Bscience final
-
Upload
kelvin-fong -
Category
Science
-
view
39 -
download
0
Transcript of Bscience final
1
SCHOOL OF ARCHITECTURE, BUILDING & DESIGN
2
TABLE OF CONTENT
Page
1.0 INTRODUCTION 1.1 Objective ………………………………………………………………………………………….......... 3
1.2 Floor Plan ……………………………………………………………………………………………….4-6
2.0 LIGHTING STUDY 2.1 Daylighting Analysis …………………………………………………………........................... 7-8
2.1.1 Medical Herb Store ……………………………………………………………….. 9-10
2.1.2 Therapy Room ……………………………………………………………………. 11-12
2.2 Artificial Lighting Analysis + PSALI
2.2.1 Medical Herb Store ………………………………………………………………. 13-18
2.2.2 Therapy Room ……………………………………………………………………. 19-23
3
1.0 INTRODUCTION
1.1 OBJECTIVE
This project aims to integrate students' understanding of the principles of lighting design in
the context their final design project of studio 04 / 05. From this project, we are able to show
understanding of artificial lighting and daylighting strategies (PSALI) in our final design.
Besides, we are able to solve design problems in relation to sustainability issues (natural
lighting, site analysis) and design spaces incorporating artificial and daylighting (when
necessary).
4
1.2 FLOOR PLAN
GROUND FLOOR PLAN
5
FIRST FLOOR PLAN
6
SECOND FLOOR PLAN
7
2.0 LIGHTING
2.1 Daylighting Factor Analysis
Where,
Ei = Illuminance due to daylight at a point on the indoor working plane
Eo = The unobstructed horizontal exterior illuminance, average day light level in Malaysia (EH) is
assumed to be 20000 lux
A standard sky is assumed to give a minimum level of illuminance on the ground.
According to MS1525, Day Light Factor distribution as below:
Natural Illumination Calculation
Illuminance Example 120,000 lux Brightest sunlight
110,000 lux Bright sunlight
20,000 lux Shaded illuminated by entire clear blue sky
1000-200 lux Typical overcast day, midday
< 200 lux Extreme of darkest storm clouds, midday
400 lux Sunrise or sunset on clear day
40 lux Fully overcast, sunset/ sunrise
< 1 lux Extreme of darkest storm clouds, sunset/ sunrise
8
ROOM ILLUMINATION LEVEL
9
2.1.1 Medical Herb Store
Ground Floor Plan
The selected Medical Herb Store area is located at the ground floor, which strategically placed at the front
perimeter of the building. The space are fully exposed during the daytime due to no obstruction is blocking
the sunlight.
Floor Area (𝑚2) 75.05 𝒎𝟐
Area of opening exposed to sunlight (𝑚2) Perimeter: 7.6m+ 4.5m =12.1m Height: 3m
Area: 22.8𝑚2 + 13.5𝑚2 =36.5𝒎𝟐
Daylight Factor, DF =36.5𝑚2
75.05 𝑚2 x 100%
= 48.63% x 0.1 = 4.86%
10
Given that Eo = 20000 lux
DF = 𝐸𝑖
𝐸𝑜 x 100%
4.86% = 𝐸𝑖
20000 x 100%
𝐸𝑖 = 972 lux
CONTOUR DIAGRAM OF DAYLIGHT FACTOR
Conclusion:
The selected Medical Herb Store area has a daylight factor of 4.86% and natural illumination
of 972 lux. Based on the recommendation of MS 1525, a conventional shop should maintain
the illuminance in between 200 lux to 750 lux, so the medical herb store area is brightly lit by
daylight as the value exceeds the standard but the daylight factor calculated (4.86%) is
maintained in between 3 – 5%, which mean the distribution of light is considered good in the
medial herb store area.
2.1.2 Therapy Room
11
First Floor Plan
The selected Therapy is located at the first floor, which also strategically placed at the back perimeter of
the building. The windows of the space are facing to north direction. The space are fully exposed to direct
sunlight during the daytime due to no obstruction is blocking the sunlight.
