2 Busbar Protection

download 2 Busbar Protection

of 79

Transcript of 2 Busbar Protection

  • 7/28/2019 2 Busbar Protection

    1/79

    1 1> Busbar Protection

    Busbar Protect ion

    Busbar Protection:Including High Impedance,

    Frame Leakage andDirectional Comparison

    Principles

    GRID

    Technical Institute

    This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior

    written consent of Alstom Grid Technical Institute. All rights reserved.

  • 7/28/2019 2 Busbar Protection

    2/79

    2 2> Busbar Protection

    Busbar Protect ion

    There are fewer faults

    on busbars than on

    other parts of the

    power system

    F2F1

    Without Busbar Protection

    No dislocation of system due to accidental operation of busbar

    protection

    Slow Fault Clearance

    Busbar faults at F1 and F2 are cleared by remote time delayed

    protection on circuits feeding the faults:

    Time Delayed Overcurrent or

    Time Delayed Distance Protection

  • 7/28/2019 2 Busbar Protection

    3/79

    3 3> Busbar Protection

    Busbar Protect ion

    F2F1

    Busbar

    Zone

    With Busbar Protection

    Fast clearance by Breakers at the Busbars

    Where Busbars are sectionalised, protection can limit the amount ofsystem disruption for a Busbar fault

  • 7/28/2019 2 Busbar Protection

    4/79

    4 4> Busbar Protection

    Busbar protect ion must be

    ReliableFailure could cause widespread damage to the substation

    Stable

    False tripping can cause widespread interruption of

    supplies to customers

    Discriminating

    Should trip the minimum number of breakers to clear the

    fault

    Fast

    To limit damage and possible power system instability

  • 7/28/2019 2 Busbar Protection

    5/79

    5 5> Busbar Protection

    Busbar faul ts are usual ly permanent

    CAUSES

    Insulation failures

    Circuit breaker failures

    Falling debris

    Isolators operated outside their ratings

    Safety earths left connected

    Current transformer failures

    THEREFORE:CIRCUIT BREAKERS SHOULD BE TRIPPED AND

    LOCKED OUT BY BUSBAR PROTECTION

  • 7/28/2019 2 Busbar Protection

    6/79

    6 6> Busbar Protection

    Methods of p rovid ing Busbar protect ion

    1. Remote Time Delayed Protection

    2. Frame to Earth (Leakage) Protection

    3. Directional Comparison Protection

    4. Phase Comparison Protection

    5. Differential Protection: High Impedance

    Low Impedance

  • 7/28/2019 2 Busbar Protection

    7/797 7> Busbar Protection

    Frame leakage pro tect ion

    ADVANTAGES

    1. Simple and economic form of protection

    2. Ideal for the protection of phase segregated switchgear where

    earth fault protection only is required

    DISADVANTAGES

    1. Insulation is required between switchgear sections

    2. It is not possible to discriminate between faults on two sets of

    busbars running through common switchgear frames

    3. Care must be taken in construction of the substation in order to

    ensure that the fixing bolts do not come in to contact with thesteel reinforcing of the concrete

  • 7/28/2019 2 Busbar Protection

    8/798 8> Busbar Protection

    Frame earth pro tect ion scheme

    Only an earth fault system

    Involves measuring fault current from switchgear frame to

    earth

    Switchgear insulated by standing on concrete plinth

    Only one earthing point allowed on switchgear

    C.T. mounted on single earth conductor used to energise

    instantaneous relay

    All cable glands must be insulated

  • 7/28/2019 2 Busbar Protection

    9/799 9> Busbar Protection

    Sing le Zone Frame - Earth Protectio n

    64

    G

    Frame-earth

    fault relay

    H J K

    +Trip all circuit breakers

    Switchgear frame

  • 7/28/2019 2 Busbar Protection

    10/7910 10> Busbar Protection

    Current Distr ibu t ion fo r External Fault

    Generator

    Frame-leakage current

    transformer

    Switchgear frame

    Switchgear frame

    bonding bar

    Outgoing feeder

    System earthing resistor

    Earth bar

    Earthing electrode

    resistance

    Frame insulation

    resistance to earth

    I1 + I2

    I2I1I1

    IF= I1 + I2

  • 7/28/2019 2 Busbar Protection

    11/7911 11> Busbar Protection

    Frame leakage Busbar protect ion

    External Fault

    I1

    I1

    >10 I2

  • 7/28/2019 2 Busbar Protection

    12/7912 12> Busbar Protection

    Frame leakage Busbar protect ion

    INTERNAL FAULT

    Suitable for phase segregated indoor metalclad

    switchgear. Only E/F protection required.

