Transmission Surge Arresters

Page 2: BO Lighting Arrester 2

2

3P8SR336 Series Parallel Surge Arrester - Fin Grid installation - Finland 1997

Page 3: BO Lighting Arrester 2

3

Tyco Electronics Energy Divisioncovers a wide range of porcelain andpolymeric transmission surgearresters. The Bowthorpe EMP rangeof arresters have demonstratedreliable performance inenvironments all over the world forover 60 years.

Bowthorpe EMP recognise thatsome Power Utilities require theneed to maintain the conventionalZnO porcelain surge arrester.

A program of continuous designupdate and development on theporcelain arrester has provided arange of surge arresters to meet thedemands of most system voltages.

Design Evaluated and Type Tested atour HV Laboratory in Brighton andalso at external Laboratories.

Bowthorpe EMP were the firstmanufacturer to develop thepolymeric housed arrester forcommercial operation (1983).

Range of HV surge arresters inservice under the severest climaticconditions up to 550kV system.

The range of arresters arecovered by worldwide patents toprotect the company’s extensiveinvestment in R & D.

Surge Arresters

Porcelain HousedSurge Arrester

MBA Class 2, 10kA (11-156kV)MAA Class 2, 10kA (11-220kV)MCA, Class 3, 10kA (11-400kV)MDA, Class 4, 20kA (11-400kV)

Polymeric HousedSurge Arrester

PSRB, Class 2, 10kA (66-220kV)PSRA, Class 3/4, 10/20kA (66-220kV)

Modular Single ColumnPolymeric Surge Arrester

2H & 3H, Class 2, 10kA (66-132kV)

Modular Series ParallelPolymeric Surge Arrester

2P, Class 3, 10kA (11-150kV)3P, Class 3/4, 10/20kA (66-400kV)4P, Class 4, 20kA (132-500kV)5P, Class 5, 20kA (300-500kV)

Page 4: BO Lighting Arrester 2

4

The module core design wasdeveloped in the early 80’s and hasover 15 years service experience,with the housing material changingin the early 90’s.

The modular single columnpolymeric surge arrester design isavailable up to 132kV systems.

The essential feature of the internalpatented construction is thepermanent homogenous resin andglass fibre bond over the completeinsulated service of the ZnOelements. The arrester module hasan inherently high mechanicalstrength and provides a uniformdielectric at the insulated surface ofthe ZnO elements.

Routine tests are carried out to showthat the manufacturing conforms tothe current International standard.

