Transmission Surge Arresters
2
3P8SR336 Series Parallel Surge Arrester - Fin Grid installation - Finland 1997
3
Tyco Electronics Energy Divisioncovers a wide range of porcelain andpolymeric transmission surgearresters. The Bowthorpe EMP rangeof arresters have demonstratedreliable performance inenvironments all over the world forover 60 years.
Bowthorpe EMP recognise thatsome Power Utilities require theneed to maintain the conventionalZnO porcelain surge arrester.
A program of continuous designupdate and development on theporcelain arrester has provided arange of surge arresters to meet thedemands of most system voltages.
Design Evaluated and Type Tested atour HV Laboratory in Brighton andalso at external Laboratories.
Bowthorpe EMP were the firstmanufacturer to develop thepolymeric housed arrester forcommercial operation (1983).
Range of HV surge arresters inservice under the severest climaticconditions up to 550kV system.
The range of arresters arecovered by worldwide patents toprotect the company’s extensiveinvestment in R & D.
Surge Arresters
Porcelain HousedSurge Arrester
MBA Class 2, 10kA (11-156kV)MAA Class 2, 10kA (11-220kV)MCA, Class 3, 10kA (11-400kV)MDA, Class 4, 20kA (11-400kV)
Polymeric HousedSurge Arrester
PSRB, Class 2, 10kA (66-220kV)PSRA, Class 3/4, 10/20kA (66-220kV)
Modular Single ColumnPolymeric Surge Arrester
2H & 3H, Class 2, 10kA (66-132kV)
Modular Series ParallelPolymeric Surge Arrester
2P, Class 3, 10kA (11-150kV)3P, Class 3/4, 10/20kA (66-400kV)4P, Class 4, 20kA (132-500kV)5P, Class 5, 20kA (300-500kV)
4
The module core design wasdeveloped in the early 80’s and hasover 15 years service experience,with the housing material changingin the early 90’s.
The modular single columnpolymeric surge arrester design isavailable up to 132kV systems.
The essential feature of the internalpatented construction is thepermanent homogenous resin andglass fibre bond over the completeinsulated service of the ZnOelements. The arrester module hasan inherently high mechanicalstrength and provides a uniformdielectric at the insulated surface ofthe ZnO elements.
Routine tests are carried out to showthat the manufacturing conforms tothe current International standard.
2HSR & 3HSR Modular Single ColumnPolymeric Surge Arresters
Stainless Steel Terminal Assembly
Die Cast Aluminium Sealing End
Aluminium End Block
Thermal Barrier
Silicone Rubber Housing
Heat Sink
ZnO Varistor Element
Finland 132kV system Fin Grid installed 1997
Norway 52kV Hafslund Energei
5
2H & 3H Arrester Type Rating MCOVwith M16 Studs & nuts both ends kV kV
2HSRB30L1E1M0 30 24
2HSRB45L1E1M0 45 36
2HSRB48L1E1M0 48 38
2HSRB60L1E1M0 60 48
2HSRC48L1E1M0 48 38
2HSRC60L1E1M0 60 48
2HSRC72L1E1M0 72 58
2HSRC84L1E1M0 84 67
3HSRC96L1E1M0 96 77
3HSRC108L1E1M0 108 86
3HSRC120L1E1M0 120 96
3HSRC126L1E1M0 126 101
2HSR & 3HSR Modular Single ColumnPolymeric Surge Arresters – Accessories
2H & 3H Arrester Type Rating MCOVwith pedestal base kV kV
2HSRBP30L1E1M5 30 24
2HSRBP45L1E1M5 45 36
2HSRBP48L1E1M5 48 38
2HSRBP60L1E1M5 60 48
2HSRCP48L1E1M5 48 38
2HSRCP60L1E1M5 60 48
2HSRCP72L1E1M5 72 58
2HSRCP84L1E1M5 84 67
3HSRCP96L1E1M5 96 77
3HSRCP108L1E1M5 108 86
3HSRCP120L1E1M5 120 96
3HSRCP126L1E1M5 126 101
Example: 3 HSRC 96 L1 E1 M0
MountingEarth Terminal
Line Terminal
StagesArrester Housing
Voltage
L6Aluminium Stem30mm Ø x 80mm high
L5Line Clamp to suitcables up to 35mm Ø
L2Line Clamp to suitcables up to 16mm Ø
M54 hole Pedestal Base127-140 PCD
M10Single PolyfibreBase Insulator
M3Set of 4 PolyfibreBase Insulatorsused with M5
E5Earth Clamp to suitcables up to 35mm Ø
E2Earth Clamp to suitcables up to 16mm Ø
L1,E1 = M16 Studs with 2 Full Nuts and Washers L1 = M16 Studs with 2 Full Nuts and WashersE1 = 2 x M10 Screws
6
The series parallel surge arresterwas developed in the late 80’s. Wehave over 12 years serviceexperience in over 60 countries.
