9RU 864f LC / 432f SC Splice and Patch Panel
Installation Guide
9RU Splice and Patch Panel
Series
2 © AFL Hyperscale. All rights reservedSeries
Safety Precautions
Laser Precautions
Warning: The laser light used to transmit information over optical fiber cables can cause severe eye damage. Because this light is invisible, it will not cause the iris of the eye to contract involuntarily as when
viewing a bright visible light, and no pain is felt as the retina is burned.
Never look into the end of a fiber or connector which may have a laser coupled to it. Should accidental eye exposure to laser light be suspected, arrange for an eye examination immediately.
General Precautions
Personnel must be thoroughly familiarized with all applicable Occupational Health and Safety (OH&S) regulations, local regulations, and your company safety practices and policies.
Warning: To reduce the chance of accidental injury:
Before work begins, all personnel must be thoroughly familiar with the operation of all equipment and procedures to be used during the installation.
Before use, all equipment, especially safety gear, must be inspected and tested for proper operation. Replace and repair as necessary.
Before installing or adjusting this product, please read these instructions carefully. Please keep this guide for future reference.
U-Series 9RU 864f LC / 432f SC Splice and Patch Panel
3
U-Series 9RU Splice and Patch Panel
© AFL Hyperscale. All rights reservedSeries
Component Overview
01
02
03
04
05
4 © AFL Hyperscale. All rights reservedSeries
In the Box
Item Number
ItemLC
QtySC
Qty
01U-Series 9RU Splice
and Patch Panel1 1
02U-Series Patch Adapter Plate
36 36
03 Front Door 1 1
04 Cable Clamp 1 1
05Pivoting Splice
Tray Stack1 1
06 M6 Cage Nuts + Screws 8 8
0712f Ribbon Splice
Protector72 36
08 Ø20mm Conduit 1 1
09 Ribbon Pigtail 36 36
(01) 9RU Splice andPatch Panel
(04) Cable Clamp
Cross-Head Screwdriver
(07) 12f Ribbon Splice Protector
Pliers
(02) U-Series Patch Adapter Plate
(05) Pivot Splice Tray Stack
Socket Wrench
(08) Ø20mm Conduit
(03) Front Door
(06) M6 Cage Nuts + Screws
(09) Ribbon Pigtail
What You Will Need Related Products
250 μm WTC with SWR®
MicroCable Assemblies
(2mm Tails)
U-Series 3456f & 6912f
Breakout Box
One-Click® Cleaner
D-LC, Duplex LC
5
U-Series 9RU Splice and Patch Panel
© AFL Hyperscale. All rights reservedSeries
Installation Procedure
Partially tighten the cage nut screws in the positions shown (both left- and right-hand sides) using a cross-head screwdriver.
4Insert the cage nuts, in the positions shown, on both the left and right hand sides of the rack.
3
Remove the panel from pallet.2Take off the crate’s top and side panels. Remove the accessory bag and the front door assembly.
1
8U
2U
2U
6 © AFL Hyperscale. All rights reservedSeries
Open the rear pivot panel and remove the knockout and raceway cover.
8Attach the door to panel.7
Insert and tighten the remaining cage nut screws.6Place the panel in position and tighten the cage nut screws.
5
Installation Procedure
Knock Out
Raceway Cover
7
U-Series 9RU Splice and Patch Panel
© AFL Hyperscale. All rights reservedSeries
Installation Procedure
Feed the conduit through the knockout and clip into the conduit clamp (clamp suitable for OD 9mm / 11mm / 20mm of conduit).
12Slide the conduit over the cable sub-units / fiber bundles and fix the conduit to the cable jacket using a cable tie.
11
Strip two meters of the cable jacket according to cable manufacturer’s guidelines. Attach to the panel with the cable clamp.
10Attach the cable clamp to the panel.9
Cable Clamp
8 © AFL Hyperscale. All rights reservedSeries
Front patch cord cable, neat and easy management using cable hooks.15
Close the rear splice tray cover / raceway cover and the rear pivot panel.14
Remove the splice tray cover. Route the incoming fiber (BLUE) as per the image above - store up to 1.5m of 144f SWR® fiber.
13
Installation Procedure
Latch / Tab
NOTE: Factory installed ribbon pigtails shown in GREEN. Splice according to the splice schedule.
9
U-Series 9RU Splice and Patch Panel
© AFL Hyperscale. All rights reservedSeries
Port labeling example.
Installation Procedure
10 © AFL Hyperscale. All rights reservedSeries
Notes
11
U-Series 9RU Splice and Patch Panel
© AFL Hyperscale. All rights reservedSeries
Notes
Thank you for choosing AFL Hyperscale
AFLHS9RUSPP030920
www.aflhyperscale.com