ADDENDUM # 001
DATE: 11-26-18
Page 1 of 5
TO CONTRACT DOCUMENTS ENTITLED:
PROJECT MANUAL FOR:
University of Missouri Medical Science
Building – Research Vivarium Upgrade &
Maintenance
PROJECT NUMBER: CP180641
ADVERTISEMENT DATE: November 12, 2018
PREPARED FOR: The Curators of the University of Missouri
CONSULTANT: The Clark Enersen Partners
2020 Baltimore Avenue
Suite 300
Kansas City, Missouri 64108
(816) 474-8237
Drawings and Specifications for the above noted project and the work covered thereby are herein
modified as follows, and except as set forth herein, otherwise remain unchanged and in full force
and effect:
ADVERTISEMENT FOR BIDS
1. CHANGE the time listed for the Prebid Meeting to be at 1:30pm. All other information related to
the Prebid Meeting remains the same.
2. ADD the following: Parking on campus in other than spaces marked as “Visitor Parking” require
pre-registration with the MU Parking & Transportation Office. Paper hangtag permits are no longer
used on the MU Campus and an electronic license plate scanner is utilized to monitor and enforce
permitted parking. Parking for the scheduled Prebid Meeting has been setup for bidders as an
event registration with parking made available on the top level of the Tiger Avenue Parking
Structure near the Medical Science Building. Please use the link provided below to pre-register
your vehicle with MU Parking & Transportation that will take you through the necessary steps to
register your license plate. License plate, make, style and color of the vehicle will be required.
Click here to register
SPECIFICATION CHANGES:
1. Section 04 43 13 – Anchored Stone Masonry Veneer
a. Subject to compliance with all specified requirements and equivalent features, construction,
and performance as specified manufacturer, the following are approved manufacturers:
2
a. EaCo Chem; NMD 80 Masonry Cleaner b. York 304; self adhering stainless steel flashing can be used but does not replace the
4mm stainless steel flshing requirement
2. Section 07 27 26 – Fluid Applied Membrane Air Barrier
a. Subject to compliance with all specified requirements and equivalent features, construction,
and performance as specified manufacturer, the following are approved manufacturers:
c. Carlisle Coating & Waterproofing; Barritech VP
3. Section 07 92 19 – Acoustical Joint Sealant
a. Subject to compliance with all specified requirements and equivalent features, construction,
and performance as specified manufacturer, the following are approved manufacturers:
b. Pecora AIS 919
4. Section 08 71 00 – Door hardware
a. Subject to compliance with all specified requirements and equivalent features, construction,
and performance as specified manufacturer, the following are approved manufacturers:
c. Closers – Stanley D4550 Closers
5. Section 09 30 00 – Tiling
a. Under subparagraph 2.5.A – Add
1) Top of Ceramic tile @ painted surface (when tile is not full height): Model
Schiene E 45: Size shall be verified by installer and consistent with tile
thickness.
2) Bottom of Ceramic tile @ epoxy cove base: Model Schiene E 45: Size shall be
verified by installer and consistent with tile thickness
6. Section 10 21 19 – Plastic Toilet Compartments
a. Subject to compliance with all specified requirements and equivalent features, construction,
and performance as specified manufacturer, the following are approved manufacturers:
b. Scranton Products
7. Section 10 51 13 – Metal Laboratory Casework
a. Subject to compliance with all specified requirements and equivalent features, construction,
and performance as specified manufacturer, the following are approved manufacturers:
b. Scranton Products
8. Section 12 35 53 – Metal Laboratory Casework
a. Subject to compliance with all specified requirements and equivalent features, construction,
and performance as specified manufacturer, the following are approved manufacturers:
b. Air Master Systems
9. Section 12 35 60 – Laboratory Furniture System
b. Subject to compliance with all specified requirements and equivalent features, construction,
and performance as specified manufacturer, the following are approved manufacturers:
b. Air Master Systems
10. Section 23 09 00 – Digital Control Equipment
a. Under subparagraph 2.1.C.2, Heading should read “Hydronic Chilled Water and Pipe
kits” and subsection a. should read “At minimum, chilled water and pipe kit control
3
valves shall be pressure independent...” The intent is that heating water AHU control
valves shall not be pressure independent. See piping schematics for additional
information.
11. Section 26 29 23 – Variable-Frequency Motor Controllers
a. Under subparagraph 2.1.A Toshiba Q9 or AS3 are acceptable model numbers.
DRAWING CHANGES:
1. Sheet C2.10 – Demolition Plan
2. Sheet C2.10 – Demolition Plan
a. REVISE limits of alley curb removal to account for a 4’-0” transition zone on both sides
3. Sheet C3.01 – Dimension Plan
a. REVISE legend to exclude new curb and gutter.
b. REVISE legend to reference Structural for the new generator pad.
c. REVISE legend to reference 6/C4.01 for sidewalk with turndown edge.
d. REVISE transition alley curb callouts to specify a 4 foot transition zone.
e. DELETE the segmental retaining wall to the south of the new generator pad.
f. REVISE generator pad callout to reference Structural.
g. DELETE new curb and gutter and associated callout.
h. ADD sidewalk with turndown edge in the area where new curb and gutter was
DELETED.
i. REVISE sidewalk callout to refence sidewalk with turndown edge.
4. Sheet C4.10 – Site Details
a. DELETE detail number 2 referencing new curb and gutter.
b. ADD detail number 6 for new sidewalk with turndown edge.
5. Sheet A6.10 – Enlarged Restroom Plans, Elevations, Schedule and Details
c. Text added to details 22, 23, 24 and 25/A6.10. Text to read “ALL WALLS WITHIN SHOWER
ENLOSURE TO BE FIBERGLASS REINFORCED EPOXY SYSTEM FROM CEILING DOWN TO INTERGRAL
EPOXY COVE BASE”
6. Sheet F1.10 – Room Finish General Notes
d. Revise Note 4 to read as: NOT USED
7. Sheet F1.30 – Room Finishes Schedule & Details
a. Room Finish General Notes
a. Revise Note 4 to read as: NOT USED
b. Add Room Finish Schedule Remark #3 to ROOM FINISH SCHEDULE room M124
c. Add room M158 – Corridor to ROOM FINISH SCHEDULE
8. Sheet M1.02 – HVAC Plan – Area B
a. Noted to make all dampers serving washers and canopy hoods motorized and stainless
steel construction.
9. Sheet M1.03 – HVAC Plan – Area C
a. Added exhaust air to Autoclave control room and made the room negative.
b. Added transfer grille and duct into control room from Clean Cage wash room.
c. Reduced supply airflow in control room and increased supply airflow in adjacent
corridor.
4
d. Reduced canopy hood exhaust to 600 CFM for each hood for autoclaves.
e. Showed fan coil units in existing electrical rooms.
10. Sheet M1.06 – HVAC Piping Plan – Area C
a. Added manual balance valve
b. Added FCU’s serving existing Electrical rooms.
11. Sheet M2.05 – First Floor Plumbing Plan – Area B
a. Added piping from Storage A153A to cage and rack washers for soap tubing distribution
12. Sheet M3.01 – Upper Level Mechanical Plan
a. Updated exhaust fan numbering to match schedule.
b. Updated VAV box airflows for new Autoclave control room pressurization.
13. Sheet M4.01 – Air Pressurization Plan
a. Updated pressurization airflows for autoclave control room.
14. Sheet M6.02 & M6.03 – Mechanical Controls
a. Updated exhaust fan callouts for new numbering.
15. Sheet M6.04 – Mechanical Details (sheet not attached)
a. See detail 15. Biosafety cabinet fan (EF-61) shall be noted as coated steel, not
fiberglass.
16. Sheet M7.01 – Mechanical Schedules
a. Updated weights and max dimensions of AHU’s and HRH.
17. Sheet M7.02 – Mechanical Schedules
a. Updated exhaust fan numbering on Exhaust Fan Schedule.
18. Sheet M7.03 – Mechanical Schedules
a. Updated CFM values to match changes to Autoclave control room pressurization.
b. Added Fan Coil Unit schedule for units that serve existing electrical rooms.
QUESTIONS:
1. Question 1 - The Room Finish Schedule of F1.30 Predominately has the floor finish of EXP-1. Does this
Exp-1 refer to the epoxy systems reference in Section 09 67 25 Reinforced & Non-Reinforced Epoxy
Wall Systems or the epoxy’s noted in Section 09 96 00 High Performance Coatings 09 96 00, 3.7, H.,
EPX-1 (Alternate).
a. EXP-1 on finish schedule for floor and base is to reference 09 67 23 - TROWELED QUARTZ
EPOXY RESINOUS FLOORING. Current finish legend references Troweled Epoxy. Addendum
002 will provide additional information.
2. Question 2 The Room Finish Schedule of F1.30 Predominately has the wall finish of PTE-1. Does this
PTE-1 refer to the epoxy systems reference in Section 09 67 25 Reinforced & Non-Reinforced Epoxy
Wall Systems or the epoxy’s noted in Section 09 96 00 High Performance Coatings 09 96 00, 3.7, G.?
a. The PTE-1 is intended to reference section 09 67 25 Reinforced & Non-Reinforced Epoxy Wall
Systems. Refer to interior lab elevations for extent of fiberglass reinforced epoxy wall system.
5
Standard Epoxy wall system to be applied at all locations where PTE-1 is shown on finish
schedule unless interior elevation states Fiberglass reinforced wainscot. Addendum 002 will
provide additional information.
3. Question 3 - Is it going to be required that we paint the new HVAC and misc. piping in Mechanical
Room A201 & M155 (reference M0.13, M3.01, FP1.01)?
a. Answer – ductwork, piping and sprinklers in A201 and M155 do not need to be painted.
b. Ceiling of A2.01 to be sprayed with cementitious fireproofing
4. Question 4 - Where might one find a good view of scheduled Room M124? Or could the length of the
corridor be defined? Partially viewed in lower Right-hand corner of G0.12?
a. Answer - Elevations of M124 to be provided in Addendum 002. Refer to A1.11 for overall
dimensions of plan and F1.10 for floor finish information.
5. Question 5 - Where can I see a detail of, or get a description of the “Closets” on each side of Rooms
A116 & A120?
a. Answer - Closets on sides of A116 & A120 to have the same floor, wall and ceiling finishes as
A116 & A120.
6. Question 6 - What is the intended wall finish for Alternate No. 3 Corridor M158?
a. Answer - Elevations of M158 to be provided in Addendum 002. M158 added to finish schedule
in addendum 001.
7. Question 7 - Rm A125 locker shower- Detail 10 shows no CT1 in shower but on F1-10 It is
marked on plans that all walls get CT1. Which is correct?
a. Answer - Ct-1 to be installed in locker areas, fiberglass reinforced epoxy system to be applied
in shower stall areas. A6.10 to be updated in addendum 001.
8. On A6-10 Detail 5- Mens locker west shows the shower wall gets ct1. Is this correct? Or
are the showers a prefab unit?
a. Answer - Showers to be epoxy reinforced wall system – info added in addendum 001. The
walls in the locker room as noted in detail 5/A6.10 are to receive tile up to the levels
shown.
9. General Note 4- Mop sink tile ,are we to use the CT1? No elevations or layout found per
the note. What room is the mop sink in? A150? and is there only one? Do we go from
inside corner to edge of the sink?
a. Answer - Only 1 mop sink in rm A150. Gen note 4 to be removed in addendum
001.
10. On all the ceramic wall details there is no schluter shown for the top of the wainscott walls
. Do you want a schluter Jolly on the top like on the outcorners?
a. Answer - Yes, additional items added to tile spec in addendum 001.
Attachments: C2.01.C3.01, C4.01, A6.10, F1.10. F1.30, M1.02, M1.03, M1.06, M2.05.
M3.01, M4.01, M6.02, M6.03, M7.01, M7.02, M7.03
END OF ADDENDUM # 001
/ / / / / / / / / / / / / / / / / / /
EXISTING SIDEWALK TO BEREMOVED AND REPLACED
EXISTING CURB AND GUTTERTO BE REMOVED
CONTRACTOR TO PROTECT EXISTING GRAVELDURING CONSTRUCTION PHASE. AT THE ENDOF CONSTRUCTION, REMOVE EXISTING GRAVELAND INSTALL NEW GRAVEL PER SHEET C3.01.
SAW CUT(TYP.)
SAW CUT(TYP.)
PORTION OF EXISTINGWALL TO BE REMOVED
EXISTING LANDSCAPINGTO BE REMOVED
EXISTING ACID WASTE TANKS TO BE REMOVED.NO REMEDIATION REQUIRED. TIE ACID WASTE LINEINTO SANITARY.
EXISTING FENCE TO BEREMOVED AND REPLACED
EXISTING SCREEN WALLTO BE REMOVED
EXISTING CONCRETE PAVEMENTTO BE REMOVED AND REPLACED
EXISTING CONCRETE PAVEMENTTO BE REMOVED AND REPLACED
SAW CUT(TYP.)
EXISTING LANDSCAPINGTO BE REMOVED
PORTION OF EXISTING ALLEY CURBTO BE REMOVED AND REPLACED NOTE:
CONTRACTOR TO COORDINATE WITH OWNERFOR THE REMOVAL OF CONCRETE PAVEMENTOUTSIDE OF THE EXISTING STAIR TOWER.
NOTE:DISTURBED AREAS IN RAISED PLANTERTO BE LEFT 18" BELOW EXISTING GRADE.
EXISTING LANDSCAPINGTO BE REMOVED
NOTE:DISTURBED AREA NORTH OF DEMARCATIONLINE TO BE LEFT 6" BELOW EXISTING GRADE.
EXISTING GRAVEL TO REMAIN
DEMARCATION LINE. MAINTENANCE SOUTHOF THIS LINE IS HOSPITAL RESPONSIBILITY.
001A
LEGEND
EXISTING GRAVEL TO BE REMOVED
EXISTING WALLS TO BE REMOVED
EXISTING SANITARY SEWER LINE TO BE REMOVED
EXISTING LANDSCAPING TO BE
REMOVED
EXISTING SIDEWALK TO BE REMOVED
EXISTING CURBS TO BE REMOVED
SAW CUT
/ / / / / / / / / / / / / / /EXISTING FENCE TO BE REMOVED
EXISTING CONCRETE PAVEMENT TO BE REMOVED
Kansas City, Missouri1251 NW Briarcliff Parkway, Suite 400Kansas City, MO 64116-1776816 474.8237 Fax 816 474.8233
Plot
Tim
e St
amp:
File
Loc
atio
n/N
ame:
www.scienceandresearchdesign.com
Science & Research Design Group
ACB
Key Plan
8/24
/201
8 12
:01:
07 P
MC
:\(1
) Rev
it Pr
ojec
ts\2
018\
6241
51-
A-1
8_dw
atki
ns.rv
t
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
CONTRACT DOCUMENTS
MU Project # CP180641
NOVEMBER 7, 2018
# SHEET HISTORY:?
? - #ISSUED 11/07/2018 CONTRACT DOCUMENTSA - 001 11/21/2018 ADDENDUM 001
C2.01PlanDemolition
NEW CONCRETE SIDEWALKWITH TURNDOWN EDGERE: 4/C4.01 AND 6/C4.01
NEW CONCRETEGENERATOR PADRE: STRUCTURAL
NEW RETAINING WALLRE: 3/C4.01
NEW CONCRETE PAVEMENTRE: 1/C4.01
EXPANSION JOINT(TYP.)
EXPANSION JOINT(TYP.)
EXPANSION JOINT(TYP.)
NEW 6' DECORATIVE FENCEWITH 4' GATE INSTALLED
NEW 8" THICK CONCRETEPAVEMENTRE: 1/C4.01
NEW 4' WIDECONCRETE SIDEWALK
INSTALL NEW GRAVEL SIMILAR TO EXISTING.BOTTOM OF GRAVEL TO BE LINED WITHGEOTEXTILE FABRIC.RE: 5/C4.01
NEW 8" THICK CONCRETE PAVEMENTRE: 1/C4.01
NEW 12" FLUSH ALLEY CURB
PROVIDE 2" PVC SLEEVE UNDER NEWSIDEWALK FOR IRRIGATION SYSTEM.RESTORE IRRIGATION SYSTEM IFDAMAGED/AFFECTED DURINGCONSTRUCTION.
CONTRACTOR TO RESTORE IRRIGATIONSYSTEM THAT MAY BE DAMAGED/AFFECTEDDURING CONSTRUCTION. (TYP.)
NEW 8' WIDE VIVARIUMDOOR
INSTALL 4" WIDE GREEN STEEL EDGINGWITH STAKES AT DEMARCATION LINE
EXISTING FUEL LINE TO BE LOCATED ANDPROTECTED DURING THE INSTALLATIONOF NEW CONCRETE GENERATOR PAD.RELOCATE IF NECESSARY.
SEE GRADING PLAN ATNORTHEAST DOOR.DETAIL 1 THIS SHEET.
INSTALL 15 LF 8" PVC PIPEPER SPECIFICATIONS
RE-STRIPE NEW CONCRETEPAVEMENT PER SPECIFICATIONS.
SEE GENERATOR PAD ELEVATIONS.DETAIL 2 THIS SHEET.
4' TRANSITION ZONE TOMATCH EXISTING ALLEYCURB HEIGHT
4' TRANSITION ZONE TOMATCH EXISTING ALLEYCURB HEIGHT
MATCH EXISTINGJOINT PATTERN
001A
001A
001A
001A
001A
001A
NEW PORTLAND CEMENT CONCRETE PAVEMENT
RE 1/C4.01
NEW RETAINING WALL
RE: 3/C4.01
LEGEND:
NEW CONCRETE PAD
RE: STRUCTURAL
NEW CONCRETE SIDEWALK
RE: 4/C4.01 AND 6/C4.01
NEW GRAVEL
RE: 5/C4.01
NEW 6' DECORATIVE FENCE
001A
742.88±
M.E.
742.78
±
M.E.
743.06±
M.E. 74
3.24±
M.E
.
743.26±
M.E.
742.96±
M.E.
743.37
743.37
743.37
743.37
743.
37743.18
743.0
9
743.26
743.28
TW 745.50
TS 744.20
743.90±M.E. 744.00±
M.E.
TS 744.20
TS 744.20TS 744.20
742.40±M.E. 742.95±M.E.
Kansas City, Missouri1251 NW Briarcliff Parkway, Suite 400Kansas City, MO 64116-1776816 474.8237 Fax 816 474.8233
Plot
Tim
e St
amp:
File
Loc
atio
n/N
ame:
www.scienceandresearchdesign.com
Science & Research Design Group
ACB
Key Plan
8/24
/201
8 12
:01:
07 P
MC
:\(1
) Rev
it Pr
ojec
ts\2
018\
6241
51-
A-1
8_dw
atki
ns.rv
t
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
CONTRACT DOCUMENTS
MU Project # CP180641
NOVEMBER 7, 2018
# SHEET HISTORY:?
? - #ISSUED 11/07/2018 CONTRACT DOCUMENTSA - 001 11/21/2018 ADDENDUM 001
C3.01PlanDimension
1" = 5'
GRADING PLAN AT NORTHEAST DOOR
1
1" = 5'
GENERATOR PAD ELEVATIONS
2
001A
Not to Scale
FULL DEPTH CONCRETE PAVEMENT DETAILS
1
8" REINFORCED CONCRETE PAVEMENT
REINFORCED W/ #4 @ 18" EACH WAY AT
MID DEPTH OF CONCRETE SUPPORTED
ON BAR SUPPORTS
6" MIN. SCARIFIED AND
COMPACTED SUBGRADE, OR
COMPACTED SUITABLE
MATERIAL PER
SPECIFICATIONS
6" MODOT TYPE 5 AGGREGATE
BASE COURSE
NOTE: ALL IRREGULAR SLABS AND
RECTANGULAR SLABS EXCEEDING LENGTH
TO WIDTH RATIO OF 1.25 SHALL BE
ADDITIONALLY REINFORCED WITH
W6X6-W6X6 W.W.F.
3
4
" MIN.
T/4
T
CONSTRUCTION JOINT DETAIL
Not to Scale
CONTRACTION JOINT DETAIL
Not to Scale
T/4
"T"
1
8
"
SAWCUT ALL
CONTRACTION JOINTS
(THICKNESS)
T/2
JOINT SEALER,
ASTM D-3406-85
NON EXTRUDED,
PRE MOLDED,
COMPRESSIBLE
MATERIAL ASTM
D-1752-83
BOND
BREAKER
MATERIAL
3
4
"
3
4
"
1
8
" TO
1
4
"
1
8
"
1
4
" R (TYP.)
EXPANSION JOINT DETAIL
Not to Scale
#4 x 10" LONG DOWELS @
18" O.C. PAINT AND GREASE
ONE END
5" x
3
4
" METAL
TUBE SLEEVE
NOTE:
ALL JOINTS SHALL BE SEALED WITH
NON-BITUMINOUS SEALANT, COLOR GRAY
SEALED
JOINTS
SEALED
JOINTS
Not to Scale
NOT USED
2
GENERAL NOTES:
1.
1
2
" EXPANSION JOINTS WITH 2' DOWELS SHALL BE
PLACED AT RADIUS POINTS AND AT 150'
INTERVALS. THESE DOWELS SHALL BE GREASED
AND WRAPPED ON ONE END WITH EXPANSION
TUBES.
2. 1” DEEP CONTRACTION JOINTS SHALL BE
INSTALLED AT APPROXIMATELY 10' INTERVALS.
THESE JOINTS SHALL PASS ACROSS THE ENTIRE
CURB SECTION.
3. FIX DOWELS WITH BAR SUPPORTS.
4. CONCRETE SHALL CONFORM TO SPECIFICATIONS.
5. USE
5
8
" Ø x 2' SMOOTH DOWELS AT LOCATIONS
SHOWN ON EACH TYPICAL SECTION.
6. DEPTH OF CURB SHALL BE A MINIMUM OF 8” THRU
THE ACCESSIBLE RAMPS.
7. CURBS SHALL BE POURED MONOLITHIC WITH
FULL DEPTH CONCRETE PAVEMENT, AS
INDICATED IN THE PLANS. OMIT CUTTER LINE
JOINT, UNLESS SPECIFICALLY SHOWN ON THE
PLANS.
8. SEE DIMENSION & GRADING PLANS FOR
LOCATION OF WET & DRY CURBS.
9. OMIT CONSTRUCTION JOINT AND POUR CURBS
MONOLITHIC WITH NEW PAVEMENT, AS INDICATED
IN THE PLANS. ANY VARIATIONS MUST BE
APPROVED BY THE ENGINEER, PRIOR TO
INSTALLATION.
PROOF ROLL SUBGRADE
SEE SPECIFICATIONS
4,000 PSI REINFORCED
CONCRETE WITH #4
REBAR AT 18' O.C.E.W ON
BAR SUPPORTS
ALL CONTROL JOINTS SHALL FIRST BE
1
8
"
STRAIGHT SAWCUTS BY 1
1
2
" DEEP. AFTER THE
CONCRETE HAS HARDENED, CONTRACTOR
SHALL BEVEL CUT THE CONTROL JOINTS WITH
WITH A
3
8
" V-GROOVE BLADE.
SLOPE
1% MIN., 1.5% MAX
SIDEWALK NOTES:
1. CONCRETE SHALL CONFORM TO SPECIFICATIONS.
2.
1
2
" RUBBER EXPANSION JOINTS SHALL BE PLACED WHERE
WALK ABUTS JUNCTION OF EXISTING WALK, CONCRETE
CURBS, DRIVEWAYS, AND SIMILAR STRUCTURES, AND AS
SHOWN IN THE PLAN DRAWINGS.
3. CONTROL JOINTS SHALL BE PLACED AS SHOWN ON THE
DRAWINGS OR AT DISTANCE NOT EXCEEDING THE LENGTH
TO WIDTH RATIO OF 1.25.
4. SAWCUT ALL CONTROL JOINTS.
5. KEY ALL CONSTRUCTION JOINTS.
6. ALL JOINTS SHALL BE SEALED WITH VULCAN 45 OR DOW
CORNING 888 SILICON JOINT SEALANT
4" MoDOT TYPE 1
AGGREGATE BASE
6"
V-GROOVE
CONTROL JOINT
EXPANSION JOINT
1
4
" R
12"
JOINT SEALER
1
2
" RUBBER
EXPANSION
JOINT
1/4
D
3
8
" V-GROOVE
D
Not to Scale
STANDARD SIDEWALK AND JOINT DETAILS
4
6"
6"
SLOPE
1% MIN., 1.5% MAX
4"
EXPANSION
JOINT
BUILDING
LINE
6"
SEE STANDARD
SIDEWALK FOR
SUBGRADE
REQUIREMENTS
Not to Scale
SIDEWALK SECTION @ BUILDING
4.1
6" 6"
1
2
" PREMOLDED
EXPANSION JOINT
WITH SEALANT
#4x9"DOWEL HALF
WRAPPED IN TAR
PAPER 18" O.C.
6"
SEE STANDARD
SIDEWALK FOR
SUBGRADE
REQUIREMENTS
Not to Scale
SIDEWALK SECTION @ CURBS
4.2
NOTE:
ALL JOINTS SHALL BE SEALED
JOINT SEALER
BELOW V-GROOVE
12"
1.00
'
2.0'
#5 VERTICAL DOWELLS @ 12"
O.C. (CENTERED)
3/4" CHAMFER (EACH SIDE)
#5 CONTINUOUS (EQUALLY SPACED)
PAVEMENT CONTROL JOINTS SHALL
EXTEND THROUGH WALLS WITH
INTERRUPTED REINFORCING STEEL.
ALL CONTROL JOINTS SHALL BE SEALED
2-#5 CONTINOUS
BOTTOM BARS
6" M
IN.
30"
MA
X.
Not to Scale
INTEGRAL RETAINING WALL DETAIL
3
2" WEEPS AT ± 10' O.C.
CENTER WEEP HOLE W/
PAVEMENT JOINTS
2" KEYED CONSTRUCTION JOINT
FULL DEPTH
PAVEMENT OR
SIDEWALK
FINISHED GRADE
± 3" BELOW
TOP OF WALL
2"
3/4" CLEAN
BACKILL
FILTER FABRIC
OVER WEEPS
Not to Scale
GRAVEL PAVEMENT DETAIL
5
GEOTEXTILE FABRIC
RE: SPECS
6" MoDOT TYPE 5
GRANULAR MATERIAL
6" COMPACTED
SUBGRADE PER SPEC.
Not to Scale
SIDEWALK WITH TURNDOWN EDGE
6
6"
12"
#5 DOWELS @
12" O.C.
12" M
IN
.
1" RADIUS
REINFORCED
CONCRETE
SIDEWALK
RE: 4/C4.01
SLOPE
1% MIN., 1.5% MAX
#5 DOWELS CONT.
