BUILDING SERVICES PROJECT 2

100
BUILDING SERVICES SYSTEMS FOR OLD FOLKS HOME BUILDING SERVICES BLD 60903/ ARC 2423 Prepared by: Chan Jia Xin 0319565 Eng Shi Yi 0317849 Evelyn Lai Kah Ying 0322732 Lee Hui Qin 0322991 Saw Hwei Ying 0318093 Sharon Lim Yu Jung 0313377 Tutor: Mr Azim

Transcript of BUILDING SERVICES PROJECT 2

Page 1: BUILDING SERVICES PROJECT 2

 

 

 

 

 

 

 

 

 

BUILDING SERVICES SYSTEMS 

FOR  

OLD FOLKS HOME 

BUILDING SERVICES 

BLD 60903/ ARC 2423 

Prepared by: 

Chan Jia Xin    0319565 

Eng Shi Yi      0317849 

Evelyn Lai Kah Ying  0322732 

Lee Hui Qin    0322991  

Saw Hwei Ying    0318093 

Sharon Lim Yu Jung  0313377 

 

Tutor: Mr Azim 

 

 

 

Page 2: BUILDING SERVICES PROJECT 2

 

 

 

Table of Content 

Content  Page 

Introduction to Building 

Literature Review 

Findings & Analysis on  

       Fire Protective System 

                       1.0 Passive 

                       2.0 Active 

        3.0 Air Conditioning System

        4.0 Mechanical Ventilation System

Page 3: BUILDING SERVICES PROJECT 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

        5.0 Mechanical Transport System

Proposal of Systems  

Summary & Conclusion 

References 

Page 4: BUILDING SERVICES PROJECT 2

 

 

 

 

 

 

 

T

K

i

w

w

B

t

 

 

 

 

 

 

 

The buildin

Kanagapura

nteraction 

wish to nar

which enga

Building By

the users' s

ng function

am, Petalin

between t

rrow the ga

ages them, 

y Laws 198

safety and 

 

s as an eld

ng Jaya, Sel

the elderly,

ap between

thus differ

84. With bu

comfort in 

erly center

angor. In t

 whereby w

n one anot

rent system

uildability a

mind can 

r located in

he double 

with the id

her. Thus, 

ms are emp

nd practica

be rooted 

n the neigh

stories eld

ea of holdi

the buildin

ployed in co

ality, only t

and realize

bourhood 

erly center

ing hands, 

ng provides

ompliance t

then conce

ed. 

of Taman 

r, we prom

building br

s various ac

to the Unif

eptual ideas

otes 

ridges, we 

ctivities 

form 

s which putt 

Page 5: BUILDING SERVICES PROJECT 2

 

 

 

 

 

 

1.0 Passive Fire Protection 

Is the integration of fire protection in the design and planning stage of a building, mainly meeting in the 

requirements of compartmentation, structural stability, fire separation and safe escape means. Since it is 

a passive design, the protection can be initiated by itself before and while Active Protection is induced, 

thus minimizing the risk of hazardous jeopardy, rebuilt cost and ease a prompt recovery from the fire. In 

a case of fire, PFP protects the building by confining the fire to prevent it to spread to unexposed 

rooms, while allowing safe evacuation to be done.  

  A. Compartmentation 

  Is the confinement and separation of a big volume into smaller sealed compartments,   which can prevent the rapid horizontal or vertical spread of fire to minimize the harm.   The critical elements in ensuring a tight seal includes doors, floors and walls. 

  B.  Means of escape 

  Provide the shortest route to direct the users to the closest safety assembly area within   a short timeframe. It should be kept clean and clear always to prevent obstructions for a   fast evacuation. In the home, it consist of unprotected area, protected area, leading to   exit and leading direct to exit.  

  C. Dead End Limit 

  Is the distance to a storey exit or to a point where alternative means of escape is   available provided that the total travel distance shall not exceed the limits. 

  D. Total Travel Distance 

  The total distance inclusive of the dead end distance from a point to either the fire‐  resisting door in the staircase enclosure or the first thread of the staircase. 

  E. Smoke Control 

  In most fire situation, smoke is one of the contributing factor that hinder evacuation as   it decrease visibility and smothers respiration. Thus, it is crucial to channel smoke out 

Literature 

Review 

Page 6: BUILDING SERVICES PROJECT 2

 

 

  from the building. In case of a fire, smoke which is relatively hotter than fresh air will   rise and accumulate at higher region before it starts to get thicker and displace the fresh   air downward. There are a few methods of Smoke Control: 

    1. Confinement 

    2. Pressurization 

    3. Automatic Ventilating Hatches 

  F. Structural Integrity 

  Refers to the performance of material to sustain its stability in a case of fire to prevent   collapse or disintegration. 

2.0 Active Fire Protection 

Active fire protection is an approach to alert the occupants in building for evacuation and 

attempt to extinguish the fire by using the manually and automatically operated fire mechanical 

system.  

Nulifire (2014) stated that the overall aim of the active fire protection system is to: 

a.) Detecting the fire early and evacuating the building 

b.) Alerting emergency services at an early stage of the fire 

c.) Control the movement of smoke and fire 

d.) Suppress and/or starve the fire of oxygen and fuel 

 

The methods that are included in this system are the sprinklers system, fire alarm and 

detection system, smoke control system and fire suppression system. For fire detention 

system, it is usually detected through the heat and smoke which in return it will alarms and 

enable an emergency evacuation.  

 

For the sprinkler system, it is usually installed at the ceiling level of the building which 

connected to the water supply. It is effective during the fire’s initial flame growth stage and will 

discharges water once it is triggered by the excessive heat to reduce the spread of the fire.  

 

For the fire suppression system, it is used in high fire risk area which is sensitive area such 

as electrical room or computer rooms with wiring. This is because water sprinkler will conduct 

electricity and cause electrical shock to the occupants and firemen.   

Page 7: BUILDING SERVICES PROJECT 2

 

 

3.0 Air Conditioning System   

Air conditioningis the process of removing heat from a confined and enclosed space, produce 

cool ventilation and removing the humidity inside the building which heat is drawn out of the 

room. The process is to achieve a more comfortable and pleasing interior environment for user. 

The main process of air conditioning system is that the air circulation is drawn to condenser 

installed in outdoor which containing refrigerant gas.  

In the most general sense, air conditioning can refer to any form of technology that modifies 

the condition of air (heating, cooling, (de‐)humidification, cleaning, ventilation, or air movement). 

Differ from mechanical ventilation system which withdraw air from an enclosed space, air‐ 

conditioning is considered as an active system which extract heat from interior to outside, with 

the aid of electrical supply and sometimes water supply in large scale building. 

  Air conditioning system is a device that fulfill heating, cooling and ventilation 

requirement of a building over a range of ambient condition specific to the building location. It 

is designed to cope with the maximum value of each of these requirements. (Billy, 2000) 

The purpose of particular system: 

To maintain thermal comfort by controlling temperature and humidity within acceptable 

limits. 

To maintain air quality within acceptable limits of carbon dioxide, oxygen and odor 

content. 

To remove airborne contaminants produced by processes, building services and 

occupants. 

To provide special environment control for equipment and processes. 

 

The air conditioning system are made up of two major cycle: 

Refrigerant Cycle 

Cooling Cycle 

 

Types of air‐ conditioning system in the market: 

a. Room air‐conditioner (Window unit) 

Page 8: BUILDING SERVICES PROJECT 2

 

 

  A simplest form of air conditioning system for smaller scale room. It usually installed in 

  single or double hung window, horizontal sliding window and casement window.The 

  unit has a double shaft fan motor mounted at the evaporator side and condenser side. 

  The evaporator side is located facing the room for cooling while the condenser faces 

  outdoor for heat rejection. It can be divided into refrigeration components (compressor, 

  condenser, expansion valve, evaporator) and air circulation & ventilation components 

  (blower, propeller fan, fan motor)  

b. Packaged unit air‐ conditioning system 

  The packaged air conditioners are used for the cooling capacities in between room ac 

  and centralized ac system. It is available in the fixed rated capacities of above 3 until 15 

  tons. These units are used commonly in places like restaurants, telephone exchanges, 

  small halls. The system can be divided into two types: ones with water cooled 

  condenser and the ones with air cooled condensers.  

c. Centralized/ plant air‐ conditioning system 

  The central air conditioning plants or the systems are used when large buildings, hotels, 

  theaters, airports, shopping malls to be air conditioned completely. There is a plant room 

  where large compressor, condenser, thermostatic expansion valveand the evaporator 

  are kept in. It performs all the functions as usual similar to a typical refrigeration system. 

  However, all these parts are larger in size and have higher capacities. There are two 

  types of central ac system: direct expansion central air conditioning plant and chilled 

  water central air conditioning plant.To operate and maintain central air conditioning 

  systems, good operators, technicians, engineers and proper preventative &breakdown 

  maintenance of these plants is vital. 

d. Split unit air‐ conditioning system 

  Split air conditioners are used for small rooms and halls, usually in places where window 

  air conditioners cannot be installed. 

4.0 Mechanical Ventilation System 

Mechanical ventilation is commonly used in Malaysia’s buildings. Mechanical ventilation helps 

to remove stale air and promotes fresh air into the spaces when the pressure difference is not 

high enough for natural ventilation to work appropriately. Motored fan is normally installed  

Page 9: BUILDING SERVICES PROJECT 2

 

 

near common sources of moisture and pollutants in a house, for instance, kitchens and 

bathrooms. Besides, air ducts and ceiling fans are also installed around the whole building to 

provide airflow throughout the spaces. It is important to ensure the airflow is not blocked by 

anything, if not the ventilation system will not function well. 

Mechanical ventilation system comprises four different types that are generally being applied 

in Malaysia’s buildings, which are: 

  A. Exhaust system  

  Extracts inside air to the outside of the building. 

  B. Supply system  

  Oppose to exhaust system, it draws in fresh air from the outside into the interior spaces. 

  C. Balanced system.  

  Allows airflow from in and out. The design of the mechanical ventilation system is 

  depends on the local climatic and air flow. Unlike other three, circulation system does 

  not really provide ventilation. Instead, it increase rate of air flow to cool down open‐

  aired spaces. 

5.0 Mechanical Transport System  

Mechanical transportation system is a system that transport goods and people in a building 

either vertically or horizontally. Elevator and escalators are the most common mechanical 

transportation system that can be seen in high rise or low rise building. An elevator is lifted up 

and down using a hoist and breaks, the energy used a huge amount of energy to lift up and 

down, but a counterweight can save most of the energy used by elevators. 

Elevator car is balanced by a counterweight which has a similar weight with a loaded half‐full 

weight elevator car, the counterweight helps the motor used lesser energy and force to raise 

and lower the elevator car. At this point motor only need to lift the difference weight of 

elevator car with the counterweight, and apply extra force to overcome the pulley. Because of 

this, it would less strain on the cables, this makes the elevator safer. Besides, counterweight 

reduce the amount of braking an elevator need, it helps to pull loaded elevators move up and 

downwards, therefore a elevator car is much more easier to control with a counterweight with 

it. 

Page 10: BUILDING SERVICES PROJECT 2

 

 

1

A

e

w

b

p

T

 

 

 

 

 

 

 

 

 

 

 

 

 

1.0 Purpo

According t

every build

within one 

building is d

purpose gro

Thus, the e

ose Group

to UBBL cl

ing or com

of the pur

divided into

oup of eac

elderly hom

 

p  

ause (134)

mpartment s

pose group

o compartm

ch compart

me is consid

). Designat

shall be reg

ps set out i

ments, use

ment shall 

dered in pu

ion of purp

garded acc

n the Fifth

d or intend

be determ

rpose grou

pose group

ording to it

h Schedule 

ded to be u

ined separ

up II, Institu

s. For the 

ts use or in

to these B

used for dif

rately. 

utional. 

purpose of

ntended us

y‐laws and

fferent pur

f this Part 

e as falling

d, where a 

poses, the 

Page 11: BUILDING SERVICES PROJECT 2

 

 

 

2.0 Fire Appliance Address 

Fire Appliance Address is the vehicular or fire appliances such as turntable ladders and 

hydraulic platforms access to the building for the purposes of fire fighting, rescue and 

evacuation. 

According to UBBL (140). Fire appliance access. 

