BBG BETA BURNER GAS SERIES -...
Transcript of BBG BETA BURNER GAS SERIES -...
BBG BETA BURNER GAS SERIES
NATURAL GAS OPERATION
MODEL NUMBER
SPECIFICATIONS _ _04 _ _06 _ _08 _ _10 _ _12 _114 _118 _124
Max. Input @ 10% Excess Air (MMBtu/hr) 2.2 4.9 8.8 13.6 19.8 27 44.5 87
Max. Air Flow @ 8 osig (scfh) 22,800 50,800 91,300 141,000 205,000 280,000 461,000 903,000
Max. Excess Air (%) 400 260 800 275 320 400 650 600
H I G H F I R E Flame Length @ Max. Input (ft.) 4.5 5.8 7 9.3 10.1 10.8 15.5 23.6
Max. Input @ 10% Excess Air (MMBtu/hr) 0.32 0.69 1.3 2.0 2.9 3.9 6.5 12.7
Air Flow @ 0.17 osig (scfh) 3,320 7,140 13,300 20,600 29,900 40,800 67,200 132,000
L O W F I R E
Max. Excess Air (%) 100 80 240 100 120 150 280 100
NOTES: 1. Capacities based on natural gas with HHV of 1034 Btu/ft3, 0.59 S.G., and a stoichiometric air/gas ratio of 9.74:1 with burner firing into chamber under no pressure. 2. Air and gas flows based on 60°F @ sea level. 3. Static air pressures measured at the burner air inlet pressure tap. 4. Flame lengths measured from the end of converging tile; for a diverging tile (available for _ _06 through _118), add 18% to the flame length. 5. To determine flame lengths at different excess air values, use the following equation: 6. All data based on industry standard air and gas piping practices. 7. Burners can be operated up to a static air pressure of 12 osig; consult Hauck. In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
CAPACITIES
BBG-2
(Metric Capacities on Reverse Side.)
HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA 17042-0090 717-272-3051 8/05 www.hauckburner.com Fax: 717-273-9882
BBG BETA BURNER GAS SERIES
NATURAL GAS OPERATION
MODEL NUMBER
SPECIFICATIONS _ _04 _ _06 _ _08 _ _10 _ _12 _114 _118 _124
Max. Input @ 10% Excess Air (kW) 582 1,300 2,860 3,600 5,240 7,140 11,800 23,000
Max. Air Flow @ 3450 Pa (nm3/hr) 611 1,360 2,450 3,780 5,490 7,500 12,300 24,200
Max. Excess Air (%) 400 260 800 275 320 400 650 600
H I G H
F I R E Flame Length @ Max. Input (m) 1.4 1.8 2.1 2.8 3.1 3.3 4.7 7.2
Max. Input @ 10% Excess Air (kW) 85 183 344 529 767 1,030 1,720 3,360
Air Flow @ 75 Pa (nm3/hr) 89 191 356 552 801 1,090 1,800 3,540
L O W
F I R E
Max. Excess Air (%) 100 80 240 100 120 150 280 100
NOTES: 1. Capacities based on natural gas with LHV of 36.74 MJ/nm3 0.59 S.G., and a stoichiometric air/gas ratio of 9.74:1 with burner firing into chamber under no pressure. 2. Air and gas flows based on 0°C @ sea level. 3. Static air pressures measured at the burner air inlet pressure tap. 4. Flame lengths measured from the end of converging tile; for a diverging tile (available for _ _06 through _118), add 18% to the flame length. 5. To determine flame lengths at different excess air values, use the following equation: 6. All data based on industry standard air and gas piping practices. 7. Burners can be operated up to a static air pressure of 5170 Pa; consult Hauck. In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC CAPACITIES
BBG BETA BURNER – PILOT IGNITION BBG _104
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
DIMENSIONS
(See Reverse Side For Metric Dimensions)
X69
05
(NO
T T
O S
CA
LE)
HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA 17042-0090 717-272-3051 8/05 www.hauckburner.com Fax: 717-273-9882
BBG-3
BBG BETA BURNER – PILOT IGNITION BBG _104
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC DIMENSIONS
X69
05 M
ET
RIC
(N
OT
TO
SC
ALE
)
BBG BETA BURNER – PILOT IGNITION BBG _106 THROUGH _118
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC DIMENSIONS
Y68
71 M
ET
RIC
(N
OT
TO
SC
ALE
)
BBG BETA BURNERS – PILOT IGNITION BBG _124
