SECTION 08874 SAFETY AND SECURITY FILM Display hidden notes to specifier. (Don't know how? Click Here ) Copyright 2004 - 2008 ARCAT, Inc. - All rights reserved PART 1 GENERAL 1.1 SECTION INCLUDES A. Safety and Security film field applied to existing glass. B. Safety and Security film factory applied to glazed surfaces. 1.2 RELATED SECTIONS A. Section 08110 - Steel Doors and Frames: New doors with glazing to receive film. B. Section 08510 - Steel Windows: New windows to receive film. C. Section 08520 - Aluminum Windows: New windows to receive film. D. Section 08590 - Window Restoration and Replacement: Existing windows to receive film. E. Section 08900 - Glazed Curtain Walls: New glazing to receive film. 1.3 REFERENCES A. American Society for Testing Materials (ASTM) B. American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) C. Association of Industrial Metallizers, Coaters and Laminators (AIMCAL) D. American National Standards Institute (ANSI) E. International Standards Organization (ISO) F. International Window Film Association (IWFA) 08874-1

Transcript of ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance:...

Page 1: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

SECTION 08874

SAFETY AND SECURITY FILMDisplay hidden notes to specifier. (Don't know how? Click Here)

Copyright 2004 - 2008 ARCAT, Inc. - All rights reserved

PART 1 GENERAL

1.1 SECTION INCLUDES

A. Safety and Security film field applied to existing glass.

B. Safety and Security film factory applied to glazed surfaces.

1.2 RELATED SECTIONS

A. Section 08110 - Steel Doors and Frames: New doors with glazing to receive film.

B. Section 08510 - Steel Windows: New windows to receive film.

C. Section 08520 - Aluminum Windows: New windows to receive film.

D. Section 08590 - Window Restoration and Replacement: Existing windows to receive film.

E. Section 08900 - Glazed Curtain Walls: New glazing to receive film.

1.3 REFERENCES

A. American Society for Testing Materials (ASTM)

B. American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE)

C. Association of Industrial Metallizers, Coaters and Laminators (AIMCAL)

D. American National Standards Institute (ANSI)

E. International Standards Organization (ISO)

F. International Window Film Association (IWFA)

G. Government Services Administration (GSA)

H. Consumer Products Safety Commission (CPSC)

I. Code of Federal Regulations (CFR)

1.4 PERFORMANCE REQUIREMENTS

A. Storm Testing: 8 mil Solar Gard Armorcoat safety films shall be capable of meeting the following tests:

08874-1

Page 2: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

1. ASTM E-1886, Standard Test Method for Missile Impact and Cycling On Exterior Windows, Shutters, Doors and Curtain Walls - Large Missile C.

2. ASTM E-1996, Standard Specification for Missile Impact and Cycling On Exterior Windows, Shutters, Doors and Curtain Wall - Large Missile C.

3. ASTM E-283-04, Test Method for Airflow through Exterior Windows, Shutters, Doors and Curtain Walls.

4. ASTM E-330-02 Test Method for Structural Performance of Exterior Windows, Shutters, Doors and Curtain Walls by uniform Static Air Pressure Difference.

5. ASTM E-331-00, Test Method for Structural Performance of Exterior Windows, Shutters, Doors and Curtain Walls by uniform Static Air Pressure Difference.

B. Bomb Blast Simulation: Independent testing of Solar Gard safety films with results from high-explosive tests evaluating the capability of Solar Gard window film in 4 mil to 14 mil thicknesses to reduce the hazards of flying glass shards during an explosion.1. GSA TS-01-2003, GSA Performance Condition with a minimum blast pressure of 4

psi-28 psi-msec when applied as a daylight application on 1/4 inch (6 mm) single pane annealed glass: 3B.

2. GSA TS-01-2003, GSA Performance Condition with a minimum blast pressure of 4 psi-28 psi-msec when applied as a daylight application on 1/4 inch (6 mm) single pane tempered glass: 3B.

3. GSA TS-01-2003, GSA Performance Condition with a minimum blast pressure of 4 psi-28 psi-msec when applied with Dow Corning 995 on 1/4 inch (6 mm) single pane annealed glass: 3A.

4. GSA TS-01-2003, GSA Performance Condition with a minimum blast pressure of 4 psi-28 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) single pane tempered glass: 2.

5. GSA TS-01-2003, GSA Performance Condition with a minimum blast pressure of 4 psi-28 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane annealed glass: 2.

6. ISO 16933 Hazard Rating with a minimum blast pressure of 7 psi-36 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane tempered glass: "Hazard Rating B (EXV33(B))" .

7. ISO 16933 Hazard Rating with a minimum blast pressure of 7 psi-36 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane annealed glass: "Hazard Rating C (EXV33(C))".

