38HK12-7038HQ18-24Cond
Product DataThe 38H Series Energy-Efficient Split condensing units incorporate innovative technology to providereliable cooling performance. Built into these units are features most desired by the industry.
Features/Benefits• Designed especially for high ambientenvironment.
• EER (Energy Efficiency Ratio) ratingsof up to 10.0.• The small footprint coupled with the horizontal airflow design means that the 38H Series units can be installed within200 mm (8 in). of an outside wall, on aroof, balcony, or deck.Electrical Range — All units are offered in 220-240v singlephase. Three-phase units are availablefrom 48 through 70 sizes in 220v.Wide Range of Sizes — The 38H Series is available in 7nominal sizes from 1.5 through 6 tomeet the needs of residential and lightcommercial applications.Application Versatility— The unit can be combined with a widevariety of evaporator coils and blowerpackages to provide quiet, dependablecomfort. Unit can be installed on a roof orat ground level.Easy access for service and maintenanceA single panel provides immediateaccess to the isolated compressor andcontrol compartment, allowing a servicetechnician access to check unit operationwithout losing condenser airflow. Coilscan be cleaned quickly from the outside.Secure operationIf security is an issue, outdoor and
indoor units are connected only byrefrigerant piping and wiring to preventintruders from crawling throughductwork. The 38H Series units can beinstalled 8 in. away from outside walls,protecting coils from vandals and severeweather.
38HK18-7038HQ18-24Condensing Units - 60Hz1 to 6 Nominal Tons
38HK-04 PD 60HZ 2011
38H
K/H
Q
Fast installation sweat adapter kit is provided units are the onlyCarrier’s compact systems take for 7/8” tube size. Valves are dedicated commercial unitsonly a few hours to install — externally located so with all safety featuresonly wire and piping need to be refrigerant tube connections standard to ensure highrun. The fast and easy can be made quickly and performance and lastinginstallation ensures minimal easily. Each valve has a reliability under the mostdisruption to customers in the service port for ease of demanding situations. Forhome or workplace. This Carrier checking operating refrigerant example, start capacitorsadvantage is especially pressures. ensure dependable start-beneficial in retrofit situations. ups, especially during low
External Service ValvesBuilt-in reliabilityCarrier split system outdoor
voltage conditions (down to 187 v). High-pressure and
— Service valves are brass, units are designed to provide low-pressure safetyfront seating type. The 38H years of trouble-free operation. switches are standardSeries has flare connections, The 38H Series condensing
Table of contentsPage.
Features/Benefits………………………………………………………………………………………. 1ModelNumber Nomenclature………………………………………………………………………….. 3Physical Data……………………………………………………………………………………………. 3Combination Ratings…………………………………………………………………………………… 4Air Deflector Accessory ……………………………………………………………………………….. 5Base Unit Dimensions………………………………………………………………………………….. 6-7Electrical Data…………………………………………………………………………………………… 8Detailed Performance Data – 42TX Matching………………………………………………………. 9,10Detailed Performance Data – FB4A Matching……………………………………………………… 11,12Detailed Performance Data – Ceiling Cassette Matching…………………………………………. 13,14Detailed Performance Data – Free Stand Matching………………..………………………………. 15Typical Wiring Schematic………………………………………………………………………………. 16-19Application Data………………………………………………………………………………………… 20Controls…………………………………………………………………………………………………... 21Appendix – Long Line Guide Line……………………………………………………………………. 22
2
Energy Efficiency labels
SASO 2663/2007
--
Model number nomenclature
38 H K C 18 D S 3 0 - 00Type38–Air-CooledCondenser
Series
Condenser TypeK-CoolQ- Heat Pump
CompressorC- ReciprocatingR- Rotary - Super Tropical
Nominal Capacity in Tons (kW)
18 - 1.5 Tons (5.3 kW)24 - 2 Tons (7 kW)30 - 2.5 Tons (8.8 kW)36 - 3 Tons (10.6 kW)48 - 4 Tons (14 kW)60 - 5 Tons (17.6 kW)70 - 6 Tons (20.6 kW)
Physical Data
Factory Reference
Design Series
Voltage3 – 220–1–605– 220–3–60 2 – 380–3–60
Fin TypeS- Standard Bare Fins P- Pre-Coated Blue Fins
ApplicationD: Ducted applicationFB4A or 42TX24 Volt compressor contactorU: Un Ducted application/DecorativeCeiling Cassette, Hi wall,--etc.220 Volt compressor contactor
38H
K/H
Q
UNIT 38H 18 24 30 36 48 60 70 NOMINAL CAPACITY (Tons) 1.5 2 2.5 3 4.0 5.0 6.0 OPERATING WEIGHT (lb) 123 139 154 161 211 227 253SHIPPING DIMENSIONS (in) (W X H X D) 37 x 29.7 x 16.1 50.4 X 40.2 X 30 COMPRESSORCool Only ReciprocatingHeat Bump RotaryREFRIGERANT TYPE R22 METERING DEVICEDucted Application Nozzle, in the indoor unitUn-ducted Application Capillary Tube Nozzle, in the indoor unit FINISH Gray OUTDOOR FAN Propeller Type RPM/CFM 1100/2000 860/3,000 Diameter, No. Blades 18 in, 3 24 in, 3 Motor Horsepower, 1/12 1/4 COIL DATA Face Area (sq ft) 6.3 12.05Tubes Smooth Helical groovedFins Aluminium, Double Wavy FPI 15 17 17 15 12 14 REFRIGERANT LINES ** Connection Type Flare Liquid Line 3/8 inch Vapour Line 5/8 in. 3/4 in. 7/8 inch* Max Length 50 ft Max Lift 30 ft Max Drop 30 ft * Sweat adapter kit is provided for 7/8” tube size.** For long line application see Appendix.
