ADIABATIC DRY COOLER-400 KW - C-DAC
Transcript of ADIABATIC DRY COOLER-400 KW - C-DAC
DRY COOLER-400 KW
EXPANSION TANK WITHPRESSURIZATION UNIT
Ø25
1000 Literwater tank
DLC
Ø 3
2
Ø 3
2
Ø ...
Ø ...P
P
MAKE UP WATER
Ø25
RACK 1DLC
RACK 2DLC
RACK 3
FM
ADIABATICadiabatic system
Battery Limit
Ø 3
2
Ø 3
2
Battery Limit
Ø 3
2
Ø 3
2
Battery Limit
DPT
ControlPanel
VFDPanel
Max 33° C
Max 49° C
....... LPS
2 Pumps (1 Working & 1 Standby)
50 to 60 LPM 50 to 60 LPM 50 to 60 LPM
PRESSURE DROP 25KPA PER DLC RACK
FLOAT VALVE
CHEMICALDOSINGSYSTEM
RAW WATER INLET
1000 Literwater tank
DLC RACK 4
Ø 3
2
Ø 3
2
Battery Limit
50 to 60 LPM
DLC RACK 5
Ø 3
2
Ø 3
2
Battery Limit
50 to 60 LPM
DLC RACK 6
Ø 3
2
Ø 3
2
Battery Limit
50 to 60 LPM
PRE
SSU
RIZ
EE
XPA
NSI
ON
TA
NK
750
LIT
RE
1000 Literwater tank
LEGEND
COOLING-P & ID
PRELIMINARY DWG
TITLE
OWNERCONSULTANT DRAWN
APPROVED
REV
SCALE
CKD
REV DESCRIPTION DATE
NTSDATE
INDIAN INSTITUTE OF TECHNOLOGY- ROORKEE
00 SUBMITTED FOR APPROVAL
CENTER FOR DEVELOPMENTOF ADVANCED COMPUTING
R0
DRAWING NO.23/10/2020
27 JAN 2021
DC LT PANEL-
3
DLM
FEEDER
CABLE
OUTGOING-2OUTGOING-1
200 kVA UPS-1
NO
RATING
3
DLM
TRIPON
MCCB, 4P
LSI
3
DLM
TRIPON
MCCB, 4P
LSI
400A
MCCB
400 A
MCCB
3
DLM
TRIPON
MCCB, 4P
LSI
63A
MCCB
UPS -MECHANICAL
BYPASS IN
PU
T
BATTERY
STATIC SWITCH
RECTIFIER
STATIC SW
ITCH
INVERTER
BATT M
CCB
MU
LTIPLE STRIN
GS BATTERY
TO
PRO
VID
E 15M
IN
. BACKU
P
200 kVA
UPS-1
OUTGOING-5
BYPASS IN
PU
T
BATTERY
STATIC SWITCH
RECTIFIER
STATIC SW
ITCH
INVERTER
BATT M
CCB
MU
LTIPLE STRIN
GS BATTERY
TO
PRO
VID
E 15M
IN
. BACKU
P
30 kVA
UPS-4
MECHANICAL DISTRIBUTION PANEL-1A
FEEDER
CABLE
100A AL. BUS BAR
MDC
MCB,TPN,4A
RS485
3
TRIPON
OUTGOING-1
RATING
100/5A
CT
CL:1,15VA
DRY COOLER
TRIPON OFF
LSI
63A, 25KA
MCCB. 4P
(COS)
TRIPON
OUTGOING-2
SPARE
TRIPON
OUTGOING-3
PRIM. PUMP-1
(COS)
TRIPON
OUTGOING-4
PRIM. PUMP-2
(COS)
TRIPON
OUTGOING-5
TRIPON
OUTGOING-6
BMS
TRIPON
OUTGOING-7
LIGHTING
(COS)
TRIPON
TANK PUMP
OUTGOING-3
200 KVA UPS-3
MCCB, 4P
LSI
400A
MCCB
MCCB, 4P
LSI
400A
MCCB
MECHANICAL DISTRIBUTION PANEL-1B
FEEDER
CABLE
250A AL. BUS BAR
MDC
MCB,TPN,4A
RS485
3
TRIPON
OUTGOING-1
NO
RATING
100/5A
CT
CL:1,15VA
DRY COOLER-1
TRIPON OFF
LSI
63A, 25KA
MCCB. 4P
(COS)
TRIPON
OUTGOING-2
SPARE
TRIPON
OUTGOING-3
PRIM. PUMP-1
(COS)
TRIPON
OUTGOING-4
PRIM. PUMP-2
(COS)
TRIPON
OUTGOING-5
SPARE
TRIPON
OUTGOING-6
BMS
(COS)
TRIPON
OUTGOING-7
LIGHTING
(COS)
TRIPON
OUTGOING-8
SPARE
TRIPON
