Br 0120008 e

download Br 0120008 e

of 16

Transcript of Br 0120008 e

  • 7/28/2019 Br 0120008 e

    1/16

    Comprehensive circuit protection forcontrol panel applications

    Industrial control circuit breakersMolded-case circuit breakersMiniature circuit breakers

    Supplementary protectorsHydraulic-magnetic circuit breakers

  • 7/28/2019 Br 0120008 e

    2/16

    The complete family of molded-caseand miniature circuit breakers:

    DIN rail, individual and front panel mounted

    UL 489 circuit breakers

    UL 489 Listed per ormance or branch circuit overcurrentprotection and disconnecting means

    Molded-case circuit breakers listed under UL T 489 are required topass stringent short-circuit and switching test requirements. In allcases, interruption must occur successfully without the assistanceof a backup device. In no instance are the contacts permitted toweld. Required electrical spacings and clearances are larger, andregular witnessed follow-up tests are mandatory.

    When applications call for compliance with the National ElectricalCode T (NEC T ) and UL requirements for branch circuit protection anddisconnecting means, choose from the indus trys most extensi veline of UL 489 circuit breaker products and accessories.

    Molded-case circuit breakersUL 489 Listed

    Series G T molded-case circuit breakers are listed for use asbranch circuit overcurrent protection and disconnecting means. 15 to 2500A Up to 200 kAIC at 480V

    Motor protector circuit breakersUL 489 Listed

    Series G motor protector circuit breakers are used to eliminatethe need for a separate overload relay by providing superiorthermal protection as well as serving as a disconnecting meansand supplying motor branch short-circuit protection.

    Motor circuit protectorsUL 489 Recognized

    Series G HMCP magnetic-only motor circuit protectors areUL recognized for use as motor branch short-circuit protectionand disconnecting means and provide a UL listed solution whenused with tested combination starters.

    Miniature circuit breakersUL 489 Listed

    Eatons WMZT DIN rail mountable miniature circuit breakers offer acomplete range from 0.5 to 40A with two levels of short-circuitprotection categorized by C and D curves.

    Export applicationsSeries G molded-case circuit breakers are also world-class rated tomeet IEC 60947-2 standards for export of assembled products thatrequire IEC compliance.

    2 EATON CORPORATION Industrial control circuit breakers

  • 7/28/2019 Br 0120008 e

    3/16

    The complete family of supplementary protectors:DIN rail mounted

    UL 1077 supplementary protectors

    UL 1077 recognized equipment and control circuit protection

    When compliance with the National Electrical Code or UL isrequired, supplementary protectors are approved for use oncircuits where branch circuit protection has already been providedor is not required.

    Eaton exclusively offers selection from two types of DIN railmounted supplementary protectors:

    WMZSsupplementary protector current limiting Dual rated to IEC 60947-2 0.5 to 63A, up to 277/480V B, C and D curves

    SPHMsupplementary protector hydraulic-magnetic In conformance with IEC 60950 and EN-60947 Ambient temperature independent 0.1 to 30A at 480 Vac 0.1 to 50A at 250/277 Vac

    WMZS and SPHM offer unique product technology, providingfeatures to respond to specific equipment and control circuitovercurrent protection requirements. Both products are an attractiveand resettable alternative to control circuit fuses.

    Export applications

    WMZS and SPHM supplementary protectors also meet IECstandards. They have the flexibility to be IEC circuit breakers whenapplications require export of assembled products to areas thatrequire IEC compliance.

    EATON CORPORATION Industrial control circuit breakers

  • 7/28/2019 Br 0120008 e

    4/16

    Applications

    Series G molded-case circuit breakers provide the worldsmost comprehensive product solutions for applications from15 to 2500A at 208 to 690V.

    Branch circuit protection

    Series G molded-case circuit breakers provide for the protectionof cable, and meet or exceed the requirements of the NEC forbranch circuit protection.

    Disconnecting means

    Series G UL 489 molded-case circuit breakers exceed therequirements of the NEC for use as disconnecting meansin branch and motor branch circuits.

    Circuit breaker mounting

    EG-Frame circuit breakers can be DIN rail mounted, or base orfront panel mounted. All other Series G frame breakers can bepanel mounted.