3
38H
K/H
Q
4
Combination ratings COOLING ONLY*
Nominal Cap.
MBtuh Indoor Type Indoor Model Outdoor Model Cap.
Btu/hr CFM Input Watts E.E.R.
18
Cassette 40KMC018-3N-IU 38HKR018US 18,000 425 2.00 8.9 Console 42VMC18-3C 38HKR018US 18,000 440 2.10 8.4
High Wall 42KPL020-3 38HKR018UP 19,000 550 2.18 8.7 High Wall 42KHC018-3 38HKR018UP 18,000 550 2.00 8.9 High Wall 42EGC018-3 38HKR018US 18,000 550 2.00 8.9
Ducted Split FB4ASNF018 38HKR018DS 19,000 650 2.30 8.1 Ducted Split 42TX-018-301 38HKR018DS 19,000 650 2.30 8.1
24
Cassette 40KMC024-3N-IU 38HKC024US 21,750 450 2.40 8.9 Console 42VMC24-3C 38HKR024US 21,000 530 2.45 8.5
High Wall 42KPL025-3 38HKR024UP 22,500 650 2.39 9.4 High Wall 42KHD024-3 38HKR024UP 21,750 650 2.40 8.9 High Wall 42EGC024-3 38HKR024US 21,750 650 2.40 8.9
Ducted Split F4ASNF024 38HKC024DS 23,000 650 2.60 8.8 Ducted Split 42TX-024-301 38HKC024DS 23,000 650 2.60 8.8
30 Cassette 40KMC036-3 38HKC030US 27,500 750 3.20 8.8 Console 42VMC30-3C 38HKC030US 29,000 675 3.20 9.0
High Wall 42XP090C3 38HKC030US 27,500 730 3.20 8.8 Ducted Split 42TX-030-301 38HKC030DS 30,500 800 3.70 8.2 Ducted Split FB4ASNF030 38HKC030DS 30,500 1150 3.70 8.2
36
Cassette 42KMC-048-3N-IU 38HKC036US 35,000 975 3.80 9.0 Cassette 40KMC036-3N-IU 38HKC036US 35,000 975 3.80 9.0 Console 42VMC36-3C 38HKC036US 32,500 765 3.60 9.0
High Wall 42XP100C3 38HKC036US 35,000 830 3.80 9.0 Free Stand 42SD6B 38HKC036US 35,500 800 3.75 9.5 Free Stand 42HD6B 38HKC036US 35,500 800 3.75 9.5 Ducted Split 42TX-036-301 38HKC036DS 35,000 1100 3.65 9.6 Ducted Split FB4ASNF036 38HKC036DS 35,800 1200 4.00 9.0
48
Cassette 40KMC048-3N-IU 38HKC048US 41,000 975 4.23 9.7 Cassette 40KMC048-3EN-IU 38HKC036US 41,000 750 4.23 9.7
Free Stand 42SD6B 38HKC048US 44,000 900 4.90 8.9 Ducted Split 42TX-048-301 38HKC048DS 44,000 1400 4.51 9.7 Ducted Split 42MX-048-301 38HKC048DS 47,500 1633 5.00 9.5 Ducted Split FB4ASNF048 38HKC048DS 46,500 1500 5.33 8.8
60
Free Stand 42SD7B 38HKC060US 55,000 1500 5.88 9.3 Ducted Split 42TX-060-301 38HKC060DS 56,500 1600 5.8 9.8 Ducted Split 42MX-060-301 38HKC060DS 58,300 1820 6.10 9.6 Ducted Split FB4ASNF060 38HKC060DS 56,800 1650 6.48 8.8
70 Ducted Split FB4ASNF070 38HKS070DS 68,750 1850 7.2 9.6
HEAT PUMP*
Nominal Cap.
MBtuh Indoor Type Indoor model Outdoor model CFM
COOLING MODE HEATING MODE CAP.
Btu/hr Input Watts E.E.R. CAP.
Btu/hr Input Watts COP
Console 42VMC18-3H 38HQR018US 440 16,000 1.90 8.3 4,900 1.70 2.80 18 High Wall 42QPL020-3 38HQR018UP 550 18,000 2.00 8.9 4,750 1.63 3.00
High Wall 42QHC018-3 38HQR018UP 550 18,000 1.90 9.5 5,100 1.70 3.00 High Wall 42EGQ018-3 38HQR018US 550 18,000 1.90 9.5 5,000 1.70 2.90
24 Console 42VMC24-3H 38HQR024US 530 21,500 2.40 8.8 5,300 1.86 2.85 High Wall 42QPL025-3 38HQR024UP 650 22,000 2.24 9.8 5,700 1.83 3.10 High Wall 42QHD024-3 38HQR024UP 650 21,000 2.40 8.7 5,500 1.86 2.95 High Wall 42EGQ024-3 38HQR024US 650 21,000 2.30 9.0 5,250 1.84 2.85
30 Console 42VMC30-3H 38HQC030US 680 28,000 3.10 9.0 8,500 2.70 3.20 LEGEND CFM — Cubic Feet Per Minute EER — Energy Efficiency Ratio * as per SASO 2681/2007 standard
NOTES: Cooling Standard: 80.6F db, 66.2F wb indoor entering-air temperature and 95.0 F db air entering outdoor unit. Heating Standard: 68 F db, 59 F wb indoor entering-air temperature and 44.6 F db air entering outdoor unit.