EQUALLY SPACED
CONCRETE PAVEMENT
RE: 1/C4.01
6"
18"
EXPANSION
JOINT
001A
001A
Kansas City, Missouri1251 NW Briarcliff Parkway, Suite 400Kansas City, MO 64116-1776816 474.8237 Fax 816 474.8233
Plot
Tim
e St
amp:
File
Loc
atio
n/N
ame:
www.scienceandresearchdesign.com
Science & Research Design Group
ACB
Key Plan
8/24
/201
8 12
:01:
07 P
MC
:\(1
) Rev
it Pr
ojec
ts\2
018\
6241
51-
A-1
8_dw
atki
ns.rv
t
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
CONTRACT DOCUMENTS
MU Project # CP180641
NOVEMBER 7, 2018
# SHEET HISTORY:?
? - #ISSUED 11/07/2018 CONTRACT DOCUMENTSA - 001 11/21/2018 ADDENDUM 001
C4.01DetailsSite
PLUMBING FIXTURE SCHEDULE
MOUNTING LOCATIONDESCRIPTION TYPE
WATER COOLERSTANDARD
ADA*
38" A.F.F. TO TOP OF WATER COOLER
34" A.F.F. TO TOP OF WATER COOLER
STANDARD
ADA*
STANDARD
ADA*
STANDARD
ADA*
TOILET
URINAL
SINK
15" A.F.F. TO TOP OF SEAT
17" A.F.F. TO TOP OF SEAT
23" A.F.F. TO RIM
15 1/4" A.F.F. TO RIM, VERIFY W/ MFR.
34" A.F.F. TO RIM
34" A.F.F. TO RIM
CHILD (CHD) 15" A.F.F. TO TOP OF SEAT
CHILD (CHD) 30" A.F.F. TO RIM
*TO COMPLY WITH 2010 ADA STANDARDS OF ACCESSIBLE DESIGN
1. REFERENCE LABORATORY SHEETS, IF APPLICABLE, FOR PAPER TOWEL DISPENSERS.
RESTROOM GENERAL NOTES:X11 X12
EJ
U
V
E
A6.1013 11
12
10
A6.1016
17
15
14
A6.10
4
A6.10
6
7
8
93
2
5
LOCKER / SHOWER
A124
MEN
A124A
WOMEN
A125A
LOCKER / SHOWER
A125
AIRLOCK
A123
H3
H3
H3
F6
A3
H3
H3
H3
G3
G3
G3
G3
G3
G3
A3
A2
A3A3
A3A3
A1
A1
A2
H3
H3
H3
A123.3
A123.1
A124 A124A
A123.2
A125
A125A
18' - 5 1/2"
1' - 4 1/2"
8' - 3 1/8"
12' - 3 3/8" 17' - 4 1/2" 1' - 0 7/8"
8' - 4"
6' - 8 1/8"
4 7/8"
12' - 9 1/8"
4 7/8" 5' - 6" 4 7/8" 13' - 6 61/128" 5 7/8" 9' - 11 99/128" 4 7/8"
4 7/8"
4' - 1 119/128"
3' - 0"
5' - 6" 4 7/8" 10' - 6 3/4" 2' - 11 93/128" 4 7/8" 10' - 0 99/128"
7' - 1 1/8" 4 7/8" 6' - 0 115/128" 4 7/8" 5' - 1 1/8" 4 7/8"
2' - 2 5/8"
5' - 11 3/8"
4 7/8"
4' - 10 7/8"
4 1/4"
1' - 1 1/2"
4 1/4"
5' - 3 3/8"
5' - 3 7/8"
2' - 1 1/8"
5' - 0 13/128" 7 1/4" 4' - 9 7/8"
3' - 6" 2' - 9"
SD-1
M1
M1
SD-1
3' - 2 3/8"
SD-1M1
SD-1M1
GB-2
GB-3
TTD-4
GB-1
GB-1
GB-2
SND-1
TTD-4
GB-3
SND-1
TTD-4
EQ
EQ
1' - 8"
8/A8.10
A6.1022
23
A6.10
25
24 6"
6"
SP-1 SP-1
SP-1
SNV-1
ELECT. HAND DRYER
ELECT. HAND DRYER
001A
ALL (4) WALLS WITHIN SHOWER ENLOSURE TO BE FIBERGLASS REINFORCED EPOXY SYSTEM FROM CEILING DOWN TO INTERGRAL EPOXY COVE BASE
15x18x72 "Z" LOCKERS
6" TROWEL APPLIED EPOXY BASE
CT-1
5' - 6"
A123.2
15x18x72 "Z" LOCKERS
6" TROWEL APPLIED EPOXY BASE
CT-1
5' - 6"
SHOWER BEYOND
8/A8.10
SimA125
15x18x72 "Z" LOCKERS
6" TROWEL APPLIED EPOXY BASE
CT-1
5' - 6"
8/A8.10
Sim
15x18x72 "Z" LOCKERS
6" TROWEL APPLIED EPOXY BASE
CT-1
LOCKER FILLER PANEL, TYP. EACH SIDE
8/A8.10
Sim
8/A8.10
Sim
A125
2' - 10"
6" TROWEL APPLIED EPOXY BASE
SD-1
5' - 6"
CT-1
M1
MAX
4' - 0"
PROVIDE STEEL ABOVE CEILING PER MANUACTURER TO SUPPORT PARTITION
CEILING HUNG TOILET PARTITIONGB-3
GB-2
GB-1
TTD-4
TTD-4
ADA
6" TROWEL APPLIED EPOXY BASE
CT-1
1' - 6"
4' - 0"
SP-1
SP-1
PROVIDE STEEL ABOVE CEILING PER MANUACTURER TO SUPPORT PARTITION
CEILING HUNG TOILET PARTITION
TTD-4
A125A
SND-1
6" TROWEL APPLIED EPOXY BASE
5' - 6"
PTD-1
CT-1
SP-1
2' - 10"
M1 M1
6" TROWEL APPLIED EPOXY BASE
SD-1
SD-1
5' - 6"
CT-1
INSTALL TILE BEHIND MIRROR, TYP.
3' - 8"
ELECT. HAND DRYER
15x18x72 "Z" LOCKERS
CT-1
6" TROWEL APPLIED EPOXY BASE
5' - 6"
5' - 6"
8/A8.10
Sim
A124A
6" TROWEL APPLIED EPOXY BASE
PTD-1
CT-1
5' - 6"
GB-3
GB-2
GB-1
TTD-4
ADA
6" TROWEL APPLIED EPOXY BASE
CT-15' - 6"
ADA
SP-1
A3
PROVIDE STEEL ABOVE CEILING PER MANUACTURER TO SUPPORT PARTITION
CEILING HUNG TOILET PARTITION
A124
6" TROWEL APPLIED EPOXY BASE
SD-1CT-1
2' - 10"
5' - 6"
PROVIDE STEEL ABOVE CEILING PER MANUACTURER TO SUPPORT PARTITION
CEILING HUNG TOILET PARTITION
2' - 10"
6" TROWEL APPLIED EPOXY BASE
M1 M1SD-1
CT-1
5' - 6"
INSTALL TILE BEHIND MIRROR, TYP.
3' - 8"
A123.3
15x18x72 "Z" LOCKERS
CT-1
6" TROWEL APPLIED EPOXY BASE
5' - 6"
8/A8.10
Sim
15x18x72 "Z" LOCKERS
LOCKER FILLER PANEL, TYP. EACH SIDE
8/A8.10
A12415x18x72 "Z" LOCKERS
CT-1
6" TROWEL APPLIED EPOXY BASE
5' - 6"
XB
X7
A
3.6
A6.10
21
20
19
A149
2' - 0 7/8" 2' - 8 1/2" 2' - 5 1/2" 4 7/8"
5 1/2"
10' - 2 1/8"
1' - 6"
RESTROOM
A149
GB-2
GB-3
TTD-4
SND-1
GB-1
SD-1
M1
ELECT. HAND DRYERGB-1
GB-3
GB-2
TTD-4
ADA
4' - 0"
SP-1
GB-3
GB-2
GB-1
SD-1TTD-4
SND-1
M1
3' - 8"
SD-1
A149
GB-1
GB-2
001A
ALL WALLS WITHIN SHOWER ENLOSURE TO BE FIBERGLASS REINFORCED EPOXY SYSTEM FROM CEILING DOWN TO INTERGRAL EPOXY COVE BASE
GB-1
GB-2
001A
ALL WALLS WITHIN SHOWER ENLOSURE TO BE FIBERGLASS REINFORCED EPOXY SYSTEM FROM CEILING DOWN TO INTERGRAL EPOXY COVE BASE
SC-1
GB-1
GB-2
001A
ALL WALLS WITHIN SHOWER ENLOSURE TO BE FIBERGLASS REINFORCED EPOXY SYSTEM FROM CEILING DOWN TO INTERGRAL EPOXY COVE BASE
FDS-1
GB-1
GB-2
001A
ALL WALLS WITHIN SHOWER ENLOSURE TO BE FIBERGLASS REINFORCED EPOXY SYSTEM FROM CEILING DOWN TO INTERGRAL EPOXY COVE BASE
38"
MA
X
48"
MA
X
33
" -
36
"
18"
33
" -
36
"18"
18"
CONTROL
AREA
GRAB
BAR
ACCESSIBLE
SHOWER STALL
CONTROL WALL
ACCESSIBLE
SHOWER STALL
BACK WALL
FIRE EXTINGUISHER
CABINET &
BRACKET
MAX
4"
27"
MIN
48
" -
54
"
48
" -
54
"
SIGNAGE
REQUIREMENTS
TEXT
TEXT
48"
MIN
60"
MA
XFOLD-
DOWN
SHOWER
SEAT
GRAB
BAR
48"
TOWEL
SLOT
ADULT PAPER
TOWEL
DISPENSER
36"
MA
X
38
" -
43
"
SPOUT
ADULT
ELECTRIC
WATER
COOLER
29"
MIN
34"
MA
X
40"
48"
MA
X
SOAP
VALVE
ADULT
LAVATORY/MI
RROR/ SOAP
DISPENSER MIN
17"
MAX
6"
MIN
8"
MIN9"
MIN
27"
INSULATE
HOT WATER
& DRAIN
PIPES
17
" -
19
"
WATER
CLOSET
ADULT
HANDICAPPED
TOILET STALL
15
" -
48
"
7" - 9"
33
" -
36
"
39
" -
41
"1
8" 42" 12"
39" - 41"
GRAB
BARS
COAT
HOOK
STALL
DOOR
9"
MIN
15
" -
48
"
TOILET
TISSUE
18"
33
" -
36
"
6" 36"
6"
Kansas City, Missouri
2020 Baltimore Avenue, Suite 300
Kansas City, MO 64108-1949
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plot Time Stamp:
File Location/N
ame:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
AC
B
Key Plan
11/21/2018 3:20:13 PM
C:\(1) Revit Projects\2018\624151- A-18_dwatkins.rvt
Enlarged Restroom
Plans, Elevations,
Schedule & Details
A6.10
TCEP No.: 624-151-18
University of Missouri
Medical Science
Building - Research
Vivarium Upgrade &
Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTSABBR. ACCESSORY MANUFACTURER MODEL NUMBER FURNISHED BY INSTALLED BY MOUNTING HEIGHT REMARKS
FDS-1 FOLD DOWN SHOWER SEAT BOBRICK B-5191 CONTRACTOR CONTRACTOR INSTALL PER MANUF. REC.
GB-1 36" GRAB BAR BOBRICK B-6806.99x36 CONTRACTOR CONTRACTOR 33" TO TOP OF GRIPPING SURFACE6" FROM SIDE WALL TOCENTERLINE
GB-2 48" GRAB BAR BOBRICK B-6806.99x48 CONTRACTOR CONTRACTOR 33" TO TOP OF GRIPPING SURFACE12" FROM SIDE WALL TOCENTERLINE
GB-3 18" GRAB BAR - VERTICAL BOBRICK B-6086.00x18 CONTRACTOR CONTRACTOR 39" FROM REAR WALL TOCENTERLINE, 39" AFF TO BOTTOM
M1 2'-0" W x 3'-0" H MIRROR BOBRICK B-165 2436 CONTRACTOR CONTRACTOR 40" A.F.F. TO BOTTOM OFREFLECTIVE SURFACE
MH-1 MOP AND BROOM HOLDER BOBRICK B-239 CONTRACTOR CONTRACTOR
PTD-1 PAPER TOWEL DISPENSER 48" A.F.F TO PAPER TOWELOPENING
S-2 SS SHELF BOBRICK B-295 x 24 CONTRACTOR CONTRACTOR
SC-1 SHOW ROD AND CURTAIN CONTRACTOR CONTRACTOR
SD-1 SOAP DISPENSER OWNER CONTRACTOR 48" A.F.F. TO DISPENSER OPENING
SND-1 SANITARY NAPKIN DISPOSAL BOBRICK B-270 CONTRACTOR CONTRACTOR BELOW GRAB BAR
SNV-1 SANITARY NAPKIN VENDOR BOBRICK B-4706 50. CONTRACTOR CONTRACTOR
SP-1 SEAT PROTECTOR BOBRICK B-221 CONTRACTOR CONTRACTOR 48" A.F.F. TO DISPENSER OPENING
TTD-4 TOILET TISSUE DISPENSER BOBRICK OWNER CONTRACTOR 30" A.F.F. TO TOP OF DISPENSER20" FROM BACK WALL
TOILET ACCESSORY SCHEDULE
SCALE: 1/4" = 1'-0"
ENLARGED RESTROOM AND LOCKER PLANS1
SCALE: 1/4" = 1'-0"
WOMENS LOCKER WEST13SCALE: 1/4" = 1'-0"
WOMENS LOCKER NORTH10SCALE: 1/4" = 1'-0"
WOMENS LOCKER EAST11 SCALE: 1/4" = 1'-0"
WOMENS LOCKER SOUTH12
SCALE: 1/4" = 1'-0"
WOMENS WEST16SCALE: 1/4" = 1'-0"
WOMENS NORTH14SCALE: 1/4" = 1'-0"
WOMENS EAST15SCALE: 1/4" = 1'-0"
WOMENS SOUTH17
SCALE: 1/4" = 1'-0"
MENS LOCKER SOUTH4
SCALE: 1/4" = 1'-0"
MENS EAST7SCALE: 1/4" = 1'-0"
MENS SOUTH8SCALE: 1/4" = 1'-0"
MENS WEST9SCALE: 1/4" = 1'-0"
MENS NORTH6
SCALE: 1/4" = 1'-0"
MENS LOCKER WEST5SCALE: 1/4" = 1'-0"
MENS LOCKER NORTH2SCALE: 1/4" = 1'-0"
MENS LOCKER EAST30 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8'
0 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8'
0 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8'
0 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8'
SCALE: 1/4" = 1'-0"
ENLARGED RESTROOM PLAN18
SCALE: 1/4" = 1'-0"
UNISEX SOUTH19SCALE: 1/4" = 1'-0"
UNISEX WEST20
SCALE: 1/4" = 1'-0"
UNISEX NORTH21
0 2' 4' 8'0 2' 4' 8'
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
WOMENS SHOWER WEST22SCALE: 1/4" = 1'-0"
WOMENS SHOWER NORTH23SCALE: 1/4" = 1'-0"
MENS SHOWER NORTH24SCALE: 1/4" = 1'-0"
MENS SHOWER SOUTH250 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8'
SCALE: 1/4" = 1'-0"
TYP. ADA MOUNTING HEIGHTS260 2' 4' 8'
A - 001 11/21/2018 ADDENDUM 001
UP
UP
UP
CORNER GUARDS
CG-1 MANUFACTURER:
PRODUCT:
COLORWAY:
PROFILE:
C/S ACROVYN
STAINLESS STEEL CORNER GAURD - CO SERIES (8'-0")
BRUSHED STAINLESS STEEL
CG-2 MANUFACTURER:
PRODUCT:
COLORWAY:
PROFILE:
C/S ACROVYN
STAINLESS STEEL CORNER GAURD - CO SERIES (8'-0")
BRUSHED STAINLESS STEEL
CG-3 MANUFACTURER:
PRODUCT:
COLORWAY:
PROFILE:
PAWLING
CG-20
TBD
1. PAINT ALL HOLLOW METAL DOORS & FRAMES TO MATCH ADJACENT WALL COLOR, TYP.
2. RUBBER BASE SHALL NOT BE APPLIED TO CMU AND CONCRETE WALLS, TYP.
3. SEE INTERIOR ELEVATIONS AND FINISH FLOOR PLAN FOR EXTENT OF PAINT AND WALL COVERING FINISHES DESIGNATED ON FINISH SCHEDULE.
4. NOT USED
5. SEE REFLECTED CEILING PLAN.
ROOM FINISH GENERAL NOTES
001A
XA
X6 X8 X10 X11 X12
XB
XD
XF
XH
XI
EJ
X13
K M
EK
EL
U
V
X7 X9X5X4X3X2X1
XC
XE
XG
1
1
2
2
3
3
4
4
5
5
A A
E E
C C
B B
D D
3.6 4.6
3.1
1 2 3 4 5
A
B
D
E
C
IRRADIATION
M149
STEP DOWN
A126A
HUMANIZED BSL II
A120
PROCEDURE
A120B
DIRTY CAGEWASH
A153
FEED & BEDDING
A131A
ANIMAL HOLDING(BREEDING)
A144
ANIMAL HOLDING(BREEDING)
A141
ANIMAL HOLDING(BREEDING)
A139
ANIMAL HOLDING(BREEDING)
A137
ANIMAL HOLDING(EXPERIMENTAL)
A138
ANIMAL HOLDING(BREEDING)
A140
ANIMAL HOLDING(EXPERIMENTAL)
A145
SURGERY
A120A
MECHANICAL
M155
AIRLOCK /GOWNING
A122
AIRLOCK
A126
MEN
A124A
WOMEN
A125A
LOCKER / SHOWER
A125
AIRLOCK
A123
LOCKER / SHOWER
A124
PROCEDURE(EUTHENASIA)
A148
PROCEDURE
A143A
PROCEDURE
A143B
PROCEDURE
A140A
PROCEDURE
A138A
PROCEDURE
A136
STORAGE
A107
VHP
A108
ANTE / GOWNING
A102
CLEAN CAGESTORAGE
A134
ANTE / GOWNING
A112
PROCEDURE
A116A
BSL II
A116
DIRTY
A116B
ANTE RM
A146
GNOTOBIOTIC /GERM FREE
A146A
CLEAN CAGEWASH
A131
RESTROOM
A149
AIRLOCK
A151
OPEN OFFICE
M157
OFFICE
A103
AREA B
AREA C
CUST.
A150
AIRLOCK
A114
ANIMAL HOLDING(BREEDING)
A143
PROCEDURE
A145A
CORRIDOR
A147
CORRIDOR
A130
CYLINDER
A152
CORRIDOR
A101
EXIST.
MY100
CORRIDOR
A109
CORRIDOR
M124
HATCHED AREAS NOT IN SCOPE
CLEAN
A116C
CLEAN
A120C
CORRIDOR
A142
EPX-1 EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1 EPX-1
EPX-1
EPX-1
CG-1
CORRIDOR
A113
CORR.
A132
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1EPX-1
EPX-1
EPX-1
EPX-1
EPX-1 EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
EPX-1
LVT-1
PI SUPPORT
A154
LVT-1
3.1 3.6 4.6
EPX-1
EPX-1
EPX-1
ENVIRONMENTAL
A106
BEHAVIORAL
A105
FRAGMENTORS
A104
RFT RFT
PTE-3
PTE-2PTE-2PTE-2
PTE-3
RFT-1 (SEE SHEET F1.30 - FINISHES LEGEND)
RFT-2 (SEE SHEET F1.30 - FINISHES LEGEND)
RFT-3 (SEE SHEET F1.30 - FINISHES LEGEND)
RFT LEGEND
2
3
2 2
2
2
2
2
2
2
2 2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2 2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3 3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3 3
3 3
3 3 3 3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
2
PTE-2
CORRIRDOR
M158
PT-2
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1CG-1 CG-1
CG-1
CG-1
CG-1
CG-1CG-1
CG-1
CG-1
CG-1
CG-1
CG-1 CG-1
CG-1
CG-1
CG-1CG-1
CG-1
CG-1 CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1 CG-1
CG-1
CG-1
CG-1 CG-1
CG-1
CG-1
CG-1CG-1
CG-1
CG-1
CG-1
CG-1CG-1
CG-1CG-1
CG-1 CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1CG-1
CG-2
CG-1
CG-1
CG-1
CG-1 CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1 CG-1
CG-1
CG-1CG-1
CG-1
CG-1
CG-1
CG-1
CG-1 CG-1
CG-1 CG-1
CG-1 CG-1
CG-1
CG-1
CG-1CG-1
CG-1
CG-1CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1 CG-1
CG-1
CG-1 CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
CG-1
2
CG-3 CG-3
CG-1
CG-1
CT-1
CT-1
CT-1CT-1
CT-1
1' - 8"
PTE-2
001A
Kansas City, Missouri
2020 Baltimore Avenue, Suite 300
Kansas City, MO 64108-1949
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plot Time Stamp:
File Location/N
ame:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
AC
B
Key Plan
11/21/2018 3:20:19 PM
C:\(1) Revit Projects\2018\624151- A-18_dwatkins.rvt
First Floor Finishes Floor
Plan
F1.10
TCEP No.: 624-151-18
University of Missouri
Medical Science
Building - Research
Vivarium Upgrade &
Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTS
FINISH EQUIPMENT
SCALE: 1/8" = 1'-0"
MAIN LEVEL FINISHES FLOOR PLAN1
A - 001 11/21/2018 ADDENDUM 001
ACOUSTIC CEILING TILE
APC-1 MANUFACTURER:
PRODUCT:
SIZE:
COLORWAY:
TYPE:
#869 WHITE
24" X 24" X 5/8"
CLEAN ROOM VL & CLEAN ROOM GRID
ARMSTRONG
SMOOTH TEXTURE/MINERAL FIBER
RESILIENT FLOORING
SOLID SURFACE
SS-1 MANUFACTURER:
PRODUCT:
COLORWAY:
APPLICATION: SEE DRAWINGS
GLACIER WHITE
CORIAN
DUPONT
WOOD SPECIES AND FINISH
WD-1 MANUFACTURER:
SPECIES:
FINISH: MATCH EXISTING
OAK - MATCH EXISTING
SEE SPECIFICATIONS
PAINT
PTE-1 MANUFACTURER:
HUE:
FINISH:
APPLICATION: SEE PARTITION SCHEDULE
SEE SPECIFICATION
MATCH SW7042
SEE SPECIFICATION (EPOXY SYSTEM)
PT-1 MANUFACTURER:
HUE:
FINISH:
APPLICATION: SEE PARTITION SCHEDULE
EGGSHELL
SW7042 SHOJI WHITE
SEE SPECIFICATION
PT-2 MANUFACTURER:
HUE:
FINISH:
APPLICATION: SEE PARTITION SCHEDULE
EGGSHELL
SW7036 ACCESSIBLE BEIGE
SEE SPECIFICATION
PT-3 MANUFACTURER:
HUE:
FINISH:
APPLICATION: SEE PARTITION SCHEDULE
EGGSHELL
SW6129 RESTRAINED GOLD
SEE SPECIFICATION
EPOXY FLOORING/BASE
EPX-1 MANUFACTURER:
PRODUCT:
THICKNESS:
COLORWAY:
TYPE:
--
1/4"
SEE SPECIFICATION
SEE SPECIFICATION
TROWELED QUARTZ
RFT-1 MANUFACTURER:
PRODUCT:
COLORWAY:
NOTE: 12" X 12"
PEWTER #51908
STANDARD EXCELON IMPERIAL TEXTURE
ARMSTRONG
RFT-2 MANUFACTURER:
PRODUCT:
COLORWAY:
NOTE: 12" X 12"
SMOKEY BROWN #51868
ARMSTRONG
RFT-3 MANUFACTURER:
PRODUCT:
COLORWAY:
NOTE: 12" X 12"
HONEY #59241
ARMSTRONG
STANDARD EXCELON IMPERIAL TEXTURE
STANDARD EXCELON IMPERIAL TEXTURE
LVT-1 MANUFACTURER:
PRODUCT:
COLORWAY:
NOTE: 36" X 36"
#832 RIVER ROCK
MOHAWK
HOT AND HEAVY - BOLDER
RESILIENT WALL BASE
RB-1 MANUFACTURER:
PRODUCT:
COLORWAY:
NOTE: TOE BASE
BURNT UMBER
RUBBER BASE
JOHNSONITE
APC-2 MANUFACTURER:
PRODUCT:
SIZE:
COLORWAY:
TYPE:
WHITE
24" X 24" X 5/8"
RADAR BASIC #2120
USG
MEDIUM TEXTURE/MINERAL FIBER
CERAMIC TILE
CT-1 MANUFACTURER:
PRODUCT:
SIZE:
COLORWAY:
GROUT:
#X714 MATTE DESERT GREY
6" X 6"
GLAZED CERAMIC TILE
DALTILE
MAPEI #27 SILVER (EPOXY)
MRF-1 MANUFACTURER:
PRODUCT:
THICKNESS:
COLORWAY:
TYPE:
AS SELECTED BY ARCH.
SEE SPECIFICATION
SEE SPECIFICATION
SEE SPECIFICATION
SEE SPECIFICATION
1. PAINT ALL HOLLOW METAL DOORS & FRAMES TO MATCH ADJACENT WALL COLOR, TYP.
2. RUBBER BASE SHALL NOT BE APPLIED TO CMU AND CONCRETE WALLS, TYP.
3. SEE INTERIOR ELEVATIONS AND FINISH FLOOR PLAN FOR EXTENT OF PAINT AND WALL COVERING FINISHES DESIGNATED ON FINISH SCHEDULE.