    I1

    I2

    Frame

    Insulation

    >10I2

    I1+ I2

    IF=

    I1 +

    I2

    Frame

    System

    Earthing

    Resistance

    Substation

    Earthing

    Electrode 0.1 IF(Max)

    Disadvantages:

    Insulation of switchgear frame and between sections

    Insulation of cable glands to prevent spurious currents

    during through faults

  • 7/28/2019 2 Busbar Protection

    13/7913 13> Busbar Protection

    Frame leakage scheme

    w ith doub le insulat ion barr ier

    64

    Z1

    Trip A

    BA

    Insulation Barrier

    Zone 1 Zone 2

    C

    Trip B

    96

    CTrip C

    Zone 3

    96

    A

    96

    B1

    64

    Z2

    96

    B2

  • 7/28/2019 2 Busbar Protection

    14/7914 14> Busbar Protection

    Frame leakage scheme

    w ith sing le insulat ion barr ier

    64

    Z1

    Trip A

    BA

    Insulation Barrier

    Zone 1 Zone 2

    C

    A

    Trip B

    B1 B2

    T

    C Trip C

    0.2 -1 SEC.

    64

    Z2

  • 7/28/2019 2 Busbar Protection

    15/7915 15> Busbar Protection

    Frame leakage scheme for dup l icate Busbars

    64Z1

    BA

    Insulation Barrier

    Zone 1 Zone 2

    c

    Zone 3

    +

    64Z3

    RM1

    a b

    Dd

    C

    96

    Aa

    b

    96D1

    96

    D296

    B196

    B296

    C

    c

    d

    M1 M2 R

    M2

    -

  • 7/28/2019 2 Busbar Protection

    16/7916 16> Busbar Protection

    Frame leakage pro tect ion

    Check feature

    To differentiate between a genuine busbar fault and a fault

    in the secondary winding of a c.t.

    The check feature provides a second line of defence

    The check relays pick up for both internal and external faults

    Both check and discriminating relays must operate beforetripping can occur

    The various methods of obtaining the check feature are:-

    a) Neutral check provided by a relay energised from a single c.t.in the power system neutral

    b) Residual check provided by a relay energised from a residually

    connected c.t. on the busbar incomersc) Residual voltage check provided by a voltage relay energised

    from a broken delta v.t. supply

    Check relays are normally self-reset in order to avoid havingto reset the relay after each external fault

    Si l Z F E th P t t i

  • 7/28/2019 2 Busbar Protection

    17/7917 17> Busbar Protection

    Single Zone Frame Earth Protect ionWith Neutral Check

    64

    +

    G H

    64

    CH

    Neutral check relay

    Trip all circuit

    breakers

    Frame-earthfault relay

    J K

    Switchgear frame

    T i l T i A d A l Ci i t F F L k

  • 7/28/2019 2 Busbar Protection

    18/7918 18> Busbar Protection

    Typical Trip And A larm Circuits For Frame Leakage

    With Double Insulat ion Barr ier And Check Feature

    CSS-Z1

    +-

    96

    A

    In Out64Z1-1

    In Out

    CSS-Z2

    64Z2-1

    96

    B1

    96

    B2

    96

    C

    Trip Supply

    Supervision

    64CH-1

    AlarmRelay

    7464CH-2 64Z1-2

    64Z2-2

    74-1

    74-2

    Lamp

    Lamp

    Lamp

    Lamp

    Buzzer

    In Out

    In Out

    CSS-Z1

    CSS-Z2Alarm

    SupplySupervision

    Lamp

    Di t i l C i S h

  • 7/28/2019 2 Busbar Protection

    19/7919 19> Busbar Protection

    Direct ional Comparison Scheme

    R

    + (a) Trip

    R

    R

    +(b)