I n accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC DIMENSIONS
Y68
72 M
ET
RIC
(N
OT
TO
SC
ALE
)
BBG BETA BURNER – DIRECT SPARK IGNITION BBG _204
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC DIMENSIONS
X78
00 M
ET
RIC
(N
OT
TO
SC
ALE
)
BBG BETA BURNER – DIRECT SPARK IGNITION BBG _206 - _212
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC DIMENSIONS
Y78
01 M
ET
RIC
(N
OT
TO
SC
ALE
)
BBG BETA BURNER GAS SERIES
BURNER MODEL BBG_ _04
NATURAL GAS OPERATION
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
SUPPLEMENTAL DATA
STATIC AIR PRESSURE AT BURNER INLET TAP
0.17 OSIG 1 OSIG 2 OSIG 4 OSIG 8 OSIG 12 OSIG
Burner Input @ 10% Excess Air (MMBtu/hr) 0.32 0.78 1.1 1.6 2.2 2.7
Max. Air Flow (Not Firing) (scfh) ---
Max. Air Flow (scfh) 3,320 8,060 11,400 16,100 22,800 27,900
Gas Inlet Pressure ("wc) --- --- --- --- 0.4 ---
Max. Excess Air (%) 100 200 300 400 400 ---
Max. Excess Fuel (%) --- --- --- --- --- ---
Flame Length (ft) 2.7 2.7 2.7 3.2 4.5 5.5
Flame Diameter (ft) 0.9 1.0 1.0 1.0 1.5 1.5
NOTES: 1. Capacities based on natural gas with HHV of 1034 Btu/ft3, 0.59 S.G. and a stoichiometric air/gas ratio of 9.74:1 with burner firing into chamber under no pressure. 2. Air and gas flows based on 60°F @ sea level; capacities for preheated air will differ from those shown. 3. Flame lengths measured from the end of converging tile; diverging tile not available. 4. All data based on industry standard air and gas piping practices.
BBG-4
(See Reverse Side for Metric Data)
HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA 17042-0090 717-272-3051 8/05 www.hauckburner.com Fax: 717-273-9882
BBG BETA BURNER
GAS SERIES
BURNER MODEL BBG_ _04
NATURAL GAS OPERATION
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC DATA
STATIC AIR PRESSURE AT BURNER INLET TAP
75 Pa 430 Pa 860 Pa 1,725 Pa 3,450 Pa 5,170 Pa
Burner Input @ 10% Excess Air (kW) 85 206 291 423 582 714
Max. Air Flow (Not Firing) (nm3/hr) ---
Max. Air Flow (nm3/hr) 89 216 305 431 611 747
Gas Inlet Pressure (Pa) --- --- --- --- -100 ---
Max. Excess Air (%) 100 200 300 400 400 ---
Max. Excess Fuel (%) --- --- --- --- --- ---
Flame Length (m) 0.8 0.8 0.8 1.0 1.4 1.7
Flame Diameter (m) 0.3 0.3 0.3 0.3 0.5 0.5
NOTES: 1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G. and a stoichiometric air/gas ratio of 9.74:1 with burner firing into chamber under no pressure. 2. Air and gas flows based on 0°C @ sea level; capacities for preheated air will differ from those shown. 3. Flame lengths measured from the end of converging tile; diverging tile not available. 4. All data based on industry standard air and gas piping practices.
BBG BETA BURNER GAS SERIES
BURNER MODEL BBG_ _06
NATURAL GAS OPERATION
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC DATA
STATIC AIR PRESSURE AT BURNER INLET TAP 75 Pa 430 Pa 860 Pa 1,725 Pa 3,450 Pa 5,170 Pa
Burner Input @ 10% Excess Air (kW) 183 450 661 926 1,300 1,590
Max. Air Flow (Not Firing) (nm3/hr) ---
Max. Air Flow (nm3/hr) 191 482 680 962 1,360 1,670
Gas Inlet Pressure (Pa) --- --- --- --- 1,240 ---
Max. Excess Air (%) 80 150 240 180 260 ---
Max. Excess Fuel (%) --- --- --- --- --- ---
Flame Length (m) 0.7 0.9 1.1 1.4 1.8 1.8
Flame Diameter (m) 0.5 0.5 0.5 0.5 0.5 0.5
NOTES: 1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G. and a stoichiometric air/gas ratio of 9.74:1 with burner firing into chamber under no pressure. 2. Air and gas flows based on 0°C @ sea level; capacities for preheated air will differ from those shown. 3. Flame lengths measured from the end of converging tile; for diverging tile add 18% to the flame length. 4. All data based on industry standard air and gas piping practices.