OUTGOING-9
TRIPON
OUTGOING-10
MDC
MCB,TPN,4A
CT 630/5A
CL:1,15VA
1250A, 50KA
MCCB 4P
LSIG
RS485
LVM
3
SPD
MCB,TP,63A
1250A AL. BUS BAR
M
A/M
TRIPON OFF
CT
CL:1,15VA
630/5A
ACB 4P
1250 A 50 KA
LSIG
3
A/M
MDC
MCB,TPN,4A
RS485
LVM
TRIPON OFF
ELECTRICAL / MECHANICAL INTERLOCK FOR
ANY 1 BREAKER TO CLOSE AT A TIME
M
T
ON OFF
100A
3P
ATS
T
ON OFF
100A
3P
T
ON OFF
100A
3P
ATS-1 ATS-2 ATS-3
T
ON OFF
100A
3P
ATS-4
T
ON OFF
63A
3P
ATS-5
T
ON OFF
63A
3P
ATS-6
T
ON OFF
63A
3P
ATS-7
ATS ATS ATS ATS ATS ATS
NOTES:
The panels will be built to relevant IEC specification
Unless otherwise stated and or where applicable :
Construction :
1. The panels will be dust and vermin proof with gaskets of the doors
Installed on the panel and not on door. The compartmentalized
construction is required with extendable bus bars. The entire
assembly must go through 7 tank process and will be oven baked .
2. Outdoor installation will be with IP55 enclosure
3. Bus bars will be tinned copper with current density of not more than
800A / Sq. inches.
4. Base frame of at-least 4" made out of steel sections is to be provided.
5. Panel will have :
Top Entry Bottom Entry
Floor Mounted Installation/Wall Mounted Installation
6. Bus bar system supports will be CPRI or equal test laboratory
approved.
7. All panel compartments shall have identification etched on Aluminum
strip.
8. All MCB DB will have each MCB identification
9. Stands should be provided for the installation of switch board
matching to height of the false floor.
10. All VFDs shall have an active-front-end design
11. All UPSs shall have an active-front-end design
12. KVAR Requirement for each transformer is 400 KVAR steps size
should be appropriate considering data centre application & to
maintain p.f .98 to unity.
Components :
1. MCCBs will be atleast 35 kA or as specified In SLD.
2. MCBs will be atleast 10 kA short circuit withstand of the curve to suit
discrimination
3. ALL protections will be coordinated
4. The range of the instruments be such that the readings will shown
the mid-range of the instrument.
5. The load manager will be installed with communication port and
win95 or similar graphic OS based software.
6. All ACBs will be draw out type with static relays provided for
over-curent, earth fault.
For DG set protection restricted earth fault protection is required.
7. MCCB to have following :
Shunt trip , fault indications, Electronics trip mechanism.
