Page 1: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

EN CMC-TC Processing Unit II DK 7320.100

Assembly, Installation and Operation

A29290 33 IT 74

Page 2: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Microsoft Windows is a registered trademark of Microsoft Corporation. Acrobat Reader is a registered trademark of Adobe Systems Incorporated.

Page 3: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Documentation Notes 1

CMC-TC Processing Unit II 3

EN Table of Contents 1 Documentation Notes .......................5

1.1 Associated Documents ....................... 5 1.2 CE Certification ................................... 5 1.3 Retention of the Documents ............... 5 1.4 Used Symbols ..................................... 5

2 Safety Notes.......................................5

3 Unit Description.................................6 3.1 Housing ............................................... 6 3.2 Power Supply ...................................... 6 3.3 Network Properties ............................. 6 3.4 Connectable Sensors.......................... 7 3.5 System Requirements......................... 7 3.6 Scope of Supply .................................. 7 3.7 Accessories......................................... 8 3.7.1 Required Accessories ......................... 8 3.7.2 Optional Accessories .......................... 9 3.8 Proper Use .......................................... 9

4 Assembly .........................................10 4.1 Assembly Notes ................................ 10 4.2 Assembling CMC-TC ........................ 10

5 Installation........................................11 5.1 Safety and Other Notes .................... 11 5.2 Connecting the Power Supply........... 11 5.3 Establishing the Network Connection11 5.4 Establishing the Sensor Connection. 12 5.4.1 Connecting the Sensor ..................... 12 5.5 Connecting the Alarm Relay ............. 12 5.6 Connecting the Voltage Extension Unit

.......................................................... 12 5.7 Connecting the Programming Interface

.......................................................... 13

6 Commissioning................................14

7 Operation .........................................16 7.1 Menu Structure.................................. 16 7.2 Operating Notes ................................ 17 7.3 Setting the Base Configuration ......... 17 7.3.1 Network Configuration ...................... 17 7.3.2 Configuring the Trap Receiver .......... 17 7.3.3 Configuring the SNMPv1 Access...... 17 7.3.4 Configuring the Read/Write Community

.......................................................... 18 7.3.5 Configuring the Authentication Traps 18 7.3.6 Changing the SNMP Version ............ 18 7.3.7 Configuring the NTP ......................... 18 7.3.8 Configuring the PPP ......................... 19 7.3.9 Configuring the Sending of E-Mails .. 20

7.3.10 Configuring the Syslog...................... 20 7.3.11 Configuring the System Name, Contact

and Location ..................................... 20 7.3.12 Configuring the Passwords............... 20 7.3.13 Changing the HTTP Port .................. 21 7.3.14 HTTPS (SSL) Function..................... 21 7.3.15 Configuring the FTP Access............. 21 7.3.16 SFTP Access .................................... 21 7.3.17 Configuring the Timeout Window ..... 21 7.3.18 Configuring the Telnet Access.......... 21 7.3.19 Activating the Restart........................ 22 7.3.20 Configuring the Connected Sensors. 22 7.3.21 General Configuration of the

Processing Unit................................. 22 7.3.22 Configuring the SMS Notification (GSM

Unit) .................................................. 22 7.3.23 Configuring the SMS Notification (ISDN

Unit) .................................................. 23 7.3.24 Entering the Telephone Numbers for

SMS Notification ............................... 23 7.3.25 Calling the CMC Information Page ... 23 7.3.26 Resetting All Settings in the Main Menu

23 7.3.27 Manual Search for Sensors .............. 23 7.4 Transferring Files Using the Serial

Interface............................................ 24 7.5 Saving Files Using the Serial Interface

.......................................................... 24 7.6 Access Using a Browser................... 24 7.6.1 Login ................................................. 24 7.6.2 Main Page View................................ 24 7.6.3 Main Settings .................................... 25 7.6.4 Configuring the Scheduler ................ 25 7.6.5 Configuring the GMS Unit................. 26 7.6.6 Configuring the ISDN Unit ................ 26 7.6.7 Configuring the Sending of E-Mails .. 26 7.6.8 Calling the Log File ........................... 27 7.6.9 Administration ................................... 27 7.7 Configuring the Sensors ................... 28 7.7.1 General Overview (Status Window) . 28 7.7.2 Sensor Overview .............................. 29 7.7.3 General Overview (Sensor

Configuration) ................................... 29 7.7.4 Configuring the Temperature Sensor 30 7.7.5 Configuring the Humidity Sensor...... 30 7.7.6 Configuring the Analogue Sensor Input

Module .............................................. 31 7.7.7 Configuring the Access Sensor ........ 32 7.7.8 Configuring the Vandalism Sensor ... 32 7.7.9 Configuring the Air Flow Sensor....... 33 7.7.10 Configuring the Smoke Detector ...... 33

Page 4: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

1 Documentation Notes

CMC-TC Processing Unit II 4

EN 7.7.11 Configuring the Motion Detector .......34 7.7.12 Configuring the Digital Input Module.34 7.7.13 Configuring the Digital Output Relay

Module...............................................35 7.7.14 Configuring Switching Combinations for

the Digital Relay Output Module .......36 7.7.15 Configuring the Voltage Monitor........36 7.7.16 Configuring the Voltage Monitoring for

the Voltage Monitor with IEC Switch Output................................................37

7.7.17 Configuring the Switch Output for the Voltage Monitor with IEC Switch Output 37

7.7.18 Configuring the Switching Combinations for the Voltage Monitor with IEC Switch Output .....................38

7.7.19 Configuring the Voltage Monitoring for the Voltage Monitor with 16 A Switch Output................................................38

7.7.20 Configuring the Switch Output for the Voltage Monitor with 16 A Switch Output................................................39

7.7.21 Configuring the Switching Combinations for the Voltage Monitor with 16 A Switch Output ....................39

7.7.22 Configuring the 48 V Voltage Monitor40 7.7.23 Configuring the Leakage Sensor.......40 7.7.24 Configuring the Acoustic Sensor.......41 7.7.25 Configuring the Fan Control System

(FCS).................................................42 7.7.26 Configuring the Fan Alarm System

(FAS) .................................................43 7.7.27 Wireless Sensors ..............................44 7.8 Access Using Telnet .........................44 7.8.1 Login Using Telnet ............................44 7.8.2 Telnet Main Menu..............................44 7.9 Performing a Software Update..........44 7.10 Error Messages.................................44 7.11 Structure of the MIB of the Processing

Unit ....................................................45 7.12 ActivePSM (4-way)............................47 7.12.1 Getting Acquainted with the Module

Connections ......................................47 7.12.2 Display and Operating Elements.......47 7.12.3 Displays.............................................48 7.12.4 Setup Menu for the Local Pushbutton

48 7.12.5 Connecting the ActivePSM to the CMC-

TC......................................................48 7.12.6 Monitoring Using a Browser ..............49 7.12.7 Configuring the ActivePSM ...............49 7.13 Metered PSM ....................................51 7.14 Monitoring the LCP and RTT I/O Unit51

7.15 Access Control Using an External Access File........................................ 51

7.16 Saving and Transferring Configuration Files................................................... 52

8 Maintenance and Cleaning............. 53 8.1.1 Cleaning............................................ 53

9 Storage and Disposal ..................... 53 9.1.1 Storage ............................................. 53 9.1.2 Disposal ............................................ 53

10 Changes from software version 2.6 54

10.1 Language selection for the browser interface ............................................ 54

10.2 Extended options under “Combinations”.................................. 54

10.3 New functions for the alarm and event log ..................................................... 54

10.4 Test functions for traps, e-mail, SMS and pings .......................................... 54

10.5 Scaling of the 4...20 mA sensor inputs of the input module ........................... 55

10.6 Server shutdown function ................. 55 10.7 Configuration of automatic door

opening ............................................. 56 10.8 Delayed alarms ................................. 57 10.9 Protection against cross-site scripting

(XSS)................................................. 57 11 Customer Service ........................... 58

12 Technical Specifications ................ 58

13 Technical Glossary ......................... 59

14 Declaration of Conformity .............. 60

Page 5: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Documentation Notes 1

CMC-TC Processing Unit II 5

EN 1 Documentation Notes The audience for this guide is the technical special-ists familiar with the assembly, installation and op-eration of the CMC-TC Processing Unit. • You should read this operating guide prior to the

commissioning and store the guide so it is readily accessible for subsequent use.

Rittal cannot accept any liability for damage and operational malfunctions that result from the non-observance of this guide. This guide applies to software level as of Version 2.50 of the Processing Unit II.

1.1 Associated Documents The guides for other CMC-TC components and their safety notes also apply together with this guide. This guide is also provided as a file on the accom-panying CD-ROM: German: 7320100VXXd.pdf English: 7320100VXXe.pdf To view the guide you require the Acrobat Reader program; Acrobat Reader can be downloaded from www.adobe.com

1.2 CE Certification The conformance declaration is contained in the appendix.

1.3 Retention of the Documents This guide and all associated documents are part of the product. They must be given to the operator of the unit and must be stored so they are available when needed.

1.4 Used Symbols The following safety and other notes are used in this guide:

Symbol for a handling instruction: • This bullet point indicates that you should perform

an action.

Safety and other notes:

Danger! Immediate danger to health and life!

Warning! Possible danger for the product and the environment!

Note! Useful information and special features.

2 Safety Notes Observe the subsequent general safety notes for the installation and operation of the unit: − Assembly and installation of the CMC-TC PU, in

particular for wiring the enclosures with mains power, may be performed only by a trained elec-trician. Other tasks associated with the CMC-TC PU, such as the assembly and installation of sys-tem components with tested standard connectors, and the operation and configuration of the CMC-TC PU may be performed only by instructed per-sonnel.

− Observe the valid regulations for the electrical installation for the country in which the unit is in-stalled and operated, and the national regulations for accident prevention. Also observe any com-pany-internal regulations (work, operating and safety regulations).

− Prior to working at the CMC-TC system, it must be disconnected from the power supply and pro-tected against being switched on again.

− Use only genuine or recommended parts and accessories (see Section 3.7 Accessories). The use of other parts can void the liability for any re-sulting consequences.

− Do not make any changes to the CMC-TC Proc-essing Unit that are not described in this guide or in the associated guides.

− The operational safety of the unit is guaranteed only for its approved use. The limit values stated in the technical specifications (see Chapter 12 Technical Specifications) may not be exceeded under any circumstances. In particular, this ap-plies to the permitted ambient temperature range and to the permitted IP protection category. When used with a higher required IP protection cate-gory, the Rittal CMC-TC must be installed in a housing or enclosure with a higher IP protection category.

− The operation of the CMC-TC system in direct contact with water, aggressive materials or in-flammable gases and vapours is prohibited.

− In addition to these general safety notes, also observe any special safety notes listed for the specific tasks in the individual sections.

Page 6: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

3 Unit Description

CMC-TC Processing Unit II 6

EN 3 Unit Description The Computer Multi Control Top Concept Process-ing Unit II (subsequently called CMC-TC PU) is an “intelligent” enclosure monitoring system. It is in-stalled in its own housing on the enclosure and uses the attached sensors in various forms to perform the complete physical monitoring of the enclosure, i.e. temperature, humidity, shock, smoke, voltage through to the complete cabinet locking and access control. All this information is transferred using SNMP to a management station where it can be administered. The supplied CD-ROM contains software (CMC-TC Manager) that can be used to monitor and adminis-ter one or more CMC-TC PUs. The associated cur-rent version of the CMC-TC Manager is located on www.rimatrix5.com.

3.1 Housing The CMC-TC Processing Unit is contained in its own housing that can be fastened with the supplied Velcro strips to the inner side of the side wall, to the punched sections with mounting flanges or to the shelves of the enclosure. Mounting units (see Sec-tion 3.7.1 Required Accessories) can also be used to install the housing.

I0I0I

1 2 3 4

1 2 3 4 5

Fig. 1 CMC-TC PU front side

Key 1 Acknowledge key (C key) 2 Status LED 3 Network LED 4 Serial interface (RS-232 connection) 5 Status LED for connected sensor units (Traffic LED)

Power

24 VDCmax. 2,5 AI0I0I

1P-I C21 243

1 2 3 4 5 6

Fig. 2 CMC-TC PU rear side

Key 1 Sensor units connections (1-4) 2 P-I²C connection 3 Alarm relay output (floating changeover contact) 4 Serial interface (IOIOI) 5 Network connection 6 Power supply connection (Power)

3.2 Power Supply The CMC-TC Processing Unit is supplied with power using an external power pack. The connec-tion cable for the external power pack is available as an accessory in various country variants. Choose the variant appropriate for the country-specific regu-lations. A selection of various connection cables is described in Section 3.7 Accessories. All connected sensors are supplied with voltage from the CMC-TC Processing Unit. The CMC-TC Processing Unit has an integrated alarm relay equipped with a floating change-over contact. It is used for the optical or acoustic alarming. There is also a connection with a serial interface that can be used for various sensor units and expansion units.

3.3 Network Properties The CMC-TC PU has an 10/100BaseT Ethernet network connection and supports the following pro-tocols: − RS232 serial interface: e.g. HyperTerminal − in the Ethernet network: e.g. TELNET − SNMPv1, compatible with popular management

systems − SNMPv3, − HTTP, HTTPS − FTP, SFTP − NTP (Network Time Protocol) − SSH (Secure Shell) − SSL 3.0 (Secure Socket Layer) − DHCP (Dynamic Host Configuration Protocol) Optionally, the CMC-TC PU can also communicate using a Master Unit or using an ISDN or GSM unit. Associated information is contained on the Rittal homepage (www.rittal.de) or in Catalogue 32. De-tailed documentation for the GSM and ISDN unit can also be found at www.rimatrix5.com.

Page 7: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Unit Description 3

CMC-TC Processing Unit II 7

EN The network connection is made using a suitable network cable with RJ-45 plug in the existing Ethernet network structure. The communication is made using a standard browser and is operating-system-independent. The number of Rittal CMC-TC Processing Units in the network is unlimited, provided adequate free IP addresses are available in the network. If this is not the case, up to ten CMC-TC PUs can be extended and administered using the Rittal CMC-TC Master. This distributed configuration allows you to also realise monitoring for enclosure suites without need-ing any large cabling effort. The network protocols are used for communication (password query, switching commands, status que-ries, and alarm signals) between the Rittal CMC-TC PU, the administrators and the users in the network (network/ internet/ intranet). The SNMP functionality is also independent of the operating system, only the network management protocol must support SNMP V1.0 or V3.0. In addi-tion, the Rittal CMC-TC PU supports the standard MIB II. The private MIB is part of the scope of sup-ply. Further information is provided on the supplied CD-ROM (CMC-TC PUII v1_1d.mib). The associ-ated current version of the MIB can be found in the internet at www.rimatrix5.com. The private MIB is required for integration in a build-ing management software system. It decodes the transferred trap messages to produce unambiguous messages.