    30 mA ground ault (earth leakage) modules

    Eaton offers a UL Listed Earth Leakage Solution consisting of athree- and four-pole 30 mA ground fault (earth leakage) protectionmodule for EG, JG and LG breakers, while not restricting the use ofother breaker accessories.

    Technology

    Series G employs the worlds most advanced molded-case circuitbreaker technology. Patented reverse loop contact designs providefor current limiting performance and the highest interrupting ratingsin the industrys most compact breaker sizes.

    Series G molded-case circuit breakersUL 489 solution

    Standards

    Series G molded-case circuit breakers are available in versions thatmeet all major electrical standards of the world.

    UL ListedSeries G molded-case circuit breakers meet NEMA T designstandards. They are tested and listed per UL 489, ensuringconformance with the NEC.

    CSA T CertifedSeries G molded-case circuit breakers are certified inaccordance with CSA 22.2 No. 5-02.

    IEC 60947-2 CE MarkEatons world-class Series G molded-case circuit breakersexceed the performance specifications of IEC 60947-2.They carry the CE mark for applications where Europeancompliance is required.

    China Compulsory CertifedThe China Compulsory Certificate mark (CCC Mark) is acompulsory safety mark for many products sold on theChinese market.

    IEC Third-Party CertifcationIn addition to self certification to IEC 60947-2 standard,

    Eatons Series G circuit breakers are witness tested bycertified third-party IEC test labs. Please check EatonsWeb site for a list of available certificates.

    Featuring the EG: The I ndustrysSmallest 125A UL Breaker

    Earth Leakage Module

    4 EATON CORPORATION Industrial control circuit breakers

  • 7/28/2019 Br 0120008 e

    5/16

    Series G breaker rame capabilities

    FrameMaximumAmperes A

    Maximum Voltages Maximum Inter rupting RatingsDimensions in InchesThree Poles

    NEMA,UL, CSA IEC 60947-2 UL 240V UL 480V UL 600V IEC 240V IEC 415V IEC 690V H W D

    E 125 600Y/347 415 200 kA 100 kA 35 kA 200 kA 100 kA N/A 5.50 3.00J 250 600 690 200 kA 200 kA 50 kA 200 kA 200 kA 18 kA 7.00 4.13

    L 600 600 690 200 kA 200 kA 65 kA 200 kA 200 kA 35 kA 10.13 5.48N 1200 600 690 200 kA 150 kA 65 kA 200 kA 100 kA 35 kA 16.00 8.25R 2500 600 690 200 kA 100 kA 65 kA 200 kA 100 kA 35 kA 16.00 15.50A Per UL and CSA listed ratings.

    Control panel and enclosure accessories

    Flex Sha t E handle mechanism

    Flex Shaft handle mechanismsmake installing and operatingenclosure-mounted breakerseasier than ever. Installation andadjustment of this flange-mounted mechanism can beaccomplished in about 10minutes or less. Optional earlybreak auxiliary switch handle isavailable. Use for Type 1, 12, 4and 4X environments.

    High-per ormance handlemechanism

    In addition to its robust designfeatures, the handle mechanismhas stand-off support that allowsfor easy operation with a glovedhand. Use for Type 1, 12, 3R or4X environments. The highperformance external handlecan accept padlocks ormulti-hasp locks.

    Power distribution blocks

    Eaton power distributionblocks are designed for highshort-circuit current ratingapplications when applied withSeries G breakers. Available inthree-pole open style and single-pole enclosed style with avariety of terminal arrangementsand current-carrying capabilityup to 570A.

    Rotary door-mountedhandle mechanism

    Rotary handle mechanismsare available for EG-, JG-, LG-and NG-Frame breakers. Use forType 1 and 12 environments.This rugged through-the-doorrotary handle mechanism isdesigned to accommodate agloved hand.

    Series G molded-case circuit breaker accessoriesUL 489 solution

    Accessories

    Series G breakers are available with a comprehensive range ofaccessories, including shunt trips, undervoltage releases, alarmlockout and auxiliary switches, multi-wire lug kits, control wireterminal kits, etc., that are field installable.

    Plug-in blocks

    Plug-in adapters simplify installation and front removal of circuit

    breakers. Plug-ins are available for rear connection applications onthree- and four-pole circuit breakers. Trip-on drawout interlock kitsare included. Stabs for EG, JG and LG plug-ins rotate 90 for flexibleinstallation. Use terminal shields for IP30 protection.

