School of Built and Natural Environment Ellison Building Newcastle Upon Tyne NE1 8ST Tel: 0191 227 4722 Fax: 0191 227 3167 Page 1 of 26 An Inter-program Analysis of Computational Fluid Dynamics Based on PHOENICS and DesignBuilder Software Aim The aim of this work is to compare the computational fluid dynamics (CFD) simulation performance provided by DesignBuilder software with a specialist commercial CFD modelling package Phoenics. Particular emphasis is placed on temperature and velocity fields within a typical built environment space including typical heating, ventilating and air condition (HVAC) components. Introduction DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort in buildings including HVAC plant. It provides results compatible with a number of energy and carbon labelling schemes such as UK Energy Performance Certificates, UK Building Regulation Compliance, UK BREEAM and US Green building Council LEED assessments. It also includes a CFD modelling capability specifically adapted for analysing air movement and ventilation problems within building spaces. The results reported in this document deal with the latter only. Phoenics is a CFD simulation package which is able to solve a wide range of industrial fluid flow problems including fluid flow in free fields, developing and fully-developed flow, flow in pipes and ducts, heat and mass transfer, chemical reaction and combustion. Phoenics is used in this project because of its advantage in dealing with CFD modelling applied to HVAC components, by means of a specialist environment called FLAIR. The nature of this work is to compare simulation results from four specific heating or cooling scenarios, and verify the DesignBuilder results against those obtained for the same test cases from Phoenics. This work is based on Phoenics version 2009 and DesignBuilder version 2.3.5.020 BETA

Transcript of An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy...

Page 1: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 1 of 26

An Inter-program Analysis of Computational Fluid Dynamics Based on

PHOENICS and DesignBuilder Software

Aim

The aim of this work is to compare the computational fluid dynamics (CFD) simulation performance

provided by DesignBuilder software with a specialist commercial CFD modelling package – Phoenics.

Particular emphasis is placed on temperature and velocity fields within a typical built environment

space including typical heating, ventilating and air condition (HVAC) components.

Introduction

DesignBuilder is a generic energy simulation program for the built environment for the modelling of

energy and comfort in buildings including HVAC plant. It provides results compatible with a number

of energy and carbon labelling schemes such as UK Energy Performance Certificates, UK Building

Regulation Compliance, UK BREEAM and US Green building Council LEED assessments. It also

includes a CFD modelling capability specifically adapted for analysing air movement and ventilation

problems within building spaces. The results reported in this document deal with the latter only.

Phoenics is a CFD simulation package which is able to solve a wide range of industrial fluid flow

problems including fluid flow in free fields, developing and fully-developed flow, flow in pipes and

ducts, heat and mass transfer, chemical reaction and combustion. Phoenics is used in this project

because of its advantage in dealing with CFD modelling applied to HVAC components, by means of a

specialist environment called FLAIR.

The nature of this work is to compare simulation results from four specific heating or cooling

scenarios, and verify the DesignBuilder results against those obtained for the same test cases from

Phoenics. This work is based on Phoenics version 2009 and DesignBuilder version 2.3.5.020 BETA

Page 2: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 2 of 26

Methodology

Four test cases have been designed for this comparison study represented by four different heating

and cooling scenarios in a typical built environment space. All cases are simulated within both

software packages under nominally identical numerical settings and boundary conditions. The small

number of instances in which identical settings could not be made are identified in the following.

The geometry of the test cases:

All cases comprise a single rectangular room with the size of 4.2m x 3.6m x 2.7m (high). There are

two isothermal cases focusing on the air distribution in the room. The other cases concentrate on

the natural and mixed convection heat transfer in the room.

For the isothermal cases (A & B), a supply diffuser with an overall dimension of 0.2m x 0.1m is

positioned at the centre of the west-facing wall at a distance of 0.2m from the ceiling to the top

edge of the diffuser. The discharge angle of the diffuser is 45° upwards from the horizontal. There

are two extract grilles located in the north-east and south-east corners of the ceiling, with a distance

of 0.2m from the upper edge of the north- and east-facing walls or south- and east-facing walls. The

dimensions of the extract grilles are 0.3m x 0.3m.