2HSR & 3HSR Modular Single ColumnPolymeric Surge Arresters

Stainless Steel Terminal Assembly

Die Cast Aluminium Sealing End

Aluminium End Block

Thermal Barrier

Silicone Rubber Housing

Heat Sink

ZnO Varistor Element

Finland 132kV system Fin Grid installed 1997

Norway 52kV Hafslund Energei

Page 5: BO Lighting Arrester 2

5

2H & 3H Arrester Type Rating MCOVwith M16 Studs & nuts both ends kV kV

2HSRB30L1E1M0 30 24

2HSRB45L1E1M0 45 36

2HSRB48L1E1M0 48 38

2HSRB60L1E1M0 60 48

2HSRC48L1E1M0 48 38

2HSRC60L1E1M0 60 48

2HSRC72L1E1M0 72 58

2HSRC84L1E1M0 84 67

3HSRC96L1E1M0 96 77

3HSRC108L1E1M0 108 86

3HSRC120L1E1M0 120 96

3HSRC126L1E1M0 126 101

2HSR & 3HSR Modular Single ColumnPolymeric Surge Arresters – Accessories

2H & 3H Arrester Type Rating MCOVwith pedestal base kV kV

2HSRBP30L1E1M5 30 24

2HSRBP45L1E1M5 45 36

2HSRBP48L1E1M5 48 38

2HSRBP60L1E1M5 60 48

2HSRCP48L1E1M5 48 38

2HSRCP60L1E1M5 60 48

2HSRCP72L1E1M5 72 58

2HSRCP84L1E1M5 84 67

3HSRCP96L1E1M5 96 77

3HSRCP108L1E1M5 108 86

3HSRCP120L1E1M5 120 96

3HSRCP126L1E1M5 126 101

Example: 3 HSRC 96 L1 E1 M0

MountingEarth Terminal

Line Terminal

StagesArrester Housing

Voltage

L6Aluminium Stem30mm Ø x 80mm high

L5Line Clamp to suitcables up to 35mm Ø

L2Line Clamp to suitcables up to 16mm Ø

M54 hole Pedestal Base127-140 PCD

M10Single PolyfibreBase Insulator

M3Set of 4 PolyfibreBase Insulatorsused with M5

E5Earth Clamp to suitcables up to 35mm Ø

E2Earth Clamp to suitcables up to 16mm Ø

L1,E1 = M16 Studs with 2 Full Nuts and Washers L1 = M16 Studs with 2 Full Nuts and WashersE1 = 2 x M10 Screws

Page 6: BO Lighting Arrester 2

6

The series parallel surge arresterwas developed in the late 80’s. Wehave over 12 years serviceexperience in over 60 countries.

The series parallel constructioncomprises individual surge arrestermodules rated between 30 and 45kVinterconnected by means of coronafree silicon aluminium alloy plates.

Each surge arrester module iscompletely impervious to theingress of moisture and utilises thehigh mechanical strength propertiesof the ZnO varistor bonded by curedresin impregnated glass fibre.

The external geometry and materialsprovide an arrester that is a virtuallyperfectly graded voltage field suchthat no grading ring is required.

The overall diameter of the seriesparallel arrester has been calculatedto reduce the radial field stress to aminimum, even under adverseenvironmental conditions.

The electrostatic capacitancecoupling between each siliconaluminium interconnection providesan even voltage field across thesurface of the silicon housing.

This arrangement has been provenunder the severest of monitorednatural pollution conditions (NGC).

The very large surface area allowsthis design to maintain thermalequilibrium after lightning orswitching duty.

The seismic performance of 500kVarrester has been proven in twoleading test facilities. BonnevillePower USA performed at PortlandState University and NEL EastKilbride UK. Test performed andpassed to IEEE 693 Annex K and theIEEE Recommended Practice forSeismic Design of Substations.

Routine tests are carried out to showthat the manufacturing conforms tothe current International standard.

