APPENDIX C Slab Calculation 2 - · PDF fileAPPENDIX C Slab Calculation 2 Now try calculating...
Transcript of APPENDIX C Slab Calculation 2 - · PDF fileAPPENDIX C Slab Calculation 2 Now try calculating...
APPENDIX CSlab Calculation 2
Now try calculating the same slab, with the minimum recommended balanced load of 50% of self-weight. (As opposed to 50% of DLLL used in the first calculation). The same thickness of slab will be used, with the same layout
Given:-- 4 bays each way 8000 x 7000 Ult. Load factors1.0 kPa finish1.8 kPa partitions2.5 kPa live loadSlab will be protected from weatherInternal columns 500 x 500External columns 300 x 500Wind loads taken bv shear walls
DL 1.2 and 1.5 as SABS 0160-1989LL 1.6
Floor to floor 3.0mAssume 15.2mm Dia cables, low relaxation
Breaking Strength 260.5 KNArea 140 sq. mm. E= 198 GPaRelaxation 1.5% at 1000 hrs
CALCULATIONAssume a 210 thick slab.
Balance 50% of Permanent Load 8.05kPa /2for internal spansFor external 8M spans, balance same proportion of load as previously, i.e 80/66x 0.5 =.606 Permanent loadFrom the formula, the slab should be somewhat thicker than 230mm, but take 210 as minimum practicable.
COMMENTSee diagrams infirst part ofcalculation
Formula wouldgive 230 slab
then self DLTotal perm =Service (1.1)
Live load
TOTAL
5.25 kPa8.058.85
2.50
11.35
Factored9.66
4.0
13.66
revised DL
12 factor toallow for extrashear in first int.
Check for shear as before, 210 is a bit thin, but acceptable with capitals
As contractor has column shutters with capitals, use capitals:For analysis assume E of slab = code value: i.e. (20 + 0.2 x 30) = 26.0 GPa
From the cross-sections, take the effective top cover as 47mm to C/L cable for 7m span, and (63 + 31)/2 = 47mmfor 8 m span. As bottom cover is 41 for 8 m span, effective drape - 210 - 88mm = 122 mm.For 7m span, drape is 210 - 98 =112 mm. (See Diag. Calculation 1)
From the diagrams of the cable shapes in the end spans (the cables in centre spans will have the same positions asat the ends of outer spans), the properties of the parabolas may be deduced, and then the losses due to curvature.Referring to the formula in Appendix A, the following table may be calculated, as before.
Span
8.0 end
8.0 cent
7.0 end
7.0 cent
al0.4
0.4
0.35
0.35
a2
0.4
0.4
0.35
0.35
0.1.,
0.163
0.13
0.163
b2.041
.041
.051
.051
b30.163
0.163
0.163
0.163
L
8.0
8.0
7.0
7.0
1
0.0330
0.0
.0330
0.0
m
1.34
1.854
1.039
149
n
-5.411
-7.418
-3.677
-5.214
X
3.7018
4.0
3.2114
3.5
cl.0096
.0122
.0086
.0112
c2
.0114
.0122
.0103
.0112
Drape
.0944
.1098
.0853
.1008
CALCULATIONLoads to be Balanced:—
For 8m span, balance 0.606 x permanent load in external span:For normal external bay 7 x 8.05 x .606 = 34.15 kN/mFor 8 m internal span, balance 0.5 of permanent loadi.e. 7 x 8.05 x 5 = 28.17 kN/m
For 7m span, balance 0.50x permanent load in external & internal span.For internal and external bay, 8 x 8.05 x .5 = 32.20kN
COMMENTSee page 1
For first internalbay, increasecables to allowfor increasedload at first
internal support
SAMPLE CALCULATION 2 Page 2
CALCULATION
~rom the loads to be balanced, the required prestress force =H > I 2
8xDrapeThis is the final force after
COMMENTinternal spanswould havesmaller prestressforce for same
losses, and assuming a loss of say 18% for 8m spans, and 16% for 7m spans, the initial prestress can be calculated, load balanced.The angle which the cable 'rotates' through is also required for the friction calculation. They are calculated from the because offormula for a parabola. larger drape.e.g. for the 8m end span O = Arctan (2 x 78.4/3268.4) x 2 + Arctan( 2 x 113.5/3931.6) x 2 = .2113 Radians
The following table shows the calculation results.