Optional Deflector Accessory – 38HK48-70
Part No. 38HK580622
The air deflector accessory converts thedirection of air flow in the side discharge outdoorcondensing units from horizontal direction to verticaldirection to make the unit more flexible and suitablefor top discharge applications.
The air deflector accessory consists of three pieces of painted galvanized sheet metal parts assembled atsite.
Note: This accessory is used only with 38HK048-070
38H
K/H
Q
5
38H
K/H
Q
Base Unit Dimensions – 38H 12-36
6
Base Unit Dimensions – 38H 048-070
A B C D E F G HUNIT 38H Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm
048-070 3-13⁄16 944.6 3-89⁄16 1131.9 1-51⁄16 433.4 1-67⁄16 468.3 2-61⁄2 774.7 1-75⁄8 498.5 1-75⁄8 498.5 2-55⁄8 752.5
NOTES:1. Required clearances: with coil facing wallallow 8 in. minimum clearance on coil side andcoil end, and 3 ft minimum clearance oncompressor end and fan side.2. Dimensions in [ ] are in millimeters.
38H
K/H
Q
7
Electrical Data Cool Only
38H
K/H
Q
Size Outdoor Model PowerSupply
Voltage Compressor FanMin Max FLA LRA FLA
38HKC018US30 220/1/60 198 242 9.6 55.0 0.9
18 38HKR018US30 220/1/60 198 242 9.1 40.0 0.938HKC018UP30 220/1/60 198 242 9.6 55.0 0.938HKC018DS30 220/1/60 198 242 9.6 55.0 0.938HKC024US30 220/1/60 198 242 12.5 60.0 0.9
24 38HKR024US30 220/1/60 198 242 10.1 53.0 0.938HKC024UP30 220/1/60 198 242 12.5 60.0 0.938HKC024DS30 220/1/60 198 242 12.5 60.0 0.9
30 38HKC030US30 220/1/60 198 242 13.5 82.0 0.938HKC030DS30 220/1/60 198 242 13.5 82.0 0.9
36 38HKC036US30 220/1/60 198 242 14.4 88.0 0.938HKC036DS30 220/1/60 198 242 14.4 88.0 0.938HKC048US30 220/1/60 198 242 18.5 118.0 2.1
48 38HKC048US50 220/3/60 198 242 11.4 78.0 2.138HKC048DS30 220/1/60 198 242 18.5 118.0 2.138HKC048DS50 220/3/60 198 242 11.4 78.0 2.138HKC060US30 220/1/60 198 242 26.6 178.0 2.1
60 38HKC060US50 220/3/60 198 242 15.0 114.0 2.138HKC060DS30 220/1/60 198 242 26.6 178.0 2.138HKC060DS50 220/3/60 198 242 15.0 114.0 2.1
70 38HKS070DS50 220/3/60 198 242 16.0 150.0 2.138HKS070DS20 380/3/60 342 418 8.3 75.0 2.1
Heat Pump
Size Outdoor Model PowerSupply
Voltage Compressor FanMin Max FLA LRA FLA
18 38HQR018US30 220/1/60 198 242 9.1 40.0 0.938HQR018UP30 220/1/60 198 242 9.1 40.0 0.9
24 38HQR024US30 220/1/60 198 242 10.1 53.0 0.938HQR024UP30 220/1/60 198 242 10.1 53.0 0.9
LEGENDFLA — Full Load AmpsLRA — Locked Rotor AmpsRLA — Rated Load AmpsMCA — Minimum Circuit AmpsMOCP — Maximum Over current Protection Amps
8
38HKC060DS20 380/3/60 342 418 10.4 55.0 2.1
38H
K/H
Q
9
Detailed Performance Data – Matching 38HK with 42TX
Nom Cap.
Mbtuh
Evaporator Air
CONDENSER AIR ENTERING Deg. F
75 85 95 105 115 120
CFM EWB
Capacity
MBtuh Tot Sys Kw
Capacity
MBtuh Tot Sys Kw
Capacity
MBtuh Tot Sys Kw
Capacity
MBtuh Tot Sys Kw
Capacity
MBtuh Tot Sys Kw
Capacity
MBtuh Tot Sys Kw
Tot
Sen Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen
18
450
72 22.6 10.9 2.0 21.8 10.7 2.2 20.7 10.4 2.3 19.7 10.0 2.6 18.4 9.5 2.7 9.2 4.8 2.8 67 20.9 13.6 2.0 19.9 13.2 2.1 18.7 12.8 2.2 17.6 12.3 2.5 16.3 11.8 2.6 8.1 5.9 2.7 62 18.9 16.0 1.9 17.8 15.5 2.0 16.7 15.0 2.1 15.7 14.4 2.3 14.5 13.5 2.5 7.3 6.8 2.6 57 18.0 16.8 1.9 17.2 16.1 2.0 16.3 15.3 2.1 15.5 14.4 2.3 14.5 13.5 2.5 7.3 6.8 2.6
550