Floor Area (𝑚2) 39 𝒎𝟐
Area of opening exposed to sunlight (𝑚2) Perimeter: 1m+ 1m+ 1m+ 1m+1m =5m Height: 4m
Area: 20𝒎𝟐
Daylight Factor, DF =20𝑚2
39 𝑚2 x 100%
= 51.28% x 0.1 = 5.13%
Given that Eo = 20000 lux
12
DF = 𝐸𝑖
𝐸𝑜 x 100%
5.13% = 𝐸𝑖
20000 x 100%
𝐸𝑖 = 1026 lux
CONTOUR DIAGRAM OF DAYLIGHT FACTOR
Conclusion:
The selected Therapy area has a daylight factor of 5.13% and natural illumination of 1026 lux.
Based on the recommendation of MS 1525, a livingroom should maintain the illuminance in
between 100 lux, and the daylight factor should maintain between 1 – 3%. Both of the values
are exceeded the standard value and severely expose to the sunlight. The result of exceeding
the recommended standard value will cause thermal discomfort and glare to the occupants.
Hence, the perimeter wall with windows which exposed to the sunlight is redesigned with
operable louvered window which allow to manually reduce sunlight due to the north facing
direct sunlight issue and maximize natural lighting when needed.
13
2.2 ARTIFICIAL LIGHTING ANALYSIS + PSALI
2.2.1 Medical Herb Store
Ground Floor Plan
14
Fixture Properties
Type of fixture LED Downlight
Product brand & Code USAI. BLSD5
Wattage 16W
Lumens 1475 lm
Color Rendering Index 80
Color Temperature 3000k
Lumen Method Calculation
Dimension of room (L x W) 7.9m x 9.5m
Floor Area (A) 75.05𝑚2
Height of Ceiling (m) 3m
Lumen (lux) 1475 lm
Height of Luminaire (m) 3m
Height of Work Level (m) 0.8m
Mounting Height (Hm) 2.2m
Reflection Factor Ceiling : 0.7 Wall : 0.5 Floor : 0.2
Standard Illumination
required according to MS1525
750 lux
15
Room Index/ RI (K)
(𝑳 𝒙 𝑾)
(𝑳 + 𝑾) 𝒙 𝒉𝒎)
(7.9𝑚 𝑥 9.5𝑚)
(7.9𝑚 + 9.5𝑚) 𝑥 2.2𝑚)
=2.2 Utilization Factor (UF) 0.6 (based on the utilization factor table)
Maintenance Factor (MF) 0.8 (standard)
Number of lamp required
N =𝐸 𝑥 𝐴
𝐹 𝑥 𝑈𝐹 𝑥 𝑀𝐹
N =750 𝑥 75.05𝑚2
1475 𝑙𝑚 𝑥 0.6 𝑥 0.8
= 18.32 = 18 bulbs
Spacing to height ratio (SHR)
SHR = 1
𝐻𝑚√
𝐴
𝑁
SHR = 1
2.2𝑚√
75.05𝑚2
18
= 0.93
SHR = 𝑆
2.2𝑚 = 0.93
S = 2.046 ≈ 2m
Fitting Layout Fitting Required along 9.5m and 7.9m wall 9.5𝑚
2𝑚 = 4.75
7.9𝑚
2𝑚 = 3.95
≈ 5 rows ≈ 4 rows
Therefore, 5 x 4= 20 bulbs (more than 18 bulbs)
To achieved the recommended MS 1525 Conventional Shop Illumination Level of 750lux x- spacing required for 7.9m wall is 7.9/4 = 1.975m y- spacing required for 9.5m wall is 9.5/5 = 1.9m
16
LIGHT FITTING LAYOUT
Proposed luminaires fitting layout
In conclusion, the medical herb store is arranged with 5 rows of 4 LED downlight with the x-
spacing of 1.975m and y-spacing of 1.9m (one of the row is adding with extra one LED
downlight due to the space designed) to achieve the requirement of 750 lux in the space as
stated in MS 1525. With the sufficient level of illumination, it allow the user to have a good
visual quality while purchasing goods.