Span Load Drape Eff. Length Angle to C/L Angle C/L to Total angle(rad) end (Cumul)
8 mend span 34.15 .0944 7.2 .09615 .1135 .20965
8m 2nd span 28.17 .1098 7.2 .122 .122 .45365
8m 3rd span -do- -do- -do- -do- -do- .69765
8m last span as 1st .9073 rad
7m 1st span 32.2 .0853 6.3 .09838 .1182 .21658
7m 2nd span 32.2 .1008 6.3 .128 .128 .4726
7m 3rd span -do- -do- .7286
7m 4th span as 1st span .9452 rad
factor = e-0025 * 32-° - -06 * -9073 = .8742 i.e. 12.58 % losses
7m spans
The total loss due to friction and wobble is
i.e. 11.9 % losses.
factor = e-'0025 x 28-° - -06 x a9452 = .8810
CALCULATION8 m spans: end spanThe prestress required to balance 59 kN/m with a drape of .0951, and an effective length of parabola of 8 - 0.8
34.15 x 122
7.2 m is given by = 2344 kN8 x .0944
allowing an estimated 18% losses, P—, = 2859 kNIf cables of 15.2mm dia (ult. strength 260 kN) are stressed to 80% of ult. the no. of cables required
28590.8 x 260
= 13.7 say 14 cables
COMMENTAlthough oneshould calculatethe losses fromthe exponentialequation, it isquite acceptableto calculate theloss at the end,and interpolate.An even numberis better ifstressed fromboth ends.
8m spans: 2nd spanThe prestress required to balance 28.17 kN with drape of .1122 =
28.17 x 7.22
= 1627 kN8 x .1122
Allowing the same losses, Pinit( = 1984 kN. and no of cables = ,
1984208
= 9.5 cables
say 10.Assume that the cables in the end span are taken to 1.5 m past the 1st support, and that half the cables are stressedfrom each end, the diagrams on the next page may be drawn. Although strictly one should calculate the losses fromthe exponential equation it is quite acceptable to use a linear method.An even number is better if stressed from both ends.
Losses:8 m spans
The total loss due to friction and wobble is
SAMPLE CALCULATION 2 Page 3
.33 kN
SAMPLE CALCULATION 2 Page 4
7 m Spans Effects of frictionStressing forces in cables before other losses
SAMPLE CALCULATION 2 Page 5
CALCULATION
For 7m external span, force to balance 32.20 kN/m, with drape of .0853, and effective length of 6.3m.=1873 kNWith 16% losses , no of cables = 10.8 say 12For internal span, force to balance34.15 kN/m with drape of .1008, Pfma] = 1585 kN -> 1887 kN before lossesNo. of cables = 9.0 say 10
Take losses due to friction and pull-in as before (see first calculation)The results are diagrammed on pages 5 and 6
COMMENT
Diagrams suchas shown makeit easy to knowwhat the force atany section is.
Other Losses:Elastic Shortening8m spansAverage stress in end 9.5 m =(2590+2699)7(7 x .21 x 2)= 1.80 MPaIn Centre part ((1927+1949)/2 x3.52)+ (1949)x2.98)/6.5( 7 x .21) = 1.32 MPaLosses in end span =1.80 x 1987(26 x 2) = 6.85 MPa
Average loss over whole span = (1.80 x 9.5 x 2 + 1.32 x 13)/(2 x 32m)x 198726 = 6.11 MPaLoss per cable = 140 x 10"6 x 6.85 x 1000 kN = .96kN in end spans (x 4 = 3.8kN)
= " x6.11 x " = 0.86 kN in centre spans (x 10=8.6kN)Total in end spans 12.4 kN
Because thecables arestressed one at atime, theaverage loss is0.5 times theRatios of Emoduli x stress
7m spansAverage stress whole length =((2223 + 2313.6)x 8.5+(1925+1956)/2 x 2.87 +1956 x 1.63) /(14x8x.21)= 1.19 MPaIn end average force =((2223 + 2313.6)/2=2268.2—>1.35MPa
Losses 10 cables per cable = 1.19x 1987(26 x 2) x 140 x 10-6 x 1000 = .63 kN
Loss in 2 cables = 1.35x 140x 10'6x 198726/2=0.72 kN10 x .63 + 2 x .72 = 7.8kN totalTotal in centre span = 6.3 kNThe resultant forces after friction and elastic losses are shown in the diagram below.