    Trip

    R

    BR

    Load

    current

    Phase to earth external

    fault, scheme (a)

    Di t i l C i S h

  • 7/28/2019 2 Busbar Protection

    20/7920 20> Busbar Protection

    Direct ional Comparison Scheme

    R

    + (a) Trip

    R

    R

    +(b)

    Trip

    R

    BR

    Load

    current

    Phase to earth external

    fault, scheme (b)

  • 7/28/2019 2 Busbar Protection

    21/7921 21> Busbar Protection

    Phase Comparison Scheme - External Fault

    Positive Half Cycle Negative Half Cycle

    A

    B

    A

    B

    B A B

    Feeder X

    A B A

    Feeder Y

    Relay Operation

    Current Transformer

    Secondary Current

    +Trip

    +Trip

    X Y X Y

    Ph C i S h I t l F l t

  • 7/28/2019 2 Busbar Protection

    22/7922 22> Busbar Protection

    Phase Comparison Scheme - Internal Fault

    A

    +

    B

    A

    BTrip

    Trip

    A B A

    Feeder X

    A B A

    Feeder YRelay Operation

    Current Transformer

    Secondary Current

    X YX Y

    Positive Half Cycle Negative Half Cycle

    +

    Basic Circ lating C rrent Scheme

  • 7/28/2019 2 Busbar Protection

    23/79

    23 23> Busbar Protection

    Basic Circulating Current Scheme

    External Fault

    R

    R

    Internal Fault

    Differential Protect ion

  • 7/28/2019 2 Busbar Protection

    24/79

    24 24> Busbar Protection

    Differential Protect ion

    Uses Merz-Price circulating current principle. All currents

    entering and leaving Busbar are compared

    One set of CTs for each circuit associated with a particularzone are all connected to a relay

    A single element relay gives earth fault protection only

    A three element relay gives phase and earth fault protection

  • 7/28/2019 2 Busbar Protection

    25/79

    25 25> Busbar Protection

    Basic Circul t ing Current Scheme

    Earth Fault Pro tect ion Only

    G H J K

    87

    Differential

    relay

    C C

  • 7/28/2019 2 Busbar Protection

    26/79

    26 26> Busbar Protection

    Phase And Earth Fault Circu lat ing Current

    Scheme Using Three-Element Relay

    G H

    AB

    C

    N

    Differentialrelay

    87A 87B 87C

    High Impedance Protect ion

  • 7/28/2019 2 Busbar Protection

    27/79

    27 27> Busbar Protection

    High Impedance Protect ion

    This is a versatile and reliable protection system applied to

    many different Busbar configurations

    If CT requirements are met, scheme performance may be

    predicted by calculation without heavy current conjunctive

    tests

    High Impedance Busbar Protect ion

  • 7/28/2019 2 Busbar Protection

    28/79

    28 28> Busbar Protection

    High Impedance Busbar Protect ion

    Simple system to apply and extend

    High Sensitivity for phase and earth faults

    Extremely stable for external faults

    Hi h I d B b P t t i

  • 7/28/2019 2 Busbar Protection

    29/79

    29 29> Busbar Protection

    High Impedance Busbar Protect ion

    RST

    87

    Metrosil

    CT Requirements: Equal ratios

    Class X

    May require stabilising resistors, RST

    May require non-linear resistors (Metrosils)

    High Impedance Differential Pro tect ion

  • 7/28/2019 2 Busbar Protection

    30/79

    30 30> Busbar Protection

    High Impedance Differential Pro tect ion

    Uses equal ratio CTs

    Scheme assumes that with heaviest through fault, one CT

    saturates, the other not

    To ensure stability, voltage setting of relay circuit made

    higher than voltage developed across relay circuit. To

    achieve this an extra relay circuit resistance is required.