    Series G accessories

    Flex Shaft

    High Performance Handle withPadlocks

    Termination Options and Accessories

    Power Distribution Blocks

    Universal Rotary

    EATON CORPORATION Industrial control circuit breakers

  • 7/28/2019 Br 0120008 e

    6/16

    Applications

    MPCBs can be used with a contactor to eliminate need for overloadrelay and still create manual motor control based on NEC standards.

    This UL 489 Listed device meets requirements for motor branchprotection by incorporating disconnecting means, branch short-circuit protection and overload protection in applications from50 to 630A and 240 to 690V.

    Features

    MPCBs provide phase unbalance protection, phase loss protection,hot trip/cold trip, high load alarm to warn of potential faults, fieldinstallable and interchangeable accessories, and Class 10, 15, 20,30 protection.

    Accessories

    A comprehensive range of accessories is available: shunt trips,undervoltage releases, alarm lockout and auxiliary switches, andpre-trip alarms.

    Handle mechanisms

    Handle mechanisms facilitate the use of MPCBs in applicationswhere external operation of enclosure mounted units is required.

    Motor circuit protection selection chart

    Feature

    Frame/Rating

    FDMP 1 HFDMP 1 JGMPS JGMPH LGMPS LGMPH

    Interruption rating at 240V 65 kA 100 kA 85 kA 100 kA 85 kA 100 kAInterruption rating at 480V 35 kA 65 kA 35 kA 65 kA 50 kA 65 kAInterruption rating at 600V 18 kA 25 kA 18 kA 25 kA 25 kA 35 kA

    Icu/Ics at 240V 65 kA/33 kA2 100 kA/50 kA2 85 kA/85 kA 100 kA/100 kA 85 kA/85 kA 100 kA/100 kAIcu/Ics at 415V 35 kA/18 kA2 65 kA/33 kA2 40 kA/40 kA 70 kA/53 kA 50 kA/50 kA 70 kA/70 kA100% rated No No Yes Yes Yes YesFLA range (A) 40205 40205 50250 50250 2506303 2506303

    Motor class protection4 5, 10, 15, 20 5, 10, 15, 20 10, 15, 20, 30 10, 15, 20, 30 10, 15, 20, 30 10, 15, 20, 30A FDMP and HFDMP are part of Eatons Series CT family.B IEC ratings available only on FWMP and HFWMP.C 630A is not a UL Listed rating. 600A is the maximum UL or CSA rating for LG breaker.D FDMP and HFDMP have adjustable and fixed motor class protection options. JGMP and LGMP have adjustable motor class protection only.

    Motor protector circuit breakersUL 489 solution

    Standards

    UL ListedAll Eaton MPCBs are UL 489 Listed.

    CSA Certifed Motor protector circuit breakers comply with CSA 22.2,meeting the requirements for motor protectorcircuit breakers.

    CE MarkEatons JG- and LG-Frame MPCBs meet the performancespecifications of IEC 60947-2. They carry the CE markfor applications where European compliance is required.

    6 EATON CORPORATION Industrial control circuit breakers

  • 7/28/2019 Br 0120008 e

    7/16

    Applications

    The NEC permits the use of adjustable instantaneous-onlycircuit breakers (MCPs) in motor branch circuits as part of alisted combination motor controller. The MCP and motor controlleract in concert. The MCP provides the disconnecting means andshort-circuit protection, and the motor controller provides theoverload protection.

    Adjustable instantaneous tripMCPs have no thermal element. The instantaneous tripcharacteristic is adjustable, providing for placement of the tripsetting just above motor inrush. The MCP clears low-level faultsquickly, ignores motor starting currents and improves coordinationwith motor overload relays.

    HMCP

    The HMCP is available in Series G-, EG-, JG- and LG-Frames to suitlarger motor applications requiring higher continuous current andshort-circuit performance.

    Accessories

    A comprehensive range of accessories is available: shunt trips,undervoltage releases and alarm lockout and auxiliary switches,both field and factory installable.

    Handle mechanisms

    Series G handle mechanisms facilitate the use of Series G MCPsin applications where external operation of enclosure mounted unitsis required.

