Bulletin 1492
IEC Terminal Blocks
32
Fuse Blocks
➊ IEC standards for 5 x 20 mm fuses do not include ratings above 6.3 A.
1492-WFB4 1492-WFB424 1492-WFB4250Dimensions are not intended to be used for manufacturing purposes.Note:Height dimension is measured
from top of rail to top of terminal block.
Specifications Single-circuit fuse block. Single-circuit fuse block with LEDblown fuse indicator.
Single-circuit fuse block with neon blown fuse indicator.
Approvals CSA IEC CSA IEC CSA IEC
Voltage Rating300V
AC/DC300V
AC/DC500V
AC/DC300V
AC/DC300V
AC/DC500V
AC/DC300V
AC/DC300V
AC/DC500V
AC/DC
Maximum Current 15 A 15 A 15 A ➊ 15 A 15 A 15 A ➊ 15 A 15 A 15 A ➊
Wire Range (Rated Cross Section) #22…#12 AWG
#22…#12 AWG
0.5…4 mm2
#22…#12 AWG
#22…#12 AWG
0.5…4 mm2
#22…#12 AWG
#22…#12 AWG
0.5…4 mm2
Indicator Type Non-Indicating LED Neon
Leakage Current — 2mA @ 24V 1mA @ 264V
Working Voltage Per Fuse Rating 10-57V AC/DC 85-264V AC
Fuse Size (Not Supplied) 5 x 20 mm 5 x 20 mm 5 x 20 mm
Wire Strip Length 0.31" (8 mm) 0.31" (8 mm) 0.31" (8 mm)
Recommended Tightening Torque 5.0…5.6 lb-in. (0.6 Nm) 5.0…5.6 lb-in. (0.6 Nm) 5.0…5.6 lb-in. (0.6 Nm)
Density 38 pcs./ft (125/m) 38 pcs./ft (125/m) 38 pcs./ft (125/m)
Insulation Temperature Range –40…+195°F (–40…+90°C) –40…+195°F (–40…+90°C) –40…+195°F (–40…+90°C)
Terminal Blocks Cat. No. Pcs./Pkg. Cat. No. Pcs./
Pkg. Cat. No. Pcs./Pkg.
Terminal Block 1492-WFB4 50 1492-WFB424 50 1492-WFB4250 50
Accessories (page 185) Cat. No. Pcs./Pkg. Cat. No. Pcs./
Pkg. Cat. No. Pcs./Pkg.
Mounting Rails: 1 m Symmetrical DIN (Steel) 199-DR1 5 199-DR1 5 199-DR1 5
1 m Symmetrical DIN (Aluminum) 1492-DR5 5 1492-DR5 5 1492-DR5 5
1 m Hi-Rise Sym. DIN (Aluminum) 1492-DR6 2 1492-DR6 2 1492-DR6 2
1 m Angled Hi-Rise Sym. DIN (Steel) 1492-DR7 2 1492-DR7 2 1492-DR7 2
End Barrier Not Required — Not Required — Not Required —
End Anchors: DIN Rail — Normal Duty 1492-EA35 50 1492-EA35 50 1492-EA35 50
DIN Rail — Heavy Duty 1492-EAH35 10 1492-EAH35 10 1492-EAH35 10
Jumpers: Side Jumper — 10-pole Insulated 1492-SJFB8-10 10 1492-SJFB8-10 10 1492-SJFB8-10 10
Other Accessories:Partition Plate 1492-PPSL3 50 1492-PPSL3 50 1492-PPSL3 50
Group Marking Carrier 1492-GM35 10 1492-GM35 10 1492-GM35 10
Marking Systems:Snap-in Marker Card — For Base Block 1492-SM8X12 5 1492-SM8X12 5 1492-SM8X12 5
For Handle 1492-SM6X9 5 1492-SM6X9 5 1492-SM6X9 5
Individual Marker Tabs (single char.) 1492-MP ➋ 10 1492-MP ➋ 10 1492-MP ➋ 10
2.0" (50.7 mm)
1.55
" (3
9.4
mm
)0.31"
(8 mm) 2.0" (50.7 mm)
1.55
" (3
9.4
mm
)
0.31"(8 mm) 2.0" (50.7 mm)
1.55
" (3
9.4
mm
)
0.31"(8 mm)
Accessories — Page 185
33
Bulletin 1492
IEC Terminal BlocksFuse Blocks, Continued
1492-H4 1492-H5 1492-H6Dimensions are not intended to be used for manufacturing purposes.Note: Height dimension is measured
from top of rail to top of terminal block.
Specifications Single-circuit fusible terminal block with neon blown fuse indicator.
Single-circuit fusible terminal block with LED blown fuse indicator.
Single-circuit fusible terminal block without a blown fuse indicator.
Approvals CSA IEC CSA IEC CSA IEC
Voltage Rating300V
AC/DC300V
AC/DC500V
AC/DC300V
AC/DC300V
AC/DC500V
AC/DC300V
AC/DC300V
AC/DC500V
AC/DC
Maximum Current 12 A 12 A 12 A 12 A 12 A 12 A 12 A 12 A 12 A
Wire Range (Rated Cross Section) #30…#12 AWG
#30…#12 AWG
0.05…4 mm2
#30…#12 AWG
#30…#12 AWG
0.05…4 mm2
#30…#12 AWG
#30…#12 AWG
0.05…4 mm2
Indicator Type Neon LED Non-Indicating
Leakage Current 2 mA @ 300V 2 mA @ 24V —
Working Voltage 100…300V AC 10…57V AC/DC Per Fuse Rating
Fuse Size (Not Supplied) 1/4" x 1-1/4" 1/4" x 1-1/4" 1/4" x 1-1/4"
Wire Strip Length 0.38" (9.7 mm) 0.38" (9.7 mm) 0.38" (9.7 mm)
Recommended Tightening Torque 3…7 lb-in. (0.3…0.8 Nm) 3…7 lb-in. (0.3…0.8 Nm) 3…7 lb-in. (0.3…0.8 Nm)
Density 33 pcs./ft (109/m) 33 pcs./ft (109/m) 33 pcs./ft (109/m)
Insulation Temperature Range –40…+221°F (–40…+105°C) –40…+221°F (–40…+105°C) –40…+221°F (–40…+105°C)
Terminal Blocks Cat. No. Pcs./Pkg. Cat. No. Pcs./
Pkg. Cat. No. Pcs./Pkg.
