Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000...

70
Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk [email protected] Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) USER MANUAL

Transcript of Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000...

Page 1: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk [email protected]

Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) USER MANUAL

Page 2: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 2 of 70 © 2015 - 2017 Protec Fire Detection plc

Document Revision Details

Issue Modification Detail Author Date

2 Removed technical specifications PD 25/10/2016

3 Revision of images Revision of testing section 2

NS 09/12/2016

3.1 Updated screenshots PD 14/09/2017

3.2 Revision of images Group sections 13.7 &13.8 updated Weekly Test section removed

CM 11/12/2017

Notice This manual may be revised as a result of enhancements to the system software or hardware. Check for revisions to this manual, and download them, from the website www.protec.co.uk

Page 3: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 3 of 70 © 2015 - 2017 Protec Fire Detection plc

Table of Contents

DOCUMENT REVISION DETAILS .............................................................................................................. 2

INTRODUCTION ....................................................................................................................................... 6

PROTEC MANUFACTURED ALGO-TEC™ 6000 EQUIPMENT 5 YEAR WARRANTY ................................... 7

1.0 USER RESPONSIBILITIES ............................................................................................................... 8

1.1 Requirements of the Premises Management Named Person ............................................................... 8

2.0 ROUTINE TESTING OF THE SYSTEM .............................................................................................. 9

2.1 Daily Inspection .......................................................................................................................................... 9 2.2 Weekly Test .................................................................................................................................................. 9 2.3 Monthly Test ................................................................................................................................................ 9

3.0 ACCESS LEVELS ............................................................................................................................. 10

3.1 Access Level 1 (General User) .................................................................................................................. 10 3.2 Access Level 2 (Authorised / Trained User) ............................................................................................ 10 3.3 Access Level 3a (Exchange Loop Devices) .............................................................................................. 10

4.0 INDICATIONS AND CONTROLS................................................................................................... 11

4.1 LCD (Liquid Crystal Display) .................................................................................................................... 11 4.2 General Indications .................................................................................................................................. 11 4.3 Status Indications ..................................................................................................................................... 11 4.4 Zone Indications ....................................................................................................................................... 11

5.0 FIRE INDICATIONS ...................................................................................................................... 12

5.1 General Fire Indicator Illuminated ........................................................................................................ 12 5.2 Zone Indicator Flashing Red ................................................................................................................... 12

6.0 FAULT INDICATIONS ................................................................................................................... 13

6.1 System Fault .............................................................................................................................................. 13 6.2 Alarm Fault ................................................................................................................................................ 13 6.3 Power Fault ............................................................................................................................................... 13 6.4 Aux. Supply Fault ...................................................................................................................................... 13 6.5 Network Fault ............................................................................................................................................ 14 6.6 Fire link Fault ............................................................................................................................................. 14 6.7 Fire Protection Fault ................................................................................................................................. 14

7.0 DISABLEMENT INDICATIONS ..................................................................................................... 15

7.1 Alarms Disabled ........................................................................................................................................ 15 7.2 Alarm Routing (Fire link) Disabled ......................................................................................................... 15 7.3 Fire Protection Disabled .......................................................................................................................... 15

8.0 OTHER INDICATIONS .................................................................................................................. 16

8.1 Power ......................................................................................................................................................... 16 8.2 Test ............................................................................................................................................................. 16 8.3 Alarm Routing (Fire Link) Operated ....................................................................................................... 16 8.4 Fire Protection Operated ......................................................................................................................... 16

Page 4: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 4 of 70 © 2015 - 2017 Protec Fire Detection plc

8.5 Outputs Delayed ....................................................................................................................................... 16

9.0 SYSTEM DELAYS ........................................................................................................................... 17

10.0 COINCIDENCE/DEPENDENCY OPERATION ............................................................................. 18

11.0 RESPONSE TO AN ALARM ........................................................................................................ 19

11.1 Automatic Detection ............................................................................................................................. 19 11.2 Manual Detection ................................................................................................................................. 19 11.3 Coincidence/Dependency Activation .................................................................................................. 19 11.4 Silencing the Alarms ............................................................................................................................. 19 11.5 Resetting the panel after an Alarm .................................................................................................... 19 11.6 New Zone in Alarm ............................................................................................................................... 20 11.7 Activating the Alarms Manually.......................................................................................................... 20

12.0 STATUS DISPLAY & MENU NAVIGATION ................................................................................ 21

12.1 The System Normal Display ................................................................................................................ 21 12.2 Navigating the menus ......................................................................................................................... 22 12.4 Printing .................................................................................................................................................. 23 12.5 Panel Selection ...................................................................................................................................... 24 12.6 Card Selection ....................................................................................................................................... 24 12.7 Loop Selection ....................................................................................................................................... 25 12.8 Device Selection .................................................................................................................................... 25 12.9 Login ...................................................................................................................................................... 26 12.10 The Fault, Disablement and Test Display .......................................................................................... 27 12.11 The Fire Alarm Display ......................................................................................................................... 29

13.0 USER MENUS ............................................................................................................................. 31

13.1 Entering the Menu System .................................................................................................................. 31 13.2 System View ........................................................................................................................................... 32 13.3 Device Detail .......................................................................................................................................... 33 13.4 Algo-Tec Data ........................................................................................................................................ 35 13.5 Panel Summary .................................................................................................................................... 36 13.6 Device State ........................................................................................................................................... 37 13.7 Input Groups ......................................................................................................................................... 38 13.8 Output Groups ...................................................................................................................................... 39 13.9 Disable / Enable .................................................................................................................................... 40 13.10 Current Disablements .......................................................................................................................... 40 13.11 Zone Disablements ............................................................................................................................... 41 13.12 Device Disablement .............................................................................................................................. 43 13.13 Output Group Disablement ................................................................................................................. 44 13.14 Output Disablement ............................................................................................................................. 45 13.15 Disable all fire Links ............................................................................................................................. 46 13.16 Disable all fault Links ........................................................................................................................... 46 13.17 Disable all fire protection outputs ..................................................................................................... 46 13.18 Disable all alarm outputs .................................................................................................................... 46 13.19 Disable all control outputs .................................................................................................................. 46 13.20 Disable all non-fire outputs................................................................................................................. 46 13.21 Settings .................................................................................................................................................. 47 13.22 Set Time / Date ...................................................................................................................................... 48