For the convection cases (C & D), there is a

window located in the south-facing wall, at a

distance of 0.8m from the floor and 0.2m from

the side walls. In case C (natural convection), a

single panel radiator with a dimension of 2m x

1m x 0.05m is added to the room, which is

located 0.1m in front of the south-facing wall

and 0.1m above the floor.

Page 3: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 3 of 26

The boundary conditions of the four cases are as follows:

A. Isothermal forced convection with a

supply air diffuser, two extract grilles

Air flow rate = 0.034m3/s, discharge

velocity = 3.0m/s

B. Isothermal forced convection with supply air diffuser, extract grilles and obstruction to

the air flow

Air flow rate = 0.034m3/s, discharge velocity = 3.0m/s

The obstruction is in the form of a beam which spans the width of the space and is

located adjacent to the ceiling equidistant between the east- and west-facing walls. The

dimensions of the beam are 3.6m x 0.2m x 0.4m.

Page 4: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 4 of 26

C. Natural convection – winter heating natural convection with radiator located beneath a

cold window

Radiator surface temperature = 75°C

Wall/ ceiling/ floor surface temperatures = 17°C

Window surface temperature = 5°C

D. Mixed convection – summer cooling mixed convection with supply diffuser and extract

grilles

Air flow rate = 0.034m3/s, discharge velocity = 3.0m/s

Supply air temperature = 17°C

Wall/ ceiling/ floor surface temperatures = 23°C

Window surface temperature = 32°C

Page 5: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 5 of 26

Numerical Model setting:

DesignBuilder Phoenics

Algorithm Simpler Simplest

Turbulence model standard k-e with wall functions standard k-e with wall functions

Discretisation scheme first order upwind first order upwind

Mesh size 0.1m 0.1m

Results:

Cases A and B are isothermal cases; the air is delivered to the room at a mean velocity of 3m/s

through a wall mounted diffuser. Only the air velocity distribution is of relevance in these two cases.

Velocity profiles developed across the middle of the room, from the west to east wall and

perpendicular with the diffuser, are plotted. Plotting in both programs is carried out at each 0.1m

increment from the diffuser, from the floor to ceiling level across the room. The average root mean

square (RMS) difference of the DesignBuilder results with reference to the Phoenics results of

velocity is 0.03 for both cases. The differences in predicted velocity fields are likely to be due ,at

least in part, to the slightly different approaches to diffuser discharge velocity calculations.

DesignBuilder uses the mean velocity and discharge angle to determine the air distribution from the

diffuser, while Phoenics uses either effective area, or throw distance, terminal velocity and a decay

constant.

In case B, the RMS difference between the two predictions reduces significantly at a distance of

2.05m from the diffuser and reduces gradually with further distance. The reduction of the RMS

differences appears to be due to the significant drop of air velocity arising from the ceiling

obstruction in this case.

Page 6: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 6 of 26

Velocity contours of case A from Phoenics (west to east plane)

Velocity contours of case A from DesignBuilder (west to east plane)

Page 7: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 7 of 26

Velocity contours of case B from Phoenics (west to east plane)

Velocity contours of case B from DesignBuilder (west to east plane)

Page 8: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 8 of 26

0

0.2

0.4

0.6

0.8

1

1.2

0.0

50

.15

0.2

50

.35

0.4

50

.55

0.6

50

.75

0.8

50

.95

1.0

51

.15

1.2

51

.35

1.4

51

.55

1.6

51

.75

1.8

51

.95

2.0

52

.15

2.2

52

.35

2.4

52

.55

2.6

52

.75

2.8

52

.95

3.0

53

.15

3.2

53

.35

3.4

53

.55

3.6

53

.75

3.8

53

.95

4.0

54

.15

Vel

oci

ty (

m/s

)

distances from the diffuser wall (west wall) (m)