Series Parallel Polymeric Surge Arresters

132kV Fin Grid installed in 1996

132kV SCECO Central – Saudi Arabia installed in 1997

500kV Tallas Valley Kyrgystaninstalled in 1997

Page 7: BO Lighting Arrester 2

7

Series Parallel Arrester Type Rating MCOVkV kV

2P1SR30L2E2M2 30 24

2P1SR36L2E2M2 36 29

2P1SR42L2E2M2 42 34

2P2SR60L2E2M2 60 48

2P2SR75L2E2M2 75 60

2P2SR84L2E2M2 84 68

2P3SR96L2E2M2 96 77

2P3SR108L2E2M2 108 87

2P3SR120L2E2M2 120 96

2P4SR132L2E2M2 132 105

2P4SR138L2E2M2 138 110

2P4SR144L2E2M2 144 115

2P4SR150L2E2M2 150 120

2P4SR168L2E2M2 168 134

M2 = 4 Hole Pedestal Base M16 on 280mm PCD

3P3SR96L2E2M7 96 77

3P3SR108L2E2M7 108 87

3P3SR120L2E2M7 120 96

3P4SR132L2E2M7 132 105

3P4SR138L2E2M7 138 110

3P4SR144L2E2M7 144 115

3P4SR150L2E2M7 150 120

3P4SR168L2E2M7 168 134

3P5SR180L2E2M7 180 144

3P5SR192L2E2M7 192 154

3P5SR198L2E2M7 198 158

3P6SR216L2E2M7 216 173

3P6SR228L2E2M7 228 182

3P7SR240L2E2M7 240 192

3P7SR264L2E2M7 264 211

3P7SR288L2E2M7 288 230

3P8SR312L2E2M7 312 250

3P8SR336L2E2M7 336 269

3P9SR360L2E2M7 360 288

4P8SR336L2E2M7 336 269

4P9SR360L2E2M7 360 288

4P10SR360L2E2M7 360 288

4P11SR396L2E2M7 396 237

4P11SR420L2E2M7 420 336

4P11SR444L2E2M7 444 355

4P12SR468L2E2M7 468 374

5P9SR360L2E2M7 360 288

5P10SR360L2E2M7 360 288

5P11SR396L2E2M7 396 237

5P11SR420L2E2M7 420 336

5P11SR444L2E2M7 444 355

5P12SR468L2E2M7 468 374

5P13SR525L2E2M7 525 420

Series Parallel Polymeric Surge Arresters –Accessories

Example: 3P 8SR 336 L2 E2 M7-4

MountingEarth Terminal

Line Terminal

Parallel PathsSeries Stages

Voltage

L2Aluminium Stem35mm Ø x 80mm high

L3Line Clamp to suitcables up to 16mm Ø(2P/3P/4P/5P)

2P/M44 Polyfibre Base Insulators M16 on 280mm PCD

3P/M73 Polyfibre Base Insulators M16 on 332mm PCD

4P/M74 Polyfibre Base Insulators M16 on 412mm PCD

5P/M75 Polyfibre Base Insulators M16 on 590mm PCD

E2/2PClamp to suit cablesup to 16mm Ø

L5Line Clamp to suitcables up to 35mm Ø(2P/3P/4P/5P)

E5Earth Clamp to suitcables up to 35mm Ø(2P/3P/4P/5P)

E2Clamp to suitcable up to 16mm Ø(3P/4P/5P)

3P-Class 4 use suffix -4

Page 8: BO Lighting Arrester 2

8

The PSRA & B surge arresters areavailable for applications for up to220kV systems.

Both designs utilise the samehousing construction, which is aresin and glass fibre pultruded tubeand aluminium flanges.

High cantilever mechanical strengthis achieved on this design with theinternal assembly similar to that ofthe porcelain.

The design has been tested to IECand demonstrated a 63kA pressurerelief performance.

Routine tests are carried out to showthat the manufacturing conforms tothe current International standard.

PSRA & PSRB Single ColumnPolymeric Housed Surge Arresters

Pressure Relief Diaphragm

Compression Spring

Aluminium Spacer

Slicone Rubber Housing

ZnO Varistor Block

Locating Ring

Glass Fibre Pultruded Tube

Aluminium Flange

Dry Air

Korea 154kV Young Chun Substation installed 2001

Page 9: BO Lighting Arrester 2

9

PSRA & PSRB Single ColumnPolymeric Housed Surge Arresters – Accessories

PSRB Arrester Type Rating MCOVkV kV

PSRB160L2E1M4 60 48

PSRB175L2E1M4 75 60

PSRB296L2E1M4 96 77

PSRB2108L2E1M4 108 86

PSRB2120L2E1M4 120 96

PSRB2132L2E1M4 132 106

PSRB2138L2E1M4 138 110

PSRB2144L2E1M4 144 115

PSRB2150L2E1M4 150 120

PSRB2168L2E1M4 168 134

PSRB3198L2E1M4 198 158

PSRB3228L2E1M4 228 182

PSRB Arrester Type Rating MCOVkV kV

PSRA160L2E1M4 60 48

PSRA175L2E1M4 75 60

PSRA296L2E1M4 96 77

PSRA2108L2E1M4 108 86

PSRA2120L2E1M4 120 96

PSRA2132L2E1M4 132 106

PSRA2138L2E1M4 138 110

PSRA2144L2E1M4 144 115

PSRA2150L2E1M4 150 120

PSRA2168L2E1M4 168 134

PSRA3198L2E1M4 198 158

PSRA3228L2E1M4 228 182

Example: PSRB 2138 L2 E1 M5

MountingEarth Terminal

Line Terminal

Arrester HousingVoltage

L2Aluminium Stem35mm Ø x 80mm high

L3/E2Line/Earth Clamp to suitcables up to 16mm Ø

L5/E5Line/Earth Clamp to suitcables up to 35mm Ø

L64 hole Nema Pad

M64 Polyfibre Base Insulatorson 280mm PCD

E1 = 2 x M10 ScrewsM4 = 4 Hole Pedestal Base on 280mm PCD

Page 10: BO Lighting Arrester 2

10

Porcelain surge arresters areavailable for applications up to400kV systems.