SAMPLE CALCULATION 2 Page 6
CALCULATIONLong term lossesRelaxation 1.5% x 2 = 3%For 8m spans: end span 3% x (2578+2687)/2 kN = 79 kN
centre 3% x( (1918+1940)/2x3.52 +(1940 x 2.98/6.5))=1934kN x 3%=58kNFor 7m spans: end span 3% x 2252 = 67.6kN
centre 3% x 1950 = 58.5 kNCreep. (Same creep factor as 1st calc)If stressed at 3 days (common for prestressed flat slabs) and with a humidity ol 45%, the creep for a 210 slab,interpolating between 150 and 300 thick slabs given in the code (BS8110) gives a creep factor of 3.7Then loss = stress in concrete x ratio of moduli x 3.78m spans: End Section conc, stress = (2.578 MN + 2.687)/(2*7*.21) = 1.79MPa
Loss of steel stress = 1.79 * 3.7 * 198/26 = 50.5MPaPer cable 50.5 x .140(Area) = 7.06 kNCentre Section( (1.918+1.94)x 3.52+1.94x 2.98)/6.5/(7 x .21) x 198/26 x 3.7 = 37.1 MPaPer cable 37. 1x .14 = 5.19 kN Therefore average loss in long cables=(5.19x6.5+7.06x9.5)/16m = 6.30 kN
Total creep loss: End 7.06 x 4 + 6.3 x 10 = 91.2 kNCentre 6.3x10 = 63kN
7m spans End Section Conc stress after elastic losses(2215.1 + 2305.8)/(2x 8 x.21)= 1.345MPaCentre ((1918.7 + 1947.7)/2 x 2.87 + 1949.7x 1.63) /(4.5 x 8 x 2.1)= 1.154 MPaAverage(1.154 x 5.5 + 1.345 x 8.5)/14 = 1.27MPaLoss of steel stress : end 1.345 x 3.7 x 198/26= 37.9MPaPer cable 37.9 x .14 = 5.306 kNCentre loss of steel stress 1.27 x 3.7 x 198/26 = 35.78MPa
loss/cable = 35.7 x .14 = 5.0kNLosses in centre 10 x 5.0 = 50kNLosses in end section 12 x 5.306 = 63.7 kN
7m spans Relaxation end span 2 cables 3% x (373.4 + 388.6V2 = 11.43kNTotal 10 cables (1956x 11.37 + 1950 x 2.63)/14--> 1912.8 kN1912.8 x 3% = 57.4 kNTotal for 12 cables = 68.8 kN
Shrinkage as before: for 1 cable 10.26 kN
8m spans 14 cables —>143.6 kN10 cables —> 102.6 kN
7m spans 12 cables —> 123.1 kN10 cables —>102.6 kN
COMMENTThe code givesa factor of 2.0on the 1000hour value forclass 1 BS5896
Varies withinitial prestress,temp etc.Should strictlybe taken asstress at thecentroid of thecables.
Total loss
Cause
No of cables
Initial force(208kN/cable)
Elastic
Relaxation
Shrinkage
Creep
TOTAL
Percentage of init. forceloss after friction loss
%Loss due to friction
Total % loss of initial
8m End span
14
2912 kN
12.4 kN
79 kN
143.6
91.2
321.2
11.1
11.4
22.5
8m Centre
10
2080
8.6
58
102.6
63
232
11.1
7.45
18.5
7m End span
12
2496
7.8
67.6
123.1
63.7
262
10.5
11.08
21.6
7m Center
10
2080
6.3
58.5
102.6
50
217.4
10.4
8.31
18.7
The losses are somewhat lower than with the higher prestress but still appreciably higher than the 16% (or less) assumed by some commercialdesigners.From the figures for long-term loss, the final prestress can be calculated
SAMPLE CALCULATION 2 Page 7
Position
8m end span
8m 2nd span
7m end span
7m 2nd span
Initial prestress (after elastic losses)
2578 kN
2669
2687
1918
1940
1940
2215
2289.5
2306
1919
1948
Loss
311
311
223
223
255.6
-do-
-do-
210
210
Final prestress
2267 kN
2358
2376
1695
1717
1717
1959
2034
2050
1709
1738
ANALYSISThe slabs are analysed by the equivalent frame method, using Long's method to calculate the equivalent stiffness of the columns.Three loading cases are needed: Dead load on all spans, Line load on even spans, and live load on odd spans.These may be combined together with the load factors to give the desired bending moments diagrams.Any method of analysis may be used: moment distribution if a computer is not available, or a frame analysis if one is available.The hogging moments for the ultimate limit state may then be reduced by 15%, and the sagging moments increased accordingly to maintainequilibrium.The design moment is at the face of the column or capital, but the the total statically required moment is: W(L-2D/3) /8If a computer program is used, there is an advantage in arranging a node at 1/3 of the column or capital dimension from the centreline ofthe column, as the moment at that point will not be less than the moment given for statically required moment.Loads (As for previous calculation)