3.4

Connectable Sensors Sensor Model No.

Temperature sensor DK 7320.500

Humidity sensor DK 7320.510

Analogue sensor input module "4 – 20 mA" DK 7320.520

Access sensor DK 7320.530

Vandalism sensor DK 7320.540

Airflow monitor DK 7320.550

Smoke alarm DK 7320.560

Motion sensor DK 7320.570

Digital input module DK 7320.580

Digital relay output module DK 7320.590

Voltage monitor DK 7320.600

Voltage monitor with switched output

DK 7320.610

Voltage monitor with 16 A switched output

DK 7320.611

48 V voltage monitor DK 7320.620

Leakage sensor DK 7320.630

Acoustic sensor DK 7320.640

Tab. 1 Connectable sensors

The sensors are interlinked with the CMC-TC I/O unit using category RJ12 patch cables.

3.5 System Requirements • Hardware: PC with serial interface and

10/100 Mbit network card • Software: Operating system (Linux or Windows)

Browser (IE 6.0 or equivalent)

3.6 Scope of Supply The unit will be delivered in a packaging unit in fully-assembled state. • Check the delivered components for complete-

ness. • Check that the packaging does not show any

signs of damage.

Page 8: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

3 Unit Description

CMC-TC Processing Unit II 8

EN

Quantity Designation

1 CMC-TC Processing Unit with net-work interface RJ-45 socket (10/100 BaseT)

2 Self-adhesive Velcro fasteners 90 x 15 mm

1 CD-ROM with software and operat-ing manual

1 Checklist for commissioning in German/English

Tab. 2 Scope of supply

3.7

Accessories

3.7.1 Required Accessories Depending on the country-specific specifications, you require an appropriate connection cable for the power pack of the CMC-TC PU.

Acces-sories Designation

Packs of

Re-quired

Model No.

Installation power pack 24 V IEC 100-230 V AC, UL approval, 3 A SELV

1 7320.425

Power supply

Installation power pack 24 V IEC 48 V DC 1

Yes, depend-ing on power supply

7320.435

Connection cable IEC connector Country version D

1 7200.210

Connection cable IEC connector Country version GB

1

7200.211

Connection cable IEC connector Country version F/B

1

7200.210

Connection cable IEC connector Country version CH

1

7200.213

Connection cable IEC connector Country version USA/CDN, UL approval FT1/VW1

1

7200.214

Connec-tion cable for power pack

Extension cable IEC connector and socket

1

Yes, once for power pack

7200.215

1 U mounting unit

1 7320.440 Assem-bly

1 U single mounting unit with strain relief

1 Optional 7320.450

Program-ming cable

Programming cable D-Sub 9 to RJ 11

1 Yes, max. 1 7200.221

Exten-sion

Extension unit – voltage

1 Optional, max. 2 7200.520

Tab. 3 Required accessories

Page 9: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Unit Description 3

CMC-TC Processing Unit II 9

EN 3.7.2 Optional Accessories

Accessories Max. required number of items

Model No.

I/O Unit 4 DK 7320.210

Wireless I/O Unit 4 DK 7320.240

Access Unit 4 DK 7320.220

Climate Unit 4 DK 7320.230

Fan Control Sys-tem (FCS) 4 DK 7320.810

Fan Control Sys-tem (FCS) 4 DK 7858.488

Automatic Door opening control Unit

4 DK 7320.790

RTT I/O Unit 4 DK 3124.200

LCP 4 DK 3301.210

LCP 4 DK 3301.230

Active PSM 4-way 4x4 DK 7856.200

Active PSM 8-way 4x4 DK 7856.201

Active PSM 8-way (19") 4x4 DK 7200.001

Active PSM 6-way 4x4 DK 7856.203

Active PSM 6-way 4x4 DK 7856.204

PSM busbar with measurement 4 DK 7856.016

PSM measuring module 4 DK 7856.019

PCU 4x4 DK 7200.001

CMC-TC Display Unit II 1 DK 7320.491

CMC-TC GSM Unit 1 DK 7320.820

CMCTC ISDN Unit 1 DK 7320.830

Extension cable RJ12; 5.0 m - DK 7200.450

Extension cable RJ12; 1.0 m - DK 7320.814

Extension cable RJ45; 0.5 m DK 7320.470

Extension cable RJ45; 2.0 m DK 7320.472

Extension cable RJ45; 5.0 m DK 7320.475

Extension cable RJ45; 10.0 m DK 7320.481

Tab. 4 Optional accessories

3.8 Proper Use The Rittal CMC-TC PUII serves as an enclosure monitoring system for the monitoring and admini-stration of various enclosure parameters. A use different from that described here is consid-ered to be an improper use. Rittal cannot accept any liability for damage resulting from the improper use or the non-observance of this guide. The guides for the used accessories may apply.

Page 10: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

4 Assembly

CMC-TC Processing Unit II 10

EN 4 Assembly 4.1 Assembly Notes Install the CMC-TC PU in an enclosure or in a suit-able housing system so that it also has additional protection from external effects. Also consider the permitted ambient temperature and humidity opera-tional areas and the application-related required IP degree of protection (see Chapter 12, page 58).

4.2 Assembling CMC-TC

Fig. 3 Assembly with the mounting module

• Move the CMC-TC PU on the retaining plate of the mounting module. Ensure that the retaining plate sits between the guide rails of the CMC-TC PU.

Fig. 4 Assembly with Velcro fasteners

• Take the self-adhesive Velcro fasteners from the supplied accessories and remove the protective foil from the Velcro fasteners.

• Ensure that the adhesion surfaces are free from grease and dust.

• Attach the Velcro fasteners to the housing of the CMC-TC PU and position the CMC-TC PU at the required attachment location.

2,4

1,53

Fig. 5 Assembly with 1 U mounting unit

1. Remove the two upper screws of the trim piece. 2. Remove the trim piece. 3. Move the CMC-TC PU on the retaining plate of

the mounting unit. Ensure that the retaining plate sits between the guide rails of the CMC-TC PU.

4. Replace the trim piece on the mounting unit. 5. Screw the trim piece back on the 1 U mounting

unit.

Page 11: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Installation 5

CMC-TC Processing Unit II 11

EN 5 Installation

Danger! The assembly and installation may be performed only by trained specialists.

5.1 Safety and Other Notes − The Rittal CMC-TC Processing Unit may be oper-

ated only with connected protective earth conduc-tor. The protective earth conductor connection is made by plugging in the IEC connection cable. This requires that the IEC connection cable at the power supply side be connected with the protec-tive earth conductor.

− The electrical connection voltage and frequency must conform to the rated values specified at the rear of the housing and in the technical specifica-tions (see page 58).

− Before commencing work on the Rittal CMC-TC PU, it must be disconnected from the mains power supply and protected against being re-connected.

− Protect the connection cables using cable ties on the used housing or enclosure.

− To prevent unnecessary cable losses, the used cable lengths must not exceed the lengths speci-fied in the technical specifications (see Chapter 12, page 58).

5.2 Connecting the Power Supply

Power

24 VDCmax. 2,5 AI0I0I

1P-I C21 243

1

Fig. 6 Connecting the power supply

Key 1 Power supply connection You must connect the CMC-TC PU to the power supply using the power packs described in Section 3.7.1 Required Accessories. • Insert the power pack plug in the "Power" socket

of the CMC-TC PU. Ensure that the marking arrow points to the “Power” socket designation.

The plug latches itself. After being connected to the power supply, the CMC-TC PU automatically begins a boot task that takes approximately three minutes. Once it has completed, the alarm LED illuminates green. To remove the connection plug, pull back the move-able ring on the plug and then pull the complete plug out of the socket.

2

3 1

Fig. 7 Pin assignment (plug, from the front)

Key 1 Pin 1: Gnd 2 Pin 2: not assigned 3 Pin 3: +24 V

5.3 Establishing the Network Connec-tion

Power

24 VDCmax. 2,5 AI0I0I

1P-I C21 243

1

Fig. 8 Establishing the network connection

Key 1 Network connection • Use the RJ45 network cable to connect the CMC-

TC PU with the existing Ethernet network struc-ture.

I0I0I

1 2 3 4

1

Fig. 9 Checking the network connection

Key 1 Network LED The network connection is established as soon as the Link LED lights green or orange. In addition, the Link LED starts to flash when data exchange occurs over the network: Green: 10 Mbit transmission Orange: 100 Mbit transmission

5.4

Page 12: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

5 Installation

CMC-TC Processing Unit II 12

EN Establishing the Sensor Connec-tion

5.4.1 Connecting the Sensor

Power

24 VDCmax. 2,5 AI0I0I

1P-I C21 243

1

Fig. 10 Establishing the sensor connection

Key 1 Sensor units connections (1-4) • Insert the connection plug of the sensor units in

any of the four connections. The connected sensors will be detected automati-cally by the CMC-TC PU.

I0I0I

1 2 3 4

1 2 3

Fig. 11 Checking the sensor connection

Key 1 Acknowledge key (C key) 2 Status LED 3 Status LEDs for connected sensor units When the sensors are connected and detected, a signal sounds and the Status LED of the connection flashes orange. • Press the C key to confirm the connection of the

sensor. The acoustic signal is terminated and the Status LED changes from orange to green. The CMC-TC Processing Unit continually polls the ports of the sensor units. Configuration changes to sensors are detected and reported automatically. The indication is made by the acoustic signal and by the Status LEDs.

5.5

Connecting the Alarm Relay The alarm relay is connected using the floating changeover contact.

Warning! Damage danger! Observe the technical specification of the alarm relay contained in the tech-nical data. If these details are not ob-served, the alarm relay can be dam-aged.

Power

24 VDCmax. 2,5 AI0I0I

1P-I C21 243

1

Fig. 12 Connecting the alarm relay

Key 1 Alarm relay output (floating changeover contact) • Connect the alarm relay with the RJ-12 sockets

using RJ-12 connectors. After the connection, you must configure the alarm relay using the software (see 7.3.21 General Con-figuration of the Processing Unit). The internal cir-cuitry of the alarm relay is shown below:

Fig. 13 Power connection of the alarm relay

5.6 Connecting the Voltage Extension Unit

You can use the P-I²C connection (RJ-45 socket) to integrate a maximum of two voltage extension units (3-phase, DK 7200.520) in the CMC-TC PU. Further information is contained in the operating instructions of the voltage extension unit.

Page 13: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Commissioning 6

CMC-TC Processing Unit II 13

EN

Power

24 VDCmax. 2,5 AI0I0I

1P-I C21 243

1

Fig. 14 P-I2C connection

Key 1 Voltage extension unit connection (P-I²C connec-

tion) • Use an RJ45 cable to establish the connection

between the voltage extension unit and the P-I²C connection of the Processing Unit.

• Set the DIP switch on the voltage extension unit as follows to address the voltage extension unit:

Switch setting Addressing

DIP switch at 1

First connected expansion unit

DIP switch at 2 Second connected expansion unit

Tab. 5 Addressing

5.7 Connecting the Programming Inter-face

If you want to configure the CMC-TC PU, for exam-ple, using a notebook, you can connect both devices with each other using the serial interface. The RS-232 interface of the CMC-TC PU is pro-vided as RJ-10 front socket.

I0I0I

1 2 3 4

1

Fig. 15 RS-232 connection

Key 1 Serial interface (RS-232 connection as RJ-10 front

socket) • Connect the programming cable (DK 7200.221)

with the RJ-10 front socket and with the serial in-terface of your PC.

Page 14: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

6 Commissioning

CMC-TC Processing Unit II 14

EN 6 Commissioning Once you have assembled the CMC-TC PU and installed all connections, you must now configure it. You can do this using either the serial interface (see Section 5.7 Connecting the Programming Interface), the network connection with an internet browser (see Section 7.6 Access Using a Browser) or Telnet (see Section 7.8 Access Using Telnet). You must first establish the connection to the CMC-TC PU. This is shown in the following sections using the example of the “HyperTerminal” terminal pro-gram that is part of the Microsoft Windows 2000 operating system. The process is similar for other operating systems. To start “HyperTerminal”, click <Programs> - <Ac-cessories> - <Communication> - <HyperTerminal>

Fig. 16 Enter name and select connection

• Enter name • Assign symbol for connection

Fig. 17 Establish connection

• Select connection via COM Port • Click “OK”

The properties of the selected COM ports must be specified once.

Fig. 18 COM port properties

• Enter the following parameters: Transmission rate: 9600 bits per second Data bits: 8 Parity: None Stop bits: 1 Protocol: None To ensure that the data is transferred without error, the standard level range must be observed for the RS-232 interface. The login window for HyperTerminal appears.

Fig. 19 Login

You must enter your login name (CMC-TC login) and your password here. As supplied, “cmc” is set as default setting for both entries. • Enter your login name (CMC-TC login) and your

password. You can change the password subsequently (see Section 7.3.12 Configuring the Passwords).

Page 15: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 15

EN

Fig. 20 HyperTerminal start window

If you have been able to establish the connection to the CMC-TC PU, the HyperTerminal configuration window with the CMC-TC PU configuration menu appears. You can now set up the CMC-TC PU for your local conditions.