72 22.9 11.3 2.1 22.1 11.1 2.2 21.1 10.8 2.4 20.1 10.5 2.6 18.7 10.1 2.8 9.4 5.0 2.9 67 21.3 14.3 2.0 20.3 14.0 2.2 19.1 13.7 2.3 17.9 13.2 2.5 16.6 12.6 2.7 8.3 6.3 2.7 62 19.3 17.1 1.9 18.3 16.6 2.2 17.1 16.0 2.2 16.2 15.1 2.4 15.2 14.1 2.6 7.6 7.1 2.6 57 18.8 17.6 1.9 17.9 16.8 2.2 17.0 16.0 2.2 16.2 15.1 2.4 15.2 14.1 2.6 7.6 7.1 2.6
650
72 23.1 11.6 2.1 22.3 11.5 2.2 21.3 11.2 2.4 20.3 10.9 2.7 19.0 10.5 2.8 9.5 5.3 2.9 67 21.5 15.0 2.1 20.6 14.8 2.2 19.0 14.4 2.3 18.2 14.0 2.6 18.0 13.4 2.7 8.4 6.7 2.8 62 19.7 18.0 2.0 18.7 17.5 2.2 17.7 16.5 2.3 16.8 15.6 2.5 15.8 14.7 2.6 7.9 7.3 2.7 57 19.5 18.2 2.0 18.6 17.5 2.2 17.7 16.5 2.3 16.8 15.6 2.5 15.8 14.7 2.6 7.9 7.3 2.7
24
450
72 26.6 12.5 2.2 25.7 12.2 2.4 24.4 11.8 2.6 23.5 11.4 2.7 21.9 10.9 2.9 11.0 5.4 3.0 67 24.6 15.5 2.2 23.4 15.1 2.3 22.0 14.6 2.5 20.9 14.0 2.6 19.4 13.5 2.8 9.7 6.7 2.9 62 22.3 18.2 2.1 21.0 17.6 2.3 19.7 17.0 2.4 18.6 16.4 2.5 17.3 15.4 2.7 8.7 7.7 2.7 57 21.2 19.2 2.1 20.2 18.3 2.2 19.2 17.4 2.4 18.5 16.4 2.5 17.3 15.4 2.7 8.7 7.7 2.7
550
72 27.0 12.9 2.3 26.0 12.7 2.4 24.8 12.3 2.6 23.9 11.9 2.8 22.3 11.5 3.0 11.2 5.7 3.1 67 25.1 16.3 2.2 23.9 16.0 2.4 22.5 15.6 2.6 21.4 15.0 2.7 19.7 14.4 2.8 9.9 7.2 2.9 62 22.8 19.5 2.2 21.5 18.9 2.4 20.2 18.3 2.4 19.3 17.2 2.6 18.1 16.1 2.7 9.1 8.1 2.8 57 22.2 20.1 2.1 21.2 19.1 2.4 20.1 18.2 2.4 19.3 17.2 2.6 18.1 16.1 2.7 9.1 8.1 2.8
650
72 27.2 13.2 2.3 26.3 13.1 2.4 25.1 12.8 2.7 24.2 12.5 2.9 22.6 12.0 3.0 11.3 6.0 3.1 67 25.4 17.1 2.3 24.2 16.8 2.4 22.9 16.5 2.6 21.7 15.9 2.8 20.0 15.3 2.9 10.0 7.7 3.0 62 23.3 20.5 2.2 22.1 20.0 2.4 20.8 18.8 2.5 20.0 17.8 2.7 18.8 16.7 2.8 9.4 8.4 2.9 57 23.0 20.8 2.2 22.0 19.9 2.4 20.8 18.8 2.5 20.0 17.8 2.7 18.8 16.7 2.8 9.4 8.4 2.9
30
600
72 34.9 15.4 2.8 33.6 15.0 3.0 32.0 14.6 3.2 29.1 14.0 3.3 27.2 13.4 3.5 13.6 6.7 3.6 67 32.3 19.1 2.7 30.7 18.6 2.9 28.9 18.0 3.1 25.9 17.3 3.2 24.0 16.6 3.3 12.0 8.3 3.4 62 29.2 22.5 2.7 27.5 21.8 2.8 25.7 21.0 3.0 23.1 20.2 3.0 21.5 19.0 3.2 10.7 9.5 3.3 57 27.7 23.7 2.6 26.5 22.6 2.8 25.2 21.5 3.0 22.9 20.3 3.0 21.5 19.0 3.2 10.7 9.5 3.3
700
72 35.3 15.9 2.9 34.1 15.6 3.1 32.5 15.2 3.3 29.7 14.7 3.4 27.7 14.1 3.7 13.8 7.1 3.8 67 32.9 20.2 2.8 31.3 19.7 3.1 29.5 19.2 3.2 26.5 18.5 3.3 24.5 17.8 3.5 12.2 8.9 3.6 62 29.9 24.0 2.7 28.2 23.3 3.1 26.4 22.5 3.1 23.9 21.2 3.2 22.5 19.9 3.4 11.2 9.9 3.5 57 29.1 24.8 2.7 27.7 23.6 3.1 26.3 22.5 3.1 23.9 21.2 3.2 22.5 19.9 3.4 11.2 10.0 3.5
800
72 35.6 16.4 3.0 34.4 16.1 3.1 32.9 15.8 3.4 30.0 15.4 3.5 28.0 14.8 3.7 14.0 7.4 3.9 67 33.3 21.1 2.9 31.8 20.8 3.1 30.0 20.3 3.3 26.9 19.7 3.4 24.8 18.9 3.6 12.4 9.5 3.7 62 30.5 25.3 2.8 28.9 24.6 3.1 27.3 23.3 3.2 24.8 22.0 3.3 23.3 20.6 3.5 11.6 10.3 3.6 57 30.1 25.6 2.8 28.8 24.5 3.1 27.3 23.3 3.2 24.8 22.0 3.3 23.3 20.6 3.5 11.7 10.3 3.6
36
800
72 40.7 18.6 3.1 39.2 18.1 3.4 37.4 17.6 3.6 35.3 16.9 3.8 33.0 16.2 4.1 16.5 8.1 4.2 67 37.6 23.0 3.0 35.8 22.4 3.3 33.7 21.7 3.5 31.4 20.9 3.7 29.1 20.0 3.9 14.5 10.0 4.0 62 34.0 27.1 3.0 32.0 26.3 3.2 30.0 25.4 3.3 28.0 24.4 3.5 26.0 22.9 3.7 13.0 11.5 3.8 57 32.4 28.5 2.9 30.9 27.3 3.1 29.3 25.9 3.3 27.8 24.5 3.5 26.0 22.9 3.7 13.0 11.5 3.8
950
72 41.2 19.2 3.2 39.8 18.8 3.4 38.0 18.3 3.7 35.9 17.8 3.9 33.5 17.1 4.2 16.8 8.5 4.3 67 38.3 24.3 3.1 36.5 23.8 3.4 34.4 23.2 3.6 32.1 22.3 3.8 29.6 21.5 4.0 14.8 10.7 4.1 62 34.9 29.0 3.0 32.9 28.1 3.4 30.8 27.2 3.4 29.0 25.5 3.6 27.2 24.0 3.8 13.6 12.0 4.0 57 33.9 29.9 3.0 32.3 28.5 3.4 30.7 27.1 3.4 29.0 25.6 3.6 27.2 24.0 3.8 13.6 12.0 4.0
