Auto Control Loops of Large-sized Thermal Plants
Janmejay MahapatraHead (Instrumentation)
Avantha Power Infrastructure LTD.6th Nov 2011 – PMI, Noida
![Page 2: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/2.jpg)
Structure of the Controller
![Page 3: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/3.jpg)
![Page 4: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/4.jpg)
![Page 5: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/5.jpg)
Is my plant performing as per Design?
An eye on the various measured values of different processes:
Temperature Pressure Flow Level Water & Steam Parameters (e.g.
conductivity, pH, silica etc.)
![Page 6: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/6.jpg)
Is my plant performing as per Design?
And, hands on the various means to regulate the different processes:
Valves Dampers Speed Regulators Stroke Controllers
![Page 7: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/7.jpg)
The Onerous task of the plant operator
The huge number of processes involved Electrical Load has to be matched with the
fluctuating demand Creeping of inefficiencies as the process
deviates from the design Safety of the equipment at risk as the
process drifts beyond allowable limits Start-up & Shut down activities Two shift operation
![Page 8: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/8.jpg)
The Basic Control Schemes
On-off Control Proportional Control Proportional-Integral ( P-I ) Control Proportional – Derivative ( P-D ) Control Proportional-Integral-Derivative ( PID ) Control Ratio Control Spilt Range Control Cascade Control Feed-forward Control Adaptive Control
![Page 9: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/9.jpg)
The Basic Control Schemes : Responses
![Page 10: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/10.jpg)
Let’s recognise these:
Roughly 75% of process control loops cause more variability running in the automatic mode than they do in the manual mode.
A third of them oscillate as a result of nonlinearities such as valve dead band.
Another third oscillate because of poor controller tuning.
The remaining loops oscillate because of deficiencies in the control strategy.
![Page 11: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/11.jpg)
Some simple rules of Tuning the Auto Control Loops
Increase the gain to achieve tight control and to
speed up the set point response.
Decrease the gain to provide a smoother, slower,
and more stable response.
Whereas insufficient gain slows down the initial
approach, inadequate reset action slows down the
final approach to set point.
If the reset action is too large (reset time too
small), there is excessive overshoot.
![Page 12: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/12.jpg)
Some simple rules of Tuning the Auto Control Loops
If there is excessive overshoot and oscillation,
decrease the reset action (increase reset time).
For level loops with low controller gains (< 5.0),
reset action must be greatly restricted (reset
time increased to 50 or more minutes) to help
mitigate nearly sustained oscillations.
Rate is primarily used in temperature loops that
have narrow span transmitters and slow scan
times.
![Page 13: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/13.jpg)
Some simple rules of Tuning the Auto Control Loops
There is noise in every process variable.
If the noise is greater than the measurement
resolution limit, the loop sees it.
If it causes an output change greater than the
final element or control valve resolution limit,
loop variability will be worse in auto than in
manual, particularly if there is any rate action.
![Page 14: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/14.jpg)
Tuning the Auto Control Loops
Test new tuning settings by changing the set
point in both directions.
Don’t leave these new settings over night
until you are sure they are right.
Before entering new settings, ask the
operator for permission to tune the loop.
Ask the operator what the maximum
allowable size of variation.
Put the controller in manual before tuning.
![Page 15: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/15.jpg)
Feed Forward Control
Useful for processes with significant dead times. Controlled condition is affecting processes
other than that is being controlled. Controller is required to respond promptly but
the response of the measured value is slow. Usually it is the derivative of the external
measurement. The “Anticipatory” action is added to the output
of the controller. Normal feedback control after the passing off of
the transient.
![Page 16: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/16.jpg)
Cascade Control
Cascade control is a type of control in which a secondary (slave or inner) loop is added.
Secondary Loop gets a set point from a primary (master or outer) loop.
The secondary loop response is normally faster than (about five times) the primary loop response.
The secondary loop can correct for upsets it can measure before they affect the primary loop.
![Page 17: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/17.jpg)
BHEL - The Base Documents
Recommended Scheme of Auto Controls –
Trichy Document
APRDS Control Scheme – Trichy Document
Analog Control Schemes – PEM Document
HPBP Control Scheme – PEM Document
CMC Scheme – PEM Document
![Page 18: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/18.jpg)
The Control Loops
Heater Level Controls LPH - 2 / 3 level controlHPH - 5A / 6A / 5B / 6B level control
Hotwell Level Control GSC minimum flow control Gland seal Water Header Pressure control Controls of Deaerator
Pressure control Level control
Dosing ControlAmmonia, Hydrazine, Phosphate
![Page 19: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/19.jpg)
The Control Loops
Furnace Press Control Secondary Air Flow Control Drum level control Fuel Flow Control PA Header press Control Mill Air Flow Control Mill Air Temperature Control SH Steam Temp Control RH Steam Temp Control Burner Tilt Control AH Cold End Temp Control
![Page 20: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/20.jpg)
The Control Loops
CBD Tank Level Control Atomising Steam Press Control HFO Flow Control LDO Flow Control HFO Heater – A O/L Temp Control HFO Pump Discharge Press Control LDO Pump Discharge Press Control
![Page 21: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/21.jpg)
The Control Loops
HP Bypass Pressure Control HP Bypass Temp. Control APRDS Pressure Control APRDS Temperature Control
Co-ordinated Master Control (CMC)
![Page 22: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/22.jpg)
Importance of Heater Level Control
![Page 23: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/23.jpg)
Feed Water / Condensate Temp. Rise
Terminal Temp. Difference (TTD)
Tsat(steam) – TFW Outlet
Increase in TTD implies worse heat transfer
Drain Cooler Approach (DCA)
TDrain Outlet – TFW Inlet
Increase in DCA implies decrease in water
level.