    This is known as the stabilising resistance

    E i l t Ci i t

  • 7/28/2019 2 Busbar Protection

    31/79

    31 31> Busbar Protection

    Equivalent Circu i t

    Y ZM

    RCT RLY RLX RCT

    RST

    RR

    R ZM X

    Hi h I d Th

  • 7/28/2019 2 Busbar Protection

    32/79

    32 32> Busbar Protection

    High Impedance Theory

    RS

    IF

    RCT

    Assume one CT saturates

    Assume relay resistance is high

    V = IF (2RL + RCT)VS > V

    RL IF

    RL

    RCT

    RL RL

    V

    High Impedance Theory

  • 7/28/2019 2 Busbar Protection

    33/79

    33 33> Busbar Protection

    High Impedance Theory

    Choose IS from min fault current ( 30%)

    VS = ISRS + ISRR

    ISRS = VS ISRR

    RS = - RR

    RS =

    IS

    RS

    RR

    VS

    S

    S

    I

    V

    2

    SS

    S

    I

    VA-

    I

    V

    Thus we can choose a value of RS:-

    Knowing 1) Max. & Min Fault Levels,

    2) C.T. Circuit Impedances,

    3) Relay Information,

    4) C.T. Ratio,

    Primary Operating Current (P O C )

  • 7/28/2019 2 Busbar Protection

    34/79

    34 34> Busbar Protection

    Primary Operating Current (P.O.C.)

    The value of primary operating current should be around

    30% of minimum fault current available. This ensures

    sufficient relay current during internal fault conditions for

    high speed operation

    Differential Relays

  • 7/28/2019 2 Busbar Protection

    35/79

    35 35> Busbar Protection

    Differential Relays

    Relays used for high impedance protection are high

    stability, unbiased and tuned to nominal frequency.

    Two modular types are available:-

    MCAG14/34

    Current calibrated with external stabilising resistor

    MFAC14/34

    Voltage calibrated with internal high impedance

    Knee Poin t Voltage Definit ion

  • 7/28/2019 2 Busbar Protection

    36/79

    36 36> Busbar Protection

    Knee-Poin t Voltage Definit ion

    For High Impedance Protection Choose VK

    such that:

    VK2VSThis ensures fast operation for all faults greater than the setting

    current.

    VK is thus dependent on setting voltage and hence on maximum

    through fault current.

    ICK

    Exciting

    Voltage

    (VS

    )

    VK

    Exciting Current (Ie)

    +10% VK

    +50% IeK

    In ternal faul t on high impedance scheme

  • 7/28/2019 2 Busbar Protection

    37/79

    37 37> Busbar Protection

    In ternal faul t on high impedance scheme

    Zm

    RST

    VF = IF.R

    = IF.

    Effective setting

    IS

    = IR

    + 2Ie

    with 2 circuits

    = IR + nIe with n circuits

    Primary effective setting

    IP = T.(IR+nIe)

    Or IP = T.(IR+ nIe+IM+ISR+IV)

    RCT

    VF

    RLY RLX RCT

    R

    ZmX

    IF

    )R+(RI

    ILXCT

    R

    Y

    F

    Y

    Use of faul t sett ing resisto r

  • 7/28/2019 2 Busbar Protection

    38/79

    38 38> Busbar Protection

    Use of faul t sett ing resisto r

    I0P = IR + ISR

    I0P

    ISR

    RSR

    IR

    RST

    RR

    Metros i l l im itat ion of relay vol tage

  • 7/28/2019 2 Busbar Protection

    39/79

    39 39> Busbar Protection

    Metros i l l im itat ion of relay voltage

    IR

    RR

    For heavy internal faults large voltages may develop across relay +Stab. Resistor.

    >3kV Voltages must use Metrosil

    VP =

    VK = Knee point voltage

    VF= Max. RMS voltage if C.T. didnt saturate= IF(RCT + 2RL + RST + RR)

    For Metrosil:

    V = CI (D.C.)

    = C (A.C.)

    VS

    RST

    Im

    V

    IOP

    )V-(V2V2 KFK

    52.0

    IRMS

    VM

    SV2

    Use of Non L inear Resis tors

  • 7/28/2019 2 Busbar Protection

    40/79

    40 40> Busbar Protection

    Use of Non L inear Resis tors

    Under in zone fault conditions it is possible for voltages above the

    relay withstand of 3kV peak to be produced. Metrosil non linearresistors may be necessary to limit the peak voltage below thislevel

    Approx peak volts =

    Metrosil characteristic:- V = CIwhere:- V and I are peak values

    C = constant depending on metrosilconstruction

    = constant in range of 0.2 to 0.25

    The values of C and are chosen to limit metrosil voltage to less

    than 3kV peak at maximum fault current

    )V-(V2V2 KFK

    Metros i l L im itat ion Of Relay Voltage

  • 7/28/2019 2 Busbar Protection

    41/79

    41 41> Busbar Protection

    Metros i l Lim itat ion Of Relay Voltage

    IR

    RR

    To ensure primary operating current not adversely affected,

    metrosil constant C must be sufficiently high to restrict metrosilcurrent at relay setting voltage VS.