Earthing :
1. All doors will have flying earth.
2. Copper earth bus is to be installed.
3. Where applicable UPS system, VS system and Raw power earth shall
be separate. All the earth bus installed on suitable insulators
Drawings and Tests :
1. Shop drawings are required to be submitted for the review and
approval
2. Test certificates for all components and the panel's routine tests are
required to be provided in triplicate
3. Panel is required to be tested at site and works
8. All Panel Should Have Tvss Protection
BYPASS IN
PU
T
BATTERY
STATIC SWITCH
RECTIFIER
STATIC SW
ITCH
INVERTER
BATT M
CCB
MU
LTIPLE STRIN
GS BATTERY
TO
PRO
VID
E 15M
IN
. BACKU
P
BYPASS IN
PU
T
BATTERY
STATIC SWITCH
RECTIFIER
STATIC SW
ITCH
INVERTER
BATT M
CCB
MU
LTIPLE STRIN
GS BATTERY
TO
PRO
VID
E 15M
IN
. BACKU
P
200 kVA
UPS-2
200 kVA
UPS-3
BYPASS IN
PU
T
BATTERY
STATIC SWITCH
RECTIFIER
STATIC SW
ITCH
INVERTER
BATT M
CCB
MU
LTIPLE STRIN
GS BATTERY
TO
PRO
VID
E 15M
IN
. BACKU
P
30 kVA
UPS-5
200kVA UPS-2
3
DLM
TRIPON
MCCB, 4P
LSI
63A
MCCB
SPARE
OUTGOING-6
200KVA,415/415, K-13
ISOLATION XMER
OFF CKT.
TAPS-380-400-415V
SPARE
STORAGE
RACK-1
DLC-R2DLC-R3
SERVICE
RACK-1
200 KVA,415/415,
K-13ISOLATION XMER
OFF CKT.
TAPS-380-400-415V
SPAREDLC-R2
DLC-R3
SERVICE
RACK-1
STORAGE
RACK-1
UPS OUT PUT PANEL-1
4Rx120sq.mmCU.UNAR.XLPE CABLE
CU UNARMOURED
CU UNARMOURED
4 R 120 SQMM
DLM
3
OUTGOING-4
SPARE
OUTGOING-7
UPS -MECHANICAL
OUTGOING-8
3
DLM
TRIPON
MCCB, 4P
LSI
100A
MCCB
EB POWER BY IIT ROORKEE
750 KVA DG Set
DLC-R1
DLC-R1
DG set
LOCT- DC ROOM
ACB 4P
1250 A 50 KA
LSIG
A/M
MDC
MCB,TPN,4A
RS485
LVM
TRIPON OFF
M
WITH AMF CONTROLLER
3
DLM
TRIPON
MCCB, 4P
LSI
63A
MCCB
OUTGOING-8
LIGHTING DB
3
DLM
TRIPON
MCCB, 4P
LSI
OUTGOING-9
3
DLM
TRIPON
MCCB, 4P
LSI
OUTGOING-10
63A
MCCB
63A
MCCB
OUTGOING-11 OUTGOING-12
UPS AREA
RAW POWER DB
UPS AREA
LIGHTING DB
SERVER AREA
RAW POWER DB
SERVER AREA
3
DLM
TRIPON
MCCB, 4P
LSI
63A
MCCB
3
DLM
TRIPON
MCCB, 4P
LSI
63A
MCCB
3
DLM
TRIPON
MCCB, 4P
LSI
63A
MCCB
3
DLM
TRIPON
MCCB, 4P
LSI
63A
MCCB
OUTGOING-13
OUTGOING-14
SPARE
SPARE
SPARE
400A
400A
DLC-R5DLC-R6
DLC-R4
SPARE
DLC-R5DLC-R6
DLC-R4
SPARE
UPS OUT PUT PANEL-2
OUTGOING-10
OUTGOING-11
STORAGE
RACK-2
SERVICE
RACK-2
OUTGOING-10
OUTGOING-11
STORAGE
RACK-2
SERVICE
RACK-2
200 KVA,415/415,
K-13ISOLATION XMER
OFF CKT.