Page 16: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 16

EN 7 Operation 7.1 Menu Structure The terminal program menu has the following struc-ture:

1 Network Configuration

1.1 IP Configuration 1.4.2 IP Addr. CMC (DialIn)

1.1.1 IP Address 1.4.3 IP Addr. Client (DialIn)

1.1.2 IP Subnet Mask 1.4.4 Username (DialIn)

1.1.3 IP Def. Gateway 1.4.5 Password (DialIn)

1.1.4 Enable/Disable DHCP 1.4.6 Callback No. (DialIn)

1.1.5 Settings Ethernet Port 1.4.7 Enable PPP (Dialout)

1.2 SNMP Configuration 1.4.8 IP Addr. CMC (Dialout)

1.2.1 Trap Receiver Configura-tion

1.4.9 IP Addr. Client (Dialout)

1.2.1.1 IP Trap Receiver 1.4.A Username (Dialout)

1.2.1.2 Enable/Disable 1.4.B Password (Dialout)

1.2.1.3 IP Trap Receiver 1.4.C Phone Number (Dialout)

1.2.1.4 Enable/Disable 1.4.D Modem Type

1.2.1.5 IP Trap Receiver 1.4.E MSN (for ISDN)

1.2.1.6 Enable/Disable 1.4.F Modem Baud Rate

1.2.1.7 IP Trap Receiver 1.5 SMTP (email) Configuration

1.2.1.8 Enable/Disable 1.5.1 IP Addr. SMTP Server

1.2.2 SNMPv1 IP Access 1.5.2 SMTP Server Authentica-tion

1.2.2.1 SNMPv1 Manager 1.5.3 Username SMTP Server

1.2.2.2 SNMPv1 Manager 1.5.4 Password SMTP Server

1.2.2.3 SNMPv1 Manager 1.5.5 E-Mail Sender Name

1.2.2.4 SNMPv1 Manager 1.5.6 E-Mail Reply to

1.2.2.5 SNMPv1 Manager 1.5.7 E-Mail upon Unit Mes-sages

1.2.2.6 SNMPv1 Manager 1.5.8 E-Mail Address

1.2.2.7 SNMPv1 Manager 1.5.8.1 E-Mail Address

1.2.2.8 SNMPv1 Manager 1.5.8.2 E-Mail Address

1.2.2.9 SNMPv1 Manager 1.5.8.3 E-Mail Address

1.2.2.A SNMPv1 Manager 1.5.8.4 E-Mail Address

1.2.2.B SNMPv1 Manager 1.6 Syslog Configuration

1.2.2.C SNMPv1 Manager 1.6.1 IP Addr. Syslog Server

1.2.3 Read Community 1.6.2 IP Addr. Syslog Server

1.2.4 Write Community 1.6.3 Syslog Facility

1.2.5 Enable Auth. Traps 1.6.4 Enable Syslog

1.2.6 Change SNMP Version 1.7 System Name

1.2.7 Default SNMPv3 User Name

1.8 System Contact

1.2.8 Default SNMPv3 Pass-word

1.9 System Location

1.2.9 Confirm SNMPv3 us-mUser/Passw

1.3 NTP Configuration 1.A Security

1.3.1 Enable NTP 1.A.1 Change Password User ´cmc´

1.3.2 IP Addr. NTP Server 1 1.A.2 Change Password User ´admin´

1.3.3 IP Addr. NTP Server 2 1.A.3 Change HTTP Port

1.3.4 NTP Offset to UTC 1.A.4 Enable SSL

1.3.5 NTP Update Frequency (h) 1.A.5 Change HTTPs Port

1.3.6 Dayl. Saving Time, Begin 1.B Enable FTP

1.3.7 Dayl. Saving Time, End 1.C Cons./Teln. Timeout Minu-tes

1.4 PPP Configuration 1.D Enable/Disable Telnet

1.4.1 Enable PPP (DialIn) 1.E Activate Actual Values

2 Sensor Units

2.1 e.g. IO Unit 1:´CMC-TC-IOU´

2.1.1.C Trap Receiver 4/Log

2.1.1 e.g. Temperature Sensor 2.1.1.D Alarm Reset

2.1.1.1 Status 2.1.1.E Send SMS

2.1.1.2 Value 2.1.1.F Send E-Mail

2.1.1.3 Setpoint High 2.1.2 e.g. Humidity Sensor

2.1.1.4 Setpoint Warning 2.1.3 not available

2.1.1.5 Setpoint Low 2.1.4 not available

2.1.1.6 Message Text 2.1.5 Name Sensor Unit

2.1.1.7 Alarm Relay 2.1.4 Status of Unit

2.1.1.8 Beeper 2.2 Unit 2 not available

2.1.1.9 Trap Receiver 1 2.3 Unit 3 not available

2.1.1.A Trap Receiver 2 2.4 Unit 4 not available

2.1.1.B Trap Receiver 3

3 General Configuration

3.1 Temperature Unit 3.9.2 SMS Service Number

3.2 Beeper 3.9.3 ISDN MSN

3.3 Quit Alarm Relay 3.9.4 ISDN Pre-Dial Number

3.4 Alarm Relay Options 3.9.5 ISDN Command

3.5 Web Access 3.9.6 SMS upon Unit Message

3.6 Actual Date 3.9.7 SMS Phone Numbers

3.7 Actual Time 3.9.7.1 SMS Phone Number

3.8 Check Link 3.9.7.2 SMS Phone Number

3.9 SMS Configuration 3.9.7.3 SMS Phone Number

3.9.1 PIN GSM-Card 3.9.7.4 SMS Phone Number

4 Info Page

5 Default, New Config. Of Sensor Units, File Transfer

5.1 Set General Configuration to Default

5.3.1 Send File to CMC

5.2 Sensor Unit Detection 5.3.2 Receive File from CMC

5.3 Serial File Transfer (ZMo-dem)

Fig. 21 Menu structure

Page 17: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 17

EN

7.2 Operating Notes The following sections list as tables all the configu-ration parameters of the CMC-TC. The basic opera-tion is always the same: • Navigate within the menu structure using the

“up” ↑ and “down” ↓ arrow keys. • Scroll in fields with several predefined values

using the “left” ← and “right” → arrow keys. • Enter the required data in fields for text and nu-

meric information from the keyboard. • You can use the “Esc” key to cancel the inputs. • Confirm all inputs with the “Return” or “Enter” key.

7.3 Setting the Base Configuration The base configuration requires only the setting of the network configuration, the alarm relay and the trap receiver. You can make further settings using a browser or Telnet.

7.3.1 Network Configuration You can use this menu to change your network settings.

Navigation

Main menu – 1 Network Configuration – 1 IP Configuration

Parameter Explanation

IP Address Enter your IP address (factory setting 192.168.0.190)

IP Subnet Mask

Enter your IP subnet mask address (factory setting 255.255.255.0)

IP Def. Gate-way

Enter the IP for the router (fac-tory setting 0.0.0.0)

Enable/Disable DHCP

Set whether the CMC-TC PU should obtain the IP address automatically: Enable or disable the function

Settings Ethernet Port

Configure the network interface of the CMC-TC PU on your network. Possible settings: Auto, 100/Half, 100/Full, 10/Half, 10/Full

Restart the system to save the settings:

Navigation

Main menu – 1 Network Configuration – D Acti-vate Actual Values

Parameter Explanation

Activate Actual Values

Activate new values: Select “Yes” and press the “Return” key to perform a restart.

If DHCP is enabled, then during the restart, a con-nection will be established to a DHCP server pre-sent in the network; an IP address is obtained from this server. If no IP address can be obtained from the DHCP server, the last valid IP address or default address will be used. A restart is also necessary when the DHCP is deactivated.

7.3.2 Configuring the Trap Receiver To receive messages and information, so-called trap messages, from the CMC-TC PU, the IP address of the console on which a management software sys-tem (e.g. HP OpenView) is installed must be en-tered. The management software must support the SNMP protocol.

Navigation

Main menu – 1 Network Configuration – 2 SNMP Configuration – 1 Trap Receiver Configuration

Parameter Explanation

IP Trap Re-ceiver

Enter the IP address of the receiver of the messages (fac-tory setting 0.0.0.0).

Enable/Disable Enable or disable the receiving at the preceding receiver.

Enter any additional recipients (maximum four) in the lines provided below.

7.3.3 Configuring the SNMPv1 Access Management software that supports SNMP (e.g. HP OpenView or CMC-TC Manager) can access the CMC-TC PU via the network. To restrict the access, you can permit the access for required IP addresses (maximum 12). The access is then blocked for all other IP addresses that have not been entered. If no IP address has been entered, every management software system in the network has access to the CMC-TC PU.

Page 18: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 18

EN Navigation

Main menu – 1 Network Configuration – 2 SNMPv1 IP Access

Parameter Explanation

SNMPv1 man-ager

Set the IP address for the PC with the SNMP management software that is to have access to the CMC-TC PU.

7.3.4 Configuring the Read/Write Com-munity

To make the settings for a management software system on the CMC-TC, you must set the commu-nity of the Processing Unit and the management software.

Navigation

Main menu – 1 Network Configuration – 2 SNMP Configuration – 3 Read Community / 4 Write Community

Parameter Explanation

3 Read Com-munity

Set the read community for the trap handling. Press the “Back-space” key to clear the factory setting and then enter the new name.

4 Write Com-munity

Set the write community for the trap handling. Press the “Back-space” key to clear the factory setting and then enter the new name.

7.3.5 Configuring the Authentication Traps

For an SNMP request (read or write) to the PUII with invalid Read/Write Community, the PUII sends an authentication trap to all activated trap receivers.

Navigation

Main menu – 1 Network Configuration – 2 SNMP Configuration – 5 Enable Auth. Traps

Parameter Explanation

Enable Auth. Traps

Enable or disable FTP with the ← and → arrow keys.

7.3.6 Changing the SNMP Version As of software version 2.45, the Processing Unit II supports two types of SNMP. SNMPv1 and SNMPv3 are available. SNMPv3 provides a higher security functionality than SNMPv1. SNMPv3 re-quires an authentication.

Navigation

Main menu – 1 Network Configuration – 2 SNMP Configuration

Parameter Explanation

6 Change SNMP Version

Set the SNMPv1 and SNMPv3 using the ← and → arrow keys.

7 Default SNMPv3 User Name

Set the user name for SNMPv3 access ´cmc´ (max. 20 charac-ters). Press the “Backspace” key to clear the factory setting and then enter the password.

8 Default SNMPv3 Password

Set the password for the SNMPv3 access ´cmc´ (max. 20 characters). Press the “Backspace” key to clear the factory setting and then enter the password.

Confirm SNMPv3 us-mUser/Passw

Confirm the SNMPv3 authenti-cation using the ← and → ar-row keys.

7.3.7 Configuring the NTP The Network Time Protocol (NTP) is a standard for the time synchronisation of the internal clock using the network. The NTP function synchronises the local internal clock of the CMC-TC using external time signals obtained from an NTP server. To use this function in the CMC-TC, the network connection to an NTP server must be possible. The IP addresses for two NTP servers can be entered (primary and secon-dary server). The time information from the NTP server is based on the coordinated world time (UTC) as reference time. The times in the various time zones of the world are derived from this time. Con-sequently, the current time zone must be set in the CMC-TC menu. The current date and the current time are then displayed with the correct value taking account of the time zone and the daylight saving status. Because the daylight saving begin and end in the various time zones differ, these two values can also be set in the CMC-TC.

Page 19: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 19

EN Navigation

Main menu – 1 Network Configuration – 3 NTP Configuration

Parameter Explanation

1 Enable NTP Enable or disable NTP with the ← and → arrow keys.

2 IP Addr. NTP Server 1

Set the first IP address of the NTP server. Press the “Back-space” key to clear the factory setting and then enter the IP address of the first NTP server.

3 IP Addr. NTP Server 2

Set the second IP address of the NTP server. Press the “Backspace” key to clear the factory setting and then enter the IP address of the second NTP server.

4 NTP Offset to UTC

Set the time zone of your coun-try using the ← and → arrow keys.

5 NTP Update Frequency (h)

Set the interval how often the Processing Unit should query the NTP server for the current date and time. The values must be set in hours. Press the “Backspace” key to clear the factory setting and then enter the interval time.

6 Dayl. Saving Time, Begin

Enter the begin of the daylight saving time. Press the “Backspace” key to clear the previous input and then enter the new data in the following format. m = month (1...12) n = week of the month (1 = first week, 5 = last week of the month) d = day (0 = Sunday, 6 = Saturday)

7 Dayl. Saving Time, End

Enter the end of the daylight saving time. Press the “Backspace” key to clear the previous input and then enter the new data in the following format. m = month (1...12) n = week of the month (1 = first week, 5 = last week of the month) d = day (0 = Sunday, 6 = Saturday)

7.3.8 Configuring the PPP You can administer the CMC-TC PU from a remote location using an analogue modem. To do this, con-nect the modem to the serial interface of the Proc-essing Unit.

Navigation

Main menu – 1 Network Configuration – 4 PPP Configuration

Parameter Explanation

1 Enable PPP (DialIn)

Enable or disable PPP with the ← and → arrow keys.

2 IP Addr. CMC (DialIn)

Set the IP address of the Proc-essing Unit to establish a con-nection from a client to the Processing Unit.

3 IP Addr. Client (DialIn)

Set the IP address of the client to dial-in on the Processing Unit.

4 Username (DialIn)

Set an arbitrary user name for the login on the Processing Unit (max. 20 characters).

5 Password (DialIn)

Set an arbitrary password for the login on the Processing Unit (max. 20 characters).

6 Callback No. (DialIn)

Enter the telephone number to which the Processing Unit should call back.

7 Enable PPP (Dialout)

Enable or disable PPP with the ← and → arrow keys.

8 IP Addr. CMC (Dialout)

Enter the IP address of the Processing Unit for the dial-in on the client.

9 IP Addr. Client (Dialout)

Enter the IP address of the client for the dial-in on the cli-ent.

A Username (Dialout)

Enter a user name as authenti-cation on the client. Note: The user name must be entered as user account in the client (max. 20 characters).

B Password (Dialout)

Enter a password as authenti-cation on the client. Note: The password must be identical with the password of the user account (max. 20 characters).

C Phone Number (Dialout)

Enter the telephone number that the Processing Unit should call in order to send a trap.

D Modem Type

Select the modem type: Ana-logue, ISDN or GSM (when a

Page 20: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 20

EN GSM unit is used as modem, ensure that the SIM card does not have a PIN number).

E MSN (for ISDN)

When an ISDN modem is used, the MSN number must be en-tered.

F Modem Baud Rate

Bit rate with which the serial interface communicates with the external modem (for an analogue modem).

7.3.9 Configuring the Sending of E-Mails As of software version 2.45, the CMC-TC PUII can send alarm messages as an e-mail via an SMTP server.

Navigation

Main menu – 1 Network Configuration – 5 SMTP (E-mail) Configuration

Parameter Explanation

1 IP Addr. SMTP Server

Enter the IP address of the SMTP server.