Heater Performance Monitoring
![Page 24: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/24.jpg)
LPH –2 LEVEL CONTROL
![Page 25: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/25.jpg)
LPH –3 LEVEL CONTROL
![Page 26: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/26.jpg)
HPH -5A LEVEL CONTROL
![Page 27: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/27.jpg)
HPH -6A LEVEL CONTROL
![Page 28: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/28.jpg)
HPH -5B LEVEL CONTROL
![Page 29: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/29.jpg)
HPH -6B LEVEL CONTROL
![Page 30: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/30.jpg)
HOTWELL LEVEL CONTROL
![Page 31: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/31.jpg)
HOTWELL LEVEL CONTROL
![Page 32: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/32.jpg)
GSC MIN FLOW CONTROL
![Page 33: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/33.jpg)
GLAND SEAL COND PR CONTROL
![Page 34: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/34.jpg)
Why is Deaerator Pegging Required
![Page 35: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/35.jpg)
Heat the incoming feed water to the saturation point to reduce the solubility of entrained gases.
The gases are basically O2, CO2 and NH3 - very corrosive at elevated temperatures.
Set of trays that separates the water into thin sheets from which the gases can easily escape.
The gases are vented out of the deaerator to the atmosphere.
To ensure mixing & elimination of corrosive gases, the FW level & steam pressure controls are important.
Why is Deaerator Pegging Required
![Page 36: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/36.jpg)
DEAERATOR PRESS CONTROL
![Page 37: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/37.jpg)
DEAERATOR LEVEL CONTROL
![Page 38: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/38.jpg)
DEAERATOR LEVEL CONTROL
![Page 39: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/39.jpg)
Hydrazine is used as oxygen scavenger. Hydrazine is one of the most costly chemical. Hydrazine dosing done at De-aerator outlet (BFP
suction)
Feed water has to be alkalized to a pH of 9 or higher, to reduce oxidation.
Also helps in forming of a stable layer of magnetite on the water-side surface of the boiler, protecting the material underneath from further corrosion.
Achieved by dosing alkaline agents into the feed water, like NaOH or volatile NH3.
Ammonia dosing done at CEP Discharge.
Dosing in Condensate & Feed Water
![Page 40: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/40.jpg)
AMMONIA DOSING CONTROL
![Page 41: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/41.jpg)
HYDRAZINE DOSING CONTROL
![Page 42: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/42.jpg)
It is the Drum which speaks in a tube type boiler! Loose reddish powder – Boiler corrosion Loose Greyish powder – Economiser / pre-boiler
corrosion
Purpose is to reduce hardness and facilitate scale control.
Phosphate is a highly soluble, powder compound – significantly effective for hardness & scale control
Binds to calcium – prevents scaling but forms a sludge.
Phosphate dosing done at boiler drum.
Chemical Dosing in Drum
![Page 43: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/43.jpg)
PHOSPHATE DOSING CONTROL
![Page 44: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/44.jpg)
FURNACE PRESS CONTROL
![Page 45: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/45.jpg)
FURNACE PRESS CONTROL
![Page 46: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/46.jpg)
FURNACE PRESS CONTROL
![Page 47: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/47.jpg)
FURNACE PRESS CONTROL
![Page 48: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/48.jpg)
FURNACE PRESS CONTROL
![Page 49: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/49.jpg)
AIR FLOW CONTROL
![Page 50: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/50.jpg)
AIR FLOW CONTROL
![Page 51: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/51.jpg)
AIR FLOW CONTROL
![Page 52: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/52.jpg)
AIR FLOW CONTROL
![Page 53: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/53.jpg)
DRUM LEVEL CONTROL
![Page 54: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/54.jpg)
Typical Drum parameters of 500/600MW sub-critical unit – 197 Kg/cm2 & 363 Deg C!
Density is proportional to Pressure. Density is inv. proportional to Temperature.
DP is affected by changing density of water & steam inside boiler.
