8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar...

53
8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Transcript of 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar...

Page 1: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

8DA10 and 8DB10Single and Double BusbarFlexible and powerful

Page 2: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 2 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

Infrastructure & Cities

Welcome!

Page 3: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 3 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

Main Applications for Medium-Voltage Switchgear

Power transmissionHigh and extra-high voltage > 72 kVPrimary distribution levelMedium voltage up to 40.5 kVup to 40 kA (3s)

Secondary distribution levelMedium voltage up to 24 kVup to 25 kA (1s)

Distribution levelLow voltage < 1 kV

8DJ10/20 8DH10 SIMOSEC

8DAB10 NXPLUS NXPLUS C

Power generationPower stations

G

x xx xxx xx x

x

Page 4: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 4 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

Technical features and general informationTechnical DataTypical Overview, fixtures and fittingsPanel Desgin

• Circuit-breaker Panel• Busbar• Operation• Metering• Low-Voltage Compartment• Cable Connection• Feeder Earthing, Cable Testing• Interlocks

Classification according to IEC 62 271-200Customer‘s Benefit

8DA/B10Content

Page 5: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 5 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Technical Features

Up to 40.5 kV, 40 kA (3s), 5000 A busbar, 2500 A feederMetal-enclosedSingle-busbar system ( 8DA10 )Double-busbar-system ( 8DB10 )Gas-insulatedHermetically single-pole enclosedFactory-assembled, type-tested switchgear according to IEC 62 271-200

Page 6: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 6 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10 General Information

Market introduction in March 1982Worldwide successful operationThe gas-insulated circuit-breaker switchgear for application in nearly all branches like Airports & Ports Automotive Buildings

Cement Industries Chemicals & Pharma MiningOil & Gas Paper Industries Steel & Aluminium Utilities Transportation & Railways

More than 63,900 panels 8DA/B (September 2011) deliveredOur experiences are based on more than 130,000 delivered panels for gas-insulated circuit-breaker switchgear (primary distribution level)

Page 7: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 7 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA10 Technical Data

2350

1625

600

IP3XD

IP65

2500

5000

40

40

100

100

185

85

50/60

40,5

2350

1625

600

IP3XD

IP65

2500

5000

40

40

100

100

170

70

50/60

36

2350

1625

600

IP3XD

IP65

2500

5000

40

40

100

100

125

50

50/60

24

2350mmHeight ( Standard )

1625mmDepth

600mmWidth

Dimensions

IP3XDSecondary part

IP65Degree of protection Primary part

2500ARated normal current of feeder

5000ARated normal current of busbar

40kARated short-circuit breaking current

40kARated short-time withstand current, 3 s

100kARated short-circuit making current

100kARated peak withstand current

75kVRated lightning impulse withstand voltage

20kVRated short-duration power-frequency withstand voltage

50/60HzRated frequency

12kVRated voltage

Page 8: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 8 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DB10 Technical Data

2350

2665

600

IP3XD

IP65

2500

5000

40

40

100

100

185

85

50/60

40,5

2350

2665

600

IP3XD

IP65

2500

5000

40

40

100

100

170

70

50/60

36

2350

2665

600

IP3XD

IP65

2500

5000

40

40

100

100

125

50

50/60

24

2350mmHeight ( Standard )

2665mmDepth

600mmWidth

Dimensions

IP3XDSecondary part

IP65Degree of protection Primary part

2500ARated normal current of feeder

5000ARated normal current of busbar

40kARated short-circuit breaking current

40kARated short-time withstand current, 3 s

100kARated short-circuit making current

100kARated peak withstand current

75kVRated lightning impulse withstand voltage

20kVRated short-duration power-frequency withstand voltage

50/60HzRated frequency

12kVRated voltage

Page 9: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 9 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA11/8DA12 ( Traction Power Supply ) Technical Data

220145kV

11060kV

27,517,5kVRated operation voltage

50/60

2000

2500

31,5

80

2350

865/1245

600

IP3XD

IP65

125

50

16,7

15

2350mmHeight ( Standard )

865/1245mmDepth ( 1-pole, 2-pole )

600mmWidth

Dimensions

IP3XDSecondary part

IP65Degree of protection Primary part

2000ARated normal current of feeder

2500ARated normal current of busbar

31,5kARated short-circuit breaking current

80kARated short-circuit making current

200kVRated lightning impulse withstand voltage EarthIsolation

95kVRated short-duration power-frequency withstand voltage EarthIsolation

HzRated frequency

25kVRated voltage

Page 10: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 10 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA10 Typical Overview