    Series G motor circuit protectors EG-Frame, JG-Frame and LG-FrameUL 489 solution

    Motor circuit protection selection chart

    Frame Size

    Maximum Ratings Dimensions in Inches

    Amperes Volts Width Height Depth

    E 84.5 480 Vac, 600Y/347 Vac 5.50 3.00 2.99J 2500 600 Vac, 250 Vdc 7.00 4.13 3.57

    L 6000 600 Vac, 250 Vdc 10.13 5.48 4.09

    Standards

    UL RecognizedAll Eaton MCPs are UL 489 Recognized and Listed foruse with Eatons IEC or NEMA motor starters ( XT andFreedom Series starters). Additional UL Listingcombinations with numerous other control productshave been obtained.

    CSA CertifedMotor circuit protectors comply with CSA 22.2, meeting therequirements for motor circuit protectors.

    CE MarkEaton HMCPs meet the p erformance specifications ofIEC 60947-2. They carry the CE mark for applicationswhere European compliance is required.

    EATON CORPORATION Industrial control circuit breakers

  • 7/28/2019 Br 0120008 e

    8/16

    WMZT miniature circuit breaker specifcationsDescription Specification

    Design according to UL 489, CSA C22.2 No.5, IEC 60947-2WMZT

    UL/CSAUL/CSAUL/CSAIEC 947-2

    10 kAIC at 277/480V from 0.5 to 32A10 kAIC at 240 Vac for 40A10 kAIC at 48 Vdc per pole15 kAIC at 240/415 Vac

    WMZDUL/CSA 10 kAIC at 125 Vdc per pole (two poles max.)

    10 kAIC at 250 Vdc with two poles connectedin series

    WMZHUL/CSAIEC 947-2

    14 kAIC at 277/480V at listed amperages15 kAIC at 240/415 Vac

    Rated frequency 50/60 HzCharacteristics C, DEndurance 20,000 operationsLine voltage connection Suitable for reverse feed

    Applications

    WMZT miniature circuit breakers are suitable for branch circuitprotection while providing thermal-magnetic overcurrent protectionin applications from 0.5 to 40A.

    Technology

    WMZT employs a current limiting design to provide fast short-circuitinterruption to reduce the let-through energy categorized by C andD curves. The trip-free design cannot be defeated by holding thehandle in the ON position.

    Accessories

    A comprehensive range of accessories is available: trip indicatingcontacts, auxiliary contacts, shunt trips, padlock hasps and bus bars.

    Standards

    UL ListedWMZT miniature circuit breakers meet NEMA designstandards. They are tested and listed per UL 489,ensuring conformance with the NEC.

    CSA Certifed WMZT miniature circuit breakers are certified inaccordance with CSA 22.2 No. 5.

    CE MarkEatons world-class WMZT miniature circuit breakersexceed the performance specifications of IEC 60947-2.They carry the CE mark for applications where Europeancompliance is required.

    RoHS Certifed

    WMZT miniature circuit breakersUL 489 solution

    8 EATON CORPORATION Industrial control circuit breakers

  • 7/28/2019 Br 0120008 e

    9/16

    Technology

    The current limiting design includes a magnetic coil and plungerassembly that acts to quickly trip the breaker during short-circuit conditions. Arc runners channel the arc into the arc chutes,extinguishing the arc before it would otherwise reach current zero,reducing the damaging short-circuit current and the resultantlet-through energy to the connected circuit or equipment.

    WMZS construction

    The WMZS internal construction ensures current limitingperformance and compliance with IEC standards. Visual Contact Position Indicator Window:

    Red = On and Green = Off Three-position handle:

    1 = On, 0 = Off,Center = Tripped

    Quick snap-on clip for secure installation and easy removalfrom DIN rail

    Interphase insulation barriers on multi -pole uni ts comply withUL 1077 electrical clearance requirements Captive posidrive terminal screws offer finger and back-of-hand

    protection (IP2)

    WMZS current limiting supplementary protectorUL 1077 solution

    Applications

    WMZS supplementary protectors are IEC current limiting type circuitbreakers that provide thermal-magnetic protection in applicationsfrom 0.5 to 63A.

    Control circuits

    WMZS current limiting performance and current ratings below 10Aprovide an attractive, resettable alternative to fuses in protectingcontrol circuits: Motor control circuits

    (per NEC 430-71, Part F) Control circuit transformers PLC l/O points Contactor coils Relays

    Standards

    WMZS supplementary protectors exceed the requirements of UL1077 and IEC 60947-2, and carry the following approval marks:

    UL RecognizedFor applications in the United States where NEC and ULrequirements apply, supplementary protectors are intendedfor use where branch circuit protection has been providedor is not required in accordance with NFPA T 70 (NEC).