2 SMTP Server Authentication

Enable (Yes) or disable (No) for an authentication on the SMTP server using the ← and → ar-row keys.

3 Username SMTP Server

Enter the user name for the SMTP server.

4 Password SMTP Server

Enter the password for the SMTP server.

5 E-Mail Sen-der Name

Enter the sender address of the PUII.

6 E-Mail Reply to

If a user responds to this alarm message, the response mail will be sent to the entered address.

7 E-Mail upon Unit Messages

For a timeout, etc. on a unit, an e-mail can be sent as notifica-tion. Set "Yes" or "No" using the ← and → arrow keys.

8 E-Mail Ad-dress

Enter up to four different e-mail addresses.

7.3.10 Configuring the Syslog Navigation

Main menu – 1 Network Configuration – 6 Syslog Configuration

Parameter Explanation

1 IP Addr. Syslog Server

Syslog Server 1 to which all alarm and event logs are sent.

2 IP Addr. Syslog Server

Syslog Server 2 to which all alarm and event logs are sent.

3 Syslog Facil-ity

Specifies the origin of the log message (Local0..Local7). Used for differentiation when several systems are used.

4 Enable Sys-log

Switches the Syslog function on (enabled) or off (disabled). The default value is "disabled".

7.3.11 Configuring the System Name, Contact and Location

A unique name, a contact address (e-mail) and a location can be entered for the Processing Unit.

Navigation

Main menu – 1 Network Configuration

Parameter Explanation

6 System Na-me

The Processing Unit can be assigned any name. Press the “Backspace” key to clear the factory setting and then enter the new name.

7 System Con-tact

Set the contact address (e.g. [email protected]). Press the “Backspace” key to clear the factory setting and then enter the new contact address.

8 System Lo-cation

Enter the location name. Press the “Backspace” key to clear the factory setting and then enter the new installation loca-tion.

7.3.12 Configuring the Passwords You can change the passwords of the Processing Unit as required. The associated character length may not exceed 20 characters. Special characters are not permitted.

Navigation

Main menu – 1 Network Configuration – 9 Secu-rity

Parameter Explanation

1 Change Password User ´cmc´

Set the password for the ´cmc´ user (max. 20 characters). Press the “Backspace” key to clear the factory setting and then enter the password. To

Page 21: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 21

EN verify the new password, it must be re-entered a second time.

2 Change Password User ´admin´

Set the password for the ´admin´ user (max. 20 charac-ters). Press the “Backspace” key to clear the factory setting and then enter the password. To verify the new password, it must be re-entered a second time.

7.3.13 Changing the HTTP Port The standard http port for some networks is not assigned to port 80. You can change the port num-ber to meet your requirements.

Navigation

Main menu – 1 Network Configuration – 9 Secu-rity

Parameter Explanation

3 Change http Port

Set the http port 80-10000 (fac-tory setting: 80). Press the “Backspace” key to clear the factory setting and then enter the new port.

7.3.14 HTTPS (SSL) Function For security, the Processing Unit supports SSL en-cryption. This encryption is used for the secure data exchange between the CMC-TC PU and the work-station.

Navigation

Main menu – 1 Network Configuration – 9 Secu-rity

Parameter Explanation

4 Enable SSL Enable or disable SSL with the ← and → arrow keys.

5 Change https Port

Set the https port 80-10000 (factory setting: 443). Press the “Backspace” key to clear the factory setting and then enter the new port.

7.3.15 Configuring the FTP Access The FTP access is used exclusively for uploading software updates, log files and configuration files. It can remain deactivated for normal usage.

Navigation

Main menu – 1 Network Configuration – A Enable FTP

Parameter Explanation

A Enable FTP Enable or disable FTP with the ← and → arrow keys.

7.3.16 SFTP Access The Secure FTP access includes the SSH data encryption. The function is always active and cannot be disabled. SFTP can be used as an alternative to FTP.

7.3.17 Configuring the Timeout Window The console and Telnet Timeout window is used for the automatic logout after a defined time. If, for ex-ample, a user has not performed any action on the Processing Unit over a period of five minutes, the user will be logged off automatically.

Navigation

Main menu – 1 Network Configuration – B Cons./Teln. Timeout Minutes

Parameter Explanation

B Cons./Teln. Timeout Min-utes

Set the timeout function in min-utes. 0 = No timeout 5 = If no changes have been made during the previous five minutes. Press the “Backspace” key to clear the factory setting and then enter the new time.

7.3.18 Configuring the Telnet Access Telnet provides the same administrative rights as those using the serial interface. If Telnet access is not wanted, you can deactivate it.

Navigation

Main menu – 1 Network Configuration – C En-able/Disable Telnet

Parameter Explanation

C Enable / Disable Telnet

Enable or disable Telnet with the ← and → arrow keys.

Note! In addition to access using Telnet, an SSH client (e.g. Putty) can be used to make an encrypted access to the PUII

Page 22: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 22

EN configuration. Unlike the Telnet access, the SSH access cannot be disabled.

7.3.19 Activating the Restart You can also restart (reboot) the Processing Unit after a software crash using this menu item.

Navigation

Main menu – 1 Network Configuration – D Acti-vate Actual Values

Parameter Explanation

D Activate Actual Values

Perform restart (Yes) or do not perform restart (No) using the ← and → arrow keys.

7.3.20 Configuring the Connected Sen-sors

The sensors can be configured using Hyper-Terminal. This method of operation is required only when the browser setting is set to view mode.

Navigation

Main menu – 2 Sensor Units

Parameter Explanation

1-4 Connected Units

Access to the connected units with the installed sensors.

7.3.21 General Configuration of the Processing Unit

The main configuration of the Processing Unit is used to setup the hardware and the units of the sensors. You can also set up the date and time, temperature unit, alarm relay, etc.

Navigation

Main menu – 3 General Configuration

Parameter Explanation

1 Temperature Unit

Set the Celsius or Fahrenheit unit using the ← and → arrow keys.

2 Beeper Set on (alarm beeper on) or off (alarm beeper off) using the ← and → arrow keys.

3 Quit Alarm Relay

Set the alarm relay acknowl-edge using the ← and → arrow keys. In case of an alarm, the "C key" can be used to reset the alarm relay on the PU.

Disabled = the alarm relay is reset automatically after an alarm. Enabled = the alarm relay is reset after an alarm by pressing the "C key".

4 Alarm Relay Options

Set the alarm relay function using the ← and → arrow keys.Close = alarm relay contact is closed. Open = alarm relay contact is open. Off = alarm relay contact is disabled.

5 Web Access Set the web access using the ← and → arrow keys. Full = full access. All current values can be fetched and set-tings changed on the Process-ing Unit. View = display. Only the current values are displayed. The set-tings cannot be changed. No = block web access. The Processing Unit can no longer be called from the web.

6 Actual Date Set the current date. Press the "Backspace" key to clear the factory setting and then enter the current date. Date format: dd.mm.yyyy

7 Actual Time Set the current time. Press the "Backspace" key to clear the factory setting and then enter the current time. Time format: hh:mm:ss

8 Check Link The individual Trap Receivers can be checked for reachability.Press the "Backspace" key to clear the factory setting and enter the number of the Trap Receiver.

9 SMS Con-figuration

Applies only when an ISDN or GSM unit is connected.

7.3.22 Configuring the SMS Notification (GSM Unit)

This function is only active if an ISDN unit is con-nected.

Navigation

Main menu – 3 General Configuration – 9 SMS Configuration

Parameter Explanation

Page 23: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 23

EN 1 PIN GSM Card

Set the 4-digit PIN number of the GSM card.

2 SMS Service Number

Set the SMS service number. The specified format must be observed, e.g. +491710760000

6 SMS upon Unit Messages

For a timeout, etc., an SMS for notification can be sent to a unit. Set using the ← and → arrow keys, "Yes" or "No".

7.3.23 Configuring the SMS Notification (ISDN Unit)

This function is only active if an ISDN unit is con-nected.

Navigation

Main menu – 3 General Configuration – 9 SMS Configuration

Parameter Explanation

3 ISDN MSN Set the MSN number of your ISDN connection. The number must be entered as follows: +49/2772/123456

4 ISDN Pre-Dial Number

Set the number to obtain an external line. This entry is required when you have connected the ISDN unit to a telephone system.

5 ISDN Com-mand

Set the SMS command for sending SMS messages over the fixed-line network. For example, "8888 ANMELD" for the T-Com network. or "09003266900" for the Arcor network.

6 SMS upon Unit Messages

For a timeout, etc., an SMS for notification can be sent to a unit. Set using the ← and → arrow keys, "Yes" or "No".

7.3.24 Entering the Telephone Numbers for SMS Notification

This function is only active if an ISDN or GSM unit is connected.

Navigation

Main menu – 3 General Configuration – 9 SMS Configuration – 7 SMS Phone Numbers

Parameter Explanation

1 - 4 SMS Phone Number

Set the SMS target call number.E.g. +4927725051234

7.3.25 Calling the CMC Information Page To display the current information for the Processing Unit, you can display an information page from the Processing Unit. This page displays all settings for the network connection, software and hardware version, etc.

Navigation

Main menu – 4 Info Page

Parameter Explanation

4 Info Page The CMC Info Page provides a complete overview of the Proc-essing Unit configuration.

7.3.26 Resetting All Settings in the Main Menu

You can reset all your sensor settings. Passwords and network settings are not reset.

Navigation

Main menu – 5 Default, NewConfig. of Sensor Units, File Transfer

Parameter Explanation

1 Set General Configuration to Default

Activate (Yes) or deactivate (No) the sensor settings using the ← and → arrow keys.

7.3.27 Manual Search for Sensors Under some circumstances, the sensors for the Processing Unit are not detected immediately. In this case, you can activate the manual search for the sensors.

Navigation

Main menu – 5 Default, NewConfig. of Sensor Units, File Transfer

Parameter Explanation

2 Sensor Unit Detection

Activate (Yes) or deactivate (No) the sensor detection using the ← and → arrow keys.

Page 24: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 24

EN 7.4 Transferring Files Using the Serial Interface

You can transfer individual files, such as access files, to the Processing Unit using the serial inter-face.

Navigation

Main menu – 5 Default, NewConfig. of Sensor Units, File Transfer – 3 Serial File Transfer (ZModem)

Parameter Explanation

1 Send File to CMC

Start (Yes) or do not start (No) the Zmodem using the ← and → arrow keys.

You will now be requested to specify the path for the file to be transferred. To do this, click "Find" and search for the file. Select Zmodem as protocol and click "Send". Once the file has been transferred, press the Esc key to return to the main menu and to save the setting.

7.5 Saving Files Using the Serial In-terface

You can save individual files from the Processing Unit on your PC.

Navigation

Main menu – 5 Default, New Config. of Sensor Units, File Transfer – 3 Serial File Transfer (ZModem)

Parameter Explanation

2 Receive File from CMC

Enter the name of the file that you want to save from the Processing Unit on your com-puter.

Now use the find icon to select a target folder for the file to be saved. Enter Zmodem as receive protocol and click "Re-ceive" to confirm your input.

7.6 Access Using a Browser Open your Web browser as usual. Enter the IP ad-dress of the Processing Unit in the address field and call the page.

7.6.1 Login

1

2

3

Fig. 22 Login window

Key 1 User name 2 Password 3 Login or Clear button Enter in the login window the http user name and the http password of the Processing Unit. Factory setting: User name: admin Password: admin To confirm the input, click the Login button. To clear the input, click the Clear button.

7.6.2 Main Page View 1

23456

78

Fig. 23 Main page overview

Key 1 Status window

As shown above 2 IP address of the Processing Unit 3 Link to the main page view 4 Setup Link 5 Alarm and event logging link 6 Administration link 7 User name 8 User logout The following buttons can be used to navigate eas-ier between the individual pages:

Setup button: Links from the overview page (main or units overview) to the setup pages of the associated unit.

Overview button: Links from the main over-view page to the units overview page.

Page 25: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 25

EN

Back button: This can be used to go back one page from any page.

Home button: Links from each units over-view page or from the setup pages directly to the home page.

7.6.3

Main Settings

1

3

2

4

56

78

9

Fig. 24 Main settings

Key 1 General

This link can be used to make basic settings of the PUII (name, location, contact name, temperature unit, beeper, alarm relay acknowledge, alarm relay op-tions, background colour, date and time).

2 Timer function (see 7.6.4 Configuring the Scheduler) 3 SMS unit (see 7.6.5 Configuring the GSM Unit or

7.6.6 Configuring the ISDN Unit) 4 E-Mail (SMTP) 5 Event Logging (see 7.6.8 Calling the Log File) 6 Administration links to the user administration, if you

are logged on as administrator. Otherwise you can only change your own password.

7 Date and time of the last alarm/warning status change

8 Current status of the alarms and warnings 9 Logged-in user

7.6.4 Configuring the Scheduler You can program up to eight timers. 1. Specify whether the timer is to be active or inac-

tive. 2. Select the day or days when the timer is to be

active. 3. Now specify the time window (format: hh:mm). 4. Specify what the timer should perform during

this time. The following functions can be selected from item 4:

Designation Function

dis.keypad unit Deactivates the associ-ated keypad.

unlock unit Opens the door (front or rear) of the associated unit.

disable Trap Receiver No alarms are sent to the trap receiver.

disable SMS (general) Deactivates the SMS

Page 26: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 26

EN notification function.

Alarm Scheduler Disables the alarms con-figured for "Scheduled Alarm off" in the sensor configuration.

disable Trap Receiver Deactivates the SMS notification function for a specific receiver.

disable E-Mail Rec. Deactivates the e-mail notification function for a specific receiver.

Status E-Mail to Rec. Sends a status e-mail to a receiver. A maximum of 150 mes-sages can be transferred for each status mail. If more than 150 mes-sages are present, only the most recent 150 will be sent in the e-mail.

7.6.5 Configuring the GMS Unit 1

2

3

4

5

Fig. 25 Setup for SMS unit

Key 1 PIN GSM-Card

Enter here the PIN for your GSM card. 2 Service Centre GSM

Set the Service Centre number. This number varies depending on the mobile telephone provider. Ob-serve the notation (e.g. +491710760000).