The series parallel constructioncomprises individual surge arrestermodules rated between 30 and 45kVinterconnected by means of coronafree silicon aluminium alloy plates.
Each surge arrester module iscompletely impervious to theingress of moisture and utilises thehigh mechanical strength propertiesof the ZnO varistor bonded by curedresin impregnated glass fibre.
The external geometry and materialsprovide an arrester that is a virtuallyperfectly graded voltage field suchthat no grading ring is required.
The overall diameter of the seriesparallel arrester has been calculatedto reduce the radial field stress to aminimum, even under adverseenvironmental conditions.
The electrostatic capacitancecoupling between each siliconaluminium interconnection providesan even voltage field across thesurface of the silicon housing.
This arrangement has been provenunder the severest of monitorednatural pollution conditions (NGC).
The very large surface area allowsthis design to maintain thermalequilibrium after lightning orswitching duty.
The seismic performance of 500kVarrester has been proven in twoleading test facilities. BonnevillePower USA performed at PortlandState University and NEL EastKilbride UK. Test performed andpassed to IEEE 693 Annex K and theIEEE Recommended Practice forSeismic Design of Substations.
Routine tests are carried out to showthat the manufacturing conforms tothe current International standard.
Series Parallel Polymeric Surge Arresters
132kV Fin Grid installed in 1996
132kV SCECO Central – Saudi Arabia installed in 1997
500kV Tallas Valley Kyrgystaninstalled in 1997
7
Series Parallel Arrester Type Rating MCOVkV kV
2P1SR30L2E2M2 30 24
2P1SR36L2E2M2 36 29
2P1SR42L2E2M2 42 34
2P2SR60L2E2M2 60 48
2P2SR75L2E2M2 75 60
2P2SR84L2E2M2 84 68
2P3SR96L2E2M2 96 77
2P3SR108L2E2M2 108 87
2P3SR120L2E2M2 120 96
2P4SR132L2E2M2 132 105
2P4SR138L2E2M2 138 110
2P4SR144L2E2M2 144 115
2P4SR150L2E2M2 150 120
2P4SR168L2E2M2 168 134
M2 = 4 Hole Pedestal Base M16 on 280mm PCD
3P3SR96L2E2M7 96 77
3P3SR108L2E2M7 108 87
3P3SR120L2E2M7 120 96
3P4SR132L2E2M7 132 105
3P4SR138L2E2M7 138 110
3P4SR144L2E2M7 144 115
3P4SR150L2E2M7 150 120
3P4SR168L2E2M7 168 134
3P5SR180L2E2M7 180 144
3P5SR192L2E2M7 192 154
3P5SR198L2E2M7 198 158
3P6SR216L2E2M7 216 173
3P6SR228L2E2M7 228 182
3P7SR240L2E2M7 240 192
3P7SR264L2E2M7 264 211
3P7SR288L2E2M7 288 230
3P8SR312L2E2M7 312 250
3P8SR336L2E2M7 336 269
3P9SR360L2E2M7 360 288
4P8SR336L2E2M7 336 269
4P9SR360L2E2M7 360 288
4P10SR360L2E2M7 360 288
4P11SR396L2E2M7 396 237
4P11SR420L2E2M7 420 336
4P11SR444L2E2M7 444 355
4P12SR468L2E2M7 468 374
5P9SR360L2E2M7 360 288
5P10SR360L2E2M7 360 288
5P11SR396L2E2M7 396 237
