5335 PRV Instructions
Transcript of 5335 PRV Instructions
-
7/31/2019 5335 PRV Instructions
1/6
FunctionPressure reducing valves are installed in residential water systems to reduce and stabilise inletpressure from the water mains supply which is generally too high and variable for domesticappliances to function properly.
These valves can also be used to control inlet pressure to domestic hot water storage.
The Caleffi 5335 series have been specifically designed andmanufactured to meet the requirements of AS1357.2:2005 Valvesprimarily for use in warm and hot water systems - P. 2: Control valves.
Inclined pressure reducing valves
38538.04
Technical specifications
Materials:Body dezincification resistant alloy EN 12165 CW602NCover: PA 66 GF 30Control spindle: dezincification resistant alloy EN 12165 CW602NCartridge: POMComponents: brass EN 12165 CW617NDiaphragm: NBRSeals: EPDMStrainer: stainless steelPlug (3 way model): PPAG40
Performance:Pressure setting range: 100 600 kPa;
100500 kPa (code 533550)Factory setting: 500 kPaMax. inlet pressure: 1600 kPaMax. working temperature: 60CMedium: waterComplies with: AS 1357.2
Series 5335 Pressure reducing valveSizes 15 mm (1/2) and 20 mm (3/4)Female end connections
Code 533550 3-way pressure reducing valveSize 20 mm (3/4)Female end connections
Product range
1
www.caleffi.com
CALEFFI
5335 Series
AS 1357.2WMKA 02467
Installation, commissioning and servicing instructions
Copyright 2008 Caleff i
-
7/31/2019 5335 PRV Instructions
2/6 2
Dimensions
A
15 mm
22 mm
Code
5335 455335
55
B
72,5
72,5
C
22,5
22,5
D
46
46
E
79
84,5
E
A A
B
C
D
Weight (kg)
0,45
0,46
1/ 2
C e r t
i f i e
d P r o
d u c t
5 3 3 5S e r i e s
P r e s s u r er a n g e :1 0 0
6 0 0k P a
M a xin le tp re s s u r e
1 6 0 0k P a
F lo wr a te : 3 0
@1 0 0k P a
1 3 0@6 0 0k P a
M a xt e m p e r a t u r e :
6 0 C A u s t r a l i
a n
S t a n d a r d
A S1 3 5 7 . 2
L I C .2 4 6 7
0 , 5 1 2 5 0
, 2
p (kPa)
50
100
20
10
150
30
40
60
80
120
90
70
p (m w.g.)
5
10
2
1
15
3
4
6
8
12
9
7
1 0
5 1 0
2 0
5 0
1 0 0 F l
o w r a t e
( l / m i n ) ( m 3 / h )
1/2 3/4
A
3/4
Code
533550
B
72,5
C
50
D
46
E
82,5
E
A A
B
C
D
Weight (kg)
0,49
C e r t
i f i e
d P r o
d u c t
5 3 3 5 S e r i e s
P r e s s u r er a n g e :1 0 0
6 0 0k P a
M a xin le tp re s s u r e
1 6 0 0k P a
F lo wr a te : 3 0
@1 0 0k P a
1 3 0@6 0 0k P a
M a xte m p e r a t u r e :
6 0 C A u s t r a l i
a n
S t a n d a r d
A S1 3 5 7 . 2
L I C .2 4 6 7
Pressure drop diagram
Under following conditions:Inlet pressure 600 kPaOutlet set pressure: 400 kPa
Installation
The pressure reducing valve must be installed by a licensed plumber and in accordance with AS/NZS 3500, relevant local requirements and following these instructions.
MAINS SUPPLY
1 / 2
C e r t
i f i e d P
r o d u c
t
5 3 3 5 S e r ie s P r e s s u r e r a n g e : 1 0 0 6 0 0 k P a M a x i n l e t p r e s s u re 1 6 0 0 k P a F lo w r a t e : 3 0 @ 1 0 0 k P a 1 3 0 @ 6 0 0 k P a
M a x t e m p e r a tu r e : 6 0 C
A u s t r a l i a n S t a n d a r d A S 1 3 5 7 .2 L IC . 2 4 6 7
Checkvalve
Pressure reducing valve Line strainer(where fitted)
Isolatingvalve
Installation diagram
S r i s
r e s s u r erne : 0 0
0 0
xin l e t r e s s u r e
0 0
l r t e :3 0 0 0 3 0 0 0 0
s t r l i
t r2
S r i s
r e s s u r ern e : 0 0
0 0
xi n le t r e s s u r e
0 0
l r t e :3 0 0 0 3 0 0 0 0
s t r l i t r
7 .2
-
7/31/2019 5335 PRV Instructions
3/63
System without recirculation
COLD WATER
INLET
STORAGE HOTWATER HEATER
Temperingvalve
1 / 2
C e r t i f i e d P r o d u c t
53 35 S e r i es P r es s u re ra n g e : 1 0 0 6 0 0 k P a M a x i n l et p r e ss u r e 1 6 0 0 k P a F l o w ra t e: 3 0 @ 1 0 0 k P
a 1 3 0 @ 6 0 0 k P a M
a x t e m p e ra t u re : 6 0 C
Au st r al i a n S ta n d a rd A S 13 5 7 .2 L I C . 24 67
A u s t r a l i a n t a n d a r d A S 1 3 5 7 .2 L I .2 4 6 7
C e r t
i f i e
d P r o
d u c t
5 3 3 5 S e r i e s
P r e s s u r er a n g e :1 0 0
6 0 0k P a
M a xi n le tp r e s s u r e
1 6 0 0k P a
F l o wr a t e :3 0@1 0 0
k P a
1 3 0@6 0 0k P a
M a xt e m p e r a t u r e :
6 0 C A u s t r a l
ia n
S t a n d a r d
A S1 3 5 7 . 2
L I C .2 4 6 7
C e r t
i f i e d
P r o
d u c t
5 3 3 5S e r i e s
P r e s s u r er a n g e :1 0 0
6 0 0k P a
M a xi n l e tp r e s s u r e
1 6 0 0k P a
F l o wr a t e :3 0@1 0 0