1100
72 41.6 19.7 3.3 40.2 19.5 3.4 38.4 19.0 3.7 36.4 18.6 4.0 33.9 17.9 4.3 17.0 8.9 4.4 67 38.8 25.5 3.2 37.1 25.1 3.4 35.0 24.5 3.6 32.6 23.7 3.9 30.0 22.8 4.1 15.0 11.4 4.2 62 35.6 30.5 3.1 33.7 29.7 3.4 31.8 28.1 3.6 30.0 26.5 3.8 28.2 24.9 4.0 14.1 12.4 4.1 57 35.1 30.9 3.1 33.6 29.6 3.4 31.8 28.1 3.6 30.0 26.5 3.8 28.2 24.9 4.0 14.1 12.4 4.1
38H
K/H
Q
Notes:1. Net Capacities shown include a deduction for evaporator fan motor heat.2. Formulas: Leaving db= Entering - Sensible Heat Cap./(1.09 x CFM)
Leaving wb= wb corresponding to air leaving coil (hwb)h wb leaving = hwb entering - Total Cap(Btuh)/(4.5 X CFM) 3. Direct Interpolation Permissible. Do not extrapolate.
10
Detailed Performance Data – Matching 38HK with 42TX
Nom Cap.
Mbtuh
Evaporator Air
CONDENSER AIR ENTERING Deg. F
75 85 95 105 115 120
CFM EWB
Capacity MBtuh Tot Sys Kw
Capacity MBtuh Tot Sys Kw
Capacity MBtuh Tot Sys Kw
Capacity MBtuh Tot Sys Kw
Capacity MBtuh Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen
48
1100
72 51.1 24.3 3.9 49.3 23.7 4.2 47.0 23.0 4.4 45.3 22.1 4.7 42.3 21.2 5.0 21.2 10.6 5.2 67 47.3 30.1 3.8 45.0 29.4 4.0 42.3 28.4 4.3 40.4 27.3 4.5 37.4 26.2 4.8 18.7 13.1 4.9 62 42.8 35.5 3.7 40.3 34.4 3.9 37.8 33.2 4.1 36.0 31.9 4.3 33.4 30.0 4.5 16.7 15.0 4.7 57 40.7 37.4 3.6 38.9 35.7 3.9 36.9 33.9 4.1 35.7 32.0 4.3 33.4 30.0 4.5 16.7 15.0 4.7
1250
72 51.8 25.1 4.0 50.0 24.7 4.2 47.7 24.0 4.5 46.2 23.3 4.8 43.0 22.3 5.1 21.5 11.2 5.3 67 48.2 31.8 3.9 45.9 31.1 4.2 43.3 30.3 4.4 41.2 29.2 4.6 38.1 28.1 4.9 19.0 14.0 5.0 62 43.8 37.9 3.8 41.4 36.8 4.2 38.8 35.6 4.2 37.2 33.4 4.4 35.0 31.4 4.7 17.5 15.7 4.8 57 42.6 39.1 3.7 40.6 37.3 4.2 38.6 35.4 4.2 37.2 33.4 4.4 35.0 31.4 4.7 17.5 15.7 4.8
1400
72 52.3 25.8 4.1 50.5 25.5 4.2 48.3 24.9 4.6 46.7 24.3 4.9 43.6 23.4 5.2 21.8 11.7 5.4 67 48.8 33.3 4.0 46.6 32.8 4.2 44.0 32.1 4.5 41.8 31.0 4.7 38.6 29.8 5.0 19.3 14.9 5.1 62 44.7 40.0 3.9 42.4 38.9 4.2 40.0 36.7 4.4 38.6 34.7 4.6 36.2 32.6 4.8 18.1 16.3 5.0 57 44.1 40.5 3.8 42.2 38.7 4.2 40.0 36.7 4.4 38.6 34.7 4.6 36.3 32.6 4.8 18.1 16.3 5.0
60
1300
72 63.8 30.3 5.0 61.5 29.6 5.4 58.6 28.7 5.7 56.6 27.6 6.4 52.9 26.4 6.9 26.5 13.2 7.1 67 59.0 37.6 4.9 56.1 36.6 5.2 52.8 35.4 5.5 50.5 34.1 6.2 46.7 32.7 6.5 23.4 16.3 6.7 62 53.4 44.3 4.7 50.2 42.9 5.0 47.1 41.4 5.3 45.0 39.8 5.9 41.8 37.4 6.2 20.9 18.7 6.4 57 50.8 46.6 4.7 48.5 44.5 5.0 46.0 42.2 5.2 44.6 40.0 5.9 41.8 37.4 6.2 20.9 18.7 6.4
1450
72 64.6 31.3 5.1 62.4 30.8 5.5 59.5 29.9 5.8 57.7 29.0 6.6 53.8 27.8 7.0 26.9 13.9 7.3 67 60.1 39.7 5.0 57.3 38.8 5.5 54.0 37.8 5.7 51.5 36.5 6.4 47.6 35.0 6.7 23.8 17.5 6.9 62 54.7 47.3 4.8 51.6 45.8 5.5 48.3 44.4 5.5 46.5 41.7 6.1 43.7 39.1 6.4 21.8 19.6 6.7 57 53.1 48.8 4.8 50.7 46.5 5.5 48.2 44.2 5.5 46.5 41.7 6.1 43.7 39.2 6.4 21.8 19.6 6.7
1600
72 65.2 32.2 5.2 63.0 31.8 5.5 60.2 31.1 6.0 58.4 30.3 6.7 54.4 29.2 7.1 27.2 14.6 7.4 67 60.9 41.6 5.1 58.1 40.9 5.5 54.9 40.0 5.8 52.3 38.7 6.5 48.2 37.2 6.9 24.1 18.6 7.1 62 55.8 49.8 5.0 52.8 48.5 5.5 49.9 45.8 5.7 48.2 43.2 6.3 45.3 40.6 6.7 22.6 20.3 6.9 57 55.0 50.5 4.9 52.6 48.3 5.5 49.9 45.8 5.7 48.2 43.2 6.3 45.3 40.6 6.7 22.7 20.3 6.9
Nom Cap.