8. ASTM F 1642 Hazard Level with a minimum blast pressure of 4 psi-28 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane annealed glass: "No Hazard".

9. ASTM F 1642 Hazard Level with a minimum blast pressure of 7 psi-36 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane tempered glass: "No Hazard".

10. UFC 4-010-01 Protection Level with a minimum blast pressure of 4 psi-28 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane annealed glass: "High Level of Protection".

11. UFC 4-010-01 Protection Level with a minimum blast pressure of 7 psi-36 psi-msec when applied with GE SCS2000 Silpruf on 1/4 inch (6 mm) double pane tempered glass: "High Level of Protection".

C. Impact Resistance: Solar Gard safety films shall be capable of meeting the following tests:1. 4 mil Solar Gard safety films:

a. Passes ANSI Z 97.1 (100 - 150 ft lb).b. Passes CFR 1201, Category I (150 ft lb impact).

2. 7 mil and thicker Solar Gard safety films:a. Passes ANSI Z 97.1 (100 - 150 ft lb).b. Passes CFR 1201, Category II.

08874-2

Page 3: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

1.5 SUBMITTALS

A. Submit under provisions of Section 01300.

B. Product Data: Manufacturer's data sheets on each product to be used, including:1. Physical properties and independent testing agency reports showing compliance with

specified tests.2. Preparation instructions and recommendations.3. Storage and handling requirements and recommendations.4. Installation methods.

C. Shop Drawings: Detailing installation of film, anchoring accessories, and sealant.

D. Verification Samples: For each finish product specified, two samples, minimum size 6 inches (150 mm) square, representing actual product, color, and patterns.

E. Manufacturer's Certificates: Certify products meet or exceed specified requirements.

F. Manufacturer's warranty information.

1.6 QUALITY ASSURANCE

A. Manufacturer Qualifications: Solar film manufacturer shall be the standard product of a manufacturer regularly engaged in the manufacture and distribution of such products in satisfactory use for a minimum of 5 years. Manufacturing facility shall be ISO 9001-2000 and ISO 14001-2004 standard registration.

B. Installer Qualifications: Documented experience in the application of self-adhesive window films with at least 3 applications of similar size and complexity, and approved by the solar film manufacturer.

C. Mock-Up: Provide a mock-up for evaluation of surface preparation techniques and application workmanship.1. Apply film to one window designated by Architect.2. Do not proceed with remaining work until workmanship and color, is approved by

Architect.

1.7 DELIVERY, STORAGE, AND HANDLING

A. Store products indoors in manufacturer's unopened packaging until ready for installation.

1.8 PROJECT CONDITIONS

A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits.

1.9 WARRANTY

A. See Section 01780 - Closeout Submittals for additional warranty requirements.

B. Provide film manufacturer's limited warranty against failure of film, including change of color, peeling, bubbling, rippling, cracking, delamination and demetalization; include cost of material and labor for removal and reinstallation. Duration of warranty shall be as follows:1. Twelve Year Limited Warranty for the following safety and security film products:

a. Solar Gard Armorcoat 4 mil Stainless Steel 50b. Solar Gard Armorcoat 4 mil Stainless Steel 35c. Solar Gard Armorcoat 4 mil Stainless Steel 20

08874-3

Page 4: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

d. Solar Gard Armorcoat 8 mil Stainless Steel 50e. Solar Gard Armorcoat 8 mil Stainless Steel 35f. Solar Gard Armorcoat 8 mil Stainless Steel 20g. Solar Gard Armorcoat 10 mil Stainless Steel 35h. Solar Gard Armorcoat 4 mil Solar Bronze 20i. Solar Gard Armorcoat 4 mil Solar Bronze 35j. Solar Gard Armorcoat 4 Mil Silver 20k. Solar Gard Armorcoat 8 mil Silver 35l. Solar Gard Armorcoat 8 mil Silver 20m. Solar Gard Armorcoat 10 Mil Silver 20n. Solar Gard Armorcoat 4 Mil Clearo. Solar Gard Armorcoat 7 Mil Clearp. Solar Gard Armorcoat 8 Mil Clearq. Solar Gard Armorcoat 10 Mil Clearr. Solar Gard Armorcoat 11 Mil Clears. Solar Gard Armorcoat 14 Mil Cleart. Panorama 8 Mil Hilite 70

PART 2 PRODUCTS

2.1 MANUFACTURERS

A. Acceptable Manufacturer: Solar Gard®, which is located at: 4540 View Ridge Ave.; San Diego, CA 92123; Toll Free Tel: 877-273-4364; Tel: 858-576-0200; Fax: 858-571-3605; Email:[email protected]; Web:www.solargard.com

B. Substitutions: Not permitted.

C. Requests for substitutions will be considered in accordance with provisions of Section 01600.

2.2 SAFETY AND SECURITY FILM

A. Film shall be manufactured from polyethylene terepthalate (polyester) and combined with sputtered metal coatings to achieve the desired performance and aesthetic characteristics. The finished film shall be self adhesive and include a coating to reduce the effects of scratching and abrasions that occur in normal daily activity and also include absorbers and inhibitors for the purpose of reducing ultra violet rays.