    Typical currents:-

    30mA for use with 1 amp CTs

    100mA for use with 5 amp CTs

    VS

    RST

    INLR

    IOP

    VMLRR

    CT Wir ing Supervision

  • 7/28/2019 2 Busbar Protection

    42/79

    42 42> Busbar Protection

    g p

    Open circuit connections between CTs and relay circuit result inunbalance currents which may operate the protection.

    Supervision is applied by a voltage relay across differential relay

    circuit

    Supervision relay is time delayed, gives alarm and also shorts out

    bus wires to protect differential relay circuit

    Typical effective setting is 25 primary amps or 10% of lowest

    circuit rating, which ever is greater.

    Healthy Cond it ion

  • 7/28/2019 2 Busbar Protection

    43/79

    43 43> Busbar Protection

    Healthy Cond it ion

    ZM4

    CT4

    I4

    ZM3

    CT3

    ZM2

    CT2

    I2 I3

    Super

    VisionRelayRR

    RST

    ZM1

    CT1

    I1

    I1 = I2 + I3 + I4

    Supervision Against Open Circuit C T s

  • 7/28/2019 2 Busbar Protection

    44/79

    44 44> Busbar Protection

    Supervision Against Open Circuit C.T. s

    I4

    ZM2

    I1

    Super

    Vision

    RelayRR

    RST

    CT1 open circuit, I1 flows through magnetising impedance and relay circuit

    in parallel

    Voltage measured by supervision relay

    V = I1 (RZM2 ZM3 ZM4)If Supervision relay setting = VSPOut-of-balance current to operate the supervision relay

    VR

    ZM4 ZM3

    I1

    I3I2

    M4

    SP

    M3

    SP

    M2

    SPSP

    Z

    V+

    Z

    V+

    Z

    V+

    R

    V=I

    Differential Relay Circu it

  • 7/28/2019 2 Busbar Protection

    45/79

    45 45> Busbar Protection

    y

    A

    Metrosil

    resistors

    BCN

    87

    V

    87

    V

    87

    V

    95X

    95X

    95X

    Stabilising

    resistors

    95 Supervisionrelay

    Bus wire shorting contacts

    Zone bus

    wires

    Current Trans form ers

  • 7/28/2019 2 Busbar Protection

    46/79

    46 46> Busbar Protection

    Current transformers must be of low reactance type (classx) and

    have identical turns ratio (1 in 100)

    They should be of similar design, or if not, of reasonably matched

    magnetic characteristics

    It is common practice to use CTs having 1 amp secondaries

    Current Transfo rmer Wir ing

  • 7/28/2019 2 Busbar Protection

    47/79

    47 47> Busbar Protection

    g

    Lead burdens between various sets of CTs must be kept low.Usually buswires are run in closed ring between breaker control