Page 5: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 5 of 70 © 2015 - 2017 Protec Fire Detection plc

13.23 Show Configuration ............................................................................................................................. 49 13.24 Clear System Fault ................................................................................................................................ 49 13.25 Software Versions ................................................................................................................................. 50 13.26 Test Menu .............................................................................................................................................. 50 13.27 Lamp / Buzzer Test ............................................................................................................................... 51 13.28 Zone Test ................................................................................................................................................ 52 13.29 Test Options .......................................................................................................................................... 53 13.30 Complete System Test .......................................................................................................................... 54 13.31 History .................................................................................................................................................... 55 13.32 View all fires .......................................................................................................................................... 55 13.33 View all non-fires .................................................................................................................................. 56 13.34 View by type........................................................................................................................................... 57 13.35 Historic Alarm Count ............................................................................................................................ 58 13.36 Printer Menu ......................................................................................................................................... 59

14.0 EXCHANGING LOOP DEVICES .................................................................................................. 61

14.1 Entering the Level 3a Main Menu ....................................................................................................... 61 14.2 Tools menu ............................................................................................................................................ 62 14.3 Loop Tools ............................................................................................................................................. 62 14.4 Exchange Device Menu ........................................................................................................................ 63

15.0 APPENDIX A, RVAV DESCRIPTION .......................................................................................... 68

16.0 STANDARDS, DIRECTIVES AND REGULATIONS INFORMATION............................................ 69

Page 6: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 6 of 70 © 2015 - 2017 Protec Fire Detection plc

Introduction This manual applies to the Protec 6500 and 6600 fire alarm control panels however for convenience; reference will be made only to the ‘6500’. Everything in this manual applies to both the 6500 and 6600 unless stated otherwise. The Protec 6500 Fire Alarm Control Panel has been designed and manufactured in the United Kingdom and complies fully with the latest standards dictating fire alarm system design practice (EN54-2:1997 + A1:2006 and EN54-4:1997 + A1:2002 + A2:2006). The 6500 is a multi-zone four loop fire alarm control panel that uses digital addressable technology to communicate with Protec 6000PLUS series loop devices (automatic detectors, Manual Call Points, sounders, interfaces etc.). Multiple panels may be networked together to create a larger fire alarm system. As the integrity and reliability of a fire alarm system is vital, the system continuously monitors all critical paths for faults. The fire detection / alarm loop devices and wiring are constantly monitored to check for faults. The integrated power supply regularly performs ‘self-checking’ to ensure it is in full working order and that the Stand-by batteries are in a good state. Any faults detected are reported on the front panel display, a fault output is also provided which may be connected to external systems (a remote monitoring centre, for example) to signal that the system has a fault and attention is required. The panel is wall mounted either flush or surface and the generously sized back box allows ample space for rear or top cable entries.

This equipment and its associated connections must be installed, commissioned and maintained by a suitably trained skilled and competent person.

This equipment is not guaranteed unless installed and commissioned in accordance with current national standards

There are no user serviceable parts inside the 6500. A competent person trained to undertake such work MUST carry out any internal maintenance work. Separate installation and commissioning manuals are available.

Page 7: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 7 of 70 © 2015 - 2017 Protec Fire Detection plc

Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended warranty on our Protec manufactured Algo-TecTM 6000 equipment. When a Protec maintenance contract is in place, we warrant all the Protec Algo-TecTM 6000 equipment we manufacture for 5 years. If, during a service visit, the Protec Service Engineer suspects any Protec manufactured Algo-TecTM

6000 devices are not working properly, they will be replaced at no cost to the client. Similarly, during the course of a call out, any suspect devices will be replaced at no cost, with only the normal labour and travelling time charged at standard agreed rates. Contact Protec Fire Detection for details.

Note that Algo-Tec™ Equipment incorporating a CO sensor is excluded from the warranty.

Page 8: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 8 of 70 © 2015 - 2017 Protec Fire Detection plc

1.0 User Responsibilities The registered owner of the fire alarm system has specific responsibilities regarding the installation, testing and maintenance of the fire alarm system. BS5839 Pt 1: 2017 Section 6 states that the user of the fire alarm system must appoint a single named person to supervise all matters regarding the fire alarm system. Summarised below are the responsibilities expected of the named person,

It is strongly advised that a full copy of BS5839 Pt 1: 2017 is obtained and thoroughly read and understood.

1.1 Requirements of the Premises Management Named Person

• Ensure that the fire alarm equipment is checked at least once every 24 hours to ensure there are no faults on the system. Report any faults to the site maintenance manager.

• Ensure that arrangements are in place for correct testing of the fire alarm system (as

specified in BS5839 Pt 1: 2017 Section 6, the user testing is summarised in section 2.0 of this document).

• Ensure that the system event log is kept up to date and is available for inspection by any

authorised person when required.

• Ensure that all occupants of the protected premises are trained how to use the system properly and that they are aware of what action to take in the event of an alarm.

• Ensure that false alarms are minimised.

• Ensure all detectors and manual call points are not obstructed. Detectors must have at

least 500mm clear space preserved in all directions around them.

• Establish a liaison with those responsible for changes in, or maintenance of the building fabric.

• Ensure that when changes are made to the system, record drawings and operating

instructions are updated.

• Ensure that, where necessary, a suitable zone plan is displayed and kept up to date.

• Ensure that any relevant spare parts for system maintenance are held within the premises.

Page 9: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 9 of 70 © 2015 - 2017 Protec Fire Detection plc

2.0 Routine Testing of the System Recommendations for testing of the system are detailed in BS5839 Pt 1: 2017 (Section 6) The routine testing is briefly detailed below.

2.1 Daily Inspection • Check that the Power indicator is illuminated. • Check for any faults on the system and report these to the site maintenance manager.

2.2 Weekly Test Perform the daily test recommended in 2.1 and;

During the test you may wish to temporarily place the zone to be tested into test mode (Consult section 13)

• Perform an indicator test (lamp test) to check the integrity of the front panel indications,

and internal buzzer.

• Ensure no Manual Call Points or detectors are obstructed.

• Operate a Manual Call Point or detector during normal working hours to ensure the fire alarm system operates correctly.