  All buildings in excess of 7000 cubic metres shall abut upon a street or road or open 

space of not less than 12 metres width and accessible to fire brigade appliances. The 

proportion of the building abutting the street, road or open space shall be in accordance with 

the following scale: 

 

Thus in the elderly home, the design had complied to the by‐Laws by providing a 3m set‐back 

from the building boundary, with an addition of 6m set‐back from the boundary at the portal 

front to ease fire engines and vehicles accessibility. 

 

 

 

 

 

 

 

Page 12: BUILDING SERVICES PROJECT 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 13: BUILDING SERVICES PROJECT 2

 

 

3.0 Walls, Floors, Doors 

Considered as the members in Compartmentation, to confine the fire in the room to prevent it 

to grow and spread within a timeframe to ensure safe emergency escape and evacuation of the 

disabled people. These components shall be fire‐resistant or non‐combustible in nature. In the 

elderly home, the building are compartmentalized into several zone according to their function 

and non‐combustible materials are opted in the selection of walls, floors and doors to 

contribute minimal or no fuel for a fire.  

According to By‐Laws, 

 (136) Provision of Compartment Walls and Compartment Floors. 

  Any building, other than a single storey‐building, of a purpose group specified in   the 

Fifth Schedule to these By‐Laws and which has: 

  (a) any storey the floor area of which exceeds that specified as relevant to a  building of 

that purpose group and height; or 

  (b) a cubic capacity which exceeds that specified as so relevant shall be so   divided into 

compartments, by means of compartments walls or compartment   floors or both, that 

    (i) no such compartment has any storey the floor area of which exceeds  

  the area specified as relevant to that building; and  

    (ii) no such compartment has a cubic capacity which exceeds that    

  specified as so relevant to that building: 

  Provided that if any building is provided with an automatic sprinkler instalation 

  which  complies with the relevant recommendations of the F.O.C. Rules for  Automatic 

Sprinkler Installation, 29th edition, this by‐law has effect in relation   to that building as if the 

limits of dimensions specified are doubled. 

(138) Other walls and floors to be constructed as compartment walls or compartment floors. 

  (a) any floor in a building of Purpose Group II (Institutional); 

  (b) any wall or floor separating a flat or maisonnette from any other part of the 

  same building; 

Page 14: BUILDING SERVICES PROJECT 2

 

 

  (c)any wall or floor separating part of a building from any other part of the same 

  building which is used or intended to be used mainly for a purpose falling with a 

  different purpose group as set out in the Fifth Schedule to these By‐Laws; and  

  (d) any floor immediately over a basement storey if such basement storey has   an 

area exceeding 100 square metres. 

Thus, compartmentalization is done in the design stage according to the function of each room. 

The area of each compartment is less than 33 meter square and the height is 3.5 meter which 

lies comparatively small within the limit of 2000meter square and the height of 28 meter as 

allocated by the Ninth Schedule of UBBL. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 15: BUILDING SERVICES PROJECT 2

 

 

 

Compartmentation of the elderly home 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 16: BUILDING SERVICES PROJECT 2

 

 

Wall 

According to By‐Laws, Ninth Schedule, a minimum period of fire resistance (in hours) of 1.5 

hours is required. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The wall constitutes of Fire Wall which are designed to prevent horizontal spread of fire that 

extends from the foundation to the roof, since the design of the home comprises of stacked 

volumes that aligns with the floor below. To comply to the 1.5 hours fire resistance as stated in 

By‐Laws, Cavity wall with both outer and inner leaf of bricks, with insulation in the cavity is 

used in general, with 12.5mm gypsum‐sand plaster on both sides. For music hall, 100mm 

autoclaves aerated concrete blocks density 475‐1200kg/mm3 is used to provide sufficient 

fire‐resistance and acoustic compliances. 

 

Page 17: BUILDING SERVICES PROJECT 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In a case of fire, ducts and pipes are prone to be the channel which smoke and fire travels to 

other compartment and this will fail the purpose of compartmentation.  In the home, ducts and 

flues are sealed in intumescent flue wall which are built in the compartment wall. Intumescent 

seal will swell when certain temperature is achieved, thus providing a barrier to protect the 

piping against the fire. This flue wall is of more than half of the fire resistance of the wall. By 

separating the ducts and flues from the compartment wall, fine fire separation can be ensured.  

 

 

 

 

 

 

Page 18: BUILDING SERVICES PROJECT 2

 

 

Floor 

The floor constitutes of compartment floor made of 150mm concrete solid flat slab, with 

25mm screed and 10mm Vermiculite‐gypsum plaster ceiling finish for a fire resistance of 1.5 

hours. 

Door 

Compartment fire door are provided to protect escape routes and limiting the spread of fire.  

UBBL (162) Fire Doors in Compartment walls and separating walls 

  (1) Fire doors of the appropriate FRP shall be provided. 

  (2) Openings in compartment walls and separating walls shall be protected by a   fire 

  door having a FRP in accordance with the requirements for that wall  specified in the 

  Ninth Schedule to these By‐Laws. 

  (3) Openings in protecting structures shall be protected by fire doors having  FRP of not 

  less than half the requirement for the surrounding wall specified in   the Ninth 

  Schedule to these By‐Laws but in no case less than half hour. 

  (4) Openings in partitions enclosing a protected corridoe or lobby shall be   protected 

  by fire doors having FRP of half‐hour. 

  (5) Fire doors including frames shall be constructed to a specification   

  which can be shown to meet the requirements for the relevant FRP    

  when  tested in accordanve with section 3 of BS 476:1951. 

 

 

 

 

 

 

 

Page 19: BUILDING SERVICES PROJECT 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The home utilize type A one hour fire swing door that is constructed in accordance of a single 

door leaf with dimension of 900mm wide, 2100mm height, from solid hardwood core of 37mm 

laminated with adhesives conforming to BS 1204, synthetic resin adhesives for wood, faced 

both sides with plywood to a total thickness of 43mm with all edges finished with a solid edge 

strip full width of the door. The vision panel of dimension is 840mm in height and 180 mm in 

width, glazed with 6mm Georgian Wired Glass in hardwood stops to prevent the breaking of 

glass which might injure the users as the wires will hold the glass in place. The door swing is a 

one way only, which follows the egress motion to facilitate the escape. To ensure a secure 

compartmentation, automatic door closers of hydraulically spring operated type are fitted. In 

the music hall compartment, two storey exits spaced at 7.68 m are provided to comply with:  

 

 

Page 20: BUILDING SERVICES PROJECT 2

 

 

UBBL (167) Storey Exits. 

  (1) Except as provided for in by‐law 194 every compartment shall be provided   with 

at least two storey exits located as far as practical from each other and in   no case closer 

than 4.5 meters and in such position that the travel distances  specified in the Seventh 

Schedule to these BY‐Laws are not exceeded. 

  (2) The width of storey‐exits shall be in accordance with the provisions in the 

  Seventh Schedule to these By‐Laws. 

 UBBL (174) Arrangement of Storey Exits. 

   (1) Where two or more storey exits are required they shall be spaced at not   less 

than 5 meters apart measured between the nearest edges of the openings. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 21: BUILDING SERVICES PROJECT 2

 

 

4.0 Means of escape 

Provide the shortest route to direct the users to the closest safety assembly area within a short 

timeframe. It should be kept clean and clear always to prevent obstructions for a fast 

evacuation. In the home, it consist of unprotected area, protected area, leading to exit and 

leading direct to exit.  

In the home, the longest escape route comprises a permitted travel distance of 44m, complying 

to the UBBL's 45m sprinklered limit, traveling from the first floor caretakers bedroom to the 

ground floor assembly point, inclusive of a 3.6m dead‐end limit, within the 9m limit in UBBL 

(Seventh Schedule). 

 

 

 

 

 

 

Emergency exit signage is crucial in illuminating the way to the escape route. Thus, exits and 

access are marked with visible signs without obstruction from view. UBBL (172) In Malaysian 

context, an illuminated sign reading "KELUAR" with an arrow indicating the direction  are 

places in every direction where the direction of travel to nearest exit is not immediately 

apparent, for instance in the caretakers office and music hall.  

 

 

 

 

 

 

Page 22: BUILDING SERVICES PROJECT 2

 

 

Emergency Exit Routes 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Emergency Exit Path 

KELUAR Sign  

Page 23: BUILDING SERVICES PROJECT 2

 

 

5.0 Smoke Control 

By understanding the convection current theory of hotter air rises and escapes and cooler air is 

drawn in to displace the vacuum space left by the hot air, smoke control mechanism can 

function effectively. In the home, confinement method and automatic ventilating hatches are 

used in smoke control system. 

Confinement  

Passive deign by understanding the nature of smoke, whereby curtain boards truncated the 

flow of smoke by providing barriers with suspended boards in interval. In early stage, it aids in 

suppressing the growth of the fire. 

 

 

 

 

 

 

 

 

In the home, smoke curtains are also used as it is more versatile than dry wall to match the soft 

interior design and can fit around all electrical conduits and does not interfer with the 

mechanism of sprinkler system, while preserving its primary function of confining the fire. 

 

 

 

 

 

  Smoke curtain can come in various design to suit the interior architecture. 

Page 24: BUILDING SERVICES PROJECT 2

 

 

Automatic Ventilating Hatches 

When fire is detected either by heat or smoke detector, the mechanism of automatic 

ventilating hatches will be triggered, whereby the hatches located at the roof top will be 

opened to allow hot smoke that rises to be vented out of the building.  

 

 

 

 

 

 

 

 

6.0 Structural Protection in Buildings 

Elements of structure can only be effective as fire breaks if they have the necessary degree of 

fire resistance. Therefore, there are three criteria should be consider to ensure the fire 

resistant compartment is maintained to allow sufficient time for safe evacuation and rescue 

operation :  

1. Insulation : The ability of an element of structures to resist passage of heat through it by 

convection.  

2. Integrity : The ability of an element of structure to maintain the separating function in 

preventing spreading of flame and smoke.  

3. Stability : The ability of an element of structural to resist collapse as the load bearing 

function to support its load.  

Material used 

The type of building materials that are used in this elderly center were reinforced concrete, 

brick walls and steel framing. Some of the materials is fire‐resistant while some materials are 

susceptible to fire required an outer layer of fire protection.                                       

Page 25: BUILDING SERVICES PROJECT 2

 

 

1. Reinforced concrete: 

It is used in fire resistant escape stairs and also as a load bearing wall due to its strength, fire‐

resistant and high thermal mass. It is able to provide strength and stability to the building and 

stairs in case of fire occurs as it can withstand the massive weight focused on a small area in 

the building exerted by the occupants while evacuation. The type of load bearing walls that are 

used in the elderly center is reinforced concrete with 12.5mm gypsum‐sand plaster. The 

thickness of the of reinforced concrete wall excluding plaster is 180mm for period of fire 

resistance of 4 hours. It is used in most of the spaces due to its characteristics. 

 

2. Steel Framing : 

It is used due to its light weight, high strength to weight ratio. Even though it is non‐

combustible, it will lose its strength from the heat for a period and cause collapse of building. 

Hence, the steel framing is sprayed with asbestos thickness of 12.5mm for period of fire 

resistance in 4 hours. By spraying asbestos, it provide heat resistance to steel framing to 

prevent losing strength.  

 

3.Brick wall : 

A non‐load bearing wall which has the same properties as the concrete which is fire resistant 

and high thermal mass thus it is suitable to use in elderly center. Its natural resistant to fire and 

heat forms an effective barrier between different rooms to lengthen the period of fire 

spreading while withstanding the high heat from fire. The type of brick walls used in this 

elderly center is bricks of clay with 12.5mm cement‐sand plaster which the thickness of the 

wall excluding plaster is 200mm for period of fire resistance of 4 hours.  

 

UBBL 

 UBBL 1984, section 217 : Fire resistance of structural member or overloading wall shall have 

fire resistance of not less than the minimum period required by these By‐Laws for any element 

which it carries.  

Fire wall  

It  is  a  lightweight  and  non‐load  bearing  concrete  wall  which  capable  for  period  of  fire 

resistance  in 2 hours.  It acts as a wall  to separate between spaces especially  those high  fire 

risks spaces such as mechanical and electrical room to prevent spread of fire which could lead 

to explosion. With the help of fire wall, it provides sufficient time for the occupants to escape 

Page 26: BUILDING SERVICES PROJECT 2

 

 

from the building. In this elderly center, it is used at the M&E room and choir  room due to high 

fire risk as these spaces consists of electricity and electrical appliances. 