    CE MarkWMZS protectors carry the CE mark.

    CSA CertifedWMZS supplementary protectors comply with CSA 22.2No. 235, meeting the requirements for supplementary

    protectors.

    RoHS Certifed

    t

    Theoretical Isc

    Theoretical Current and Actual Limited Current

    Isc

    Limited Isc

    Theoretical Isc Peak

    Limited Isc Peak

    Current limiting interruption per ormance

    Current Limiting Technologyin a DIN Rail Mounted CompactIEC Circuit Breaker

    EATON CORPORATION Industrial control circuit breakers

  • 7/28/2019 Br 0120008 e

    10/16

    Accessories

    Lock-o devices

    To lock off any WMZSprotector, use padlockabledevice Catalog NumberWMZPLK.

    Bus bar systems

    Bus bars are available for usewith or without auxiliarycontacts. The bars can be fedfrom line or load side.

    Trip indicating contact

    Auxiliary/trip indicating contactis field installable to the left sideof a WMZS or shunt trip andis selectable between auxiliaryand trip indicating modes. UseCatalog Number WMZSAUXTRIP.

    Technical dataDescription B Curve C Curve D Curve

    ElectricalApprovals UR (UL 1077), CSA (CSA 22.2 No. 235), CEStandards IEC/EN 60947-2

    Short-circuit trip response 3 x 5I

    n 5 x 10I n 10 x 20

    I n

    Supplementary ProtectorsUL/CSACurrent range 663A 0.563A 0.540AMaximum voltage ratingsUL/CSA

    Single-pole

    Two-, three-poleTwo-pole

    277 Vac48 Vdc480Y/277 Vac96 Vdc

    277 Vac48 Vdc480Y/277 Vac96 Vdc

    277 Vac48 Vdc480Y/277 Vac96 Vdc

    Thermal tripping characteristicsSingle-poleMulti-pole

    1.35 xI n @ 40C1.45 xI n @ 40C

    1.35 xI n @ 40C1.45 xI n @ 40C

    1.35 xI n @ 40C1.45 xI n @ 40C

    Short-circuit ratings (at maximum voltage)Single-poleTwo-, three-poleTwo poles in series

    10 kA (5 kA for 40A device)10 kA (5 kA for 40A device)10 kA@ 96 Vdc

    10 kA (5 kA for 40A device)10 kA (5 kA for 40A device)10 kA@ 96 Vdc

    10 kA (5 kA for 40A device)10 kA (5 kA for 40A device)10 kA@ 96 Vdc

    Miniature Circuit BreakerIECCurrent range 663A 0.563A 0.540AMaximum voltage ratingsIEC 60947-2

    Single-pole

    Two-, three-pole

    230 Vac48 Vdc230/400 Vac

    230 Vac48 Vdc230/400 Vac

    230 Vac48 Vdc230/400 Vac

    Maximum voltage ratingsIEC 60898

    Single-pole

    Two-, three-pole

    240 Vac48 Vdc240/415 Vac

    240 Vac48 Vdc240/415 Vac

    240 Vac48 Vdc240/415 Vac

    Thermal tripping characteristicsSingle-poleMulti-pole

    >1 hour@ 1.05 xI n1 hour@ 1.05 xI n1 hour@ 1.05 xI n

  • 7/28/2019 Br 0120008 e

    11/16

    Supplementary protector type SPHM hydraulic-magneticUL 1077 solutionApplications

    SPHM supplementary protectors provide magnetic-only overcurrentprotection for applications from 0.1 to 50A at 250/277V, 0.1 to 30Aat 480 Vac and 0.1 to 63A at 80 Vdc.

    Equipment and control circuit protectionLong, medium and short delay over cur rent curves provide for closeover current protection in applications like: Electronics Motor control circuits (per NEC 430-71, Part F) Control circuit transformers PLC I/O points Contactor coils Relays

    Precise overload protection

    Protection is not affected by ambient temperatures (40 to +85 C).The protector will hold 100% rated current, eliminating nuisancetripping at higher ambients, and will not allow higher than ratedcurrent at lower ambients.

    Immediate reset

    The protector can be reset (closed) immediately after an overcurrenttrip, maximizing continuity to the affected circuit.