3 Unit Messages Set whether for a unit error, for example, timeout or configuration change, an SMS should be sent.

4 Enter the target call numbers (max. four target call numbers, e.g. +4927725051234).

5 Accept or Reset button Accept or reset the settings.

7.6.6 Configuring the ISDN Unit

1

23

4

6

5

Fig. 26 Setup for ISDN unit

Key 1 ISDN MSN

Enter here the MSN number of the ISDN connec-tion. The MSN number must be entered as follows: +49/2772/123456

2 ISDN Pre Dial If the ISDN unit is to be connected to a telephone system, you must enter the number used to obtain an external line, for example, "0".

3 ISDN Command Specify the SMS command so that SMS can be sent over the fixed-line network (e.g. the following com-mand must be entered for T-Com: "8888 AN-MELD").

4 Unit Messages Set whether for a unit error, for example, timeout or configuration change, an SMS should be sent.

5 Phone Number 1 - 4 Enter here the target call numbers to receive an SMS when an alarm is issued; these numbers are entered in the following format: +492772123456.

6 Accept or Reset button Accept or reset the settings.

7.6.7 Configuring the Sending of E-Mails If you have not entered the e-mail addresses of the alarm recipient using Hyperterminal, you can do this here now. Proceed as follows:

12345678

Fig. 27 Setup for sending e-mails

Key 1 IP SMTP Server

Enter here the IP address of the SMTP server.

Page 27: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 27

EN 2 SMTP Authent. If your SMTP server requires a user name and password for the authentication, click "Yes".

3 Username Server Enter the user name for the authentication.

4 Password Server Enter the password of the server for the authentica-tion and repeat the input in the "Retype" field.

5 Sender Name Enter a sender name. This name is then used as sender in the alarm mail.

6 Reply to If a reply is to be sent for the alarm mail, you can specify the e-mail address for the recipient to which the response mail is to be forwarded.

7 Unit Messages If the individual units display an error message (configuration change, timeout), you can send this alarm as an e-mail. To do this, click "Yes".

8 E-Mail Address 1-4 Enter here up to four different e-mail addresses.

To accept and save the settings, click the "Accept" button.

7.6.8 Calling the Log File Two different types of logging are performed. Firstly, the "Alarm Log". This displays all alarms that the logged-in user is permitted to view.

Fig. 28 Alarm log

Secondly, the "Event Log". This shows the time when each user performed a login and logoff, when an update was performed, when a file was uploaded or downloaded, and various other events.

Fig. 29 Event log

Up to 100 messages are recorded. If the storage area is full with 100 messages and a new message is received, the oldest message will be deleted.

7.6.9 Administration Login as administrator on the login page (see 7.6.1 Login).

2

1

3456789

101112

Fig. 30 User administration

Key 1 Page title 2 User page:

Up to sixteen different users or user groups can be created (max. 20 characters; special characters are not permitted).

3 Username: Enter the user name or group name. Maximum character length: 20 characters (special characters are not permitted).

4 Password: The password may contain a maximum of 20 char-acters (special characters are not permitted).

5 Unit 1 – 6: The access rights for the individual units are speci-fied per user or user group. No Access: The user does not have any access to the unit. Read: User only has read rights. Settings cannot be changed. Read/Write: User has read and write rights. User has access to the unit; the user can read and change the settings but not switch the unit 1 – 4. Read/Write/Switch: User has read, write and switching rights. Connected socket strips, and digi-tal and analogue inputs/outputs can be operated by the user.

6 General Setup: No Access: The user does not have any access to the unit. Read: User only has read rights. Settings cannot be changed. Read/Write: User has read and write rights. The user has access to the unit, and can read and change the settings.

7 Timer Functions: No Access: The user does not have any access to the unit. Read: User only has read rights. Settings cannot be changed. Read/Write: User has read and write rights. The user has access to the unit, and can read and change the settings.

8 SMS Setup: No Access: The user does not have any access to the unit.

Page 28: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 28

EN Read: User only has read rights. Settings cannot be changed. Read/Write: User has read and write rights. The user has access to the unit, and can read and change the settings.

9 Alarm Logs: No Access: The user does not have any access to the Event Logging page. Own alarms: If a user only has access to one or more units, the user will see only the alarm mes-sages of the units assigned to the user. All alarms: The logged in user is permitted to view all alarm messages.

10 Timeout: If a user does not make any activity in the browser window for an extended period of time, the user will be logged off from the system after a set time.

11 Login Status: If you are logged in as administrator, you can log off logged in users.

12 Accept/Reset Button: Accept button: Accept settings. Reset button: Settings are not accepted.

Note! If you are logged in as user, you can only change your password in the Administra-tion window.

Logged in users can only change their own pass-word.

7.7 Configuring the Sensors You can make various settings for each sensor. The CMC-TC PU has four connections to each of which a sensor unit (I/O Unit, Access Unit, etc.) can be connected.

Navigation

Main menu

The sensor overview window appears.

7.7.1 General Overview (Status Window) 1 2 3

4 5

Fig. 31 I/O units overview

Key 1 Connection number and type of the sensor units. 2 Name of the sensor unit: Click to change to the

sensor overview (7.7.2) of the I/O unit. 3 Warning and alarm status of the sensor

green: No warning/alarm yellow: Warning red: Alarm (malfunction) unit detected: New sensor unit has been connected to the PUII Configuration changed: New sensor connected to the I/O unit or configuration change of a sensor

4 Acknowledge events Click the Clear button to acknowledge timeouts and configuration changes. This causes the CMC-TC PU to be queried again and the web page rebuilt.

5 Refresh Forces an immediate updating of the CMC-TC PU web page. The sensor overview will also be updated automati-cally every ten seconds.

7.7.2

Page 29: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 29

EN Sensor Overview 1 2 3

4 5 6

Fig. 32 Sensors on an I/O unit overview

Key 1 Connection number and sensor type. 2 Message text of the sensor. Can be selected freely

using the sensor configuration (7.7.3). 3 Status or measurement value of the sensor. The

font colour indicates the status of the sensor. For analogue values, an arrow indicates the over-shooting or undershooting of the alarm or warning thresholds.

4 Acknowledge events Click the Clear button to acknowledge timeouts and configuration changes. This causes the CMC-TC PU to be queried again and the web page rebuilt.

5 Refresh Forces an immediate updating of the CMC-TC PU web page. The sensor overview is also updated automatically every ten seconds.

6 Warning and alarm status of the sensors (overall) green: No warning/alarm yellow: Warning red: alarm (malfunction)

7.7.3 General Overview (Sensor Configu-ration)

You can individually set the attached sensors. Be-cause the structure of the configuration overview is generally always identical, it is shown here as an example. To reach this page, click the message text of the sensor or the tool icon on the general overview (status window) of the PUII.

1

23456789

10111213

14 15

Fig. 33 Configuring the sensor – overview

Key 1 Connected sensor type. 2 Current status of the connected sensor. 3 This message text will also be transferred when a

warning/alarm message is sent and serves as in-formation for the recipient of the message to identify the sensor. You can delete the specified text and add your own message text (e.g. TempSensor-Rack1).

7 You can set for each sensor whether (enable) or not (disable) the alarm relay is to be switched for an alarm.

8 You can set for each sensor whether (enable) or not (disable) the integrated alarm beeper is to be acti-vated for an alarm.

9 You can set for each sensor type whether after a warning or alarm status the CMC-TC PU should self-acknowledge (auto) or the administrator must acknowledge manually (manual).

10 By clicking the individual option fields you can de-termine to which of the entered trap receivers the traps for this sensor are to be sent.

11 By clicking the individual option fields you can set which alarm configuration is to be enabled or dis-abled. You can specify the individual functions in the "Setup – Timer" menu item and assign the associ-ated scheduler.

12 You can enter up to four mobile wireless numbers that you entered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

13 You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

14 Accept all changes. 15 Reset all settings to their default values. The following buttons can be used to navigate eas-ier between the individual pages:

Back button: This can be used to go back one page from any page.

Home button: Links from each units over-view page or from the setup pages directly to the home page.

Page 30: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 30

EN 7.7.4 Configuring the Temperature Sen-sor

You configure the temperature sensor (DK 7320.500) as follows:

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Measured temperature and sensor status. Green = OK, yellow = warning, red = alarm.

Message Text The message text which is also transferred when a warn-ing/alarm message is sent. Enter here a designation that uniquely identifies your sensor, e.g. "TempSensor rack 1".

Setpoint High Temperature limit which when overshot causes an alarm mes-sage to be issued.

Setpoint Warn-ing

Temperature limit which when overshot causes a warning message to be issued.

Setpoint Low Temperature limit which when undershot causes an alarm message to be issued.

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of a warn-ing/alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of a warn-ing/alarm.

Alarm Reset Should a warning/alarm be acknowledged automatically (Auto) or does it need to be acknowledged by the adminis-trator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent warning/alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.5 Configuring the Humidity Sensor You configure the humidity sensor (DK 7320.510) as follows. The humidity is specified as relative humid-ity (% rH).

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Measured humidity and sensor status. Green = OK, yellow = warning, red = alarm.

Message Text The message text which is also transferred when a warn-ing/alarm message is sent. Enter here a designation that uniquely identifies your sensor, e.g. "Air humidity rack 1".

Setpoint High Humidity limit which when over-shot causes an alarm message to be issued.

Setpoint Warn-ing

Humidity limit which when over-shot causes a warning mes-sage to be issued.

Setpoint Low Humidity limit which when un-dershot causes an alarm mes-sage to be issued.

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of a warn-ing/alarm.

Page 31: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 31

EN Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of a warn-ing/alarm.

Alarm Reset Should a warning/alarm be acknowledged automatically (Auto) or does it need to be acknowledged by the adminis-trator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent warning/alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.6 Configuring the Analogue Sensor Input Module

You configure the analogue sensor input module (DK 7320.520) as follows. The individual values are specified as percentage.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Measured input current (as percentage) and sensor status. Green = OK, yellow = warning,

red = alarm.

Message Text The message text which is also transferred when a warn-ing/alarm message is sent. Enter here a designation that uniquely identifies your sensor, e.g. "Analogue sensor rack 1".

Setpoint High Input current limit which when overshot causes an alarm mes-sage to be issued.

Setpoint Warn-ing

Input current limit which when overshot causes a warning message to be issued.

Setpoint Low Input current limit which when undershot causes an alarm message to be issued.

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of a warn-ing/alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of a warn-ing/alarm.

Alarm Reset Should a warning/alarm be acknowledged automatically (Auto) or does it need to be acknowledged by the adminis-trator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent warning/alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any

Page 32: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 32

EN changes are not accepted.

7.7.7 Configuring the Access Sensor You configure the access sensor (DK 7320.530) as follows:

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Access sensor status; green = OK, red = alarm.

Message Text The message text which is also transferred when a warn-ing/alarm message is sent. Enter here a designation that uniquely identifies your sensor, e.g. "Access sensor rack 1".

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of a warn-ing/alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of a warn-ing/alarm.

Alarm Reset Should a warning/alarm be acknowledged automatically (Auto) or does it need to be acknowledged by the adminis-trator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent warning/alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered

previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.8 Configuring the Vandalism Sensor You configure the vandalism sensor (DK 7320.540) as follows. The individual values are specified as pulses.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Measured pulses and sensor status. Green = OK, yellow = warning, red = alarm.

Message Text The message text which is also transferred when a warn-ing/alarm message is sent. Enter here a designation that uniquely identifies your sensor, e.g. "Vandalism sensor rack 1".

Setpoint High Pulse limit which when overshot causes an alarm message to be issued.

Setpoint Warn-ing

Pulse limit which when overshot causes a warning message to be issued.

Setpoint Low Pulse limit which when under-shot causes an alarm message to be issued.

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of a warn-ing/alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of a warn-ing/alarm.

Alarm Reset Should a warning/alarm be acknowledged automatically (Auto) or does it need to be acknowledged by the adminis-

Page 33: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 33

EN trator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent warning/alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.9 Configuring the Air Flow Sensor You configure the air flow sensor (DK 7320.550) as follows. Only the status of the sensor is specified.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Air flow status and sensor status. Green = OK, red = a-larm.

Message Text The message text which is also transferred when a warning message is sent. Enter here a designation that uniquely identi-fies your sensor, e.g. "Air flow rack 1".

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of an alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of an alarm.

Alarm Reset Should an alarm be acknowl-edged automatically (Auto) or does it need to be acknowl-edged by the administrator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.10 Configuring the Smoke Detector You configure the smoke detector (DK 7320.560) as follows. Only the status of the sensor is specified.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Smoke detector status and sensor status. Green = OK, red = alarm.

Message Text The message text which is also transferred when a warning message is sent. Enter here a

Page 34: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 34

EN designation that uniquely identi-fies your sensor, e.g. "Smoke detector rack 1".

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of an alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of an alarm.

Alarm Reset Should an alarm be acknowl-edged automatically (Auto) or does it need to be acknowl-edged by the administrator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.11 Configuring the Motion Detector You configure the motion detector (DK 7320.570) as follows. Only the status of the sensor is specified.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Motion detector status and sensor status. Green = OK, red = alarm.

Message Text The message text which is also transferred when a warning message is sent. Enter here a designation that uniquely identi-fies your sensor, e.g. "Motion detector rack 1".

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of an alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of an alarm.

Alarm Reset Should an alarm be acknowl-edged automatically (Auto) or does it need to be acknowl-edged by the administrator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.12 Configuring the Digital Input Module

You configure the digital input module (DK 7320.580) as follows. Only the status of the sensor is specified.

Page 35: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 35

EN Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Input status and sensor status. Green = OK, red = alarm.

Message Text The message text which is also transferred when a warning message is sent. Enter here a designation that uniquely identi-fies your sensor, e.g. "Digital input rack 1".

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of an alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of an alarm.

Alarm Reset Should an alarm be acknowl-edged automatically (Auto) or does it need to be acknowl-edged by the administrator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.13 Configuring the Digital Output Re-lay Module

You configure the digital output relay module (DK 7320.590) as follows. Only the status of the sensor is specified.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Output Status Relay output status; enabled = on, disabled = off.

Message Text The message text which is also transferred when a warning message is sent. Enter here a designation that uniquely identi-fies your sensor, e.g. "Digital output rack 1".

Delay Delay time for next switch on or off. 0 s = no release time; 999 s = 999 seconds release time.

Timeout Module behaviour for failure of the PUII provided the module itself is still being supplied with power: stay = return to the original status after expiration of the time; switch off = the output is switched off after expiration of the time; switch on = the relay is switched on after expiration of the time.

