Balancing Variable Flow Systems Taylor
-
Upload
chuctb-pham -
Category
Documents
-
view
219 -
download
1
Transcript of Balancing Variable Flow Systems Taylor
-
8/11/2019 Balancing Variable Flow Systems Taylor
1/27
Balancing Variable FlowHydronic Systems
Steven T. Taylor, PEJeff SteinTaylor EngineeringAlameda, CA
-
8/11/2019 Balancing Variable Flow Systems Taylor
2/27
Agenda
Balancing Issues Why balance? Balancing Options
Piping System Analysis
Results
Controllability Flow during Transients Energy costs First costs
Ranking
Recommendations Resources: Balancing Variable Flow Hydronic Systems,
Steve Taylor and Jeff Stein, October 2002, ASHRAE Journal
-
8/11/2019 Balancing Variable Flow Systems Taylor
3/27
Balancing Issues
Ensure adequate flow available at all coils to meetloads
Less than design flow may be adequate most of the time Ensure differential pressure across control valves is not
so high as to cause erratic control Two-positioning Unstable control at low loads
Cost considerations
First costs (installed costs and start-up costs) Pump energy costs (peak demand and annual) Rebalancing costs (if any) as coils are added to system
-
8/11/2019 Balancing Variable Flow Systems Taylor
4/27
Balancing Options
1. No balancing
Relying on 2-way control valves to automatically providebalancing
2. Manual balance Using ball or butterfly valves and coil pressure drop
Using calibrated balancing valves (CBVs)3. Automatic flow limiting valves (AFLVs)
4. Reverse-return
5. Oversized main piping
6. Undersized branch piping7. Undersized control valves
8. Pressure independent control valves Not studied in our ASHRAE paper
-
8/11/2019 Balancing Variable Flow Systems Taylor
5/27
Piping Systems Analysis
Heating system 540 gpm 400 VAV reheat coils Constant speed pumps
Based on actual building inOakland Cooling system
1,200 gpm
20 Floor-by-floor AHUs Variable speed pumps All valves: 2-way modulating
Analyzed using Pipe-Flo
-
8/11/2019 Balancing Variable Flow Systems Taylor
6/27
HW Piping Floor Plan
-
8/11/2019 Balancing Variable Flow Systems Taylor
7/27
Typical Coil Piping
Options 1, 4, 5, 6, & 7
Option 2
-
8/11/2019 Balancing Variable Flow Systems Taylor
8/27
Typical Coil Piping
Option 3
Option 8
-
8/11/2019 Balancing Variable Flow Systems Taylor
9/27
Option 1: No Balancing
Advantages No balancing labor Coils may be
added/subtracted
without rebalance
Disadvantages Imbalance during
transients or ifsetpoints are
improper Control valves near
pumps can be over-pressurized,
reducingcontrollability
-
8/11/2019 Balancing Variable Flow Systems Taylor
10/27
Option 2: Manual w/CBVs
Advantages Valves can be used for
future diagnosis (flow
can be measured)
Reduced over-pressurization of controlvalves at low flow
Disadvantages Added cost of calibratedbalancing valve
Higher balancing cost Complete rebalance may
be required if coils
added/subtracted Slightly higher pump head
due to balancing valve
Coils may be starved ifvariable speed drives areused without DP reset
Slightly higher pumpenergy depending on flowvariations and pumpcontrols
-
8/11/2019 Balancing Variable Flow Systems Taylor
11/27
Starved Loads with CBVs and Fixed DP
Setpoint: Design Condition
VFDLoad
Load
DP
100 GPM
5 PSI D
100 GPM
5 PSI D
5 PSI D
28 PSI D, Cv=19
5 PSI D
2 PSI D
12 PSI D38 PSI D45 PSI D
PUMP CLOSE LOAD REMOTE LOAD
20
60
50
40
30
10
0
70
PRESSURE
PSIG
-
8/11/2019 Balancing Variable Flow Systems Taylor
12/27
Starved Loads with CBVs and Fixed DP
Setpoint: No Remote Flow Condition
56 GPM
1. 6 PSI D
0 GPM
0 PSI D
1. 6 PSI D
8. 8 PSI D
12 PSI D
0 PSI D
VFDLoad
Load
DP
12 PSI D12 PSI D19 PSI D
PUMP CLOSE LOAD REMOTE LOAD
20
60
50
40
30
10
0
70
PRESSURE
PSIG
-
8/11/2019 Balancing Variable Flow Systems Taylor
13/27
Option 3: Automatic Flow Limiting
Valves
Advantages No balancing labor Coils may be
added/subtracted withoutrebalance
Disadvantages Added cost of strainer andflow limiting valve
Cost of labor to clean strainerat start-up
Higher pump head andenergy due to strainer andflow limiting valve
Valves have custom flowrates and must be installed incorrect location
Valves can clog or springscan fail over time
Control valves near pumpscan be over-pressurized,reducing controllability
-
8/11/2019 Balancing Variable Flow Systems Taylor
14/27
Option 4: Reverse-return
-
8/11/2019 Balancing Variable Flow Systems Taylor
15/27
Reverse Return Configurations
C/C
C/C
C/C
C/C
Reverse return riser
(elevation)
Reverse return on f loor
(plan)
H/C
H/C
H
/C
H
/C
H/C
H/C
-
8/11/2019 Balancing Variable Flow Systems Taylor
16/27
Option 4: Reverse-return
Advantages No balancing labor Coils may be
added/subtracted withoutrebalance
No significant over-pressurization of controlvalves close to pumps.