• A different Manual Call Point or detector on a different zone should be tested each week,

in this way all the devices on all the zones are tested.

• Ensure the system sounders are operational.

• Ensure the sounders are not operated for longer than 30 seconds during testing. The occupants of the building can then distinguish genuine alarms.

2.3 Monthly Test Perform the weekly test recommended in 2.2 and;

• If an automatic generator is used as part of the mains failure back-up system it should be

started up once each month by simulated failure of the normal power supply, and then run in this mode for at least 1 hour.

• Visually inspect the stand-by batteries and their connections. Check that the batteries are

capable of supplying the alarm sounders. Note:- Care is necessary to ensure that any person undertaking these tasks is competent to do so safely and has the relevent technical knowledge and training

Page 10: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 10 of 70 © 2015 - 2017 Protec Fire Detection plc

3.0 Access Levels There are three access levels to allow users of different authorisation levels access to various parts of the system. The access levels and a description of functions available are given in the next sections.

3.1 Access Level 1 (General User) Access level 1 allows the general user to view the status of the panel at any time. Zone fire, fault, disablement and test states are clearly displayed as are any current system faults and disablements.

Full detail of the front panel display is given in the next section.

The following functions may be performed at access level 1. • Entering code for access level 2 or 3a • Viewing current fires • Viewing current faults • Viewing current disablements • Viewing current tests • Accepting current faults or alarms ( Mute Buzzer )

Accepting at access level 1 is only available if the button has been made available during the commissioning stage

3.2 Access Level 2 (Authorised / Trained User) Access level 2 allows the authorised user access to various critical system functions. To enter access level 2 enter the user code using the touchscreen LCD (section 12.8).

Refer to section 13 for the features accessible at access level 2.

3.3 Access Level 3a (Exchange Loop Devices)

Access level 3a allows the maintenance staff access to the loop device exchange function. To enter access level 3a enter the level 3a code using the touchscreen LCD (section 12.8).

Refer to sections 13 & 14 for the features accessible at access level 3a.

Page 11: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 11 of 70 © 2015 - 2017 Protec Fire Detection plc

4.0 Indications and Controls Each panel has a comprehensive front panel display enabling the current state of the system to be rapidly determined. Figure 5.0 shows the indications and controls. Figure 5.0 Front panel indications and controls.

4.1 LCD (Liquid Crystal Display) The LCD gives a clear indication of the current status of the panel. Under normal conditions the LCD shows the System Normal screen. This screen changes to the status display screen if the panel has fires, faults, disablements or tests present.

4.2 General Indications These are the General Fire, Fault, Disablement and Test indicators. These give clear indication that the panel has at least one Fire, Fault, Disablement or Test condition. It is possible for the panel to indicate multiple conditions simultaneously.

4.3 Status Indications These provide important fault and status information at a glance without having to search for it on the LCD.

4.4 Zone Indications The zone in fire is always indicated on the LCD however if the fire occurs in one of the first 100 zones (40 zones on a standalone panel) then it is also indicated by the zone indicator flashing red. If the user touches Accept then the zone indicator will remain on but stop flashing.

Page 12: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 12 of 70 © 2015 - 2017 Protec Fire Detection plc

5.0 Fire Indications The panel displays fire information on the LCD along with the General Fire indicator and the relevant zone indicators. The following sections detail the meaning of each indicator.

5.1 General Fire Indicator Illuminated The panel has detected a fire on one of its zones, or has been activated from another panel via the network.

The building fire plan should be executed immediately

5.2 Zone Indicator Flashing Red The panel has detected a fire in the zone shown. The General Fire indicator will always accompany this and the internal buzzer will be fast pulsing.

Page 13: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 13 of 70 © 2015 - 2017 Protec Fire Detection plc

6.0 Fault Indications When the panel has detected a fault in any of the critical operating paths of the system it will display this on the LCD. The internal buzzer will also pulse slowly. The General Fault indicator will be illuminated and is always accompanied by other indicator(s) detailing the exact fault. In general, fault indicators flash until the fault is accepted (by touching the Accept button) the fault indicator then illuminates steadily and the internal buzzer will be muted. Further faults activate the buzzer again. In the event of any fault the following action should be taken:- • Investigate the fault, and then accept the fault by touching the Accept button. • Note the fault down in the Logbook and take action to remedy the fault. In all cases expert

advice should be sought. When the fault has been rectified the fault indicator will automatically extinguish. Note: - Some faults latch and once rectified must be cleared by pressing Reset. Any faults that have not been fixed will reappear. The following sections give descriptions of each fault indication

6.1 System Fault The panel performs regular self-tests to ensure the software is working correctly. If a fault is detected in software operation a System Fault is declared. This is a latching fault and can only be cleared by touching Clear System Fault. If the fault is still present it will then reappear.

6.2 Alarm Fault A fault has been detected on one or more of the alarm devices connected to the loop or on one of the sounder circuits. One or more alarm devices may no longer operate correctly.

6.3 Power Fault A fault has been detected in the panel’s power supply. This may be because the local mains supply has failed or because the internal stand-by batteries or circuitry are faulty.

6.4 Aux. Supply Fault A fault has been detected with the Auxiliary 24V supply output of the panel. There may no longer be an auxiliary supply to external devices or the auxiliary devices are drawing too much current. The General Fault indicator will be illuminated accompanied by the ‘Aux Supply Fault’ indicator.

Page 14: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 14 of 70 © 2015 - 2017 Protec Fire Detection plc

6.5 Network Fault A fault has been detected on the network connecting the panels together.

6.6 Fire link Fault A fault has been detected on the monitored fire link path. This may be a wiring fault or a fire link interface fault. The connection to the fire station link is no longer reliable. Expert advice should be sought immediately.

6.7 Fire Protection Fault A fault has been detected on the monitored path to fire protection equipment. This may be a wiring fault or a fire protection interface fault. The connection to the fire protection equipment is no longer reliable. Expert advice should be sought immediately.