 

                                             Ground Floor Plan 

 

 

 

 

 

 

 

 

 

 

 

UBBL 

 Section 148(6) Any compartment walls or compartment floor which is required by these By‐

Laws to have FRP of one hour or more shall be constructed wholly of non‐combustible 

materials and, apart from any ceiling, the required FRP of wall or floor shall be obtained 

without assistance form any noncombustible materials. 

 

M&E room Music and choir 

room 

Figure : Fire wall structure 

 

Page 27: BUILDING SERVICES PROJECT 2

 

 

 

  

 

 

Active Fire

Active fire

manually a

can then f

fire detect

1. Water B

1.1 Wet p

Wet pipe s

system co

immediate

sprinkler s

their simp

draining p

Fire sprink

behind the

The sprink

The Alarm

the neares

 

 

 

 

 

 

 

e Protectio

e protection

and autom

further divi

tion system

Based Syste

ipe sprinkle

sprinkler sy

ontaining w

ely from sp

system. The

licity. It is e

ipes and m

klers includ

e ceiling. T

klers will be

m Gong that

st fire statio

 

on 

n system is

atically ope

ided into d

m and fire s

em 

er system 

ystem adop

water and co

rinters whe

ey are very

easy to hav

making alter

de a networ

he fire spri

e activated

t connecte

on to infor

s an integra

erated fire 

ifferent cat

suppression

pts automa

onnected t

enever it is

y reliable an

ve modifica

rations. It a

rk of piping

nklers are 

 when the

d to the sy

m them. 

al part of fir

mechanica

tegories su

n system. 

tic sprinkle

o a water s

s triggered.

nd require 

ation such a

lso require

g filler with

“on called”

air temper

ystem will t

re protectio

l system. A

ch as sprin

er heads wh

supply so t

It is the m

less installa

as shutting

ed the least

 pressurise

 as the pip

rature beco

hen detect

on. It can b

Active fire p

nklers syste

hich attach

hat water d

ost commo

ation and m

down the 

t amount of

ed water w

ing is alway

omes high w

ted it and s

be classified

protection s

em, fire alar

hed to a pip

discharges 

on and sim

maintenanc

water supp

f effort to 

hich are in

ys filled wit

when fire b

send alert s

d into 

system 

rm system,

pping 

plest 

ce due to 

ply, 

restore. 

stalled 

th water. 

breaks out.

signal to 

 

Page 28: BUILDING SERVICES PROJECT 2

 

 

Components of wet pipe fire sprinkler system  Wet pipe sprinkler system is made up from a series of components including stop valve, alarm 

valve, sprinkler head and alarm test valve and motorised alarm bell. In addition to this system, 

additional components are also used to support this arrangement including a valve monitor, 

pressure switch and flow switch. The pipes of a sprinkler system is progressively decreasing in 

size from the water supply to each of the most remote fire sprinkler which the elements can 

be categorised into riser, range, branch and dropper. 

  

Component  Function 

Stop valve  Isolate the water supply. It is often locked in the open position to ensure free flow of 

Valve monitor  Fitted with stop valve to monitor the state (open or closed) of the stop valve. 

Alarm valve  Control the water flow into the fire sprinkler system. When the pressure equalises or falls below the water supply pressure, the valve opens to enable water 

Automatic fire sprinkler  A valve that exposed for a suffirent time to a temperature at or above the temperature rating of the heat sensitive element releases, allowing water to flow from only the affected 

Alarm test valve  Opened to stimulate the flow of water from a single automatic fire sprinkler. 

Motorised alarm bell  Operated by the water flow oscillating a hammer that strikers a gong to cause an audible alarm signal. 

Pressure switch  Monitors a fall in water pressure to activate a switch which is monitored by fire alarm panel for signalling an alarm to the fire 

Flow switch  Monitors the water flow through a section of pipe within fire sprinkler system to prevent minor water flow fluctuations from signalling an alarm. 

Jacking pump  Provide pumping water from water supply to fire sprinkler system and maintaining water pressure to reduce false alarm caused by low pressure. 

Page 29: BUILDING SERVICES PROJECT 2

 

 

Location of wet pipe fire sprinkler system components in the system arrangement 

Pipe elements of wet pipe fire sprinkler system 

Page 30: BUILDING SERVICES PROJECT 2

 

 

                         

Sprinkler head component 

        

    How the fire sprinkler works 

 

.      1. The sprinkler head 

consists a plug held in 

place by a trigger 

mechanism. The glass 

ampule triggers which 

filled with glycerin‐based 

liquid will expand when 

heated 

2. The liquid will expand and 

break the time at certain 

temperature (normally 155 

degrees). Ampule as thin as 

1mm are designed for a 

faster response time. 

 

3. The plug is forced out by the 

pressurised water and defeated 

away by a beveled edge. The 

water sprays over the de8lected 

plate which is designed in an 

even pattern. Water will 

continue to 8low until the main 

valve is shut down.  

 

Page 31: BUILDING SERVICES PROJECT 2

 

 

Advantage of wet pipe sprinkler 

 

Effective as they react very quickly.  

Reduce the heat, flames and smoke produced to reduce the risk of death. 

Able to control the growth of fire as it releases approximately 10 to 25 gallons of 

water per minute.     Classes of Sprinkler System 

  

Occupancy hazard  Square foot per head  Maximum spacing between sprinklers 

Extra Light Hazard  130‐200 square foot per head (39.6‐60.96 square meter) 

15 foot (4.5m) 

   

UBBL  

UBBL 1984 section 226 :  

Where hazardous processes, storage or occupancy are of such character as to require 

automatic sprinklers or other automatic extinguishing system, it shall be of a type and 

standard appropriate to extinguish fires in the hazardous materials stored or handled or for 

the safety of the occupants. 

  UBBL 1984 section 228 :  

(1) Sprinkler valves shall be located in a safe and enclosed position on the exterior wall and 

shall be readily accessible to the Fire Authority. 

(2) All sprinkler systems shall be electricity connected to the nearest fire station to provide  

immediate and automatic relay of the alarm when activated.   

Reasoning 

Water tank is placed outside the building instead of the ceiling to avoid fire obstructs the 

wet pipe sprinkler system when a fire breaks out. Wet pipe sprinkler system is used in 

spaces which only cause Class A fire which can be extinguished by water. 

Page 32: BUILDING SERVICES PROJECT 2

 

 

 

     

  

Page 33: BUILDING SERVICES PROJECT 2

 

 

1.2 Hose Reel System  

Hose Reel System is used primarily to respond to the early stage of fire. It consists of pump, 

pipes, water supply and the reels which located strategically in a building to ensure proper 

coverage of water to combat a fire. This system is manually operated by opening valve to 

enable the water to flow into the hose. Fire hose reel  provides a virtually unlimited supply of 

water, as they are connected to the mains water supply which extends for approximately 35 

metres. The non‐kinking tubing is permanently connected to a water supply which has a main 

turn on or off valve, a hose guide and a hose with a nozzle. The control nozzle attached to 

the end of the hose enables the operators to control the direction and water flow to the fire. 

Water based hose reel system is suitable to use combat Class A fire which include quantities 

of ordinary combustable materials such as timber, paper, fabric and et cetera. It should be 

located at noticeable places such as beside the exit doors or along escape routes. 

                               

Component of a fire hose reel                       Fire hose reel installation UBBL 

248. (1) Wet riser, dry riser, sprinkler and other fire installation pipes and fittings shall be 

painted red. 

248. (2) All cabinets and area of recessed in walls for location of fire installation and 

extinguishers shall be clearly identified to the satisfaction of the Fire Authority or otherwise 

clearly identified.

Page 34: BUILDING SERVICES PROJECT 2

 

 

2. Non Water Based System  2.1 Carbon Dioxide Fire Suppression System  

Fire suppression system can be categorised into fixed and portable which the fixed 

suppression system is to extinguish a developing fire and alert the occupants while portable 

fire extinguisher is used for fighting incipient stage fire. Carbon dioxide fire suppression 

system is used for the extinguishment of cooking oils, fats and electrical equipments. In fire 

protection system, carbon dioxide will be stored under high pressure tanks (high pressure 

system) by compression and cooling to in low pressure refrigerated containers (low pressure 

system).  Total flood systems discharging into confined spaces will displace oxygen with high 

concentrations of carbon dioxide necessary for fire extinguishment (typically 35‐ 70% by 

volume based on the material) and will extinguish the fire. There are two methods of 

applications of carbon dioxide agent. One method is to discharge sufficient amount into an 

enclosed space to create an extinguishment atmosphere (tital flood 

system) or local application (nozzles and cetera). Total flood systems employ a piping 

distribution system from a central source while local applications involve using a carbon 

dioxide mobile tank to be applied to the fire. 

    

Types of space  Types of fire  Types of fire protection system 

Kitchen  E ( Electrical Equipement) F (Cooking Oils and Fats)

Carbon dioxide 

Choir room  E ( Electrical Equipement)  Carbon dioxide     

Carbon dioxide fire suppression system is adopted in kitchen and choir room because these 

area consists of cooking oils, fats and electrical appliances which will lead to fire type E and F 

when fire breaks out. Both total flood systems and local applications should be included in the 

space. This system works fast as carbon dioxide can penetrate the hazard area to smother the 

combustion very quickly. Besides, it does not cause spoilage as it requires no clean up while 

remains its effectiveness on wide rage of combustible materials. 

Page 35: BUILDING SERVICES PROJECT 2

 

 

   

Carbon dioxide fire suppression system components      

How kitchen carbon dioxide suppression system works  

1.  When a fire occurs in a protected area, it is quickly sensed by the detector located 

at the ductwork or cooking appliances hood. 

 

 

Kitchen carbon dioxide suppression system components 

Page 36: BUILDING SERVICES PROJECT 2

 

 

 

How kitchen carbon dioxide suppression system works  

1.  When a fire occurs in a protected area, it is quickly sensed by the detector located 

at the ductwork or cooking appliances hood. 

2.  The detectors actuate the system and pressurising the agent storage tank and 

automatically shutting off appliances energy source in the event of a fire. 

3.  Carbon dioxide fire suppressant flows through the piping and is discharged into the 

plenum and duct areas and onto the cooking appliances. 

4.  The agent is applied directly on the fire in specific spray patterns, suppressing the 

fire in seconds. As it smothers the hot cooking greases, a foam blanket is formed, 

sealing off 

combustible vapour to help prevent fire reflashes.  

   

Reasoning 

Carbon dioxide fire suppression system is used in areas which will lead to Class E and F 

fire that cause by electrical equipments, cooking oils and fats. Carbon dioxide fire 

suppression cylinders are placed at the back walls to maintain the aesthetic appearance of 

the front walls. 

Page 37: BUILDING SERVICES PROJECT 2

 

 

 

Carbon dioxide fire  suppression system sprinkler and carbon dioxide fire  suppression cylinder placement 

                   

Page 38: BUILDING SERVICES PROJECT 2

 

 

 

 

     

 

 

 

2.2 Fire 

A portable

extinguish

vessel wh

types of p

use the co

to reignite

Dry powd

Portable d

A, B, C an

mainly ele

extinguish

element o

the oxyge

Portable c

Extinguis

e fire exting

her small fir

ich contain

portable fire

orrect extin

e after appa

er fire exti

dry powder

d E fire. Ca

ectrical app

hes the fire 

f the fire tr

n element 

carbon diox

her 

guisher is o

re when fir

ns agent tha

e extinguis

nguisher fo

arently exti

nguisher an

r extinguish

arbon dioxi

liances and

by separat

riangle. Car

of the fire 

xide fire ext

one of activ

e breaks ou

at can be d

hers which

r the type o

inguished s

nd carbon

hers are pla

ide fire ext

d cooking o

ting the fue

rbon discoi

triangle an

tinguisher  

ve fire prot

ut. It consis

discharged

h contain di

of fuel as s

successfully

dioxide fire

aced in mos

inguishers

oils and fats

el form the

id fire extin

nd also rem

                

ection dev

sts of an ha

to extingui

ifferent typ

suing incorr

y. 

e extinguish

st of the sp

are placed

s. Dry pow

 oxygen ele

nguisher ex

oving the h

     Portabl

ice which u

and‐held cy

ish a fire. T

pes of agen

rect agent 

her are use

paces as it 

in spaces w

wder fire ext

ement or b

xtinguishes 

heat with a

e carbon dco

uses to con

ylindrical p

There are va

nt. It is impo

may cause

ed in the bu

can extingu

which cons

tinguisher 

by removin

fire by tak

a very cold 

ioxide fire omponent 

ntrol or 

ressure 

arious 

ortant to 

 the fire 

uilding. 

uish class 

sists of 

g heat 

king away 

discharge.

extinguisher 

Page 39: BUILDING SERVICES PROJECT 2

 

 

   

 

    

 Dry powder fire extinguisher  Dry powder fire extinguisher 

component  

    

UBBL    

UBBL 1984 section 227: 

Portable extinguisher shall be provided in accordance with the relevant codes of practice 

and shall be sited in prominent positions on exit routes to be visible from all directions and 

similar extinguishers in a building shall be of the same method of operation.  