4. NOT USED
5. SEE REFLECTED CEILING PLAN.
ROOM FINISH GENERAL NOTES
001A
4" OR 6" AS SHOWN
EPX FLOORING
SELF COVE, HEIGHT 4"
ALUM. EDGE TRIM
4" - 6" VARIES
4" OR 6" AS SHOWN
EPX FLOORING
SELF COVE, HEIGHT 4"
ZINC EDGE TRIM
1" RADIUS COVE
FIBERGLASS REINFORCED WALL COATING
TAPER WITH BODIED EPOXY
PROVIDE SEAMLESS TRANSITION
LVT
EPOXY TO RFT/RFMANUFACTURER:SCHLUTER STYSTEMS PRODUCT: SCHIENE-EMATERIAL/FINISH: STAINLESS STEEL, 304VERIFY HEIGHT REQUIRED
EPOXY
SEE FINISH SCHEDULE
SEE SPECIFICATION
SEE PARTITION TYPE
SEE FINISH SCHEDULE
CG-1 AS SPECIFIED
SEE PARTITION TYPE
2"
2"
Kansas City, Missouri
2020 Baltimore Avenue, Suite 300
Kansas City, MO 64108-1949
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plot Time Stamp:
File Location/N
ame:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
AC
B
Key Plan
11/21/2018 3:20:20 PM
C:\(1) Revit Projects\2018\624151- A-18_dwatkins.rvt
Room Finishes Schedule
& Details
F1.30
TCEP No.: 624-151-18
University of Missouri
Medical Science
Building - Research
Vivarium Upgrade &
Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTS
ROOM FINISH SCHEDULE FINISH LEGEND
ROOM FINISH SCHEDULE REMARKSNO. REMARK
1 SEE ALTERNATE #1
2 SEE ALTERNATE #2
3 SEE ALTERNATE #3
ROOM NO. ROOM NAME
FLOOR
BASE
NORTH
WALL
EAST
WALL
SOUTH
WALL
WEST
WALL CEILING
REMARK NO.FIN. FIN. FIN. FIN. FIN. FIN.
. PIPE SPACE
A101 CORRIDOR EPX-1 EPX-1 PTE-1,PTE-3
PTE-1 PTE-1 PTE-1 APC-2
A102 ANTE / GOWNING EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A103 OFFICE LVT-1 RB-1 PTE-1 PTE-1 PTE-2 PTE-1 APC-2
A104 FRAGMENTORS EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A105 BEHAVIORAL EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PT-1 PT-2
A106 ENVIRONMENTAL EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A107 STORAGE EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A108 VHP EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A109 CORRIDOR EPX-1 EPX-1 PTE-1,PTE-2
PTE-1 PTE-1 PTE-1 PT-2,APC-1
A112 ANTE / GOWNING EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A113 CORRIDOR EPX-1 EPX-1 PTE-1,PTE-2
PTE-1 PTE-1 PTE-1 PT-2
A114 AIRLOCK EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A116 BSL II EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A116A PROCEDURE EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A116B DIRTY EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A116C CLEAN EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A120 HUMANIZED BSL II EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A120A SURGERY EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A120B PROCEDURE EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A120C CLEAN EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A122 AIRLOCK / GOWNING EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A123 AIRLOCK EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A124 LOCKER / SHOWER EPX-1 EPX-1 CT-1,PTE-1
CT-1,PTE-1
CT-1,PTE-1
CT-1,PTE-1
PT-2
A124A MEN EPX-1 EPX-1 CT-1,PTE-1
CT-1,PTE-1
CT-1,PTE-1
CT-1,PTE-1
APC-2
A125 LOCKER / SHOWER EPX-1 EPX-1 CT-1,PTE-1
CT-1,PTE-1
CT-1,PTE-1
CT-1,PTE-1
PT-2
A125A WOMEN EPX-1 EPX-1 CT-1,PTE-1
CT-1,PTE-1
CT-1,PTE-1
CT-1,PTE-1
APC-2
A126 AIRLOCK EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A126A STEP DOWN EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A130 CORRIDOR EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A131 CLEAN CAGEWASH EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A131A FEED & BEDDING EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A132 CORR. EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A134 CLEAN CAGE STORAGE EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A136 PROCEDURE EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A137 ANIMAL HOLDING (BREEDING) EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A138 ANIMAL HOLDING(EXPERIMENTAL)
EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A138A PROCEDURE EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A139 ANIMAL HOLDING (BREEDING) EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A140 ANIMAL HOLDING (BREEDING) EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A140A PROCEDURE EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A141 ANIMAL HOLDING (BREEDING) EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A142 CORRIDOR EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A143 ANIMAL HOLDING (BREEDING) EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A143A PROCEDURE EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A143B PROCEDURE EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A144 ANIMAL HOLDING (BREEDING) EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A145 ANIMAL HOLDING(EXPERIMENTAL)
EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A145A PROCEDURE EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A146 ANTE RM EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A146A GNOTOBIOTIC / GERM FREE EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A147 CORRIDOR EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A148 PROCEDURE (EUTHENASIA) EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A149 RESTROOM EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A150 CUST. EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A151 AIRLOCK EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A152 CYLINDER EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A153 DIRTY CAGEWASH EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A153A STORAGE EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
A154 PI SUPPORT EPX-1 EPX-1 -- PTE-1 PTE-1 PTE-1 PT-2
A201 MECHANICAL ROOM MRF-1 MRF-1 PT-1 PT-1 PT-1 PT-1 --
A202 ELECTRICAL MRF-1 MRF-1 PT-1 PT-1 PT-1 PT-1 PT-2
M124 CORRIDOR RFT-1,2,3 RB-1 PT-1 PT-1 PT-1 PT-1 APC-2 3
M149 IRRADIATION EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 PT-2
M155 MECHANICAL CONC-1 RB-1 PT-1 PT-1 PT-1 PT-1 PT-2
M157 OPEN OFFICE LVT-1 RB-1 PT-1 PT-2 PT-1 PT-1 APC-2 1
M158 CORRIRDOR RFT-1,2,3 RB-1 PT-1 PT-1 PT-1 PT-1 APC-2 3
M168 JANITOR EPX-1 EPX-1 PTE-1 PTE-1 PTE-1 PTE-1 APC-1
SCALE: 12" = 1'-0"
EPOXY COVE BASE1 SCALE: 12" = 1'-0"
EPOXY COVE BASE - TYP2
SCALE: 12" = 1'-0"
EPOXY TO LVT3SCALE: 12" = 1'-0"
TILE TRANSITION4
SCALE: 12" = 1'-0"
CORNER GUARD TRIM DETAIL - CG-15
A - 001 11/21/2018 ADDENDUM 001
001A
001A
T
T
S
SS
S
S
S
S
M
M
PROCEDURE(EUTHENASIA)
A148
PROCEDURE
A143B
AIRLOCK
A151
RESTROOM
A149
DIRTY CAGEWASH
A153
VHP
A108
STORAGE
A107
2
2
3
3
4
4
5
5
A A
C C
B B
3.1
CORRIDOR
A109
PROCEDURE
A116A
ANTE / GOWNING
A112
BSL II
A116
DIRTY
A116B
PROCEDURE
A145A
16/1
2 S
A
12/8
SA
8Ø SA
12/8
SA
12/8
SA
12/1
0 S
A
12/8 SA
12/12 SA
CUST.
A150
12/8
EA
12/1
0 E
A
12/10 SA UP
VBR-88-107300 CFM
VB-88-108150 CFM
VBR-88-108150 CFM
VB-88-109600 CFM
12/10 SA
12/8 EA
12/12 EA
16/12 SA
20/12 EA
12/10 EA
24/1
4 E
A
PROCEDURE
A143A
CYLINDER
A152
8/12 EA UP TO VB-138
CLEAN CAGESTORAGE
A134
AIRLOCK
A114
16/12 EA DN
12ØG-3
435
(2) G-114/14395
D-1
19510Ø
D-1
19510Ø
12/8
SA
D-1
24010Ø
D-1
19510Ø D-1
19510Ø
D-1
19510Ø
D-1
19510Ø
12/10 SA
12/8
SA
D-1
39512Ø
D-1
39512Ø
D-1
21010Ø
D-1
21010Ø
D-1
50012Ø
D-1
50012Ø
D-1
50012Ø
D-1
1008Ø
12/8
EA
14/1
2 E
A
D-1
1008Ø
8ØG-2
150
D-3
1508Ø
12/8 SA
D-1
1508Ø
D-1
1508Ø
12/8 SA
8Ø E
A
D-1
1508Ø
D-1
29010Ø
(2) G-112/8170
12/8 EA DN
(2) G-112/8195
12/8 EA DN
(2) G-112/10195
(2) G-112/8210
12/10 EA DN
8ØG-2
1008ØG-2
100
6ØG-2
100
8ØG-2
150
D-1
1258Ø
G-1 (E)12/10195
12/8 EA DN
D-1
1258Ø
CORRIDOR
A113
D-1
508Ø
D-1
1008Ø
D-1
32510Ø
6ØG-3
120
6ØG-3
120
6ØG-3
120
6ØG-3
120
6ØG-3
1106ØG-3
110 6ØG-3
120
6ØG-3
120
14/1
2 E
A
12ØG-3
440
CLEAN
A120C
CLEAN
A116C
12/8 EA DN
ENVIRONMENTAL
A106
D-1
20010Ø
D-1
20010Ø
(2) G-112/8150
VB-88-106300 CFM
24/72 CANOPY HOOD, BOTTOM AT 8'-0" AFF
36/72 CANOPY HOOD, BOTTOM AT 8'-0" AFF
MD-1
MD-1 MD-1
MD-1 MD-1
MD-1MD-1
MD-1 MD-1
MD-1
MD-1
MD-1
MD-1
MD-1 MD-1
MD-1 MD-1
MD-1
MD-1
MD-1
MD-1 MD-1
MD-1
MD-1MD-1
MD-1 MD-1
MD-1
MD-1
MD-1
MD-1 MD-1 MD-1
MD-1 MD-1
MD-1
MD-1
MD-1
DCP-1
DCP-1
DCP-1
DCP-1DCP-1
DCP-1
DCP-1
MD-1
MD-1
18/36 CANOPY HOOD, BOTTOM AT 7'-0", BALANCE TO 450 CFM
MD-1
8ØG-2
150
MD-1
14/1
2 E
A
12/10 EA
14/12 SA
10/10 FEA DN, BALANCE HOOD TO 400 CFM
15/5 DN TO EQMT BREATHER VENT
10/10 FEA DNTAP INTO SIDE OF CANOPY HOOD
SS DAMPER TIED TO EQMT, SHALL CLOSE WHEN EQMT EXHAUST DAMPER OPENS
16/1
0 F
EA
15/5 FEA DN TO EQMT EXHAUST
18/12 FEA DN
13/8 FEA (BELOW), ROUTE FROM EQMT BREATHER VENT TO SIDE OF CANOPY HOOD
13/8 FEA DN TO EQMT EXHAUST VENT
18/12 FEA DN, BALANCE HOOD TO 1200 CFM
12/14 SA UP TO VBR-141
8/12 SA UP TO VBR-146
12/8 EA UP TO VB-146
12/10 EA UP TO VB-142 8/12 SA UP
TO VBR-14212/8 EA UP TO VB-147
24/14 EA UP TO VB-149
12/8 EA UP TO VB-148
8/12 SA UP TO VBR-111
24/16 SA UP TO VBR-149
12/8 SA UP TO VBR-110
10/12 EA UP TO VB-114
8/12 SA UP TO VBR-114
14/12 SA UP TO VBR-113
2
2
8/12 EA UP TO VB-113
8/12 EA UP TO VB-115
12/12 SA UP TO VBR-115
8/12 SA UP TO VBR-116
16/12 SA UP TO VBR-117
20/12 EA UP TO VB-117
12/8 SA UP TO VBR-139
12/12 EA UP TO VB-139
12/8 SA UP TO VBR-138
MD-1, STAINLESS STEEL
MD-1, STAINLESS STEEL
24/16 FEA
15/5 FEA BELOW
36/1
6 F
EA
36/16 FEA UP
30/16 FEA
MD-1MD-1
D-1
47012Ø
D-1
47512Ø
18/1
6 S
A
MD-1
MD-1MD-1
MD-1
MD-1MD-1
D-1
50012Ø
D-1
50012Ø
D-1
50012Ø
D-1
50012Ø
1
1
1
1
1
1
1
24/1
6 S
A14ØG-2
525
14ØG-2
525
14ØG-2
525
14ØG-2
525
MD-1 MD-1
MD-1 MD-1
D-1
506Ø
MD-1
3
3
S V
4 5
14/12 EA
14/1
2 E
A
MD-1 MD-1
6
7
MD-1, STAINLESS STEEL
001A
Kansas City, Missouri
2020 Baltimore, Suite 300
Kansas City, MO 64108-1914
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plo
t Ti
me
Sta
mp
:
File
Lo
ca
tio
n/N
am
e:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
B
Key Plan
11
/21
/20
18
10
:16
:30
AM
C:\
(1)
Re
vit
Pro
jec
ts\
20
18
\6
24
15
1-
M-1
8_ja
me
s.m
ah
on
ey
@c
lark
en
ers
en
.co
m.r
vt
HVAC Plan - Area B
M1.02
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTS
SCALE: 1/4" = 1'-0"
HVAC PLAN - AREA B
0 2' 4' 8'
GENERAL NOTES:
1. ALL NEW WORK IS SHOWN IN HEAVY LINEWEIGHT. ALL WORK TO REMAIN AS EXISTING IS SHOWN IN LIGHT LINEWEIGHT.
2. ALL STAINLESS STEEL DUCTWORK IS SHOWN AS SHADED IN PLAN.
3. VBR AND VB TAGS ON THIS PLAN ARE CONDENSED TO INCREASE VISUAL CLARITY.
PLAN NOTES:
INSTALL EXHAUST GRILLES AT HEIGHTS OF 1' 6" AND 7'.
BALANCER TO MEASURE STATIC PRESSURE THROUGH EXHAUST VENT OF MACHINE AND THEN CLEAN SIDE CANOPY HOOD. USE THIS BALANCE DAMPER TO CREATE AN EQUIVALENT AIRFLOW AND PRESSURE LOSS THROUGH EACH. THE INTENT IS TO ENSURE EF-5 CAN OPERATE AS CONSTANT VOLUME AND WILL FUNCTION WITH THE OTHER EQUIPMENT.
PROVIDE BUBBLE-TIGHT CONTROL DAMPER, GREENHECK HBTR-151 OR EQUIVALENT.
PROVIDE WALL TOGGLE SWITCH LABELED "HVAC OPERATION" AND TIED INTO THE BMS. INTERLOCK OPERATION OF BUBBLE-TIGHT DAMPER AND VAV BOXES IN SPACE TO COMPLETELY SHUT-OFF AIRFLOW AS SWITCH IS FLIPPED. IF SWITCH IS TURNED OFF AND HVAC IS OFF TO THE SPACE FOR LONGER FOR 2 HOURS (ADJ) THE BMS SHALL ALARM.
PROVIDE VHP SENSOR IN ROOM, STERIS MODEL VHP-TS1000, MOUNTED AT 4'-0" AFF. SENSOR SHALL BE TIED INTO BOTH THE BMS AND VMS. IF HVAC CONTROL DAMPER IS TURNED "ON" AND VHP LEVELS EXCEED SAFE LEVELS OF 1 PPM (ADJ.), THE DAMPERS SHALL SHUT AND THE BMS SHALL ALARM.
INSTALL ALL CANOPY EXHAUST AT SAME LEVEL OR SLOPED BACK TO HOOD.
INSTALL OXYGEN DEFICIENCY MONITOR, PURE-AIRE MODEL TX-1100DRA OR EQUIVALENT, AT 48" AFF ON WALL. PROVIDE REQUIRED 24V TRANSFORMER AND PLUG INTO NEARBY WALL OUTLET.
1
2
3
4
5
6
7
A - 001 11/21/18 ADDENDUM #001
T
T
T
TT
T
S
SS
S
S
SS
S
M
TT
T
T
PROCEDURE
A143B
PROCEDURE
A140A
PROCEDURE
A138A
PROCEDURE
A136
FEED & BEDDING
A131A
STEP DOWN
A126A AIRLOCK
A126
LOCKER / SHOWER
A125
WOMEN
A125A
MEN
A124A
LOCKER / SHOWER
A124
AIRLOCK /GOWNING
A122
HUMANIZED BSL II
A120
OFFICE
A103
IRRADIATION
M149
2
2
3
3
4
4
5
5
E E
C C
D D
3.6 4.6
3.1
PROCEDURE
A120B
SURGERY
A120A
ANTE / GOWNING
A102
12/1
0 S
A
12/8 SA
12/12 SA
24/12 SA UP
16/1
4 S
A
12/8
SA
12/1
2 E
A
12/1
2 S
A
16/1
2 S
A
20/1
2 E
A
12/1
0 E
A
8/8
EA
8/8
EA
12/8 SA
8Ø S
A
8Ø SA
12/8 SA
12/8 EA
12/8 EA
12/8 SA
24/12 SA
24/12 EA
18/1
2 S
A
20/1
2 E
A
12/8 EA
12/8 SA
VBR-88-103125 CFM
VB-88-105550 CFM
VB-88-101375 CFM
VB-88-120550 CFM
VBR-88-120350 CFM
VB-88-121600 CFM
VBR-88-121400 CFM
VB-88-154225 CFM
VBR-88-154125 CFM
VB-88-109600 CFM
16/12 SA
20/12 EA
8/12 EA UP TO VB-138
EXIST.
MY100
VBR-88-155500 CFM
VB-88-155500 CFM
CLEAN CAGESTORAGE
A134
AIRLOCK
A123
(2) G-112/10360
22/8 EA DN
(2) G-118/12400
14/12 EA DN
D-1
19510Ø
D-1
19510Ø
12/10 SA
12/8
SA
D-1
36012Ø
D-1
36012Ø
D-1
35012Ø
D-1
1958Ø
D-1
1958Ø
D-1
55012Ø
D-1
19510Ø
D-1
19510Ø
D-1
21510Ø
D-1
21510Ø
D-1
26510Ø
D-1
27010Ø
D-1
27010Ø
D-1
26510Ø
D-2
2008Ø
D-2
2008Ø
D-2
1758Ø
D-2
1758Ø
D-2
1258Ø
D-2
27010Ø
14/1
2 E
A
D-1
1008Ø
D-1
29010Ø
12/10 SA
8ØG-2
225
12/8 EA
12/8R-1
250
12/8R-1
250
12/10 SA
D-2
30010Ø
14/1
2 S
A
12ØG-2
445
12/8 EA DN
(2) G-112/10195
8ØG-2
250
8ØG-2
50
8ØG-2
3008ØG-2
300
8ØG-2
300(2) G-114/14610
20/12 EA DN
(2) G-112/8110
12/8 EA DN 12/8 EA DN
(2) G-112/855
8ØG-2
190
D-2
1008Ø
D-2
506Ø
D-2
506Ø
D-2
32010Ø
12/8 EA DN
(2) G-112/10195
G-1 (E)12/10195
12/8 EA DN
8ØG-2
185
10ØG-2
270
CORR.
A132
D-2
506Ø
D-1
32510Ø
12/10 SA
12/8
EA
(2) G-118/12385
20/12 EA DN
6ØG-3
110
6ØG-3
110
6ØG-3
110
6ØG-3
110
6ØG-3
110
14/1
2 E
A
CLEAN
A120C
12/8 EA DN
D-2
1258Ø
OPEN OFFICE
M157
FRAGMENTORS
A104
BEHAVIORAL
A105
ENVIRONMENTAL
A106
VBR-88-104450 CFM
VBR-88-105450 CFM
VBR-88-106400 CFM
D-1
20010Ø
D-1
20010Ø
D-1
22510Ø
D-1
22510Ø
D-1
22510Ø
D-1
22510Ø
D-2
2008Ø
D-2
2008Ø
VBR-88-150500 CFM
R-1
50018/8
VBR-88-112500 CFM
D-2
1708Ø
D-2
1658Ø
12/10 SA
12/1
2 S
A
VB-88-150500 CFM
TRANSFER400 CFM
(2) G-112/10275(2) G-112/8175
(2) G-112/8150
36/72 CANOPY HOOD, BOTTOM AT 8'-0" AFF
18/60 CANOPY HOOD, BOTTOM AT 8'-0", TYP 4 FOR AUTOCLAVES, BALANCE TO 600 CFM
MD-1MD-1
MD-1 MD-1
MD-1 MD-1
MD-1
MD-1
MD-1
MD-1
MD-1 MD-1
MD-1MD-1
MD-1
MD-1 MD-1
MD-1
MD-1
MD-1
MD-1
MD-1
MD-1
MD-1
MD-1 MD-1
MD-1
MD-1
MD-1 MD-1
MD-1 MD-1
MD-1MD-1
MD-1
MD-1
MD-1
MD-1
MD-1
MD-1
MD-1MD-1
DCP-1
DCP-1 DCP-1
MD-1
DCP-1
DCP-1
MD-1
MD-1
MD-1
DCP-1
DCP-1
DCP-1
18/36 CANOPY HOOD, BOTTOM AT 7'-0", BALANCE TO 450 CFM
12/10 EA
12/10 SA
12/8 SA
12/10 SA
12/10 SA
12" PVC DUCT DN TO CLASS II B2 CABINET
MD-1D-1
55012Ø
10/10 FEA DNTAP INTO SIDE OF CANOPY HOOD
18/12 FEA DN
13/8 FEA (BELOW), ROUTE FROM EQMT BREATHER VENT TO SIDE OF CANOPY HOOD
12/14 SA UP TO VBR-131
2
12/12 FEA DN
CLEAN CAGEWASH
A131
8/12 SA UP TO VBR-116
16/12 SA UP TO VBR-117
20/12 EA UP TO VB-117
20/12 EA UP
12/8 EA UP TO VB-118
8/12 EA UP TO VB-119
8/8 EA UP TO VB-122 12/8 SA UP TO
VBR-118
20/12 EA UP TO VB-123
10/10 SA UP TO VBR-125
12/10 EA UP TO VB-125
16/12 SA UP TO VBR-123
18/38 SA UP TO VBR-124
14/12 SA UP TO VBR-153
12/12 SA UP TO VBR-128
12/12 EA UP TO VB-128
8/12 SA UP TO VBR-132
12/8 EA UP TO VB-132
14/16 SA UP TO VBR-129
12/8 SA UP TO VBR-135
12/8 SA UP TO VBR-139
12/8 EA UP TO VB-135
12/12 EA UP TO VB-139
12/8 SA UP TO VBR-138
12/12 FEA DN
MD-1, STAINLESS STEEL
12/12 FEA DN
12/12 FEA DN
MD-1
MD-1MD-1
MD-1
20/12 FEA
20/1
2 F
EA20
/12
FE
A
15/5 FEA BELOW
14/12 SA UP TO VBR-126
T
TEMP SENSOR FOR VBR-88-126
G-4
50018/8
12/10 SA
G-4
50018/8
12/10 EA
28/1
6 SA
16/1
6 S
A
MD-1
MD-1MD-1
MD-1MD-1
MD-1MD-1
D-1
47012Ø
D-1
47512Ø
D-1
47512Ø
D-1
47012Ø
D-1
47012Ø
D-1
47012Ø
D-1
47012Ø
12/1
2 S
AMD-1
MD-1
MD-1
10/1
0 E
A
12/10 SA UP TO VBR-153
12/8 EA
12/1
0 S
A12
/10
SA
12ØG-2
12ØG-2 3
2
2
4
12/8 SA
12/8 EA
24/12 EA
12/1
2 E
A
VB-88-104350 CFM
12/10 EA
1
1
1
1
1
1
1
11
1
1
12/8 SA UP TO VBR-119
12/8 SA UP TO VBR-102
12/8 EA
14/14R-1
30014/12 SA
MD-1
12" PVC DUCT UP
PVC DRAIN FROM BSC FAN, SEE DETAIL 15 SHEET M6.04
D-2
1658Ø
12/14 EA24/14 EA
5
10/10 SA
6
7
7
FCU-2
FCU-1
D-2
30010ØMD-1
G-4
30012/8
12/1
2 F
EA
12/1
2 F
EA
G-4
30012/8
MD-1PROVIDE SS MD-1IN FEA, TYP ALL
001A
001A
001A
8
Kansas City, Missouri
2020 Baltimore, Suite 300
Kansas City, MO 64108-1914
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plo
t Ti
me
Sta
mp
:
File
Lo
ca
tio
n/N
am
e:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
C
Key Plan
11
/21
/20
18
10
:16
:41
AM
C:\
(1)
Re
vit
Pro
jec
ts\
20
18
\6
24
15
1-
M-1
8_ja
me
s.m
ah
on
ey
@c
lark
en
ers
en
.co
m.r
vt
HVAC Plan - Area C
M1.03
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTS
SCALE: 1/4" = 1'-0"
HVAC PLAN - AREA C
0 2' 4' 8'
GENERAL NOTES:
1. ALL NEW WORK IS SHOWN IN HEAVY LINEWEIGHT. ALL WORK TO REMAIN AS EXISTING IS SHOWN IN LIGHT LINEWEIGHT.
2. ALL STAINLESS STEEL DUCTWORK IS SHOWN AS SHADED IN PLAN.
3. VBR AND VB TAGS ON THIS PLAN ARE CONDENSED TO INCREASE VISUAL CLARITY.
PLAN NOTES:
INSTALL EXHAUST GRILLES AT HEIGHTS OF 1' 6" AND 7'.
SUPPLY DUCT, AIR TERMINALS, AND ALL ASSOCIATED COMPONENTS FOR THIS ROOM SHALL BE PROVIDED UNDER ALTERNATE #1 ONLY. UNDER BASE BID, PROVIDE VAV BOX AND BACKFEED EXISTING LOCKER ROOMS WITH 12/10 SUPPLY DUCT. REBALANCE EACH LOCKER ROOM TO 200 CFM EACH. REUSE EXISTING THERMOSTAT IN SPACE AND TIE INTO NEW VAV BOX CONTROLS.
SUPPLY DUCT, AIR TERMINALS, AND ALL ASSOCIATED COMPONENTS FOR THE MAIN CORRIDOR SHALL BE PROVIDED UNDER BASE BID AND ALTERNATE #3. UNDER ALTERNATE #3, THE DIFFUSERS SHALL BE SHIFTED TO FIT WITH NEW CEILING. UNDER BASE BID, PLACE AIR TERMINALS IN EXISTING LAY-IN CEILING.
12" FLUE DUCT OFF OF GENERATOR EXHAUST PORT. ROUTE DUCTWORK UP THE SIDE OF THE 7 STORY ADJACENT BUILDING AND TERMINATE ABOVE PARAPET AT EQUAL HEIGHT OF EXISTING FLUE DUCT TO THE EAST. PROVIDE DRAIN AT BOTTOM OF 7-STORY DUCT RISER AND SLOPE DUCT FROM GENERATOR TOWARDS DRAIN. INSULATE HORIZONTAL DUCT AND FIRST 5' OF VERTICAL RISER FOR SOUND ABSORPTION. INSULATION SHOULD BE EXTERIOR TYPE WITH ALUMINUM JACKET TO MATCH EXISTING FLUE TO THE EAST. REFER TO SPECIFICATION SECTION 23 51 00 FOR REQUIREMENT OF A PRE-ENGINEERED FLUE SYSTEM FOR THIS DUCT. CONTRACTOR TO COORDINATE FINAL SIZE AND ROUTING WITH FLUE MANUFACTURER SHOP DRAWINGS. COORDINATE FLUE WITH FINAL GENERATOR DESIGN. VERTICAL RISER SHALL BE SUPPORTED BY STRUCTURAL POST WITH FOOTING, SEE GENERATOR FLUE SUPPORT DETAIL ON SHEET S3.01. VERTICAL RISER SHALL BE BRACED TO EXISTING BUILDING AS NECESSARY, CONNECTION BY FLUE MANUFACTURER.