Terminal Block 1492-H4 25 1492-H5 25 1492-H6 25
Accessories (page 185) Cat. No. Pcs./Pkg. Cat. No. Pcs./
Pkg. Cat. No. Pcs./Pkg.
Mounting Rails: 1 m Symmetrical DIN (Steel) 199-DR1 10 199-DR1 10 199-DR1 10
1 m Symmetrical DIN (Aluminum) 1492-DR5 10 1492-DR5 10 1492-DR5 10
1 m Hi-Rise Sym. DIN (Aluminum) 1492-DR6 2 1492-DR6 2 1492-DR6 2
1 m Angled Hi-Rise Sym. DIN (Steel) 1492-DR7 2 1492-DR7 2 1492-DR7 2
End Barrier 1492-N37 50 1492-N37 50 1492-N37 50
End Anchors:DIN Rail — Normal Duty 1492-EA35 50 1492-EA35 50 1492-EA35 50
DIN Rail — Heavy Duty 1492-EAH35 10 1492-EAH35 10 1492-EAH35 10
Jumpers: Side Jumper — 10-pole Uninsulated 1492-N49 10 1492-N49 10 1492-N49 10
Side Jumper — Insulating Sleeve 1492-SJS 10 1492-SJS 10 1492-SJS 10
Other Accessories:Group Marking Carrier 1492-GM35 10 1492-GM35 10 1492-GM35 10
Marking Systems:Snap-in Marker Card 1492-SM8X12 5 1492-SM8X12 5 1492-SM8X12 5
Accessories — Page 185
3.20" (81.3 mm)
1.85
" (4
7 m
m)
0.36"(9.1 mm) 3.20" (81.3 mm)
1.85
" (4
7 m
m)
0.36"(9.1 mm) 3.20" (81.3 mm)
1.85
" (4
7 m
m)
0.36"(9.1 mm)
Bulletin 1492
IEC Terminal Blocks
34
Fuse Blocks, Continued
➊ Overall height varies with plug-in component. For 1492-DP4, use 1.8" (45 mm); for 1492-CP4, use 2.2" (55.5 mm); and for 1492-FP4…, use 2.4"(60.0 mm).
➋ Maximum current and voltage rating of component plug is 1 A @ 600V. Maximum current rating for the base terminal block is listed under Specifications.
➌ Maximum current and voltage ratings for the fuse plug are 10 A and 250V,respectively. Maximum ratings for the base blocks are listed under Specifications.
➍ See page 216 for Fuse Plug Specifications.➎ Cat. no. is not complete. See page 186.
1492-W4PDimensions are not intended to be used for manufacturing purposes.Note:Height dimension is measured
from top of rail to top of terminal block.
Specifications Pluggable terminal block.
Approvals CSA IEC
Voltage Rating600V
AC/DC600V
AC/DC800V
AC/DC
Maximum Current 20 A 20 A 32 A
Wire Range (Rated Cross Section)#22…
#12 AWG#22…
#12 AWG0.5…
2.5 mm2
Indicator Type —
Wire Strip Length 0.35" (9 mm)
Recommended Tightening Torque 5.0…5.6 lb-in. (0.6 Nm)
Density 50 pcs./ft (166/m)
Insulation Temperature Range –40…+195°F (–40…+90°C)
Working Voltage —
Fuse Size (Not Supplied) 5 x 20 mm
Terminal Blocks Cat. No. Pcs./Pkg.
Color: Gray 1492-W4P 50
Red 1492-W4P-RE 50
Inserts: Disconnect Plug 1492-DP4 50
Component Plug 1492-CP4 ➋ 50
Fuse Plug 1492-FP4 ➌➍ 50
Fuse Plug w/LED Blown Fuse Indication 1492-FP424 ➌➍ (shown) 50
Fuse Plug w/Neon Blown Fuse Indication 1492-FP4250 ➌➍ 50
Accessories (page 185) Cat. No. Pcs./Pkg.
Mounting Rails: 1 m Symmetrical DIN (Steel) 199-DR1 10
1 m Symmetrical DIN (Aluminum) 1492-DR5 10
1 m Hi-Rise Sym. DIN (Aluminum) 1492-DR6 2
1 m Angled Hi-Rise Sym. DIN (Steel) 1492-DR7 2
End Barrier 1492-EB3 50
End Anchors: DIN Rail — Normal Duty 1492-EA35 50
DIN Rail — Heavy Duty 1492-EAH35 10
Jumpers: Insulated Side Jumper 1492-N42 (2-pole)
1492-SJ6-10 (10-pole)5010
Other Accessories: Partition Plate 1492-PP3 50
Marking Systems:Snap-in Marker Card 1492-SM6X12 5
Individual Marker Tabs (single char.) 1492-MP ➎ 10
➊
1.78" (45.3 mm)0.24"
(6 mm)