Case ARMS differences of velocity across the room

0

0.2

0.4

0.6

0.8

1

1.2

0.0

50

.15

0.2

50

.35

0.4

50

.55

0.6

50

.75

0.8

50

.95

1.0

51

.15

1.2

51

.35

1.4

51

.55

1.6

51

.75

1.8

51

.95

2.0

52

.15

2.2

52

.35

2.4

52

.55

2.6

52

.75

2.8

52

.95

3.0

53

.15

3.2

53

.35

3.4

53

.55

3.6

53

.75

3.8

53

.95

4.0

54

.15

Vel

oci

ty (

m/s

)

distances from the diffuser wall (west wall) (m)

Case BRMS differences of velocity across the room

Page 9: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 9 of 26

Case C is a natural convective heat transfer case with a radiator fixed beneath a cold window on the

south wall. Both the air velocity and temperature distributions within the space are considered in

this case. Results are plotted at every 0.1m away from the source, (i.e. the radiator) from south to

north over the full height of the room, perpendicular with the radiator surface. The radiator is fixed

at 0.15m away from the window.

The average RMS difference between temperature and velocity predictions from DesignBuilder are

0.13 and 0.01 (across the entire room) with respect to the Phoenics results, respectively. The results

taken from 0.2m away from the radiator (i.e. 0.35m away from the window) to the end of the room

(north wall) yield a relatively low RMS difference of 0.23 or less. In addition, the details of

temperature comparison between both programs at three representative locations (close to the

south wall/window/radiator, middle of the room, close to the north wall) demonstrate a reasonably

good agreement between Phoenics and DesignBuilder simulations on natural convective heat

transfer in an upward direction (from floor to ceiling).

For the velocity measurement, the average RMS difference across the whole measurement plane is

relatively low, only 0.01.

Page 10: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 10 of 26

Temperature contours of case C from Phoenics (south to north plane)

Temperature contours of case C from DesignBuilder (south to north plane)

Page 11: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 11 of 26

0

0.2

0.4

0.6

0.8

1

1.2

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9 1

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9 2

2.1

2.2

2.3

2.4

2.5

2.6

2.7

2.8

2.9 3

3.1

3.2

3.3

3.4

Tem

per

atu

re (°c

)

distances from the radiator (south wall) (m)

Case CRMS differences of temperature across the room

0

0.2

0.4

0.6

0.8

1

1.2

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9 1

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9 2

2.1

2.2

2.3

2.4

2.5

2.6

2.7

2.8

2.9 3

3.1

3.2

3.3

3.4

Vel

oci

ty (

m/s

)

distances away from the raditor (south wall) (m)

Case CRMS differences of velocity across the room

Page 12: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 12 of 26

Case D represents a summer cooling scenario with mixed convection heat transfer within the space.

There are two sources applied in this case, including a wall mounted diffuser on the west wall and a

warm window surface on the south wall. Therefore, all relevant parameters are plotted in two

directions, from south to north and west to east according to the centreline of the room, at

increments of 0.1m away from the sources. The average RMS differences in the prediction of

temperatures across the room are 0.07 (from south to north direction) and 0.06 (from west to east

direction), while the average RMS differences in the prediction of velocity are 0.03 (from south to

north direction) and 0.06 (from west to east direction). All RMS differences in this case are all below

0.07, representing a high level of agreement between the DesignBuilder and Phoenics simulations.

The difference in the prediction of velocity arising next to the diffuser outlet (RMS = 0.27), and is

similar to case A and B likely to be due, again, to slightly different velocity calculation approaches for

the diffuser model used in both programs.

Differences in temperature prediction are thought to be due, in part, to possible differences in the

temperature wall functions adopted by the different programs.