Porcelain housing designs havebeen used by us for over 60 years.

From 1936 we produced porcelainsurge arresters to the gappedsilicone carbide pattern and since1980 we have produced arresters tothe gapless ZnO design.

The design consists of a porcelainhousing which conforms to IEC-815with an Aero Dynamic shed profile.

The varistors, spacers and locatingrings are assembled undercompression with pressure reliefdiaphragms at either end, The airvoid is evacuated and replaced withdry air, then sealed.

All arrester designs have beenproved by Type Testing IEC60099-4.

Routine tests are carried out to showthat the manufacturing conforms tothe current International standard.

Porcelain Housed Surge Arresters

Aluminium End Flange

Pressure Relief Diaphragm

Dry Air

Porcelain Housing

ZnO Varistor Block

Locating Ring

Aluminium Spacer

Four Vent Ports

Compression Spring

UK 132kV Seeboard installed in 1975Kuwait 300kV system MEW installed 1982

Page 11: BO Lighting Arrester 2

11

Porcelain Housed Surge Arresters –Accessories

Voltage MCOV MBA Porcelain MAA Porcelain MCA Porcelain MDA PorcelainMax Arrester Type Arrester Type Arrester Type Arrester Type

RatingkV kV L2E1M1 L2E1M2 L2E1M2 L2E1M2

3 2.4 MBA0 MAA0 MCA0 MDA0

6 4.8 MBA0 MAA0 MCA0 MDA0

12 9.6 MBA0 MAA0 MCA0 MDA0

15 12 MBA0 MAA0 MCA0 MDA0

18 14 MBA0 MAA0 MCA0 MDA0

21 17 MBA0 MAA0 MCA0 MDA0

24 19 MBA0 MAA0 MCA0 MDA0

27 22 MBA1 MAA1 MCA1 MDA1

30 24 MBA1 MAA1 MCA1 MDA1

36 29 MBA1 MAA1 MCA1 MDA1

39 31 MBA1 MAA1 MCA1 MDA1

42 34 MBA1 MAA1 MCA1 MDA1

60 48 MBA2 MAA2 MCA2 MDA2

75 60 MBA2 MAA2 MCA2 MDA2

96 77 MBA3 MAA3 MCA3 MDA3

108 86 MBA3 MAA3 MCA3 MDA3

120 96 MBA3 MAA3 MCA3 MDA3

126 101 MBA3 MAA3 MCA3 MDA3

132 106 MBA3 MAA3 MCA3 MDA3

144 115 MBA4 MAA4 MCA4 MDA4

150 120 MBA4 MAA4 MCA4 MDA4

144 115 MBA3.0 MAA3.0 MCA3.0 MDA3.0

150 120 MBA3.1 MAA3.1 MCA3.1 MDA3.1

150 120 MBA3.2 MAA3.2 MCA3.2 MDA3.2

150 120 MBA3.3 MAA3.3 MCA3.3 MDA3.3

150 120 MBA4.0 MAA4.0 MCA4.0 MDA4.0

198 158 – MAA4.1 MCA4.1 MDA4.1

198 158 – MAA4.2 MCA4.2 MDA4.2

198 158 – MAA4.3 – –

198 158 – MAA4.4 – –

240 192 – – MCA4.3 MDA4.3

288 230 – – MCA4.4 MDA4.4

360 288 – – MCA3.3.3 MDA3.3.3

Example: MCA4.2 198 L2 E1 M2

MountingEarth Terminal

Line Terminal

Arrester HousingVoltage

L2Aluminium Line Stem30mm Ø x 80mm high

L3/E2Line/Earth Clamp to suitcables up to 16mm Ø

L5/E5Line/Earth Clamp to suitcables up to 35mm Ø

L64 hole Nema Pad

M3/M4M3 = MBA - 210mm PCDM4 = MAA/MCA/MDA - 280mm PCD4 Polyfibre Base Insulators

E1 = 2 x M10 screwsMBA-M2 = 4 Hole Pedestal Base on 210mm PCD MAA, MCA, MDA = 4 Hole Pedestal Base on 280mm PCDMax Rating MBA = 156kV, MAA = 198kV, MCA & MDA = 360kV

Page 12: BO Lighting Arrester 2

BKK Nett Norway

Transmission Line Surge Arrester.