    

Reasoning 

Portable dry powder extinguishers are mostly used in the building which cause Class A fire 

while carbon dioxide fire extinguishers are placed at specific rooms which will lead to Class 

E and F fire. The fire extinguishers are placed along the exit routes and beside the doors so 

that they are visible to the users.      

     

Page 40: BUILDING SERVICES PROJECT 2

 

 

             

                   

Page 41: BUILDING SERVICES PROJECT 2

 

 

3. Fire Detection System    

Automatic fire detection systems combine with other elements of an emergency response 

and evacuation plan to reduce property damage, personal injuries, and loss of life from fire in 

the workplace. The main function is to identify a developing fire and alert building occupants 

and emergency response personnel. Automatic fire detection system is a system to detect 

smoke, heat or flame and provide an early warning through visual and audio appliances when 

emergencies are present. 

  

Fire detector  Types of space 

Smoke detector  Of8ice, Emergency room, Counselling room, Game room, 

Dance room. Choir room, Storage, M&E, Caretaker room, 

Meditation room (enclosed space) 

Thermal heat detector  Lobby, Cafe, Social hub,  Discussion area, Resource 

area,Reading area, Exhibition area  (Opened/Semi‐opened     

Different types of 8ire detector is chosen to use to different space. The smoke detector can 

work well in an enclosed space. Thermal heat detector replaces smoke detector in an opened 

or semi‐opened space as smoke is not able to trap and detect in by the smoke detector in 

these spaces. The detectors must be installed to the ceiling to detect the rising smoke when 

there is 

a 8ire.  Besides, the 8ire detectors are used to trigger the 8ire sprinklers and other types of 8ire  

suppression systems.  

   

Ionisation smoke detector component  Thermal heat detector component 

Page 42: BUILDING SERVICES PROJECT 2

 

 

 

Types of Fire detector 

Ionisation smoke detector  Thermal heat detector 

How it works  Smoke particles enter the detector and clog up the ionisation chamber. 

When temperature increases, the bimetal curves undergoes a greater increase in length. 

  The smoke particles attached to the ions and shut down the electric current. The circuit in the detector spots and activates the alarm. 

With one end 8ixed, the movement of the strip free end cam be arranged to close an electric circuit that operates the alarm 

 

                             

 

 

 

 

Ionisation smoke detector schematic diagram 

    Thermal heat detector schematic diagram 

Page 43: BUILDING SERVICES PROJECT 2

 

 

    

Fire Detection System  Square foot per head  Maximum spacing between fire detector 

Ionisation Smoke Detector  367.5 square foot (112 square meter) 

34.8 foot (10.6m) 

Thermal Heat Detector  184.7 square foot (56.3 square meter) 

24.6 foot (7.5m) 

 

 

UBBL 

UBBL 1984 section 225: 

(1) Every building shall be provided with means of detecting and extinguishing fire and with 

fire alarms together with illuminated exit signs in accordance with the requirements as 

specified in the Tenth Schedule to these By‐laws. 

 

Reasoning 

Ionisation smoke detectors are used in enclosed spaces which the smoke can be trapped 

and detector easily. Thermal heat detectors are used in opened areas where smoke is hard 

to detect as they will be diffused to low concentrated areas. Thermal heat detector is also 

used in kitchen as smoke will be produced during cooking process which will be detected 

and cause false alarm. 

Page 44: BUILDING SERVICES PROJECT 2

 

 

 

Location of Smoke and Heat Detector

Page 45: BUILDING SERVICES PROJECT 2

 

 

Fire Alarm System  

Fire alarm system can be activated manually by manual call points or pull 

stations or automatically from heat detectors. The alarm can provide warning of 

the outbreak of fire through visual and audio appliances. Visual alarm system is 

important in this elderly center as some elderly have auditory problem and the 

visual alarm signal should be in white or amber flash with high intensity to draw 

the attention of the occupants. There are two types of fire alarm systems used in 

buildings such as single and two stage system. Single alarm system is designed to 

activate the alarm signal immediately throughout the building. In a two stage alarm 

system, a distinct alert signal first advises the staff of the fire emergency.  

 

Two stage alarm system 

Two stage alarm system is adopted in the building. In a two stage alarm 

system, a distinct alert signal first advises the staff of the fire emergency. It is to 

prevent shocking the elderly when there is any false alarm. This system consists of 

alarm initiating device (fire detector system), alarm notification appliances (sirens) 

and fire control units (sprinkler system and fire suppression system).   

How the fire alarm system work  

The fire alarm system can be set off automatically by smoke detector, thermal heatdetector or manually. 

When the sensor detects certain level of heat or smoke that could be an indicationof fire. The alert signal will be send to the staff of fire emergency in order to prevent shocking the elderly if there is any false alarm. 

If there is no false alarm, the digital alarm communicator that is directly linked toJabatan Bomba located above the control panel will send message to the nearest fire station as associated in the emergency event.  

A siren and blinking of flashing lights will be activated to warn the occupants toevacuate from the building.  

Page 46: BUILDING SERVICES PROJECT 2

 

 

Schematic Diagram of Fire Alarm System

UBBL  

Section 155(1) : The fire mode of operation shall be initiated by a signal from the 

fire alarm panel which may be activated automatically by one of the alarm devices 

in the building or manually.  

 

Manual Call Point 

In some of the cases where the fire could not be detected through the fire 

detector system due to malfunction or other reasons, manual call point system can 

be used to trigger the fire alarm system. It is usually located nearby the exits or 

doorway for the occupants to break the glass immediately when exiting during fire 

event. The signal will then send of to the fire control panel and trigger the fire 

alarm, cut off other services such of electrical and ventilation system.  

 

Emergency Break Glass 

It is placed at a height of 1.2m above floor level at 

easily accessible position for disabled occupants on 

exit routes. Occupants need to break the glass and 

press the button in order to trigger the emergency 

alarm.   

Page 47: BUILDING SERVICES PROJECT 2

 

 

Fire Alarm Bell 

It is installed throughout the building, which usually located near the doorways 

with an even distribution to ensure all of the occupants is alerted during fire 

event. Special circuit is needed for the fire alarm system as an independent power 

supply will be required. The strobe light will be flashing together when the fire 

alarm bell is activated to provide visual alarm signal to those elderly that have 

auditory problem.  

  Fire alarm bell with strobe light  

 

UBBL 

UBBL 1984 Section 237: 

(1) Fire alarms shall be provided in accordance with the Tenth Schedule to these 

By‐Laws. 

 

UBBL 1984 Section 241 : 

In places where there are deaf persons and in places where by nature of the 

occupancy audible alarm system is undesirable, visible indicator alarm signals shall 

be incorporated in addition to the normal alarm system.  

It is a device that create loud sound with a 

minimum sound level of 65dB(A) or +5dB(A) 

above any background noise which is likely 

to persist more than 30 seconds. It also 

usually be placed about 1200mm above the 

manual call point and 2700mm from the 

ground level. 

Page 48: BUILDING SERVICES PROJECT 2

 

 

                     Ground Floor Plan                     First Floor Plan  

Diagram showing the location of fire alarm bells and manual call points   

The location of the fire alarm bells and manual call points are set at the 

correct location in accordance to UBBL section 155 as manual call points are easy 

access by the occupants. Besides, the fire alarm bells are evenly distributed 

around the building to ensure all occupants in each space are alerted. The visible 

indicator fire signals (strobe light that attached to the fire alarm bell) is located at 

the corner that are visible by the occupants in accordance to UBBL section 241, 

as audible alarm system is undesirable for deaf person or elderly which auditory 

problem.  

 

 

 

Page 49: BUILDING SERVICES PROJECT 2

 

 

6.1 

Most

Alwa

prov

hum

comf

toge

ductw

In th

purp

hous

syste

is les

elder

The 

Syste

units

the i

that 

amou

Indo

casse

they 

the r

Introduct

t buildings 

ays referred

ide an acce

idity, air dis

fortable atm

ther to rem

work etc.  

e elderly c

osed as it i

se which ha

em which is

ss disruptiv

rly and care

system intr

em (VRF) w

s while eac

ndividual r

correspond

unt of outd

or unit suc

ette air con

not only a

room

 

tion 

and homes

d to as air‐

eptable lev

stribution a

mosphere. 

move heat f

enter inves

is more eco

as several e

s controllin

ve to the un

etaker. 

roduced w

which one h

h unit has 

oom tempe

dent to the

door units i

ch as wall m

nditioning s

esthetically

s in Malays

con or AC,

vel of occup

and indoor 

Air‐condit

from a par

stigate in th

onomically 

enclosed sp

ng the room

nrelated ar

ill be zone 

heat pump 

its own ind

erature. Th

e indoor un

in limited a

mounted air

system are 

y pleasing a

sia have ins

, air‐condit

pancy com

air quality

ioning syst

ticular spac

his report, 

friendly an

pace. The a

m temperat

ea offers c

control un

unit (outd

dividual tem

his reduces 

nits and sav

area. 

r condition

introduced

and also fu

stalled air‐c

ioning syst

fort by con

(IAQ) in ord

tem is grou

ce, such as

split air co

nd more su

advantages

ture individ

onvenienc

nit under Va

oor unit) co

mperature c

the amoun

ves more sp

ing system

d in zone c

ulfill the hig

conditionin

tem is devic

ntrolling the

der to main

up of comp

s compress

nditioning 

uitable to in

s of split air

dually, easil

e to the us

ariable refr

onnects to

controller t

nt of the o

pace to pla

m and ceilin

control unit

ghest efficie

ng system. 

ce used to 

e temperat

ntain a coo

onents wo

ors, conde

system wil

nstalled in t

r condition

y installed 

ser which is

rigerant flo

 several ind

thus mainta

utdoor uni

aced such 

g mounted

t system as

ency in coo

ture, 

ol and 

orking 

nsers, 

l be 

the 

ing 

and 

s the 

door 

ain 

ts 

oling 

Page 50: BUILDING SERVICES PROJECT 2

6.2 Major Cycle of Air Conditioning System 

6.2.1 Refrigerant Cycle 

A process to remove heat from one place to another. The refrigerant is used 

repeatedly for economically wise. All air conditioners use the same cycle of 

compression, condensation, expansion, and evaporation in a closed circuit. There are 

four main components of air conditioning system used in the refrigerant cycle, the 

evaporator, compressor, condenser and expansion valve. 

Process of Refrigerant cycle:  

a) Evaporator  Compressor 

The refrigerant comes into the compressor as a low‐pressure gas, compressed 

and then moves out of the compressor as a high‐pressure gas. 

b) Compressor  Condenser 

The high pressure gas flows to the condenser and condenses to liquid, giving 

off its heat to the outside air. 

c) Condenser  Expansion Valve 

The high pressure liquid moves to the expansion valve. The valve restricts the 

flow of the fluid and lowers its pressure before leaving the expansion valve. 

d) Expansion Valve  Evaporator 

The low pressure liquid moves to the evaporator, where heat from the inside air 

is absorbed and changes it from a liquid to a gas. 

The low pressure gas, the refrigerant moves to the compressor where the entire cycle 

is repeated. 

 

 

 

 

 

Page 51: BUILDING SERVICES PROJECT 2

6.2.2 Air Cycle 

A process to distribute treated air into the room that needs to be conditioned 

by compression and expansion of hot bleed air. The advantages of air cycle are 

environmentally benign, no pollution and high efficiency by working together with 

refrigerant cycle. 

