Altivar Flange Mounting Kit

8
1/8 E6581354-04 02/2019 Altivar Flange Mounting Kit Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this product. © 2019 Schneider Electric. All Rights Reserved. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Only appropriately trained persons who are familiar with and understand the contents of this manual and all other pertinent product documentation and who have received safety training to recognize and avoid hazards involved are authorized to work on and with this drive system. Installation, adjustment, repair, and maintenance must be performed by qualified personnel. • The system integrator is responsible for compliance with all local and national electrical code requirements as well as all other applicable regulations with respect to grounding of all equipment. • Many components of the product, including the printed circuit boards, operate with mains voltage. Do not touch. Use only electrically insulated tools. • Do not touch unshielded components or terminals with voltage present. • Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the drive system, block the motor shaft to prevent rotation. • AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused conductors of the motor cable. • Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals. • Before performing work on the drive system: - Disconnect all power, including external control power that may be present. - Place a "Do Not Turn On" label on all power switches. - Lock all power switches in the open position. - Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator of the absence of DC bus voltage that can exceed 800 Vdc. - Measure the voltage on the DC bus between the DC bus terminals (PA/+ and PC/-) using a properly rated voltmeter to verify that the voltage is <42 Vdc. - If the DC bus capacitors do not discharge properly, contact your local Schneider Electric representative. Do not repair or operate the product. • Install and close all covers before applying voltage. Failure to follow these instructions will result in death or serious injury. VW3A9510...VW3A9515 VW3A9510 VW3A9512...515 VW3A9511 E658135404

Transcript of Altivar Flange Mounting Kit

Page 1: Altivar Flange Mounting Kit

1/8E6581354-0402/2019

Altivar Flange Mounting Kit

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibilityis assumed by Schneider Electric for any consequences arising out of the use of this product.© 2019 Schneider Electric. All Rights Reserved.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH• Only appropriately trained persons who are familiar with and understand the contents of this manual and all other

pertinent product documentation and who have received safety training to recognize and avoid hazards involved are authorized to work on and with this drive system. Installation, adjustment, repair, and maintenance must be performed by qualified personnel.

• The system integrator is responsible for compliance with all local and national electrical code requirements as well as all other applicable regulations with respect to grounding of all equipment.

• Many components of the product, including the printed circuit boards, operate with mains voltage. Do not touch. Use only electrically insulated tools.

• Do not touch unshielded components or terminals with voltage present.• Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the drive system, block

the motor shaft to prevent rotation.• AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused conductors of

the motor cable.• Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.• Before performing work on the drive system:

- Disconnect all power, including external control power that may be present.- Place a "Do Not Turn On" label on all power switches.- Lock all power switches in the open position.- Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator of the

absence of DC bus voltage that can exceed 800 Vdc.- Measure the voltage on the DC bus between the DC bus terminals (PA/+ and PC/-) using a properly rated

voltmeter to verify that the voltage is <42 Vdc.- If the DC bus capacitors do not discharge properly, contact your local Schneider Electric representative. Do

not repair or operate the product.• Install and close all covers before applying voltage.

Failure to follow these instructions will result in death or serious injury.

VW3A9510...VW3A9515

VW3A9510 VW3A9512...515

VW3A9511

Lorem ipsum

E658135404

Page 2: Altivar Flange Mounting Kit

E6581354-04 www.schneider-electric.com2/8

Cut and holes

Flange Mounting Kit

VW3A9510VW3A9511

VW3A9510

ain mm

260

310

10.23

12.20VW3A9511

c

d

e

af

195

4xØ8

8xØ8

6xØ10

7.67

g

ai

h

b

bin mm

790

845

31.10

33.26

cin mm

340

360

13.38

14.17

din mm

150

160

5.90

6.29

ein mm

15

18

0.59

0.70

fin mm

100

83.5

3.93

3.28

gin mm

15

10

0.59

0.39

hin mm

120

70

4.72

2.75

iin mm

80

91.5

3.14

3.60

Page 3: Altivar Flange Mounting Kit

E6581354-04 www.schneider-electric.com3/8

Cut and holes

Flange Mounting Kit

VW3A9512 VW3A9513

VW3A9512

ain mm

280

280

11.02

11.02VW3A9513

bin mm

970

970

38.18

38.18

cin mm

360

460

14.17

18.11

din mm

160

150

6.29

5.90

ein mm

15

15

0.59

0.59

fin mm

120

120

4.72

4.72

gin mm

20

20

0.78

0.78

hin mm

60

60

2.36

2.36

iin mm

195

195

7.67

7.67

af

b b

g

i i

aa

h

af

aa

h

c

eg

c

e

d d4xØ8 8xØ8

8xØ10

6xØ8

8xØ10

6xØ8

Page 4: Altivar Flange Mounting Kit

E6581354-04 www.schneider-electric.com4/8

Cut and holes

Flange Mounting Kit

VW3A9514VW3A9515

VW3A9514

ain mm

280

280

11.02

11.02VW3A9515

bin mm

970

970

38.18

38.18

cin mm

610

685

24.01

26.96

din mm

160

160

6.29

6.29

ein mm

17.5

17.5

0.68

0.68

fin mm

120

120

4.72

4.72

gin mm

20

20

0.78

0.78

hin mm

60

60

2.36

2.36

iin mm

215

240

8.46

9.44

af

g

a

b

ah

c

iii

e

d

195

7.67

8xØ8

8xØ10

8xØ8

Page 5: Altivar Flange Mounting Kit

E6581354-04 www.schneider-electric.com5/8

1

2 3

4

VW3A9510

Mounting

Flange Mounting Kit

M4 1.1...1.7 N·m (9.74...15.05 lbf.in)

M6 4.2...5.1 N·m (37.17...45.14 lbf.in)

Page 6: Altivar Flange Mounting Kit

E6581354-04 www.schneider-electric.com6/8

5

6 7

8 9

Mounting

Flange Mounting Kit

M5 2.6...3.3 N·m (23.01...29.21 lbf.in)

VW3A9510

Page 7: Altivar Flange Mounting Kit

E6581354-04 www.schneider-electric.com7/8

2

1

Mounting

Flange Mounting Kit

VW3A9512...515VW3A9511

VW3A9511...515

M8 13.5 N·m (119.5 lbf.in)M6 4.2...5.1 N·m (37.17...45.14 lbf.in)

VW3A951010

M12 41 N·m (360 lbf.in)M12

M8

M8 10.0...13.5 N·m (88.51...119.49 lbf.in)

Page 8: Altivar Flange Mounting Kit

E6581354-04 www.schneider-electric.com8/8

3

4

Mounting

Flange Mounting Kit

5

M12 M8

VW3A9511

M12

M8

VW3A9512...515

M12 41 N·m (360 lbf.in)

M8 10.0...13.5 N·m (88.51...119.49 lbf.in)