17
PSALI (Permanent Supplementary Artificial Lighting Of Interior)
Proposed reflected ceiling plan with switch arrangement
18
Light contour diagram from artificial light analysis
CONCLUSION
Based on the calculation and light contour analysis. There are total 21 light fittings in the
medical herb store which controlled by using two switches. Switch 1 control the first two row
of light fitting (total 8 luminaires) which located at the front part of the space. Switch 2
controlled the following three row of light fittings (total 13 luminaires). Reason being is the
medial herb store will receive a enough daylight distribution of 4.86% during the day from the
glass window faç ade, so the switch 1 which control the light fitting located at the front part of
the space can be switch off during the period of time to save the electric cost and energy
wasted, but the switch 2 need to remain open during day and night to provide sufficient lighting.
19
2.2 ARTIFICIAL LIGHTING ANALYSIS + PSALI
2.2.2 Therapy Room
First Floor Plan
20
Fixture Properties
Type of fixture LED ROUND CEILING MOUNT LIGHT
Product brand & Code Pegasus. FM-4610
Diameter (inch) 10
Input Voltage 120V
Wattage 12.5W
Lumens 964
Color Rendering Index 90
Color Temperature 2700k
Lumen Method Calculation
Dimension of room (L x W) 9.7m x 3.7m
Floor Area (A) 35.89𝑚2
Height of Ceiling (m) 4m
Lumen (lux) 964 lm
Height of Luminaire (m) 4m
Height of Work Level (m) 0.8m
Mounting Height (Hm) 3.2m
Reflection Factor Ceiling : 0.7 Wall : 0.5 Floor : 0.2
Standard Illumination
required according to MS1525
100 lux
21
Room Index/ RI (K)
(𝑳 𝒙 𝑾)
(𝑳 + 𝑾) 𝒙 𝒉𝒎)
(9.7𝑚 𝑥 3.7𝑚)
(9.7𝑚 + 3.7𝑚) 𝑥 3.2𝑚)
=0.84 Utilization Factor (UF) 0.43 (based on the utilization factor table)
Maintenance Factor (MF) 0.8 (standard)
Number of lamp required
N =𝐸 𝑥 𝐴
𝐹 𝑥 𝑈𝐹 𝑥 𝑀𝐹
N =100 𝑥 35.89𝑚2
964 𝑙𝑚 𝑥 0.43 𝑥 0.8
= 10.42 = 10 bulbs
Spacing to height ratio (SHR)
SHR = 1
𝐻𝑚√
𝐴
𝑁
SHR = 1
3.2𝑚√
35.89𝑚2
10
= 0.59
SHR = 𝑆
3.2𝑚 = 0.59
S = 1.888 = 1.89m
Fitting Layout Fitting Required along 9.7m and 3.7m wall 9.7𝑚
1.89𝑚 = 5.13
3.7𝑚
1.89𝑚 = 1.96
≈ 5 rows ≈ 2 rows
Therefore, 5 x 2= 10 bulbs ( Need more than 10 bulbs)
To achieved the recommended MS 1525 Living Room Illumination Level of 100 lux x- spacing required for 9.7m wall is 9.7/5 = 1.94m y- spacing required for 3.7m wall is 3.7/2 = 1.85m
22
LIGHT FITTING LAYOUT
Proposed luminaires fitting layout
In conclusion, the therapy room is arranged with 2 rows of 5 LED ceiling mount light with the
x-spacing of 1.94m and y-spacing of 1.85m to achieve the requirement of 100 lux in the space
as stated in MS 1525. With the sufficient level of illumination, it allow the occupants to have
a comfortable visual quality and thermal comfort in the therapy room.
23
PSALI (Permanent Supplementary Artificial Lighting Of Interior)
Proposed reflected ceiling plan with switch arrangement
Light contour diagram from artificial light analysis
CONCLUSION
Based on the calculation and light contour analysis. There are total 10 light fittings in the
therapy room which controlled by using 6 switches. Switch 1 control the first row of light fitting
(total 5 luminaires) which located at the walkway of the therapy room. Switch 2-6 are control
each luminaire individually. Reason being is the therapy room will receive excessive daylight
distribution of 5.13% during the day from the glass window faç ade, so the switch 1 which
control the light fitting at the front row can be switch off during the period of time to prevent
excessive daylighting. The indivual switch 2-6 are designed based on the space requirement
which allow the occupants to switch on and off based on their need accordingly.