AHU retrieves a set mixture of outside air and return air and supplies the areas 

in need of the conditioned air. Latent heat inside the room is removed when the return 

air is absorbed by the evaporator. The medium to absorb the heat is either air or water. 

Air can be distributed through ducts or chilled water pipes. Internal air become cooler 

when heat is removed from the interior. 

  Most often the AHU is equipped with a heating, cooling coil or both to supply 

the area with appropriately conditioned air. A reheat system is added into the 

ductwork if necessary. 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure: Air Cycle (Drexel, n.d.) 

Page 52: BUILDING SERVICES PROJECT 2

6.2.3 Components of Air Cycle 

1. Air Handling Unit (AHU) 

  For heating, cooling, humidifying, dehumidifying, 

  filtering and distributing air. Recycling some of 

  the return air from the room. 

 

2. Air Filter 

  Reduce the quantity of dust released into the room 

 

3. Humidifier or dehumidifier 

  Required only if humidity is an issue 

 

 

4. Blower Fan 

  To propel the air for distribution. Centrifugal fan is commonly used in AHU as it 

  can move a small or large quantity of air efficiently. Propeller fan is used 

  especially to remove heat from the condenser 

 

 

 

 

 

 

 

 

Figure: Air Handling Unit 

Figure: AC Centrifugal Fan 

Figure: Humidifier 

Page 53: BUILDING SERVICES PROJECT 2

5. Ductwork & Diffusers 

  To distribute the air from AHU to the rooms that need to be air‐conditioned. 

  Usually the ductwork is hidden inside the suspended ceiling. A diffuser is placed 

  at the part where the air comes out. 

 

 

 

 

 

 

6. Clean Air Intake 

  To renew the contents of air to be distributed which contains heat and dirt will 

  be returned. 

   

MS 1525:2007 code 8.4.1.2.1  

Control setback and shut‐off Each system should be equipped with a readily accessible means of shutting 

off or reducing the energy used during periods of non‐use or alternate uses of the building spaces or 

zones served by the system. The following are examples that meet these requirements: 

 a) Manually adjustable automatic timing devices;  

b) Manual devices for use by operating personnel; and  

Figure: Ductwork  Figure: Diffuser 

Page 54: BUILDING SERVICES PROJECT 2

6.3 Types of Air Conditioning System 

There are few types of air‐ conditioning system in the market: 

e. Room air‐conditioner (Window unit) 

f. Split unit air‐ conditioning system 

g. Packaged unit air‐ conditioning system 

h. Centralized/ plant air‐ conditioning system 

6.3.1 Purposed Air Conditioning System in Elderly Center 

a. Split Air Conditioning System 

The split air conditioner is one of the most widely used type of the air conditioners that 

catching up with the earlier window air conditioner which was used extensively. The 

main reasons behind the popularity of split air conditioner are their advantages in silent 

operation, elegant looks and it doesn’t need to drill a hole in the wall to install and thus 

preserve the appearance of the wall. Nowadays, there are wide range of brands, color 

and design of indoor units available in the market. 

Advantages  Disadvantages 

Quick and easy to install & operate Rarely designed into the fabric of the 

building & can look unsightly 

Individual temperature control and 

suitable for small areas/ rooms. 

Have a maximum vertical and total 

refrigeration pipe work length allowable. 

Cool spaces very quickly and are easy to 

control via a remote control. 

Installation is less disruptive to other 

unrelated area. 

No ductwork means less labor costs, 

quicker and more affordable installation. 

Low maintenance costs. The indoor 

Page 55: BUILDING SERVICES PROJECT 2

compo

remove

 

6.3.2 C

There a

outdoo

these t

The ind

split air

a.

b.

c.

d.

 

 

 

 

 

6.3.3 P

a.

Wall m

can be 

also su

fulfill d

Figure

indoor

nents, air f

ed and clea

Compone

are two ma

or unit (Figu

two major p

door unit o

r‐ condition

Wall Moun

Ceiling Mo

Floor Stan

Floor/Ceili

Purposed ty

Wall Moun

ounted typ

installed o

itable to co

ifferent siz

: Wall moun

r unit 

filters can e

aned. 

ents in Sp

ain parts of

ure 1,2). Th

parts that c

f the split A

ners can be

nted Type 

ounted Cas

ding Type 

ing Suspen

ypes of Indo

nted Type 

pe air cond

n your mo

ondition a r

zes of room

ted type 

easily be 

plit Unit S

f the split a

here are co

connecting

AC is insta

e found: 

ssette Type

nded Dual T

oor Units 

ditioner can

st convenie

room with 

m. 

Figure

indoor

2016)

System 

air conditio

opper tubin

g between t

lled inside 

Type 

n be placed

ent part of

small area 

: Ceiling mou

r unit (Subur

ner which 

ng and othe

the indoor 

the room f

d strategica

f the wall w

as it offers

unted type 

rban Splits, 

are the ind

er compone

and outdo

for cooling,

 

lly in the ro

without bloc

s different 

Figure

outdoo

door unit an

ents apart 

oor units. 

, several ty

oom which

cking the w

horse pow

: Wall mount

or unit 

nd the 

from 

ypes of 

h it can 

way. It 

wer to 

ted type 

Page 56: BUILDING SERVICES PROJECT 2

b. Ceiling Mounted Cassette Type 

The duct‐free split heat‐pump systems provide comfort in large, open spaces.Duct‐

free installation with an aesthetically pleasing indoor unit design. The four‐way 

controlled louvers and fan speed features on these ceiling cassette indoor units allow 

for even air distribution. Easy control through a wireless remote or wired wall‐mounted 

controller. 

6.3.4 Components of Indoor Unit 

The components including evaporator coil, air filter, blower, drain pipe and fins.  

1. Evaporator coil/ Cooling coil 

The cooling coil is a copper coil made of number turns of the 

copper tubing with one or more rows depending on the capacity 

of the air conditioning system. The evaporator drawn the hot air 

over the coil that filled with refrigerant, produce cool air. 

2. Air filter 

It removes all the dirt particles from the room air and helps 

supplying clean air to the room.  

3. Blower 

The blower sucks the hot and unclean air from the room and 

supplies cool and clean air back.  

4. Fins 

The louvers help changing the angle or direction in which the air 

needs to be supplied into the room as per the requirements.  

5. Drain Pipe 

The drain pipe helps removing dew water collected inside the 

indoor unit. 

 

 

Page 57: BUILDING SERVICES PROJECT 2

6.3.5 Components of Outdoor Unit 

The outdoor unit is installed outside the room in open space for the ease of installation 

and maintenance, consist components like compressor, condenser, expansion valve, 

condenser cooling fan and etc. It can be hide either at the back yard of the house or at 

the roof top. 

1. Compressor 

It compresses the refrigerant and increases its pressure before 

sending it to the condenser. In most of the domestic split air 

conditioners hermetically sealed type of compressor is used. External 

power for compressing refrigerant has to be supplied to the compressor. 

2. Condenser 

The high temperature and pressure refrigerant from the compressor 

comes in the condenser to give up the heat. The tubing is made up 

of copper for higher heat. The condenser is also covered with the 

aluminum fins so that the heat from the refrigerant can be removed at faster rate. 

3. Condenser Cooling Fan  

It absorbs the surrounding air and blows it over the compressor and 

the condenser to cool them. The hot air is released back to the open 

space and the circulation of air continues unhindered. 

4. Expansion Valve 

The high pressure and medium temperature refrigerant leaves the 

condenser and enters the expansion valve, where its temperature 

and pressure drops suddenly. 

 

 

 

 

Page 58: BUILDING SERVICES PROJECT 2

6.3.6 C

Copper

The ref

connec

refriger

The dis

possibl

  

 

 

 

 

 

 

 

Figur

MS 152

Temper

of temp

over a m

MS 152

Outdoo

other m

Compone

r Tubing 

frigerant pi

cts the indo

rant to the 

stance betw

e. 

e: Wall Mou

5:2007 code

rature Contro

perature. Eac

minimum ran

5Code 8.4.4

r air supply a

means of auto

ents that 

iping is mad

oor and the

 cooling co

ween the in

nted AC 

e 8.4.1  

ol Each syste

ch thermosta

nge of betwe

.2  

and exhaust 

omatic volum

Connects

de up of co

e outdoor u

oil and the 

ndoor and 

em should be

at should be 

een 22’C to 2

systems sho

me shut‐off o

Figure

s Indoor &

opper tubin

unit. It cons

other to re

the outdoo

e provided w

capable of b

27’C. 

ould be provi

or reduction

: Ceiling cass

& Outdoo

ng covered

sists of two

eturn the re

or unit sho

with at least o

being set by a

ided with mo

during perio

sette AC 

or Unit 

d with insul

o pipes: on

efrigerant t

uld be kept

 

Figure: C

one thermos

adjustment o

otorized or g

od of non‐use

ation and i

ne to supply

to the com

t as minimu

Components

stat for the re

or selection o

gravity damp

e or alternat

y the 

mpressor. 

um as 

s of split AC

egulation 

of sensors 

pers or 

te use of

Page 59: BUILDING SERVICES PROJECT 2

6.4 Consideration for placement  

6.4.1 Consideration for placement of the indoor unit  

a. The indoor unit is located inside the room at the location from where the air can 

be distributed evenly throughout the room. 

b. The wall mounted indoor unit should be located at the height of about 8 to 10 

feet (2.4m) from the floor so that that most of the chilled air is used for cooling 

the room. 

c. The indoor unit should be accessible easily so that one can conveniently clean 

the filter every fortnight and also easier to change the position of the louvers 

manually. 

d. If the indoor unit is installed above certain window, make sure that it is in 

symmetry with the window to add aesthetics of the room but not destroy it. 

 

6.4.2 Consideration for placement of the outdoor unit  

a. The outdoor unit should be located in the open space (preferably on the terrace) 

so that the air can flow freely over the compressor and the condenser. If the 

terrace is not available, it can be kept on the awning or hanged on the external 

wall supported by the angles. 

b. The location of outdoor unit should be easily accessible for carrying out the 

maintenance works of the compressor, condenser, and other devices. 

c. There should not be any hindrances in front of the outdoor that would block 

the passage of fan air from passing to the open space. Any blockages will affect 

the performance of the air conditioners and can also lead to the burning of 

hermetically sealed compressor coil. 

d. The surface on which the outdoor unit is to be installed should be rigid enough 

to avoid its vibration. The vibration of the outdoor unit will raise excessive noise 

and also lead to the breaking of the copper tubing and leakage of the refrigerant. 

 

 

 

Page 60: BUILDING SERVICES PROJECT 2

 

 

 

 

 

 

6.4.3 Position of Indoor & Outdoor Units‐ Zone Control Unit 

   

Figure: placement of indoor & 

outdoor unit 

Figure: placement of 

outdoor unit on rooftop 

Figure: placement of outdoor 

unit on angle 

Page 61: BUILDING SERVICES PROJECT 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 62: BUILDING SERVICES PROJECT 2

6.5 Types of split unit air‐ conditioning system: 

a. Split unit without outside air (ductless) 

Ductless split system recycles and recirculates the indoor air as it provides no supply of 

renew fresh air to the interior. The main advantages of ductless split are it is easy to 

install, lower up‐front cost and can be placed strategically to cool particular area in the 

house. However, compared to ducted system, the air is not circulated, dehumidified or 

filtered. 

b. Split unit with outside air (ducted) 

Ducted system allows to cool multiple rooms using only one system. It provides 

efficient cooling throughout the room and have larger capacity. The indoor unit is 

usually concealed in the ceiling or under the floor. Conditioned air is circulated via 

flexible ducting and controlled by a control panel. 

c. Variable refrigerant flow (VRF) / Variable refrigerant volume(VRV) 

 

6.5.1 Purposed Split Air Conditioning System 

Variable refrigerant flow (VRF) / Variable refrigerant volume(VRV) 

VRV system is a multi‐ split type air conditioner that uses variable refrigerant flow to 

maintain individual zone control in each room. The coolant material in this system is 

refrigerant instead of chilled water system. 

There are 3 types of of multi‐Split System under VRF: 

1. Master and slave system 

One outdoor unit is connecting to several indoor units function as the master setting. 