TAPS-380-400-415V
SPAREDLC-R2
DLC-R3
DLC-R1
400A
DLC-R5DLC-R6
DLC-R4
SPARE
UPS OUT PUT PANEL-3
OUTGOING-10
OUTGOING-11
SPARESPARE
SPARE
SPARE
EMERGENCY
EMERGENCY
ADIABATIC
MAKE UP
WATER
TANK PUMP
MAKE UP
WATER
PUMP
ADIABATIC
PUMP
TRIPON
OUTGOING-9
TRIPON
OUTGOING-10
SPARE
SPARE
LOCATION OF IEC SOCKET BOX IS
ABOVE FALSE CEILING ON CABLE
TRAY
POWER INPUT
INSIDE THE
RACK IS FROM
TOP
LOCATION OF IEC SOCKET BOX IS
ABOVE FALSE CEILING ON CABLE
TRAYPOWER INPUT
INSIDE THE
RACK IS FROM
TOP
LOCATION OF IEC SOCKET BOX IS
ABOVE FALSE CEILING ON CABLE
TRAYPOWER INPUT
INSIDE THE
RACK IS FROM
TOP
LINE VOLTAGE MONITOR & CONTROL FOR
DIGITAL LOAD MONITOR - EM6436
LVM
DLM
MANUALLY OPERATED DRAWOUT (MDO) TYPE ACB
CURRENT TRANSFORMER (CT) RESIN CAST
POTENTIAL TRANSFORMER (PT)
MINIATURE CIRCUIT BREAKER (MCB)
LOAD BREAK SWITCH
MANUALLY OPERATED FIXED TYPE MCCB
MANUALLY OPERATED FIXED TYPE MCCB
WITH O/L, S/C & E/F RELEASE (LSIG).
WITH O/L & S/C RELEASE (LSI).
MANUALLY OPERATED DRAWOUT (MDO) TP+N(100%) TYPE ACB
WITH O/L, S/C & E/F RELEASE (LSIG).
WITH O/L & S/C RELEASE (LSI).
ELECTRICALLY OPERATED DRAWOUT (EDO) TYPE ACB
WITH O/L, S/C & E/F RELEASE (LSIG).
M
ELECTRICALLY OPERATED DRAWOUT (ED0) TYPE ACB
WITH O/L & S/C RELEASE (LSI).
M
LEGENDS
TRANSIENT VOLTAGE SURGE SUPPRESSOR
R,Y,B (RED,YELLOW,BLUE) INDICATING LAMPS
TVSS
R BY
TRIPOFF
ON-OFF-TRIP INDICATING LAMPS
MAIN SWITCH BOARD
MOTOR CONTROL CENTRE
MSB
MCC
TRANSFORMERTFR
MAXIMUM DEMAND CONTROLLER - EM6400MDC
OVER, UNDER VOLTAGE, SINGLE PHASE &
PHASE REVERSAL PROTECTION
INTEGRATED BASIC POWER & ENERGY PARAMETERS
CHANGEOVER SWITCH
MOTOR PROTECTION CIRCUIT BREAKER (MPCB)
RESIDUAL CURRENT CIRCUIT BREAKER (RCCB)
BASIC ENERGY METER - A,kW,kWHkWH
H
ALARM - HOOTER / BUZZER
MOE (MOTOR OPERATED) FIXED TYPE MCCB
WITH O/L & S/C RELEASE (LSI).
M
ONAN 11KV/433V STEPDOWN TRANSFORMER
AIR COOLED K-20 400/400V ISOLATION TRANSFORMER
ABBREVIATIONS
L S I G L : OVER CURRENT WITH TIMER DELAY
S : SHORT CIRCUIT CURRENT WITH TIMER DELAY
I : CONTINUOS SHORT CIRCUIT
G : GROUND FAULT CURRENT WITH TIME DELAY
12 ANNUNCIATION PANEL WITH HOOTER
HOOTER
1 2 3 4
5 6 7 8
9 10 11 12
MANUALLY OPERATED DRAWOUT (MDO) TYPE MCCB
WITH O/L & S/C RELEASE (LSI).