Usually lower pump headdue to reverse-return piping
having lower pressure dropthan mains (due to largerpipe)
Disadvantages Added cost of reverse-returnpiping
Not always practicaldepending on physical layout
of system
-
8/11/2019 Balancing Variable Flow Systems Taylor
17/27
Option 5: Oversized Main Piping
Standard main design
C/C
C/C
C/C
C/C
Oversized main riser
6
6
6
6
C/C
C/C
C/C
C/C
2
6
2
6
3 3
4 4
-
8/11/2019 Balancing Variable Flow Systems Taylor
18/27
Option 5: Oversized Main Piping
Advantages No balancing labor Coils may be
added/subtracted withoutrebalance
Reduced over-pressurization of controlvalves close to pumps
Lowest pumphead/energy due to
oversized piping, nobalance valves
Increased flexibility to addloads due to oversizedpiping
Disadvantages Added cost of larger piping
-
8/11/2019 Balancing Variable Flow Systems Taylor
19/27
Option 6: Undersized Branch Piping
Advantages No balancing labor Reduced cost of smaller
piping
Coils may beadded/subtracted withoutrebalance
Reduced over-pressurizationof control valves close topumps where piping hasbeen undersized
Disadvantages Limited effectiveness andapplicability due to limitedavailable pipe sizes
High design and analysis costto determine correct pipe
sizing Reduced flexibility to add
coils where piping has beenundersized
Coils may be starved ifvariable speed drives areused without DP reset
Slightly higher pump energydepending on flow variationsand pump controls
-
8/11/2019 Balancing Variable Flow Systems Taylor
20/27
Option 7: Undersized Control Valves
Advantages No balancing labor Reduced cost of smaller
control valves
Coils may beadded/subtracted without
rebalance Reduced over-pressurization
of control valves close topumps where control valveshave been undersized
Improved valve authoritywhich could improvecontrollability where controlvalves have beenundersized
Disadvantages Limited effectiveness andapplicability due to limitedavailable control valve sizes(Cv)
High design and analysis costto determine correct controlvalve sizing
Coils may be starved ifvariable speed drives arewithout DP reset
Slightly higher pump energydepending on flow variationsand pump controls
-
8/11/2019 Balancing Variable Flow Systems Taylor
21/27
Option 8: Pressure Independent Control
Valves
Advantages
No balancing labor Coils may beadded/subtracted withoutrebalance
No over-pressurization ofcontrol valves close topumps
Easy valve selection flowonly not Cv
Perfect valve authority willimprove controllability
Less actuator travel andstart/stop may improve
actuator longevity
Disadvantages
Added cost of strainer andpressure independent controlvalve
Cost of labor to clean strainerat start-up
Higher pump head andenergy due to strainer andpressure independent controlvalve
Valves have custom flowrates and must be installed incorrect location
Valves can clog or springscan fail over time
-
8/11/2019 Balancing Variable Flow Systems Taylor
22/27
PICVs May Improve T?
NBCIP Test Lab (as reported
by manufacturer)
-
8/11/2019 Balancing Variable Flow Systems Taylor
23/27
Controllability & Transients
Percent of design flow
(percent of design coil sensible capacity)
with all control valves 100% open
Maximum
pressure drop
of control valverequired for
design flow,
feet
Maximum flow
through closest coil
Minimum flow
through most
remote coil
Balancing Method
CHW HW CHW HW CHW HW
1 No balancing 20.5 44.4 143%
(106%)212%
(119%)
73%
(89%)75%
(96%)
2 Manual balance
using calibratedbalancing valves
0 0 100%
(100%)100%
(100%)
100%
(100%)
100%
(100%)
3 Automatic flowlimiting valves
20.5* 44.4* 100%(100%)
100%(100%)
100%(100%)
100%(100%)
4 Reverse-return 1.2 10.4 103%
(100%)
150%
(109%)
99%
(100%)
85%
(97%)5 Oversized main
piping7.0 20.9 122%
(103%)173%
(112%)94%
(99%)82%
(97%)
6 Undersized branchpiping
19.5 NA 142%(106%)
NA 73%(100%)
NA
7 Undersized controlvalves
8.0 NA 120%(103%)
NA 86%(89%)
NA
-
8/11/2019 Balancing Variable Flow Systems Taylor
24/27
-
8/11/2019 Balancing Variable Flow Systems Taylor
25/27
Ranks
Balancing Method
Controllability
(all conditions)
Pump Energy
CostsFirst Costs
1 No balancing 7 3 3
2 Manual balance using calibrated
balancing valves4 6 6
3 Automatic flow limiting valves 7 7 7
4 Reverse-return 2 2 5
5 Oversized main piping 3 1 4
6 Undersized branch piping 6 4 2
7 Undersized control valves 5 4 18 Pressure independent control
valve1 8 87
-
8/11/2019 Balancing Variable Flow Systems Taylor
26/27
Conclusions & Recommendations
for Variable Flow Hydronic Systems
Automatic flow-limiting valves and calibrated balancing valves are
not recommended on any variable flow system Few advantages and high first costs and energy costs Reverse-return and oversized mains may have reasonable pump
energy savings payback on 24/7 chilled water systems
Undersizing piping and valves near pumps improves balance and
costs are reduced, but significant added engineering time required
Pressure independent valves should be considered on very large
systems for coils near pumps
Cost is high but going down now with competition
When costs are competitive, this may be best choice for all jobs For other than very large distribution systems, option 1 (no
balancing) appears to be the best option
Low first costs with minimal or insignificant operational problems
-
8/11/2019 Balancing Variable Flow Systems Taylor
27/27
Questions