B. Solar Gard Armorcoat 4 Mil Stainless Steel 50 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance: 39 percent.b. Solar Absorptance: 50 percent.c. Solar Reflectance: 11 percent.d. Visible Light Transmittance: 46 percent.e. Visible Light Reflectance: (Exterior) 13 percent.f. Visible Light Reflectance: (Interior) 11 percent.g. Emissivity: .90.h. U-Factor (Winter): 1.12.i. Shading Coefficient: .62.j. Solar Heat Gain Coefficient: .53.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percentl. Total Solar Energy Rejected: 46 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mils (100 microns).b. Peel Strength: 2,500 g/in (984 g/cm)

08874-4

Page 5: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (22 kg/cm).e. Elongation at Break: Greater than 100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).i. Meets GSA Level C criteria (3B at 4 psi, 28 psi/milliseconds)

C. Solar Gard Armorcoat 4 Mil Stainless Steel 50 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 43 percentb. Solar Absorptance 46 percentc. Solar Reflectance 12 percentd. Visible Light Transmittance 47 percente. Visible Light Reflectance (Exterior) 13 percentf. Visible Light Reflectance (Interior) 11 percentg. Emissivity: .90.h. U-Value (Winter) 1.07.i. Shading Coefficient .65.j. Solar Heat Gain Coefficient .56.k. Ultraviolet Light Blocked (300-380 nanometers) Greater than 99 percentl. Total Solar Energy Rejected 44 percent

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mil (100 micron)b. Peel Strength: 2,500 g/in (984 g/cm)c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (22 kg/cm).e. Elongation at Break: Greater than 100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).

D. Solar Gard Armorcoat 4 Mil Stainless Steel 35 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 39 percentb. Solar Absorptance 48 percentc. Solar Reflectance 14 percentd. Visible Light Transmittance 42 percente. Visible Light Reflectance (Exterior) 16 percentf. Visible Light Reflectance (Interior) 13 percentg. Emissivity: .87.h. U-Factor (Winter) 1.05.i. Shading Coefficient .61.j. Solar Heat Gain Coefficient .53.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percentl. Total Solar Energy Rejected 47 percent

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mils (100 microns).b. Peel Strength: 2,500 g/in (984 g/cm)c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (22 kg/cm).e. Elongation at Break: 160 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.

08874-5

Page 6: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).

E. Solar Gard Armorcoat 4 Mil Stainless Steel 35 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 36 percentb. Solar Absorptance 52 percentc. Solar Reflectance 12 percentd. Visible Light Transmittance 42 percente. Visible Light Reflectance (Exterior) 14 percentf. Visible Light Reflectance (Interior) 14 percentg. Emissivity: .87.h. U-Factor (Winter) 1.03.i. Shading Coefficient .60.j. Solar Heat Gain Coefficient .51.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 87 percent

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mils (100 microns).b. Peel Strength: 2,500 g/in (984 g/cm)c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (22 kg/cm).e. Elongation at Break: 160 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

F. Solar Gard Armorcoat 4 Mil Stainless Steel 20 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 19 percent.b. Solar Absorptance 61 percent.c. Solar Reflectance 20 percent.d. Visible Light Transmittance 22 percente. Visible Light Reflectance (Exterior) 26 percent.f. Visible Light Reflectance (Interior) 25 percent.g. Emissivity: .85.h. U-Factor (Winter) 1.09.i. Shading Coefficient .42.j. Solar Heat Gain Coefficient .37.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 63 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mils (100 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (22 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

G. Solar Gard Armorcoat 4 Mil Stainless Steel 20 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.

08874-6

Page 7: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

1. Film Performance Results, Nominal:a. Solar Transmittance 21 percent.b. Solar Absorptance 56 percent.c. Solar Reflectance 23 percent.d. Visible Light Transmittance 22 percent.e. Visible Light Reflectance (Exterior) 27 percent.f. Visible Light Reflectance (Interior) 25 percent.g. Emissivity: .85.h. U-Factor (Winter) 1.11.i. Shading Coefficient .43.j. Solar Heat Gain Coefficient .37.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 63 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mils (100 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (22 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).