UNDER BASE BID, RELOCATE EXISTING EXHAUST DUCTWORK AS SHOWN TO KEEP LOCKER ROOMS OPERATIONAL. REBALANCE EXHAUST GRILLES IN EACH LOCKER ROOM TO 300 CFM EACH. UNDER ALTERNATE #1, DEMOLISH EXHAUST DUCTWORK BACK TO PROJECT BOUNDARY.
BRANCH TO SERVE EXISTING WOMEN'S LOCKER ROOM UNDER BASE BID. DO NOT PROVIDE IF ALTERNATE #1 IS ACCEPTED. REBALANCE TO 200 CFM.
ROUTING SHOWN IS FOR ALTERNATE #1. UNDER BASEBID, CONNECT 12/10 SA TO MEN'S LOCKER ROOM SUPPLY DUCTWORK. REBALANCE TO 200 CFM.
INSTALL 12/8 G-4 GRILLE AT 18" AFF TO TRANSFER AIR INTO AUTOCLAVE CONTROL ROOM. INSTALL 12/8 TRANSFER DUCT WITH ELBOW UP AT SAME HEIGHT.
1
2
3
4
5
6
7
A - 001 11/21/18 ADDENDUM #001
8001A
2
2
3
3
4
4
5
5
E E
C C
D D
3.6 4.6
3.1
12" CWS (E)12" CWR (E)
6" H
WR
(E
)6"
HW
S (
E)
6" H
WS
(E
)
6" H
WR
(E
)
6" H
WS
(E
)
6" H
WR
(E
)
6" HWR (E)6" HWS (E)
8" HPS (E)
8" H
PS
(E
)3"
PD
(E
)
3" PD (E)4" HPS (E)
2" L
PS
(2)
(E
)
4" P
D (
E)
12"
CW
R (
E)
12"
CW
S (
E)
12"
CW
R (
E)
12"
CW
S (
E)
12" CWS (E)12" CWR (E)
4" LPS (2) (E)
4" LPS (2) (E)
3" L
PS
(2)
(E
)
4" HPS (E)
LPS/R UP TO RADIATOR (E)
LPS/R UP TO RADIATOR (E)
2 1/
2" H
PS
(E
)2
1/2"
HP
R (
E)
2 1/2" HPR (E)3" HPS (E)
8" HPS (E)8" HPS (E)
1-1/4" HPS/R (E) UP TO STERILIZERS (E)
1 1/
2" H
PS
(E
)1
1/2"
HP
R (
E)
3/4" HPS (E)3/4" HPR (E)
3/4" HPS/R (E) UP TO GLASS WASHER (E)
1 1/
2" H
PS
(E
)
1/2" HPS (E) UP
HPR (E) UP
1 1/
2" L
PR
(E
)
1 1/2" LPR (E)
LPS/R UP TO RADIATOR (E)
1-1/4" LPS (E) DN
1-1/4" LPR (E) DN
LPS/R UP TO RADIATOR (E)
1-1/4" LPS (E) DN
1-1/4" LPR (E) DN
LPS/R UP TO RADIATOR (E)
3" L
PS
(2)
(E
)2"
LP
R (
E)
2" LPR (E)
2" L
PR
(E
)
2" LPR (E)
1-1/4" LPR (E) UP
LPS/R (E) UP TO RADIATOR
1 1/
4" L
PR
(E
)
1-1/4" LPR (E) UP
3" L
PS
(2)
(E
)
3" LPS (E) UP
LPS/R (E) UP TO RADIATOR
8" LPS (7) (E)
3" L
PS
(2)
(E
)2"
LP
R (
E)
LPS/R (E) UP TO RADIATOR
3" LPS (E) UP
2" LPR (E) UP
2" LPR (E)
1 1/4" LPS (2) (E)
1 1/
4" L
PS
(2)
(E
)
1-1/4" LPS (E) DN
1-1/4" LPS (E) DN
4" PD (E)
6" LPS (2) (E)
3" PD (E)3" PD (E)
3" P
D (
E)
2" S
V (
E)
2" SV UP THRU ROOF (E)
2" SV (E) DN
3" PD (E)
3" PD (E)
2" L
PR
(E
)
2" LPR (E) UP
1 1/
4" L
PS
(2)
(E
)
1-1/4" LPS (E) UP
2 1/2" LPS (2) (E)2 1/2" LPR (E)
LPS/R (E) UP TO RADIATORLPS/R (E) UP TO RADIATOR
4" L
PS
(2)
(E
)2"
LP
R (
E)
3" L
PS
(2)
(E
)
LPS/R (E) UP TO RADIATOR
12" CWS/R (E) TO REMAIN
HWS (E)HWR (E)
12" CWS (E)12" CWR (E)
VBR-88-103
0.3 GPM
VBR-88-154
0.3 GPM
VBR-88-120
1.0 GPM
VBR-88-121
1.0 GPM
2 1/2" HPS (E)2" HPR (E)
1 1/
2" H
WS
1 1/
2" H
WR
1" H
WR
1" H
WS
3/4"
HW
R3/
4" H
WS
6" C
WS
6" C
WR
1 1/2" LPR
6" LPS (7) (E)
4" LPS (7)
4" L
PS
(7)
4" HWS/R, 6" CWS/R, 4" LPS, 1-1/2" LPR UP TO PENTHOUSE
3/4"
HP
S
PROCEDURE
A136
PROCEDURE
A138A
PROCEDURE
A140A
PROCEDURE
A143B
CLEAN CAGEWASH
A131
FEED & BEDDING
A131A
STEP DOWN
A126A
MECHANICAL
M155
AIRLOCK
A126LOCKER / SHOWER
A125
WOMEN
A125A
MEN
A124ALOCKER / SHOWER
A124
AIRLOCK /GOWNING
A122
PROCEDURE
A120B SURGERY
A120A
ANTE / GOWNING
A102
HUMANIZED BSL II
A120
OFFICE
A103
IRRADIATION
M149
3/4" HPS/R (E) UP
4" L
PS
(7)
CLEAN CAGESTORAGE
A134
PI SUPPORT
A154
1
1
6" CWS
6" CWR
1 1/
4" L
PR
2" H
PS
1" H
PS
2" HPS
1 1/4" LPR
ROUTE LPR PIPING BELOW GRADE TO EXISTING BASEMENT MECHANICAL ROOM
VBR-88-104
0.5 GPM
VBR-88-106
0.8 GPM
VBR-88-105
0.5 GPM
BEHAVIORAL
A105
ENVIRONMENTAL
A106
FRAGMENTORS
A104
OPEN OFFICE
M157
3/4" HPS
3/4" HPS
3/4" HPS DN TO AUTOCLAVE
3/4" HPS DN TO AUTOCLAVE
2" L
PR
2" L
PR
CRP-1
1" P
D
2" SV UP
2" S
V
2" SV
2" SV, 2" LPR, 1" PD DN TO CRP-1
2" LPR (E)
VBR-88-155
1.3 GPM
VBR-88-112
0.4 GPM
MANUAL BALANCE VALVE, SET TO 0.5 GPM
FCU-1
1" C
WR
1" C
WS
5.8 GPM (C)
3/4" HWS3/4" HWR
FCU-2
4.5 GPM (C)1.7 GPM (H)
1" C
WS
1" C
WR
3/4" CD 3/4" CD
3/4" CD FROM FCU'S, ROUTE TO FLOOR SINK, TERMINATE WITH AIR GAP
001A
Kansas City, Missouri
2020 Baltimore, Suite 300
Kansas City, MO 64108-1914
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plo
t Ti
me
Sta
mp
:
File
Lo
ca
tio
n/N
am
e:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
C
Key Plan
11
/21
/20
18
10
:16
:47
AM
C:\
(1)
Re
vit
Pro
jec
ts\
20
18
\6
24
15
1-
M-1
8_ja
me
s.m
ah
on
ey
@c
lark
en
ers
en
.co
m.r
vt
HVAC Piping Plan - Area
C
M1.06
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTS
GENERAL NOTES:
1. ALL NEW WORK IS SHOWN IN HEAVY LINEWEIGHT. ALL WORK TO REMAIN AS EXISTING IS SHOWN IN LIGHT LINEWEIGHT.
PLAN NOTES:
RAISE EXISTING HIGH PRESSURE STEAM LINE TO ABOVE NEW CEILING GRID. STEAM ONLY SERVES ABSORPTION CHILLER IN BASEMENT, SO LINE MAY BE TAKEN OFF-LINE DURING HEATING MONTHS FOR RELOCATION.
1
SCALE: 1/4" = 1'-0"
HVAC PIPING PLAN - AREA C
0 2' 4' 8'
A - 001 11/21/18 ADDENDUM #001
VHP
A108
STORAGE
A107
2
2
3
3
4
4
5
5
A A
C C
B B
3.1
PROCEDURE
A143B
DIRTY CAGEWASH
A153
PROCEDURE(EUTHENASIA)
A148
RESTROOM
A149
CUST.
A150
AIRLOCK
A151CORRIDOR
A109
PROCEDURE
A116A
ANTE / GOWNING
A112
BSL II
A116
DIRTY
A116B
PROCEDURE
A145A
PROCEDURE
A143A
CYLINDER
A152
TD-1 CB-1
S-1
S-1
S-1
SS-1
S-1
S-1
S-1
HL-2
HWC-1
MSB-1
3" C
W2"
HW
1" H
WC
CLEAN
A116C
CLEAN
A120C
SI-1
4" W
4" W
1" H
WC
2" H
W2"
CW
1" LSCW
1 1/2" N1" CO2
1 1/2" O21" HWC2" HW3" CW
1/2" CA (70 PSIG)
1" CO2
1 1/
2" C
A (
70 P
SIG
)
1" O
21"
CO
21"
N
FD-1
S-1
4" W DN
2" LHW2" LCW
3/4" LHW3/4" LCW
3/4"
LH
W
2" L
SC
W
4" W UP4" W UP
2" C
W2"
HW
1" H
WC
4" W
4" VTR
4" W UP
1 1/
2" N
1" C
O2
1 1/
2" O
2
1 1/
2" N
1" C
O2
1 1/
2" O
2
1" HWC3/4" HW3/4" CW
2" CW, 2" HW, 1" HWC UP TO BACKFLOW PREVENTERS
2" LCW, 2" LHW FROM BACKFLOW PREVENTERS
ENVIRONMENTAL
A106
1 1/2" VAC
2
M6.04
2" L
CW
4" W
6" DSN-1 18" TO CENTER OF PIPE ABOVE GRADE
6" DSN-1 18" TO CENTER OF PIPE ABOVE GRADE
4" S
4" OS
4" S DN
4" S UP TO RD-14" OS UP TO OD-1
4" S
4" S UP TO RD-1
4" OS UP TO OD-1
1
PIPING ROUTED DOWN TO MISS STRUCTURE
PIPING ROUTED DOWN TO MISS STRUCTURE
2" W UP (E) TO REMAIN
3" V
3" V
3" V
2" V2" CW3/4" HW
4" VTR
VA
C-1
CO
2-1
LN-1
O2-
1
VA
C-1
CO
2-1
LN-1
O2-
1
1 1/
2" V
AC
1 1/
2" V
AC
VA
C-1
CO
2-1
LN-1
O2-
1
VA
C-1
CO
2-1
LN-1
O2-
1
3/4" VAC, 1/2" N, 1/2" CO2, 1/2" O2 DN TO LAB OUTLETS
3/4" VAC, 1/2" N, 1/2" CO2, 1/2" O2 DN TO LAB OUTLETS
3/4" VAC, 1/2" N, 1/2" CO2, 1/2" O2 DN TO LAB OUTLETS
1/2" CW, 1/2" HW, 1 1/2" V DN
EW-1
EW-1
EW-1
EW-1
ESH-1
3/4" LCW, 3/4" LHW DN
1 1/2" V
1 1/2" V DN
1 1/2" CW DN
3/4" CW, 3/4" HW DN
4" S DN
3/4" CW, 3/4" CA, 3/4" VAC, 3/4" HW, 3/4" HWC, 3/4" G UP (E) TO REMAIN
1" CW, 3/4" HW, 3/4" HWC, 3/4" G, 3/4" VAC UP (E) TO REMAIN
2
2
2
2
2
CDM-1
1" CO2 DN TO CDM-1. INSTALL PER MANUFACTURES INSTALLATION INSTRUCTIONS
FS-1
4" VTR
WS-1
FCO (E)1 1/2" CW, 1 1/2" HW DN TO ESH-1
3/4" LCW, 3/4" LHW DN TO HB-2
3" V
1 1/
2" C
W1
1/2"
HW
1" H
WC
2" V DN
3" V
FS-1
FS-1
1/2" CA, 1" LSCW, 1" LHW DN TO BOTTLE WASHER. INSTALL BALL VALVES IN THE VERTICLE SECTION OF PIPING.
1/2" CA, 1" LSCW, 1" LHW DN TO RACK/ CAGE WASHER. INSTALL BALL VALVES IN THE VERTICLE SECTION OF PIPING
FCO (E)
1" LSCW1" LHW
1/2"
CA
(70
PS
IG)
1" CA (70 PSIG)
2" V DN2"
V
2" V DN
3" V
2" V
FCO
FCO (E)
3/4" CW UP TO HB-1
4" S
(E
)
4" S UP (E) TO REMAIN
4" S DN (E)
2 1/2" G (E)1 1/4" CA (E)
3" W UP/DN (E) TO REMAIN. CONTRACTOR TO ADJUST WASTE LINE AS NEEDED TO FIT IN NEW WALL.
FCO (E)
FCO (E)
2 1/2" G, 1 1/4" CA UP (E) TO REMAIN
2" W, 2" V, 3/4" HW UP (E) TO REMAIN
3" VTR (E) TO REMAIN
3/4" G UP (E) TO REMAIN
3/4" CW, 3/4" HW UP (E) TO REMAIN
2" W (E)
3/4" HW (E)3/4" G (E)
3/4" CA, 1" LSCW DN TO AUTOCLAVE
3" C
W2"
HW
1" H
WC
1" O
21"
CO
21"
N1
1/2"
VA
C
1" LSCW 1" LSCW
2" V (E)
VA
C-1
CO
2-1
LN-1
O2-
1
1 1/
2" C
A (
70 P
SIG
)
3/4" VAC, 1/2" N, 1/2" CO2, 1/2" O2 DN TO LAB OUTLETS
1/2" HW, 1/2" CW, 1 1/2" V DN
EW-1
1" CW
1" HW
3/4"
CW
3/4"
HW
1 1/
2" V
2" V
4" VTR
VA
C-1
CO
2-1
LN-1
O2-
1
VA
C-1
CO
2-1
LN-1
O2-
1
1/2" CW1/2" HW
HL-2
4" W
1/2" HW1 1/2" V1/2" CW
BALANCE VALVE SET TO 0.5 GPM
1 1/
2" V
1 1/
2" V
AC
3/4" CA (70 PSIG)
1/2" HW, 1/2" CW, 1 1/2" V DN
FCO (E)
2" SCHEDULE 40 PVC ROUTED FROM STORAGE A153A ABOVE CEILING TO RACK AND CAGE WASHERS. CONTRACTOR TO USE LONG SWEEPING ELBOWS. COORDINATE ROUTING WITH SCIENTEK AND SOAP SUPPLY COMPANY.
STORAGE
A153A
001A
Kansas City, Missouri
2020 Baltimore, Suite 300
Kansas City, MO 64108-1914
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plo
t Ti
me
Sta
mp
:
File
Lo
ca
tio
n/N
am
e:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
B
Key Plan
11
/21
/20
18
10
:16
:55
AM
C:\
(1)
Re
vit
Pro
jec
ts\
20
18
\6
24
15
1-
M-1
8_ja
me
s.m
ah
on
ey
@c
lark
en
ers
en
.co
m.r
vt
First Floor Plumbing Plan -
Area B
M2.05
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTS
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLUMBING PLAN - AREA B
0 2' 4' 8'GENERAL NOTES:
1. ALL NEW WORK IS SHOWN IN HEAVY LINEWEIGHT. ALL WORK TO REMAIN AS EXISTING IS SHOWN IN LIGHT LINEWEIGHT.
2. WASTE AND VENT PIPING THROUGH FIRST FLOOR SLAB MAY NEED TO BE RELOCATED TO KEEP PIPING CONCEALED. RELOCATION OF THIS PIPING MAY INCLUDE MOVING OF THE SLAB PENETRATIONS AND REWORKING PIPING BELOW SLAB. NO ADDITIONAL COMPENSATION WILL BE PROVIDED FOR LACK OF COORDINATION.
PLAN NOTES:
EXISTING PIPING SERVING FLOORS ABOVE TO REMAIN INTACT AND OPPERATIONAL DURING CONSTRUCTION. CONTRACTOR SHALL COORDINATE WITH FACILITIES IF SYSTEMS WILL BE TAKEN OFFLINE.
3/4" CW, 3/4" HW, 1 1/2" V DN TO SINK. ROUTE 1/2" CW, 1/2" HW TO SINK. ROUTE 3/4" CW, 3/4" HW TO EYEWASH. REFER TO DETAIL #1 ON M6.06.
1
2
A - 001 11/21/18 ADDENDUM #001
M
M
M
M
M
T
T
T
T
1
1
2
2
3
3
4
4
5
5
A A
E E
C C
B B
D D
3.6 4.6
3.1
AHU-2
AHU-8884/30 EA, OFFSET AT HRH DISCHARGE AND UP THRU ROOF, TERMINATE WITH CONCENTRIC TRANSITION TO 60/24, SEE DETAILS SHEET, DETAIL 1
HRH-2
VBR-88-111150 CFM0.5 GPM
VBR-88-116200 CFM0.5 GPM
VBR-88-114420 CFM1.0 GPM
VBR-88-113790 CFM2.0 GPM
VBR-88-115440 CFM1.0 GPM
VBR-88-1171070 CFM2.5 GPM
VBR-88-110300 CFM0.5 GPM
VBR-88-102200 CFM0.5 GPM
VBR-88-119215 CFM0.5 GPM
VBR-88-118215 CFM0.8 GPM
VBR-88-125270 CFM0.8 GPM
L-1 (96/78), BOTTOM MIN 36" ABOVE ADJACENT ROOF
VBR-88-1243300 CFM
VBR-88-1493500 CFM5.0 GPM
VBR-88-156650 CFM1.0 GPM
OUTDOOR AIR PLENUM
OUTDOOR AIR PLENUM
VBR-88-128645 CFM1.5 GPM
VBR-88-146240 CFM0.5 GPM
VBR-88-145500 CFM1.3 GPM
VBR-88-127300 CFM1.0 GPM
VBR-88-132390 CFM1.0 GPM
VBR-88-131820 CFM2.0 GPM
VBR-88-130980 CFM2.5 GPM
VBR-88-1331000 CFM2.5 GPM
VBR-88-1291100 CFM3.0 GPM
VBR-88-135390 CFM
VBR-88-139390 CFM
VBR-88-142390 CFM1.0 GPM
VBR-88-138390 CFM
VBR-88-134895 CFM2.0 GPM
VBR-88-137895 CFM2.0 GPM
VBR-88-141895 CFM2.0 GPM
VBR-88-1361000 CFM2.5 GPM
VBR-88-1401000 CFM2.5 GPM
VBR-88-143500 CFM1.3 GPM
VBR-88-144665 CFM1.8 GPM
24/12 EA
24/12 SA
VB-88-118115 CFM
VB-88-119215 CFM
VB-88-12250 CFM
VB-88-1171320 CFM
VB-88-115640 CFM
VB-88-113940 CFM
VB-88-114420 CFM
VB-88-148100 CFM
VB-88-1492100 CFM
VB-88-147200 CFM
VB-88-146340 CFM
VB-88-142390 CFM
VB-88-138390 CFM
VB-88-139390 CFM
VB-88-135390 CFM
VB-88-145875 CFM
VB-88-141795 CFM
VB-88-144565 CFM
VB-88-143450 CFM
VB-88-140900 CFM
VB-88-137795 CFM
VB-88-136900 CFM
VB-88-134795 CFM
VB-88-133900 CFM
VB-88-130880 CFM
VB-88-127675 CFM
VB-88-131720 CFM
VB-88-132390 CFM
VB-88-128445 CFM
VB-88-1231220 CFM
VB-88-125270 CFM
24/12 EA DN
24/12 SA DN
12/8 SA DN
12/8 EA DN
8/12 EA DN
12/8 SA DN
12/8 SA DN
8/8 EA DN10/10 SA DN10/12 EA DN
12/20 EA DN
16/12 SA DN
16/42 SA DN
14/12 SA DN
12/12 SA DN
12/12 EA DN8/12 EA DN
16/14 SA DN
12/14 EA DN 14/12 SA DN
12/14 EA DN12/10 SA DN
12/14 EA DN
14/12 SA DN
12/16 EA DN
14/12 SA DN
12/14 EA DN
14/12 SA DN
14/12 SA DN
12/16 EA DN
12/16 EA DN
14/12 SA DN
14/12 SA DN
12/16 EA DN
12/14 EA DN
14/12 SA DN
12/8 SA DN
8/12 EA DN
12/10 SA DN
12/14 EA DN
12/14 EA DN14/12 SA DN
8/12 EA DN
12/8 SA DN
10/12 EA DN
12/10 SA DN 8/12 EA DN
24/16 EA DN
12/8 SA DN8/12 EA DN
10/12 EA DN
12/8 SA DN
12/10 SA DN
14/12 SA DN
8/12 EA DN
12/12 EA DN
12/12 SA DN
16/12 SA DN
20/12 EA DN
8/12 EA DN
12/8 SA DN
12/8 EA DN
12/10 SA DN
12/10 SA DN
12/8 EA DN
56/24 SA
56/2
4 S
A
96/24 SA
96/2
4 S
A
96/24 SA
56/24 SA
28/2
4 S
A
28/24 SA20/24 SA
20/1
6 S
A
28/24 SA
14/1
8 S
A
20/18 SA
14/1
2 S
A
20/1
6 E
A
20/16 EA
84/2
8 E
A
12/1
4 E
A
SA DN TO AHU-2
SA DN TO AHU-88
EA DN TO HRH-1
EA DN TO HRH-2
18/2
0 E
A
12/1
4 E
A 12/1
4 E
A
12/1
4 E
A
24/18 EA
56/2
4 E
A
28/24 EA 8/8 EA
8/8 EA
12/1
2 E
A
8/12
EA
24/1
8 E
A
28/24 EA
28/2
4 E
A
48/2
4 E
A
18/16 EA
12/1
4 E
A
12/1
4 E
A
32/24 EA
12/12 EA
18/20 EA
1 1/2" LPR
1 1/2" LPR
4" HWS/R, 6" CWS/R, 4" LPS, 1-1/2" LPR DN
6" C
WS
6" C
WR
6" C
WR
6" C
WS
1" HWS1" HWR
2" H
WR
2" H
WS
2" H
WS
2" H
WR
2" HWS2" HWR
HRP-1
ET-1
GF-1
4" EQUIPMENT PAD, TYP
4" HRS
4" H
RS
4" H
RR
4" HRR
4" HRS4" HRR
6" CWS/R DN TO CC-89A/89B, TYP BOTH UNITS
4" HWS/R DN TO PHC-89A/89B, TYP BOTH UNITS
4" HRS/R DN TO HRC-89A/89B, TYP BOTH UNITS
4" LPS, 1-1/2" LPR TO HUMIDIFIER H-89, TYP BOTH UNITS
4" HRS/R DN TO HRC-1C/1D, TYP BOTH UNITS
(2) 4" HRS DN TO HRP-1
MECHANICALROOM
A201
MD-6
MD-4
MD-3
8Ø SA
12/1
2 E
A
8
M6.06
L-3 (48/36), BOTTOM @ 5'-0" AFF
L-2 (96/78), BOTTOM MIN 36" ABOVE FINISHED ROOF
MD-5
48/20 OA, ELBOW UP, OPEN TO PENTHOUSE
SLOPE DUCTWORK BACK TOWARDS LOUVER
UH-1
1.5 GPM
UH-1
1.5 GPM
UH-1
1.5 GPM
UH-1
1.5 GPM
UH-1
UH-1
UH-1
T
ECWP-1
6" CWR
6" CWR
VFD-SF-88
VFD-SF-89
VFD-EF-2
VFD-EF-1
VFD-ECWP-1
EMCS CONTROL PANELS
FD-1, TYPICAL ALL DUCT PENETRATIONS THROUGH PENTHOUSE FLOOR. FACE DAMPER HARDWARE TOWARDS CENTER OF PENTHOUSE FOR ACCESSIBILITY
2" HWS
2" HWR
RELOCATED BACKFLOW PREVENTERS. INSTALL ON UNISTRUT. REFER TO M6.06 FOR DETAIL
FS-1
FS-1FS-1
FS-1
FS-1
VBR-88-251750 CFM2.0 GPM
12/1
2 S
A
16/12 SA
12/1
2 S
A
12/12 SA
12/12 SA OPEN TO DOGHOUSE, BALANCE TO 250 CFM EACH, TYP 3
12/12 TXFR FROM DOGHOUSE, PROVIDE TEMPERATURE SENSOR IN DUCT FOR VBR-A200
12/12 TXFR FROM DOGHOUSE
1
M6.04
4" V DN, 4" VTR
VBR-88-2521000 CFM
12/1
0 S
A
12/10 SA
14/1
2 S
A
R-1
50012/10
R-1
50012/10
2" HWR2" HWS
12" PVC DUCT DN
EF-61
12" PVC DUCT STACK, TERMINATE 5' ABOVE PENTHOUSE ROOF, MOUNT TO PENTHOUSE WALL
VBR-88-126300 CFM
2
M6.04
2" HWR2" HWS
36/16 FEA36/16 FEA
31Ø FEA
EF-62
20/26 FEA DUCT STACK, TERMINATE 5' ABOVE PENTHOUSE ROOF, MOUNT TO PENTHOUSE WALL 36/16 FEA DN
4" HWS4" HWR
FD-1, PROVIDE AT WALL OF PLENUM ON OA DUCT SERVING AHU, TYP BOTH UNITS
FD-1
SP
SP
SP
SP
SP
2" SV, TERMINATE 2' ABOVE ROOF
2" SV, TERMINATE 2' ABOVE ROOF
1" H
WS
1" H
WR
VBR-88-153400 CFM0.3 GPM
EQUIPMENT PAD
1
FD-1
FD-1
FD-1
HB-1 MOUNTED 48" A.F.F
NITROGEN AND OXYGEN GENERATORS. PROVIDED BY OWNER.