Page 13: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 13 of 26

Temperature contours of case D from Phoenics (south to north plane)

Temperature contours of case D from DesignBuilder (south to north plane)

Page 14: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 14 of 26

0

0.2

0.4

0.6

0.8

1

1.2

0.0

5

0.1

5

0.2

5

0.3

5

0.4

5

0.5

5

0.6

5

0.7

5

0.8

5

0.9

5

1.0

5

1.1

5

1.2

5

1.3

5

1.4

5

1.5

5

1.6

5

1.8

1.9

5

2.0

5

2.1

5

2.2

5

2.3

5

2.4

5

2.5

5

2.6

5

2.7

5

2.8

5

2.9

5

3.0

5

3.1

5

3.2

5

3.3

5

3.4

5

3.5

5

Tem

per

atu

re (°c

)

distances from the window (south wall) (m)

Case D (south to north plane) RMS differences of temperature across the room

0

0.2

0.4

0.6

0.8

1

1.2

0.0

5

0.1

5

0.2

5

0.3

5

0.4

5

0.5

5

0.6

5

0.7

5

0.8

5

0.9

5

1.0

5

1.1

5

1.2

5

1.3

5

1.4

5

1.5

5

1.6

5

1.8

1.9

5

2.0

5

2.1

5

2.2

5

2.3

5

2.4

5

2.5

5

2.6

5

2.7

5

2.8

5

2.9

5

3.0

5

3.1

5

3.2

5

3.3

5

3.4

5

3.5

5

Vel

oci

ty (

m/s

)

distances from the window (south wall) (m)

Case D (south to north plane)RMS differences of velocity across the room

Page 15: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 15 of 26

Temperature contours of case D from Phoenics (west to east plane)

Temperature contours of case D from DesignBuilder (west to east plane)

Page 16: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 16 of 26

0

0.2

0.4

0.6

0.8

1

1.2

0.0

50

.15

0.2

50

.35

0.4

50

.55

0.6

50

.75

0.8

50

.95

1.0

51

.15

1.2

51

.35

1.4

51

.55

1.6

51

.75

1.8

51

.95

2.0

52

.15

2.2

52

.35

2.4

52

.55

2.6

52

.75

2.8

52

.95

3.0

53

.15

3.2

53

.35

3.4

53

.55

3.6

53

.75

3.8

53

.95

4.0

54

.15

Tem

per

atu

re (°c

)

distances from the diffuser wall (west wall) (m)

Case D (west to east plane)RMS differences of temperature across the room

0

0.2

0.4

0.6

0.8

1

1.2

0.0

50

.15

0.2

50

.35

0.4

50

.55

0.6

50

.75

0.8

50

.95

1.0

51

.15

1.2

51

.35

1.4

51

.55

1.6

51

.75

1.8

51

.95

2.0

52

.15

2.2

52

.35

2.4

52

.55

2.6

52

.75

2.8

52

.95

3.0

53

.15

3.2

53

.35

3.4

53

.55

3.6

53

.75

3.8

53

.95

4.0

54

.15

Vel

oci

ty (

m/s

)

distances from the diffuser wall (west wall) (m)

Case D (west to east plane)RMS differences of velocity across the room

Page 17: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 17 of 26

Discussion

Small differences in the prediction of velocity and temperature fields are thought to be largely due

to the different diffuser models used and possible differences in temperature wall function,

respectively.

In all four test cases, the temperature and velocity distributions across the room predicted by

DesignBuilder compare favourably with those simulated by Phoenics.. The average RMS differences

in the prediction of velocity across the room in each individual case is equal to, or less than, 0.06.

The accuracy of a typical air velocity meter is about +/- 3% to 5% of the reading. In cases A, B & D,

the air is delivered to the room at 3m/s from the diffuser outlet and hence the maximum acceptable

range of errors is about 0.09 to 0.15 m/s (apart from the velocity measurement next to the diffuser

outlet at 0.05m over the maximum range of errors; all other measurements at further locations are

within or below the this range). Thus the predictions from both programs agree to within a

reasonable tolerance for practical measurement.