H. Solar Gard Armorcoat 8 Mil Stainless Steel 50 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 40 percent.b. Solar Absorptance 49 percent.c. Solar Reflectance 11 percent.d. Visible Light Transmittance 44 percent.e. Visible Light Reflectance (Exterior) 14 percent.f. Visible Light Reflectance (Interior) 11 percent.g. Emissivity: .88.h. U-Factor (Winter) 1.06.i. Shading Coefficient .62.j. Solar Heat Gain Coefficient .54.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 46 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 8.0 mil (200 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 240 lbs/in (43 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).

I. Solar Gard Armorcoat 8 Mil Stainless Steel 50 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 37 percent.b. Solar Absorptance 53 percent.c. Solar Reflectance 10 percent.d. Visible Light Transmittance 43 percent.e. Visible Light Reflectance (Exterior) 13 percent.

08874-7

Page 8: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

f. Visible Light Reflectance (Interior) 11 percent.g. Emissivity: .88.h. U-Factor (Winter) 1.11.i. Shading Coefficient .60.j. Solar Heat Gain Coefficient .51.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 48 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 8.0 mil (200 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 240 lbs/in (43 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

J. Solar Gard Armorcoat 8 Mil Stainless Steel 35 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 34 percent.b. Solar Absorptance 52 percent.c. Solar Reflectance 14 percent.d. Visible Light Transmittance 38 percent.e. Visible Light Reflectance (Exterior) 16 percent.f. Visible Light Reflectance (Interior) 13 percent.g. Emissivity: .88.h. U-Factor (Winter) 1.05.i. Shading Coefficient .57.j. Solar Heat Gain Coefficient .50.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 50 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 8.0 mil (200 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 240 lbs/in (43 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).

K. Solar Gard Armorcoat 8 Mil Stainless Steel 35 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 32 percent.b. Solar Absorptance 56 percent.c. Solar Reflectance 12 percent.d. Visible Light Transmittance 38 percent.e. Visible Light Reflectance (Exterior) 16 percent.f. Visible Light Reflectance (Interior) 13 percent.g. Emissivity: .88.h. U-Factor (Winter) 1.11.i. Shading Coefficient .55.j. Solar Heat Gain Coefficient .48.

08874-8

Page 9: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 52 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 8.0 mil (200 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 240 lbs/in (43 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

L. Solar Gard Armorcoat 8 Mil Stainless Steel 20 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 20 percent.b. Solar Absorptance 58 percent.c. Solar Reflectance 22 percent.d. Visible Light Transmittance 21 percent.e. Visible Light Reflectance (Exterior) 26 percent.f. Visible Light Reflectance (Interior) 24 percent.g. Emissivity: .86.h. U-Factor (Winter) 1.05.i. Shading Coefficient .43.j. Solar Heat Gain Coefficient .37.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 63 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 8.0 mil (200 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 240 lbs/in (43 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).

M. Solar Gard Armorcoat 8 Mil Stainless Steel 20 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 18 percent.b. Solar Absorptance 62 percent.c. Solar Reflectance 20 percent.d. Visible Light Transmittance 21 percent.e. Visible Light Reflectance (Exterior) 26 percent.f. Visible Light Reflectance (Interior) 24 percent.g. Emissivity: .86.h. U-Factor (Winter) 1.03.i. Shading Coefficient .43.j. Solar Heat Gain Coefficient .3.7k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 63 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 8.0 mil (200 microns).b. Peel Strength: 2,500 g/in (984 g/cm).

08874-9

Page 10: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 240 lbs/in (43 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28psi/milliseconds).

N. Solar Gard Armorcoat 10 Mil Stainless Steel 35 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 39 percent.b. Solar Absorptance 48 percent.c. Solar Reflectance 13 percent.d. Visible Light Transmittance 43 percent.e. Visible Light Reflectance (Exterior) 16 percent.f. Visible Light Reflectance (Interior) 13 percent.g. Emissivity: .84h. U-Factor (Winter) 1.03.i. Shading Coefficient .62.j. Solar Heat Gain Coefficient .53k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 47 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 10.0 mil (250 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 300 lbs/in (54 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 174 lbs (78 (kg).

O. Solar Gard Armorcoat 10 Mil Stainless Steel 35 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 36 percent.b. Solar Absorptance 52 percent.c. Solar Reflectance 10 percent.d. Visible Light Transmittance 43 percent.e. Visible Light Reflectance (Exterior) 13 percent.f. Visible Light Reflectance (Interior) 13 percent.g. Emissivity: .84.h. U-Factor (Winter) 1.01.i. Shading Coefficient .60.j. Solar Heat Gain Coefficient .52.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 48 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 10.0 mil (250 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 300 lbs/in (54 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.