    panels. Typical route:-

    CTs to marshalling kiosk

    Marshalling kiosk to isolator auxiliaries

    Loop between marshalling kiosks Conductor size:-

    Normally 2.5mm2

    Effect of C.T. Lo cation

  • 7/28/2019 2 Busbar Protection

    48/79

    48 48> Busbar Protection

    Effect of C.T. Lo cation

    on Busbar Protect ion Performance

    (a)Overlapping C.T.s

    Circuit

    Protection

    F1

    Busbar

    Protection

    F3

    F4

    F2

    (b)All C.T.s on line side of

    circuit breaker

    F1

    Circuit

    Protection

    F3

    F2

    Busbar

    Protection

    Interlocked

    Overcurrent

    Relay

    (c)All C.T.s on Busbar side of

    circuit breaker

    F1Interlocked

    Overcurrent

    Relay

    F3

    F2

    Circuit

    Protection

    Busbar

    Protection

    Zones of Protect ion fo r Doub le Bu s Stat ion

  • 7/28/2019 2 Busbar Protection

    49/79

    49 49> Busbar Protection

    Zones of Protect ion fo r Doub le Bus Stat ion

    BC

    Zone G

    Typical feeder circuits

    Zone H

    BS

    Zone J

    BC

    Check Featu re

  • 7/28/2019 2 Busbar Protection

    50/79

    50 50> Busbar Protection

    Check Featu re

    Zone B

    Usually provided by duplication of primary protection using second set of CTs on

    all circuits other than bus section and coupler units. Check system forms one

    zone only, covering whole of busbar systems and not discriminating betweenfaults on various sections.

    87B

    87

    CK

    Check Zone

    87A

    Zone A

    Iso lator Aux i l iary Sw itches

  • 7/28/2019 2 Busbar Protection

    51/79

    51 51> Busbar Protection

    y

    R

    Auxiliary Switches Should:

    1) Close before the isolator closes

    2) Open after the isolator opens

    in order to maintain stability on switching

    A

    Buswires

    M

    B C D

    m

    r

    a b c d

    Busbar Auxi l iary Sw itches Requ irements

  • 7/28/2019 2 Busbar Protection

    52/79

    52 52> Busbar Protection

    y q

    Reserve Bar

    Normal Operating Condition

    R

    RMain Bar

    Busbar Auxi l iary Sw itches Requ irements

  • 7/28/2019 2 Busbar Protection

    53/79

    53 53> Busbar Protection

    y q

    On-Load Transfer

    R

    R

    Main & reserve zones

    Ultimately paralleled by

    reserve busbar selector

    auxiliary switches

    Circui t Breaker Bypass

  • 7/28/2019 2 Busbar Protection

    54/79

    54 54> Busbar Protection

    yp

    M

    R

    A.C.Buswires

    M

    c1

    b1 a1

    c2

    b2 a2

    a1

    b1

    c1

    R

    N

    CH

    N

    a2

    b2

    c2a

    1b1

    Circui t B reaker and CT Bypass

  • 7/28/2019 2 Busbar Protection

    55/79

    55 55> Busbar Protection

    yp

    M

    R

    M

    b1 a1

    R

    N

    CH

    N

    Check

    Zone

    CTs

    Normally

    Shorted

    AC

    Buswires

    a1

    b1

    Tripping Circui ts

  • 7/28/2019 2 Busbar Protection

    56/79

    56 56> Busbar Protection

    One tripping relay (device 96) is required for each feeder

    breaker and 2 for each bus section or bus coupler breakers

    Both main and check relays must be energised before

    tripping relays trip all breakers associated with zone

    Typical Trip Relay ArrangementDouble Busbar System

  • 7/28/2019 2 Busbar Protection

    57/79

    57 57> Busbar Protection

    Double Busbar System

    -+

    CSS M1

    CSS M2

    CSS - R

    In Out87M1 - 1

    87M2 - 1

    87R - 1

    96

    D1

    M1M2R

    a1

    c1

    96

    D2

    96E

    96

    F196

    F2

    96G

    b1

    c2 96H196

    H2

    87CH - 1

    80T

    D.C. Buswires

    Through Fault Stabi l i ty

  • 7/28/2019 2 Busbar Protection

    58/79

    58 58> Busbar Protection

    Busbar protection stability is based on maximum through fault

    current

    Generally this value is derived from the rating of the associated

    switchgear irrespective of existing fault level, since it can beexpected that system will develop up to limit of rating

    Earth-fau l t p rotect ion for bu sbars and o ther pr imary plant

  • 7/28/2019 2 Busbar Protection

    59/79

    59 59> Busbar Protection

    connect ions (one relay per zone)

    T

    A A A

    D

    G H K

    Relay

    Circuit

    G KH

    E F

    B B B

    T

    T

    C C C

    Vs

    Rated stabi l i ty l imit ph ase

    to earth external fault

    Vs > TxIFx(2H+2K+F+C)

    OR: -

    IF

    Earth-fau l t p rotect ion for bu sbars and o ther pr imary plant

    i ( l )

  • 7/28/2019 2 Busbar Protection

    60/79

    60 60> Busbar Protection

    connect ions (one relay per zone)