Circuit-breaker Panel Disconnector Panel Bus Sectionalizer

Page 11: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 11 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA10 Fixtures and Fittings Circuit-breaker Panel

Page 12: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 12 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA10 Fixtures and Fittings Disconnector Panel

Page 13: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 13 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA10 Fixtures and Fittings Bus Sectionalizer

Page 14: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 14 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA10 Fixtures and Fittings Bus Sectionalizer without additonal required space

Page 15: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 15 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

Circuit-Breaker Panel 8DA10 Single-Busbar System

Busbar housingLight-metal vessel

Circuit-breaker housing Light-metal vessel

Cable connection Inside-cone system

Low-voltage compartmentInstallation of secondary devices

Operating mechanism for three-position switchDisconnector and earthing switch

Operating mechanism for circuit-breaker Vacuum switching technology

Page 16: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 16 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

Circuit-Breaker Panel 8DB10 Double-Busbar System

Busbar housingLight-metal vessel

Circuit-breaker housing Light-metal vessel

Cable connection Inside-cone system

Three-position switch housingLight-metal vessel

Low-voltage compartmentInstallation of secondary devices

Operating mechanism for three-position switchDisconnector and earthing switch

Operating mechanism for circuit-breaker Vacuum switching technology

Page 17: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 17 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

Circuit-Breaker Panel 8DA11/121-Pole and 2-Pole Traction Systems

Busbar housingLight-metal vessel

Circuit-breaker housingLight-metal vessel

Cable connection Inside-cone system

Low-voltage compartmentInstallation of secondary devices

Operating mechanism for three-position switchDisconnector and earthing switch

Operating mechanism for circuit-breaker Vacuum switching technology

Page 18: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 18 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Busbar current up to 5000A

Three-position switch

Pole housing

Busbar

Busbar

Busbar housing

Twin busbar housing

Busbar up to 4000 A

Busbar 5000 AExample 8DA10

Page 19: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 19 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA10 Operation of Three-position Switch

Switch position indicatorDisconnector switch

Operating shaftDisconnector switch

Switch position indicatorCircuit-breaker switch

Operating shaftEarthing switch

Switch position indicatorEarthing switch

Preselection key

Page 20: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 20 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA10 Operation

Switch position indicatorCircuit-breaker switch

Switch position indicatorDisconnector switch

Operating shaftDisconnector switch / Earthing switch

Preselection key

Switch position indicatorEarthing switchON pushbuttonCirciut-breaker switch

OFF pushbuttonCirciut-breaker switch

De-earthing interlock

Raedy-for-service indicator

Filling valve

Opening for charging thecircuit-breaker spring by hand

“Spring charged” indicator

Counter

Page 21: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 21 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Current Measurement

Ring-core current transformersMain circuit as primary part without dielectric and thermal problems Secondary part accessible outside the enclosure without dangerFree of dielectrically stressed cast-resin parts

Current transformerFitted at cablehousing

Current transformerFitted at busbar

Current transformerFitted at pole housing

Current transformerFitted at cable

Page 22: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 22 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Voltage Measurement

Voltage transformerSingle-pole insulatedMetal-enclosedPlug-in typeAt the busbar:Surge-proof for 80 % UPrepeat test with connected transformer

Voltage TransformerFitted at busbar

Type 4MT3Type 4MU4

Voltage TransformerFitted at cabelhousingType 4MT7Type 4MU3

Page 23: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 23 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Low-Voltage Compartment

Height: 850 mm1200 mm (option)

Removable, bus wires and control cables plugged in (via 6 or 10-pole coded module plug connectors)Panel control via conventional control devices or digital bay controllerCustomer-specific equipment (protection, control, metering, annunciation)Wiring in H07VK, optionally also heat-resistant and halogen-free

Page 24: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 24 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Panel Connection – Inside Cone according to IEC 50 181

Maintenance-free due to inside cone plug-in systemFor connection type sizes2, 3 und 4 (depending on cablecross section)1 to 6 cables possible per phaseCable connection with different connection types / sizes realisablePlug-in voltage transformer and surge arrester realisable

Single cable connection Multiple cable connection

Page 25: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 25 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Fully Insulated Bar Connections

Fully insulated bar

for rated normal current up to 2500 A

Gas-insulated bar

for rated normal current up to 2500 A

Page 26: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 26 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Cable Earthing with the Circuit-Breaker

1) Close three-position switch / Earthed positionEarthing preparedElectrical OFF-signals are suppressed