08874-10

Page 11: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

h. ASTM D 4830 Puncture Test: 174 lbs (78 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

P. Solar Gard Armorcoat 4 Mil Solar Bronze 35 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 19 percent.b. Solar Absorptance 38 percent.c. Solar Reflectance 43 percent.d. Visible Light Transmittance 32 percent.e. Visible Light Reflectance (Exterior) 29 percent.f. Visible Light Reflectance (Interior) 27 percent.g. Emissivity: .68.h. U-Factor (Winter) .95.i. Shading Coefficient .34.j. Solar Heat Gain Coefficient .29.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 71 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mils (100 microns).b. Peel Strength: 2,500 g/in (984 g/cm)c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (22 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).

Q. Solar Gard Armorcoat 4 Mil Solar Bronze 35 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 18 percent.b. Solar Absorptance 46 percent.c. Solar Reflectance 36 percent.d. Visible Light Transmittance 31 percent.e. Visible Light Reflectance (Exterior) 28 percent.f. Visible Light Reflectance (Interior) 27 percent.g. Emissivity: .68.h. U-Factor (Winter) 1.01.i. Shading Coefficient .34.j. Solar Heat Gain Coefficient .30.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 70 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mils (100 microns).b. Peel Strength: 2,500 g/in (984 g/cm)c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (22 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

R. Solar Gard Armorcoat 4 Mil Solar Bronze 20 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.

08874-11

Page 12: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

1. Film Performance Results, Nominal:a. Solar Transmittance 10 percent.b. Solar Absorptance 40 percent.c. Solar Reflectance 50 percent.d. Visible Light Transmittance 18 percent.e. Visible Light Reflectance (Exterior) 38 percent.f. Visible Light Reflectance (Interior) 39 percent.g. Emissivity: .68.h. U-Factor (Winter) .95.i. Shading Coefficient .24.j. Solar Heat Gain Coefficient .20k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 80 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mils (100 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (22 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).

S. Solar Gard Armorcoat 4 Mil Solar Bronze 20 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 9 percent.b. Solar Absorptance 49 percent.c. Solar Reflectance 42 percent.d. Visible Light Transmittance 18 percent.e. Visible Light Reflectance (Exterior) 37 percent.f. Visible Light Reflectance (Interior) 40 percent.g. Emissivity: .68.h. U-Factor (Winter) 1.01.i. Shading Coefficient .25.j. Solar Heat Gain Coefficient .22.k. Ultraviolet Light Transmittance (300-380 nanometers) less than 2 percent.l. Total Solar Energy Rejected 78 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mils (100 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (22 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

T. Solar Gard Armorcoat 4 Mil Silver 20 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 10 percent.b. Solar Absorptance 45 percent.c. Solar Reflectance 45 percent.d. Visible Light Transmittance 15 percent.

08874-12

Page 13: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

e. Visible Light Reflectance (Exterior) 56 percent.f. Visible Light Reflectance (Interior) 60 percent.g. Emissivity: .71.h. U-Factor (Winter) 1.03.i. Shading Coefficient .25.j. Solar Heat Gain Coefficient .22.k. Ultraviolet Light Transmittance (300-380 nanometers) less than 2 percent.l. Total Solar Energy Rejected 78 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mils (100 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (22 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

U. Solar Gard Armorcoat 4 Mil Silver 20 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 11 percent.b. Solar Absorptance 37 percent..c. Solar Reflectance 52 percentd. Visible Light Transmittance 15 percent.e. Visible Light Reflectance (Exterior) 59 percent.f. Visible Light Reflectance (Interior) 60 percent.g. Emissivity: .71.h. U-Factor (Winter) .97.i. Shading Coefficient .24.j. Solar Heat Gain Coefficient .21.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 79 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mils (100 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (22 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).

V. Solar Gard Armorcoat 8 Mil Silver 35 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 24 percent.b. Solar Absorptance 47 percent.c. Solar Reflectance 29 percent.d. Visible Light Transmittance 34 percent.e. Visible Light Reflectance (Exterior) 34 percent.f. Visible Light Reflectance (Interior) 33 percent.g. Emissivity: .71.h. U-Factor (Winter) 1.02.i. Shading Coefficient .42.

08874-13

Page 14: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

j. Solar Heat Gain Coefficient .37.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 63 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 8.0 mils (200 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 240 lbs/in (43 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

W. Solar Gard Armorcoat 8 Mil Silver 35 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 26 percent.b. Solar Absorptance 40 percent.c. Solar Reflectance 34 percent.d. Visible Light Transmittance 35 percent.e. Visible Light Reflectance (Exterior) 35 percent.f. Visible Light Reflectance (Interior) 33 percent.g. Emissivity: .71.h. U-Factor (Winter) 1.04.i. Shading Coefficient .43.j. Solar Heat Gain Coefficient .37.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 63 percent

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 8.0 mils (200 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 240 lbs/in (43 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).