LOAD
Finishes
Partitions
Self. Wt
Total DL
Live load
Service(1.1DL + LL)
1.l0kPa
1.98
5.77
8.85
2.50
Ultimate(1.2DL + 1.6LL)
1.20kPa
2.16
6.30
9.66
4.00
Ultimate Dead Load(1.5 DL)
l.SkPa
2.7 kPa
7.87kPa
12.07kPa
Total loads on spans
8m Spans DL
8m spans LL
7m spans DL
7m spans LL
Service
61.95kn/m
17.5
70.8
20.0
Ultimate
67.62kN/m
28.0
77.28
32.0
Self only
36.75
36.75
42.0
42.0
NOTE: As the Ultimate Deadload case of 1.5 DL at 12.07 kPa is less than the Ultimate DL + LL of 13.66 kPa, it may be effectively ignored,although there may be some places where the moments could be fractionally higher. A construction loading at initial prestress may needto be calculated if the propping is not adequately arranged.
Loads due to prestressFor a parabola, the equivalent uniform load caused by a tension in the cable is given by w L2 /8 = P h where h is the drapefor the cables. The drapes can be read from the table on page 1The loads will not be uniform, but will be trapezoidal if the variation of prestress along the beam is taken into accountIn addition the moments due to eccentricity at the ends must be taken into account in the analysis if the cables are not exactly central. Inour case we have assumed a 20mm eccentricity upwards at the end'The moment at the end of the 8m spans will be 2267 x .02 =56.7 kNmThe moment at the end of the 7m spans will be 1959 x .02 = 49.0kNmThe loads given are for final prestress. Initial prestress (after friction and elastic losses) combined with deadload only may be a critical state,but it is probably sufficient to take the stresses due to final prestress and multiply them by an average factor.
SAMPLE CALCULATION 2 Page 8
Note: The forces at intermediate points are interpolated
Position
8m 1st. span L end
8m 1st start of sag
8m 1st . end of sag
8m 1st span RH end
8m 2nd span L end
-do- end of cable
-do- beyond end
8m 2nd RH end
7m 1st span LH
7m 1st: start of sag
7m 1st end of sag
7m 1st RH
7m 2nd LH end
7m 2nd end of cable
7m 2nd beyond end cable
7m 2nd Rh end
Prestress
2267
2272
2353
2358
2354
2376
1717
1717
1959
1966
2026
2034
2034
2050
1709
1738
Drape
.0096
.0944
.0944
.0114
.0122
.1098
.1098
.0122
.0086
.0853
.0853
.0103
.0122
.1008
.1008
.0122
Length
0.8
7.2
7.2
0.8
0.8
7.2
7.2
0.8
0.7
6.3
6.3
0.7
0.7
6.3
6.3
0.7
Lateral load
272.0 kN/m down
33.1kN/m up
34.28 -do-
336.0 kN/m down
359.6 down
40.26 up
29.1 up
261.8 kN/m down
275.1 down
33.80 up
34.83 up
342.0 down
405.1 down
41.65 up
34.72 up
346.2 kN/m down
272 kN/m 336 359.6 261.6
0.4
Loads on 8m spans due to final prestress
275.1 kN/m 342 405.1 346.2
Loads on 7m spans due to f i n a l prestress
Columns: Stiffness by Long's method (See Sample Calculation 1)7m spans Exterior: E (30 MPa)=26GPa
fe =.5 x .33 /12 = 1.125 x 10-3 m unitsKc = 4EI/LC
Kc = Kc /(1+.1272KC L/EhJc)Ke = Kc /(I + .1272 (4IcL/Lch
3c)
SAMPLE CALCULATION 2 Page 9
where L=8m, LC =3, h=.21. and c= .3Then equivalent stiffness = stiffness x .645orequiv. I = 725 x 10"6
8m spans interior : Ic = .54/12 = 5.208 x 10-3 , k = .0564c= 0.5Then equiv. stiff = stiff x .596 Equiv I = 3.10 x 10-3
7m exterior Ic = .3 x -53/12 = :- .125 x 10-3
c=0.5 k=.1272Then equiv stiff = stiff x .555 Equiv I = 1.73 x 10-3
7m interior I = 5.20?, x 10-3 . c=.5. k= .0564Then equiv. stiff = stiff x .628 Equiv I = 3.27 x 1-3
Slab Stiffness The moment of Inertia of the 8m spans is 7 x .213 /12 = .0054 mThe moment of inertia of the 7m spans is 8 x .213 /12 = .00617 m
The E is taken as the same as the columns, and the creep factor (for calculation deflections due to long term loads) as 3.5The results of the analysis are given below: Because the structure is symmetrical, only the first two spans are shown.