1 1/2" N, 1 1/2" O2 DN TO BE INSTALLED UNDER BASE BID
2
2
12" PVC DUCT DN
12Ø FEA
EF-60, SIDEWALL MOUNTED
MD-2
3/4" DRAIN OFF BOTTOM OF EXHAUST STACK, SEE DETAIL 1 SHEET M6.04, TYP BOTH UNITS
HRH-1/2 STATIC PRESSURE SENSOR
AHU-88/89 STATIC PRESSURE SENSOR
AHU-88/89 STATIC PRESSURE SENSOR
HRH-1/2 STATIC PRESSURE SENSOR
3
001A
001A
001A
001A
Kansas City, Missouri
2020 Baltimore, Suite 300
Kansas City, MO 64108-1914
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plo
t Ti
me
Sta
mp
:
File
Lo
ca
tio
n/N
am
e:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
AC
B
Key Plan
11
/21
/20
18
10
:17
:04
AM
C:\
(1)
Re
vit
Pro
jec
ts\
20
18
\6
24
15
1-
M-1
8_ja
me
s.m
ah
on
ey
@c
lark
en
ers
en
.co
m.r
vt
Upper Level Mechanical
Plan
M3.01
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTS
SCALE: 1/4" = 1'-0"
UPPER LEVEL MECHANICAL PLAN
0 2' 4' 8'
GENERAL NOTES:
1. ALL NEW WORK IS SHOWN IN HEAVY LINEWEIGHT. ALL WORK TO REMAIN AS EXISTING IS SHOWN IN LIGHT LINEWEIGHT.
2. ALL STAINLESS STEEL DUCTWORK IS SHOWN AS SHADED IN PLAN.
PLAN NOTES:
VAV BOX AND ASSOCIATED COMPONENTS TO BE INSTALLED ONLY UNDER ALTERNATE #1.
PROVIDE SHIPPING SPLIT FOR HRH UNIT BETWEEN COIL AND INTAKE SECTION. PROVIDE FULL-SIZE FLEXIBLE DUCT CONNECTION TO ACCOMMODATE BUILDING EXPANSION JOINT AND UP TO 2" OF MOVEMENT. CONTINUE EXPANSION JOINT THROUGH EQUIPMENT PAD AS WELL, SEE STRUCT.
ECWP-1 DIFFERENTIAL PRESSURE SENSOR.
1
2
3
A - 001 11/21/18 ADDENDUM #001
1
1
2
2
3
3
4
4
5
5
A A
E E
C C
B B
D D
3.6 4.6
3.1
ANIMAL HOLDING(BREEDING)
A144
ANIMAL HOLDING(BREEDING)
A141
ANIMAL HOLDING(BREEDING)
A139
ANIMAL HOLDING(BREEDING)
A137
ANIMAL HOLDING(EXPERIMENTAL)
A138
ANIMAL HOLDING(BREEDING)
A140
PROCEDURE(EUTHENASIA)
A148
PROCEDURE
A143B
PROCEDURE
A140A
PROCEDURE
A138A
PROCEDURE
A136
AIRLOCK
A151
DIRTY CAGEWASH
A153
CLEAN CAGEWASH
A131
FEED & BEDDING
A131A
MECHANICAL
M155
STEP DOWN
A126A
AIRLOCK
A126LOCKER / SHOWER
A125
WOMEN
A125A
MEN
A124A
LOCKER / SHOWER
A124
AIRLOCK /GOWNING
A122
HUMANIZED BSL II
A120
VHP
A108
STORAGE
A107
OFFICE
A103
IRRADIATION
M149
ANIMAL HOLDING(EXPERIMENTAL)
A145
AIRLOCK
A123
PROCEDURE
A120B
SURGERY
A120A
ANTE / GOWNING
A102
DIRTY
A116B
BSL II
A116
PROCEDURE
A116A
CORRIDOR
A109
RESTROOM
A149
CUST.
A150
CLEAN CAGESTORAGE
A134
ANTE RM
A146
GNOTOBIOTIC /GERM FREE
A146A
ANTE / GOWNING
A112
AIRLOCK
A114PROCEDURE
A145A
100 100
300200
200
200
100
100
100
100
100
150
100
100
150
100
100
100
100
100
100
100
100
100
200
200
100
150
100
100
150
200
100
100
100
100
100 100
100 150
200
0
+1
0
-1
-2
-3
0
-2
0 -1
+1
+1
+2
+3
+2+3
0
0
+1
+3
+3
0
+4
+4
+4
+4
+2
+4
+4
+4
+4
+5
+4
+4
+4
+4
+1
150
0
100
0+2
0
-1
+1
X
PRESSURIZATION LEGEND
ROOM PRESSURIZATION CLASS INDICATOR
100AIRFLOW DIRECTION AND RATE (CFM)
INDICATION OF WALL TO SEALED WALL TO STRUCTURE - SEAL ALL PENETRATIONS AIRTIGHT
SA: 125
EA: 225
SA: 150
EA: 250
SA: 200
EA: 300
SA: 250
EA: 350
SA: 150
EA: 250
SA: 100
EA: 50
SA: 1070
EA: 1220
SA: 50 SA: 125
SA: 50
SA: 215
EA: 115
SA: 215
EA: 215
SA: 1070
EA: 1320
SA: 100
SA: 440
EA: 640
SA: 790
EA: 940
SA: 50SA: 420
EA: 420
SA: 150
EA: 150
SA: 300
EA: 375
125
300
SA: 50
SA: 250SA: 100
EA: 2100
SA: 3500
SA: 3300
EA: 270
SA: 270
EA: 100EA: 100
EA: 340
SA: 240
EA: 390
SA: 390
EA: 390
SA: 390
EA: 390
SA: 390
EA: 390
SA: 390
EA: 390
SA: 390
EA: 0
SA: 1100
EA: 720
SA: 820
EA: 795
SA: 895
EA: 795
SA: 895
EA: 795
SA: 895
SA: 500
EA: 115
SA: 665
EA: 900
SA: 1000
EA: 900
SA: 1000
EA: 900
SA: 1000
EA: 880
SA: 980
EA: 875
SA: 500
SA: 650
EA: 445
SA: 645
100
ANIMAL HOLDING(BREEDING)
A143
PROCEDURE
A143A
CYLINDER
A152100
CLEAN
A116C
CLEAN
A120CSA: 100
+1100
100
SA: 450
EA: 350
SA: 450
EA: 550
SA: 400
EA: 300
SA: 500
EA: 100
400
OPEN OFFICE
M157
CORRIDOR
M124
EA: 600
CORRIDOR
A113
CORR.
A132
CORRIDOR
A147
CORRIDOR
A142
EXIST.
MY100
SA: 500
EA: 500
SA: 500
EA: 500
FEA: 1200
FEA: 400
FEA: 1200FEA: 400
FEA: 600 FEA: 600
FEA: 600FEA: 600
FEA: 450FEA: 450
FEA: 1200
SA: 300
ENVIRONMENTAL
A106
BEHAVIORAL
A105
FRAGMENTORS
A104
SA: 400
+2
300
EA: 600
001A
Kansas City, Missouri
2020 Baltimore, Suite 300
Kansas City, MO 64108-1914
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plo
t Ti
me
Sta
mp
:
File
Lo
ca
tio
n/N
am
e:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
AC
B
Key Plan
11
/21
/20
18
10
:17
:10
AM
C:\
(1)
Re
vit
Pro
jec
ts\
20
18
\6
24
15
1-
M-1
8_ja
me
s.m
ah
on
ey
@c
lark
en
ers
en
.co
m.r
vt
Air Pressurization Plan
M4.01
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTS
SCALE: 1/8" = 1'-0"
AIR PRESSURIZATION PLAN
4'0 8' 16'
A - 001 11/21/18 ADDENDUM #001
AIR TERMINAL UNITS
SEQUENCE OF OPERATIONS
NO SCALE
PENTHOUSEPANEL LOCATION:
NO SCALE
NO SCALE
SEE ELECPANEL LOCATION:
NO SCALE
TO BE DETERMINEDPANEL LOCATION:
SEQUENCE OF OPERATIONS
EXHAUST FAN EF-60
CONTROLS SCHEMATIC8
EF-60 / PENTHOUSE
11 MISCELLANEOUS ELEC. CONTROL POINTS
9
EMERGENCY POWER
ANNUNCIATOR PANEL
CONTROLS SCHEMATIC10
EF-61
DDC POINTS LIST
EF-61
EXHAUST FAN EF-61
SEQUENCE OF OPERATIONS
7VAV EXHAUST BOX CONTROL DIAGRAMNO SCALE
4
AIR IN
DDC VMA
CONTROLLER
1
KEYED NOTES:
NOTES:
2
3
2
5
1.
2.
AIR OUT
1
2
3
4
5
6VAV BOX CONTROL DIAGRAM WITH REHEAT AND EXHAUSTNO SCALE
FC COMMUNICATION BUSWIRE DAISY CHAINED TOPREVIOUS VMA CNTRLR
LOW VOLTAGEWIRE
7
AIR FLOWMEASURING
TAPS
AIR IN
FC COMMUNICATION BUSWIRE DAISY CHAINED TONEXT VMA CONTROLLER
DDC VMA
CONTROLLER
1
HWS HWR
SUPPLY AIRSENSOR6
AIR OUT
AIR VALVEDAMPER
NETWORKSENSOR
4
T
T S
OCCUPANCYSENSOR(S)
2
KEYED NOTES:
NOTES:
3
5
3
9
8
VMA TERMINAL INCLUDES CONSTANT VOLUME (CV) UNITS & VARIABLE AIR VOLUME (VAV) UNITS. UNLESS OTHERWISE NOTED, ALL CONTROL
WORK SHALL BE BYCONTRACTOR.
CAPS FOR VAV DP TEST PORTS MUST BE 1/4" BRASS PLUGS.
1.
2.
NC
EXHAUSTAIR VALVE
DAMPERAIR FLOW
MEASURINGTAPS
11
AIR IN AIR OUT
6 CONDUCTOR MIN
SA BUSWIRE
10
1
2
3
4
5
6
7
8
9
10
11
NETWORKSENSOR
4
S
OCCUPANCYSENSOR(S)
2
CO2SENSOR
11
10. EXHAUST FANS
10.1 CONTROL SHALL BE THROUGH THE EMCS.
10.2 EXHAUST FAN: THE EXHAUST FAN SHALL RUN CONTINUOUSLY AFTER RECEIVING A START COMMAND. IF
THE EXHAUST FAN HAS BEEN COMMANDED TO START AND THE EXHAUST FAN CURRENT TRANSFORMER
(CT) INDICATES THE FAN IS NOT RUNNING, THE EXHAUST FAN SHALL STOP AND AN ALARM SHALL BE
SIGNALED.
CONTROLLER WILL BE FURNISHED AND INSTALLED BY OWNER. CONTROLLER WILL BE JCI MODEL MS-VMA-16XX SERIES. PROGRAMMING ANDCOMMISSIONING WILL BE DONE BY OWNER.
NETWORK SENSOR WILL BE FURNISHED BY OWNER & INSTALLED BY CONTRACTOR. NETWORK SENSOR WILL BE JCI NS SERIES.
FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 3 CONDUCTOR, WITH BLUE OUTER CASING, DESCRIPTED AS
22-03 OAS STR PLNM NEON BLU JK DISTRIBUTED BY WINDY CITY WIRE CONSTRUCTED BY CABLE-TEK, OR APPROVED EQUIVALENT.
INSTALLATION OF OCC SENSOR IS WORK OF DIVISION 26, SEE E-SERIES SHEETS FOR FINAL LOCATIONS. A CONTROL CIRCUIT SHALL BE CONNECTED TOALL OCC SENSORS AS WORK OF DIVISION 23. A CONTROL SIGNAL SHALL BE RELAYED TO THE VAV TERMINAL UNIT THAT SERVES THAT SPACE. IN
LOCATIONS WHERE MULTIPLE OCC SENSORS ARE PRESENT, ALL SENSORS SHALL BE MONITORED AND TRANSMIT A SIGNAL TO THE VAV TERMINAL UNITWITHIN THAT SPACE. ALL SENSORS SHALL BE WIRED IN PARALLEL.
CONTROLLER MUST HAVE A MINIMUM OF 18 INCHES OF ACCESSIBLE CLEARANCE.
VAV SUPPLY TEMP SENSOR 1000 OHM PLATINUM RTD LOCATED APPROX. 8 FT. FROM VAV BOX DISCHARGE. PROVIDED, INSTALLED, & WIRED TOCONTROLLER BY CONTRACTOR.
FUSE LOCATED WITHIN 2 FEET OF VMA CONTROLLER.
LOW VOLTAGE WIRE BY DIVISION 23. SEE ELECTRICAL DRAWINGS FOR SOURCE.
VALVE WITH PROPORTIONAL 0-10 VOLT ACTUATOR OR EQUIVALENT.
SA BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 4 CONDUCTOR.
ELECTRIC ACTUATOR / DIFFERENTIAL PRESSURE TRANSMITTER - JOHNSON CONTROLS MODEL M9106-GGA-2 / DPT-2015-0 OR EQUIVALENT PROVIDED BYCONTRACTOR.
CONTROLLER WILL BE FURNISHED AND INSTALLED BY OWNER. CONTROLLER WILL BE JCI MODEL MS-VMA-16XX SERIES. PROGRAMMING AND
COMMISSIONING WILL BE DONE BY OWNER.
FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 3 CONDUCTOR, WITH BLUE OUTER CASING, DESCRIPTED
AS 22-03 OAS STR PLNM NEON BLU JK DISTRIBUTED BY WINDY CITY WIRE CONSTRUCTED BY CABLE-TEK, OR APPROVED EQUIVALENT.
CONTROLLER MUST HAVE A MINIMUM OF 18 INCHES OF ACCESSIBLE CLEARANCE.
FUSE LOCATED WITHIN 2 FT. OF VMA CONTROLLER.
LOW VOLTAGE WIRE BY DIVISION 23. SEE ELECTRICAL DRAWINGS FOR SOURCE.
VMA TERMINAL INCLUDES CONSTANT VOLUME (CV) UNITS & VARIABLE AIR VOLUME (VAV) UNITS. UNLESS OTHERWISE NOTED, ALL CONTROLWORK SHALL BE BY CONTRACTOR.
CAPS FOR VAV DP TEST PORTS MUST BE 1/4" BRASS PLUGS.
FC COMMUNICATION BUS
WIRE DAISY CHAINED TO
NEXT VMA CONTROLLER
FC COMMUNICATION BUS
WIRE DAISY CHAINED TO
PREVIOUS VMA CNTRLR
LOW VOLTAGE
WIRE
AIR FLOW
MEASURING
TAPS
AIR VALVE
DAMPER
ANNUNCIATOR
PANEL
1. AIR TERMINAL UNITS
1.1 CONTROL SHALL BE THROUGH THE EMCS.
1.2 AIRFLOW RATE: THE AIRFLOW RATE SHALL BE MEASURED BY THE AIRFLOW SENSOR
LOCATED IN THE NECK OF THE AIR TERMINAL UNIT.
1.3 DAMPER CONTROL: THE VOLUME DAMPER SHALL MODULATE TO MAINTAIN THE AIRFLOW
SETPOINT REQUIRED BY THE APPLICABLE MODE OF OPERATION.
1.4 REHEAT COIL VALVE: THE REHEAT COIL VALVE SHALL MODULATE TO MAINTAIN THE SPACE
TEMPERATURE SETPOINT. A DISCHARGE TEMPERATURE SENSOR LOCATED DOWNSTREAM OF THE
REHEAT COIL SHALL MEASURE THE DISCHARGE AIR TEMPERATURE.
1.5 SPACE TEMPERATURE SETBACK (FOR ROOMS WITH OCCUPANCY SENSORS): IF ALL OF THE
OCCUPANCY SENSORS SERVED BY A GIVEN ZONE INDICATE THAT THE ZONE IS UNOCCUPIED
FOR AN ADJUSTABLE TIME PERIOD, THE EMCS SHALL ADJUST THE SPACE TEMPERATURE
SETPOINT TO A PREDETERMINED (ADJUSTABLE) SETPOINT. ONCE ANY OF THE OCCUPANCY
SENSORS SERVED BY A GIVEN ZONE INDICATE THAT THE ZONE IS OCCUPIED, THE EMCS SHALL
CHANGE THE SPACE TEMPERATURE SETPOINT TO THE NORMAL VALUE.
1.6 PRESSURIZATION CONTROL (FOR ROOMS WITH TRACKING PAIRS): THE SUPPLY AIR TERMINAL
UNIT VOLUME DAMPER SHALL MODULATE TO MAINTAIN PROPER TEMPERATURE CONTROL.
THE EXHAUST AIR TERMINAL UNIT VOLUME DAMPER SHALL MODULATE TO MAINTAIN A
CONSTANT OFFSET AIRFLOW INTO OR OUT OF THE ZONE.
EXHAUST
AIR
OUTSIDE
AIR
EF
60-S
S
EF
60-S
802 803
EF M
DM
NO
DM
NO
804
ISO
-DT
ZN
-TP
801
3.
3.1
3.2
3.3
3.4
3.5
3.6
EM
ER
-PN
L
901
DEVICE
ANNUNCIATOR PANEL
DESCRIPTION
EMERGENCY POWER STATUS (HARDWIRED)
POINT NAME
EMER-PNL
TYPE
BI
TAG#
901
SEE ELECTRICAL SHEETS FOR LOCATION OF EMERGENCYANNUNCIATOR PANEL.
1.
GENERAL NOTES:
TAG# TYPE POINT NAME DESCRIPTION DEVICE801 AI ZN-TP ZONE TEMP ZONE SENSOR802 BI EF60-S EXH FAN 60 STATUS CURRENT SWITCH
803 BO EF60-SS EXH FAN 60 START/STOP CONTROL RELAY804 BO ISO-D ISOLATION DAMPER CONTROL ELECTRIC ACTUATOR
TAG# TYPE POINT NAME DESCRIPTION DEVICE1101 BI VMS-ALM VMS ALARMS VMS OUTPUT
5VAV BOX CONTROL DIAGRAM WITH REHEATNO SCALE
FC COMMUNICATION BUSWIRE DAISY CHAINED TOPREVIOUS VMA CNTRLR
LOW VOLTAGEWIRE
7
AIR FLOWMEASURING
TAPS
AIR IN
FC COMMUNICATION BUSWIRE DAISY CHAINED TONEXT VMA CONTROLLER
DDC VMA
CONTROLLER
1
HWS HWR
SUPPLY AIRSENSOR6
AIR OUT
AIR VALVEDAMPER
T
M
KEYED NOTES:
NOTES:
3
5
3
ELECTRICACTUATOR
9
8
VMA TERMINAL INCLUDES CONSTANT VOLUME (CV) UNITS & VARIABLE AIR VOLUME (VAV) UNITS. UNLESS OTHERWISE NOTED, ALL CONTROL
WORK SHALL BE BYCONTRACTOR.
CAPS FOR VAV DP TEST PORTS MUST BE 1/4" BRASS PLUGS.
1.
2.
NC
CO2
SA BUSWIRE
10
1
2
3
4
5
6
7
8
9
10
11
EX
HA
US
T
AIR
EF4-SS
EF4-S1001
1002
EF-61
M
2.
1.
ANY DEVICE REQUIRING POWER MUST BE POWERED BY CONTRACTOR.
SEE SPECIFICATIONS FOR DEVICE SPECIFICATIONS.
GENERAL NOTES:
BLDGEXHAUST
AIR
10.3 EXHAUST FAN OPERATION: THE EXHAUST FAN SHALL RUN CONTINUOUSLY.
TAG # TYPE POINT NAME DESCRIPTION DEVICE
1001 BI EF61-S EXH FAN 61 STATUS CURRENT SWITCH/CONTROL RELAY
1002 BO EF61-SS EXH FAN 61 S/S CONTROL RELAY
CONTROLLER WILL BE FURNISHED AND INSTALLED BY OWNER. CONTROLLER WILL BE JCI MODEL MS-VMA-16XX SERIES. PROGRAMMING AND
COMMISSIONING WILL BE DONE BY OWNER.
NETWORK SENSOR WILL BE FURNISHED BY OWNER & INSTALLED BY CONTRACTOR. NETWORK SENSOR WILL BE JCI NS SERIES.
FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 3 CONDUCTOR, WITH BLUE OUTER CASING, DESCRIPTED AS22-03 OAS STR PLNM NEON BLU JK DISTRIBUTED BY WINDY CITY WIRE CONSTRUCTED BY CABLE-TEK, OR APPROVED EQUIVALENT.
INSTALLATION OF OCC SENSOR IS WORK OF DIVISION 26, SEE E-SERIES SHEETS FOR FINAL LOCATIONS. A CONTROL CIRCUIT SHALL BE CONNECTED TOALL OCC SENSORS AS WORK OF DIVISION 23. A CONTROL SIGNAL SHALL BE RELAYED TO THE VAV TERMINAL UNIT THAT SERVES THAT SPACE. INLOCATIONS WHERE MULTIPLE OCC SENSORS ARE PRESENT, ALL SENSORS SHALL BE MONITORED AND TRANSMIT A SIGNAL TO THE VAV TERMINAL UNIT
WITHIN THAT SPACE. ALL SENSORS SHALL BE WIRED IN PARALLEL.
CONTROLLER MUST HAVE A MINIMUM OF 18 INCHES OF ACCESSIBLE CLEARANCE.
VAV SUPPLY TEMP SENSOR 1000 OHM PLATINUM RTD LOCATED APPROX. 8 FT. FROM VAV BOX DISCHARGE. PROVIDED, INSTALLED, & WIRED TOCONTROLLER BY CONTRACTOR.
FUSE LOCATED WITHIN 2 FT. OF VMA CONTROLLER.
LOW VOLTAGE WIRE BY DIVISION 23. SEE ELECTRICAL DRAWINGS FOR SOURCE.
VALVE WITH PROPORTIONAL 0-10 VOLT ACTUATOR OR EQUIVALENT.
SA BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 4 CONDUCTOR.
CO2 SENSOR. SEE PLANS FOR LOCATIONS.
EXHAUST FANS
CONTROL SHALL BE THROUGH THE EMCS.
START/STOP: THE EXHAUST FAN (EF) SHALL BE STARTED AND STOPPED BY THE EMCS
OR MANUALLY FROM THE OPERATOR'S WORKSTATION THROUGH CONTROL RELAYS.
EXHAUST FAN: THE EXHAUST FAN SHALL RUN CONTINUOUSLY AFTER RECEIVING A
START COMMAND.
IF THE EXHAUST FAN HAS BEEN COMMANDED TO START AND THE EXHAUST FAN
CURRENT TRANSFORMER (CT) INDICATES THE FAN IS NOT RUNNING, THE EXHAUST FAN
SHALL STOP AND AN ALARM SHALL BE SIGNALED.
DAMPER CONTROL: ON A COMMAND FOR A SYSTEM START, THE EXHAUST FAN
ISOLATION DAMPER AND LOUVER ISOLATION DAMPER SHALL OPEN. ONCE THE
DAMPERS ARE OPEN, THE EXHAUST FAN SHALL START. ON A STOP COMMAND, THE
ISOLATION DAMPERS SHALL CLOSE.
COOLING MODE: ON A CALL FOR COOLING, THE SYSTEM SHALL BE GIVEN A START
COMMAND AND SHALL RUN CONTINUOUSLY UNTIL THE TEMPERATURE SETPOINT IS
REACHED.
HEATING MODE: ON A CALL FOR HEATING, THE SYSTEM SHALL BE GIVEN A STOP
COMMAND.
PENTHOUSE
MECHANICAL ROOM
DDC POINTS LIST
EF-3
ANNUNCIATOR PANEL POINTS LIST
Kansas City, Missouri
2020 Baltimore, Suite 300
Kansas City, MO 64108-1914
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plo
t Ti
me
Sta
mp
:
File
Lo
ca
tio
n/N
am
e:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
11
/21
/20
18
10
:17
:12
AM
C:\
(1)
Re
vit
Pro
jec
ts\
20
18
\6
24
15
1-
M-1
8_ja
me
s.m
ah
on
ey
@c
lark
en
ers
en
.co
m.r
vt
Mechanical Controls
M6.02
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTSA - 001 11/21/18 ADDENDUM #001
001A
001A
TYPICAL BLDG-DP DPT ARRANGEMENT
NO SCALE
EXISTING MECHANICAL ROOMPANEL LOCATION:
NO SCALE
MECHANICAL ROOM M141PANEL LOCATION:
NO SCALE
TO BE DETERMINEDPANEL LOCATION:
**NOTE - BOTTLE WASHER CONTROL SIMILAR**
17
19
EMERG. CHILLED WATER PUMP
SEQUENCE OF OPERATIONS
SEQUENCE OF OPERATIONS
HEATING WATER PUMPS
EMERGENCY CHILLED WATER
PUMP CONTROL SCHEMATIC
EXISTING HOT WATER SYSTEM
CONTROLS SCHEMATIC
13
CONTROLS SCHEMATIC18
EF-62 / CAGE WASHER
DDC POINTS LIST
EF-62 / CAGE WASHER
EXHAUST FAN EF-62 / CAGE WASHER
SEQUENCE OF OPERATIONS
SIGNAL TO ASC
LOCATE VENTS AT ALL HIGH POINTS IN TUBING LINES.
DPT MUST BE ACCESSIBLE AND LOCATED 5' ABOVE FLOOR UNLESSAPPROVED BY OWNERS REPRESENTATIVE. SEE MECH. DRAWINGSFOR LOCATION.
BYPASS VALVE ASSEMBLY TO BE PRE-MANUFACTURED. SEESPECIFICATIONS.
ENERGIZE DPT PER MANUFACTURER'S RECOMMENDATIONS TOENSURE MEMBRANE IS NOT DAMAGED.
1.
2.
3.
4.
REQUIREDPOWER BY TCC
3/8" COPPERTUBING (TYP.)
GAGE COCK
(TYPICAL)
VENT
1/2" BALL VALVE
DPT
L
VENT
BYPASS VALVE
ASSEMBLY
H
VENT
4-20 mA
1/2" NPT THREAD-O-LET
RETURN PIPE
C/H WATER
SUPPLY PIPE
C/H WATER VENT
NO SCALE
LOCATE DPT AS SHOWN ON PLANS. CONTROL WIRINGFROM DPT MUST BE RUN BACK TO SAME CONTROLLERWITH CHILLED WATER PUMP SPEED CONTROL OUTPUT.
