BARCOL-AIR ENGINEERING PTE LTD
Prepare by: Jerome Low 19 September 2013 Page 1
Woodward Easygen 3500 Generator Control and
LS-5 Circuit Breaker Control and Protection
APPLICATION POSSIBILITY
BARCOL-AIR ENGI
Prepare by: Jerome Low 19 September 2013
This documentation is made for end user to understand the implementation and application
concepts of using the Woodward Easygen 3500 generator controller together with the
Woodward LS-521 circuit breaker control. The part number that we are demonstrating h
Woodward Easygen 3500 Part
Woodward LS-521 Part Number:
For more information about the functionality and features of the implemented modules, please
refer to the product specifications as below
a) Easygen 3500 – Product Specification
b) LS-521 – Product Specification
The application in this case is 6 generators divided into 2 groups and a tie breaker in between
(Please refer to figure 1). Each of the
management and a single controller LS
the group 1 and group 2 generators.
Traditionally management between 2 or more group of generators requires intensive amount
of wiring and PLC for commun
or failure can result in system being unstable especially during critical stages of generator group
synchronization and load sharing.
Figure 1
AIR ENGINEERING PTE LTD
19 September 2013
This documentation is made for end user to understand the implementation and application
concepts of using the Woodward Easygen 3500 generator controller together with the
circuit breaker control. The part number that we are demonstrating h
3500 Part Number: 8440-1934 and
Part Number: 8440-1947
For more information about the functionality and features of the implemented modules, please
refer to the product specifications as below
Product Specification 37522A
Product Specification 37523A
The application in this case is 6 generators divided into 2 groups and a tie breaker in between
(Please refer to figure 1). Each of the generators is installed with an Easygen 3500 f
management and a single controller LS-521 is installed on the tie-breaker for management of
the group 1 and group 2 generators.
Traditionally management between 2 or more group of generators requires intensive amount
of wiring and PLC for communications with the individual generators and these wiring mistake
or failure can result in system being unstable especially during critical stages of generator group
synchronization and load sharing.
NEERING PTE LTD
Page 2
This documentation is made for end user to understand the implementation and application
concepts of using the Woodward Easygen 3500 generator controller together with the
circuit breaker control. The part number that we are demonstrating here is
For more information about the functionality and features of the implemented modules, please
The application in this case is 6 generators divided into 2 groups and a tie breaker in between
Easygen 3500 for genset
breaker for management of
Traditionally management between 2 or more group of generators requires intensive amount
ications with the individual generators and these wiring mistake
or failure can result in system being unstable especially during critical stages of generator group
BARCOL-AIR ENGINEERING PTE LTD
Prepare by: Jerome Low 19 September 2013 Page 3
Now with the combination of Easygen 3500 and LS-521, the application requirements are made
simpler without sacrificing the flexibility of these solutions. The communication between the
LS-521 and individual generators are made possible by a simple 2 wire (CAN-H, CAN-L) CANBus
protocol. This not only allows the respective modules to communicate more effectively but also
reduce the wiring and even replaces the PLC under certain situation.
The proposed solution can be connected with up to 32 Easygen 3500 together with 16 LS-521
for multiple mains incoming and bus bar coupling.
Refer to figure 1, each Easygen 3500 is assigned to control their respective GCB. The controllers
will manage the synchronization and load sharing process within the group without the
involvement of the LS5 if the tie breaker is open.
For coupling of Group 1 and 2 generators, the LS-521 is already pre-assigned with what we call
the segment. Busbar A is assigned segment 1 while Busbar B is 2. Upon the command from PLC
or panel input switches to the LS-521 input for synchronization, LS-521 via CANBus will
command group 1 and 2 for a synchronization electrical parameters matching to close the tie-
breaker. Once the synchronization process is complete, the LS-521 must receive tie-breaker
feedback input to start the load sharing process as a single group (G1,2,3,4,5,6). In this case
now all the units will recognize Busbar A and B as only segment 1.
The philosophy of Woodward Easygen 3500 and LS5 on more complex applications with
multiple mains and busbar coupler is by making use of the segment assignment concept. When
2 or more Busbar /mains of different segment are coupled together, the lower number will be
assigned and recognized by the Woodward controllers for the group load management. A
typical example is illustrated in figure 2 below
BARCOL-AIR ENGI
Prepare by: Jerome Low 19 September 2013
Figure 2
Load dependant start/stop comes as a standard feature for the Easygen 3500. As the name
implies ‘load dependent’ ,modern generator controllers must have the capability to
management starting and stopping sequence
Easygen 3500 achieves this by assigning based on customer
engines size, remaining maintenance hour or the generator number. With these settings pre
programmed into the controller and via Canbus
plant/factory/datacenter load.
AIR ENGINEERING PTE LTD
19 September 2013
Load dependant start/stop comes as a standard feature for the Easygen 3500. As the name
modern generator controllers must have the capability to
management starting and stopping sequence in order to be energy efficient. Woodward
this by assigning based on customer requirement to
engines size, remaining maintenance hour or the generator number. With these settings pre
programmed into the controller and via Canbus, the generators will start/stop depending on
plant/factory/datacenter load.
NEERING PTE LTD
Page 4
Load dependant start/stop comes as a standard feature for the Easygen 3500. As the name
modern generator controllers must have the capability to
energy efficient. Woodward
requirement to generator priority,
engines size, remaining maintenance hour or the generator number. With these settings pre-
, the generators will start/stop depending on