    T

    A A A

    D

    G H K

    Relay

    Circuit

    G KH

    E F

    B B B

    T

    T

    C C C

    Vs

    Rated stabi l i ty l imit ph ase

    to earth external fault

    Vs > TxIFx(A+D+2G)

    OR: -

    IF

    Earth-fau l t p rotect ion for bu sbars and o ther pr imary plant

    t i ( l )

  • 7/28/2019 2 Busbar Protection

    61/79

    61 61> Busbar Protection

    connect ions (one relay per zone)

    T

    A A A

    D

    G H K

    Relay

    Circuit

    G KH

    E F

    B B B

    T

    T

    C C C

    Vs

    Rated stabi l i ty l imit ph ase

    to earth external fault

    Vs > TxIFx(B+E+2H)

    whichever is the

    greatest.

    IF

    Phase and earth-fault pro tect ion fo r bus bars and other

    i l t t i ( l )

  • 7/28/2019 2 Busbar Protection

    62/79

    62 62> Busbar Protection

    prim ary plant conn ect ions (one relay per zone)

    G H

    Relay

    Circuit

    G H

    E F

    T

    T

    A A A

    D

    K

    K

    B B B

    TC C C

    K

    KG

    G

    H

    H

    Relay

    CircuitRelay

    Circuit

    IF

    Rated stabi l i ty l im it phase

    to p hase external fault

    Vs

    VsVs > TxIFx(H+K+C)

    OR: -

    Phase and earth-fault pro tect ion fo r bus bars and other

    i l t t i ( l )

  • 7/28/2019 2 Busbar Protection

    63/79

    63 63> Busbar Protection

    prim ary plant conn ect ions (one relay per zone)

    G H

    Relay

    Circuit

    G H

    E F

    T

    T

    A A A

    D

    K

    K

    B B B

    TC C C

    K

    KG

    G

    H

    H

    Relay

    CircuitRelay

    Circuit

    IF

    Rated stabi l i ty l im it phase

    to p hase external fault

    Vs > TxIFx(A+G)

    OR: -

    Vs

    Vs

    Phase and earth-fault pro tect ion fo r bus bars and other

    i l t t i ( l )

  • 7/28/2019 2 Busbar Protection

    64/79

    64 64> Busbar Protection

    prim ary plant conn ect ions (one relay per zone)

    G H

    Relay

    Circuit

    G H

    E F

    T

    T

    A A A

    D

    K

    K

    B B B

    TC C C

    K

    KG

    G

    H

    H

    Relay

    CircuitRelay

    Circuit

    Rated stabi l i ty l im it phase

    to p hase external fault

    Vs > TxIFx(B+H)

    whichever is the

    greatest

    IF

    Vs

    Vs

    Busbar Protect ion With Separate Relays Per Circuit

    Breaker Basic Scheme

  • 7/28/2019 2 Busbar Protection

    65/79

    65 65> Busbar Protection

    Breaker Basic Scheme

    12

    TR

    +

    +1

    +

    +

    2

    +

    2

    D

    CH

    21

    D

    CH

    TR

    + 1

    Busbar Protect ion With Separate Relays Per Circuit

    Breaker Basic Scheme With Addi t ional Tr ipp ing Route

  • 7/28/2019 2 Busbar Protection

    66/79

    66 66> Busbar Protection

    Breaker Basic Scheme With Addi t ional Tr ipp ing Route

    1

    2

    TR

    +

    +2

    +

    +

    1

    +2

    D

    CH

    21

    D

    CH

    TR

    + 1

    +

    +

    2

    1

    TR

    +

    +

    TR

    1

    2

    STN+

    Busbar Protect ion With Separate Relays Per Circuit

    Breaker Basic Scheme With Addit ion al Relays Per Zone

  • 7/28/2019 2 Busbar Protection

    67/79

    67 67> Busbar Protection

    Breaker Basic Scheme With Addit ion al Relays Per ZoneAnd B ack Tr ipp ing Faci l i t ies