k P a
1 3 0@6 0 0k P a
M a xt e m p e r a t u r e :
6 0 C A u s t r a l
i a n
S t a n d a r d
A S1 3 5 7 . 2
L I C .2 4 6 7
Straightoutlet
Angleoutlet
Inlet Outlet
Plug
Inlet
Outlet
Plug
MAINS SUPPLY
Checkvalve
Pressure reducing valveLine strainer(where fitted)
Isolatingvalve
C e r t i f i e d P r o d u c t
5 3 3 5 S e r i e s
P r e s s u r e r a n g e : 1 0 0
6 0 0 k P a
M a x i n l e t p r e s s u r e
1 6 0 0 k P a
F l o w r a t e : 3 0 @ 1 0 0
k P a
1 3 0 @ 6 0 0 k P a
M a x t e m p e r a t u r e :
6 0 C A u s t r a l
i a n
S t a n d a r d
A S 1 3 5 7 . 2
L I C . 2 4 6 7
-
7/31/2019 5335 PRV Instructions
4/64
Recommendations for installation
1. Installation below groundIf installing the 5335 series valve underground, please ensure that steps are taken to protect thevalve from becoming frozen in frost-prone areas.Please allow yourself sufficient space to remove the cartridge should maintenance be required.
The reading of a gauge for setting purposes may be difficult and an alternate means of checkingdownstream pressure may ne necessary.
2. Water hammering
This is one of the main problems which may affect pressure reducing valves. It is best to fitspecial devices to absorb water hammering when fitting pressure reducing valves in systems at risk.
WARNING:If it is critical to maintain the downstream pressure setting to protect equipment, asa safety measure, we recommend that a pressure, or safety, relief valve is installeddownstream of the pressure reducing valve.
Trouble-shooting
1. Increased downstream pressure near a waterheater
This problem is due to the water being heated bythe water heater. There is no relief of the pressurebecause the reducing valve is correctly closed. Thesolution is to install an expansion vessel (between theheater and the reducer) to absorb the pressureincrease.
2. The pressure reducing valve does not maintain its set pressure
In most cases this is the result of impurities that deposit on the valve seat causing leakagewith a resulting increase in pressure downstream. The solution is to fit a filter upstream fromthe reducer and subsequently to maintain and clean the cartridge (see Maintenance ).
1. Flush the system.
2. Install the pressure reducing valve in any position either vertically or horizontally, not upsidedown, paying attention to the direction of flow indicator on the body of the valve.
3. Caleffi 5335 series pressure reducing valves are factory set at 500 kPa.
4. If required, reset the pressure by turning the screw on the top of the plastic cover. Turn it clockwise to increase the pressure andanticlockwise to decrease it.
-
7/31/2019 5335 PRV Instructions
5/6
SafetyIf the pressure reducing valve is not installed, commissioned and maintained properly inaccordance with the instructions contained in this manual, it may not operate correctly,and may cause damage to objects and/or persons.
Make sure that all the connections are water-tight.
When installing the pressure reducing valve, make sure not to over-tighten the connections to thevalve as, over time, a failure can occur with subsequent water leakage causing damage.
In the case of highly aggressive water, arrangements must be made to treat the water before it entersthe pressure reducing valve, in accordance with current legislation. Otherwise, the pressure reducingvalve may be damaged and not function correctly.
Leave this operating manual with the user
Maintenance
Proceed as follows for periodic cleaning of the strainer and inspection of the cartridge:
1 Turn off upstream water supply to the pressure reducing valve and open an outlet downstreamto relief pressure
2 Unscrew (anticlockwise) the setting screw to decompress the spring inside.3 Unscrew the cover.4 Extract the cartridge with the aid of pincers to grip the head of the screw.5 After inspection and cleaning, refit the cartridge or, alternatively, fit a replacement cartridge.6 Reset the valve (see Installation ).
2 3 4
5
-
7/31/2019 5335 PRV Instructions
6/6
CALEFFIS.R. 229, n. 25 I-28010 Fontaneto dAgogna (NO) Tel. Int. +39 322 8491 R.A. Fax +39 322 863723
Http://www.caleffi.com E-mail:[email protected]
AUSTRALIAN AGENT
ALL VALVE INDUSTRIES Pty Ltd30/205 Port Hacking Road
Miranda NSW 2228Tel. (02) 8543.5111Fax (02) 8543.5122
E-mail: [email protected]