2) Close circuit-breaker switch / ON positionOutgoing / Feeder earthed

3) Secure switch position “Outgoing/Feeder earthedwith padlock

Circuit-breaker is blocked mechanicallySignal: Outgoing / Feeder earthed (option)

1)

2) 3)

Page 27: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 27 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10 Cable testing

Cable test with DC voltage or AC voltage 0.1 HzThree-position switch and circuit-breaker in OFF positionCable fault location with lightning impulse voltageFull operating voltage at the busbar

Page 28: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 28 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DB10 Typical Overview

Circuit-breaker Panel Bus Coupler Bus Sectionalizer

Page 29: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 29 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DB10 Fixtures and Fittings Circuit-breaker Panel

Page 30: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 30 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DB10 Fixtures and Fittings Bus Coupler

Page 31: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 31 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DB10 Fixtures and Fittings Bus Sectionalizer

Page 32: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 32 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DB10 Operation

Switch position indicatorCircuit-breaker switch

Raedy-for-service indicatorsFilling valves

Switch position indicatorEarthing

Switch position indicatorDisconnector switch BB1

Opening for charging thecircuit-breaker spring by hand

“Spring charged” indicator

Counter

Switch position indicatorDisconnector switch BB2

Preselection key

Operating shaftDisconnector switch BB2

ON pushbuttonCirciut-breaker switch

OFF pushbuttonCirciut-breaker switch

De-earthing interlock

Page 33: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 33 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Interlocks (Selection)

Interlocks are designed according to IEC 62 271-200Standard interlocks

Three-position disconnector against circuit-breaker – mechanicalDisconnector against earthing switch (within three-position disconnector) – mechanical Locking device at the circuit-breaker switchLocking device at the three-position disconnector switch

Additional interlocksElectromagnetic interlock at the three-position switch / disconnector switchElectromagnetic interlock at the three-position switch / earthing switch

Page 34: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 34 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

Special feature - Single-pole enclosure

L1L2L3

Example 8DA10

Advantage of single-pole enclosure

Exclude phase-to-phase short circuits.

In worst case only phase-to-earth short circuits couldhappen.

Minimizing of fault risks.

Page 35: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 35 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

Special feature - Multiple-Vessel-Principle 8DA10

Busbar and circuit-breaker are single-pole enclosed within different vessels

Measures in case of faults at circuit-breaker or cable connection:

Shut down of the busbar is not necessary

Replacement of panels is possible, while busbar is under high voltage operation

Single-phase enclosure

2 Compartments

6 Vessels

► Shut down is only for the damaged panel necessary

Page 36: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 36 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

Special feature - Multiple-Vessel-Principle 8DB10

Busbar and switching devices are single-pole enclosed within different vessels

Measures in case of faults at switching devices or cable connection:

Shut down of the busbar is not necessary

Replacement of panels is possible, while busbar is under high voltage operation

Single-phase enclosure

5 Compartments

15 Vessels

► Shut down is only for the damaged panel necessary

Page 37: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 37 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

Statement 8DA10 and 8DB10

Maximum reliability of supply

No disconnecting of the busbar while outgoing feeder will be repaired or replaced.

Extension 8DB10 without shutdown of the busbar.

Special feature - Multiple-Vessel-Principle

Page 38: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 38 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Classification according to IEC 62 271-200

Partition Class: PMLoss of Service Continuity Category: LSC 2BAccessibility of Compartments:

Busbar compartment: tool-based Switching device compartment: tool-based Low-voltage compartment: tool-based Cable compartment: tool-based

Internal arc classification: IAC A FLR 40 kA 1 s

Page 39: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 39 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Customer’s Benefit

Security of Operation, ReliabilityPersonal SafetyEnvironmental IndependenceCompactnessMaintenance-free Design for DevicesEconomy, Ecology

Page 40: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 40 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Security of Operation, Reliability

Our solutionHermetically enclosed systemCurrent transformers outside the gas compartmentsMetal-enclosed voltage transformers plugged in from outsideHermetically enclosed busbar systemModular designMinimum use of insulating materialType and routine tests, quality managementNC production processes

Your benefitTwo and three-phase short circuits not possible because of single-phase encapsulationIndependent of the environment, maintenance-free,no condensation, no oxidationFast transformer replacement possibleNo dielectric and dynamic stress for current transformersRestriction of failure by compartmentReduced fire loadMTBF (> 3,000 years at the moment)

Page 41: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 41 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10 Maximum Security of Operation

Separate compartments for busbar and circuit-breaker offer a maximum degree of availability

Busbar ( in operation )