It should be realised that as the loads are calculated for an interior span, the first interior column band should be reinforced forapproximately a 7% greater load.
i.e. for this design, 1 extra prestressing cable, and some additional reinforcement over the columns.
MOMENTS
Position
8m 1st span Left
8m 1st span centre
8m 1st span right
8m 2nd span left
8m 2nd span centre
8m 2nd span right
7m 1st span left
7m 1 st span centre
7m 1st span right
7m 2nd span left
7m 2nd span centre
7m 2nd span right
ULT(1.2DL +1.6L1)
-22.9 kNm
367.0
-557.3
-476.8
215.5
-343.1
-40.8
293.7
-445.4
-400.9
185.9
-287.3
ULT(adjusted 15%)
-14.1
403.1
-441.7
-378.4
264.1
-264.7
-25.6
326.5
-352.0
-314.1
225.9
-217.5
Service(1.1DL +LL)
-17.0
301.4
-457.9
-396.2
170.9
-285.1
-31.1
240.8
-369.9
-333.1
146.6
-238.7
DL self only
- 6.0
134.4
-211.6
-183.3
67.5
-131.9
-10.5
106.8
-170.8
-154.1
56.8
-110.4
Final Prestress
+63.4
-99.6
167.9
148.1
-54.1
105.7
48.8
-69.7
125.1
118.6
-49.7
98.0
DEFLECTIONS (allowing 3.5 creep factor on permanent loads)Assuming an uncracked section (see later for correction)
Position
8m 1st span
8m 2nd span
7m 1st span
7m 2nd span
Service Load (1.1 DL +LL)
28.7 mm
9.0 mm
14.9 mm
5.0 mm
Final Prestress
-10.7 mm
- 3.7 mm
- 4.6 mm
- 2.0 mm
Net Deflection
18.0 mm
6.3 mm
10.3 mm
3.0 mm
Serviceability Limit State
For controlling cracking, it has been traditional to limit tensile stresses.For the sake of completeness, this will be done, but the incremental stressmethod is considered better.. (Use the program described in Appendix E)The permissible tensile stress is given as 0.45Ö fcor 2.46 MPa
4.O4 Mfti
\^
\T = 4.O4x75.2/2 \=151.9 kN ^
4.P4 \ /1 x 210 mm/
4.04 -i- 7.24 / /
= 75.2 mm
// \
t
752. mm
»
h = 21O mm
\•
V^ 4.0
7.24 MRi
Elastic interacted etraeeee- equivalent tension
SAMPLE CALCULATION 2 Page 10
Serviceability Tensile stress
Position
8m 1st L
8m 1st C
8m 1st R
8m 2nd L
8m 2nd C
8m 2nd R
7m 1st L
7m 1st C
7m 1st R
7m 2nd L
7m 2nd C
7m 2nd R
Net moment(service-prestress)
46.4
201.8
-290.0
-248.1
116.8
179.4
17.7
172.1
-244.8
-214.5
96.9
-140.7
Comp. kN
2267
2358
2376
2376
1717
1717
1959
2034
2050
2050
1709
1738
Stress(moment)
±0.90
3.93
5.64
4.83
2.27
3.49
0.30
2.93
4.16
3.65
1.65
2.39
Stress (comp)
1.54
1.57
1.60
1.60
1.17
1.17
1.17
1.19
1.21
1.21
1.02
1.03
Net tensilestress (MPa)
2.36
4.04*
3.23*
1.10
2.32
-
1.74
2.95*
2. 44
0.63
1.36
Z of section(M units)
.0514
.0588
Slab Area(M units)
1.47
1.68
It may be seen that 3 of the stresses are more than the Report 25 stresses, and reinforcement is required. The tension to be taken byreinforcement is calculated by simply taking the force from the tensile stress diagram as in the sketch at a stress of 0.58 fv It should benoted that it is assumed that the moments are evenly distributed across the section. This is clearly incorrect.151.9kN /(.58 x 450) ->582sq.mm/m ->Y12 @ 180