    High inrush tolerance

    Half cycle immunity to high inrush is available at 8, 18 or 25 timesthe continuous current rating for high inrush applications likeelectronic power supplies.

    High vibration and shock

    SPHM protectors meet MIL standard for vibration (MIL-STD-202Method 204) and shock (MIL-STD-202, Method 213).

    Standards

    SPHM supplementary protectors exceed the requirements ofUL 1077 and IEC 60950 and carry the following approval marks:

    UL RecognizedFor applications where NEC and UL requirements apply,supplementary protectors are intended for use where branchcircuit protection has been provided or is not required.

    VDE ApprovedFor export applications where IEC requirements apply,SPHM supplementary protectors can be applied as circuitbreakers that exceed the requirements of IEC 60950.

    CE MarkSPHM protectors carry the CE mark in accordance withLow Voltage Directive (LVD) (73/23/EEC).

    RoHS CompliantSPHM protectors submit to limiting the presence ofhazardous chemicals in accordance with the Restrictionon Hazardous Substances (RoHS) directive 2002/95/EC.

    Hydraulic-Magnetic Technologyin a DIN Rail Mounted CompactIEC Circuit Breaker

    Precise and Accurate OvercurrentPerformance Independent fromAmbient Temperature

    High Resistance to Shockand Vibration

    Integrally Mounted Auxiliary Switch(optional)

    Coil

    PolePiece

    Protector Overload

    HydraulicFluid

    Core

    Spring

    Trip Latch

    Protector Tripped

    Hydraulic-magnetic design

    Technology

    The hydraulic-magnetic design includes an iron core that movesagainst a spring in an oil-filled tube. A current-carrying magnetic coilwraps around the tube assembly. During overload conditions, themagnetic flux generated by the coil moves the core through the oilenough to overcome the spring force and trip the breaker. The resultis overcurrent protection that is purely current-sensitive andresistant to changes in ambient temperature.

    EATON CORPORATION Industrial control circuit breakers

  • 7/28/2019 Br 0120008 e

    12/16

    SPHM construction

    The SPHM hydraulic-magneticconstruction ensures preciseovercurrent protectionindependent of ambienttemperature and resistantto shock and vibration. Two-position handle:

    1= On, 0 = Off (tripped) Spring clip for secure

    installation and easy removalfrom DIN rail

    Hydraulic-magnetic tubeprovides precise overcurrentprotection

    SPHM approvals VDE, UL, CSA

    Type Number of PolesRating OperatingVoltage U e

    Rating CurrentI n

    Interrupting CapacityIcu = Ics

    EN 60947-2A CertifiedCENELEC SPHM 1 230V 50/60 Hz 0.163A 1500A

    SPHM 24 400V 50/60 Hz 0.163A 1500A

    SPHM 12 80 Vdc 0.163A 3000A

    UL 1077CSA C22.2 SPHM 3 250 Vac 0.150A 5000AB

    SPHM 14 277 Vac 0.150A 5000AB

    SPHM 3 480 Vac 0.130A 3000AB

    SPHM 14 65 Vdc 0.150A 5000AC

    SPHM 14 80 Vdc 0.150A 5000AB

    SPHM 14 80 Vdc 5163A 5000AD

    A Rating insulation voltage (Ui): 400 Vac.Working shock strength voltage (Uimp): 8 kV, T1/T2 = 1.2/50 s.Working category: A.

    B Series fuse required: In fuse between 15A and 4 times ln of the protector.C Series fuse not required.D Series fuse required. In Fuse maximum 200A.

    Supplementary protector hydraulic-magneticUL 1077 solution

    Integral auxiliary switchavailable

    Overcurrent curves, long,medium or short delay

    time characteristic curves areavailable as short, medium orlong delay

    Integral auxiliary switch(optional selection)oneauxiliary switch (a or b) canbe factory installed per polea separate pole for auxiliaryis not required. Contact Eatonfor price adder