X. Solar Gard Armorcoat 8 Mil Silver 20 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 9 percent.b. Solar Absorptance 47 percent.c. Solar Reflectance 44 percent.d. Visible Light Transmittance 14 percent.e. Visible Light Reflectance (Exterior) 56 percent.f. Visible Light Reflectance (Interior) 59 percent.g. Emissivity: .70.h. U-Factor (Winter) 1.02.i. Shading Coefficient .25.j. Solar Heat Gain Coefficient .22.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 78 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 8.0 mils (200 microns).

08874-14

Page 15: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 240 lbs/in (43 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

Y. Solar Gard Armorcoat 8 Mil Silver 20 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 10 percent.b. Solar Absorptance 39 percent.c. Solar Reflectance 51 percent.d. Visible Light Transmittance 14 percent.e. Visible Light Reflectance (Exterior) 58 percent.f. Visible Light Reflectance (Interior) 59 percent.g. Emissivity: .70.h. U-Factor (Winter) .96.i. Shading Coefficient .24.j. Solar Heat Gain Coefficient .21.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 79 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 8.0 mils (200 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 240 lbs/in (43 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).

Z. Solar Gard Armorcoat 10 Mil Silver 20 Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 11 percent.b. Solar Absorptance 46 percent.c. Solar Reflectance 43 percent.d. Visible Light Transmittance 17 percent.e. Visible Light Reflectance (Exterior) 54 percent.f. Visible Light Reflectance (Interior) 55 percent.g. Emissivity: .70.h. U-Factor (Winter) 1.02.i. Shading Coefficient .27.j. Solar Heat Gain Coefficient .23.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 77 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 10.0 mil (250 microns).b. Peel Strength: 2,500 g/in (984 g/cm)c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 300 lbs/in (54 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.

08874-15

Page 16: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 174 lbs (78 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

AA. Solar Gard Armorcoat 10 Mil Silver 20 Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 12 percent.b. Solar Absorptance 39 percent.c. Solar Reflectance 49 percent.d. Visible Light Transmittance 17 percent.e. Visible Light Reflectance (Exterior) 56 percent.f. Visible Light Reflectance (Interior) 55 percent.g. Emissivity: .70.h. U-Factor (Winter) .96.i. Shading Coefficient .26.j. Solar Heat Gain Coefficient .22.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 78 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 10.0 mil (250 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 300 lbs/in (54 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 174 lbs (78 (kg).

BB. Solar Gard Armorcoat 4 Mil Clear Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance: 73 percent.b. Solar Absorptance: 19 percent.c. Solar Reflectance: 8 percent.d. Visible Light Transmittance: 87 percent.e. Visible Light Reflectance: (Exterior) 9 percent.f. Visible Light Reflectance: (Interior) 9 percent.g. Emissivity: .90.h. U-Factor (Winter): 1.12.i. Shading Coefficient: .91.j. Solar Heat Gain Coefficient: .78.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected: 21 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mils (100 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (230 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

CC. Solar Gard Armorcoat 4 Mil Clear Safety and Security film shall have the following properties

08874-16

Page 17: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance: 79 percent.b. Solar Absorptance: 13 percent.c. Solar Reflectance: 8 percent.d. Visible Light Transmittance: 89 percent.e. Visible Light Reflectance: (Exterior) 9 percent.f. Visible Light Reflectance: (Interior) 9 percent.g. Emissivity: .90.h. U-Factor (Winter): 1.07.i. Shading Coefficient: .96.j. Solar Heat Gain Coefficient: .83.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected: 17 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 4.0 mils (100 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 120 lbs/in (22 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 70 lbs (32 (kg).

DD. Solar Gard Armorcoat 7 Mil Clear Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 79 percent.b. Solar Absorptance 13 percent.c. Solar Reflectance 8 percent.d. Visible Light Transmittance 89 percent.e. Visible Light Reflectance (Exterior) 9 percent.f. Visible Light Reflectance (Interior) 9 percent.g. Emissivity: .90.h. U-Factor (Winter) 1.07.i. Shading Coefficient .95.j. Solar Heat Gain Coefficient .83.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 17 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 7.0 mils (175 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 210 lbs/in (38 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 118 lbs (52 (kg).

EE. Solar Gard Armorcoat 7 Mil Clear Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 73 percent.b. Solar Absorptance 19 percent.c. Solar Reflectance 8 percent.d. Visible Light Transmittance 87 percent.