Attention: High voltage

Feeder earthed ( earthing )

Circuit-breaker

Access without danger to current transformer, feeder voltage transformer, cable plugs, operating mechanisms

Page 42: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 42 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Personal Safety

Your benefitTouching of live parts excluded,extremely high degree of protection of the primary partAccidental opening of vessel excludedAccess to switching devices not required due to maintenance-free designMaloperation excludedVerification of safe isolation from supply without opening the enclosure

Our solutionHermetically enclosed systemInternal arc classified according to IEC 62 271-200 for 1 sLogical mechanical interlocksCapacitive voltage detection systemMake-proof earthing throughthe circuit-breaker

Page 43: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 43 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Environmental Independence

Our solutionHermetically encapsulationHermetically enclosed pressure systemMaintenance-free switching devices and operating mechanisms,no adjustment and lubricationHermetically enclosed busbar systemEnclosed cable plugs,screened, independent of the environment

Your benefitInsensitive to aggressive environments (salt water, tropical areas, dust, humidity, chemical pollutants),no oxidation of contacts and bolted joints, no condensation,no pollution layers on insulators, no resinifying greaseContinuous insulation qualityNo ingress of foreign bodies, small animalsIndependent of site altitude

Page 44: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 44 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Compactness

Our solutionSF6-insulation,compact constructionCombined disconnector and earthing switch,compact switch designSIPROTEC bay controller: Digital control, interlocking and protection system,compact secondary systems with high functional density

Your benefitMinimum space requirements, building volume saved, efficient use of existing rooms, reduced volume for new constructions, compact design reduces transport and installation costs to a minimumEconomic use of space in urban areas,installation in conurbation, load centres to minimise transmission losses

Page 45: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 45 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Maintenance-free Design for Devices

Our solutionHermetically enclosed pressure systemMaintenance-free switching devices and operating mechanisms,no adjustment and lubricationHermetically enclosed busbar systemEnclosed cable plugs,screened, independent of the environment

Your benefitMaximum reliability of supply and availability,no shutdowns for maintenanceSealed for lifetime(according IEC 62 271-200)Low maintenance costs,minimized operational costsHighly economic investment

Page 46: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 46 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10Economy, Ecology

Our solutionMaintenance-free switchgearCompact constructionEconomic productionSF6 only used in hermetically sealed pressure system100 % SF6-recycling by means of special toolsIdentified, recyclable insulating materialListing of all materials used

Your benefitMinimized operator expenses, high availabilityReduced transport costsMinimum requirements regarding the buildingMinimized transmission losses by installation in load centresReliable, calculable disposal

Page 47: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 47 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10MTBF (1)

The term major failures and minor failures are taken from the CIGRE publication of the work group 13.06 “Reliability of High Voltage Switchgears”.

Definition:

MTBFMeantime between failure

Major failure (MF)Complete failure of a panel which causes the lack of one or more of its fundamentalfunctions.NOTE: A major failure will result in an immediate change in the system operating e.g. the backup protective equipment being required to remove the fault, or will result in mandatory removal from service for non scheduled maintenance (Intervention required within 30 minutes).

Minor failure (mF)Failure of a panel other than a major failure or any failure, even complete, of a constructional element or a sub-assembly which does not cause a major failure of the panel.

MTTFMeantime to failure

Page 48: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 48 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10MTBF (2)

Download from the Intranet

Page 49: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 49 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10 References Selected Projects (1)

Kulmbach / Germany

8DA10 / 16 panels

24 kV / 16 kA (3s) / 1250 A

First SIEMENS gas-insulated medium-voltage switchgear (March 1982)

Page 50: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 50 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10 References Selected Projects (2)

Tibet / China

8DA10

205 panels

40.5 kV / 31.5 kA (3s) / 1250 A

Site altitude: 3000 – 5000 m

Page 51: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 51 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10 References Selected Projects (3)

GECOL / Libya

8DA10 and 8DB10

1398 panels

36 kV / 40 kA (3s) / 2500 A

Page 52: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 52 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10 References Selected Projects (4)

Emirates Palace Hotel

8DB10

117 panels

12 kV / 31,5 kA (3s) / 2500 A

Page 53: 8DA10 and 8DB10 Presentation 2011.10 EN - Siemens · 8DA10 and 8DB10 Single and Double Busbar Flexible and powerful

Page 53 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10

© Siemens AG 2008

8DA/B10, the gas-insulated switchgear up to

40,5 kV, 40 kA (3 s), 5000 A busbar, 2500 A feeder

Thanks for your attention.