To calculate the steel required to control crackwidth by a more logical method, the formula in BS8007 is used. Moments are taken aboutthe level of the tension steel reinforcement, i.e.The required area of steel is given by calculating the tension required for a moment of M + P(d-h/2), and then reducing the tension by P.i.e. transferring the compressive force to the reinforcement level.. 75% of the total hogging moment and 55% of the total sagging momentshould be taken in the column band for the purpose of calculating crackwidths
The following table was calculated using a computer program for crackwidths to BS8007 It may be seen that areas are similar to the areasrequired for ultimate load, which supports the Report 25 stresses. SABS 0100 seems to give slightly higher areas if the tensile stress in theconcrete is taken into account. Hogging moments are taken as 75% of total in column bands, and 55% for sagging momentsThe result is slightly more reinforcement in the position which requires more than nominal reinforcement
Required area of reinforcement for cracking (0.15% = 315 sq.mm/m)
Position
8m 1st L
8m 1st C
8m 1st R
8m 2nd L
8m 2nd C
8m 2nd R
7m 1st L
7m 1st C
7m 1st R
7m 2nd L
7m 2nd C
7m 2nd R
Net. Moment(service-prestress)
46.4 kNm
201.8
-290.0
-248.1
116.8
-179.4
-17.7
172.1
-244.8
-214.5
96.9
-140.7
Moment /min band
9.9
31.7
62.!
-18.3
38.4
-
23.6
45.9
-13.3
26.4
PrestressMPa
1.54
1.57
1.60
1.17
1.17
1.17
1.19
1.21
1.21
1.02
1.03
Steel stressMPa
-
238
246
360
271
Bar Dia.
10@300
16 @ 200
12@ 120
nom
10@250
12@180
nom
d
180
166
Area(sq.mm/m)
nil
nil
992
946
nil
Nominal(297)
nil
Nominal
625
Nominal
Nominal
(Calculated using SABS0100 with 0.2mm crackwidth. See Appendix E) The areas are slightly greater than for the Report 25 Calculation(e.g Y16 at 200 or Y12 @ 1?0 as compared with Y12 at 180)
Ultimate Load Limit State.15% reduction of hogging moments ( with corresponding increase of sagging moments) is allowed and has been taken.The decompression moment, equal to the prestress x Z, is the moment required to reduce the compression on the extreme fibre to zero.If the applied moment (Ultimate dead + Live + prestress) is less than the decompression moment, no reinf. is required. If it is greater, anequivalent moment M' is calculated, by displacing the prestress to the level of the reinforcement, and adding a moment of P(d-h/2). Thetension calculated from this moment then has the prestress force deducted, to obtain the net tension on the reinforcement M7Jd-P. Therequired steel area, is then (M;/Jd-P)/fs
The ultimate M.R. of concrete = 4651 bd2 = 126 kNm for the 7m spans and 154 kNm for the 8m spans. None of the design moments
SAMPLE CALCULATION 2 Page 11
SAMPLE CALCULATION 2 Page 12
exceeds this. The lever arm as a proportion of effective depth is given approximately by
d-h/2 = 65mm for the 8m spans, and 49mm for the 7m spans.