Mbtuh
Evaporator Air
CONDENSER AIR ENTERING Deg. F 75 85 95 105 115 120
CFM EWB
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen
48
1250
72 52.9 24.3 4.3 51.0 23.7 4.6 48.6 23.0 4.9 45.2 22.1 5.1 42.2 21.2 5.4 21.1 10.6 5.6 67 48.9 30.1 4.2 46.5 29.4 4.5 43.8 28.4 4.8 40.2 27.3 4.9 37.2 26.2 5.2 18.6 13.1 5.3 62 44.2 35.5 4.1 41.6 34.4 4.3 39.0 33.2 4.6 35.9 31.9 4.7 33.3 30.0 4.9 16.6 15.0 5.1 57 42.1 37.4 4.0 40.2 35.7 4.3 38.1 33.9 4.5 35.5 32.0 4.6 33.3 30.0 4.9 16.7 15.0 5.1
1440
72 53.6 25.1 4.4 51.7 24.7 4.7 49.4 24.0 5.0 46.0 23.3 5.2 42.9 22.3 5.5 21.4 11.2 5.7 67 49.8 31.8 4.3 47.5 31.1 4.7 44.8 30.3 4.9 41.1 29.2 5.0 37.9 28.1 5.3 19.0 14.0 5.4 62 45.3 37.9 4.2 42.8 36.8 4.7 40.1 35.6 4.7 37.1 33.4 4.8 34.8 31.4 5.1 17.4 15.7 5.2 57 44.1 39.1 4.1 42.0 37.3 4.7 39.9 35.4 4.7 37.1 33.4 4.8 34.8 31.4 5.1 17.4 15.7 5.2
1550
72 54.1 25.8 4.5 52.2 25.5 4.7 49.9 24.9 5.1 46.6 24.3 5.3 43.4 23.4 5.6 21.7 11.7 5.8 67 50.5 33.3 4.4 48.2 32.8 4.7 45.5 31.8 5.0 41.7 31.0 5.1 38.5 29.8 5.4 19.2 14.9 5.6 62 46.2 40.0 4.3 43.8 38.9 4.7 41.4 36.7 4.9 38.5 34.7 5.0 36.1 32.6 5.3 18.1 16.3 5.4 57 45.6 40.5 4.2 43.6 38.7 4.7 41.4 36.7 4.9 38.5 34.7 5.0 36.1 32.6 5.3 18.1 16.3 5.4
60
1450
72 67.8 32.6 5.2 65.4 31.9 5.6 62.2 30.9 6.0 55.9 29.7 6.2 52.2 28.4 6.6 26.1 14.2 6.9 67 62.7 40.5 5.1 59.6 39.4 5.5 56.1 38.1 5.8 49.8 36.7 6.0 46.1 35.2 6.3 23.0 17.6 6.5 62 56.7 47.7 5.0 53.4 46.2 5.3 50.0 44.6 5.6 44.4 42.8 5.7 41.2 40.3 6.0 20.6 20.2 6.2 57 53.9 50.2 4.9 51.5 47.9 5.2 48.9 45.5 5.5 44.0 43.0 5.7 41.2 40.3 6.0 20.6 20.2 6.2
1600
72 68.7 33.7 5.4 66.3 33.1 5.7 63.3 32.3 6.1 56.9 31.3 6.3 53.1 30.0 6.7 26.5 15.0 7.0 67 63.9 42.7 5.2 60.8 41.8 5.7 57.4 40.7 6.0 50.8 39.3 6.2 46.9 37.7 6.4 23.5 18.9 6.6 62 58.1 50.9 5.1 54.8 49.4 5.7 51.4 47.8 5.7 45.9 44.9 5.9 43.1 42.2 6.2 21.5 21.1 6.4 57 56.5 52.5 5.0 53.8 50.1 5.7 51.2 47.6 5.7 45.9 44.9 5.9 43.1 42.2 6.2 21.6 21.1 6.4
1800
72 69.3 34.7 5.5 66.9 34.2 5.7 64.0 33.5 6.3 57.6 32.6 6.5 53.7 31.4 6.9 26.9 15.7 7.1 67 64.7 44.8 5.4 61.7 44.1 5.7 58.3 43.1 6.1 51.6 41.7 6.3 47.6 40.1 6.6 23.8 20.0 6.8 62 59.2 53.7 5.2 56.1 52.2 5.7 53.0 49.3 5.9 47.6 46.6 6.1 44.7 43.7 6.4 22.3 21.9 6.6 57 58.4 54.4 5.2 55.9 52.0 5.7 53.0 49.3 5.9 47.6 46.6 6.1 44.7 43.7 6.4 22.4 21.9 6.6
Matching 38HK with 42MX
38H
K/H
Q
11
Detailed Performance Data – Matching 38HK with FB4A
Nom Cap.