To provide customer solutions fortheir lines.

Utilising a series parallel arrester toprotect a 45kV system today and ata later stage give protection at120kV, without removing theinstalled arrester.

Surge Arrester Special Applications

12

Surge Arrester with extendedcreepage up to 55mm/kV

The extended creepage modulecould be used on2HSR/3HSR/2P/3P/4P/5P designs.

Page 13: BO Lighting Arrester 2

13

Surge Counters

Surge Counters SC13, SC12 designed to be used with Surge Arresters

Both SC12/SC13 counters can be supplied with an auxiliarycontact rated 0.5 amps 250V for connection to remote

signalling equipment. If required put suffix AC e.g. SC12/AC

Meter : 6 digit cyclometer at least 5 counts/second

Minimum count current : 200 amps 8/20 microsecond wave

Maximum High Current Withstand : 100 kA 4/10 microsecond wave

Nominal Residual Voltage at 100 kA : 5 kV peakwith 4/10 Microsecond Wave

Meter scale : 0 - 30 mA (bilinear scale) Ref SC13

SC13 leakage : 0 - 50 mA (bilinear scale) Ref SC13L

Surge Counter installation

Surge Arrester insulated fromearth with earth connected throughSurge Counter.

Polyfibre Base Insulators

Surge Counter

Earth Cable

Page 14: BO Lighting Arrester 2

14

Committed to Quality

Our HV Laboratory at Brighton - UK

Tyco Electronics at Shannon - Ireland

Page 15: BO Lighting Arrester 2
Page 16: BO Lighting Arrester 2

All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct andreliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance ofany particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for theseproducts is set forth in our standard terms and conditions of sale. ALR, AMP, AXICOM, B&H, Bowthorpe EMP, Critchley, Dorman Smith, Dulmison, Hellstern, La Prairie, Morlynn, Raychem, SIMEL and SUCOFIT are trademarks.

ArgentinaPhone: ++54-11-4733 2277Fax: ++54-11-4733 2267AustraliaPhone: ++61-2-4390 1111Fax: ++61-2-4353 2497BrazilPhone: ++55-11-3611 1862Fax: ++55-11-3611 2457

CanadaPhone: ++1-905-475 6222Fax: ++1-905-470-4453FrancePhone: ++33-3-80583200Fax: ++33-3-80341015MexicoPhone: ++52-5-729 0405Fax: ++52-5-361-8545

ThailandPhone: ++66-2-7394026 - 32Fax: ++66-2-3260563 - 64United States of AmericaPhone: ++1-800-327-6996Fax: ++1-800-527-8350United KingdomPhone: ++44-1772-325400Fax: ++44-1772-726276

Tyco Electronics Bowthorpe EMPStevenson Road, Brighton, East Sussex, England BN2 0DFPhone: +44 (0) 1273 692591, Fax: +44 (0) 1273 601741

http:www.bowthorpe-emp.com

Tyco Electronics Raychem GmbHEnergy DivisionHaidgraben 6, 85521 Ottobrunn/Munich, GermanyPhone: ++49-89-6089-0, Fax: ++49-89-6096345 http://energy.tycoelectronics.com

© T

yco

Ele

ctro

nic

s B

OW

-EP

P 0

001-

08-0

2For further information contact [email protected]