5P11SR420L2E2M7 420 336
5P11SR444L2E2M7 444 355
5P12SR468L2E2M7 468 374
5P13SR525L2E2M7 525 420
Series Parallel Polymeric Surge Arresters –Accessories
Example: 3P 8SR 336 L2 E2 M7-4
MountingEarth Terminal
Line Terminal
Parallel PathsSeries Stages
Voltage
L2Aluminium Stem35mm Ø x 80mm high
L3Line Clamp to suitcables up to 16mm Ø(2P/3P/4P/5P)
2P/M44 Polyfibre Base Insulators M16 on 280mm PCD
3P/M73 Polyfibre Base Insulators M16 on 332mm PCD
4P/M74 Polyfibre Base Insulators M16 on 412mm PCD
5P/M75 Polyfibre Base Insulators M16 on 590mm PCD
E2/2PClamp to suit cablesup to 16mm Ø
L5Line Clamp to suitcables up to 35mm Ø(2P/3P/4P/5P)
E5Earth Clamp to suitcables up to 35mm Ø(2P/3P/4P/5P)
E2Clamp to suitcable up to 16mm Ø(3P/4P/5P)
3P-Class 4 use suffix -4
8
The PSRA & B surge arresters areavailable for applications for up to220kV systems.
Both designs utilise the samehousing construction, which is aresin and glass fibre pultruded tubeand aluminium flanges.
High cantilever mechanical strengthis achieved on this design with theinternal assembly similar to that ofthe porcelain.
The design has been tested to IECand demonstrated a 63kA pressurerelief performance.
Routine tests are carried out to showthat the manufacturing conforms tothe current International standard.
PSRA & PSRB Single ColumnPolymeric Housed Surge Arresters
Pressure Relief Diaphragm
Compression Spring
Aluminium Spacer
Slicone Rubber Housing
ZnO Varistor Block
Locating Ring
Glass Fibre Pultruded Tube
Aluminium Flange
Dry Air
Korea 154kV Young Chun Substation installed 2001
9
PSRA & PSRB Single ColumnPolymeric Housed Surge Arresters – Accessories
PSRB Arrester Type Rating MCOVkV kV
PSRB160L2E1M4 60 48
PSRB175L2E1M4 75 60
PSRB296L2E1M4 96 77
PSRB2108L2E1M4 108 86
PSRB2120L2E1M4 120 96
PSRB2132L2E1M4 132 106
PSRB2138L2E1M4 138 110
PSRB2144L2E1M4 144 115
PSRB2150L2E1M4 150 120
PSRB2168L2E1M4 168 134
PSRB3198L2E1M4 198 158
PSRB3228L2E1M4 228 182
PSRB Arrester Type Rating MCOVkV kV
PSRA160L2E1M4 60 48
PSRA175L2E1M4 75 60
PSRA296L2E1M4 96 77
PSRA2108L2E1M4 108 86
PSRA2120L2E1M4 120 96
PSRA2132L2E1M4 132 106
PSRA2138L2E1M4 138 110
PSRA2144L2E1M4 144 115
PSRA2150L2E1M4 150 120
PSRA2168L2E1M4 168 134
PSRA3198L2E1M4 198 158
PSRA3228L2E1M4 228 182
Example: PSRB 2138 L2 E1 M5
MountingEarth Terminal
Line Terminal
Arrester HousingVoltage
L2Aluminium Stem35mm Ø x 80mm high
L3/E2Line/Earth Clamp to suitcables up to 16mm Ø
L5/E5Line/Earth Clamp to suitcables up to 35mm Ø
L64 hole Nema Pad
M64 Polyfibre Base Insulatorson 280mm PCD
E1 = 2 x M10 ScrewsM4 = 4 Hole Pedestal Base on 280mm PCD
10
Porcelain surge arresters areavailable for applications up to400kV systems.