BBG BETA BURNER GAS SERIES
BURNER MODEL BBG_ _08
NATURAL GAS OPERATION
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC DATA
STATIC AIR PRESSURE AT BURNER INLET TAP
75 Pa 430 Pa 860 Pa 1,725 Pa 3,450 Pa 5,170 Pa
Burner Input @ 10% Excess Air (kW) 344 820 1,160 1,640 2,330 2,860
Max. Air Flow (Not Firing) (nm3/hr) ---
Max. Air Flow (nm3/hr) 356 865 1,220 1,730 2,450 3,000
Gas Inlet Pressure (Pa) --- --- --- --- 1,690 ---
Max. Excess Air (%) 240 425 425 500 800 ---
Max. Excess Fuel (%) --- --- --- --- --- ---
Flame Length (m) 1.2 1.6 1.9 2.0 2.1 ---
Flame Diameter (m) 0.6 0.8 0.8 0.8 0.9 ---
NOTES: 1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G. and a stoichiometric air/gas ratio of 9.74:1 with burner firing into chamber under no pressure. 2. Air and gas flows based on 0°C @ sea level; capacities for preheated air will differ from those shown. 3. Flame lengths measured from the end of converging tile; for diverging tile add 18% to the flame length. 4. All data based on industry standard air and gas piping practices.
BBG BETA BURNER GAS SERIES
BURNER MODEL BBG_ _10
NATURAL GAS OPERATION
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC DATA
STATIC AIR PRESSURE AT BURNER INLET TAP
75 Pa 430 Pa 860 Pa 1,725 Pa 3,450 Pa 5,170 Pa
Burner Input @ 10% Excess Air (kW) 529 1,270 1,800 2,540 3,600 4,420
Max. Air Flow (Not Firing) (nm3/hr) ---
Max. Air Flow (nm3/hr) 552 1,340 1,890 2,670 3,780 4,630
Gas Inlet Pressure (Pa) --- --- --- --- 2,070 ---
Max. Excess Air (%) 100 250 320 300 275 ---
Max. Excess Fuel (%) --- --- --- --- --- ---
Flame Length (m) 1.5 2.8 2.8 2.8 2.8 ---
Flame Diameter (m) 1.0 1.3 1.4 1.3 1.3 ---
NOTES: 1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G. and a stoichiometric air/gas ratio of 9.74:1 with burner firing into chamber under no pressure. 2. Air and gas flows based on 0°C @ sea level; capacities for preheated air will differ from those shown. 3. Flame lengths measured from the end of converging tile; for diverging tile add 18% to the flame length. 4. All data based on industry standard air and gas piping practices.
BBG BETA BURNER GAS SERIES
BURNER MODEL BBG_ _12
NATURAL GAS OPERATION
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC DATA
STATIC AIR PRESSURE AT BURNER INLET TAP
75 Pa 430 Pa 860 Pa 1,725 Pa 3,450 Pa 5,170 Pa
Burner Input @ 10% Excess Air (kW) 767 1,850 2,620 3,700 5,240 6,400
Max. Air Flow (Not Firing) (nm3/hr) ---
Max. Air Flow (nm3/hr) 801 1,940 2,760 3,880 5,490 6,720
Gas Inlet Pressure (Pa) --- --- --- --- 746 ---
Max. Excess Air (%) 120 250 280 300 320 ---
Max. Excess Fuel (%) --- --- --- --- --- ---
Flame Length (m) 0.9 1.9 2.1 2.3 3.0 ---
Flame Diameter (m) 0.8 0.8 0.8 0.8 1.3 ---
NOTES: 1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G. and a stoichiometric air/gas ratio of 9.74:1 with burner firing into chamber under no pressure. 2. Air and gas flows based on 0°C @ sea level; capacities for preheated air will differ from those shown. 3. Flame lengths measured from the end of converging tile; for diverging tile add 18% to the flame length. 4. All data based on industry standard air and gas piping practices.