Page 15: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 15 of 70 © 2015 - 2017 Protec Fire Detection plc

7.0 Disablement Indications When a user has disabled a critical feature of the system it will display this on the LCD. The internal buzzer will also pulse slowly. The General Disablement indicator will be illuminated and is always accompanied by other indicator(s) detailing the exact disablement. In general, the buzzer will sound for disablements until the disablement is accepted (by touching the Accept button). Further disablements activate the buzzer again. The following sections give descriptions of each disablement indication

7.1 Alarms Disabled Activation of outputs designated as ‘alarm’ outputs is prevented. The sounders will not operate in the event of a fire.

7.2 Alarm Routing (Fire link) Disabled Activation and faults on the alarm routing output are inhibited. The fire link will not activate in the event of a fire.

7.3 Fire Protection Disabled Activation and faults on the fire protection equipment output are inhibited. The fire protection equipment output will not activate in the event of a fire.

Page 16: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 16 of 70 © 2015 - 2017 Protec Fire Detection plc

8.0 Other Indications

8.1 Power This indication illuminates when the panel is powered up from mains or batteries.

8.2 Test This indication illuminates when part or the whole of the panel is in test mode.

8.3 Alarm Routing (Fire Link) Operated This indication is illuminated when the fire link path has been activated on this panel. This does not confirm that the fire event has been sent to a remote monitoring centre unless the confirmation input option has been programmed and the receiving equipment supports this confirmation feature.

8.4 Fire Protection Operated This indication is illuminated when the fire protection equipment path has been activated. This does not confirm that the fire event has been sent to the fire protection equipment unless the confirmation input option has been programmed and the receiving equipment supports this confirmation feature.

8.5 Outputs Delayed This indicator will be illuminated if the commissioning engineer has programmed the system in a manner that will delay the alarm outputs, the fire link activation or the fire protection equipment output if the system detects a fire signal. The alarms, fire link or fire protection equipment output may not activate immediately in the event of a fire.

Page 17: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 17 of 70 © 2015 - 2017 Protec Fire Detection plc

9.0 System Delays Delays may have been programmed into the panel at commissioning time to allow a predetermined delay time from a zone activation until:- • The alarm outputs activate • The fire link activates • The fire protection equipment output activates Delays may be used in order to allow time for the cause of the activation to be investigated by the premises management. If the cause of the activation is found to be legitimate the alarm outputs can be manually activated. If the cause of the activation is found to be false the system can be silenced and reset. The system set-up chart must be consulted to determine exactly which outputs have been delayed, how the delay time has been set up and what action is taken if the Silence button is touched before a delay has expired.

In general, delays only apply to automatic detector activations whilst a manual activation on a zone (Activating a Manual Call Point) overrides delays.

Page 18: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 18 of 70 © 2015 - 2017 Protec Fire Detection plc

10.0 Coincidence/Dependency Operation At the time of commissioning, the system may have been programmed to operate in one of three ‘coincidence’ modes where a confirmation signal is required. The confirmation signal is normally the same or a second device generating a fire signal.

Mode ‘C’ is the standard coincidence mode used in Protec fire alarm systems.

Coincidence operation is used to minimise the effects of false alarms by providing time to investigate the first fire signal and if found to be an unwanted activation, prevent a full evacuation of the premises and an unnecessary call to the fire brigade. Mode ‘A’, also known as Dependency/Coincidence Type ‘A’ indicates the zone in alarm and sounds the panel buzzer, however it does not light the general fire led and activate the outputs unless there is a confirmation signal from the same device or an automatic device in the same zone. Mode ‘B’, also known as Dependency/Coincidence Type ‘B’ indicates the zone in alarm and sounds the panel buzzer, however it does not light the general fire led and activate the outputs unless there is a confirmation signal from the same device or an automatic device in any zone. Mode ‘C’, also known as Coincidence/Dependency Type ‘C’ indicates the fire alarm as normal but does not activate any outputs until there is a confirmation signal from another device (manual or automatic) in any zone or a programmed timeout expires.

In general, coincidence only applies to automatic detector activations whilst a manual activation on a zone (Activating a Manual Call Point) overrides coincidence.

Page 19: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 19 of 70 © 2015 - 2017 Protec Fire Detection plc

11.0 Response to an Alarm

11.1 Automatic Detection If a detector (smoke, heat etc.) activates in a zone of the panel this is known as an automatic activation. The panel responds by;

• Illuminating the ‘General Fire’ indicator. • Flashing the relevant zone fire indicator and displaying on the LCD. • Fast pulsing of the internal buzzer. • Activating alarm outputs as programmed, after any delays have expired. • Activating the Fire Link output after any programmed delays have expired. • Activating the Fire Protection equipment output after any programmed delays have

expired.

11.2 Manual Detection If a Manual Call Point is operated in the zone of a panel this is known as manual activation. The panel responds by;

• Illuminating the ‘General Fire’ indicator. • Flashing the relevant zone fire indicator and displaying on the LCD. • Fast pulsing of the internal buzzer. • Activating alarm outputs as programmed, after any delays have expired. • Activating the Fire Link output after any programmed delays have expired. • Activating the Fire Protection equipment output after any programmed delays have

expired.

It is usual to have no programmed delay for a manual activation.

11.3 Coincidence/Dependency Activation Please see section 10.0

11.4 Silencing the Alarms

Touching and holding Silence when logged in will silence the alarm outputs.

11.5 Resetting the panel after an Alarm After the cause of the alarm has been determined (and entered in the log by the authorised user) the panel can be reset if required. Manual Call Points, if triggered, must first be reset locally.

When logged in, touch and hold reset. The panel will reset any latched devices on its loops. The Reset sequence takes about 20 seconds during which time the panel will not detect new fires.

Page 20: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 20 of 70 © 2015 - 2017 Protec Fire Detection plc

11.6 New Zone in Alarm If a new zone or a previously silenced zone goes into alarm, the panel will re-activate the alarms and re-sound the internal buzzer.

11.7 Activating the Alarms Manually

Touch and hold Sound Alarms when logged in to evacuate the building. Output group types will be activated as programmed but the Control and Fire Link outputs WILL NOT be activated.

If the sound alarms input is set to operate a fire link output this will create a design error.

Page 21: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 21 of 70 © 2015 - 2017 Protec Fire Detection plc

12.0 Status Display & Menu Navigation At any given time the system will be in one of three main states. These are the normal state, the fault / disablement / test state or the fire state.

