01/10/2009 1 ALICE-PHOS Alexei.Kuryakin@cer n.ch PHOS Cooling status (1 Oct) Incident happened (ECV failure) 1 Oct at 5 Am cooling plant failure happened: ECV (electrical control valve) controller alarm raised due to battery failure (a small battery inside controller) Compressors worked as usually, but freon didn’t flow because ECV was closed, so cooling liquid temperature start to increase. At 10 Am interlock blocking occurred because liquid temperature increase up to 25°C At 1 Pm after analysis problem temporary fixed: ECV switched on in manual mode and 43% opened. But that is only temporary solution: battery should be replaced to new one ASAP. PHOS cooling now working in normal operation mode.

Transcript of [email protected] 01/10/2009 1 PHOS Cooling status (1 Oct) Incident happened (ECV failure) 1...

Page 1: Alexei.Kuryakin@cern.ch 01/10/2009 1 PHOS Cooling status (1 Oct) Incident happened (ECV failure) 1 Oct at 5 Am cooling plant failure happened: ECV (electrical.

01/10/2009 1

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1 Oct)Incident happened (ECV failure)

1 Oct at 5 Am cooling plant failure happened: ECV (electrical control valve) controller alarm raised due to battery failure (a small battery inside controller)

Compressors worked as usually, but freon didn’t flow because ECV was closed, so cooling liquid temperature start to increase.

At 10 Am interlock blocking occurred because liquid temperature increase up to 25°C

At 1 Pm after analysis problem temporary fixed: ECV switched on in manual mode and 43% opened.

But that is only temporary solution: battery should be replaced to new one ASAP.

PHOS cooling now working in normal operation mode.

Page 2: Alexei.Kuryakin@cern.ch 01/10/2009 1 PHOS Cooling status (1 Oct) Incident happened (ECV failure) 1 Oct at 5 Am cooling plant failure happened: ECV (electrical.

01/10/2009 2

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1 Oct) Liquid temperature

ECV failure

Normaloperation

Interlock on Tmax

ECV operation in manual mode

Page 3: Alexei.Kuryakin@cern.ch 01/10/2009 1 PHOS Cooling status (1 Oct) Incident happened (ECV failure) 1 Oct at 5 Am cooling plant failure happened: ECV (electrical.

01/10/2009 3

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1 Oct)Pressure in evaporation tube

Compressor works but no freon(vacuum in evaporatortube)

Normaloperation

Fatal Interlock

Electronic Control Valve (ECV) failure

Continue in manual ECV mode

Page 4: Alexei.Kuryakin@cern.ch 01/10/2009 1 PHOS Cooling status (1 Oct) Incident happened (ECV failure) 1 Oct at 5 Am cooling plant failure happened: ECV (electrical.

01/10/2009 4

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1 Oct) Compressor cover temperature

Compressor 3 cover raise up to 80°C

Compressor 1

Compressor 2

Compressor 4

Compressor 3

ECV failure

Interlock

ECV work in manual mode

Page 5: Alexei.Kuryakin@cern.ch 01/10/2009 1 PHOS Cooling status (1 Oct) Incident happened (ECV failure) 1 Oct at 5 Am cooling plant failure happened: ECV (electrical.

01/10/2009 5

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1 Oct) PWO, FEE temperatures

PWO3

FEE2

PWO2

PWO4

FEE4FEE3

Liquid

Page 6: Alexei.Kuryakin@cern.ch 01/10/2009 1 PHOS Cooling status (1 Oct) Incident happened (ECV failure) 1 Oct at 5 Am cooling plant failure happened: ECV (electrical.

01/10/2009 6

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1 Oct) What is ECV controller

Page 7: Alexei.Kuryakin@cern.ch 01/10/2009 1 PHOS Cooling status (1 Oct) Incident happened (ECV failure) 1 Oct at 5 Am cooling plant failure happened: ECV (electrical.

01/10/2009 7

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1 Oct) ECV controller diagnosis

Alarm: Battery failure

Page 8: Alexei.Kuryakin@cern.ch 01/10/2009 1 PHOS Cooling status (1 Oct) Incident happened (ECV failure) 1 Oct at 5 Am cooling plant failure happened: ECV (electrical.

01/10/2009 8

ALICE-PHOS

ALICE-PHOS

[email protected]

PHOS Cooling status (1 Oct) What should be done

• Battery should be replaced with new one inside ECV controller (access to pit required)

• New blocking (interlock) should be added for compressor cover temperature (need few days for programming)