GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin...

23

Transcript of GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin...

Page 1: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 2: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 3: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 4: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 5: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 6: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 7: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 8: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 9: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 10: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 11: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 12: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 13: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 14: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 15: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 16: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 17: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 18: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 19: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 20: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 21: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040
Page 22: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040

Bulletin No. 6040-2 AddendumSeptember,2000

Smyrna, TN, USA

Appends Bulletin 6040-2 dated 11/92

ADDENDUMMetal-Enclosed Switchgear2.4 kV to 38 kVClass 6040

1

Instruction Bulletin

© 1992–2000 Schneider Electric All Rights Reserved

Retain for future use.

The information contained in this bulletin appends bulletin no. 6040-2, page 8, Forming Cables, following paragraph 1.

Read and understand all of the information contained in this addendum.

When installing cables in switchgear the clearances shown must be maintained to avoid insulation breakdown and flashover.

NOTE: Clearances also apply to any grounded component in the assembly (i.e., stress cone ground)

Figure 5: Shielded Cable Clearances

SECTION 1—INTRODUCTION

Forming Cables

See note (2)

X/Y dimension

Stress cone

HVL switch

NOTE: (1) X and Y clearances apply to both insulated and bare bus bars.

(2) If required, cable support assemblies are available to hold cables away from bus bars.

Clearance Requirements for Shielded Cables

kV Rating

X Inches Shields Bare

Y Inches Shields Insulated

Cable Support Assembly

5 4 3 44037-613-50

15 5 4 44037-613-50

25 8 7 44039-523-50

29 8 7 44039-523-50

38 10 9 44039-523-51

Electrical equipment should be serviced only by qualified electrical maintenance personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

Square D Company330 Weakley RoadSmyrna, TN 371671-888-SquareD (1-888-778-2733)www.squared.com

Page 23: GCBSINVENTORY.COM · Bulletin No. 6040-2 Addendum September,2000 Smyrna, TN, USA Appends Bulletin 6040-2 dated 11/92 ADDENDUM Metal-Enclosed Switchgear 2.4 kV to 38 kV Class 6040

Bulletin No. 6040-2 AddendumSeptember,2000

Smyrna, TN, USA

Appends Bulletin 6040-2 dated 11/92

ADDENDUMMetal-Enclosed Switchgear2.4 kV to 38 kVClass 6040

1

Instruction Bulletin

© 1992–2000 Schneider Electric All Rights Reserved

Retain for future use.

The information contained in this bulletin appends bulletin no. 6040-2, page 8, Forming Cables, following paragraph 1.

Read and understand all of the information contained in this addendum.

When installing cables in switchgear the clearances shown must be maintained to avoid insulation breakdown and flashover.

NOTE: Clearances also apply to any grounded component in the assembly (i.e., stress cone ground)

Figure 5: Shielded Cable Clearances

SECTION 1—INTRODUCTION

Forming Cables

See note (2)

X/Y dimension

Stress cone

HVL switch

NOTE: (1) X and Y clearances apply to both insulated and bare bus bars.

(2) If required, cable support assemblies are available to hold cables away from bus bars.

Clearance Requirements for Shielded Cables

kV Rating

X Inches Shields Bare

Y Inches Shields Insulated

Cable Support Assembly

5 4 3 44037-613-50

15 5 4 44037-613-50

25 8 7 44039-523-50

29 8 7 44039-523-50

38 10 9 44039-523-51

Electrical equipment should be serviced only by qualified electrical maintenance personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

Square D Company330 Weakley RoadSmyrna, TN 371671-888-SquareD (1-888-778-2733)www.squared.com