12.1 The System Normal Display When the system does not have any fires, faults, disablements or tests it is in the System Normal state. In this state the panel will have its power on indicator illuminated and the LCD will show the System Normal display, as shown below:-

Touch the centre of the screen to display the code entry screen, refer to section 12.8.

Page 22: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 22 of 70 © 2015 - 2017 Protec Fire Detection plc

12.2 Navigating the menus Touching the up arrow scrolls up a menu list. If already at the top of the list then a touch of this button wraps round to the bottom of the menu list.

Touching the down arrow button scrolls down a menu list. If already at the bottom of the list then a touch of this button wraps round to the top of the menu list.

Some menu options require a number of steps to select from a menu list. To avoid having to exit then go through the whole process again, touching this arrow selects the previous item in the menu list. This button will eventually wrap round from the top of the list to the bottom.

Some menu options require a number of steps to select from a menu list. To avoid having to exit then go through the whole process again, touching this arrow selects the next item in the menu list. This button will eventually wrap round from the bottom of the list to the top.

To leave any menu, touch the EXIT button. As a security measure the panel will exit the menus automatically if no key activity has been detected for 30 minutes.

Page 23: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 23 of 70 © 2015 - 2017 Protec Fire Detection plc

12.3 Number entry

Some menu lists contain many lines. To speed up the search through a list, touch the Keypad button (if available) to display a keypad. Enter a menu item number then press Enter to move directly to that menu number position in the list.

The keypad for the zone list is shown below :-

Similar keypads are used to enter other menu information such as dates

Touch Cancel to exit the keypad menu Touch Enter to accept the entered number

12.4 Printing If the panel has a printer fitted then some menus will offer the option to print.

Touch the button to print the information

Page 24: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 24 of 70 © 2015 - 2017 Protec Fire Detection plc

12.5 Panel Selection Many menu options start by requiring the user to select a panel. If the system comprises a single panel then this screen is not required. Navigate the list to find the correct panel then touch to select it.

During commissioning of the system, the panels can be assigned text relevant to their location to assist in finding the appropriate one.

12.6 Card Selection Each panel comprises a number of cards. Once the user has selected a panel then the list of relevant cards is presented. If searching for a loop device, touch to select the correct loop card.

Page 25: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 25 of 70 © 2015 - 2017 Protec Fire Detection plc

12.7 Loop Selection Each loop card has two loops. Touch to select the correct loop. During commissioning of the system, the loops can be assigned text relevant to their location to assist in finding the appropriate one.

Note :- A loop with 000 devices may not be selected

12.8 Device Selection Each loop comprises up to 200 devices. Search the list for the correct device then touch to select it.

Note :- Only addresses with a device assigned will be displayed.

Page 26: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 26 of 70 © 2015 - 2017 Protec Fire Detection plc

12.9 Login

If the Login button is not displayed then touch the centre of the screen to Login, refer to section 12.1

Access to the features of the panel is achieved by logging in. Press Login and the display will show :-

Enter the user code by touching the relevant number buttons then touch Enter. If the code is correct then the display will show the User main menu screen – see section 13, or the Level 3a main menu screen – see section 14

Touching the Service Info button will display contact details of the company responsible for servicing your system.

Page 27: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 27 of 70 © 2015 - 2017 Protec Fire Detection plc

12.10 The Fault, Disablement and Test Display If the system has one or more faults, disablements or tests the panel will display this as shown below Faults, disablements and tests are always accompanied by the relevant general indicator, Touching the Accept button will mute the panel buzzer. Touching one of the summary buttons will retrieve more detailed information about the individual faults, disablements or tests.

The summaries of Disablements, Tests and Other information are displayed in a similar manner to the fault summary below.

The ‘Accept’ button at this level is optional and will only be displayed if configured to do so during the panel commissioning.

Page 28: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 28 of 70 © 2015 - 2017 Protec Fire Detection plc

Touching the Fault summary will display a list of the current faults:-

General faults will automatically clear when the cause of the fault is fixed. System faults do not clear automatically but have to be cleared by pressing ‘Clear System Fault’, refer to section 13.24

Touch Reset to clear latching faults such as loop faults. Any faults that have not been fixed will reappear.

Page 29: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 29 of 70 © 2015 - 2017 Protec Fire Detection plc

12.11 The Fire Alarm Display The panel enters the alarm state if one or more loop devices have triggered (this may be because an automatic detector has sensed a fire, or a Manual Call Point has been operated). The panel will activate its alarms as dictated by the system programming once commissioned. The General Fire indicator will illuminate and (if the alarm is in zones 1 to 100) the zone indicator will flash red. Note: - A standalone panel will only illuminate zone indicators 1 to 40 as it only allows 40 zones to be used. The LCD shows the fire display (overriding any normal or fault displays) as shown below The display follows the format of displaying the first zone in fire, latest zone in fire and the total number of zones in fire.

Touching ‘Accept’ will mute the panel buzzer

To silence the sounders (section 11.4) and to reset the system (section 11.5) requires the user to login (section 12.8) by pressing the ‘To silence touch here and login’ button instead of the usual ‘Login’ button.

Page 30: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 30 of 70 © 2015 - 2017 Protec Fire Detection plc

The user may touch either the first or latest fire to retrieve more detailed information about them.

Touching ‘View all fires’ will display a list of all the current fire events:-

The screen automatically returns to the standard fire display if no buttons are touched for 30 seconds.

Touching one of the fire events will show details of the fire event:-

The screen automatically returns to the standard fire display if no buttons are touched for 30 seconds.

Page 31: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 31 of 70 © 2015 - 2017 Protec Fire Detection plc

13.0 User Menus

13.1 Entering the Menu System When the user code is entered, the ‘User’ Main Menu screen will be displayed. The Sound Alarms, Silence and Reset buttons are now enabled.

The printer menu option is only available on panels configured to have a printer

Touch a menu option to select it. System View – refer to section 13.2 Disable / Enable – refer to section 13.9 Settings – refer to section 13.21 Test Menu – refer to section 13.26 History Menu – refer to section 13.31

Page 32: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 32 of 70 © 2015 - 2017 Protec Fire Detection plc

13.2 System View Touching System View displays options to show the system configuration.

Page 33: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 33 of 70 © 2015 - 2017 Protec Fire Detection plc

13.3 Device Detail

Touching Device Detail displays the list of panels on the system. Select a Panel (section 12.4), Loop Card (section 12.5), Loop (section 12.6) and a Device (section 12.7).