Trap Receiver Specify which of the entered trap receivers is to be sent status messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Page 36: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 36

EN Combinations Configure the switching combi-nations (see 7.7.14 Configuring Switching Combinations for the Digital Relay Output Module).

Switch Output Manual enable (On) or disable (Off).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.14 Configuring Switching Combina-tions for the Digital Relay Output Module

You configure the switching combination for the digital relay output module (DK 7320.590) as fol-lows. Various switching combinations can be set.

Navigation

Main menu – Setup – Click the sensor name – Switching combinations

Parameter Explanation

If status of Select the first sensor for the switching combination.

is Select the first sensor status for a switching operation.

and/or Select an "and" or "or" opera-tion.

status of Select the second sensor for the switching combination.

is Select the second sensor status for a switching operation.

Then.....output Select the switching state when the switching combination is satisfied. Switch off = deacti-vate relay output; switch on = activate relay output.

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.15 Configuring the Voltage Monitor You configure the voltage monitor (DK 7320.600) as follows. Only the status of the sensor is specified.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Input state and sensor status. Green = OK, red = alarm.

Message Text The message text which is also transferred when a warning message is sent. Enter here a designation that uniquely identi-fies your sensor, e.g. "VltgRack01".

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of an alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of an alarm.

Alarm Reset Should an alarm be acknowl-edged automatically (Auto) or does it need to be acknowl-edged by the administrator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

Page 37: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 37

EN 7.7.16 Configuring the Voltage Monitor-ing for the Voltage Monitor with IEC Switch Output

You configure the voltage monitor with IEC switch output (DK 7320.610) as follows. The individual values are specified in volts.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Measured voltage and sensor status. Green = OK, red = a-larm.

Message Text The message text which is also transferred when a warning message is sent. Enter here a designation that uniquely identi-fies your sensor, e.g. "VltgRack01".

Setpoint High Voltage limit which when over-shot causes an alarm message to be issued.

Setpoint Warn-ing

Voltage limit which when over-shot causes a warning mes-sage to be issued.

Setpoint Low Voltage limit which when un-dershot causes an alarm mes-sage to be issued.

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of a warn-ing/alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of a warn-ing/alarm.

Alarm Reset Should an alarm be acknowl-edged automatically (Auto) or does it need to be acknowl-edged by the administrator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions

can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.17 Configuring the Switch Output for the Voltage Monitor with IEC Switch Output

You configure the switch output of the voltage moni-tor with IEC switch output (DK 7320.610) as follows. Only the status of the sensor is specified.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Output Status Relay output status; enabled = on, disabled = off.

Message Text The message text which is also transferred when a warning message is sent. Enter here a designation that uniquely identi-fies your sensor, e.g. "VltgRack01".

Delay Delay time for next switch on or off. 0 s = no release time; 999 s = 999 seconds release time.

Timeout Module behaviour for failure of the PUII provided the module itself is still being supplied with power: stay = return to the original status after expiration of the time; switch off = the output is switched off after expiration of

Page 38: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 38

EN the time; switch on = the relay is switched on after expiration of the time.

Trap Receiver Specify which of the entered trap receivers is to be sent status messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Combinations Configure the switching combi-nations (see 7.7.18 Configuring Switching Combinations for the Voltage Monitor with IEC Switch Output).

Switch Output Manual enable (On) or disable (Off).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.18 Configuring the Switching Com-binations for the Voltage Monitor with IEC Switch Output

You configure the switching combination for the voltage monitor with IEC switch output (DK 7320.610) as follows. Various switching combi-nations can be set.

Navigation

Main menu – Setup – Click the sensor name – Switching combinations

Parameter Explanation

If status of Select the first sensor for the switching combination.

is Select the first sensor status for a switching operation.

and/or Select an "and" or "or" opera-tion.

status of Select the second sensor for the switching combination.

is Select the second sensor status for a switching operation.

Then.....output Select the switching status when the switching combination is satisfied. switch off = disable switch output; switch on = en-able switch output.

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.19 Configuring the Voltage Monitor-ing for the Voltage Monitor with 16 A Switch Output

You configure the voltage monitor with 16 A switch output (DK 7320.611) as follows. The individual values are specified in volts.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Measured voltage and sensor status. Green = OK, yellow = warning, red = alarm.

Message Text The message text which is also transferred when a warn-ing/alarm message is sent. Enter here a designation that uniquely identifies your sensor, e.g. "VltgRack01".

Setpoint High Voltage limit which when over-shot causes an alarm message to be issued.

Setpoint Warn-ing

Voltage limit which when over-shot causes a warning mes-sage to be issued.

Setpoint Low Voltage limit which when un-dershot causes an alarm mes-sage to be issued.

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of a warn-ing/alarm.

Page 39: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 39

EN Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of a warn-ing/alarm.

Alarm Reset Should a warning/alarm be acknowledged automatically (Auto) or does it need to be acknowledged by the adminis-trator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent warning/alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.20 Configuring the Switch Output for the Voltage Monitor with 16 A Switch Output

You configure the switch output of the voltage moni-tor with 16 A switch output (DK 7320.611) as fol-lows. Only the status of the sensor is specified.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Output Status Relay output status; enabled = on, disabled = off.

Message Text The message text which is also transferred when a status mes-sage is sent. Enter here a des-ignation that uniquely identifies your sensor, e.g. "VltgRack01".

Delay Delay time for next switch on or off. 0 s = no release time; 999 s = 999 seconds release time.

Timeout Module behaviour for failure of the PUII provided the module itself is still being supplied with power: stay = return to the original status after expiration of the time; switch off = the output is switched off after expiration of the time; switch on = the relay is switched on after expiration of the time.

Trap Receiver Specify which of the entered trap receivers is to be sent status messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Combinations Configure the switching combi-nations (see 7.7.21 Configuring Switching Combinations for the Voltage Monitor with 16 A Switch Output).

Switch Output Manual enable (On) or disable (Off).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.21 Configuring the Switching Com-binations for the Voltage Monitor with 16 A Switch Output

You configure the switching combination for the voltage monitor with 16 A switch output

Page 40: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 40

EN (DK 7320.611) as follows. Various switching combi-nations can be set.

Navigation

Main menu – Setup – Click the sensor name – Switching combinations

Parameter Explanation

If status of Select the first sensor for the switching combination.

is Select the first sensor status for a switching operation.

and/or Select an "and" or "or" opera-tion.

status of Select the second sensor for the switching combination.

is Select the second sensor status for a switching operation.

Then.....output Select the switching status when the switching combination is satisfied. switch off = disable switch output; switch on = en-able switch output.

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.22 Configuring the 48 V Voltage Monitor

You configure the 48 V voltage monitor (DK 7320.620) as follows. Only the status of the sensor is specified.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status 48 V voltage monitor state and sensor status. Green = OK, red = alarm.

Message Text The message text which is also transferred when a warn-ing/alarm message is sent. Enter here a designation that uniquely identifies your sensor, e.g. "48 V VltgRack01".

Alarm Relay Whether (enable) or not (dis-

able) an alarm relay should switch in the event of an alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of an alarm.

Alarm Reset Should an alarm be acknowl-edged automatically (Auto) or does it need to be acknowl-edged by the administrator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.23 Configuring the Leakage Sensor You configure the leakage sensor (DK 7320.630) as follows. Only the status of the sensor is specified.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Smoke detector status and sensor status. Green = OK, red = alarm.

Page 41: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 41

EN Message Text The message text which is also transferred when a warning message is sent. Enter here a designation that uniquely identi-fies your sensor, e.g. "Leakage Rack01".

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of an alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of an alarm.

Alarm Reset Should an alarm be acknowl-edged automatically (Auto) or does it need to be acknowl-edged by the administrator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.24 Configuring the Acoustic Sensor You configure the acoustic sensor (DK 7320.640) as follows. Various limit values can be entered as per-centages.

Navigation

Main menu – Setup – Click the sensor name

Parameter Explanation

1 … n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Measured loudness as per-centage and sensor status. Green = OK, yellow = warning, red = alarm.

Message Text The message text which is also transferred when a warn-ing/alarm message is sent. Enter here a designation that uniquely identifies your sensor, e.g. "Acoustic Rack01".

Setpoint High Loudness limit (as percentage) which when overshot causes an alarm message to be issued.

Setpoint Warn-ing

Loudness limit (as percentage) which when overshot causes a warning message to be issued.

Setpoint Low Loudness limit (as percentage) which when undershot causes an alarm message to be issued.

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of a warn-ing/alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of a warn-ing/alarm.

Alarm Reset Should a warning/alarm be acknowledged automatically (Auto) or does it need to be acknowledged by the adminis-trator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent warning/alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered

Page 42: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 42

EN previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.25 Configuring the Fan Control Sys-tem (FCS)

You configure the FCS (DK 7320.810) as follows:

Navigation

Main menu – Setup – Click the first sensor name

Parameter Explanation

1...n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Measured temperature and sensor status. Green = OK, yellow = warning, red = alarm.

Message Text The message text which is also transferred when a warn-ing/alarm message is sent. Enter here a designation that uniquely identifies your sensor, e.g. "FCS-Temp Rack01".

Setpoint High Temperature limit which when overshot causes an alarm mes-sage to be issued.

Setpoint Temperature limit above which the fan operates at 100% power.

Setpoint Low Temperature limit which when undershot causes an alarm message to be issued.

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of an alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of an alarm.

Alarm Reset Should an alarm be acknowl-edged automatically (Auto) or does it need to be acknowl-edged by the administrator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent

alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

Click tab 2 to continue the configuration.

Navigation

Main menu – Setup – Click the second sensor name

Parameter Explanation

2 Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Sensor status. Green = OK, red = alarm.

Message Text The message text which is also transferred when a warn-ing/alarm message is sent. Enter here a designation that uniquely identifies your sensor, e.g. "FCS-Fan Rack01".

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

Click tab 3 to continue the configuration.

Navigation

Main menu – Setup – Click the third sensor name

Page 43: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 43

EN Parameter Explanation

3 Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Fan Status Sensor status. Green = OK, red = alarm, grey = fan not con-nected.

Message Text The message text which is also transferred when a warning message is sent. Enter here a designation that uniquely identi-fies your sensor, e.g. "FCS fan rack 1".

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of an alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of an alarm.

Alarm Reset Should an alarm be acknowl-edged automatically (Auto) or does it need to be acknowl-edged by the administrator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.26 Configuring the Fan Alarm Sys-tem (FAS)

You configure the FAS (DK 7320.811) as follows:

Navigation

Main menu – Setup – Click the first sensor name

Parameter Explanation

1...n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Sensor status. Green = OK, red = alarm.

Message Text The message text which is also transferred when a warning message is sent. Enter here a designation that uniquely identi-fies your sensor, e.g. "FAS-Fan Rack01".

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of an alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of an alarm.

Alarm Reset Should an alarm be acknowl-edged automatically (Auto) or does it need to be acknowl-edged by the administrator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Page 44: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 44

EN Reset Reset all settings to the values saved most recently; any changes are not accepted.

7.7.27 Wireless Sensors The configuration of the wireless sensors corre-sponds to the configuration of the associated cable-connected sensor.

Wireless sensor type see configura-tion in

Temperature Section 7.7.4

Humidity Section 7.7.5

Access Section 7.7.7

Digital input Section 7.7.12

The connection of the wireless sensors to the wire-less I/O unit is described in detail in the Wireless I/O Unit manual (7320.240).

7.8 Access Using Telnet You can also configure the Processing Unit using Telnet. This requires that you have used the termi-nal program to permit access using Telnet (see Section 7.3.18 Configuring the Telnet Access).

7.8.1 Login Using Telnet The following section describes the access using Telnet under Windows. a. Open the input prompt and enter the command:

telnet <IP-address> b. Confirm with Enter or Return. c. Enter for “Login” the Telnet login (factory set-

ting: ´cmc´). Confirm with Enter or Return. d. Enter for “Password” the Telnet password (fac-

tory setting: 'cmc'). Confirm with Enter or Re-turn.

7.8.2 Telnet Main Menu After the login by Telnet, the same main menu as for access using HyperTerminal appears. Because all procedures are similar, refer to 7.

Note! In addition to access using Telnet, an SSH client (e.g. Putty) can be used to make an encrypted access to the PUII configuration. Unlike the Telnet access, the SSH access cannot be disabled.

7.9

Performing a Software Update Download from the internet page www.rimatrix5.com (Security) in the download area, the software update to your PC. Unzip the file into a separate folder, for example, with the name: puupdate.

Note! The update takes approximately 10 min-utes. Also observe the guidelines for the update provided for download with the update in the internet.

Warning! The update must not be cancelled, because this can cause the complete failure of the PUII.

• Open the input prompt and navigate to the folder

that contains the unzipped software update. • Enter the following command: update <IP-

address> (e.g. update 192.168.0.130). The PUII must be reachable in the network with the specified IP address. The file is now sent to the CMC-TC Processing Unit. This is displayed with several #-characters in the input prompt window. The CMC-TC Processing Unit independently per-forms two restarts during the update process. This operation takes several minutes. Do not change anything on the CMC-TC. Do not disconnect the Processing Unit from the mains. Wait until the Op-erating LED lights again and the Updating finished, login to Rittal CMC PU <IP-address> again mes-sage appears.

7.10 Error Messages Operating/Alarm LED off.

Cause Correction

Power pack not con-nected.

Connect power pack.

Power pack defec-tive.

Replace the defective power pack with an op-erational one.

Power supply missing.

Establish the power sup-ply.

PUII is booting. Wait several minutes until the LED illuminates.

Link/Traffic LED off.

Cause Correction

Network connection Connect RJ-45 network

Page 45: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 45

EN missing. cable.

Incorrect IP address. Check the IP address.

Incorrect subnet mask.

Check the subnet mask.

Incorrect gateway address.

Check the gateway ad-dress.

No access authorisation via Telnet.

Cause Correction

Telnet access for the PUII blocked.

Use the HyperTerminal to activate the Telnet access.

Incorrect IP ad-dress entered.

Check the IP address.

Incorrect user name entered.

Check the user name.

Incorrect pass-word entered.

Check the password.

No access authorisation via browser.

Cause Correction

Incorrect user name entered.

Check the user name.

Incorrect pass-word entered.

Check the password.

No access authorisation via HyperTerminal.