KEYED NOTES1
1
NOTES:
FRONT VIEW
6" x 6" WIRE TROUGH
FLOOR
120 VAC INPUT POWERDEDICATED 15A CIRCUIT
I/O
SIDE VIEW
FLOOR
EXP. ANCHORS
WAL
L
14ASC PANEL MOUNTING DETAILNO SCALE
BY DIVISION 16
3'-6
" TYP
ICAL
3' MIN DISTANCE
OPTIONAL FLOOR MOUNT
NOTES:
FRONT VIEW
FLOOR
1-1/2" UNISTRUTCHANNEL (2)
6" x 6" WIRE TROUGH
3/4" (MIN)
SIDE VIEW
FLOOR
EXP. ANCHORS
CHANNEL (2)1-1/2" UNISTRUT
VFD
WAL
L
12VFD MOUNTING DETAILNO SCALE
3'-6
" T
YP
ICA
L
8"(M
IN)
VFD
(TYPICAL)
TO POWER
OPTIONAL FLOOR MOUNT
18. EXHAUST FANS
18.1 CONTROL SHALL BE THROUGH THE EMCS. FANS ARE INTENDED TO RUN 24/7.
18.2 START/STOP: IF AN EXHAUST FAN IS GIVEN A START COMMAND, THE FAN SHALL START. IF THE EXHAUST
FAN CURRENT TRANSFORMER (CT) INDICATES THAT THE FAN IS NOT RUNNING, THE FAN SHALL BE SENT
A STOP COMMAND AND THE EMCS SHALL ALARM.
KEYED NOTES1
2
1
2
VENTILATION DAMPER LOCATED BETWEEN HOOD ON
CLEAN SIDE AND EXHAUST MAIN, SEE PLANS FORLOCATION.
POV (POWER-OPERATED VENT) PROVIDED WITH
EQUIPMENT, DO NOT CONNECT TO BMS
VARIABLE FREQUENCY DRIVE (VFD) IS PROVIDED AND INSTALLED BY CONTRACTOR.
KEEP ALL LOW VOLTAGE CONTROL WIRING (UNDER 25V) AND HIGH VOLTAGE POWER WIRING (OVER 25V) SEPARATED.(RUN IN SEPARATE CONDUIT).
PLYWOOD SIZE IS BASED ON ONE VFD IN EACH LOCATION. FOR MULTIPLE VFD'S, COORDINATE WITH OWNER'SREPRESENTATIVE.
POWER TO DRIVE AND LEADS TO MOTOR MUST BE IN SEPARATE CONDUIT.
INSTALL ISO TRANSFORMER IF REQUIRED.
DO NOT PLACE ISO TRANSFORMER BELOW VFD.
IF REMOTE SERVICE DISCONNECT IS REQUIRED IT MUST BE HARDWIRED TO VFD SAFTEY CIRCUIT TO SHUT DOWNDRIVE IF DISCONNECT IS OPENED.
1.
2.
3.
4.
5.
6.
7.
EXTEND 3/4" PLYWOOD
1" BELOW BOTTOM OF VFD
SIZE FOR VFD POWER
REQUIREMENTS
EXTEND 3/4" PLYWOOD 6" WIDER
THAN VFD ON BOTH SIDES
3/4" PLYWOOD PAINT BOTH
SIDES & ENDS MACHINE GRAY
VFD
DISCONNECTSIZE FOR MOTOR LOAD
POWER REQUIREMENTS
DO NOT PLACE
ISO BELOW VFD
EXTEND 3/4" PLYWOOD
3" ABOVE TOP OF VFD
POST
BASE (2)
BRACE
FITTING (2)
4'x4'x3/4" PLYWOOD (MIN)
(PAINT FRONT AND
ENDS MACHINE GRAY.)
1-1/2" UNISTRUT
CHANNEL (2)
ASC CONTROLLERS ARE SUPPLIED BY OWNER AND MOUNTED BY CONTRACTOR.
KEEP ALL LOW VOLTAGE CONTROL WIRING ( UNDER 25V) AND LOW VOLTAGE POWERWIRING (OVER 25V) SEPARATED. (RUN IN SEPARATE CONDUIT).
PLYWOOD SIZE IS BASED ON THE NUMBER OF CONTROLLERS IN EACH LOCATION.COORDINATE WITH OWNERS REPRESENTATIVE.
4/0 BOX WITH PULL CHAIN.
18W LED LIGHT WITH GUARD.
1.
2.
3.
3/4" CONDUIT
1" CONDUITMINIMUM
6"x6" WIRE
TROUGH
1-1/2" UNISTRUT
CHANNEL (2)
4'x4'x3/4" PLYWOOD (MIN)
(PAINT FRONT AND ENDS
MACHINE GRAY)
3/4" CONDUIT
4/0 BOX WITH
PULL CHAIN. 18W
LED WITH GUARD.
ASC ASC2" MIN. CONDUIT (2)
POST
BASE (2)
BRACE
FITTING (2)
3 BREATHER VENT DAMPER CONTROL HARDWIRED TO
EQUIPMENT, DO NOT CONNECT TO BMS
HC
P10
-SC
(E
)
HC
P10
-SS
(E
)
HC
P10
-S (
E)
M
VFD
HCP-10 (E)
GENERAL NOTES:1. SEE SPECIFICATIONS AND PIPING SCHEMATIC DRAWINGS FOR
ADDITIONAL REQUIRED VALVES, PIPE ACCESSORIES, ETC.
2. HEATING WATER PUMPS
2.1 CONTROL SHALL BE THROUGH THE EMCS.
2.2 EMERGENCY OPERATION: THE INTENT IS FOR THE EXISTING HCP-10 TO RUN WHEN THE
GENERATOR SERVING THE VIVARIUM IS STARTED TO PROVIDE HEATING WATER TO THE
AHU'S. THE CIRCULATING HEATING WATER PUMP SHALL OPERATE IN THE SAME FASHION AS
THE EXISTING SEQUENCE OF OPERATIONS USING THE EXISTING CONTROL PANEL AND
CONTROL DEVICES (DP SHOWN). SEE ELECTRICAL SHEETS: THE EXISTING CONTROL PANEL
POWER TO ALSO BE BACKED UP ON EMERGENCY POWER.
UNIT HEATER/CABINET UNIT HEATER
SEQUENCE OF OPERATIONS
EC
WP
1-S
C
EC
WP
1-S
S
EC
WP
1-S
M
VFD
ECWP-1
19011903 1902
- - -
HW
-DP
(E
)
DPT
-
CW
-DP
DPT
1904
TAG# TYPE POINT NAME DESCRIPTION DEVICE
1904 AI CW-DP CW DIFF PRESSURE DIFF PRESSURE TRANSMITTER
1901 AO ECWP1-SC ECW PUMP 1 SPEED CONTROL VFD
1902 BI ECWP1-S ECW PUMP 1 STATUS CURRENT SWITCH1903 BO ECWP1-SS ECW PUMP 1 START/STOP CURRENT RELAY
TAG# TYPE POINT NAME DESCRIPTION DEVICE- AO HCP10-SC (E) HW PUMP 10 SPEED CONTROL VFD (E)
- BI HCP10-S (E) HW PUMP 10 STATUS CURRENT SWITCH (E)- BO HCP10-SS (E) HW PUMP 10 START/STOP CONTROL RELAY (E)- AI HW-DP (E) HW DIFF PRESSURE DIFF PRESSURE TRANSMITTER (E)
CAMPUS CHILLEDWATER LOOP SUPPLY
CAMPUS CHILLEDWATER LOOP RETURN
1.
2.
NOTES:
1
2
3
4
5
KEYED NOTES:
100 VA
PSH500A
1
100 VA
100 VA
100 VA
100 VA
DISCONNECT
SWITCH
24V
COM
24V
COM
24V
COM
24V
COM
24V
COM
480
277
240
120
COM
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
RIB AC
3
2
BREAKER
SWITCH
ENCLOSED AC POWER SUPPLY
POWER
SUPPLY/TRANSFORMER
5
4
(FUSE)
6
6 7
7
ALL CONDUIT AND WIRING SHALL BE BY CONTRACTOR.
CONNECT CONTROL POINTS TO NEAREST DDC CONTROLLER.
TWO POSITION ELECTRIC ACTUATOR.
1000 OHM PLATINUM ZONE SENSOR LOCATED IN AREA SERVED BY UNIT HEATER. DO
NOT INSTALL IN DIRECT PATH OF UNIT HEATERDISCHARGE.
1
2
3
4
4
16UH/CUH DETAILNO SCALE
KEYED NOTES:
3
AIR OUTAIR IN
HOT WATERHEATING COIL
T
ZONE SENSOR
M
ELECTRICACTUATOR
HW
S
HW
R
DEVICE
ZONE SENSOR
CONTROL RELAY
POINT NAME
ZN-T
UH-C
TAG#
1601
1602
TYPE
AI
BO
DESCRIPTION
ZONE TEMP
UNIT HEATER COMMAND
UNIT HEATER DDC POINT LIST
1602UH-C
1601ZN-T
EXHAUSTAIR
EF62-SS
EF62-S1801
1802
EF-5M
2.
1.
ANY DEVICE REQUIRING POWER MUST BE POWERED BY CONTRACTOR.
SEE SPECIFICATIONS FOR DEVICE SPECIFICATIONS.
GENERAL NOTES:
DMNO
1803EXH-D E
S ED-ES1804
DM
NO
1806VENT-DDM
NC
TO CLEAN SIDE CANOPY HOOD
1805POV-D
18.3 DAMPER CONTROL: ON A COMMAND FOR A SYSTEM START, THE EXHAUST FAN DAMPER SHALL OPEN.
ONCE THE DAMPER IS OPEN, THE EXHAUST FAN SHALL START. ON A STOP COMMAND, THE ISOLATION
DAMPERS SHALL CLOSE.
TO BOTTLE WASHER (CONTROLLED SIMILAR) AND
AUTOCLAVE HOODS (CONSTANT VOLUME)
TAG # TYPE POINT NAME DESCRIPTION DEVICE
1801 BI EF62-S EXH FAN 62 STATUS CURRENT SWITCH/CONTROL RELAY
1802 BO EF62-SS EXH FAN 62 S/S CONTROL RELAY
1803 BO EXH-D EXHAUST DAMPER CONTROL ELECTRIC ACTUATOR
1804 BI ED-ES EXHAUST DAMPER END SWITCH END SWITCH
1805 BO VENT-D BREATHER VENT DAMPER CONTROL ELECTRIC ACTUATOR
1806 BO POV-D POWER OPERATED VENT PROVIDED WITH EQUIPMENT
18.4 CAGE WASHER / BOTTLE WASHER CONTROL: THE VENTILATION DAMPER SHALL BE CONNECTED TO
THE WASHER CONTROL PANEL AND LINKED WITH THE COMMAND OF THE POWER OPERATED VENT
(POV). WHEN THE POV OPENS, THE VENTILATION DAMPER SHALL CLOSE AND VICE-VERSA. THE
INTENT IS TO ALWAYS PULL THROUGH THE CLEAN SIDE HOOD AND EITHER GO THROUGH THE
BREATHER VENT INTO THE CAGE WASHER TO BE EXHAUSTED, OR EXHAUST DIRECTLY THROUGH
THE HOOD TO THE EXHAUST FAN. IF EITHER DOOR OF THE WASHER IS OPENED, THE POV SHALL
CLOSE AND THE VENTILATION DAMPER SHALL OPEN.
EACH SECONDARY OUTPUT LINE CAN POWER 3-5 VAV CONTROLLERS MAXIMUM. (100 VA)
PRIMARY LINE INFO: 480/277/240/120 Vac, #12 AWG MINIMUM
SECONDARY LINE INFO: 24 Vac, #12-26 AWG, 100 VA. MAX LENGTH 175 FEET USING #14 AWG
DISCONNECT SWITCH REQUIRED, EXTERNALLY MOUNTED WITHIN 12 INCHES OF RIB POWER SUPPLY
500VA POWER SUPPLY - INCLUDED IN RIB MODEL# PSH500A OR APPROVED EQUIVALENT
ALL SECONDARY LINES MUST BE LABELED IN ENCLOSURE AS TO WHICH VAV'S THEY POWER PRIOR TOENERGIZING POWER SUPPLY
A SEPARATE 3 AMP FUSE IS REQUIRED WITHIN 3 FEET OF EACH VAV
SECONDARY LINE CAN BE RAN IN SAME CONDUIT AS FC BUS
ENCLOSED POWER SUPPLY MUST BE LOCATED IN ELECTRICAL ROOM, MECHANICAL ROOM, OR JANITOR'SCLOSET AND BE ACCESSIBLE. ANY OTHER LOACAION MUST BE APPROVED BY THE OWNER'SREPRESENTATIVE
19. CHILLED WATER PUMPS
19.1 CONTROL SHALL BE THROUGH THE EMCS.
19.2 START/STOP: THE PUMP IS INTENDED TO OPERATE WHEN THE EMERGENCY
GENERATOR IS STARTED. IF THE CHILLED WATER PUMP IS GIVEN A START
COMMAND, THE PUMP SHALL START. IF THE CHILLED WATER PUMP CURRENT
TRANSFORMER (CT) INDICATES THE PUMP IS NOT RUNNING,THE EMCS SHALL
ALARM AND THE NEXT PUMP SHALL BE SENT A START COMMAND.
19.3 CHILLED WATER PRESSURE CONTROL: THE PUMP WILL UTILIZE THE
DIFFERENTIAL PRESSURE SENSOR TO CONTROL PUMP SPEED. THE CHILLED
WATER PUMP VFD SHALL MODULATE THE CHILLED WATER PUMP SPEED TO
MAINTAIN THE CHILLED WATER DIFFERENTIAL PRESSURE SETPOINT
(ADJUSTABLE). ONCE THE PUMP DROPS TO MINIMUM SPEED AND THE VALVE
CLOSES BELOW A DETERMINED SETPOINT (ADJUSTABLE) THE PUMP SHALL STOP.
NOTES:
FIRST FLOOR
PENTHOUSE
15FC BUS SCHEMATIC DIAGRAMNO SCALE
HRU's
VAV VAV
AH-89AH-88 VAV VAV
BASEMENT
AIR-CUITY
IMS
NAENET-
WORKPANEL
PH M297
MR G001
FC BUS TO BE CONTINUOUS DAISY CHAIN WITHOUT SPLICES. CONNECTIONS CAN ONLY BEMADE AT CONTROLLERS. SEE PLANS FOR QUANTITY AND LOCATIONS OF VAVCONTROLLERS.
OWNER WILL MAKE TERMINATION CONNECTIONS AT PANELS. LOCATE PANELS IN SAMEROOM AS EQUIPMENT SERVED.
FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 3CONDUCTOR, WITH BLUE OUTER CASING, DESCRIPTED AS 22-03 OAS STR PLNM NEON BLUJK DISTRIBUTED BY WINDY CITY WIRE, CONSTRUCTED BY CABLE-TEK, OR APPROVEDEQUIVALENT.
ROUTE 34" CONDUIT WITH PULL STRING FROM BASEMENT TO PENTHOUSE AS SHOWN FOR
OWNER INSTALLED CAT 6 CABLE. NO LB'S. COORDINATE TERMINATION POINTS WITHOWNERS REP.
COORDINATE FIELD ROUTING WITH OWNERS REPRESENTATIVE.
1.
2.
3.
4.
5.
FC BUS
3/4" CONDUIT
2. CONNECT POINTS TO NEAREST FEC CONTROLLER.
HEATING WATER SYSTEM DDC POINTS LIST
CHILLED WATER SYSTEM DDC POINTS LIST
Kansas City, Missouri
2020 Baltimore, Suite 300
Kansas City, MO 64108-1914
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plo
t Ti
me
Sta
mp
:
File
Lo
ca
tio
n/N
am
e:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
11
/21
/20
18
10
:17
:13
AM
C:\
(1)
Re
vit
Pro
jec
ts\
20
18
\6
24
15
1-
M-1
8_ja
me
s.m
ah
on
ey
@c
lark
en
ers
en
.co
m.r
vt
Mechanical Controls
M6.03
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTSA - 001 11/21/18 ADDENDUM #001
001A
PACKAGED AIR HANDLING UNIT SCHEDULE
EQUIPMENT MARK: AHU-88 (AHU-89 SIMILAR) BLANK / HUMIDIFIER GRID SECTION:
LOCATION: PENTHOUSE MECHANICAL ROOM Airflow (CFM): 27,500
Steam Flowrate (LB/HR): 1323.47 AT 7 PSI
UNIT TYPE: Grid Manufacturer and Model: PROVIDED WITH AHU
Draw Thru / Blow Thru DRAW THRU Remarks: DOUBLE-SLOPED IAQ DRAIN PAN, INSTALL BLANK-OFF PANELS AS
Sgl Zone/Dual Duct/VAV VARIABLE AIR VOLUME REQUIRED, DIRECT INJECT STEAM, NON-JACKETED SINGLE TUBE DISPERSION
Cooling Medium/Heating Medium CHILLED WATER/HOT WATER
ACCESS SECTION
UNIT ARRANGEMENT: Remarks: MIN. 24" MODULE LENGTH, ACCESS DOOR, COMPARTMENT LIGHT
Horizontal/Vertical HORIZONTAL BACK OPENING, FRONT OPENING.
Fan Discharge Arrangement TOP
COOLING COIL: CC-88A/88B
MANUFACTURER AND MODEL: TRANE PERFORMANCE CLIMATE CHANGER SIZE 57 Coil Airflow (CFM): 27,500
OR APPROVED EQUIVALENT Minimum Coil Face Area (Sqft.): 56.5
Maximum Coil Face Velocity (FPM): 487
UNIT COMPONENTS IN DIRECTION Total Coil Capacity (MBH): 2438.8
OF AIR FLOW: OUTSIDE AIR / FILTER SECTION Sensible Coil Capacity (MBH): 1301.4
HEAT RECOVERY COIL HRC-1A/1B Entering Air Temperature DB / WB (Deg. F): 95.0 / 78.0
EXTENDED-MEDIUM ACCESS SECTION Leaving Air Temperature DB / WB (Deg. F): 52.5 / 52.4
PREHEAT COIL PHC-88 Air Pressure Drop (in w.g.) 1.12
EXTENDED-MEDIUM ACCESS SECTION Fluid Type: CHILLED WATER
BLANK / HUMIDIFER GRID SECTION Water Temperature EWT / LWT (Deg. F): 46 / 60
EXTENDED-MEDIUM ACCESS SECTION Water Pressure Drop (ft w.g.): 23.6
COOLING COIL SECTION CC-88A/88B Water Flowrate (GPM) 347.4
EXTENDED-MEDIUM ACCESS SECTION Rows / Fins per Foot: 8 / 139
SUPPLY FAN SECTION SF-88A - SF-88D Coil Tube Diameter / Material: 5/8" / 0.025" COPPER TUBE
SILENCER SECTION Remarks: SAME-SIDE COIL CONNECTION, DRAINABLE COIL, DOUBLE-SLOPED IAQ DRAIN PAN
HEPA FILTER SECTION
DISCHARGE PLENUM ACCESS SECTION
Remarks: MIN. 24" MODULE LENGTH, ACCESS DOOR, COMPARTMENT LIGHT
AIR MIXING / FILTER SECTION: BACK OPENING, FRONT OPENING.
Remarks: MIN. 48" MODULE LENGTH, ACCESS DOOR, COMPARTMENT LIGHT, STRAIGHT PRE-FILTERS
PARALLEL BLADE DAMPER, TOP FRONT OPENING. FAN SECTION: SF-88A - 88D
Module Air Pressure Drop (in. w.g.): 1.09 Type: PLENUM
Design Airflow (CFM): 27,500 Airflow (CFM): 27,500 (6875 EA)
Filter Face Area (Sqft): 100.0 External Static Pressure (in w.g.): 3.50
Filter Face Velocity (FPM): 275 Total Static Pressure (in w.g.): 7.99
Filter Bank Pressure Drop (in w.g.): 1.00 Fan BHP / RPM: 13.8 / 2990 (EACH) 55.2 TOTAL
Filter Type / Efficiency: 2" PLEATED / MERV 8 Motor HP / RPM: 15 / 1750 (EACH) 60 TOTAL
Remarks: ACCESS DOOR, COMPARTMENT LIGHT, MAGNAHELIC GAUGE ACROSS FILTER BANK MOUNTED ON Motor VOLTAGE / PHASE / HERTZ: 460 / 3 / 60
OUTSIDE OF UNIT. AIR PRESSURE DROP FOR "DIRTY" FILTERS. CAULK/SEAL FILTER RACKS AIRTIGHT Motor Class / Drive Service Factor: NEMA PREMIUM ODP
TO ENSURE ALL AIR TRAVELS THROUGH FILTER MEDIA. Vibration Isolators: 2" SEISMIC
Fan Wheel: No./Size/Blade Type: 4 / 20" DD PLENUM
HEAT RECOVERY COIL: HRC-1A/1B Remarks: VFD SPEED CONTROL, HIGH EFFICIENCY MOTOR, ACCESS DOOR,
Coil Airflow (CFM): 27,500 COMPARTMENT LIGHT, EXTENDED LUBE LINES, FACTORY-PROVIDED
Minimum Coil Face Area (Sqft): 56.50 FAN BASE WITH MOUNTED FAN AND MOTOR, 120V/1P RECEPTACLE
Maximum Coil Face Velocity (FPM): 487
SILENCER SECTION:
Summer Performance: Design Airflow (CFM): 27,500
Total Coil Capacity (MBH): 346.4 Silencer Length (ft): 3.00
Sensible Coil Capacity (MBH): 346.4 Air Pressure Drop (in. w.g.): 0.08
Entering Air Temperature DB / WB (Deg. F): 95.0 / 78.0 Remarks: DISSIPATIVE TYPE
Leaving Air Temperature DB / WB (Deg. F): 83.7 / 75.8
Air Pressure Drop (in. w.g.): 0.5 HEPA FILTER SECTION:
Water Temperature EWT / LWT (Deg. F): 78.6 / 90.2 Design Airflow (CFM): 27,500
Water Pressure Drop (ft. w.g.): 4.01 Filter Face Area (Sqft): 57
Filter Face Velocity (FPM): 482
Winter Performance: Filter Bank Pressure Drop (in w.g.): 2.00
Total Coil Capacity (MBH): 774.25 Filter Type / Efficiency: HEPA FILTER 99.97% EFFICIENT
Sensible Coil Capacity (MBH): 774.25 Remarks: ACCESS DOOR, COMPARTMENT LIGHT, MAGNAHELIC GAUGE ACROSS FILTER BANK MOUNTED ON
Entering Air Temperature (Deg. F): 0.0 OUTSIDE OF UNIT. AIR PRESSURE DROP FOR "DIRTY" FILTERS. CAULK/SEAL FILTER RACKS AIRTIGHT
Leaving Air Temperature (Deg. F): 31 TO ENSURE ALL AIR TRAVELS THROUGH FILTER MEDIA.
Air Pressure Drop (in. w.g.): 0.46
Water Temperature EWT / LWT (Deg. F): 50 / 21.5 AHU-1 SOUND DATA:
Water Pressure Drop (ft. w.g.): 4.66 Supply Top / Outdoor / Casing:
1st Octave Band: 79 / 91 / 89
Coil Data: 2nd Octave Band: 82 / 84 / 90
Fluid Type: 40% PROPYLENE GLYCOL 3rd Octave Band: 74 / 87 / 89
Water Flowrate (GPM): 60.0 4th Octave Band: 69 / 83 / 91
Rows / Fins per Foot: 6 / 132 5th Octave Band: 61 / 83 / 88
Remarks: SAME-SIDE COIL CONNECTION, DRAINABLE COIL, 0.035" THICK COPPER TUBE, ALUMINUM FINS, 6th Octave Band: 61 / 83 / 79
DOUBLE-SLOPED IAQ DRAIN PAN 7th Octave Band: 65 / 81 / 79
8th Octave Band: 58 / 71 / 75
ACCESS SECTION
Remarks: MIN. 24" MODULE LENGTH, ACCESS DOOR, COMPARTMENT LIGHT DISCHARGE PLENUM
BACK OPENING, FRONT OPENING. Remarks: MIN. 48" MODULE LENGTH, ACCESS DOOR, COMPARTMENT LIGHT
BACK OPENING, TOP OPENING.
PREHEAT COIL: PHC-1
Coil Airflow (CFM): 27,500 ADDITIONAL REMARKS: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11
Coil Capacity (MBH) 1567 (APPLIES TO AHU-1 AND AHU-2)
Coil Face Velocity (FPM) 487 SCHEDULE NOTES (APPLY TO AHU-1 AND AHU-2):
Air Temperature EAT / LAT (Deg. F): 0 / 52.5 1. ALL FANS TO BE PROVIDED WITH FIXED PITCH SHEAVES AND EXTENDED LUBE LINES TO OUTSIDE OF CASING.
Air Pressure Drop (in w.g.): 0.08 2. PROVIDE MIN 12"x12" VIEWING WINDOWS ON ACCESS DOORS AT ALL FAN AND DAMPER SECTIONS.
Fluid Type: HOT WATER 3. PROVIDE MINIMUM 6" HIGH BASE RAILS FOR MOUNTING TO EQUIPMENT PAD, UPSIZE IF NECESSARY FOR CONDENSATE TRAP, SEE DETAILS
Water Temperature EWT / LWT (Deg. F): 180 / 160 SHEET.
Water Flowrate (GPM) 165.9 4. ALL COIL AND FAN PERFORMANCE DATA SUBMITTALS MUST BE COMPUTER GENERATED - NO EXCEPTIONS.
Water Pressure Drop (ft. w.g.): 21.1 5. PROVIDE DOUBLE WALL CONSTRUCTION WITH 2" THICK, 3.0 LB DENSITY INSULATION.
Rows / Fins per Foot: 1 / 99 6. ALL FAN MOTORS SHALL INVERTER DUTY TYPE AND MEET NEMA MG 1 MINIMUM FULL LOAD EFFICIENCIES.
Coil Tube Diameter / Material: 5/8" / 0.025" COPPER TUBE 7. SEE MECHANICAL SHEETS FOR AHU CONFIGURATION. MAX UNIT DIMENSIONS: 422" L X 126" W X 89" H. MAX WEIGHT OF 17,000 LB.
Remarks SAME-SIDE COIL CONNECTION, DRAINABLE COIL, 120V/1P RECEPTABLE ON EACH SIDE OF MODULE 8. ALL FILTER PRESSURE DROPS CALCULATED AT DIRTY CONDITIONS.
9. PROVIDE INDIVIDUAL LIGHT CIRCUIT AND RECEPTACLE CIRCUIT, EACH PRE-WIRED.
ACCESS SECTION 10. ALL DAMPERS SHALL BE LOW-LEAK CONSTRUCTION, EQUIVALENT TO RUSKIN CD-60.