A/M
AUTO MANUAL SELECTOR SWITCH
FIXED TYPE MCCB WITH O/L & S/C RELEASE (LSIG).
MANUALLY OPERATED MICROPROCESSOR BASED
µP
TNC SWITCH WITH SPRING RETURN TO NEUTRAL AUTO /
MANUAL SELECTOR SWITCH
ON
MOTORISED LOAD BREAK CHANGEOVER SWITCH (ATS)
ONAN 11KV/433V STEPDOWN TRANSFORMER WITH OLTC
AIR COOLED K-20 400/400V ISOLATION TRANSFORMER
BYPASS IN
PU
T
BATTERY
STATIC SWITCH
RECTIFIER
STATIC SW
ITCH
INVERTER
BATT M
CCB
MU
LTIPLE STRIN
GS BATTERY
TO
PRO
VID
E 15M
IN
. BACKU
P
UNINTERRUPTED POWER SUPPLY (UPS)
ATS
ELECTRICAL-SLD
PRELIMINARY DWG
TITLE
OWNERCONSULTANT DRAWN
APPROVED
REV
SCALE
CKD
REV DESCRIPTION DATE
NTSDATE
INDIAN INSTITUTE OF TECHNOLOGY- ROORKEE
00 SUBMITTED FOR APPROVAL
CENTER FOR DEVELOPMENTOF ADVANCED COMPUTING
R0
DRAWING NO.23-10-2020
27 JAN 2021
550
UP
UP
UP
TOILET
BENEATH THE
STAIRS
PROPOSED EXPANSION
OF HPC LAB
IMG LAB
8900 x 5185
CENTRALIZED
UPS ROOM
CENTRAL
FACULTY ROOM
FACULTY ROOM
NETWORKING
CENTER
RAMP
FULL HT. WOODEN
PARTITION
STORAGE
M.S
. G
RIL
L
TW
O W
HE
ELE
R
PA
RK
IN
G
ROLLING SHUTTER
U.P.S.
BATTERIES
BATTERIES
PROPOSED EXPANSION
OF HPC LAB
FACULTY ROOM
SHED FOR
D.G.
LO
W H
T.
BR
IC
K W
AL
L
COLLAPSIBLE
SHUTTER
COLLAPSIBLE
SHUTTER
ELECT.
PANEL
ROOM
UP
WHEELCHAIR
LIFT
PORCH
STAIRCASE
FULL HT. PARTITION
ENT. LOBBY
PARKING
SHED
PARKING
SHED
LAWN
ENT. PORCH
PARKING
SHED
LAWN
PAVED
LAWN
PAVED
PAVED
BSNL
TOWER
CHEMISTRY DEPTT.
AREA
GREEN
ROAD
ROAD
LIFT LOBBY
HE TOILET
CABIN
CABIN
15970
10370
UPS ROOM
10607 x 8570
SERVER ROOM
15970 x 10370
8570
5400
5400 3500540054003500
2930
2940
2930
3530
3540
3530
8800
8800
5300
5300
8800
3360
UP
2635
CRAC
UP
S 2
X3
0 K
VA
UP
S 3
X2
00
K
VA
ELECTRICAL INCOMING PANEL
CRAC
CRAC
BA
TT
ER
IE
S
2X
30
K
VA
UPS
OUTPUT
PANEL -1
CRAC
CRAC
SequenaDLC
RACK-1
SequenaDLC
RACK-2
SequenaDLC
RACK-3
SequenaDLC
RACK-5
SequenaDLC
RACK-6
SERVICE
RACK-1
SERVICE
RACK-2
STORAGE
RACK-1
STORAGE
RACK-2
10607
BA
TT
ER
IE
S
1X
20
0 K
VA
1200
1513
BA
TT
ER
IE
S
1X
20
0 K
VA
BA
TT
ER
IE
S
1X
20
0 K
VA
DG-750 KVA
4406
2500
5906
3520
5556
ADIABATIC
DRY COOLER
-400 kw
SPACE ALLOCATION FOR EARTHING PIT
13696
FUEL DAY
TANK 990
LITERS
ODU-1