    12 EATON CORPORATION Industrial control circuit breakers

  • 7/28/2019 Br 0120008 e

    13/16

    OutletOutletOutlet

    Wiring System

    MCCB UL 489Branch CircuitProtection

    NEC branch circuit

    OutletOutletOutlet

    Wiring System

    MCCB UL 489Branch CircuitProtection

    2AProtector

    Equipment

    NEC 240-10

    Equipment Protected by:2A UL 1077Supplementary Protector

    Typical supplementary overcurrent protection

    M

    1. DisconnectingMeans(MCCB, MCPor Switch)

    2. Branch Short-Circuit Protection(MCCB, MCPor Fuse)

    3. Motor Controller(Contactor)

    4. Motor OverloadProtection(Overload Relay)

    Wiring System

    NEC motor branch circuits

    Typical group motor circuit Typical motor control circuit

    Control CircuitTransformer

    SPUL 1077

    SPUL 1077

    SPUL 1077

    SPUL 1077

    SPUL 1077

    PLCI/O

    Points

    ContactorCoils

    Relays

    Manual MotorControllerUL 508

    Manual MotorControllerUL 508

    OptionalContactor

    MCCBUL 489

    M M

    NEC 430-53(c)

    A single short-circuit and ground fault protective device ispermitted for a group of motors if each motor controller and eachmotor overload device is listed for group installations witha specified rating of fuse or inverse time circuit breaker, or both.

    NEC Article 210

    The circuit conductorsbetween the final overcurrentdevice protecting the circuitand the outlet(s) where:

    Overcurrent device:Branch circuit protector

    Outlet(s): Point on thewiring system at whichcurrent is taken to supplyutilization equipment

    NEC Article 240-10

    Where supplementary overcurrent protection is used it shallnot be used as a substitute for branch circuit overcurrentdevices or in place of the branch circuit protection in Article 210.

    NEC Article 430

    Requires that each motorbranch circuit contain thefollowing components orfunctions:

    NEC 430-112 NEC 430 Part F

    Applies to the particular conditions of motor control circuits.

    Defnition o Motor Control Circuit

    The circuit of a control apparatus or system that carries theelectric signals directing the performance of the controller,but does not carry the main power current.

    A Guide to Industrial Control Circuit Breaker Selection and the Requirements o the National Electrical Code

    EATON CORPORATION Industrial control circuit breakers

  • 7/28/2019 Br 0120008 e

    14/16

    A Guide to Industrial Control Circuit Breaker Selection and the Requirements o the National Electrical Code

    For Direct Application to NEC,See Color Coordinated Bases

    Standards Product Ratings NEC 210 Branch Circuit Application

    ULStandardsandApprovals

    IECStandardMarks andStandards

    Numberof Poles

    CurrentRangeAmperes(Min.Max.)

    UL VoltageRatings(Volts AC)

    InterruptingRatings atMaximumUL Voltage(kA) A

    BranchCircuitDisconnectingMeans

    BranchShort-CircuitProtection

    Molded-casecircuit breakers(MCCB)UL 489 Listedthermal-magneticprotection

    Series GE-Frame

    UL 489Listed

    IEC 60947-2 14 15160AB 220480 Vac125/250 Vdc

    35 kA Yes Yes

    Series GJ-Frame UL 489Listed IEC 60947-2 24 20250A 220600 Vac125/250 Vdc 50 kA Yes Yes

    Series GL-Frame

    UL 489Listed

    IEC 60947-2 34 100630A 220600 Vac125/250 Vdc

    65 kA Yes Yes

    Series GN-Frame

    UL 489Listed

    IEC 60947-2 24 4001200A 220600 Vac 65 kA Yes Yes

    Series GR-Frame

    UL 489Listed

    IEC 60947-2 34 8002500A 220600 Vac 65 kA Yes Yes

    Motor protectorcircuit breaker(MPCB)UL 489 Listed

    Series G UL 489Listed

    IEC 60947-2 3 250630A 220600 Vac 35 kA Yes Yes

    Motor circuit protector(MCP)UL 489 Recognized

    Series G UL 489Recognized

    3 3600A 600 Vac250 Vdc

    ListedCombinationC

    ListedCombinatio

    Miniature

    circuit breakers (MCB)UL 489 Listedthermal-magneticprotection

    WMZT UL 489

    Listed

    IEC 60947-2 13 0.540A 277/480 Vac 10 kA UL/CSA

    15 kA IEC 60947

    Supplementary protectors(SP)UL 1077 Recognizedsupplementaryovercurrent protection

    WMZSThermal-magneticprotection

    UL 1077Recognized

    IEC 60947-2 13 0.563A 277/480 Vac 10 kA

    SPHMHydraulic-magneticprotection

    UL 1077Recognized

    IEC 60947-2IEC 60950VDE 0660

    14 0.150A0.150A0.130A

    250 Vac277 Vac480 Vac

    5 kAD 5 kAD 3 kAD

    Manual motor controllerUL 508 ListedType F

    MMC UL 508ListedType F

    IEC 60947-4-1 3 0.1665A 220600 Vac Yes Yes

    A Contact Eaton for DC voltage ratings.B 125A maximum rated per UL.C UL Listed for use with Eaton motor starters.D Series fuse required.I n fuse between 15A and 4 timesI n of the protector.