Remarks: MIN. 24" MODULE LENGTH, ACCESS DOOR, COMPARTMENT LIGHT 11. AIRFLOW VALUES ARE LISTED FOR CURRENT DESIGN. AHU MUST BE SIZED AND CAPABLE OF 120% OF SCHEDULED CAPACITIES.
BACK OPENING, FRONT OPENING. 12. PROVIDE BLANK-OFF PLATES FOR EACH FAN FOR MAINTENANCE.
GENERAL NOTES:
1. ELECTRICAL CONTRACTOR WILL PROVIDE (2) 120V/1P CIRCUITS, (1) FOR AHU LIGHTS AND (1) FOR AHU RECEPTACLES.
2. PROVIDE DIGITAL TIME SWITCHES, WATTSTOPPER MODEL TS-400-120V OR EQUIVALENT FOR AHU LIGHTS.
3. LIGHT LEVELS IN SECTIONS WITH LIGHTS SHALL BE MINIMUM 20 FC. PROVIDE ADD'L FIXTURES AS REQUIRED.
EXHAUST FAN / HEAT RECOVERY SCHEDULE
EQUIPMENT MARK: HRH-1 (HRH-2 SIMILAR)
LOCATION: PENTHOUSE
UNIT TYPE: HEAT RECOVERY / EXHAUST FAN
MANUFACTURER AND MODEL: TRANE PERFORMANCE CLIMATE CHANGER SERIES
OR EQUIVALENT, SIZE 57
UNIT COMPONENTS IN DIRECTION AIR MIXING SECTION
OF AIR FLOW: HEAT RECOVERY COIL HRC-1C / 1D
EXTENDED-MEDIUM ACCESS SECTION
EXHAUST FAN SECTION EF-1A, 1B, 1C, 1D
AIR MIXING SECTION:
Exhaust Air Entering Location: TOP
Openings: TOP OPENING W/ PARALLEL BLADE DAMPER, FULL FACE FRONT OPENING.
Design Airflow (CFM): 23,000
Damper Face Area (Sqft): 22.8
External Air Pressure Drop (in. w.g.): 0.15
Module Air Pressure Drop (in. w.g.): 0.62
Filter Data:
Filter Type / Efficiency: 2" PLEATED / MERV 8
Design Airflow (CFM): 23,000
Filter Face Area (Sqft): 100.0
Filter Face Velocity (FPM): 230
Total Filter Pressure Drop (in w.g.): 1.00 (AIR PRESSURE DROP FOR "DIRTY" FILTERS.)
Remarks: MAGNAHELIC GAUGE ACROSS FILTER BANK MOUNTED ON OUTSIDE OF UNIT. CAULK/SEAL FILTER
RACKS AIRTIGHT TO ENSURE ALL AIR TRAVELS THROUGH FILTER MEDIA. PROVIDE W/
ACCESS DOOR AND COMPARTMENT LIGHT.
PROVIDE SHIPPING SPLIT BETWEEN MIXING AND COIL SECTION TO ACCOMMODATE EXPANSION
JOINT AND FLEXIBLE DUCT CONNECTION, SEE PLAN.
HEAT RECOVERY COIL: HRC-1C/1D
Coil Airflow (CFM): 23,000
Minimum Coil Face Area (Sqft): 56.50
Maximum Coil Face Velocity (FPM): 407
Summer Performance:
Total Coil Capacity (MBH): 323.8
Entering Air Temperature DB (Deg. F): 72.0
Leaving Air Temperature DB (Deg. F): 84.9
Air Pressure Drop (in. w.g.): 0.45
Water Temperature EWT / LWT (Deg. F): 78.4 / 90.2
Water Pressure Drop (ft. w.g.): 4.5
Winter Performance:
Total Coil Capacity (MBH): 774.5
Entering Air Temperature (Deg. F): 70 / 52
Leaving Air Temperature DB / WB (Deg. F): 37.1 / 36.9
Air Pressure Drop (in. w.g.): 0.46
Water Temperature EWT / LWT (Deg. F): 21.5 / 50
Water Pressure Drop (ft. w.g.): 4.3
Coil Data:
Fluid Type: 40% PROPYLENE GLYCOL
Water Flowrate (GPM): 60.0
Rows / Fins per Foot: 6 / 132
Remarks: MIN. 24.5" SECTION LENGTH, ACCESS DOOR, COMPARTMENT LIGHT, SAME-SIDE COIL CONNECTION,
DRAINABLE COIL, 0.020" THICK COPPER TUBE, ALUMINUM FINS, DOUBLE-SLOPED IAQ DRAIN PAN.
ACCESS SECTION
Remarks: MIN. 24" MODULE LENGTH, ACCESS DOOR, COMPARTMENT LIGHT
BACK OPENING, FRONT OPENING.
FAN SECTION: EF-1A, 1B, 1C, 1D
Type: PLENUM
Airflow (CFM): 23000 (5750 EA)
External Static Pressure (in w.g.): 3.00
Total Static Pressure (in w.g.): 5.25
Fan BHP / RPM: 7.34 / 2259 (EACH) 29.4 TOTAL
Motor HP / RPM: 7.5 / 1800 (EACH) 30 TOTAL
Motor VOLTAGE / PHASE / HERTZ: 460 / 3 / 60
Motor Class / Drive Service Factor: ODP EPACT / 1.5 FIXED
Vibration Isolators: INTERNAL SPRING - MINIMUM 2" DEFLECTION
Fan Wheel: Size/Type: 20" DD PLENUM FULL WIDTH
Remarks: VFD SPEED CONTROL, PREMIUM EFFICIENCY MOTOR, ACCESS DOOR, FIXED PITCH SHEAVES,
COMPARTMENT LIGHT, EXTENDED LUBE LINES, FACTORY-PROVIDED FAN BASE WITH
MOUNTED FAN AND MOTOR, 120V/1P RECEPTACLE, BACK OPENING, TOP FRONT DISCHARGE
SOUND DATA:
Unit Discharge/Return/Casing Sound Power
1st Octave Band: 81 / 78 / 82
2nd Octave Band: 80 / 75 / 85
3rd Octave Band: 81 / 75 / 79
4th Octave Band: 74 / 79 / 80
5th Octave Band: 84 / 74 / 75
6th Octave Band: 85 / 79 / 70
7th Octave Band: 83 / 76 / 66
8th Octave Band: 70 / 62 / 57
REMARKS: 1. FAN TO BE PROVIDED WITH FIXED PITCH SHEAVES AND EXTENDED LUBE LINES TO OUTSIDE OF CASING.
2. PROVIDE VIEWING WINDOWS ON ACCESS DOORS AT ALL FAN AND DAMPER SECTIONS.
3. ALL COIL AND FAN PERFORMANCE DATA SUBMITTALS MUST BE COMPUTER GENERATED - NO EXCEPTIONS.
4. PROVIDE DOUBLE WALL CONSTRUCTION WITH 2" THICK, 3.0 LB DENSITY INSULATION.
5. ALL FAN MOTORS SHALL BE PREMIUM EFFICIENCY, INVERTER DUTY TYPE.
6. SEE MECHANICAL SHEETS FOR CONFIGURATION, MODULE SIZES, AND LOCATION OF ACCESS DOORS.
7. ALL FILTER PRESSURE DROPS CALCULATED AT DIRTY CONDITIONS.
8. PROVIDE INDIVIDUAL LIGHT CIRCUIT AND RECEPTACLE CIRCUIT, EACH PRE-WIRED.
9. ALL DAMPERS SHALL BE LOW-LEAK CONSTRUCTION, EQUIVALENT TO RUSKIN CD-60.
10. ALL ACCESS DOORS SHALL BE THE FULL HEIGHT OF THE UNIT, MINIMUM 18" WIDE.
11. ELECTRICAL CONTRACTOR WILL PROVIDE (2) 120V/1P CIRCUITS, (1) FOR AHU LIGHTS AND (1) FOR
RECEPTACLES.
12. WEIGHT OF UNIT SHALL BE RESTRICTED TO 6100 LBS (INSTALLED WEIGHT).
13. PROVIDE MINIMUM 8" CURB. MAX UNIT DIMENSIONS: 147" L X 126" W X 89" H
14. PROVIDE LIGHT FIXTURE QUANTITIES IN SECTIONS TO PROVIDE MINIMUM 20 FC.
Kansas City, Missouri
2020 Baltimore, Suite 300
Kansas City, MO 64108-1914
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plo
t Ti
me
Sta
mp
:
File
Lo
ca
tio
n/N
am
e:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
11
/21
/20
18
10
:17
:16
AM
C:\
(1)
Re
vit
Pro
jec
ts\
20
18
\6
24
15
1-
M-1
8_ja
me
s.m
ah
on
ey
@c
lark
en
ers
en
.co
m.r
vt
Mechanical Schedules
M7.01
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTSA - 001 11/21/18 ADDENDUM #001
001A
001A
HYDRONIC UNIT HEATER SCHEDULE
FAN COIL HEATING WATER FLUID PRESSURE ELECTRICAL
AIRFLOW MOTOR MOTOR CAPACITY FLOWRATE DROP REQUIREMENTS MANUFACTURER AND REMARKS
MARK SERVES (CFM) HP RPM (MBH) (GPM) (FT. W.G.) VOLTS/HZ/PH MODEL CONFIGURATION
CUH-1 VESTIBULE 169 37 W 831 13.4 0.75 2.85 115 / 60 / 1 TRANE FORCE FLO VERTICAL SLOPE TOP, 1, 2, 4, 5, 6
V100 FFJB02 OR EQUIVALENT FRONT TOE SPACE INLET,
V142 TOP BAR GRILLE OUTLET
UH-1 MECHANICAL ROOMS 591 1/20 1550 15.0 1.50 0.05 115 / 60 / 1 TRANE MODEL 42-S PROPELLER UNIT HEATER 1, 2, 3, 4, 5, 6
OR EQUIVALENT WITH FAN GUARD
SCHEDULE NOTES AND REMARKS:
1. PROVIDE ELECTRIC THERMOSTAT WITH MANUAL SETPOINT ADJUSTMENT
2. PROVIDE DISCONNECT SWITCH
3. PROVIDE FIN LOUVER
4. PROVIDE DISPOSABLE FILTER
5. COPPER TUBING WITH ALUMINUM FINS
6. RATED FOR 200 PSIG
HYDRONIC SPECIALTIES SCHEDULE
OPERATING MANUFACTURER
MARK: FUNCTION: SERVES: CONDITIONS: CAPACITY: OR EQUIVALENT: MODEL: REMARKS:
AS-1 AIR/DIRT SEPARATOR WITH HEAT RECOVERY 30-90 DEG. F 120 GPM AT 0.8 FT WPD, SPIROTHERM VDT300 1
INTEGRAL AIR VENT SYSTEM 3" FLANGED CONNECTION
CCV-88/89 COIL PIPE KIT AHU-88/89 COOLING COIL 40 - 60 DEG. F 347.4 GPM, 6" PIPE SIZE, DANFOSS ABQM 8
PACKAGE 3 - 60 PSID RANGE OR APPROVED
EQUIVALENT
HCV-88/89 COIL PIPE KIT AHU-88/89 HEATING COIL 140 - 180 DEG. F 165.9 GPM, 4" PIPE SIZE, FURNISHED BY N/A N/A
PACKAGE TWO WAY MODULATING 3 - 60 PSID RANGE TEMPERATURE
CONTROL CONTRACTOR
CV-1/2 THREE WAY HEAT RECOVERY 30 - 90 DEG. F 60 GPM, 3" PIPE SIZE, FURNISHED BY N/A N/A
CONTROL VALVE SYSTEM THREE WAY MODULATING, MAXIMUM 5 FT PD TEMPERATURE
NORMALLY CLOSED CONTROL CONTRACTOR
ET-2 VERTICAL HEAT RECOVERY 30 - 90 DEG. F 23 GALLON TANK CAPACITY, TACO CA-90 3
EXPANSION TANK SYSTEM 23 GALLON ACCEPTANCE VOLUME,
FACTORY CHARGED TO 12 PSIG
GF-1 GLYCOL FEED HEAT RECOVERY 30 - 90 DEG. F 50 GALLON TANK, J.L. WINGERT GL50-E1 7
SYSTEM SYSTEM 40% PROPYLENE GLYCOL DUPLEX 1/3 HP GEAR PUMPS
120V / 1 PH / 60 HZ
PK-1 COIL PIPE KIT UNIT HEATERS 140 - 180 DEG. F SEE DRAWINGS FOR MAX FLOW NEXUS CPP-N2Y 4
PACKAGE VAV BOXES WITH WITH
REHEAT COILS DANFOSS ABQM
OR APPROVED
EQUIVALENT
SRV-1 SAFETY HEAT RECOVERY 30 - 90 DEG. F 50 PSIG SET PRESSURE, WATTS SERIES 174A 6
RELIEF VALVE SYSTEM 1-1/4" INLET AND 1-1/4" OUTLET
T-1/2/3/4/5 STEAM TRAP LPR DRIP LEGS 7 PSIG STEAM, 5 LBS/HR, ARMSTRONG 800 5
6 PSIG DIFFERENTIAL INVERTED BUCKET TRAP
T-6 STEAM TRAP HPR DRIP LEGS 50 PSIG STEAM, 5 LBS/HR, ARMSTRONG 800 5
49 PSIG DIFFERENTIAL INVERTED BUCKET TRAP
T-7 STEAM TRAP HPS TO BOTTLE WASHER 65 PSIG STEAM, 400 LBS/HR, ARMSTRONG 75-A2 8
64 PSIG DIFFERENTIAL FLOAT & THERMOSTATIC TRAP
T-8 STEAM TRAP HPS TO CAGE WASHER 65 PSIG STEAM, 600 LBS/HR, ARMSTRONG 75-A2 8
64 PSIG DIFFERENTIAL FLOAT & THERMOSTATIC TRAP
T-9 STEAM TRAP HPS TO AUTOCLAVE 65 PSIG STEAM, 170 LBS/HR, ARMSTRONG 75-A2 8
64 PSIG DIFFERENTIAL FLOAT & THERMOSTATIC TRAP
T-10 STEAM TRAP HPS TO AUTOCLAVE 65 PSIG STEAM, 170 LBS/HR, ARMSTRONG 75-A2 8
64 PSIG DIFFERENTIAL FLOAT & THERMOSTATIC TRAP
REMARKS:
1. STEEL CONSTRUCTION, RATED FOR 150 PSIG DESIGN PRESSURE, INTERNAL COPPER COALESCING MEDIUM, HIGH CAPACITY FLOAT-ACTUATED AIR VENT, SUPPORT LUGS (AS APPLICABLE).
2. PRESSURE INDEPENDENT MODULATING CONTROL VALVE, CLASS 5 SHUT-OFF , CAST IRON BODY, NON-PLASTIC INTERNAL PARTS, FACTORY MOUNTED FULLY MODULATING ELECTRIC ACTUATOR
SHALL BE COMPATIBLE WITH THE INSTALLED CONTROL SYSTEM. COORDINATE WITH CONTROLS CONTRACTOR.
3. 150 PSIG DESIGN PRESSURE, HEAVY DUTY BUTYL DIAPHRAGM, CARBON STEEL SHELL, CONSTRUCTED TO ASME SECTION VIII, DIVISION 1.
4. SUPPLY SIDE-BRASS BALL VALVE, STAINLESS STEEL MESH FORGED BRASS BODY STRAINER, P&T PLUG AND UNION CONNECTION
RETURN SIDE-UNION COUPLING WITH MANUAL AIR VENT, CONTROL VALVE, PRESSURE INDEPENDENT MODULATING CONTROL VALVE, 2-P&T PLUG, BRASS BALL VALVE
CONTRACTOR TO PROVIDE PIPE KIT WITH CONTROL VALVE, FACTORY MOUNTED FULLY MODULATING ELECTRIC ACTUATOR SHALL BE COMPATIBLE WITH THE INSTALLED CONTROL SYSTEM. COORDINATE WITH CONTROLS
CONTRACTOR. PROVIDE FLEXIBLE HOSE CONNECTIONS.
5. CAST IRON BODY, RATED FOR 250 PSIG AT 450 DEG. F, CONTINUOUS AIR VENTING AT STEAM TEMPERATURE, FREE-FLOATING STAINLESS STEEL MECHANISM, DISCHARGE ORIFICE AT TOP OF TRAP, THERMIC VENT BUCKET.
6. CAST IRON BODY, STAINLESS STEEL STEM, DISC, SEAT, AND DIAPHRAGM, STEEL SPRING, SELF-OPERATED, EXTERNAL PILOT TYPE VALVE. RATED FOR 250 PSIG AT 450 DEG. F. PROVIDE WITH ENGINEERED NOISE SUPPRESSION
CONSISTING OF ORIFICE PLATE ASSEMBLY THAT WILL PRODUCE SPECIFIED DBA RATING.
7. 50-GALLON POLYETHYLENE TANK WITH HINGED COVER, NEMA 4X CONTROL PANEL WITH 8-FT POWER CORD, H-O-A SWITCHES, LOW LEVEL LIGHT, LOW LEVEL SWITCH, FACTORY-PIPED WITH BALL VALVES, Y-STRAINERS,
CHECK VALVES, PRESSURE GAUGES, AND PRESSURE RELIEF VALVES.
8. CAST IRON BODY, RATED FOR 125 PSIG AT 450 DEG. F, THERMOSTATIC AIR VENT.
9. TBD
LOUVER SCHEDULE
MINIMUM
OPERATING AIRFLOW FREE AREA VELOCITY APD CONSTRUCTION SCREEN MFR. OR
MARK: CONDITIONS: SIZE: (CFM): (SQFT): (FPM): (IN. W.G.): MATERIAL: TYPE: FINISH: EQUIVALENT: MODEL: REMARKS:
L-1 AMBIENT 96" x 78" 24,000 27.79 864 0.11 ALUMINUM BIRD SEE NOTE 1 RUSKIN EME520DD 1, 2
L-2 AMBIENT 96" x 78" 24,000 27.79 864 0.11 ALUMINUM BIRD SEE NOTE 1 RUSKIN EME520DD 1, 2
L-3 AMBIENT 48" x 36" 5,000 5.61 891 0.11 ALUMINUM BIRD SEE NOTE 1 RUSKIN EME520DD 1, 2
REMARKS:
1. BAKED ENAMEL FINISH, SUBMIT COLOR CHART FOR COLOR SELECTION BY ARCHITECT
2. 5" DEEP EXTRUDED ALUMINUM FRAME, DOUBLE DRAINABLE BLADES, 44% FREE AREA, BEGINNING POINT OF WATER PENETRATION AT 1250 FPM FREE AREA VELOCITY
PUMP SCHEDULE
WATER TOTAL MOTOR DATA: MANUFACTURER
OPERATING WATER FLUID PUMP FLOW HEAD % MODEL NO. SIZE SUCTION
MARK: FUNCTION: TEMPERATURE: TYPE: TYPE: (GPM): (FT): EFF: RPM: HP: VOLTS: PH: HZ: OR EQUIVALENT S x D x IMP DIFFUSER REMARKS
HRP-1 HEAT RECOVERY PUMP 60-90 DEG. F B 1 120 60 76.2 3,500 3 460 3 60 BELL & GOSSETT e-1535 1.5AAC 2 x 1.5 x 4.38 DB-3 1,2,3,4,5,6
ECWP-1 EMERGENCY CHILLED WATER PUMP 40-60 DEG. F C 1 695 55 82.4 1,754 15 460 3 60 BELL & GOSSETT e-1510 4BD 5 x 4 x 8.75 FF-3 1,2,3,4,5,6
HCP-1/2 HOT WATER COIL HC-1/2 CIRCULATION PUMP 140-180 DEG. F A 2 165.9 35 70.3 1,721 3 460 3 60 BELL & GOSSETT e-80 3x3x7C 3 x 3 x 6.5 N/A 1,2
CRP-1 STEAM CONDENSATE RETURN PUMP 200 DEG. F D 3 6 46.2 - 3,500 1/2 120 1 60 FABTEK AERO 12250505C5AB3S OR APPROV. EQUIV. N/A N/A 7
CRP-2 STEAM CONDENSATE RETURN PUMP 200 DEG. F D 3 6 46.2 - 3,500 1/2 120 1 60 FABTEK AERO 12250505C5AB3S OR APPROV. EQUIV. N/A N/A 7
FLUID TYPE:
A. HEATING HOT WATER - NO GLYCOL
B. HEAT RECOVERY WATER - 40% PROPYLENE GLYCOL
C. CHILLED WATER
D. STEAM CONDENSATE
PUMP TYPE:
1. CLOSE COUPLED, BASE MOUNTED, END SUCTION PUMP.
2. SMALL CLOSE-COUPLED IN-LINE CENTRIFUGAL PUMP.
3. ELECTRIC SIMPLEX CONDENSATE PUMP
SUCTION DIFFUSER:
D-1. DA-3X, 3.13FT WPD, Cv=68, 175PSI WORKING PRESSURE, CAST IRON BODY, STEEL INLET VANES AND ORIFICE CYLINDER
D-2. DA-3X, 2.70FT WPD, Cv=68, 175PSI WORKING PRESSURE, CAST IRON BODY, STEEL INLET VANES AND ORIFICE CYLINDER
REMARKS
1. PREMIUM EFFICIENCY, INVERTER DUTY MOTOR
2. OPEN DRIP PROOF MOTOR
3. MECHANICAL SEALS
4. BRONZE FITTED WITH BRONZE WEAR RINGS
5. PROVIDE T.B. WOODS DURA-FLEX COUPLING AND OSHA-COMPLIANT COUPLING GUARD
6. REFER TO VFD SCHEDULE FOR VFD MOUNTING AND PERFORMANCE INFORMATION.
7. SEE SPECIFICATION SECTION 23 22 14 FOR ADDITIONAL REQUIREMENTS.
DAMPER SCHEDULE
OPERATING MOUNTING LEAKAGE BLADE MANUF. OR
MARK: FUNCTION: CONDITIONS: SIZE: POSITION: BLADE STYLE: FRAME CONSTRUCTION: BLADE CONSTRUCTION @ 1" WG PD: SEALS: EDGE: BEARINGS: ACTUATOR: EQUIVALENT: MODEL: REMARKS:
FSD-1 FIRE/SMOKE DAMPER SEE PLANS SQUARE, VERTICAL/ PARALLEL 5" x 16-GA GALVANIZED HAT-SHAPED CHANNEL 6" WIDE, 14-GA GALVANIZED STEEL, AIRFOIL SHAPE 4 CFM / S.F. SILICONE SS SS 3 RUSKIN FSD-60 1,2,9,10,11,12,13
SEE PLANS HORIZONTAL
FSD-2 FIRE/SMOKE DAMPER SEE PLANS ROUND, VERTICAL/ PARALLEL 20-GA GALVANIZED STEEL TWO PIECE 14-GA GALVANIZED STEEL 4 CFM / S.F. SILICONE SS SS 3 RUSKIN FSDR-25 1,2,9,10,11,12,13
SEE PLANS HORIZONTAL
MD-1, MOTORIZED DAMPER SEE PLANS ROUND & SQUARE, VERTICAL SINGLE BLADE 20-GA GALVANIZED STEEL 20-GA GALVANIZED STEEL - - - SELF- 2 MAT ROUND: EB-250 2 - 8
DCP-1 SEE PLANS LUBRICATING SQUARE: EB-200
FD-1 FIRE DAMPER SEE PLANS SQUARE, VERTICAL/ PARALLEL 5" x 16-GA GALVANIZED HAT-SHAPED CHANNEL 6" WIDE, 14-GA GALVANIZED STEEL, AIRFOIL SHAPE 4 CFM / S.F. SILICONE SS SS - RUSKIN DFD60 1,2,11, 12, 13
SEE PLANS HORIZONTAL
MD-2 MOTORIZED DAMPER SUPPLY AIR 96"W x 24"H VERTICAL OPPOSED 5" x 1" 6063T5 EXTRUDED ALUMINUM HAT CHANNEL 6" WIDE, 6063T5 HEAVY GAUGE EXTRUDED ALUMINUM, AIRFOIL SHAPE 3 CFM / S.F. NEOPRENE SS SYNTHETIC 1 RUSKIN CD-60 1
MD-3 MOTORIZED DAMPER EXHAUST AIR 96"W x 24"H VERTICAL OPPOSED 5" x 1" 6063T5 EXTRUDED ALUMINUM HAT CHANNEL 6" WIDE, 6063T5 HEAVY GAUGE EXTRUDED ALUMINUM, AIRFOIL SHAPE 3 CFM / S.F. NEOPRENE SS SYNTHETIC 1 RUSKIN CD-60 1
MD-4 MOTORIZED DAMPER EXHAUST AIR 96"W x 24"H VERTICAL OPPOSED 5" x 1" 6063T5 EXTRUDED ALUMINUM HAT CHANNEL 6" WIDE, 6063T5 HEAVY GAUGE EXTRUDED ALUMINUM, AIRFOIL SHAPE 3 CFM / S.F. NEOPRENE SS SYNTHETIC 1 RUSKIN CD-60 1
MD-5 MOTORIZED DAMPER OUTSIDE AIR 48"W x 36"H VERTICAL OPPOSED 5" x 1" 6063T5 EXTRUDED ALUMINUM HAT CHANNEL 6" WIDE, 6063T5 HEAVY GAUGE EXTRUDED ALUMINUM, AIRFOIL SHAPE 3 CFM / S.F. NEOPRENE SS SYNTHETIC 1 RUSKIN CD-60 1
MD-6 MOTORIZED DAMPER SUPPLY AIR 96"W x 24"H VERTICAL OPPOSED 5" x 1" 6063T5 EXTRUDED ALUMINUM HAT CHANNEL 6" WIDE, 6063T5 HEAVY GAUGE EXTRUDED ALUMINUM, AIRFOIL SHAPE 3 CFM / S.F. NEOPRENE SS SYNTHETIC 1 RUSKIN CD-60 1
ACTUATOR
1. FACTORY-PROVIDED MODULATING ELECTRIC ACTUATOR WITH END SWITCH.
2. MAT MODEL EB-UDD UNIVERSAL DAMPER DRIVE OR EQUIVALENT, FACTORY MOUNTED TO DAMPER.
3. 120-VOLT, 2-POSITION, 350 DEG. F UL555S RATED, FACTORY-PROVIDED, NORMALLY CLOSED. PROVIDE WITH FACTORY HEAT DETECTION DEVICE SYSTEM THAT ACTIVATES AT 165 DEG. F, RUSKIN EFL OR EQUIVALENT,
WITH AUTOMATIC RESET AFTER TEST, SMOKE DETECTION OR POWER FAILURE. AFTER EXPOSURE TO ELEVATED TEMPERATURE, THE DAMPER SHALL BE RESET MANUALLY.