Slave units control itself while Master unit control individual unit or all units at the 

MS 1525:2007 code 8.4.1  

Temperature Control Each system should be provided with at least one thermostat for the 

regulation of temperature. Each thermostat should be capable of being set by adjustment or 

selection of sensors over a minimum range of between 22’C to 27’C.

Page 63: BUILDING SERVICES PROJECT 2

same time. It is suitable for single rooms or even multiple rooms with similar heat gain 

or loss. 

2. Variable refrigerant volume (VRV) systems 

Variable capacity with heating and cooling‐ 3 pipe system 

One outdoor unit connects to several indoor units. By installing a 3rd refrigerant pipe, it 

provides total versatility that each indoor unit may cool/heat independently. The 

indoor units can be wall mounted, ceiling mounted, ceiling suspended, floor standing 

and etc. 

3. Zoned Control Units 

Variable capacity all cooling or all heating‐ 2 pipe system 

For the elderly center in tropical climatic condition, zone control units were purposed. 

Zoned control units 

Variable capacity all cooling or all heating‐ 2 pipe system 

One heat pump unit connects to several indoor units while each unit has its own 

individual temperature controller thus maintain the individual room temperature. The 

limitation is only one function (cooling/heating) can be provided by the same system at 

as the compressors willonly function in either cooling or heating mode. 

However, in tropical climate environment, only cooling function will be undergo, 

therefore zone control units will be sufficient to provide air‐ conditioning. 

 Figure: 2 pipe system‐ cooling operation (Hardy,n.d.) 

Page 64: BUILDING SERVICES PROJECT 2

 

6.6 UBBL Requirement or Related Regulations 

UBBL section 41 Law Section 10 Water Closets and toilet 

Water closets, toilets, lavatories, bathrooms, latrines, urinals or similar rooms or 

enclosures used for ablutions which are situated in the internal portions of the building 

and in respect of which no such external walls(or those overlooking verandahs, 

pavements or walkways) are present, shall be provided with air‐ conditioning having a 

minimum of fresh air change at the rate of 0.61cm per square meter of floor area of 

then air changes per hour, whichever is the lower. 

UBBL section 41(1) Mechanical Ventilation & air conditioning 

Where permanent mechanical ventilation or air‐conditioning is intended, the relevant 

building by‐laws relating to natural ventilation, natural lighting and heights of rooms 

may be waived at the discretion of the local authority. 

UBBL section 41(2) Mechanical Ventilation & air conditioning 

Any application for the waiver of the relevant by‐laws shall only be considered if in 

addition to the permanent air‐conditioning system there is provided alternative 

approved means of ventilating the air‐conditioned enclosure, such that within half an 

hour of the air‐conditioned system failing, not less than the stipulated volume of fresh 

air specified hereinafter shall be introduced into the enclosure during the period when 

the air‐conditioning system is not functioning.  

 

Figure: 2 pipe system‐ heat pump operation (Hardy,n.d.) 

Page 65: BUILDING SERVICES PROJECT 2

MS 1525:2007 code 8.2 System and Equipment Sizing  

8.2.2 Where chillers are used and when the design load is greater than 1000 kWr, a 

minimum of two chillers or a single multi‐compressor chiller should be provided to 

meet the required load.  

8.2.3 Multiple units of the same equipment type, such as multiple chillers, with 

combined capacities exceeding the design load may be specified to operate 

concurrently only if controls are provided which sequence or otherwise optimally 

control the operation of each unit based on the required cooling load. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 66: BUILDING SERVICES PROJECT 2

1.0 Int

Ventila

and hu

ventilat

occupa

and em

place a

and int

 

Ventila

draw o

Besides

will get

structu

Headac

poor ve

environ

continu

risks. 

 

Ventila

mechan

proper

ventilat

stale ai

troductio

tion is a pr

midity con

tion, therm

ants and to 

missions fro

nd circulat

terior comf

tion is mai

ut the war

s, a proper 

t rid of moi

ural support

ches, Drow

entilation a

nment for m

uously supp

tion can be

nical ventil

ly and ther

tion depen

r and draw

 

n  

rocess whe

trol and no

mal mass an

 remove po

om the build

ting air with

ort level. 

nly serving

m air from 

 ventilation

isture. It wi

t. Bad air q

wsiness and

and moistu

mould and 

plying fresh

e divided in

ation. Natu

re is difficu

ds on num

wing in the f

ere air exch

ormally is c

nd solar gai

ollutants th

ding mater

hin a space

g as cooling

the buildin

n can helps

ill prevent 

quality cond

d respirator

re control i

dust mites

h air to occ

nto two dif

ural ventila

lty in contr

merous varia

fresh air. R

hange is tak

ombined w

n. It helps t

hat generat

rials and fu

e. Therefore

g purpose. 

ng and flus

s in humidit

mould hap

dition can c

ry problem

is happene

s to form. H

cupants, it c

fferent type

tion needs

rolling the a

able aspect

Rather than

ke place an

with the int

to replenis

ted by brea

rnishing wh

e, ventilatio

During the

h in fresh c

ty control, 

pens and c

contribute 

s are the c

ed. As sogg

Hence, a bu

can result i

es, which a

 a high air 

air airflow. 

ts to dictat

n natural ve

d includes 

teraction w

h oxygen u

athing, hou

hen air exc

on is crucia

e process c

cool air fro

as an unint

cause dama

to health d

ommon sy

y condition

uilding sho

in mitigatin

are natural 

pressure d

Thus, the 

te efficienc

entilation, m

heating, co

with natural 

used by the

usehold act

change is to

al to our he

hanging air

om the outs

terrupted a

age to woo

damage. 

mptoms w

n is the per

uld ensure 

ng these he

ventilation

ifference t

process of

y in remov

mechanical 

ooling 

ivities 

ook 

ealth 

r, it will 

side. 

air flow 

od 

when 

rfect 

to 

ealth 

n and 

o work 

f natural 

ving the 

Page 67: BUILDING SERVICES PROJECT 2

ventilation is more often to use in Malaysia’s building. As the process of mechanical 

ventilation can ensure that the building or the interior space is consistently ventilated. 

 

Types of mechanical ventilation system 

Circulation system  

A circulation system such as ceiling fans are commonly visible circulation system in a 

building. Ceiling fan creates internal air movement but do not provide real ventilation, 

as there is no introduction of fresh air. It only circulates air within a room for the 

purpose of reducing the perceived temperature by method of evaporation of 

perspiration on the skin of the occupants. 

 

 

Figure 1.1 Example of ceiling fan 

Page 68: BUILDING SERVICES PROJECT 2

Diagram 1.1shows the position of the ceiling fans in the elderly care center

Page 69: BUILDING SERVICES PROJECT 2

Whole‐House ventilation systems 

Whole‐house ventilation systems have three different types of air movement involve 

which are the supply system, exhaust system and balanced system. The main purpose 

of having a whole‐house ventilation system is to provide a continuous air change for 

fresh and filtered air to maintain healthy living conditions for the occupants. Whole‐

house ventilation system do not cool the temperature of the spaces like circulation 

system does. As whole‐house ventilation systems are designed to deliver building with 

fresh and filtered air, thus these systems can prevent damp, condensation and mould 

problems.  

Comparison of Whole‐House Ventilation Systems  

Mechanical Ventilation System 

Pros Cons 

Supply system 

 

Easy to install  Inexpensive  Prevent back drafting of 

combustion gases  Minimize pollutants from 

outside  Allow filtering of pollen and 

dust  Better control of ait enters 

into the building  Dehumidification of outside 

air  

Will not remove moisture from incoming air 

Increase heating and cooling costs  

Exhaust system  easy to install  inexpensive  

 

Draw in pollutants  Increase heating and 

cooling costs  Cause back drafting in 

combustion appliances. 

Balanced system  Suitable for all kind of climates 

Allow filtering of pollen and dust 

Costs more to install and operate 

Increase heating and cooling costs  

Page 70: BUILDING SERVICES PROJECT 2

Supply system 

Diagram 1.2 shows how a supply system works 

 

A supply system uses a fan or other blower which placed at the inlet to blow 

outside air through the building. It will create a greater internal pressure than 

the outer atmosphere. 

Supply ventilation system is simple and inexpensive to install. It is normally 

installed in rooms that visitors occupy most, for example, bedrooms, meditation 

room, café and dance room. A typical supply ventilation system consists of a fan 

and duct system that introduces fresh air into the space. Other than that, it may 

include adjustable window or wall vents in other rooms that not many visitors 

occupy. 

Supply ventilation system allows better control of the air that enters to the 

building. It can minimize outdoor pollutant inside the building and also 

preventing back drafting of combustion gases from the fireplaces and 

appliances by pressurizing the internal pressure of the building. Besides, a 

Page 71: BUILDING SERVICES PROJECT 2

supply ventilation system can provide humidity control and filtration. It can 

dehumidify and remove pollen and dust particles found in the outdoor air 

before the air enter to the building.  

Comparing between hot climates and cold climates, supply ventilation system 

work best in a hot climate country. As supply ventilation draws outside air into 

the building, it will cause the warm interior air leak through openings and lower 

the indoor temperature. 

Figure 1.2 Example of supply fan

Diagram 1.3 shows the position of supply fans in the elderly care center.

Page 72: BUILDING SERVICES PROJECT 2

Justification 

Ground floor 

M&E room: helps to reduce the heat that produced from the devices in M&E room. 

First floor 

Pantry: helps to bring in fresh air from the outside as the space is small. 

Meditation Room: bring in ‘Green’ fresh air to the interior space of the meditation room to enhance the air quality. 

Resource Area: helps to reduce the heat that produced form the computers.

 

Exhaust system 

Diagram 1.4 shows how an exhaust system works 

An exhaust system works opposite of the pressure system.  Vacuum system 

extracts internal air from the building causing an inrush of fresh air by an 

exhaust fan which placed at the outlet. It will cause the internal pressure is 

lower than the outer atmosphere. 

Same as Supply ventilation system, exhaust ventilation is simple and inexpensive 

to install.  A typical exhaust ventilation system involves a single fan which will be 

connected to a single exhaust point in the house. It is normally installed in 

rooms where pollutants are generated, such as bathrooms, café and pantry. 

Page 73: BUILDING SERVICES PROJECT 2

Exhaust fan is preferably compared to passive vents through windows. For the 

reason that passive vent requires a high pressure differences to work properly.  

Excluding fresh air, an exhaust ventilator may draw in pollutants too. These 

pollutants including dust, fumes and flue gases which are should be concerned 

when bath fans and exhaust ventilator are both operating.  

Diagram 1.5 Example of toilet exhaust ventilation system

Diagram 1.6 Example of kitchen exhaust ventilation system

Page 74: BUILDING SERVICES PROJECT 2

Diagram 1.7 shows the position of exhaust fans in the elderly care center. 

 

Justification 

Ground Floor 

Washroom: to remove stale air and moisture from the washrooms. 

Kitchen:  to remove airborne grease, combustion products, fumes, smoke, odours, heat, and 

steam from the air by evacuation of the air and filtration. 

First Floor 

Washroom: to remove stale air and moisture from the washrooms. 

Page 75: BUILDING SERVICES PROJECT 2

Balanced

 

A balanced

uses both 

the extern

In a balanc

every room

time and ro

example to

consists of

more expe

Neverthele

system can

outside air

 system 

Diagram 

d system is

inlet and o

al atmosph

ced system

m but most

ooms wher

oilet, art cra

f two duct 

ensive to in

ess, a balan

n function 

r before it i

1.8 shows 

s a combina

outlet fan to

here.   

, fresh air s

tly will be i

re moisture

aft room an

and fan sy

nstall and o

nced system

as air filtra

ntroducing

how a bala

ation of pre

o maintain 

supply and

nstalled in 

e and pollu

nd kitchen.

stems. The

perate.  

m is suitab

tion becau

g it into the

anced syst

essure syst

the interna

 exhaust ve

rooms whe

utants are o

. In a balan

erefore, bal

le for all ty

se it can re

e house. Ba

em works 

tem and va

al air press

ents can be

ere visitors

often gener

ced ventila

lanced syst

pes of clim

emove dus

alanced ven

cuum syste

ure is simil

e installed 

s spend the

rated. For 

ation syste

tems are us

mate. Balanc

t and polle

ntilation sy

em. It 

ar to 

in 

e most 

m, it 

sually 

ced 

n from 

ystems 

Page 76: BUILDING SERVICES PROJECT 2

supply fresh air to the interior spaces and exhausting stale air at the same time 

at an equal rate. This result the indoor air quality improved.  