MBtuh
Evapora
to
r Air
CONDENSER AIR ENTERING Deg. F
75 85 95 105 115 120
CFM, BP EWB
Capacity
MBtuh Tot Sys Kw
Capacity
MBtuh Tot Sys Kw
Capacity
MBtuh Tot Sys Kw
Capacity
MBtuh Tot Sys Kw
Capacity
MBtuh Tot Sys Kw
Capacity
MBtuh Tot Sys Kw
Tot
Sen Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen
18
525
72 22.5 11.6 2.0 21.7 11.3 2.2 20.6 11.0 2.3 20.1 10.6 2.7 19.3 10.1 2.9 18.3 9.7 3.0 67 20.8 14.4 2.0 19.8 14.0 2.1 18.6 13.5 2.3 18.0 13.0 2.6 17.1 12.5 2.8 16.1 12.1 2.8 62 18.8 16.9 1.9 17.7 16.4 2.0 16.6 15.8 2.2 16.0 15.2 2.5 15.3 14.3 2.6 14.6 13.6 2.7 57 17.9 17.8 1.9 17.1 17.0 2.0 16.2 16.1 2.1 15.9 15.3 2.5 15.3 14.3 2.6 14.6 13.6 2.7
600
72 22.7 12.0 2.1 22.0 11.8 2.2 21.0 11.4 3.0 20.5 11.1 2.8 19.7 10.6 2.9 18.6 10.3 3.1 67 21.2 15.2 2.0 20.2 14.8 2.2 19.0 14.4 2.3 18.3 13.9 2.7 17.4 13.4 2.8 16.4 13.0 2.9 62 19.2 18.1 2.0 18.2 17.5 2.1 17.0 17.0 2.2 16.6 15.9 2.6 16.0 15.0 2.7 15.2 14.3 2.8 57 18.7 18.6 2.0 17.8 17.8 2.1 17.0 16.9 2.2 16.5 15.9 2.6 16.0 15.0 2.7 15.2 14.3 2.8
675
72 23.0 12.3 2.1 22.2 12.1 2.3 21.2 11.9 2.4 20.8 11.6 2.8 19.9 11.1 2.9 18.9 10.8 3.0 67 21.4 15.9 2.1 20.5 15.6 2.2 19.3 15.3 2.4 18.6 14.8 2.7 17.6 14.2 2.8 16.6 13.8 2.9 62 19.6 19.0 2.0 18.6 18.5 2.2 17.6 17.5 2.3 17.2 16.5 2.6 16.6 15.5 2.7 15.8 14.8 2.8 57 19.4 19.3 2.0 18.5 18.5 2.2 17.6 17.5 2.3 17.1 16.5 2.6 16.6 15.5 2.7 15.8 14.8 2.8
24
550
72 27.8 13.4 2.3 26.8 13.1 2.5 25.5 12.7 2.7 24.1 12.2 2.9 23.4 11.7 3.1 22.1 11.2 3.2 67 25.7 16.6 2.3 24.4 16.2 2.4 23.0 15.6 2.6 21.5 15.0 2.8 20.6 14.4 2.9 19.4 14.0 3.0 62 23.2 19.6 2.2 21.9 18.9 2.4 20.5 18.3 2.5 19.1 17.6 2.6 18.4 16.5 2.8 17.6 15.8 2.9 57 22.1 20.6 2.2 21.1 19.6 2.3 20.0 18.6 2.5 19.0 17.6 2.6 18.4 16.5 2.8 17.6 15.8 2.9
625
72 28.1 13.8 2.4 27.2 13.6 2.6 25.9 13.2 2.7 24.5 12.8 2.9 23.7 12.3 3.1 22.5 11.9 3.2 67 26.2 17.5 2.3 24.9 17.2 2.5 23.5 16.7 2.7 21.9 16.1 2.9 21.0 15.5 3.0 19.8 15.0 3.1 62 23.8 20.9 2.3 22.5 20.2 2.4 21.0 19.6 2.6 19.8 18.4 2.7 19.3 17.3 2.9 18.4 16.5 3.0 57 23.1 21.5 2.3 22.1 20.5 2.4 21.0 19.5 2.6 19.8 18.4 2.7 19.3 17.3 2.9 18.4 16.5 3.0
700
72 28.4 14.2 2.4 27.4 14.0 2.6 26.2 13.7 2.8 24.8 13.4 3.0 24.0 12.9 3.2 22.8 12.5 3.3 67 26.5 18.3 2.4 25.3 18.1 2.5 23.9 17.7 2.7 22.2 17.1 2.9 21.3 16.4 3.1 20.1 16.0 3.2 62 24.3 22.0 2.3 23.0 21.4 2.5 21.7 20.2 2.7 20.5 19.1 2.8 20.0 17.9 3.0 19.1 17.1 3.1 57 23.9 22.3 2.3 22.9 21.3 2.5 21.7 20.2 2.7 20.5 19.1 2.8 20.0 17.9 3.0 19.1 17.1 3.1
30
1000