Touch Disable to disable the device

If the device is already disabled, touch Enable to cancel the device disablement

Each device has a serial number. This serial number is associated with an address number by the panel. In order to assist with the location of devices, it is possible to force a device to flash its address details. This process is known as Remote Visual Address Verification (RVAV).

Putting a device in RVAV mode prevents it from detecting a fire event. A multiple address device such as a 16 way board loses the ability to detect a fire event from all its 16 addresses.

Touch Locate device to instruct the device to flash its address using its LED

Page 34: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 34 of 70 © 2015 - 2017 Protec Fire Detection plc

A device will time out of RVAV mode after 20 minutes however the menu will time out after 30 minutes

(Refer to Appendix A for details of the LED flashing)

Page 35: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 35 of 70 © 2015 - 2017 Protec Fire Detection plc

13.4 Algo-Tec Data Algo-Tec Data is only available for detector devices. Touching Algo-Tec Data displays the algorithm data for the device.

Page 36: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 36 of 70 © 2015 - 2017 Protec Fire Detection plc

13.5 Panel Summary

Touching Panel Summary displays the list of panels on the system. Select a Panel (section 12.4) to display its loop device summary.

Page 37: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 37 of 70 © 2015 - 2017 Protec Fire Detection plc

13.6 Device State Touch Device State to display the list of panels on the system. Select a Panel (section 12.4), Loop Card (section 12.5) and a Loop (section 12.6). The device state of up to 20 loop devices is displayed at once.

Touch a device icon to display the device details. Refer to section 13.3 for the device details screen Press Help for information about the screen

Note that indication of Device Pre-Alarm is not currently supported.

Page 38: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 38 of 70 © 2015 - 2017 Protec Fire Detection plc

13.7 Input Groups Touch Input Groups to display the list of input groups and their current state.

Note: - The Input Groups – Active menu may be blank if no input groups are active.

Press View All to view all input groups (Active and Inactive).

Press View Active to return to viewing only the active input groups.

Page 39: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 39 of 70 © 2015 - 2017 Protec Fire Detection plc

13.8 Output Groups

Touch Output Groups then displays the list of output groups local to the panel and their current state.

Note: - The Output Groups – Active menu may be blank if no output groups are active.

Press View All to view all output groups (Active and Inactive).

Press View Active to return to viewing only the active output groups.

Page 40: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 40 of 70 © 2015 - 2017 Protec Fire Detection plc

13.9 Disable / Enable

Touching Disable / Enable displays the disablement options. Disabling an input device temporarily prevents it from generating a fire signal or a fault signal. Disabling outputs temporarily prevents them from signalling that the system is in a fire state. A disablement remains in place until the user cancels (normalises) it.

13.10 Current Disablements

Touching Current Disablements displays the disablement summary.

Page 41: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 41 of 70 © 2015 - 2017 Protec Fire Detection plc

13.11 Zone Disablements Touching Zone displays the three zone disablement options.

Touching any of the option buttons displays the zone list.

Touch a ‘normal’ zone to disable it and the disabled count will increment by one. Touch a ‘Disabled’ zone to normalise it and the disabled count will decrement by one. The list of zones contains 10000 zones, many of which may not be used. The system will allow these unused zones to be disabled however no devices will actually be disabled. Note: - A single panel will only display 40 zones not 10000.

Page 42: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 42 of 70 © 2015 - 2017 Protec Fire Detection plc

This indicates that those devices in this zone which were assigned as Manual Class when the panel was commissioned are disabled. This disablement can only be removed in the manual call points zone disablement menu.

This indicates that those devices in this zone which were assigned as Automatic Class when the panel was commissioned are disabled. This disablement can only be removed in the automatic detection zone disablement menu. This indicates that all the devices in this zone are disabled. This disablement can only be removed in the all devices zone disablement menu.

Page 43: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 43 of 70 © 2015 - 2017 Protec Fire Detection plc

13.12 Device Disablement Touching Device displays the list of panels on the system. Select a Panel (section 12.4), Loop Card (section 12.5) and a Loop (section 12.6). A list of devices on the loop will be presented.

Touch a device address to disable its input, touch it again to normalise it (cancel the disablement). Disabling a device without an input e.g. a sounder, is possible but does not prevent the sounder from activating.

Page 44: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 44 of 70 © 2015 - 2017 Protec Fire Detection plc

13.13 Output Group Disablement

Touching Output Group displays the list of panels on the system. Select a Panel (section 12.4). A list of output groups on the panel will be presented.

Touch an output group to disable it, touch it again to normalise it (cancel the disablement).

Output groups of type ‘Alarm’ are greyed out because they cannot be disabled.

Output groups that are greyed out may be disabled using the panel logic and are usually operated by a keyswitch or invisible switch device.

Page 45: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 45 of 70 © 2015 - 2017 Protec Fire Detection plc

13.14 Output Disablement Touching Output displays the list of output options that can be disabled.

Touch a disablement option to disable it, touch it again to normalise it (cancel the disablement).

Outputs that are greyed out and listed as “unavailable” are disabled via the panel logic and are usually operated by a keyswitch or invisible switch device.

Page 46: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 46 of 70 © 2015 - 2017 Protec Fire Detection plc

13.15 Disable all fire Links

The fire link is the output used to signal a fire event to a remote monitoring centre.

13.16 Disable all fault Links

The fault link is the output used to signal a fault event to a remote monitoring centre.

13.17 Disable all fire protection outputs

The fire protection output is the output used to trigger another panel controlling fire protection equipment.

13.18 Disable all alarm outputs

‘Alarm’ outputs are sounder devices that turn on when there is a fire event and turn off when the system is silenced.

13.19 Disable all control outputs

‘Control’ outputs are typically interface devices that shutdown plant equipment when there is a fire event. These shutdowns remain in place when the system is silenced and only cancelled when the system is reset.

13.20 Disable all non-fire outputs

‘Non-fire’ outputs are typically interface devices that do not control equipment when there is a fire event. These outputs are not affected when the system is silenced or reset.