Diagram 1.9 shows the position of balanced system in the elderly care center. 

Justification 

Groud Floor 

Dance Studio: As the dance studio is the most occupant and where moisture and pollutants are often generated due to the activity that conducted, balanced system can help to remove pollutants and introduce fresh air into the enclosed space.

Figure 1.3 Example of balanced ventilator 

Page 77: BUILDING SERVICES PROJECT 2

Main components of Mechanical Ventilation System 

1. Ducts  Ducts are used to channels the air from those interior spaces to outside of the buildings. Air ducts can ensure the indoor air quality by delivering stale airthroughout the tunnels and remove the stale air.  

 Figure 1.4 Example of duct  

2. Vent adapter 

A vent adapter helps to maximize the ventilation system. It connects ducts to each other 

with a round duct connector and help to reduce energy consumption by installing 

ventilators in areas remote from air intake with an inline adapter kit. 

 Figure 1.5 example of a vent adapter. 

3. Fire Damper Wherever the duct passes through a firewall, a fire damper will be found. There is fusible link in afire damper, it will melt or break when the temperature has reached at a certain temperature. This will allow the damper to close and preventing the necessary air to burn. 

Page 78: BUILDING SERVICES PROJECT 2

 Figure 1.6 Example of a fire damper   

4. Air filter 

An air filter can be found in most of the mechanical ventilation system. Typically, there 

are at least two filters that stand guard over the building’s air. Air filter helps to remove 

bacteria and harmful particles that found in the air that coming into the buildings. 

Figure1.8  Example of an air filter 

5. Range Hood 

A range hood is installed above the stove or cooktops. It removes airborne grease, 

combustion products, fumes, smoke, odors, heat, and steam from the air by evacuation 

of the air and filtration. 

Figure 1.7 Example of different dimension of fusible link. 

Page 79: BUILDING SERVICES PROJECT 2

 Figure1.9 Example of a range hood 

6. Faceplate 

A perforated plate, mounted on the live spindle, to which the work is attached. 

  

7. Roof cap 

A roof cap is designed to exhaust kitchen and bath fans through the roof. 

  

Figure1.11 example of a Kitchen exhaust roof cap. 

   

Figure1.10 example of a 

supply system faceplate 

 

Page 80: BUILDING SERVICES PROJECT 2

UBBL 

By‐Laws (41), Mechanicals ventilation and air‐conditioning 

(1) Where permanent mechanical ventilation or air conditioning is intended, the 

relevant building by‐laws relating to natural ventilation, natural lighting and 

heights of rooms may be waived at the discretion of the local authority. 

(2)  Any application for the waiver of the relevant by laws‐ shall only be considered 

if in addition to the permanent air‐ conditioning system there is provided 

alternative approved means of ventilating the air‐conditioned enclosure, such 

that within half an hour of the air‐conditioning system failing, not less than the 

stipulated volume  fresh air specified hereinafter shall be introduced into the 

enclosure during the period when the air‐conditioning system is not functioning. 

(3)  The provisions of the Third Schedule to these By‐laws shall apply to buildings 

which are mechanically ventilated or air‐conditioned. 

 

Third Schedule By‐Laws (41), (3) Filters for exhaust fan 

(1) Filters for the removal of airborne bacteria shall be provided for all exhaust air 

discharge points to the requirements of the governing health authority. 

(2) Exhaust air discharge points shall be at high or roof level and shall not in any 

case be lower than 5 metres form the external ground or pavement level. 

 

Third Schedule By‐Laws (41), (5) Openings for mechanical ventilation system 

Where mechanical ventilation or air‐conditioning is provided‐ : 

(b) The underside of openings for the entry of air into any mechanical 

ventilation or air‐conditioning plant shall be not less than 1 metre from any 

external pavement, road way, ground level or similar external surface; 

 (c) The underside of openings for the exhaust of air from any mechanical 

ventilation or air‐ conditioning plant shall be not less than 2.5 metres from any 

exteral pavement, road way, ground level or similar external surface; 

(d) To any of the enclosures from which foul air will be exhausted, the ducts, 

trunking, service shafts or other such items containing or conveying the foul air 

from such enclosure shall in no way be connected to any air inlet system.  

 

Page 81: BUILDING SERVICES PROJECT 2

 

Third Schedule By‐Laws (41), (10) Water‐ closets and toilets. 

Water closets, toilet, lavatories, bathrooms, latrines, urinals or similar rooms or 

enclosures used for ablutions which are situated in the internal portions of the 

building and in respect of which no such external walls (or those overlooking 

verandahs, pavements or walkways) are present, shall be provided with 

mechanical ventilation or air‐ conditioning having a minimum of fresh air change 

at the rate of 0.61cmm per square metre of floor area of ten air changes per 

hour, whichever is the lower. 

 

Third Schedule By‐Laws (41), (12) Fresh air changes. 

(2) The minimum scale of fresh air ventilation in conjunction with the 

mechanical ventilation systems shall be as follow: 

Kitchen    …    …    …   20 air changes per hour

 

 

 

 

 

 

 

 

   

Page 82: BUILDING SERVICES PROJECT 2

1.0 Int

Mecha

building

mechan

elevato

of ener

by elev

Elevato

half‐ful

force to

differen

overco

elevato

it helps

much m

troductio

nical transp

g either ve

nical transp

or is lifted u

rgy to lift u

vators. 

or car is ba

ll weight el

o raise and

nce weight

me the pul

or safer. Be

s to pull loa

more easier

portation s

rtically or h

portation sy

up and dow

up and dow

lanced by a

evator car,

d lower the

t of elevato

lley. Becau

esides, coun

aded elevat

r to contro

 

system is a 

horizontally

ystem that

wn using a 

wn, but a co

a counterw

, the count

 elevator c

or car with 

se of this, 

nterweight

tors move 

l with a co

Figurecompo

system tha

y. Elevator 

t can be see

hoist and b

ounterweig

weight whic

terweight h

car. At this 

the counte

it would le

t reduce th

up and dow

unterweigh

 showing tonents of e

at transpor

and escala

en in high 

breaks, the 

ght can save

ch has a sim

helps the m

point moto

erweight, a

ss strain on

e amount o

wnwards, t

ht with it.

he system elevators.

rt goods an

ators are th

rise or low 

energy us

e most of t

milar weigh

motor used 

or only nee

and apply e

n the cable

of braking a

therefore a

nd people in

he most com

rise buildin

ed a huge 

the energy 

ht with a loa

lesser ene

ed to lift the

extra force 

es, this mak

an elevato

a elevator c

n a 

mmon 

ng.An 

amount 

used 

aded 

rgy and 

to 

kes the 

r need, 

car is 

Page 83: BUILDING SERVICES PROJECT 2

Figure showing ratchet system below the elevator 

There is a ratchet system act as a backup just in case the cable which holding the 

elevator car broke it would avoid elevator car crash to the floor level. There are sturdy 

metal teeth on the vertical guide rails of elevators, and a spring‐loaded mechanism with 

hooks attached on top on elevator cars, so if the cable broke, the elevator car will be 

lock safely at the position because the hooks will sprung outward and jammed into the 

metal teeth. 

 

There is few types of elevators which is are commonly use are traction with a machine 

room, machine‐room‐less traction, and hydraulic elevator. As our case study, the most 

suitable elevator is hydraulic elevator, because it is a low rise residential building and 

hydraulic elevator is suitable for elderly center and hospitals. 

 

Elevators  

Elevators  is a transport device usually found in multiple storeys building that used to 

move goods or people vertically in high rise buildings and also allow elderly or disable 

person access to higher levels for residential or public buildings. A minimum standard 

for elevator is 4 storeys for exception when wheelchair movement is required and a 

maximum walking distance of 45 meter. The size and number of elevators is 

determined by the population, height and scale of the building. There is few types of 

Page 84: BUILDING SERVICES PROJECT 2

elevators which is are commonly use are traction with a machine room, machine‐room‐

less traction, and hydraulic elevator. 

Hydraulic elevators 

Hydraulic elevators are a type of elevators which supported by a pistol located at the 

bottom of elevator that push to elevators up  to move vertically as an electric motor 

forces oil or another hydraulic fluid into the piston. It is normally used for low rise 

building which only have two to eight storeys with a maximum speed of 61 meter per 

minute.The machine room for hydraulic elevator located lowest level beside the 

elevator shaft. 

The advantages of choosing hydraulic elevators are the noise sources can be placed 

under the shaft, and it is safe while doing service or repair work. Other than that low 

maintenance require, simple and economical assembly. 

Hydraulic elevator used a hydraulic ram to lift and lower a elevator car, it do not use 

counterweight to lift and lower a elevator so it consume more power or energy than 

the traction elevator. Normally the hydraulic ram will be installed underneath the 

elevator car, but if there is not much space under it, it can be installed beside the lift 

shaft. 

There is also two different type of hydraulic elevator : 

 

 

 

1. Holed hydraulic elevator 

Most convenient hydraulic elevator, have a sheave extends to the bottom of elevator 

pit, which the retracting piston would goes while the elevator descends. Some holed 

hydraulic elevator designed to have telescoping piston require shallower hole below 

the pit. Travel a maximum of 18 meters. 

Page 85: BUILDING SERVICES PROJECT 2

 

 

 

2. Hole‐less hydraulic elevator 

Have piston either side of the elevator car, it divided into 3 different types : 

a. Telescopic hydraulic elevator  

Telescoping piston are fixed at the base of elevator pit and do not need to 

have a sheave or hole below it, it contain 2 or 3 pieces of telescoping 

pistons. Travels a maximum of 15 meters. 

b. Non‐telescoping (single stage) Hydraulic elevator 

Has only 1 piston and only travels a maximum of 6 meters.  

c. Roped hydraulic elevator 

A combination of rope and a piston to move the elevator.Travels a maximum 

of 18 meters. 

Figure roped hydraulic elevator 

Figure Non‐telescopic hydraulic elevator

Figure Telescopic hydraulic elevator 

Page 86: BUILDING SERVICES PROJECT 2

Component of hydraulic elevator 

Component in machine/drive system 

1. Cylinder   

Made by steel pipe with acceptable thickness and suitable for safety margin. 

Cylinder head with an internal guide ring and self‐adjusting packing was 

equipped on the cylinder. 

2. The tank 

Holds the hydraulic fluid, have sufficient spaces to provide an adequate reserve 

to prevent the entrance of air into the system, a sight glass shall be provided to 

check the level of oil and a mark that indicate the minimum level of oil. 

3. Motor/Pump 

Figure components in machine/drive system of hydraulic elevator 

Page 87: BUILDING SERVICES PROJECT 2

4.

Externa

1.

Pump is us

fluid to go 

by using th

Valve  

Valve is us

pressure a

reservoir, a

can go to t

upwards. 

al elevator 

Elevator ca

A double la

the landing

requested 

 

 

 

 

 

 

 

 

 

 

se to push 

left or righ

he force. 

se to contro

nd the pre

and when i

the cylinde

Componen

ar door 

ayered doo

g for safety

to stop. 

liquid into 

ht which al

ol the pres

ssurized flu

it is high pr

er which pu

nt 

or which 1 

y purpose. 

the cylinde

lows the el

sure of the

uid will use

ressure wh

ush the pist

is attached

It would be

Figure eleva

er to lift th

levator goi

e tank, it w

e the small 

hich the val

ton up and

d to the ele

e open on 

ator door

e elevator.

ng upward

ill open wh

path back 

ve is closed

 lift the ele

evator car a

the floor w

 It control 

s or downw

hen there is

to the fluid

d the fluid 

evator car 

and 1 attac

which was 

the 

wards 

s low 

only 

ched to 

Page 88: BUILDING SERVICES PROJECT 2

2. Fireman’s Switch 

 

 

 

 

 

 

3. Hall Lantern 

 

 

 

 

4. Call Buttons 

 

 

 

 

 

 

 

 

 

 

Figure fireman’s switch

Used for fire department to over‐ride all floor 

calling system to allow all the lifts returned to 

where the switch is located. Normally located at 

the ground floor, so that is easier to escape from 

the building. 

