Balancing Variable Flow Systems Taylor

download Balancing Variable Flow Systems Taylor

of 27

Transcript of Balancing Variable Flow Systems Taylor

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    1/27

    Balancing Variable FlowHydronic Systems

    Steven T. Taylor, PEJeff SteinTaylor EngineeringAlameda, CA

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    2/27

    Agenda

    Balancing Issues Why balance? Balancing Options

    Piping System Analysis

    Results

    Controllability Flow during Transients Energy costs First costs

    Ranking

    Recommendations Resources: Balancing Variable Flow Hydronic Systems,

    Steve Taylor and Jeff Stein, October 2002, ASHRAE Journal

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    3/27

    Balancing Issues

    Ensure adequate flow available at all coils to meetloads

    Less than design flow may be adequate most of the time Ensure differential pressure across control valves is not

    so high as to cause erratic control Two-positioning Unstable control at low loads

    Cost considerations

    First costs (installed costs and start-up costs) Pump energy costs (peak demand and annual) Rebalancing costs (if any) as coils are added to system

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    4/27

    Balancing Options

    1. No balancing

    Relying on 2-way control valves to automatically providebalancing

    2. Manual balance Using ball or butterfly valves and coil pressure drop

    Using calibrated balancing valves (CBVs)3. Automatic flow limiting valves (AFLVs)

    4. Reverse-return

    5. Oversized main piping

    6. Undersized branch piping7. Undersized control valves

    8. Pressure independent control valves Not studied in our ASHRAE paper

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    5/27

    Piping Systems Analysis

    Heating system 540 gpm 400 VAV reheat coils Constant speed pumps

    Based on actual building inOakland Cooling system

    1,200 gpm

    20 Floor-by-floor AHUs Variable speed pumps All valves: 2-way modulating

    Analyzed using Pipe-Flo

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    6/27

    HW Piping Floor Plan

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    7/27

    Typical Coil Piping

    Options 1, 4, 5, 6, & 7

    Option 2

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    8/27

    Typical Coil Piping

    Option 3

    Option 8

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    9/27

    Option 1: No Balancing

    Advantages No balancing labor Coils may be

    added/subtracted

    without rebalance

    Disadvantages Imbalance during

    transients or ifsetpoints are

    improper Control valves near

    pumps can be over-pressurized,

    reducingcontrollability

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    10/27

    Option 2: Manual w/CBVs

    Advantages Valves can be used for

    future diagnosis (flow

    can be measured)

    Reduced over-pressurization of controlvalves at low flow

    Disadvantages Added cost of calibratedbalancing valve

    Higher balancing cost Complete rebalance may

    be required if coils

    added/subtracted Slightly higher pump head

    due to balancing valve

    Coils may be starved ifvariable speed drives areused without DP reset

    Slightly higher pumpenergy depending on flowvariations and pumpcontrols

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    11/27

    Starved Loads with CBVs and Fixed DP

    Setpoint: Design Condition

    VFDLoad

    Load

    DP

    100 GPM

    5 PSI D

    100 GPM

    5 PSI D

    5 PSI D

    28 PSI D, Cv=19

    5 PSI D

    2 PSI D

    12 PSI D38 PSI D45 PSI D

    PUMP CLOSE LOAD REMOTE LOAD

    20

    60

    50

    40

    30

    10

    0

    70

    PRESSURE

    PSIG

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    12/27

    Starved Loads with CBVs and Fixed DP

    Setpoint: No Remote Flow Condition

    56 GPM

    1. 6 PSI D

    0 GPM

    0 PSI D

    1. 6 PSI D

    8. 8 PSI D

    12 PSI D

    0 PSI D

    VFDLoad

    Load

    DP

    12 PSI D12 PSI D19 PSI D

    PUMP CLOSE LOAD REMOTE LOAD

    20

    60

    50

    40

    30

    10

    0

    70

    PRESSURE

    PSIG

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    13/27

    Option 3: Automatic Flow Limiting

    Valves

    Advantages No balancing labor Coils may be

    added/subtracted withoutrebalance

    Disadvantages Added cost of strainer andflow limiting valve

    Cost of labor to clean strainerat start-up

    Higher pump head andenergy due to strainer andflow limiting valve

    Valves have custom flowrates and must be installed incorrect location

    Valves can clog or springscan fail over time

    Control valves near pumpscan be over-pressurized,reducing controllability

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    14/27

    Option 4: Reverse-return

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    15/27

    Reverse Return Configurations

    C/C

    C/C

    C/C

    C/C

    Reverse return riser

    (elevation)

    Reverse return on f loor

    (plan)

    H/C

    H/C

    H

    /C

    H

    /C

    H/C

    H/C

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    16/27

    Option 4: Reverse-return

    Advantages No balancing labor Coils may be

    added/subtracted withoutrebalance

    No significant over-pressurization of controlvalves close to pumps.