For temperatures, the average RMS difference in predictions between the two programs in case C

and D across the centreline of the room are 0.13 in case C, and 0.07 (south to north) and 0.06 (west

to east) in case D. The accuracy of typical air temperature sensor for room air is 0.2K for a high-

specification sensor. The calculated RMS differences in prediction for temperature from these two

programs are, therefore, practically within the minimum range of uncertainty that might be

expected from practical measurements.

Page 18: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 18 of 26

Conclusion

In this inter-program comparison exercise, the relatively low RMS differences between predicted

results from the two programs considered in four contrasting built environment test cases suggest

that the CFD modelling capability of DesignBuilder software is comparable with a high-exposure

specialist CFD package.

Page 19: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 19 of 26

Appendix

Case A Velocity profiles

0

0.5

1

1.5

2

2.5

3

0 0.1 0.2 0.3 0.4 0.5

Me

tre

ab

ove

th

e f

loo

r (

m)

Velocity in the y-z plane (m/s)

Velocity profile from floor to ceiling (middle of the plane)

0

0.5

1

1.5

2

2.5

3

0 0.5 1 1.5 2

Me

tre

ab

ove

th

e f

loo

r (

m)

Velocity in the y-z plane (m/s)

Velocity profile from floor to ceiling (near west wall - diffuser)

Design Builder

Phoenics

0

0.5

1

1.5

2

2.5

3

0 0.1 0.2 0.3 0.4 0.5

Me

tre

ab

ove

th

e f

loo

r (

m)

Velocity in the y-z plane (m/s)

Velocity profile from floor to ceiling (near east wall)

Page 20: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 20 of 26

Case B Velocity profiles

0

0.5

1

1.5

2

2.5

3

0 0.5 1 1.5 2

Me

tre

ab

ove

th

e f

loo

r (

m)

Velocity in the y-z plane (m/s)

Velocity profile from floor to ceiling (near west wall - diffuser)

Design Builder

Phoenics

0

0.5

1

1.5

2

2.5

3

0 0.1 0.2 0.3 0.4 0.5

Me

tre

ab

ove

th

e f

loo

r (

m)

Velocity in the y-z plane (m/s)

Velocity profile from floor to ceiling (middle of the plane)

0

0.5

1

1.5

2

2.5

3

0 0.1 0.2 0.3 0.4 0.5

Me

tre

ab

ove

th

e f

loo

r (

m)

Velocity in the y-z plane (m/s)

Velocity profile from floor to ceiling (near east wall)

Page 21: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 21 of 26

Case C Temperature profiles

0

0.5

1

1.5

2

2.5

3

15 16 17 18 19 20 21 22 23 24 25

Me

tre

ab

ove

th

e f

loo

r (

m)

temperature in the x-z plane (°c)

Temperature profile from floor to ceiling (middle of the plane)

0

0.5

1

1.5

2

2.5

3

15 16 17 18 19 20 21 22 23 24 25

Me

tre

ab

ove

th

e f

loo

r (

m)

temperature in the x-z plane (°c)

Temperature profile from floor to ceiling (near north wall)

0

0.5

1

1.5

2

2.5

3

15 16 17 18 19 20 21 22 23

Me

tre

ab

ove

th

e f

loo

r (

m)

temperature in the x-z plane (°c)

Temperature profile from floor to ceiling (near radiator)

Design Builder

Phoenics

Page 22: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 22 of 26

Case C Velocity profiles

0

0.5

1

1.5

2

2.5

3

0 0.1 0.2 0.3 0.4 0.5

Me

tre

ab

ove

th

e f

loo

r (

m)

velocity in the x-z plane (m/s)

Velocity profile from floor to ceiling (near north wall)

0

0.5

1

1.5

2

2.5

3

0 0.1 0.2 0.3 0.4 0.5

Me

tre

ab

ove

th

e f

loo

r (

m)

velocity in the x-z plane (m/s)

Velocity profile from floor to ceiling (middle of the plane)

0

0.5

1

1.5

2

2.5

3

0 0.1 0.2 0.3 0.4

Me

tre

ab

ove

th

e f

loo

r (

m)

velocity in the x-z plane (m/s)