08874-17

Page 18: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

e. Visible Light Reflectance (Exterior) 9 percent.f. Visible Light Reflectance (Interior) 9 percent.g. Emissivity: .90.h. U-Factor (Winter) 1.09.i. Shading Coefficient .90.j. Solar Heat Gain Coefficient .78.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 22 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 8.0 mils (200 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 240 lbs/in (43 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).i. Meets GSA Level C criteria (3B at 4 psi, 28psi/milliseconds).

FF. Solar Gard Armorcoat 8 Mil Clear Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 69 percent.b. Solar Absorptance 21 percent.c. Solar Reflectance 10 percent.d. Visible Light Transmittance 83 percent.e. Visible Light Reflectance (Exterior) 13 percent.f. Visible Light Reflectance (Interior) 12 percent.g. Emissivity: .88.h. U-Factor (Winter) 1.11.i. Shading Coefficient .87.j. Solar Heat Gain Coefficient .74.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 24 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 8.0 mils (200 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 240 lbs/in (43 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

GG. Solar Gard Armorcoat 8 Mil Clear Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 75 percent.b. Solar Absorptance 14 percent.c. Solar Reflectance 11 percent.d. Visible Light Transmittance 84 percent.e. Visible Light Reflectance (Exterior) 13 percent.f. Visible Light Reflectance (Interior) 12 percent.g. Emissivity: .88.h. U-Factor (Winter) 1.05..

08874-18

Page 19: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

i. Shading Coefficient .91j. Solar Heat Gain Coefficient .79.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 21 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 8.0 mils (200 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 240 lbs/in (43 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 141 lbs (64 (kg).

HH. Solar Gard Armorcoat 10 Mil Clear Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 71 percent.b. Solar Absorptance 21 percent.c. Solar Reflectance 8 percent.d. Visible Light Transmittance 86 percent.e. Visible Light Reflectance (Exterior) 10 percent.f. Visible Light Reflectance (Interior) 11 percent.g. Emissivity: .88.h. U-Factor (Winter) 1.11.i. Shading Coefficient .89.j. Solar Heat Gain Coefficient .76.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 23 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 10.0 mil (250 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 300 lbs/in (54 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 174 lbs (78 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

II. Solar Gard Armorcoat 10 Mil Clear Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 77 percent.b. Solar Absorptance 14 percent.c. Solar Reflectance 9 percent.d. Visible Light Transmittance 87 percent.e. Visible Light Reflectance (Exterior) 10 percent.f. Visible Light Reflectance (Interior) 11 percent.g. Emissivity: .88.h. U-Factor (Winter) 1.05.i. Shading Coefficient .94.j. Solar Heat Gain Coefficient .81.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 19 percent.

2. Physical and Thermal Properties, Nominal:

08874-19

Page 20: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

a. Film Thickness: 10.0 mil (250 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 300 lbs/in (54 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 174 lbs (78 (kg).

JJ. Solar Gard Armorcoat 11 Mil 2-Ply Clear Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 72 percent.b. Solar Absorptance 20 percent.c. Solar Reflectance 8 percent.d. Visible Light Transmittance 86 percent.e. Visible Light Reflectance (Exterior) 10 percent.f. Visible Light Reflectance (Interior) 10 percent.g. Emissivity: .89.h. U-Factor (Winter) 1.11.i. Shading Coefficient .90.j. Solar Heat Gain Coefficient .77.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 22 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 11.0 mil (275 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 330 lbs/in (59 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 198 lbs (89 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28psi/milliseconds).

KK. Solar Gard Armorcoat 11 Mil 2-Ply Clear Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 78 percent.b. Solar Absorptance 13 percent.c. Solar Reflectance 9 percent.d. Visible Light Transmittance 88 percent.e. Visible Light Reflectance (Exterior) 10 percent.f. Visible Light Reflectance (Interior) 10 percent.g. Emissivity: .89.h. U-Factor (Winter) 1.06.i. Shading Coefficient .95.j. Solar Heat Gain Coefficient .82.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 18 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 11.0 mil (275 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 330 lbs/in (59 kg/cm).e. Elongation at Break: greater than100 percent.

08874-20

Page 21: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 198 lbs (89 (kg).

LL. Solar Gard Armorcoat 14 Mil Clear Safety and Security film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 71 percent.b. Solar Absorptance 21 percent.c. Solar Reflectance 8 percent.d. Visible Light Transmittance 85 percent.e. Visible Light Reflectance (Exterior) 10 percent.f. Visible Light Reflectance (Interior) 11 percent.g. Emissivity: .89.h. U-Factor (Winter) 1.11.i. Shading Coefficient .88.j. Solar Heat Gain Coefficient .76.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 23 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 14.0 mil (350 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 420 lbs/in (75 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 230 lbs (104 (kg).i. Meets GSA Level C criteria (3B at 4psi, 28 psi/milliseconds).