    14 EATON CORPORATION Industrial control circuit breakers

  • 7/28/2019 Br 0120008 e

    15/16

    NEC 420 Motor Branch Circuit Miscellaneous

    chuitload

    ection

    SupplementaryOvercurrentProtection

    Motor BranchCircuitDisconnectingMeans

    Motor BranchShort-CircuitProtection

    MotorBranchOverloadProtection

    Multi-Motor(Group) MotorCircuits

    Motor ControlCircuitOvercurrentProtection

    HandleMechanism

    BreakerDIN RailMount

    Product Notesand UniqueFeatures

    Yes Yes Group circuitdisconnectingmeans andovercurrentprotection

    Yes Flex Shaft,rotary orclose-coupled

    Yeswith adapter

    Mounting hardwareand lugs included foyour convenience

    Other accessoryoptions includealarm switch, auxiliswitch, undervoltagrelease, safety devicshunt trip, terminati

    Breaker can be reseafter a trip conditionunlike fusible switcreducing downtime eliminating the needfor replacement

    Yes Yes Group circuitdisconnectingmeans andovercurrentprotection

    Yes Flex Shaft,rotary orclose-coupled

    Yes Yes Group circuitdisconnectingmeans andovercurrentprotection

    Yes Flex Shaft,rotary orclose-coupled

    Yes Yes Group circuitdisconnectingmeans andovercurrentprotection

    Yes Flex Shaftor rotary

    Yes Yes Group circuitdisconnectingmeans andovercurrentprotection

    Yes Flex Shaftor rotary

    Yes Yes Yes Group circuitdisconnectingmeans andovercurrentprotection

    Yes Flex Shaft,rotary orclose-coupled

    Eliminates need forseparate overload re

    ListedCombinationC

    ListedCombinationC

    Flex Shaft,rotary orclose-coupled

    Listed for use withEaton motor starters

    Yes Yes Yes

    standardmounting

    Ideal for feeder and

    branch circuit protetion applications

    Yes Yes Yesstandardmounting

    Current limitinginterruption ideal foreplacing fuses incontrol circuits

    Yes Yes Yesstandardmounting

    Precise overloadprotection regardlesof ambient temperat

    Yes Yes Yes Yes Yesstandardmounting

    Provides a completemotor protectionsolution by combinidisconnect functionoverload protectionshort-circuit protectand remote operatioin one compact unit

    NEC branch circuit

    Typical supplementaryovercurrent protection

    NEC motor branch circuits

    Typical group motor circuit

    Typical motor control circuit

    Re er to Page 13 or circuit breaker selection drawings

    EATON CORPORATION Industrial control circuit breakers

  • 7/28/2019 Br 0120008 e

    16/16

    Eatons Electrical Sector isa global leader in powerdistribution, power quality,control and automation, andmonitoring products. Whencombined with Eatons full-scaleengineering services, theseproducts provide customer-driven PowerChain E solutionsto serve the power systemneeds of the data center,industrial, institutional, publicsector, utility, commercial,

    residential, IT, mission critical,alternative energy and OEMmarkets worldwide.

    PowerChain solutions helpenterprises achieve sustainableand competitive advantagesthrough proactive managementof the power system as astrategic, integrated assetthroughout its life cycle,resulting in enhanced safety,greater reliability and energyefficiency. For more information,visit www.eaton.com/electrical.

    Eaton CorporationElectrical Sector1111 Superior Ave.Cleveland, OH 44114United States877-ETN-CARE (877-386-2273)Eaton.com

    2010 Eaton CorporationAll Rights ReservedPrinted in USAPublication No. BR01200008E / Z10648December 2010

    PowerChain Management is a registeredtrademark of Eaton Corporation.

    All other trademarks are property of theirrespective owners.