    Usually lower pump headdue to reverse-return piping

    having lower pressure dropthan mains (due to largerpipe)

    Disadvantages Added cost of reverse-returnpiping

    Not always practicaldepending on physical layout

    of system

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    17/27

    Option 5: Oversized Main Piping

    Standard main design

    C/C

    C/C

    C/C

    C/C

    Oversized main riser

    6

    6

    6

    6

    C/C

    C/C

    C/C

    C/C

    2

    6

    2

    6

    3 3

    4 4

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    18/27

    Option 5: Oversized Main Piping

    Advantages No balancing labor Coils may be

    added/subtracted withoutrebalance

    Reduced over-pressurization of controlvalves close to pumps

    Lowest pumphead/energy due to

    oversized piping, nobalance valves

    Increased flexibility to addloads due to oversizedpiping

    Disadvantages Added cost of larger piping

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    19/27

    Option 6: Undersized Branch Piping

    Advantages No balancing labor Reduced cost of smaller

    piping

    Coils may beadded/subtracted withoutrebalance

    Reduced over-pressurizationof control valves close topumps where piping hasbeen undersized

    Disadvantages Limited effectiveness andapplicability due to limitedavailable pipe sizes

    High design and analysis costto determine correct pipe

    sizing Reduced flexibility to add

    coils where piping has beenundersized

    Coils may be starved ifvariable speed drives areused without DP reset

    Slightly higher pump energydepending on flow variationsand pump controls

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    20/27

    Option 7: Undersized Control Valves

    Advantages No balancing labor Reduced cost of smaller

    control valves

    Coils may beadded/subtracted without

    rebalance Reduced over-pressurization

    of control valves close topumps where control valveshave been undersized

    Improved valve authoritywhich could improvecontrollability where controlvalves have beenundersized

    Disadvantages Limited effectiveness andapplicability due to limitedavailable control valve sizes(Cv)

    High design and analysis costto determine correct controlvalve sizing

    Coils may be starved ifvariable speed drives arewithout DP reset

    Slightly higher pump energydepending on flow variationsand pump controls

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    21/27

    Option 8: Pressure Independent Control

    Valves

    Advantages

    No balancing labor Coils may beadded/subtracted withoutrebalance

    No over-pressurization ofcontrol valves close topumps

    Easy valve selection flowonly not Cv

    Perfect valve authority willimprove controllability

    Less actuator travel andstart/stop may improve

    actuator longevity

    Disadvantages

    Added cost of strainer andpressure independent controlvalve

    Cost of labor to clean strainerat start-up

    Higher pump head andenergy due to strainer andpressure independent controlvalve

    Valves have custom flowrates and must be installed incorrect location

    Valves can clog or springscan fail over time

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    22/27

    PICVs May Improve T?

    NBCIP Test Lab (as reported

    by manufacturer)

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    23/27

    Controllability & Transients

    Percent of design flow

    (percent of design coil sensible capacity)

    with all control valves 100% open

    Maximum

    pressure drop

    of control valverequired for

    design flow,

    feet

    Maximum flow

    through closest coil

    Minimum flow

    through most

    remote coil

    Balancing Method

    CHW HW CHW HW CHW HW

    1 No balancing 20.5 44.4 143%

    (106%)212%

    (119%)

    73%

    (89%)75%

    (96%)

    2 Manual balance

    using calibratedbalancing valves

    0 0 100%

    (100%)100%

    (100%)

    100%

    (100%)

    100%

    (100%)

    3 Automatic flowlimiting valves

    20.5* 44.4* 100%(100%)

    100%(100%)

    100%(100%)

    100%(100%)

    4 Reverse-return 1.2 10.4 103%

    (100%)

    150%

    (109%)

    99%

    (100%)

    85%

    (97%)5 Oversized main

    piping7.0 20.9 122%

    (103%)173%

    (112%)94%

    (99%)82%

    (97%)

    6 Undersized branchpiping

    19.5 NA 142%(106%)

    NA 73%(100%)

    NA

    7 Undersized controlvalves

    8.0 NA 120%(103%)

    NA 86%(89%)

    NA

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    24/27

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    25/27

    Ranks

    Balancing Method

    Controllability

    (all conditions)

    Pump Energy

    CostsFirst Costs

    1 No balancing 7 3 3

    2 Manual balance using calibrated

    balancing valves4 6 6

    3 Automatic flow limiting valves 7 7 7

    4 Reverse-return 2 2 5

    5 Oversized main piping 3 1 4

    6 Undersized branch piping 6 4 2

    7 Undersized control valves 5 4 18 Pressure independent control

    valve1 8 87

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    26/27

    Conclusions & Recommendations

    for Variable Flow Hydronic Systems

    Automatic flow-limiting valves and calibrated balancing valves are

    not recommended on any variable flow system Few advantages and high first costs and energy costs Reverse-return and oversized mains may have reasonable pump

    energy savings payback on 24/7 chilled water systems

    Undersizing piping and valves near pumps improves balance and

    costs are reduced, but significant added engineering time required

    Pressure independent valves should be considered on very large

    systems for coils near pumps

    Cost is high but going down now with competition

    When costs are competitive, this may be best choice for all jobs For other than very large distribution systems, option 1 (no

    balancing) appears to be the best option

    Low first costs with minimal or insignificant operational problems

  • 8/11/2019 Balancing Variable Flow Systems Taylor

    27/27

    Questions