Brief Introduction for Automated Testing of LFDC101/102 Relay
Kamin DaveManager – Marketing & Protection Applications
South Asia & Middle EastDOBLE ENGINEERING COMPANY, INDIA
![Page 2: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/2.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Protection Relay Testing:
Testing of LFDC101/102Relay by using F6150
![Page 3: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/3.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
High speed directional comparison protection using signaling channel
Distance Zone Backup
Switch On to Fault Protection
Voltage Transformer supervision
![Page 4: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/4.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
Operating time of Directional comparison unit is 12 to 15ms
Operating time of Distance zone (Backup) is adjustable
![Page 5: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/5.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
![Page 6: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/6.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
![Page 7: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/7.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
![Page 8: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/8.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
![Page 9: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/9.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
![Page 10: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/10.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
![Page 11: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/11.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
![Page 12: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/12.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
![Page 13: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/13.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
RA RBCommunication(Signaling betn two relays)
![Page 14: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/14.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
Carrier scheme supervised by Mho elementIf there is fault in Line & fault impedance falls under preset value then Both relays will send carrier signals to each otherScheme is normally applied as a primary protection for short line length (<5km)
![Page 15: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/15.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
F1 External fault (F1) in Forward direction
IA = - IBIA + IB = 0
![Page 16: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/16.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
F1
External fault (F1) in Forward direction
IA
IB
![Page 17: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/17.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
F1
External fault (F1) in Forward direction
ZA
ZB
ZF
ZF
Forward Direction
Reverse Direction
![Page 18: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/18.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
F1 External fault (F1) in Reverse direction
Both currents are zero in Radial feeder IA = 0IB = 0
![Page 19: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/19.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
External fault (F1) in Reverse direction
ZA ZB
ZFZF
Reverse Direction
S1 S2
RA RB
F1
IA IB
![Page 20: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/20.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
F1 Internal fault (F1) in Forward direction
IA
IB
![Page 21: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/21.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
F1 Internal fault (F1) in Forward direction
ZA
ZBZF
ZF
![Page 22: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/22.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
ZA
ZB ZF
ZF
RF
RF
Kn = 0.75
Internal Fault: Fault measurement for Phase to Ground faults
Kn = 0.75
R in Ohms
X in Ohms
R in Ohms
X in Ohms
RA
RB
![Page 23: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/23.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
Internal fault (F1) in Forwarddirection& fault feeding is from End A
F1 F2
Internal fault (F2) in Forwarddirection& fault feeding is from End B
![Page 24: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/24.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
Internal fault (F1) in Forward direction & Fault feeding is from source “S1”
ZA ZB
ZFZF
S1RA RBF1
RC RDZC ZD
ZF
ZF
Relay “RC” will operate on Back Zone
IA IB
![Page 25: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/25.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
ZA
ZB ZF
ZF
Relay Operating time faster (12 to 15ms) when carrier signal receive & impedance falls under preset value during internal faults
R in Ohms
X in Ohms
R in Ohms
X in Ohms
RA
RB
![Page 26: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/26.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
ZA
ZB ZF
ZF
Relay Operating time based on time delay set in relay when carrier signal NOT receive & impedance falls under preset value during internal faults
R in Ohms
X in Ohms
R in Ohms
X in Ohms
RA
RB
![Page 27: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/27.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
LFDC Relay for Line1
LFDC Relay for Line2
220KV GETCO S/S
![Page 28: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/28.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
220KV GACL S/S
LFDC Relay for Line1
LFDC Relay for Line2
PLCC Cabinet
![Page 29: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/29.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCCPLCC: Power Line Carrier Communication (PLCC) is used to communicate devices between substations.The Audio frequency is carried out by a carrier frequency and the range of carrier frequency is 24kHz to 500kHzWave trap: It is an inductor of rating in mili henry. It is connected in series with the power transmission line. It blocks the high frequency carrier waves (24kHz to 500kHz) and let Power waves (50Hz – 60Hz) to pass through.
![Page 30: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/30.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCCCoupling Capacitor: It provides low impedance path for carrier energy to H.V. line and blocks the power frequency circuit by being a high impedance path.HF Cable: It is used to carry to signal from PLCC cabinet to switchyard
![Page 31: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/31.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCCPLCC Cabinet: It indoor equipment. It is divided in two parts;
TransmitterReceiver
![Page 32: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/32.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCCWave trap or Line trap
![Page 33: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/33.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Carrier send Carrier receive
Carrier receive Carrier send
Communication through PLCC
Exchange SignalsBoth are thinking same
Scheme Stable on External Faults
220KV GETCO S/S 220KV GACL S/S
F1RA RB
Delta V = 0Delta I = 0IA - IB = Delta IIA = IB VA - VB = Delta VVA = VB
IA IB
![Page 34: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/34.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Carrier send Carrier receive
Carrier receive Carrier send
Communication through PLCC
Scheme Operates on Internal Faults
220KV GETCO S/S 220KV GACL S/S
F1RA RB
Delta V = ?Delta I = ?IA - IB = Delta IIA not equal to IBVA - VB = Delta VVA not equal to VB
Exchange SignalsBut both are thinking in different
IA IB
![Page 35: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/35.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Carrier send Carrier receive
Carrier NOT receive Carrier send
Communication through PLCC
Scheme Operates on Internal Faults
220KV GETCO S/S 220KV GACL S/S
F1RA RB
Delta V = ?Delta I = ?IA - IB = Delta IIA not equal to IBVA - VB = Delta VVA not equal to VB
No Exchange of SignalsBut both are thinking in different
IA IB
![Page 36: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/36.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCC
![Page 37: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/37.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCC
![Page 38: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/38.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
Relay Settings:Location: GETCO and GACL Ends, DahejLine length: 1.5kmLine voltage: 220kV (Line1)• Z = 0.2 Ohms• tZ = 0.2s• Line Angle = 78 Deg.• Kn = 0.75
![Page 39: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/39.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Test Equipment
• Make : DOBLE
• Model : F6150
Software
• F6TesT Version 2.19-1065
![Page 40: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/40.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
VA
VB
VC
I1
I2
I3
Relay
Test Circuit:
Source Configurations:3V X 3I
CT Inputs
![Page 41: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/41.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
• Zone Time Test during carrier signal received from other end