MM. Solar Gard Armorcoat 14 Mil Clear Safety and Security film shall have the following properties when applied to 1/8 inch (3 mm) clear float glass.1. Film Performance Results, Nominal:

a. Solar Transmittance 77 percent.b. Solar Absorptance 14 percent.c. Solar Reflectance 9 percent.d. Visible Light Transmittance 87 percent.e. Visible Light Reflectance (Exterior) 11 percent.f. Visible Light Reflectance (Interior) 11 percent.g. Emissivity: .89.h. U-Factor (Winter) 1.06.i. Shading Coefficient .93.j. Solar Heat Gain Coefficient .81.k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percent.l. Total Solar Energy Rejected 19 percent.

2. Physical and Thermal Properties, Nominal:a. Film Thickness: 14.0 mil (350 microns).b. Peel Strength: 2,500 g/in (984 g/cm).c. Tensile Strength; 30,000 lbs/sq in (2,110 kg/cm sq).d. Break Strength; 420 lbs/in (75 kg/cm).e. Elongation at Break: greater than100 percent.f. Combustion Rate: Negligible.g. Melting Point: 260-265 degrees C.h. ASTM D 4830 Puncture Test: 230 lbs (104 (kg).

NN. Panorama 8 Mil Hilite 70 solar safety film shall have the following properties when applied to

08874-21

Page 22: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

1/8 inch (3 mm) clear float glass with pressure sensitive adhesive.1. Film Performance Results, Nominal

a. Solar Transmittance 38 percentb. Solar Absorptance 30 percentc. Solar Reflectance 32 percentd. Visible Light Transmittance 72 percente. Visible Light Reflectance (Exterior) 10 percentf. Visible Light Reflectance (Interior) 10 percentg. Emissivity .79h. U-Factor (Winter) 1.02i. Shading Coefficient .54j. Solar Heat Gain Coefficient .47k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percentl. Total Solar Energy Rejected 53 percent

2. Physical and Thermal Properties, Nominala. Film Thickness: 8 mil (200 micron)b. Peel Strength: 2,500 g/in (985 gm/cm).c. Tensile Strength 30,000 lbs/sq in (2,110 kg/cm sq)d. Break Strength; 240 lbs/in (43 kg/cm)e. Combustion Rate Negligiblef. Melting Point 260-265 degrees Cg. ASTM D 4830 Puncture Test: 141 lbs (64 kg)

OO. Panorama 8 Mil Hilite 70 solar safety film shall have the following properties when applied to 1/4 inch (6 mm) clear float glass with pressure sensitive adhesive.1. Film Performance Results, Nominal

a. Solar Transmittance 37 percentb. Solar Absorptance 37 percentc. Solar Reflectance 26 percentd. Visible Light Transmittance 71 percente. Visible Light Reflectance (Exterior) 9 percentf. Visible Light Reflectance (Interior) 10 percentg. Emissivity .79h. U-Factor (Winter) 0.99i. Shading Coefficient .55j. Solar Heat Gain Coefficient .47k. Ultraviolet Light Blocked (300-380 nanometers) greater than 99 percentl. Total Solar Energy Rejected 53 percent

2. Physical and Thermal Properties, Nominala. Film Thickness: 8 mil (200 micron)b. Peel Strength: 2,500 g/in (985 gm/cm).c. Tensile Strength 30,000 lbs/sq in (2,110 kg/cm sq)d. Break Strength; 240 lbs/in (43 kg/cm)e. Combustion Rate Negligiblef. Melting Point 260-265 degrees Cg. ASTM D 4830 Puncture Test: 141 lbs (64 kg)

PART 3 EXECUTION

3.1 EXAMINATION

A. Do not begin installation until substrates have been properly prepared.

B. If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.

3.2 PREPARATION

08874-22

Page 23: ARCAT · Web viewSolar Transmittance: 39 percent. Solar Absorptance: 50 percent. Solar Reflectance: 11 percent. Visible Light Transmittance: 46 percent. Visible Light Reflectance:

A. Clean surfaces thoroughly prior to installation.

B. Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.

3.3 INSTALLATION

A. Install in accordance with manufacturer's instructions. Installation must be accomplished by a recognized professional installer of film for energy control purposes or safety and security purposes. Completed work must meet IWFA visual acceptance standard.

B. Install without bubbles, ripples, drips, dirt, cuts, tears or gaps between film and frame.

C. Clean newly installed film and window frames after installation.

D. Clean up cleaning solutions, run-off cleaning water and adhesive mounting solution.

3.4 PROTECTION

A. Protect installed products until completion of project.

B. Where installed film could be damaged by subsequent construction provide tape warning strips or barricades to prevent contact.

END OF SECTION

08874-23