Drum Level Measurement - Facts
![Page 55: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/55.jpg)
![Page 56: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/56.jpg)
![Page 57: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/57.jpg)
DRUM LEVEL CONTROL
![Page 58: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/58.jpg)
DRUM LEVEL CONTROL
![Page 59: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/59.jpg)
DRUM LEVEL CONTROL
![Page 60: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/60.jpg)
DRUM LEVEL CONTROL
![Page 61: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/61.jpg)
DRUM LEVEL CONTROL
![Page 62: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/62.jpg)
DRUM LEVEL CONTROL
![Page 63: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/63.jpg)
DRUM LEVEL CONTROL
![Page 64: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/64.jpg)
AIR FLOW CONTROL
![Page 65: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/65.jpg)
FUEL FLOW CONTROL
![Page 66: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/66.jpg)
FUEL FLOW CONTROL
![Page 67: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/67.jpg)
PA HDR PRESS CONTROL
![Page 68: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/68.jpg)
PA HDR PRESS CONTROL
![Page 69: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/69.jpg)
MILL-A AIR FLOW CONTROL
![Page 70: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/70.jpg)
MILL –A AIR TEMP CONTROL
![Page 71: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/71.jpg)
SH STM TEMP CONTROL
![Page 72: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/72.jpg)
SH STM TEMP CONTROL
![Page 73: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/73.jpg)
SH STM TEMP CONTROL
![Page 74: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/74.jpg)
BURNER TILT CONTROL
![Page 75: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/75.jpg)
BURNER TILT CONTROL
![Page 76: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/76.jpg)
RH STM TEMP CONTROL
![Page 77: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/77.jpg)
RH STM TEMP CONTROL
![Page 78: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/78.jpg)
RH STM TEMP CONTROL
![Page 79: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/79.jpg)
Boiler Flue gas contains water vapour, sulfur & other chemicals.
Low Flue gas temp. (below dew point) at AH cold end may result in condensation of water vapour.
Combination with sulfur forms sulfuric acid.
Results in corrosion of the cold end metal.
Why AH Cold end needs to be protected?
![Page 80: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/80.jpg)
AH COLD END TEMP CONTROL
![Page 81: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/81.jpg)
AH COLD END TEMP CONTROL
![Page 82: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/82.jpg)
CBD TANK LEVEL CONTROL
![Page 83: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/83.jpg)
ATOMISING STEAM PRESS CONTROL
![Page 84: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/84.jpg)
HFO FLOW CONTROL
![Page 85: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/85.jpg)
LDO FLOW CONTROL
![Page 86: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/86.jpg)
HFO HEATER – A O/L TEMP CONTROL
![Page 87: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/87.jpg)
HFO PUMP DISCH PRESS CONTROL
![Page 88: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/88.jpg)
LDO PUMP DISCH PRESS CONTROL
![Page 89: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/89.jpg)
HP BYPASS SYSTEM PRESS CONTROL
![Page 90: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/90.jpg)
HP BYPASS SYSTEM PRESS CONTROL
![Page 91: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/91.jpg)
SPRAY BLOCK VALVE LOGIC
![Page 92: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/92.jpg)
HP BYPASS SYSTEM MISC ALARMS
![Page 93: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/93.jpg)
HP BYPASS SYSTEM TEMP CONTROL
![Page 94: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/94.jpg)
HP BYPASS SYSTEM TEMP CONTROL
![Page 95: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/95.jpg)
AUX STEAM HDR PRESS CONTROL
![Page 96: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/96.jpg)
AUX STEAM HDR PRESS CONTROL
![Page 97: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/97.jpg)
HT AUX STEAM HDR TEMP CONTROL
![Page 98: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/98.jpg)
LT AUX STEAM HDR TEMP CONTROL
![Page 99: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/99.jpg)
COORDINATED MASTER CONTROL SCHEME
![Page 100: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/100.jpg)
COORDINATED MASTER CONTROL SCHEME
![Page 101: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/101.jpg)
COORDINATED MASTER CONTROL SCHEME
![Page 102: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/102.jpg)
COORDINATED MASTER CONTROL SCHEME
![Page 103: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/103.jpg)
COORDINATED MASTER CONTROL SCHEME
![Page 104: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/104.jpg)
LOGO
![Page 105: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/105.jpg)
Heater Performance Monitoring
![Page 106: Auto Control Loops Presentation](https://reader036.fdocuments.us/reader036/viewer/2022081417/552d725b4a795906588b46d1/html5/thumbnails/106.jpg)
Heater Performance Monitoring
Off design final FWH temperature at a 500MW Coal fired plant
Outlet Temperature Target 225◦ C
Actual 214◦ C
Difference -11 ◦ C
CHECKED PERFORMANCE PARAMETERS Temp Rise Target 27◦ C
Actual 18◦ C
DCA Target -12.22◦ C
Actual -16.1◦ C
TTD Target -12.22◦ C
Actual -6.94◦ C