Cause Correction

Incorrect user name entered.

Check the user name.

Incorrect pass-word entered.

Check the password.

No settings can be made via browser.

Cause Correction

Web access set only to read au-thorisation.

Set the access authorisation using Hyperterminal or Tel-net in the Web Access menu item. Alternatively, the administra-tor must set the appropriate rights for the user in the web interface.

SNMP does not send (or traps do not arrive)

Cause Correction

The entries for the read and

Use HyperTerminal or Telnet to compare the read and

write authorisa-tion (read and write community) are not set cor-rectly.

write authorisation with the management software.

Trap receivers have not been entered.

Check the trap receivers.

Sensor not detected or not displayed.

Cause Correction

Sensor not con-tained in the software.

Perform a software update.

Sensor defective. Replace sensor.

Sensor not con-nected.

Connect sensor; if neces-sary, remove and reinsert the sensor several times. It sometimes helps to briefly insert a different sensor in order to directly switch back to the first sensor.

7.11 Structure of the MIB of the Process-ing Unit

Only the device-typical part of the MIB of the Proc-essing Unit (CMC-TC.MIB) is briefly described here. This part of the MIB in particular must satisfy the modular flexible system concept of the CMC-TC system. For this reason, the associated information that applies to the sensor units (e.g. I/O Unit, Ac-cess Unit, Climate Unit) and the downstream sen-sors or actuators is mainly shown in tables. A table for the sensors, the outputs/actuators and the messages is provided for each connectable Sensor Unit. It is possible to connect up to four Sen-sor Units to the Processing Unit. The number of table rows differs for each table type and depends on the maximum number of available ports for the Sensor Unit. Overview of the maximum table entries for each Sensor Unit.

Sensor Unit

Sensors Outputs Messages

I/O Unit 4 4 4

Access Unit

8 6 4

FCS 3 1 3

RTT 40 (4 per device)

RLCP 36 16 4

Page 46: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 46

EN Active PSM

12 (3 per module)

12 (3 per module)

12 (3 per module)

Climate Unit

2 1 3

Note that the number of possible sensors, outputs and messages is stored in the associated MIB vari-ables. Sensors:

Note! The numbers in column 2 correspond to the port numbers of the I/O Unit. The sen-sors are assigned in accordance with their physical connection. This table does not show the outputs, refer to the next table.

Outputs:

Note! The numbers in column 2 correspond to the port numbers of the I/O Unit. The shown outputs correspond to their physi-cal connection on the port.

Messages:

Note! The numbers in column 2 correspond to the port numbers of the I/O Unit. The shown table entries correspond to the current status and the configuration set-tings for the port.

Representation of the table and the sample table entries of the Access Unit Sensors:

Note! Column 2 indicates to which port the ac-cessory components are connected. Ports 1, 2, 3 and 7 correspond to door system 1; ports 4, 5, 6, and 8 correspond to door system 2.

Outputs:

Note! Column 2 indicates the physical connec-tion of the port assignment.

Messages:

Note! The shown table entries correspond to the current status and the configuration set-tings for the door closing system 1 or 2.

Representation of the table and the sample table entries of the Climate Unit Sensors:

Note! The numbers in column 2 correspond to the port numbers of the Climate Unit. The sensors are assigned in accordance with

Page 47: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 47

EN their physical connection. This table does not show the outputs, refer to the next table.

Outputs:

Note! Column 2 indicates the physical connec-tion and the status of the port.

Notifications:

Note! The numbers in column 2 correspond to the port numbers of the Climate Unit. The shown table entries correspond to the current status and the configuration set-tings for the port.

Representation of the general setup table and sample table entries Another table provides the general setup settings shown below.

7.12 ActivePSM (4-way) The ActivePSM modules are available in various configurations.

PSM module Configuration Model No.

Active 4-way 4x C13 7865.200

Active 8-way 8x C13 7856.201

Active 8-way 8x C13 (19") 7200.001

Active 6-way 2x C13, 4x C19 7856.204

Active 6-way 2x C13, 4x earthing contacts

7856.203

The information for the ActivePSM (4-way) de-scribed here also applies to the four other active

module types. Additional details for the other mod-ule types are contained in the associated operating instructions.

7.12.1 Getting Acquainted with the Mod-ule Connections

1

2 3

4

56 7

Fig. 34 ActivePSM (4-way)

Key: 1 Fuse (10 A thermal circuit-breaker). 2 Display element (display of the actual current value). 3 LED circuit 2 (depending on the installation position

and the configuration, the LED illuminates). 4 Connection to the Processing Unit or to the previous

module. 5 LED circuit 1 (depending on the installation position

and the configuration, the LED illuminates). 6 Pushbutton (used for configuring the module). 7 Connection to the next module (up to four modules

can be cascaded).

7.12.2 Display and Operating Elements 2-digit 7-segment display, digit height 10 mm, col-our: Red The 7-segment display shows the actual current value. In setting mode, it also shows the settings parameter. Up to a value of 9.9 A, the current is shown with one decimal place; above 10 A, the current is shown as integer value without decimal place. In a fault situation, this display flashes. Note that any changes made to the installation posi-tion also change the reading direction of the 7-segment display. Two 3-colour LEDs (green, orange, red), labelled "I" and "II". These LEDs each flash in accordance with the in-stallation position of the module.

Page 48: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 48

EN Parameter Explanation

Green OK

Orange Warning, fuse triggered or mains voltage missing.

Red Maximum current value ex-ceeded or minimum current value under-shot

Pushbutton: The pushbutton is used to enter or change the limit values, the BUS address and for the fixed definition of the reading direction of the display. Briefly pressing the pushbutton changes the setting value or the setting level. Press the pushbutton for a longer period (approx. 4 seconds) to confirm the set value or the preselected setting level.

7.12.3 Displays Parameter Explanation

Flashing dis-play

Current not within the limits.

0.0 displayed No consumers connected to the ActivePSM.

3.2, etc., dis-played

Consumers connected; their "consumed" current value is 3.2 A.

n.P. displayed "No power" means that no power is supplied to the PSM bus or the fuse has deactivated the system.

LED display green

Everything OK.

LED display red

Value not within the limits.

LED display orange

No voltage or fuse has deacti-vated the system.

A detailed description of the setting menu for the ActivePSM is contained on the next page.

7.12.4 Setup Menu for the Local Pushbutton

Important parameters must be set for the initial commissioning of the active 4-way PSM. The follow-ing list displays how the active 4-way PSM is set. Short press = UP Long press (approx. 4 seconds) = Enter

When no pushbutton is pressed for approximately five seconds, the system returns to the base display.

Actual current value base display

Enter

"L" dis-play

Enter Set the low limit value by pressing the pushbutton briefly.

Enter

"H" dis-play

Enter Set the high limit value by pressing the pushbutton briefly.

Enter

"A" dis-play

Enter Set the BUS address by pressing the pushbutton briefly.

Enter

"o" dis-play

Enter Set the display orien-tation: 1 = fixed circuit 1 2 = fixed circuit 2 3 = automatic

Enter

7.12.5 Connecting the ActivePSM to the CMC-TC

The ActivePSM is connected to the CMC-TC Proc-essing Unit II (in short, PUII) using one of the RJ45 connections of the Processing Unit. This socket also functions as the power supply for the module dis-play. The connection between the PUII and the Ac-tivePSM is made using a special adaptor cable and a Cat5 cable (7320.472). The adaptor cable is in-cluded in the scope of supply. The connecting ca-bles must not exceed the specified maximum length of 10 m, otherwise Rittal cannot warrant that the product will function correctly. Insert the Cat5 cable in the provided sockets of the PU and in the adaptor cable of the ActivePSM.

Note! Prior to the installation and commission-ing, read and observe the Installation and Operating Instructions, in particular, the contained safety notes.

These operating instructions are available in two languages as a downloadable PDF file at http://www.rimatrix5.com. Assembly Before commencing the installation, ensure the completeness of the scope of supply. Also ensure that the system complies with the admissible condi-tions of use, in particular, the permitted ambient temperatures and the required IP protection cate-gory.

Enter

Page 49: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 49

EN Integration of ActivePSM and PSM Busbars The ActivePSM is centred over the busbar’s plug connector and pressed on under gentle force. The ActivePSM is connected correctly when all four of the ActivePSM’s catches are engaged in the busbar. To remove the module from the bus, you must care-fully retract and withdraw all four catches at the same time. Ensure no consumers are connected to the sockets, otherwise they will be disconnected from the power supply when the module is removed from the bus-bar. In addition, you must note the direction in which the ActivePSM is connected. The busbar also serves as a redundant power supply, so the ActivePSM can be installed in either direction between Circuit 1 and Circuit 2. Power supply: The power is supplied to the Ac-tivePSM electronics from the CMC-TC Processing Unit II (PUII). This requires that the Category 5 patch cable is inserted in the RJ 45 socket of the PUII and in the adaptor cable of the ActivePSM. Up to four modules can be connected in series on a PUII channel. Unique addresses must be assigned for each module (1, 2, 3, 4).

Note! For the series connection of PSM mod-ules to the PUII, only one active PSM module type can be cascaded for each sensor unit input of the PUII. Example: Sensor input 1: 3x active PSM (4-way, 7865.200) Sensor input 2: 4x active PSM (8-way, 7856.201) Sensor input 3: 2x active PSM (8-way, 7200.001) Cascaded PSM modules must be num-bered consecutively (module 1= address 1, module 2 = address 2, etc.) If only one module is connected, address 1 must be specified here.

Once the ActivePSM is supplied with power, 0.0 A appears on the display. The display shows the im-mediate active current drawn by diverse consumers when they are connected to the sockets.

7.12.6 Monitoring Using a Browser

12

3

Fig. 35 ActivePSM browser display

Key 1 Current: Display of the actual current value of the

consumers (server, etc.) connected to the Ac-tivePSM.

2 Status: Indicates whether the specified current limit value is observed. A message will be issued if the current lies outside the limit values.

3 Position: Indicates the installation position (0° or 180°) of the associated module.

7.12.7 Configuring the ActivePSM Navigation

Main menu – Status – Click 1 Current

Parameter Explanation

1...n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Sensor status. Green = OK, red = alarm.

Message Text The message text which is also transferred when a warning message is sent. Enter here a designation that uniquely identi-fies your sensor, e.g. "Current Rack01".

Setpoint High Current limit which when over-shot causes an alarm message to be issued.

Setpoint Low Current limit which when over-shot causes an alarm message to be issued.

Page 50: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 50

EN Delay Time in seconds how long the power socket should remain switched off.

Relay Output Off = manual disable of the PSM module; On = manual enable of the PSM module.

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

Navigation

Main menu – Status – Click 2 Status

Parameter Explanation

1...n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Sensor status. Green = OK, red = alarm.

Alarm Relay Whether (enable) or not (dis-able) an alarm relay should switch in the event of an alarm.

Alarm Beeper Whether (enable) or not (dis-able) an audio signal should be issued in the event of an alarm.

Alarm Reset Should an alarm be acknowl-edged automatically (Auto) or does it need to be acknowl-edged by the administrator (Manual).

Trap Receiver Specify which of the entered trap receivers is to be sent status messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-

rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

Navigation

Main menu – Status – Click 3 Position

Parameter Explanation

1...n Connection number of the sen-sor.

Type Sensor type. Will be detected automatically.

Sensor Status Sensor status. Black = Circuit 1, blue = Circuit 2

Trap Receiver Specify which of the entered trap receivers is to be sent alarm messages. Enter the trap receivers at 7.3.2 Configuring the Trap Receiver.

Scheduled Alarm Off

Specify which alarm configura-tion should be enabled or dis-abled. The individual functions can be setup from the "Setup – Timer" menu item.

Send SMS You can enter up to four mobile wireless numbers that you en-tered previously at Setup – SMS Unit; each number is separated with the ampersand character "&" (e.g. 1&2&3&4).

Send E-Mail You can enter up to four e-mail addresses that you entered previously at Setup – E-Mail (SMTP); each number is sepa-rated with the ampersand char-acter "&" (e.g. 1&2&3&4).

Accept Accept the changes.

Reset Reset all settings to the values saved most recently; any changes are not accepted.

Page 51: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Operation 7

CMC-TC Processing Unit II 51

EN 7.13 Metered PSM

Note! The installation and commissioning of the PSM busbars with measurement is de-scribed in the operating guide for the Metered PSM.

7.14 Monitoring the LCP and RTT I/O Unit

The LCP/RTT I/O unit is connected to the CMC-TC Processing Unit II (in short PUII) using one of the four RJ45 connections.

Note! The installation and commissioning of the LCP and RTT-I/O unit is described in the operating instructions for the LCP or RTT I/O unit.

Power

24 VDCmax. 2,5 AI0I0I

1P-I C21 243

1

I0I0I

1 2 3 4

2

Fig. 36 Establishing the sensor connection

Key 1 Sensor units connections (1-4) 2 Status LEDs for connected sensor units The network connection of the PUII (item 1) is made using the network cable with RJ45 plug in the exist-ing Ethernet network structure. The data connection exists when the appropriate Link LED (item 2) illuminates green/orange. Estab-lishing the connection for the RTT I/O unit can take as long as 70 seconds.

7.15 Access Control Using an External Access File

An extended access control is integrated in the Processing Unit II software. The access codes can be edited using a text file sent by FTP to the PUII. This form of access control has the following proper-ties: a keypad (or card reader) can be used to control up to eight doors on four Access Units. Up to 200 different codes can be stored (each code can release up to eight doors concurrently). If several identical codes with different authorisa-tions are entered, only the first entry will be used. The file must have the name 'access.cmc' and can be created and edited using any ASCII text editor (e.g. Notepad). A line with the following syntax must be created for each access code:

Page 52: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

7 Operation

CMC-TC Processing Unit II 52

EN "1234" , "0102" = user

User identification:

This optional maxi-mum 8-digit decimal number (10000-99999999) can be used to specify whether a user identi-fication will be sent with the trap message.

Separator: (e.g. '=')

Door release: This 4-digit number contains a decimal number 0...3 for each of the four possible Access Units. This number specifies which door is to be released: 0 - do not release any door 1 - release door 1 2 - release door 2 3 - release door 1 and 2 This number must always contain four digits, irrespective of how many Access Units are connected; a '0' must be specified for any Access Units that are not present.