Porcelain housing designs havebeen used by us for over 60 years.
From 1936 we produced porcelainsurge arresters to the gappedsilicone carbide pattern and since1980 we have produced arresters tothe gapless ZnO design.
The design consists of a porcelainhousing which conforms to IEC-815with an Aero Dynamic shed profile.
The varistors, spacers and locatingrings are assembled undercompression with pressure reliefdiaphragms at either end, The airvoid is evacuated and replaced withdry air, then sealed.
All arrester designs have beenproved by Type Testing IEC60099-4.
Routine tests are carried out to showthat the manufacturing conforms tothe current International standard.
Porcelain Housed Surge Arresters
Aluminium End Flange
Pressure Relief Diaphragm
Dry Air
Porcelain Housing
ZnO Varistor Block
Locating Ring
Aluminium Spacer
Four Vent Ports
Compression Spring
UK 132kV Seeboard installed in 1975Kuwait 300kV system MEW installed 1982
11
Porcelain Housed Surge Arresters –Accessories
Voltage MCOV MBA Porcelain MAA Porcelain MCA Porcelain MDA PorcelainMax Arrester Type Arrester Type Arrester Type Arrester Type
RatingkV kV L2E1M1 L2E1M2 L2E1M2 L2E1M2
3 2.4 MBA0 MAA0 MCA0 MDA0
6 4.8 MBA0 MAA0 MCA0 MDA0
12 9.6 MBA0 MAA0 MCA0 MDA0
15 12 MBA0 MAA0 MCA0 MDA0
18 14 MBA0 MAA0 MCA0 MDA0
21 17 MBA0 MAA0 MCA0 MDA0
24 19 MBA0 MAA0 MCA0 MDA0
27 22 MBA1 MAA1 MCA1 MDA1
30 24 MBA1 MAA1 MCA1 MDA1
36 29 MBA1 MAA1 MCA1 MDA1
39 31 MBA1 MAA1 MCA1 MDA1
42 34 MBA1 MAA1 MCA1 MDA1
60 48 MBA2 MAA2 MCA2 MDA2
75 60 MBA2 MAA2 MCA2 MDA2
96 77 MBA3 MAA3 MCA3 MDA3
108 86 MBA3 MAA3 MCA3 MDA3
120 96 MBA3 MAA3 MCA3 MDA3
126 101 MBA3 MAA3 MCA3 MDA3
132 106 MBA3 MAA3 MCA3 MDA3
144 115 MBA4 MAA4 MCA4 MDA4
150 120 MBA4 MAA4 MCA4 MDA4
144 115 MBA3.0 MAA3.0 MCA3.0 MDA3.0
150 120 MBA3.1 MAA3.1 MCA3.1 MDA3.1
150 120 MBA3.2 MAA3.2 MCA3.2 MDA3.2
150 120 MBA3.3 MAA3.3 MCA3.3 MDA3.3
150 120 MBA4.0 MAA4.0 MCA4.0 MDA4.0
198 158 – MAA4.1 MCA4.1 MDA4.1
198 158 – MAA4.2 MCA4.2 MDA4.2
198 158 – MAA4.3 – –
198 158 – MAA4.4 – –
240 192 – – MCA4.3 MDA4.3
288 230 – – MCA4.4 MDA4.4
360 288 – – MCA3.3.3 MDA3.3.3
Example: MCA4.2 198 L2 E1 M2
MountingEarth Terminal
Line Terminal
Arrester HousingVoltage
L2Aluminium Line Stem30mm Ø x 80mm high
L3/E2Line/Earth Clamp to suitcables up to 16mm Ø
L5/E5Line/Earth Clamp to suitcables up to 35mm Ø
L64 hole Nema Pad
M3/M4M3 = MBA - 210mm PCDM4 = MAA/MCA/MDA - 280mm PCD4 Polyfibre Base Insulators
E1 = 2 x M10 screwsMBA-M2 = 4 Hole Pedestal Base on 210mm PCD MAA, MCA, MDA = 4 Hole Pedestal Base on 280mm PCDMax Rating MBA = 156kV, MAA = 198kV, MCA & MDA = 360kV
BKK Nett Norway
Transmission Line Surge Arrester.