Used to indicate the arriving elevator and the 

direction it will travel. Dimension of hall lantern is 

a minimum of 2m above the finished floor and 

must be visible from the vicinity of the call buttons  Figure hall lantern

Figure call button

Used to request an elevator, it allow the lift stop 

at the floor which had been request. Once 

request the button will light up until the elevator 

arrive 

Page 89: BUILDING SERVICES PROJECT 2

Internal elevator Component 

1. Monitor Beam 

A small screen usually located above the floor selection button or above the lift 

door that indicate the floors that which the user is, it also indicate the lift is 

going upwards or downwards. 

 

2. Floor Selection Button 

Used to control which floor of the elevator should stop. 

 

3. Operation and Emergency Buttons 

Located below the floor selection buttons, included open door, close door 

button, emergency stop, emergency alarm, intercom and telephone. 

Figure internal monitor beam

Figure floor selection button

Figure operation and emergency buttons

Page 90: BUILDING SERVICES PROJECT 2

4. Key Switch Controls 

A locked spaces where located either above the floor selection buttons or 

below the operation and emergency buttons to allow different function to be 

turned on and off by building operation staff.   

5. Emergency Railings 

Railings located inside the lift so that it could allow user to get stable if any 

emergency occur 

 

6. Elevator ventilation 

A vent located inside the elevator car to provide at least 10 hours air change 

while the elevator door is closed.It located on top of the elevator car. 

Figure key switch controls

Figure emergency railings

Figure elevator ventilation

Page 91: BUILDING SERVICES PROJECT 2

Location of elevator  

Page 92: BUILDING SERVICES PROJECT 2

Stair lift 

Stair lift can be mostly found in residential area or transport station such as train 

station that more than 1 storey height building or houses. It is not mainly for disable 

person but for elderlies who had difficulties on walking up the stairs. 

Stair lift could get power from 2 sources, 1 is from the battery and the other is directly 

from electric‐power. They both have pros and cons. The pros of using battery is it 

could be function even there is an electric outages while electric‐power could not use. 

But battery could be suddenly die when the stair lift is being used and this could not 

happen when using direct electric‐power. 

The advantages of using stair lift are it could be easily installed at home or other 

building and can allow elderly access the whole building which more than 1 storey 

without any difficulties. It is also comfortable and slow while moving the elderly up or 

down the staircase. 

Components of stair lift

Figure stair lift

Page 93: BUILDING SERVICES PROJECT 2

1) Carriage  

A seat attached at the side of staircase which carry the user move up and down 

from the stairs 

 

2) Track 

A rail made of metal that allow the carriage move. 

 

3) Safety switch 

It lock the seat in a safe position so that the carriage does not move. It located 

on the carriage. 

Figure stair lift carriage/seats 

Figure stair lift metal track 

Figure stair lift safety switch 

Page 94: BUILDING SERVICES PROJECT 2

 

4) Limit switch (Safety Cut Out Sensors) 

A switch that control the carriage to stop when there is a obstruction in the 

path. itis a sensor located top or bottom of the track or on the seats or platform.  

 

 

5) Handheld controller 

Remote control that control the stair lift. 

 

 

Figure limit switch

Page 95: BUILDING SERVICES PROJECT 2

Location of stair lift

Page 96: BUILDING SERVICES PROJECT 2

To con

compo

the ser

comfor

clude, the 

nents to su

renity of th

rtable. 

elderly cen

uit the nee

e space, w

nter utilized

ds for elde

which is esse

d most of t

erly people.

ential in ma

the medium

. Heavy ma

aking the h

m‐scale sys

achinery is 

home liveab

tems and 

avoided to

ble and 

o retain 

Page 97: BUILDING SERVICES PROJECT 2

Air Con

 

ALS Sta 

Archto  

Archto  

Be Air  

Bilco. (n  

Brick W 

Bunche  

Chapte 

Cool‐in  

Daikin  

nditioning S

fromhttp:/

airlift. (n.d)http://ww

olbox. (n.d)from httpscirculation

olbox. (n.d)https://wwcirculation

Conditionifromhttp:/

n.d.). Type http://ww1*Type‐SV

Walls ‐ Fire 2016, from

er HydrauliRetrieved http://ww

er 10: Fire https://ww

nfo.(n.d.) MRetrieved info.co.uk/

Industry Lt10, fromht

System (n.d

//www.airc

. Why Use w.ukstairlif

). Elevator s://www.ar/elevcontr

). Elevator ww.archtoo/elevatorty

ng(2009). V//www.bea

SV Automw.bilco.comV‐‐‐Automa

Resistancem http://ww

ics.(n.d). Hy13 Novemw.bucherh

Barriers. (nww.jlab.org

Multi‐ split sNovember/multi_dx_s

td (2016). Vttps://www

d.). Window

conditioning

a Stairlift: fts.com/wh

Controls archtoolbox.ols.html 

Types. Retolbox.com/ypes.html

VRV. Retrieaircondition

matic Smokem/Foundatatic‐Smoke

e of Brick Www.azom.c

ydraulic Lifber 2016 fydraulics.c

n.d.). Retrievg/ehs/ehsm

system andr 13, from hsystems/M

VRV Multi‐w.daikin.co

w Air Cond

g‐systems.

Advantagehy‐use‐a‐st

nd Indicato.com/mate

trieved 12 /materials‐s

eved Novening.co.uk/

e Vent. Rettions/Storee‐Vent 

Walls. (200com/article

fts Are Enefrom com/argum

ved Novemmanual/fire/

 variable rehttp://wwwulti‐split%2

‐split type am/product

ditioner. Re

com/windo

es. Retrievetairlift‐adva

ors. Retrieverials‐system

Novembersystems/ve

ember 13, air_conditio

trieved Nove/shopdeta

02, June 4).e.aspx?Artic

ergy Efficie

ents 

mber 16, 20/Ch10.htm

efrigerant vw.cool‐20Systems

air conditiots/ac/lineup

etrieved No

ow‐air‐con

ed 22 Noveantages/ 

ved 12 Novms/vertica

r 2016 fromertical‐

oning_vrv.h

vember 14ail.asp?prod

 Retrieved cleID=1445

nt and Fut

016, from m 

volume(VRV

s.html 

oner. Retriep/vrv/ 

ovember 13

nditioner.ht

ember 201

vember 20l‐

htm 

4, from duct=1SV‐

Novembe5 

ure‐oriente

V) system. 

eved Nove

3, 

tml

16 from 

016 

r 15, 

ed. 

mber 

Page 98: BUILDING SERVICES PROJECT 2

Easy Climber.(n.d). How to Choose a Stairlift. Retrieved 22 November 2016 from   https://www.easyclimber.com/how‐to‐choose‐a‐stair‐lift/ 

Electrical Know How. (n.d). Hydraulic Elevators Basic Components. Retrieved 13   November 2016 from http://www.electrical‐  knowhow.com/2012/04/hydraulic‐elevators‐basic‐components.html 

Fabri‐Lock. (2014). Draft Curtain, Curtain Boards & Smoke Curtains. Retrieved   November 14, from http://www.smokeandfireprevention.com/curtain.htm 

Fire and steel construction ‐ Steelconstruction.info. (n.d.). Retrieved November 14,   2016, from http://www.steelconstruction.info/Fire_and_steel_construction 

Fire Detection & Alarm Systems | Tyco SimplexGrinnell. (n.d.). Retrieved November 22,   2016, from https://www.tycosimplexgrinnell.com/how‐we‐can‐help/protect‐  your‐business/fire‐detection‐and‐alarm 

Fire Detection & Alarm Systems and Solutions. (n.d.). Retrieved November 21, 2016,   from https://www.mircom.com/fire 

Fire resistance. (n.d.). Retrieved November 14, 2016, from   http://www.concretecentre.com/Performance‐Sustainability‐(1)/Fire‐  Resistance.aspx 

Fire Sprinkler Wet & Dry Pipe Systems. (n.d.). Retrieved November 22, 2016, from   http://dynamicpiping.com/Systems.html 

Fujitsu (2015). Ducted Air Conditioning Solution. Retrieved November 10,   fromhttps://www.fujitsugeneral.com.au/docs/default‐  source/Brochures/fujitsu_ducted_range_brochure_web_lr.pdf 

Hoffman, P.(2006) Basic Refrigeration Cycle. Retrieved November 10,   fromhttps://www.swtc.edu/ag_power/air_conditioning/lecture/basic_cycle.htm 

How sprinklers work ‐ Fire Sprinker Initiative. (n.d.). Retrieved November 22, 2016,   from http://www.firesprinklerinitiative.org/advocacy‐tools/fact‐sheets/how‐  sprinklers‐work.aspx 

Introduction to Fire Protection Systems ‐ pdhonline.com. (n.d.). Retrieved November 22,   2016, from http://www.pdhonline.com/courses/m110/Module4.pdf 

Khemani, H. (2013). Types of Air Conditioning Systems. Retrieved November 13,   fromhttp://www.brighthubengineering.com/hvac/897‐types‐of‐air‐  conditioning‐ systems/ 

Legal Research Board. (2013). Uniform Building By‐Laws 1984. Petaling Jaya: SS Graphic   Printers. 

Page 99: BUILDING SERVICES PROJECT 2

Lygate, J.F. & Nolan, S. (n.d.). Compartmentation and Fire Sealing. Retrieved November   14, from   http://www.airm.ie/system/download_images/41/original/Compartmentation%  20and%20Fire%20Sealing.pdf?1353591110 

Malaysia Clay Brick. (2011). Double Brick Cavity Wall. Retrieved Novermber 14, from   http://myclaybrick.com/html/whybrick‐doublebrick.html 

Mitsubishi Electric Corporation (2016).Ducted Air Conditioning. Retrieved November   10, fromhttp://www.mitsubishielectric.com.au/ducted‐air‐conditioning.html 

O'Brien, P. (2016). Issues Relating to Certificates of Compliance. Retrieved November   14, 2016, from   https://www.engineersireland.ie/EngineersIreland/media/SiteMedia/groups/Div  isions/civil/05‐Issues‐Relating‐to‐Certificates‐of‐Compliance‐by‐Assigned‐  Certifiers‐Philip‐O‐Brien.pdf?ext=.pdf 

Panasonic Australia (2016). Panasonic Air Conditioning Buyer’s Guide – Part 2 of 2.   Retrieved November 10,   fromhttps://blogs.panasonic.com.au/consumer/2016/08/13/air‐conditioning‐  buyers‐guide‐part‐2‐of‐2/ 

Protection of Openings and Fire Stopping. (n.d.). Retrieved November 14, 2016, from   http://cvcdirect.co.uk/Firestopping%20Section%2011.pdf 

Shield, TL.(n.d). The “Nuts & Bolts” About Elevators. T.L. Shield & Associates, Inc.   Retrieved 13 November 2016from https://www.tlshield.com/nuts‐bolts‐about‐  elevators 

Sprinkler Head Spacing and Location ‐ archtoolbox.com. (n.d.). Retrieved November22,   2016, from https://www.archtoolbox.com/materials‐systems/fire‐  supression/sprinklerspacing.html 

Stanco Climate Control (2015). Ducted and Ductless Air Conditioning: What it Means   and How to Choose. Retrieved November 10, from   http://stancoclimate.com/ducted‐and‐ductless‐air‐conditioning‐what‐it‐means‐  and‐how‐to‐choose/ 

Thermal Fire Detectors Working Principle. (2015). Retrieved November 22, 2016,   from http://marineengineeringonline.com/thermal‐fire‐detectors/ 

Top 5 Fire Alarm Strobe Visual Signal Challenges. (n.d.). Retrieved November 21, 2016,   from https://www.mircom.com/blog/item/248‐top‐5‐fire‐alarm‐strobe‐visual‐  signal‐challenges 

Page 100: BUILDING SERVICES PROJECT 2

Wet Pipe Fire Sprinkler System. (n.d.). Retrieved November 22, 2016, from   http://www.afpgusa.com/wet‐pipe‐fire‐sprinkler‐system.php 

Woodford, C. (2016). How smoke detectors work. Retrieved November 22, 2016,   from http://www.explainthatstuff.com/smokedetector.html 

Woodford, C. (April 28, 2016). Elevators. Explain That Stuff. Retrieved 12 November   2016 from http://www.explainthatstuff.com/how‐elevators‐work.html