BBG BETA BURNER GAS SERIES
BURNER MODEL BBG_114
NATURAL GAS OPERATION
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC DATA
STATIC AIR PRESSURE AT BURNER INLET TAP
75 Pa 430 Pa 860 Pa 1,725 Pa 3,450 Pa 5,170 Pa
Burner Input @ 10% Excess Air (kW) 1,030 2,540 3,570 5,050 7,140 8,750
Max. Air Flow (Not Firing) (nm3/hr) ---
Max. Air Flow (nm3/hr) 1,090 2,650 3,750 5,300 7,500 9,190
Gas Inlet Pressure (Pa) --- --- --- --- 149 ---
Max. Excess Air (%) 150 200 250 285 400 ---
Max. Excess Fuel (%) --- --- --- --- --- ---
Flame Length (m) 1.2 1.6 2.3 2.8 3.4 ---
Flame Diameter (m) 0.5 0.6 0.8 0.8 1.0 ---
NOTES: 1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G. and a stoichiometric air/gas ratio of 9.74:1 with burner firing into chamber under no pressure. 2. Air and gas flows based on 0°C @ sea level; capacities for preheated air will differ from those shown. 3. Flame lengths measured from the end of converging tile; for diverging tile add 18% to the flame length. 4. All data based on industry standard air and gas piping practices.
BBG BETA BURNER GAS SERIES
BURNER MODEL BBG_118
NATURAL GAS OPERATION
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC DATA
STATIC AIR PRESSURE AT BURNER INLET TAP
75 Pa 430 Pa 860 Pa 1,725 Pa 3,450 Pa 5,170 Pa
Burner Input @ 10% Excess Air (kW) 1,720 4,150 5,900 8,330 11,800 14,400
Max. Air Flow (Not Firing) (nm3/hr) ---
Max. Air Flow (nm3/hr) 1,800 4,370 6,190 8,730 12,400 15,100
Gas Inlet Pressure (Pa) --- --- --- --- 1,620 ---
Max. Excess Air (%) 280 280 300 480 650 ---
Max. Excess Fuel (%) --- --- --- --- --- ---
Flame Length (m) 0.9 3.5 4.0 4.1 4.7 ---
Flame Diameter (m) 0.5 0.8 0.8 0.9 1.3 ---
NOTES: 1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G. and a stoichiometric air/gas ratio of 9.74:1 with burner firing into chamber under no pressure. 2. Air and gas flows based on 0°C @ sea level; capacities for preheated air will differ from those shown. 3. Flame lengths measured from the end of converging tile; for diverging tile add 18% to the flame length. 4. All data based on industry standard air and gas piping practices.
BBG BETA BURNER GAS SERIES
BURNER MODEL BBG_124
NATURAL GAS OPERATION
In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
METRIC DATA
STATIC AIR PRESSURE AT BURNER INLET TAP
75 Pa 430 Pa 860 Pa 1,725 Pa 3,450 Pa 5,170 Pa
Burner Input @ 10% Excess Air (kW) 3,360 8,150 11,500 16,300 23,000 28,000
Max. Air Flow (Not Firing) (nm3/hr) ---
Max. Air Flow (nm3/hr) 3,540 8,550 12,100 17,100 24,200 29,700
Gas Inlet Pressure (Pa) --- --- --- --- -249 ---
Max. Excess Air (%) 100 150 250 400 600 ---
Max. Excess Fuel (%) --- --- --- --- --- ---
Flame Length (m) 1.5 2.2 4.4 6.1 7.3 ---
Flame Diameter (m) 0.7 0.9 1.2 1.2 1.5 ---
NOTES: 1. Capacities based on natural gas with LHV of 36.74 MJ/nm3, 0.59 S.G. and a stoichiometric air/gas ratio of 9.74:1 with burner firing into chamber under no pressure. 2. Air and gas flows based on 0°C @ sea level; capacities for preheated air will differ from those shown. 3. Flame lengths measured from the end of converging tile; diverging tile not available. 4. All data based on industry standard air and gas piping practices.
BBG BETA BURNER GAS SERIES In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice. BBG-4.8
SUPPLEMENTAL DATA
Y77
29
(NO
T T
O S
CA
LE)
CR
OS
S-C
ON
NE
CT
ED
RA
TIO
CO
NT
RO
L
GA
S W
/PIL
OT
IGN
ITIO
N
(OVER)
HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA 17042-0090 717-272-3051 8/05 www.hauckburner.com Fax: 717-273-9882
BBG BETA BURNER GAS SERIES In accordance with Hauck’s commitment to Total Quality Improvement, Hauck reserves the right to change the specifications of products without prior notice.
CR
OS
S-C
ON
NE
CT
ED
RA
TIO
CO
NT
RO
L
GA
S W
/DIR
EC
T S
PA
RK
IGN
ITIO
N
Y78
23
(NO
T T
O S
CA
LE)
SUPPLEMENTAL DATA