The approximate moment /metre taken by Nominal reinforcement is 391 MPa x 0.75 d x .15% x .21m=
Required Area of reinforcement for Ultimate Limit State
16.8 kNmford=.182 mm15.3kNm/m for d=. 166
Position
8m 1st L
8m 1st C
8m 1st R
8m 2nd L
8m 2nd C
8m 2nd R
7m 1st L
7m 1st C
7m 1st R
7m 2nd L
7m 2nd C
7m 2nd R
Net. Moment(Ult-prestress)
49.3
303.5
-273.8
-230.3
210.0
-159.0
-23.2
256.8
-226.9
176.2
-119.5
Net Moment/m in band
(A)
10.6
47.7
-58.7
33.0
-34.1
4.3
35.3
-42.5
24.2
-22.4
Mom. /mP(d-h/2)
(B)
21.0
21.4
21.8
16.0
16.0
'2.0
12.2
12.4
10.5
10.6
DecomMom/mPrestress x Z
11.3
8.6
DesignMoment/m
(A+B)
—69.1
80.5
49.0
50.1
—
47.5
54.9
34.7
33.0
NetTension
kN/m
—
116.6
155.4
47.1
105.4
Bar Dia& spacing
Y10@250
Y10@250
Y10@200
Y10@250
Area(sq.mm/m)
Nom
298
398
Nom
121
Nom
Nom
270
Nom
Nom
The reinforcement areas required for ultimate load by this method are a bit smaller than those required for crack controlCompare the above calculation with the Report 25 method of calculating the reinforcement required for ultimate moments:-
This method does not take account of the moments due to prestress, but effectively assumes the cables are bonded, and that the momentsare taken over the full width of the section.At the first interior support, of the 8m spansf, = 2.358lMN/( 14 x 140. x 10-6) =1203.1 MPa (Effectivepeprestress)f pu = 260.5 MN/140. x 10-6=1860.7 MPa
-.Aps = 14x 140 x10-6 =l.96x 10-6
Effective depth of cables =.163m (see page 3 of calcs)From equation 52 of BS8110
for l/d =16/0.163 =98, f pb = 1203.1 + 61.2= 1264 MPa0.7 f = 1302 MPa therefore use 1264MPaFor 7m end spans , 1=28/2=14, and for 7m internal spans, 1=28/3=9.33
For prestress only, Tult = 2.478 MNThen N.A. depth = 2.478/(7 x .45 x 30) = 26.2 mm andlever arm = .163 -.026/2 = .150 mM.R. Prestress = .150x 2.478= 371.4 kNmActual ultimate moment 441.7kNm. Therefore additional steel is required.
d re inf=.182and dcable = .163Say approximately Tensionreinff= (441.7- 371.4)7371.4 x 2478kN = 469At 391 MPa (450/1.15), the area required = 1392 sq.mm over 3.5 m width = 343 sq. mm/m (Y10 @ 220 )Try Y10 @ 200 : Area = 1374 sq.mm Tensile capacity =537 kNSee diagram, Tension = 2478+537 kN = 3015kN. N.A depth = 3015/C7 - .45 x 30)=31.9mmMR =537x .16 6+ 2478 x .147 = 453kNm O.K.The other positions are checked in the table below0.15% =315sqmm/m-->Y10 @ 250
For end 8m spans (SABS 0100) 1=32/2=16For internal spans, 1= 32/3 = 10.67
(for 8m int 1295MPa, for 7m end 1274.for 7m internal f b = 1302MPa)
Position
8m 1st L
8m 1st C
8m 1st R
8m 2nd C
Ult. M
-14.1
403.1
-441.5
264.1
fpb x!40. x 10-6
x No. cables
2.478 MN
-do-
-do-
1.813 MN
Eff.d
.130
.163
-do-
-do-
N.A. depth
27mm
-do-
19.3mm
Lever arm
116
149
153
M.R.
287
371
371
279
DM
0
32
70.5
0
As reqd.
0(.15%
min)
Nom
Y10 @200
Nominal
SAMPLE CALCULATION 2 Pase 13
Position
8m 2nd R
7m 1st L
7m 1st C
7m 1st R
7m 2nd C
7m 2nd R
Ult. M
-264.7
- 25.6
326.5
-352.0
225.9
-217.5
fpb x!40. x 10-6
x No. cables
1.813 MN
2.138 MN
-do-
-do-
1.813MN
-do-
Eff.d
-do-
.130
.163
-do-
-do-
-do-
N.A. depth
19.8mm
-do-
16.8mm
Lever arm
120
153
154.6
M.R.
268
257
327.3
-do-
282
-do-
DM
0
25
0
As reqd.
Y10 @250
Y10@250
Y10@250
The reinforcement required for ultimate moments by this method are slightly less than required for cracking, and slightly less than the reinforcementrequired by the suggested method..