REMARKS
1. SUBMIT AMCA-CERTIFIED PERFORMANCE.
2. FIELD VERIFY DUCT SIZE PRIOR TO ORDERING AS ACTUAL DUCT SIZE MAY VARY DUE TO FABRICATION.
3. PROVIDE MAT MODEL EB-SP8 OR EQUIVALENT EIGHT CONNECTOR WALL PLATE AS SHOWN ON PLAN, DENOTED BY DCP-1, WITH COVER PLATE. COVER AND PLATE TO MATCH ADJACENT WALL COLOR, RE: ARCH.
4. ROUTE PLENUM-RATED LOW VOLTAGE WIRING FROM DAMPER TO DAMPER CONTROL PANEL, NOT TO EXCEED 75 FEET OF TOTAL WIRE LENGTH.
5. PROVIDE MAT MODEL EB-RC OR EQUIVALENT REMOTE CONTROL.
6. PROVIDE BALANCING CONTROLLER TO OWNER AFTER INSTALLATION IS COMPLETE.
7. CONTRACTOR SHALL LABEL ALL DAMPERS AT THE DAMPER CONTROL PANEL. CONTRACTOR SHALL MARK DAMPER SHAFT IN FIELD TO INDICATE DAMPER POSITION.
8. PROVIDE STAINLESS STEEL DAMPER AND COMPONENTS FOR MOIST AIRSTREAM WHERE NOTED ON PLANS.
9. CONTROLS SHALL INTERFACE WITH THE FIRE ALARM SYSTEM PROVIDED BY THE DIV. 26 CONTRACTOR.
10. SMOKE DETECTOR PROVIDED BY FIRE ALARM CONTRACTOR. MECHANICAL CONTRACTOR SHALL COORDINATE INSTALLATION OF FIRE DETECTOR WITH FIRE ALARM CONTRACTOR.
11. DAMPER TO MEET THE REQUIREMENTS OF UL555 AND UL555S. DAMPER SHALL BE DYNAMIC.
12. PROVIDE RUSKIN SP100 SWITCH PACKAGE (OR EQUIVALENT) TO REMOTELY INDICATE DAMPER BLADE POSITION.
13. CONTRACTOR SHALL PROPERLY LABEL ALL COMBINATION FIRE/SMOKE AND FIRE DAMPERS PER CODE REQUIREMENTS.
EXHAUST FAN SCHEDULE
ELECTRICAL DATA MANUFACTURER
MARK: SERVES: TYPE: CFM: WEIGHT (LB): S.P. IN. WG.: DRIVE: RPM: HP: V: PH: HZ: AND MODEL NUMBER: REMARKS:
EF-60 MECHANICAL SIDEWALL 4,000 81 0.5 BELT 1,199 3/4 115 1 60 GREENHECK MODEL SBE-3H24-7 PROVIDE WALL HOUSING WITH BACKDRAFT DAMPER AND WEATHERHOOD
PENTHOUSE BELT DRIVE OR EQUIVALENT MOTORS SHALL MEET NEMA MG 1 MINIMUM FULL LOAD EFFICIENCIES.
DISCONNECT/MOTOR STARTER TO BE PROVIDED BY DIV. 26 CONTRACTOR
INTERLOCK FAN WITH THERMOSTAT IN SPACE, SET TO MAINTAIN 85F
EF-61 BSC COATED STEEL 1,200 100 3.75 BELT 1,745 2 208 3 60 LABCONCO MODEL 7071900 COATED STEEL CONSTRUCTION, DISCONNECT AND STARTER PROVIDED BY DIV 26.
EXHAUST FAN BELT DRIVE OR APPROVED EQUIVALENT DRY POWDER EPOXY-COATED BASE AND WEATHER COVER.
HOUSING DRAIN CONNECTION FOR WASHDOWN SYSTEM.
PROVIDE FAN SHEAVE TO ACHIEVE LISTED AIRFLOW.
PROVIDE AIR-TIGHT DAMPER MODEL 37768 AT HOOD OUTLET.
PROVIDE BACKDRAFT DAMPER MODEL 3858800 DOWNSTREAM OF AIR-TIGHT DAMPER.
PROVIDE 12" ROOF CURB, UPBLAST DISCHARGE, DRAIN IN BASE OF FAN
EF-62 CAGE WASH UTILITY SET 6,200 361 1.5 BELT 1,076 3 480 3 60 GREENHECK MODEL CSW-24-AF PROVIDE WITH 18" ROOF CURB, MOTORIZED DAMPER SEE CONTROL SEQUENCE
EXHAUST CENTRIFUGAL OR EQUIVALENT MOTORS SHALL MEET NEMA MG 1 MINIMUM FULL LOAD EFFICIENCIES.
DISCONNECT/MOTOR STARTER TO BE PROVIDED BY DIV. 26 CONTRACTOR
UPBLAST DISCHARGE, PROVIDE 10' EXHAUST STACK AND DRAIN IN BOTTOM OF FAN.
BAKED ENAMEL FINISH, COLOR BY ARCHITECT.
FAN SHALL BE ALL ALUMINUM CONSTRUCTION, RATED FOR MOIST AIR CONDITIONS.
Kansas City, Missouri
2020 Baltimore, Suite 300
Kansas City, MO 64108-1914
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plo
t Ti
me
Sta
mp
:
File
Lo
ca
tio
n/N
am
e:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
11
/21
/20
18
10
:17
:20
AM
C:\
(1)
Re
vit
Pro
jec
ts\
20
18
\6
24
15
1-
M-1
8_ja
me
s.m
ah
on
ey
@c
lark
en
ers
en
.co
m.r
vt
Mechanical Schedules
M7.02
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTSA - 001 11/21/18 ADDENDUM #001
001A
AIR TERMINAL UNIT SCHEDULE
FLUID PD
INLET MAXIMUM MINIMUM COIL UNIT WATER PRESSURE
SERVES SIZE AIRFLOW AIRFLOW AIRFLOW AIR PD CAPACITY FLOWRATE EWT LWT EAT LAT COIL DROP MANUFACTURER
MARK: ROOMS: (INCHES): (CFM): (CFM): (CFM): (IN. W.G.): (MBH): (GPM): (ºF): (ºF): (ºF): (ºF): ROWS: (FT. W.G.) OR EQUIVALENT: REMARKS:
VB-88-101 SOUTHEAST CORRIDOR 7 375 375 - - - - - - - - - - TITUS DESV 1,2,3,4,5,6
VBR-88-102 ANTE/GOWNING 6 200 200 200 0.02 6.6 0.5 180 150 55 85 1 0.13 TITUS DESV 1,2,3,4,5,7
VBR-88-103 OFFICE 5 125 125 125 0.01 4.7 0.3 180 148 55 90 1 0.07 TITUS DESV 1,2,3,4,5
VBR-88-104FRAGMENTORS
7 450 225 225 0.06 8.2 0.5 180 146 55 89 1 0.19 TITUS DESV 1,2,3,4,5,6
VB-88-104 7 350 125 - - - - - - - - - - TITUS DESV 1,2,3,4,5
VBR-88-105BEHAVIORAL
7 450 215 215 0.06 8.1 0.5 180 147 55 90 1 0.19 TITUS DESV 1,2,3,4,5,6
VB-88-105 8 550 315 - - - - - - - - - - TITUS DESV 1,2,3,4,5
VBR-88-106ENVIRONMENTAL
7 400 345 345 0.05 10.8 0.8 180 151 55 84 1 0.33 TITUS DESV 1,2,3,4,5,6
VB-88-106 7 300 245 - - - - - - - - - - TITUS DESV 1,2,3,4,5
VBR-88-107 STORAGE 6 300 300 300 0.05 6.0 0.3 180 139 55 73 1 0 TITUS DESV 1,2,3,4,5
VBR-88-108VHP
6 150 150 150 0.01 7.0 1.0 180 166 55 98 1 0.43 TITUS DESV 1,2,3,4,5,9
VB-88-108 4 250 250 - - - - - - - - - - TITUS DESV 1,2,3,4,5,9
VB-88-109 NORTHEAST CORRIDOR 8 600 600 - - - - - - - - - - TITUS DESV 1,2,3,4,5
VBR-88-110 NORTH CORRIDOR 6 300 300 300 0.03 7.4 0.5 180 150 55 82 1 0.14 TITUS DESV 1,2,3,4,5,7
VBR-88-111 NORTH AIRLOCK 6 150 50 50 0.04 4.6 0.5 180 161 55 2 TITUS DESV 1,2,3,4,5,7
VBR-88-112 SOUTH CORRIDOR 8 500 500 500 0.07 9.3 0.4 180 132 55 72 1 0 TITUS DESV 1,2,3,4,5
VBR-88-113BSL II
9 790 475 790 0.08 20.5 2.0 180 159 55 79 1 0.4 TITUS DESV 1,2,3,4,5,6,7,8
VB-88-113 10 940 625 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-114PROCEDURE
7 420 285 285 0.05 10.7 1.0 180 158 55 90 1 0.56 TITUS DESV 1,2,3,4,5,7
VB-88-114 7 420 285 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-115DIRTY
7 440 250 440 0.06 12.6 1.0 180 154 55 81 1 0.56 TITUS DESV 1,2,3,4,5,7
VB-88-115 8 640 450 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-116 CLEAN 6 200 100 100 0.02 5.1 0.5 180 159 55 102 1 0.14 TITUS DESV 1,2,3,4,5,7
VBR-88-117HUMANIZED BSL II
12 1070 415 745 0.12 24.4 2.5 180 160 55 85 1 0.83 TITUS DESV 1,2,3,4,5,6,7,8
VB-88-117 14 1320 665 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-118SURGERY
6 215 215 215 0.03 7.8 0.8 180 159 55 88 1 0.25 TITUS DESV 1,2,3,4,5,7
VB-88-118 6 115 115 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-119PROCEDURE
6 215 140 140 0.03 6.0 0.5 180 156 55 94 1 0.14 TITUS DESV 1,2,3,4,5,6,7
VB-88-119 6 215 140 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-120MENS LOCKER/SHOWER
6 350 350 350 0.06 9.9 1.0 180 160 55 81 1 0.43 TITUS DESV 1,2,3,4,5 .
VB-88-120 6 550 550 - - - - - - - - - - TITUS DESV 1,2,3,4,5 .
VBR-88-121WOMENS LOCKER/SHOWER
7 400 400 400 0.05 12.2 1.0 180 155 55 83 1 0.56 TITUS DESV 1,2,3,4,5 .
VB-88-121 6 600 600 - - - - - - - - - - TITUS DESV 1,2,3,4,5 .
VB-88-122 STORAGE 6 50 50 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-123STEP DOWN
12 1,070 715 1,070 0.12 28.1 2.5 180 157 55 79 1 0.84 TITUS DESV 1,2,3,4,5,7,8
VB-88-123 12 1,220 865 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-124 CLEAN CAGEWASH 40 3,300 3,300 3,300 0.15 78.2 6.0 180 152 55 78 1 4.89 TITUS DESV 1,2,3,4,5,7
VBR-88-125FEEDING AND BEDDING
6 270 270 270 0.04 8.5 0.8 180 157 55 84 1 0.25 TITUS DESV 1,2,3,4,5,6,7
VB-88-125 6 270 270 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-126 AUTOCLAVE VESTIBULE 9 300 300 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-127SOUTHWEST CORRIDOR
6 300 120 120 0.05 6.3 1.0 180 167 55 103 1 0.43 TITUS DESV 1,2,3,4,5,7
VB-88-127 9 675 675 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-128CLEAN CAGE STORAGE
8 645 645 645 0.11 15.6 1.5 180 159 55 77 1 1.19 TITUS DESV 1,2,3,4,5,7
VB-88-128 8 445 445 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-129 PROCEDURE 12 1,100 1,100 1,100 0.15 28.5 3.0 180 159 55 79 1 1.19 TITUS DESV 1,2,3,4,5,6,7
VBR-88-130ANIMAL HOLDING (BREEDING)
10 980 655 980 0.11 23.0 2.5 180 161 55 77 1 0.61 TITUS DESV 1,2,3,4,5,6,7,8
VB-88-130 10 880 555 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-131ANIMAL HOLDING (EXPERIMENTAL)
9 820 545 820 0.08 20.7 2.0 180 159 55 78 1 0.4 TITUS DESV 1,2,3,4,5,6,7,8
VB-88-131 9 720 445 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-132PROCEDURE
7 390 200 200 0.05 9.1 1.0 180 161 55 97 1 0.56 TITUS DESV 1,2,3,4,5,6,7
VB-88-132 7 390 200 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-133ANIMAL HOLDING (BREEDING)
10 1,000 670 1,000 0.12 23.2 2.5 180 161 55 76 1 0.61 TITUS DESV 1,2,3,4,5,6,7,8
VB-88-133 10 900 570 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-134ANIMAL HOLDING (BREEDING)
10 895 595 895 0.10 21.3 2.0 180 158 55 77 1 0.4 TITUS DESV 1,2,3,4,5,6,7,8
VB-88-134 10 795 495 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-135PROCEDURE
7 390 200 200 0.05 9.1 1.0 180 161 55 97 1 0.56 TITUS DESV 1,2,3,4,5,6,7
VB-88-135 7 390 200 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-136ANIMAL HOLDING (BREEDING)
10 1,000 670 1,000 0.12 23.2 2.5 180 161 55 76 1 0.61 TITUS DESV 1,2,3,4,5,6,7,8
VB-88-136 10 900 570 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-137ANIMAL HOLDING (BREEDING)
10 895 595 895 0.10 21.3 2.0 180 158 55 77 1 0.4 TITUS DESV 1,2,3,4,5,6,7,8
VB-88-137 10 795 495 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-138PROCEDURE
7 390 200 200 0.05 9.1 1.0 180 161 55 97 1 0.56 TITUS DESV 1,2,3,4,5,6,7
VB-88-138 7 390 200 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-139PROCEDURE
7 390 200 200 0.05 9.1 1.0 180 161 55 97 1 0.56 TITUS DESV 1,2,3,4,5,6,7
VB-88-139 7 390 200 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-140ANIMAL HOLDING (BREEDING)
10 1,000 670 1,000 0.12 23.2 2.5 180 161 55 76 1 0.61 TITUS DESV 1,2,3,4,5,6,7,8
VB-88-140 10 900 570 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-141ANIMAL HOLDING (EXPERIMENTAL)
10 895 595 895 0.10 21.3 2.0 180 158 55 77 1 0.4 TITUS DESV 1,2,3,4,5,6,7
VB-88-141 10 795 495 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-142PROCEDURE
7 390 200 200 0.05 9.1 1.0 180 161 55 97 1 0.56 TITUS DESV 1,2,3,4,5,6,7
VB-88-142 7 390 200 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-143ANTE RM
7 500 500 500 0.07 13.8 1.3 180 157 55 80 1 0.85 TITUS DESV 1,2,3,4,5,6,7,8
VB-88-143 7 450 450 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-144GNOTOBIOTIC/GERM FREE
9 665 665 665 0.06 18.7 1.8 180 158 55 81 1 0.31 TITUS DESV 1,2,3,4,5,6,7,8
VB-88-144 8 565 565 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-145CORRIDOR
7 500 500 500 0.07 13.8 1.3 180 157 55 80 1 0.85 TITUS DESV 1,2,3,4,5,7
VB-88-145 9 875 875 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-146PROCEDURE (EUTHENASIA)
7 240 240 240 0.02 8.4 0.5 180 146 55 87 1 0.2 TITUS DESV 1,2,3,4,5,6,7
VB-88-146 7 340 340 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VB-88-147 UNISEX/CUST. 6 200 200 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VB-88-148 CYLINDER 6 100 100 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-149DIRTY CAGEWASH
40 3,500 2,000 2,000 0.16 66.0 5.0 180 153 55 85 1 3.42 TITUS DESV 1,2,3,4,5,6,7
VB-88-149 16 2,100 600 - - - - - - - - - - TITUS DESV 1,2,3,4,5,7
VBR-88-150TELECOM
8 500 0 - - - - - - - - - - TITUS DESV 1,2,3,4,5
VB-88-150 8 500 - - - - - - - - - - - TITUS DESV 1,2,3,4,5
VBR-88-251 UPPER LEVEL DOGHOUSE 9 750 750 750 0.08 20.5 2.0 180 159 55 79 1 0.4 TITUS DESV 1,2,3,4,5,7,8
VBR-88-252 ELECTRICAL 10 1,000 0 - - - - - - - - - - TITUS DESV 1,2,3,4,5
VBR-88-153 OPEN OFFICE 7 400 400 400 0.05 7.3 0.3 180 129 55 72 1 0.1 TITUS DESV 1,2,3,4,5,7
VBR-88-154IRRADIATION
6 125 125 125 0.01 4.7 0.3 180 148 55 90 1 0.07 TITUS DESV 1,2,3,4,5
VB-88-154 6 225 225 - - - - - - - - - - TITUS DESV 1,2,3,4,5
VBR-88-155EXIST.
8 500 175 175 0.07 8.8 1.3 180 166 55 102 1 0.84 TITUS DESV 1,2,3,4,5
VB-88-155 6 500 175 - - - - - - - - - - TITUS DESV 1,2,3,4,5
VBR-88-156 CORRIDOR 6 650 650 650 0.06 18.7 1.8 180 158 55 81 1 0.31 TITUS DESV 1,2,3,4,5,7
SCHEDULE NOTES AND REMARKS:
1. ALL AIR TERMINAL UNITS SHALL BE PROVIDED WITH TITUS "FIBRE-FREE" LINER OR EQUIVALENT.
2. ALL AIR TERMINAL UNITS SHALL BE PROVIDED WITH A HINGED, GASKETED ACCESS DOOR UPSTREAM OF AIRFLOW STATION FOR CLEANING PURPOSES.
3. UNIT AIR PRESSURE DROPS LISTED ARE AT MAXIMUM AIRFLOW.
4. CROSS-TYPE FLOW SENSING GRID AND DAMPER SHALL BE PROVIDED BY AIR TERMINAL UNIT MANUFACTURER.
5. MINIMUM BOX INLET SIZE SHALL BE 6".
6. LOCATE THERMOSTAT FOR THIS BOX IN EXHAUST DUCTWORK PRIOR TO VOLUME BOX.
7. BOX ORIENTATED IN THE VERTICAL.
8. BOX IS IN A ZONE WITH AIRCUITY AIRFLOW CONTROLS.
9. INTERLOCK OPERATION OF BOXES TO TOGGLE SWITCH IN SPACE. BOXES SHALL GO TO ZERO WHEN SWITCH IS FLIPPED.
DIFFUSER, REGISTER AND GRILLE SCHEDULE
MAX. P.D. MAX. MAXIMUM MANUFACTURER AND
MARK: TYPE: (IN. WG.): N.C.: CFM: MODEL NUMBER: REMARKS:
D-1 HIGH MIXING 0.1 25 SEE PLANS TITUS MODEL TDX-AA 24" X 24" FACE SIZE, ALL ALUMINUM CONSTRUCTION, WHITE FINISH
DIFFUSER FOR CFM OR EQUIVALENT PROVIDE APPROPRIATE BORDER FOR CONSTRUCTION, DIFFUSER BACKPAN SIZE
(FOR ANIMAL ROOMS) AND NECK SIZE TO BE AS FOLLOWS: 9x9 FOR 6" NECK, 12x12 FOR 8" NECK, 15x15 FOR 10" NECK,
AND 18x18 FOR 12" NECK
D-2 SQUARE CEILING 0.15 25 SEE PLANS TITUS MODEL "OMNI-AA" OR 24" X 24" FACE SIZE, ALL ALUMINUM CONSTRUCTION, WHITE FINISH
DIFFUSER - ARCH. FOR CFM EQUIVALENT PROVIDE APPROPRIATE BORDER FOR CONSTRUCTION
TYPE AND NECK SIZE
D-3 SQUARE CEILING 0.15 25 SEE PLANS TITUS MODEL "OMNI-AA" OR 12" X 12" FACE SIZE, ALL ALUMINUM CONSTRUCTION, WHITE FINISH
DIFFUSER - ARCH. FOR CFM EQUIVALENT PROVIDE APPROPRIATE BORDER FOR CONSTRUCTION
TYPE AND NECK SIZE
G-1 FILTER GRILLE -0.1 25 SEE PLANS TITUS MODEL 350FLF1 ALUMINUM CONSTRUCTION, WHITE FINISH, 3/4" BLADES, FRONT BLADES PARALLEL TO LONG
FOR SIZE OR EQUIVALENT DIMENSION, 1" WASHABLE FILTER
G-2 EGGCRATE RETURN -0.1 25 SEE PLANS TITUS MODEL 50F OR 24"x24" FACE, ALUMINUM CONSTRUCTION, 1/2" CORE SIZE, WHITE FINISH.
GRILLE FOR CFM EQUIVALENT PROVIDE APPROPRIATE BORDER FOR CONSTRUCTION.
AND NECK SIZE
G-3 EGGCRATE RETURN -0.1 25 SEE PLANS TITUS MODEL 50F OR 12"x12" FACE, ALUMINUM CONSTRUCTION, 1/2" CORE SIZE, WHITE FINISH.
GRILLE FOR SIZE EQUIVALENT PROVIDE APPROPRIATE BORDER FOR CONSTRUCTION.
G-4 GRILLE -0.1 25 SEE PLANS TITUS MODEL 350RL OR STEEL CONSTRUCTION, WHITE FINISH, 3/4" BLADES, FRONT BLADES PARALLEL TO LONG
FOR SIZE EQUIVALENT DIMENSION
R-1 REGISTER 0.15 25 SEE PLANS TITUS MODEL 301RL STEEL CONSTRUCTION. WHITE FINISH, 3/4" BLADES, DOUBLE DEFLECTION,
FOR CFM AND OR EQUIVALENT FRONT BLADES PARALLEL TO LONG DIMENSION
NECK SIZE
VARIABLE FREQUENCY DRIVE SCHEDULE
MARK: SERVES: ELECTRICAL REQUIREMENTS: CAPACITY: MANUFACTURER REMARKS:
VFD SF-1 AHU-88 SUPPLY FAN 88 480 V / 3 PH / 60 HZ 60 HP MOTOR TOSHIBA Q9 HVAC 1, 2, 4
VFD SF-2 AHU-89 SUPPLY FAN 89 480 V / 3 PH / 60 HZ 60 HP MOTOR TOSHIBA Q9 HVAC 1, 2, 4
VFD EF-1 HRH-1 EXHAUST FAN 1A-1D 480 V / 3 PH / 60 HZ 30 HP MOTOR TOSHIBA Q9 HVAC 1, 2, 4
VFD EF-2 HRH-1 EXHAUST FAN 2A-2D 480 V / 3 PH / 60 HZ 30 HP MOTOR TOSHIBA Q9 HVAC 1, 2, 4
VFD ECWP-1 ECWP-1 480 V / 3 PH / 60 HZ 15 HP MOTOR TOSHIBA Q9 HVAC 1, 2, 3, 4
REMARKS:
1. LISTED CAPACITY IS THE NOMINAL MOTOR SIZE FOR EACH EQUIPMENT ITEM. VFD CAPACITY SHALL BE APPROPRIATELY
MATCHED TO THE ACTUAL MOTOR, INCLUDING CAPACITY BASED ON 1.15 SERVICE FACTOR.
2. PROVIDE SHAFT GROUNDING RING/SYSTEM ON MOTORS WITH VFD'S. SEE SPECIFICATION SECTION 23 05 13 FOR MORE INFORMATION.
3. VFD TO BE UNISTRUT MOUNTED NEAR PUMP.
4. DIV 23 TO PROVIDE VFD, REFERENCE SPECIFICATION SECTION 26 29 23 FOR MORE INFORMATION.
5. VFD MOUNTED IN PENTHOUSE,
FAN COIL UNIT SCHEDULE
FAN EXT. STATIC WATER FLUID PRESSURE WATER FLUID PRESSURE
AIRFLOW MOTOR UNIT PRESSURE COOLING COIL TOTAL COIL COOLING SENSIBLE COIL COOLING FLOWRATE DROP HEATING COIL HEATING COIL HEATING COIL FLOWRATE DROP MANUFACTURER AND
MARK SERVES (CFM) HP VOLTAGE (in WC) EAT DB/WB (DEG F) CAPACITY (MBH) CAPACITY (MBH) (GPM) (FT. W.G.) CAPACITY (MBH) EAT DB (DEG F) LAT DB (DEG F) (GPM) (FT. W.G.) MODEL CONFIGURATION REMARKS
FCU-1 EXISTING 933 145 W 208/1/60 0.00 80.0/67.0 30.0 21.0 5.84 9.57 - - - - - TRANE FCDX1002 HORIZONTAL CABINET 1, 2, 3, 4, 5, 6, 7
ELEC OR EQUIVALENT BACK STAMPED LOUVER INLET
FRONT BAR GRILLE OUTLET
FCU-2 EXISTING 510 79 W 208/1/60 0.00 80.0/67.0 20.0 13.2 4.54 9.31 16.8 60.0 94.3 1.7 0.8 TRANE FCDX0602 HORIZONTAL CABINET 1, 2, 3, 4, 5, 6, 7
ELEC OR EQUIVALENT BACK STAMPED LOUVER INLET
FRONT BAR GRILLE OUTLET
SCHEDULE NOTES AND REMARKS:
1. PROVIDE 2" PLEATED DISPOSABLE FILTER
2. REAR RETURN
3. COOLING COIL PERFORMANCE BASED ON 44 DEG. F EWT. HEATING COIL PERFORMANCE BASED ON 180 DEG. EWT.
4. COPPER TUBING WITH ALUMINUM FINS
5. RATED AT 200 PSI
6. PROVIDE WITH DRAIN AND VENT CONNECTIONS ON COIL
7. PROVIDE WITH DISCONNECT SWITCH. THERMOSTAT PROVIDED BY TEMPERATURE CONTOLS CONTRACTOR.
Kansas City, Missouri
2020 Baltimore, Suite 300
Kansas City, MO 64108-1914
816 474.8237 Fax 816 474.8233
#SHEET HISTORY:
?
? - #
Plo
t Ti
me
Sta
mp
:
File
Lo
ca
tio
n/N
am
e:
ISSUED
www.scienceandresearchdesign.com
Science & Research Design Group
11
/21
/20
18
10
:17
:26
AM
C:\
(1)
Re
vit
Pro
jec
ts\
20
18
\6
24
15
1-
M-1
8_ja
me
s.m
ah
on
ey
@c
lark
en
ers
en
.co
m.r
vt
Mechanical Schedules
M7.03
TCEP No.: 624-151-18
University of MissouriMedical ScienceBuilding - ResearchVivarium Upgrade &Maintenance
NOVEMBER 07, 2018
CONTRACT DOCUMENTS
MU Project # CP180641
11/07/2018 CONTRACT DOCUMENTSA - 001 11/21/18 ADDENDUM #001
001A
001A
001A