Page 47: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 47 of 70 © 2015 - 2017 Protec Fire Detection plc

13.21 Settings

Touching Settings displays the settings menu.

Page 48: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 48 of 70 © 2015 - 2017 Protec Fire Detection plc

13.22 Set Time / Date

Touch the Set Time / Date button to adjust the time and date.

Note: - The ‘seconds’ cannot be adjusted.

Touch the ‘+’ button to increment the relevant counter. Touch the ‘–‘button to decrement the relevant counter.

Indicates that the panel will NOT update the time to allow for the beginning and end of British Summer Time (Daylight Saving). This function is not currently supported.

Indicates that the panel will automatically update the time to allow for the beginning and end of British Summer Time (Daylight Saving). This function is not currently supported.

When finished setting both the Time and Date, touch set to save the information. To exit without changing the Time or Date, touch Cancel.

Page 49: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 49 of 70 © 2015 - 2017 Protec Fire Detection plc

13.23 Show Configuration

Touch Show Configuration to display the panel’s site file configuration information.

13.24 Clear System Fault

Touch the Clear System Fault button to remove any system faults. If the cause of the system fault remains then the system fault will reappear.

Page 50: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 50 of 70 © 2015 - 2017 Protec Fire Detection plc

13.25 Software Versions

Press Software Versions to display the list of panels on the system. Select a Panel (section 12.4). The panel cards and firmware versions will be displayed.

13.26 Test Menu Touch Test Menu to display the test options.

Page 51: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 51 of 70 © 2015 - 2017 Protec Fire Detection plc

13.27 Lamp / Buzzer Test

Touch to test the LCD, panel buzzer and the LED indications.

Page 52: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 52 of 70 © 2015 - 2017 Protec Fire Detection plc

13.28 Zone Test

Activations from a zone programmed into test mode will not activate the Fire Link output. Remember to take the zone out of test mode when testing has been completed.

Touch Zone Test to select a zone for testing.

Note: - It is possible to select and test a Zone that is not used.

If a device is activated in a zone under test then only the alarm outputs, including talking sounders, on that panel will be activated (assuming the alarm outputs have been enabled during test – see section 13.29).

Page 53: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 53 of 70 © 2015 - 2017 Protec Fire Detection plc

13.29 Test Options Touch Test Options to display the status of each test option.

Alarm Outputs During Test In test mode, only alarm outputs, including talking sounder outputs can be activated. If this option is ‘Disabled’ then no outputs will activate during test fire events. User System Test The feature to allow the user access to the Complete System Test is an option. If this is ‘Disabled’ then the user is not permitted access to the Complete System Test. Selective Display This feature is an engineer option used to restrict the display of test fire events to a selected panel. Auto Reset / Auto Reset Delay If ‘Auto Reset’ is ‘Enabled’ then a test fire event will be automatically reset after a pre-programmed delay. This delay is the ‘Auto Reset Delay’ time.

Page 54: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 54 of 70 © 2015 - 2017 Protec Fire Detection plc

13.30 Complete System Test

Complete System test will put the entire fire system into test mode. During complete system test, the fire link output will not transmit the fire signal to a remote monitoring centre. Remember to take the system out of complete system test mode when testing has been completed.

Touch Complete System Test to put the entire fire system into test mode.

Touch to cancel the Complete System Test.

Note: - When a device is activated in complete test mode, the alarm outputs, including talking sounders, will be activated on all panels (assuming the alarm outputs have been enabled during test – see section 13.29).

Page 55: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 55 of 70 © 2015 - 2017 Protec Fire Detection plc

13.31 History Touch History to display the Historic log options.

13.32 View all fires

Touch View all fires to view all the fire events from the log.

Page 56: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 56 of 70 © 2015 - 2017 Protec Fire Detection plc

13.33 View all non-fires Touch View all non-fires to view all events from the log except fire events.

Page 57: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 57 of 70 © 2015 - 2017 Protec Fire Detection plc

13.34 View by type Touch View by type to select the type of event to view from the log.

The display of events from the log will begin by displaying the most recent events first.

Touch Today to begin by displaying today’s events. Touch Date to display events since a specific date and time.

In the above example, the user has chosen to display events since 8:30 on the 10th September 2017.

Page 58: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 58 of 70 © 2015 - 2017 Protec Fire Detection plc

13.35 Historic Alarm Count Touch Historic Alarm Count to display the current alarm count.

The alarm count is a count of the number of times that the panel has entered the fire alarm state since the count was last reset. Note: - The user cannot reset the alarm count.

Page 59: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 59 of 70 © 2015 - 2017 Protec Fire Detection plc

13.36 Printer Menu Touch Printer Menu to access the printer options.

Note; - The printer menu option is only available on panels configured to have a printer.

Touch to print all current fault events.

Touch to print all current disablement events.

Touch to print all current test mode events.

Page 60: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 60 of 70 © 2015 - 2017 Protec Fire Detection plc

Touch Loop Device Reports to display the loop device Report options.

Touch to print the device analogue values from a selected panel and loop.

Touch to print the device isolator number, software version and sensitivity from a selected panel and loop. Touch to power up the printer so that its paper feed sensor is active and a new roll of paper can be installed. Fitting a new roll of paper requires the panel door to be opened possibly exposing high voltage terminals. A competent person trained to undertake such work MUST carry out any internal maintenance work.

A competent person trained to undertake such work MUST carry out any internal maintenance work.

Touch to print the last one hundred events that the panel has logged.

Page 61: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 61 of 70 © 2015 - 2017 Protec Fire Detection plc

14.0 Exchanging Loop Devices

14.1 Entering the Level 3a Main Menu To login see section 12.8. When the level 3a code is entered, the Main Menu screen will be displayed. The Sound Alarms, Silence and Reset buttons are now enabled.

Touch a menu option to select it. System View – refer to section 13.2 Disable / Enable – refer to section 13.9 Settings – refer to section 13.21 Test Menu – refer to section 13.26 History Menu – refer to section 13.31 Tools Menu – refer to section 14.2

Page 62: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 62 of 70 © 2015 - 2017 Protec Fire Detection plc

14.2 Tools menu Touching Tools Menu displays the loop tools and printer menu options.

Loop Tools – see section 14.3 Printer Menu – see section 13.36 (only appears if a printer is fitted)

14.3 Loop Tools

Pressing the loop tools button will show the option for exchanging loop devices.

