • 8/17/2019 Busbar Protection by GE

    87/92

    87GE Consumer & Industrial

    Multilin

    May 3, 2016

    Phase A C si#nals(ired ,ere+ bus reli!a!on"#ured ,ere

    Phase B C si#nals(ired ,ere+ bus reli!a!on"#ured ,ere

    Phase C C si#nals(ired ,ere+ bus reli!a

    !on"#ured ,ere

     Auu7'a%> .;'tc=$. ;'%$ =$%$D

    I.o7ato% on'to%'n* &unct'on

    con&'*u%$ =$%$

      I s o  l a  t o r 

      7 o s  i  t  i o

     n

    I s o l a t o r  7 o s i t i o n 

    I  s o l  a t  o r   7  o s i  t  i  o n 

     I s o l a t

     o r  7 o s i t i o n

    E*ample Architecture namicBus 2eplica and -solator

    Position

    E*ample Architecture / BF

  • 8/17/2019 Busbar Protection by GE

    88/92

    88GE Consumer & Industrial

    Multilin

    May 3, 2016

    Phase A C si#nals(ired ,ere+ !urrentstatus monitored ,ere

    Phase B C si#nals(ired ,ere+ !urrentstatus monitored ,ere

    Phase C C si#nals(ired ,ere+ !urrent

    status monitored ,ere

    rea.er *ailureelements!on"#ured ,ere

      5  *   I n  i  t  i a

      t e  &

       C u r r e n  t

       ; u   %1

    5 *  I n i t i a t e  &  C u r r e n t  ; u   % 1

    5  *   I  n i  t  i  a t  e  &  C  u r  r  e n t   ;  u   %  1

     5 *  I n i t i a

     t e  &  C u r r e

     n t  ; u

      %1

    E*ample Architecture BF-nitiation 5 Current Super'ision

    E*ample Architecture / Brea+er

  • 8/17/2019 Busbar Protection by GE

    89/92

    89GE Consumer & Industrial

    Multilin

    May 3, 2016

    Phase A C si#nals(ired ,ere+ !urrentstatus monitored ,ere

    Phase B C si#nals(ired ,ere+ !urrentstatus monitored ,ere

    Phase C C si#nals(ired ,ere+ !urrent

    status monitored ,ere

    rea.er *ail = !ommand#enerated ,ere and send totri aroriate brea.ers

      5 r e a  . e r 

      * a  i  l   = 

    5 r e a . e r  * a i l  =   

    5  r  e 

    a .  e r   *  a i  l   =   

     5 r e a . e

     r  * a i l  = 

     )ri

     )ri )ri

    E*ample Architecture Brea+erFailure Tripping )ri

    -EEE 7I7

  • 8/17/2019 Busbar Protection by GE

    90/92

    90GE Consumer & Industrial

    Multilin

    May 3, 2016

    -EEE 7I7

    • >Guide for Protecti'e 2ela# Applicationsto Po%er S#stem Buses?  is currentl#!eing re'ised !# the =or+ing Groupof the -EEE Po%er S#stem 2ela#ing

    CommitteeI

  • 8/17/2019 Busbar Protection by GE

    91/92

    91GE Consumer & Industrial

    Multilin

    May 3, 2016

  • 8/17/2019 Busbar Protection by GE

    92/92