• Zone Time Test (Distance Zone Backup)
• Zone Characteristic Test
• SOTF Test
• Stability Test of scheme
Test Conducted:
![Page 42: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/42.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Zone Time Test during Carrier signal received
from other end
Use “ZTime” Module
![Page 43: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/43.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Location Level
Right click on Mouse & click on “Append” and create new Location
![Page 44: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/44.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Level
Right click on Mouse & click on “Append” and create new Relay
![Page 45: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/45.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Parameters
Click on “Add” button & select “Impedance” function
![Page 46: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/46.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Click here & then click on “New Zone” button
![Page 47: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/47.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select “MHO” & enter relay settings
![Page 48: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/48.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Click on “Yes”
![Page 49: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/49.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Characteristic created for Ph-N fault
![Page 50: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/50.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Characteristic created for Ph-Ph & 3-Ph faults
![Page 51: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/51.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Click on “Yes”
![Page 52: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/52.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right Click on “Mouse” & Click on “Append” to create new Test plan
![Page 53: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/53.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right click on “Mouse” & click on “Append” to create new test module for testing
![Page 54: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/54.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select “Z-Time” Module from list
![Page 55: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/55.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Press on “OK” & Create New Test Definition
![Page 56: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/56.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select characteristic from list
![Page 57: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/57.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Enter Test current (i.e. 2.3A)
Select Test Method
![Page 58: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/58.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select Trigger (i.e. Open to Close)
Enter Prefault duration & Max. fault duration
![Page 59: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/59.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Click Test points in R-X Plane for “Ph-Ph” fault
![Page 60: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/60.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right Click on check box
Green/Red Points areActual Points have been tested
Blue color shows;Expected characteristic
Line Angle
Relay operated in 12 to 13ms
Carrier signal received from other end on E19 & E20terminals of Relay
![Page 61: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/61.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Display shows relay tripped on DIR (A-N fault)
Time Test: Directional Comparison
![Page 62: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/62.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Zone Time Test (Distance Zone Backup)
Use “ZTime” Module
![Page 63: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/63.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right Click on check box
Green/Red Points areActual Points have been tested
Blue color shows;Expected characteristic
Line Angle
Relay operated in 250 to 260ms
Carrier signal NOT received from other end on E19 & E20 terminals of Relay
![Page 64: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/64.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right Click on check box
Green/Red Points areActual Points have been tested
Blue color shows;Expected characteristic
Line Angle
Relay operated in 250 to 260ms
Carrier signal NOT received from other end on E19 & E20 terminals of Relay
![Page 65: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/65.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Display shows relay tripped on Z (T) (BC fault)
Time Test: Distance Backup Zone
![Page 66: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/66.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Characteristic Test
Use “ZChar” Module
![Page 67: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/67.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right click on “Mouse” & Press on “Append”& Create new Test Module
![Page 68: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/68.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select “Z-Char” Module from list
![Page 69: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/69.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Double click on “Characteristic Test”
![Page 70: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/70.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Press on “OK” & Create New Test Definition
![Page 71: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/71.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select characteristic from list
![Page 72: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/72.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select Test Method
![Page 73: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/73.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Enter Test current (i.e. 2.3A)
![Page 74: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/74.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select Trigger (i.e. Open to Close)
![Page 75: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/75.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Enter Angle Boundary for test (Say; start from 0 to 180 Degree)
![Page 76: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/76.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Enter Angle Boundary for test (Say; start from 0 to 180 Degree)
![Page 77: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/77.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Green Points (white lines) areActual Points have been tested
Blue color shows;Expected characteristic
Line Angle
Right Click on check box
![Page 78: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/78.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right Click on check box
Green Points (white lines) areActual Points have been tested
Blue color shows;Expected characteristic
Line Angle
![Page 79: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/79.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
SOTF Test
Use “SSIMUL” Module
![Page 80: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/80.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select SSIMUL Module from list
![Page 81: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/81.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
State1 set for SOTF
![Page 82: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/82.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Operating time recorded 47ms
![Page 83: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/83.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Scheme Testing
![Page 84: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/84.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Comm Channel
Protectionunder test
GPS Synch: End to End Testing
Test PUTT/POTT Schemes
1pps Signal 1pps SignalF6910+F6885+F6895 Option
![Page 85: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/85.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCC
Counter for Carrier send signals
Counter for Carrier receive signals
Both end relays tripped on 13ms
![Page 86: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/86.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
![Page 87: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/87.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6TEST2.21-1157 Advance Line Version
![Page 88: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/88.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
![Page 89: 38.LFDC Relay Testing With F6150-1](https://reader031.fdocuments.us/reader031/viewer/2022012405/547f13afb4af9fb9158b590c/html5/thumbnails/89.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
DOBLE ENGINEERING COMPANY2nd Floor Suvidhi Pride,Opp. Shell Petrol Pump,Gorwa-Refinery RoadVADODARA-390 015INDIA. Cell:- +91 98980 55956EMAIL ID:- [email protected]:- www.doble.com