To provide customer solutions fortheir lines.
Utilising a series parallel arrester toprotect a 45kV system today and ata later stage give protection at120kV, without removing theinstalled arrester.
Surge Arrester Special Applications
12
Surge Arrester with extendedcreepage up to 55mm/kV
The extended creepage modulecould be used on2HSR/3HSR/2P/3P/4P/5P designs.
13
Surge Counters
Surge Counters SC13, SC12 designed to be used with Surge Arresters
Both SC12/SC13 counters can be supplied with an auxiliarycontact rated 0.5 amps 250V for connection to remote
signalling equipment. If required put suffix AC e.g. SC12/AC
Meter : 6 digit cyclometer at least 5 counts/second
Minimum count current : 200 amps 8/20 microsecond wave
Maximum High Current Withstand : 100 kA 4/10 microsecond wave
Nominal Residual Voltage at 100 kA : 5 kV peakwith 4/10 Microsecond Wave
Meter scale : 0 - 30 mA (bilinear scale) Ref SC13
SC13 leakage : 0 - 50 mA (bilinear scale) Ref SC13L
Surge Counter installation
Surge Arrester insulated fromearth with earth connected throughSurge Counter.
Polyfibre Base Insulators
Surge Counter
Earth Cable
14
Committed to Quality
Our HV Laboratory at Brighton - UK
Tyco Electronics at Shannon - Ireland
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct andreliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance ofany particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for theseproducts is set forth in our standard terms and conditions of sale. ALR, AMP, AXICOM, B&H, Bowthorpe EMP, Critchley, Dorman Smith, Dulmison, Hellstern, La Prairie, Morlynn, Raychem, SIMEL and SUCOFIT are trademarks.
ArgentinaPhone: ++54-11-4733 2277Fax: ++54-11-4733 2267AustraliaPhone: ++61-2-4390 1111Fax: ++61-2-4353 2497BrazilPhone: ++55-11-3611 1862Fax: ++55-11-3611 2457
CanadaPhone: ++1-905-475 6222Fax: ++1-905-470-4453FrancePhone: ++33-3-80583200Fax: ++33-3-80341015MexicoPhone: ++52-5-729 0405Fax: ++52-5-361-8545
ThailandPhone: ++66-2-7394026 - 32Fax: ++66-2-3260563 - 64United States of AmericaPhone: ++1-800-327-6996Fax: ++1-800-527-8350United KingdomPhone: ++44-1772-325400Fax: ++44-1772-726276
Tyco Electronics Bowthorpe EMPStevenson Road, Brighton, East Sussex, England BN2 0DFPhone: +44 (0) 1273 692591, Fax: +44 (0) 1273 601741
http:www.bowthorpe-emp.com
Tyco Electronics Raychem GmbHEnergy DivisionHaidgraben 6, 85521 Ottobrunn/Munich, GermanyPhone: ++49-89-6089-0, Fax: ++49-89-6096345 http://energy.tycoelectronics.com
© T
yco
Ele
ctro
nic
s B
OW
-EP
P 0
001-
08-0
2For further information contact [email protected]