    1

    2

    TR

    +

    +2

    +

    +

    1

    +2

    D

    CH

    21

    D

    CH

    TR

    + 1 STN

    2+

    CH

    BT BT

    +1

    D

    +

    Busbar Protect ion With Separate Relays Per Circuit

    Breaker Basic Scheme With Addit ion al Relays Per Zone

  • 7/28/2019 2 Busbar Protection

    68/79

    68 68> Busbar Protection

    Breaker Basic Scheme With Addit ion al Relays Per ZoneAnd Back Trippin g Faci l i t ies With Separate Trip Relays

    1 2

    TR

    +

    +2

    +

    +

    1

    +2

    D

    CH

    D

    CH

    TR

    + 1 + STN

    2

    CH

    BT BT

    D

    +

    +2

    1+

    +1

    2

    TR TR

    +1

    Double Busbar With Trans fer Faci l i t ies

  • 7/28/2019 2 Busbar Protection

    69/79

    69 69> Busbar Protection

    Main

    By-Pass

    Isolator

    Reserve/ Transfer

    By-Pass

    Isolator

    Triple Busbar

  • 7/28/2019 2 Busbar Protection

    70/79

    70 70> Busbar Protection

    Main

    Transfer

    CB.

    Reserve

    Transfer

    Transfer

    CB.

    1 Breaker Scheme

  • 7/28/2019 2 Busbar Protection

    71/79

    71 71> Busbar Protection

    1 Breaker Bus Pro tec tion

  • 7/28/2019 2 Busbar Protection

    72/79

    72 72> Busbar Protection

    87

    87

    Mesh BusbarF1 F3

  • 7/28/2019 2 Busbar Protection

    73/79

    73 73> Busbar Protection

    F4

    T1

    F1

    T4

    F3

    T3

    F2

    T2

    Mesh Busbar Protect ion

  • 7/28/2019 2 Busbar Protection

    74/79

    74 74> Busbar Protection

    F4

    T1

    F1

    T4

    F3

    T3

    F2

    T2

    87

    R187

    R3

    87

    R4

    87

    R2

    Busbar Protect ion and Breaker Fai l

  • 7/28/2019 2 Busbar Protection

    75/79

    75 75> Busbar Protection

    Where breaker fail protection is applied to a system, backtripping of associated breakers is required in the event of abreaker failure

    Often, breaker fail protection is arranged in conjunction withbusbar protection tripping circuits to initiate tripping of

    breakers on a busbar zone associated with the failedbreaker

    Midos Relays for High Impedance Protect ion

  • 7/28/2019 2 Busbar Protection

    76/79

    76 76> Busbar Protection

    Differential Relay MCAG34 or MFAC34

    Supervision Relay MVTP31

    Tripping Relay (Hand Reset) MVAJ13 No Volt Relay MVAX12

    Zone Indication Relay MVAA13

    Modern Low Impedance Busbar Protect ion

  • 7/28/2019 2 Busbar Protection

    77/79

    77 77> Busbar Protection

    Fast

    Modular scheme design allows relays to relate to each circuit and

    function of the protection. This enables the user to easily

    understand the principles of application

    High sensitivity for phase and earth faults. Protection for each

    phase can be relatively independent

    Earlier schemes were less stable than high impedance schemes.

    Modern schemes incorporate saturation detectors and are

    extremely stable

    Duplicate measuring circuits are included

    Current transformers can be:

    Of different ratio

    Of relatively small output

    Shared with other protections

    Current transformer secondary circuits are not switched

    Continuous supervision of CT circuits and constant monitoring of

    vital circuits are included

    MBCZ 10 Single Bus Protect ion

  • 7/28/2019 2 Busbar Protection

    78/79

    78 78> Busbar Protection

    F1

    FM1

    Z1

    Z1

    ZCK

    Z1

    FM2 BSM

    BS

    FM3

    Z2

    FM4

    Z2

    ZCK

    Z2

    F2 F3 F4

    ZCK

    MBCZ 10 Double Bus Protect ionBS

  • 7/28/2019 2 Busbar Protection

    79/79

    Z1

    Z1

    FM1 BSM

    BS

    Z1

    ZCK

    Z3

    ZCK

    BC1

    BCM

    1

    Z3

    Z3

    FM2

    Z2

    F2F1

    Z4

    F3

    FM3

    Z2

    Z4

    FM4

    F4BC2

    BCM

    2

    Z2

    Z4

    ZCK