Ultimate MR of section = 537x .166 + 2473 x .147= 453 kNm
It is also desirable to check the ultimate load case with half of the cables in the end span removed, with DL + .25 LL. in the end spans only. TheMR due to half the number of cables may be taken as half the M.R. in the table above if Report 25 method is used, or the moments calculated forprestress may be halved and deducted from the moments for DL + .25LLThe second method will be used
Position
8m 1st L
8m 1st C
8m 1st R
7m 1st L
7m 1st C
7m 1st R
Ult. M(DL + .25LL)
- 8.2 kNm
172.8
-267.9
- 15.4
137.6
-190.0
PSMom/2
36.7
-49.8
83.9
27.0
-24.4
62.6
Moment/mPS (d-h/2)/2
10.7
10.7
4.3
4.3
4.3
UltMom/m
27.1
57.4
2.9
18.9
35.6
Net. M/mfor tension
37.8
68.1
7.2
23.2
39.9
Required Area(per m col band)
-
169. sq mm
622. sq mm
-
-
355. sq mm
Norn
Y12 at 180
Nom
It may be seen that the reinforcement for the 1.2DL + 1.6LL ultimate load case is adequate everywhere except the first interior support of the 8mspans
Deflections:The deflections in the table above were calculated for a non-cracked slabIf the sections are cracked, the Moment of Inertia would be 2.56 x 10-3' instead of the uncracked value of 5.4 x 10-3
Using the ACI formula , and taking moment at first cracking as the moment at which the tensile stress reaches 2MPa, the
cracking moment in the 8m 1st span is (1.54+ 2) x 7 x .212/6 = 182 kNm. Taking the design moments as the serviceability moments, and takingthe moments due to prestress into account, the moment at midspan of the 8 m 1st span is 201.8 kNm. i.e. cracked, and at the first internal support290 kNmThen Ie midspan = 4.13 xl0-3
I Support = 3.26 x 10-3 using the service load moments calculated aboveThe actual moment over the support is more concentrated, and there may be more cracking.The net equivalent M. of I. is then.85 x 4.13 + .15 x 3.26 =4.0The calculated deflection will then be 5.4/4.0 x the calculated one.Now the calculated deflection assumes that the slab acts as a band spanning in one direction, and neglects the span in the other direction.If one adds half the calculated deflection in the short direction to the calculated deflection in the long direction, this will probably be a reasonableestimate.
SAMPLE CALCULATION 2 Page 14
The total deflection is then (18.0 + 5.15) x 5.4/4.0 = 31mmThis is 1/223 of the short span, and may be acceptable if there are no rigid partitions. It should be noted that if there are reasons the slab might bemore cracked, e.g. temperature stresses or shrinkage, the deflections could be considerably greater.
Shear: The calculated ultimate shear at the first interior support ( at the face of the supports) is (from the computer calculations) 841.95 kN (ascompared to the simply supported load of 765.9 kN) . The shear assumed in the preliminary calculations was 860 kNThe design shear is 1.15 times this, or 968. kNAlternatively, from the code, Veff = Vt (1 + 1.5M/Vt x)
Mt, the moment transmitted to the column, is 226.0 kNm, and x is 1.5 + .18 x 1.5 (The column capital +1.5 slab depths)
then Veff = 1.227 x 841.95 =1033.4 kNFrom this may be deducted the vertical component of the prestressing cablesAt 1.06 m from the c/1 of column, the slope of the cables is .0529 from the properties of the parabola in the 8m spanvertical component = 4/14x 2267 x .0529 =34 kN x 2 = 68 kNIn the 7m span the slope is .0575Component = 5/12 x .0525 x 2056 kN =44.9 kN x 2 =89.8 kNTotal vert. component on 4 sides =157.8 kN and net design shear = 1033.4 - 157.8=875 kN
Area of reinforcement (Y10@200) in one direction, and Y12 @ 180 in the other. Average is 510 sq mm/mAverage % = 100(1860 x 4,5 x 140.x 10"6 + 510x1.71 x 10-6 x 450)/(1.71 x .21x 450) = 0.97%Permissible shear stress = .0.70 MPaActual shear stress = 851/(4 x 2.04 x .167) = .63 MPa. Therefore no shear reinf. reqdAt other columns, shear is less, and moment transferred to column is smaller. No shear reinforcement required.
One should also calculate that the width of slab at the external columns is adequate to transfer the moment, but with Long's method, the momenttransferred is quite small, and with the column capitals, it is not necessary.