Separator: (e.g. comma)

Release code: This 4-digit decimal number con-tains the release code entered from the keypad or entered on the magnetic card or chip card. The release code can have the number 0001 to 9999; four digits must always be entered. In contrast to the code input from the web page, no range can be entered here. A unique 4-digit deci-mal number must always be specified.

The normal access control is voided when this ac-cess file is copied to the Processing Unit II, i.e. the codes stored in the file now have priority. To reacti-vate the normal access control, the file must be deleted using FTP. This causes all access authori-sations to be lost and new authorisations must be entered. To enter the default values, a reboot must be performed after the file has been deleted. The transfer to the Processing Unit II is made with FTP by the 'admin' user. The file must be transferred to the 'upload' directory. It is possible to connect up to eight keypads (or card readers) to the system. This requires, however, that a door (handle and access sensor) is present at the connection to which the keypad (card reader) is connected. These maximum eight keypads (card readers) all have the same authority. This means, irrespective where the code is entered, the door(s) specified in the access file will be released.

7.16 Saving and Transferring Configura-tion Files

This function can be used to save the configuration for the CMC-TC system and, if necessary, restore it to the system later. The configuration can also be transferred to other CMC-TC systems that have the identical wiring and construction.

Note! Warning, this function may only be used when the CMC-TC systems are identical with regard to: - sensor types and the used ports - sensor units and the used ports and addresses - software versions In addition, no sensors or sensor units may be missing or connected in a differ-ent sequence. If these conditions are not observed, the PUII system will not accept the configura-tion.

Save configuration files: Once the commissioning, installation and the set-tings of all text items, limit values, links, network settings, etc., has been completed, this information can be saved on an external system (network PC). The FTP or SFTP protocol can be used to establish access to the Download directory in the PUII. The three files can be loaded and saved on a net-work PC there. cmc.cfg System data (cannot be edited) cmc.user User administration data

(cannot be edited) net.cfg Network settings (can be edited) The changes are accepted immediately after trans-ferring the file. The correctness of the transfer can be seen in the event log.

Note! Warning, during the editing of the net.cfg file, under no circumstances may the for-mat or the file structure be changed. If this is not observed, the system may suffer a complete failure.

Transferring configuration files: Prerequisite -> The three configuration files have been saved beforehand. The FTP or SFTP protocol can be used to establish access to the Upload directory in the PUII.

Page 53: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Maintenance and Cleaning 8

CMC-TC Processing Unit II 53

EN Configuration files on the target device to which transfers are made: cmc.cfg Installation data (cannot be edited) cmc.user User administration data

(cannot be edited) net.cfg Network settings (can be edited)

8 Maintenance and Cleaning The Rittal CMC-TC Processing Unit is a mainte-nance-free system. The housing does not need to be opened for the installation or during operation.

Note! Opening the housing or any accessory components will void any warranty and liability claims.

8.1.1 Cleaning

Warning!

Danger of damage! Do not use any aggressive sub-stances, such as white spirit, acid, etc., for cleaning because such sub-stances can damage the unit.

Use a slightly moistened soft cloth to clean the housing.

9 Storage and Disposal

9.1.1 Storage If the device is not used for a longer period, we rec-ommend that it is disconnected from the mains power supply and protected from dampness and dust. Further information concerning the operating condi-tions is contained in the technical specifications.

9.1.2 Disposal Because the CMC-TC Processing Unit consists primarily of the housing and PCB, the unit must be disposed of through the electronic waste recycling system when it is no longer required.

Page 54: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

10 Changes from software version 2.6

CMC-TC Processing Unit II 54

EN 10 Changes from software ver-sion 2.6

A number of changes and new functions have been implemented in various areas of the CMC-TC Proc-essing Unit II from software version 2.6. These amendments are documented in this chapter.

10.1 Language selection for the browser interface

The menu item Setup > General > Language (German: Einstellung > Allgemein > Sprache) permits you to switch between the English and German versions of the browser interface. This language setting is used not only for the browser interface, but also for log files, e-mail texts, SMS texts and the display output.

10.2 Extended options under “Combina-tions”

Switching combinations, e.g. for the digital relay output module (see Chapter 7.7.14), were in the past limited to combinations of two sensor values. From software version 2.6, it is possible to define logical combinations of up to four sensors. To this end, the sensors are first configured in two “groups” of two sensors each. These groups can then be combined by way of a further AND or OR operation.

1

2

3

Fig. 37 Extended “Combinations” configuration

Key 1 Group 1: Combination of the first two sensors.

The sensors and logic operation can be chosen freely using any of the connected sensors.

2 Group 2: Combination of sensors 3 and 4. The sensors and logic operation can be chosen freely using any of the connected sensors.

3 Combination of the two groups (AND/OR opera-tion). The final result then controls triggering of the action. In this example, the door is unlocked.

10.3 New functions for the alarm and event log

Two new functions have been added to the alarm and event log (see Chapter 7.6.8): Delete and Re-fresh.

1 2 Fig. 38 Alarm and event log

Key 1 Delete button: Deletes all entries from the log. 2 Refresh button: Refreshes the log page and

displays the latest log entries.

10.4 Test functions for traps, e-mail, SMS and pings

The alarm simulation menu is called via the menu item Administration > Admin > Simulation. It is here possible to test the e-mail, SMS and trap func-tions, and to send a ping to a specified IP address.

1

2 3 4

Fig. 39 Alarm simulation menu

Page 55: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Changes from software version 2.6 10

CMC-TC Processing Unit II 55

EN Key 1 Sends a test e-mail to all e-mail addresses entered

under Setup > Email 2 Sends a test SMS to all telephone numbers entered

under Setup > SMS-Unit 3 Sends a test trap to all entered and enabled trap

receivers (see Chapter 7.3.2) 4 Sends a ping to the specified IP address

10.5 Scaling of the 4...20 mA sensor in-puts of the input module

In the settings for the analog sensor input module 7320.520, it is now possible to define start and end values for automatic scaling of the output. In other words, you can specify which measurement values are to correspond to an input of 4 mA or 20 mA. During operation, the Processing Unit II then con-verts the current input value accordingly before out-putting the corresponding measurement value. It is furthermore possible to specify the unit to be displayed with the measurement values. This serves to simplify evaluation and improves display clarity when using this universal sensor option.

10.6 Server shutdown function The function Setup > Shutdown can be used to shut servers down conditionally via the Processing Unit II. The prerequisite is that an RCCMD client must be installed on the target servers.

Note! The installation file for the RCCMD client can be downloaded from www.rimatrix5.com under Ser-vice&Support > Downloads. A 30-day test licence is also available there.

1

2

3

4

5

6 Fig. 40 Server shutdown configuration

Key 1 Tabs for the 4 server groups. Each group controls

up to 10 servers. 2 Group 1: Combination of the first two sensors. The

sensors and logic operation can be chosen freely using any of the connected sensors.

3 Group 2: Combination of sensors 3 and 4. The sen-sors and logic operation can be chosen freely using any of the connected sensors.

4 Combination of the two groups (AND/OR operation). The final result then triggers the shutdown of the server group.

5 Each line contains settings for one server. Server Name: Freely chosen server name. IP Address: IP address of the server. Port: Port used to communicate with the RCCMD client (default: 6003). Delay: Delay in seconds before the shutdown com-mand is sent to the server when the switching condi-tions are met (point 4). Enable: If this check box is marked, the server is shut down if the switching conditions are met (point 4). In addition, the connection to this server will be tested when the Test button (point 6) is clicked.

6 Test button to test the connections to the servers.

Page 56: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

10 Changes from software version 2.6

CMC-TC Processing Unit II 56

EN

Note! The Test button does not send shut-down commands to the servers! It merely checks whether communication with the specified servers is possible. This test is performed for all the servers on all four tabs for which the Enable check box is marked.

A maximum of four sensor values, configured in two groups as for the general switching combinations (see chapter 10.2), can be used to shut the servers down on the basis of defined conditions. The tabs 1 to 4 permit the configuration of four server groups. Within each group, up to 10 servers can be sent a shutdown command on the basis of the specified sensor conditions. The conditions must be defined individually for each server group.

10.7 Configuration of automatic door opening

Fig. 41 shows the configuration screen for the Automatic Door Opening Control Unit 7320.790. Observe also the instructions given in the user manual enclosed with the unit.

1

2

4

3

Fig. 41 Configuration of automatic door opening

Key 1 Current status of the door control. 2 Time for which the contact remains open upon

opening before switching back to the status closed. 3 Timeout response of the door control.

Stay: Current status is maintained Open: Door control opens Close: Door control closes

4 Manual switching of the door control. It is necessary to confirm the action by clicking on Accept

Page 57: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Changes from software version 2.6 10

CMC-TC Processing Unit II 57

EN 10.8 Delayed alarms To prevent a warning or alarm being issued in case of insignificant short-time fluctuations, it is possible to define a delay time for each sensor.

1

Fig. 42 Configuration of delayed alarms

Key 1 Alarm Delay: Delay between exceeding of the

threshold value and actual issuing of an alarm. The time must be specified in seconds (between 0 and 999 seconds).

The “Alarm Delay” value defines how long a thresh-old value must be exceeded before the correspond-ing warning or alarm is issued. Example of a temperature sensor: If the alarm delay is set to 120 seconds and the threshold for a warn-ing is set to 50°C, an increase in temperature to 55°C will only result in a warning being issued if this excess temperature is measured for at least 120 seconds. If the measurement falls back below 50°C after 60 seconds, for example, no warning will be issued, despite the fact that the temperature was for a time above the defined threshold value.

Note! It is not possible to enter “Alarm Delay” values for ActivePSM busbars/modules.

10.9 Protection against cross-site script-ing (XSS)

As protection against a cross-site scripting attack, the input fields of the browser interface, e.g. the message texts, accept only a certain set of charac-ters. The permissible characters are:

• A-Z, a-z • 0-9 • _.,;=+:?/%$*@-&() • Space

All other characters are deemed invalid and are automatically rejected.

Page 58: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

11 Customer Service

CMC-TC Processing Unit II 58

EN 11 Customer Service If you have any technical questions or questions concerning our product spectrum, contact the follow-ing service address: Tel.: +49 (0)2772/505-1855 http://www.rimatrix5.de E-mail: [email protected]

Note! To allow us to process your enquiry quickly and correctly, please always specify the article number in the subject line for e-mails.

Further information and the current operating guides and updates of the Rittal CMC-TC are available for download under Security on the Rimatrix5 home-page.

12 Technical Specifications Designation CMC-TC

Housing

Housing type Plastic covering with metal trim

Height 1 U / 44.5 mm

Width 136 mm

Depth 129 mm

Weight without packaging

approx. 0.6 kg

Potential equa-lisation

- 1)

Earthing - 1)

Protection category

IP 40 to EN 60529

Interfaces

Pushbuttons 1 membrane pushbutton, ac-knowledge pushbutton

Front socket 1 x RJ10 socket (RS 232 serial interface)

LED display 6 x (active/alarm, link, for each connectable sensor island)

Acoustic signal 1 x piezo signal transmitter

I2C connection RJ45 socket (P-I2C), shielded

Alarm relay

Output 1 x RJ12 socket, shielded

Configuration Potential-free change-over contact

Rated voltage 24 V DC, internal or 24 V for external power supply

Current 200 mA

Operational area

Temperature +5 to +45 °C +42 to +113 °F

Humidity 5 – 95 %

Storage tem-perature

-20 to +60 °C -4 to +140 °F

Rated voltage 1 x 24 V DC 2.5 A SELV

Fuse Miniature fuse T2A, 250 V, UL approval

Network 1 x RJ-45 socket (Ethernet, 10/100 BaseT), shielded

Sensor island 4 x RJ45 sockets, shielded, for shielded twisted-pair patch cable, Category 5

Page 59: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Technical Glossary 13

CMC-TC Processing Unit II 59

EN Maximum cable length

PU to I/O Unit 10 m, after consultation with Rittal maximum 50 m, UL approval

PU to the Ac-cess Unit

10 m, after consultation with Rittal maximum 50 m, UL approval

PU to the Cli-mate Unit

10 m, after consultation with Rittal maximum 50 m, UL approval

PU to the Wireless I/O Unit

10 m, after consultation with Rittal maximum 50 m

Protocols

Available protocols

- TCP/IP - SNMP v1 (incl. MIB II) - SNMP v3 - TELNET, SSH - FTP, SFTP - http, https, SSL 3.0 - NTP - DHCP

Technical Specifications 1) Not required because safety extra-low voltage 24 V DC

13 Technical Glossary CMC-TC CMC-TC (Computer Multi Control – Top Concept) is a Rittal product used to monitor network enclosure components. GSM card A GSM card is a telephone card for a mobile tele-phone. Internet browser An Internet browser can be used to display html pages (and pages that conform to a similar stan-dard). In the case of CMC-TC PU, they can be con-figured using a user interface displayed with an Internet browser. Link A link causes a jump to another Internet page or establishes a connection between two Internet pages. MAC address The MAC address is a unique combination of alpha-betic characters and digits assigned to a network interface that may be assigned just once throughout the world. One of its uses is to identify a network interface in a network.

MIB (Management Information Base) The MIB was developed to fetch and change net-work elements. The MIB II was defined in the RFC 1213. Some manufacturers define their own MIBs that provide information about the special properties of their product. The MIBs are registered for the OID with the IANA (Internet Assigned Numbers Author-ity). Once an object has been assigned to an OID, the meaning can no longer be changed. There also cannot be any overlapping with other OIDs. SMS service number This is a telephone number that the telephone pro-vider makes available for sending SMS messages. SNMP (Simple Network Management Protocol) The SNMP is a simple network management proto-col based on TCP/IP. It was developed to monitor network components on a central management station. Telnet Telnet is a protocol for guest access to a remote server. The Telnet program provides the required client functions of the protocol. Trap Trap is the sending of SNMP messages. Trap Receiver The trap receiver is the receiver of SNMP mes-sages. Web Access The Web Access is used to define the access pos-sibility via the Internet.

Page 60: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

14 Declaration of Conformity

CMC-TC Processing Unit II 60

EN 14 Declaration of Conformity

Page 61: Anleitung CMC-TC Processing Unit II - Rittal · Documentation Notes 1 CMC-TC Processing Unit II 5 1 Documentation Notes EN The audience for this guide is the technical special-ists

Declaration of Conformity 14

CMC-TC Processing Unit II 61

EN