ODU-2
ODU-3
ODU-4
2000
SYSTEM
ADMINISTRATION
ROOM
11.7 SQ METER
BMS ROOM
13.2 SQ METER
SequenaDLC
RACK-4
5035
4565
20
T
D
ua
l
Co
mp
re
sso
r
20 T Dual
Compressor
20 T Dual
Compressor
1218
3073
3914
4426
3073
NOVEC
CYLINDER
FIRE RATED VISION
WINDOW -GLASS
ALUMINUM
PARTITION WITH
GLASS
GLASS
DOOR
1450
1450
2000 2000
2 -HOURS FIRE
RATED DOOR
UPS
OUTPUT
PANEL -2
UPS
OUTPUT
PANEL -3
DATA CENTER -SITE LAYOUT
PRELIMINARY DWG
TITLE
OWNERCONSULTANT DRAWN
APPROVED
REV
SCALE
CKD
REV DESCRIPTION DATE
NTSDATE
INDIAN INSTITUTE OF TECHNOLOGY- ROORKEE
00 SUBMITTED FOR APPROVAL
CENTER FOR DEVELOPMENTOF ADVANCED COMPUTING
R2
DRAWING NO.14/12/2020
R1 CHANGE OF LOCATIONR2 GLASS DIMENSIONS CHANGE
27 JAN 2021
15543
FIRE RATEDGLASS
PARTITION-VISION
WINDOW
800
2262
527
538547
554
3720 1254
599
800
PROPOSED EXPANSION
OF HPC LAB
BATTERIES
BATTERIES
PROPOSED EXPANSION
OF HPC LAB
COLLAPSIBLE
SHUTTER
15970
10370
UPS ROOM
10607 x 8570
SERVER ROOM
15970 x 10370
8570
3360
UP
2635
UP
S 2
X3
0 K
VA
UP
S 3
X2
00
K
VA
ELECTRICAL INCOMING PANEL
BA
TT
ER
IE
S
2X
30
K
VA
10607
BA
TT
ER
IE
S
1X
20
0 K
VA
1200
1513
BA
TT
ER
IE
S
1X
20
0 K
VA
BA
TT
ER
IE
S
1X
20
0 K
VA
SYSTEM
ADMINISTRATION
ROOM
11.7 SQ METER
BMS ROOM
13.2 SQ METER
5035
4565
20
T
D
ua
l
Co
mp
re
sso
r
20 T Dual
Compressor
20 T Dual
Compressor
1218
3073
3914
4426
3073
FIRE RATED VISION
WINDOW -GLASS
ALUMINUM
PARTITION WITH
GLASS
GLASS
DOOR
5400
5400 3500540054003500
2930
2940
2930
3530
3540
3530
8800
8800
5300
5300
8800
20 T Dual
Compressor
20 T Dual
Compressor
350
FIRE RATEDGLASS
PARTITION-VISION
WINDOW
2000
1500
938
1450RAISED
FLOORING
FALSE
CEILING
TRUE
SLAB
EXISITING
BRICK
WALL
550
BRICK
WALL
FIRE
RATED
DOOR
FIRE
RATED
DOOR
FIRE
RATED
DOOR
FIRE RATED GYPSUM
PARTITION
UPS
OUTPUT
PANEL -1
UPS
OUTPUT
PANEL -2
UPS
OUTPUT
PANEL -3
DATA CENTER -LAYOUT
PRELIMINARY DWG
TITLE
OWNERCONSULTANT DRAWN
APPROVED
REV
SCALE
CKD
REV DESCRIPTION DATE
NTSDATE
INDIAN INSTITUTE OF TECHNOLOGY- ROORKEE
00 SUBMITTED FOR APPROVAL
CENTER FOR DEVELOPMENTOF ADVANCED COMPUTING
R2
DRAWING NO.14/12/2020
R1 LOCATION CHANGER2 GLASS DIMESNIONS CHANGE
R227 JAN 2021