Page 63: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 63 of 70 © 2015 - 2017 Protec Fire Detection plc

14.4 Exchange Device Menu

Do not begin exchanging devices before entering the exchange devices menu. Any MCPs that are to be exchanged must be disabled before exchanging.

Pressing exchange devices will allow the level 3a user to begin the process of exchanging a device without the need to re-log and allocate the system.

A menu will appear instructing the user to exchange any necessary devices before continuing.

All necessary devices must be exchanged before continuing, wait until all relevant device missing and device added faults have been generated before pressing ‘OK’. Wait for 3 minutes for the faults to generate before pressing OK, as it is not possible to view the fault menu whilst exchanging and the fault counter will not increment or decrement.

A maximum of 8 devices per loop can be exchanged at any one time.

Press cancel to exit the exchange menu.

Press OK to begin the exchange of devices.

Page 64: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 64 of 70 © 2015 - 2017 Protec Fire Detection plc

After pressing OK select a Panel (section 12.4), Loop Card (section 12.5), and Loop (section 12.6).

A warning is given asking if the user wishes to continue, incorrect exchanging of devices could result in a configuration error or the incorrect operation of devices.

Press cancel to abandon the exchange or to select a different loop.

Page 65: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 65 of 70 © 2015 - 2017 Protec Fire Detection plc

Press OK to continue with the exchange.

After pressing OK the devices that require exchanging will be displayed. Select a device address to be exchanged.

Select the replacement device you wish to exchange with.

Note that devices of a different type to the original are greyed out and cannot be exchanged.

Page 66: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 66 of 70 © 2015 - 2017 Protec Fire Detection plc

Press cancel to select a different replacement device to exchange with.

Press OK to confirm the selection of the replacement device.

After pressing OK the user is asked if they wish to save the changes.

Page 67: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 67 of 70 © 2015 - 2017 Protec Fire Detection plc

Press continue to confirm the exchange and continue exchanging further devices (Any changes will not be saved at this stage).

After pressing continue the menu reverts to device selection and now displays previously exchanged devices as assigned.

Select and exchange any further devices as necessary. After exchanging the final device the user will again be presented with the following menu.

Press exit to cancel the exchange and leave the menu (Any changes will not be saved). Press save after all exchanges are finished to save the changes. A progress bar will be displayed whilst the changes are saved.

Page 68: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 68 of 70 © 2015 - 2017 Protec Fire Detection plc

15.0 Appendix A, RVAV Description

• Availability: RVAV is available on loop devices that have a ‘Fire LED’.

• Format : When the device receives the signal to RVAV, it outputs its address in the following format:-

The address is output as hundreds, tens and units with a one and a half second delay between. If the address is less than 100 then the leading zero for the hundreds is not output. The address is determined by counting the LED flashes. A zero is denoted by a long flash of approximately one second. There is a half second delay (approx.) between LED flashes.

• Address 41

• Address 05

• Address 102

1 second

ON

OFF

0.5 seconds

ON

OFF

0 1 + 1 + 1 + 1 + 1 = 05

1 0 1 + 1 = 102

ON

OFF

0.5 seconds

1 + 1 + 1 + 1 1 = 41

1.5 seconds

Note: The delay following a zero is reduced to one second

Fire LED State

Fire LED State

1 second See Note below

1 second

1.5 seconds

Fire LED State

Page 69: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 69 of 70 © 2015 - 2017 Protec Fire Detection plc

16.0 Standards, directives and regulations information

0832-CPR-F0179 201ag

Protec Fire Detection plc, Nelson, Lancashire, England BB9 6RT

PFD-CPR-0114

This equipment has been manufactured in conformance with the requirements of all applicable EU council directives and regulations.

BS EN 54-2:1997 + A1:2006

BS EN 54-4:1997 + A1:2002 + A2:2006

Control / Indicating and Power Supply equipment for fire detection and fire alarm systems for buildings

6500/6600 Fire Alarm Control Panel

Options Provided 7.8 Output to fire alarm devices 7.9.1 Output to fire alarm routing equipment 7.9.2 Alarm confirmation input from fire alarm routing equipment 7.10.1 Output to automatic fire protection equipment (type A) 7.10.2 Output to automatic fire protection equipment (type B) 7.10.3 Output to automatic fire protection equipment (type C) 7.10.4 Fault monitoring of fire protection equipment (type B) 7.11 Delays to outputs 7.12.1 Dependencies on more than one alarm signal(Type A) 7.12.2 Dependencies on more than one alarm signal(Type B) 7.12.3 Dependencies on more than one alarm signal(Type C) 7.13 Alarm counter 8.3 Fault signals from points 8.9 Output to fault routing equipment 9.5 Disablement of each point 10 Test condition Supports more than 512 fire detectors and/or manual call points (clause 13.7b) Control & Indicating: Performance under fire conditions: Pass Response delay (response time to fire): Pass Operational reliability: Pass Durability of operational reliability, Temperature resistance: Pass Durability of operational reliability, Vibration resistance: Pass Durability of operational reliability, Electrical stability: Pass Durability of operational reliability, Humidity resistance: Pass Power supply: Performance of power supply: Pass Durability of operational reliability, Temperature resistance: Pass Durability of operational reliability, Vibration resistance: Pass Durability of operational reliability, Electrical stability: Pass Durability of operational reliability, Humidity resistance: Pass

Page 70: Algo-Tec™ 6500/6600 INTERACTIVE ADDRESSABLE FIRE … · Protec Manufactured Algo-Tec™ 6000 Equipment 5 year warranty To demonstrate confidence in our product, we provide an extended

RDM0001/3_2 Page 70 of 70 © 2015 - 2017 Protec Fire Detection plc

Designed and manufactured in the United Kingdom

The policy of Protec Fire Detection plc is one of continuous improvement. As such we reserve the right to make changes to product specifications at any time and without prior notice. Errors and omissions excepted.

Electrical or electronic devices that are no longer serviceable must be collected separately and sent for environmentally compatible recycling (in accordance with the European Waste Electrical and Electronic Equipment Directive). To dispose of old electrical or electronic devices, you should use the return and collection systems put in place in the country concerned.