Velocity profile from floor to ceiling (near radiator)

Design Builder

Phoenics

Page 23: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 23 of 26

Case D Temperature profiles (south to north wall)

0

0.5

1

1.5

2

2.5

3

20.5 21 21.5 22 22.5 23 23.5

Me

tre

ab

ove

th

e f

loo

r (

m)

temperature in the x-z plane °c

Temperature profile from floor to ceiling (near south wall - window)

Design Builder

Phoenics

0

0.5

1

1.5

2

2.5

3

20.5 21 21.5 22 22.5 23 23.5

Me

tre

ab

ove

th

e f

loo

r (

m)

temperature in the x-z plane °c

Temperature profile from floor to ceiling (middle of the plane)

0

0.5

1

1.5

2

2.5

3

20.5 21 21.5 22 22.5 23 23.5

Me

tre

ab

ove

th

e f

loo

r (

m)

temperature in the x-z plane °c

Temperature profile from floor to ceiling (near north wall)

Page 24: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 24 of 26

Case D Velocity profiles (south to north wall)

0

0.5

1

1.5

2

2.5

3

0 0.2 0.4 0.6 0.8 1

Me

tre

ab

ove

th

e f

loo

r (

m)

velocity in the x-z plane (m/s)

Velocity profile from floor to ceiling (near south wall - window)

Design Builder

Phoenics

0

0.5

1

1.5

2

2.5

3

0 0.2 0.4 0.6 0.8 1

Me

tre

ab

ove

th

e f

loo

r (

m)

velocity in the x-z plane (m/s)

Velocity profile from floor to ceiling (near north wall)

0

0.5

1

1.5

2

2.5

3

0 0.2 0.4 0.6 0.8 1

Me

tre

ab

ove

th

e f

loo

r (

m)

velocity in the x-z plane (m/s)

Velocity profile from floor to ceiling (middle of the plane)

Page 25: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 25 of 26

Case D Temperature profiles (west to east wall)

0

0.5

1

1.5

2

2.5

3

20 20.5 21 21.5 22 22.5 23

Me

tre

ab

ove

th

e f

loo

r (

m)

temperature in the y-z plane °c

Temperature profile from floor to ceiling (near east wall)

0

0.5

1

1.5

2

2.5

3

20 20.5 21 21.5 22 22.5 23

Me

tre

ab

ove

th

e f

loo

r (

m)

temperature in the y-z plane °c

Temperature profile from floor to ceiling (middle of the plane)

0

0.5

1

1.5

2

2.5

3

20 20.5 21 21.5 22 22.5 23

Me

tre

ab

ove

th

e f

loo

r (

m)

temperature in the y-z plane °c

Temperature profile from floor to ceiling (near west wall - diffuser)

Design Builder

Phoenics

Page 26: An Inter-program Analysis of Computational Fluid Dynamics ......DesignBuilder is a generic energy simulation program for the built environment for the modelling of energy and comfort

School of Built and Natural Environment Ellison Building

Newcastle Upon Tyne NE1 8ST

Tel: 0191 227 4722 Fax: 0191 227 3167

Page 26 of 26

Case D Velocity profiles (west to east wall)

0

0.5

1

1.5

2

2.5

3

0 0.2 0.4 0.6 0.8 1

Me

tre

ab

ove

th

e f

loo

r (

m)

Velocity in the y-z plane (m/s)

Velocity profile from floor to ceiling (middle of the plane)

0

0.5

1

1.5

2

2.5

3

0 0.5 1 1.5 2

Me

tre

ab

ove

th

e f

loo

r (

m)

Velocity in the y-z plane (m/s)

Velocity profile from floor to ceiling (near west wall - diffuser)

Design Builder

Phoenics

0

0.5

1

1.5

2

2.5

3

0 0.2 0.4 0.6 0.8 1

Me

tre

ab

ove

th

e f

loo

r (

m)

Velocity in the y-z plane (m/s)

Velocity profile from floor to ceiling (near east wall)