72 36.0 19.1 3.2 34.8 18.6 3.5 33.1 18.1 3.7 31.2 17.4 3.9 29.2 16.6 4.1 27.7 16.0 4.3 67 33.4 23.7 3.2 31.7 23.1 3.4 29.8 22.3 3.6 27.8 21.4 3.8 25.8 20.6 3.9 24.3 20.0 4.1 62 30.1 27.9 3.1 28.4 27.0 3.3 26.6 26.1 3.5 24.8 25.0 3.6 23.0 23.6 3.8 22.0 22.5 3.9 57 28.7 29.3 3.0 27.4 28.0 3.2 26.0 26.6 3.4 24.6 25.2 3.5 23.0 23.6 3.8 22.0 22.5 3.9
1150
72 36.5 19.7 3.3 35.3 19.4 3.6 33.6 18.9 3.8 31.8 18.3 4.0 29.7 17.5 4.2 28.1 17.0 4.4 67 34.0 25.0 3.2 32.4 24.5 3.5 30.5 23.8 3.7 28.4 23.0 3.9 26.3 22.0 4.0 24.7 21.4 4.2 62 30.9 29.8 3.2 29.1 28.9 3.4 27.3 27.9 3.6 25.7 26.3 3.7 24.1 24.6 3.9 23.0 23.5 4.0 57 30.0 30.7 3.1 28.6 29.3 3.4 27.2 27.8 3.6 25.7 26.2 3.7 24.1 24.6 3.9 23.0 23.5 4.0
1300
72 36.8 20.3 3.4 35.6 20.0 3.6 34.0 19.6 3.9 32.2 19.1 4.1 30.0 18.4 4.3 28.5 17.8 4.5 67 34.4 26.2 3.3 32.8 25.8 3.5 31.0 25.2 3.8 28.8 24.4 3.9 26.6 23.4 4.1 25.1 22.8 4.3 62 31.5 31.4 3.2 29.9 30.5 3.5 28.2 28.8 3.7 26.6 27.2 3.8 25.0 25.6 4.0 23.8 24.3 4.2 57 31.1 31.8 3.2 29.7 30.4 3.5 28.2 28.8 3.7 26.6 27.2 3.8 25.0 25.6 4.0 23.8 24.3 4.2
36
1050
72 42.3 21.2 3.5 40.8 20.8 3.7 38.9 20.1 4.0 37.9 19.4 4.2 35.4 18.5 4.4 33.5 17.9 4.6 67 39.1 26.3 3.4 37.2 25.7 3.6 35.0 24.8 3.9 33.7 23.9 4.0 31.2 22.9 4.2 29.4 22.2 4.4 62 35.4 31.0 3.3 33.3 30.1 3.5 31.2 29.0 3.7 30.1 27.9 3.8 27.9 26.2 4.0 26.6 25.0 4.2 57 33.7 32.7 3.3 32.1 31.2 3.5 30.5 29.6 3.7 29.8 28.0 3.8 27.9 26.2 4.0 26.6 25.0 4.2
1200
72 42.9 21.9 3.6 41.4 21.6 3.8 39.5 21.0 4.1 38.6 20.3 4.3 36.0 19.5 4.5 34.1 18.9 4.7 67 39.9 27.8 3.5 38.0 27.2 3.7 35.8 26.5 4.0 34.4 25.6 4.1 31.8 24.5 4.3 30.0 23.8 4.5 62 36.3 33.1 3.4 34.2 32.1 3.6 32.1 31.1 3.8 31.1 29.2 3.9 29.2 27.4 4.2 27.9 26.2 4.3 57 35.2 34.2 3.4 33.6 32.6 3.6 31.9 31.0 3.8 31.1 29.2 3.9 29.2 27.4 4.2 27.9 26.2 4.3
1350
72 43.2 22.6 3.7 41.8 22.3 3.9 39.9 21.8 4.2 39.1 21.3 4.3 36.4 20.4 4.6 34.5 19.9 4.8 67 40.4 29.1 3.6 38.5 28.7 3.8 36.4 28.0 4.1 35.0 27.1 4.2 32.3 26.1 4.4 30.4 25.3 4.6 62 37.0 34.9 3.5 35.0 34.0 3.7 33.1 32.1 4.0 32.3 30.3 4.1 30.3 28.5 4.3 28.9 27.1 4.5 57 36.5 35.4 3.5 34.9 33.9 3.7 33.1 32.1 4.0 32.2 30.3 4.1 30.3 28.5 4.3 28.9 27.1 4.5
38H
K/H
Q
Multipliers to Determine the Performance With Other Indoor CoilsCondenser Evaporator Cooling Cap. Power
N. Cap. MBtuh N. Cap. MBtuh 18 24 1.10 1.0724 30 1.05 1.0530 36 1.03 1.0536 42 1.04 1.0548 60 1.05 1.0560 70 1.02 1.03
Notes:1. Net Capacities shown include a deduction for evaporator fanmotor heat.2. Formulas:Leaving db= Entering - Sensible Heat Cap./(1.09 x CFM)
Leaving wb= wb corresponding to air leaving coil (hwb)h wb leaving = hwb entering - Total Cap(Btuh)/(4.5 X CFM) 3. Direct Interpolation Permissible. Do not extrapolate.
12
Detailed Performance Data – Matching 38HK with FB4A
Evaporator Air
CONDENSER AIR ENTERING Deg. F
Capacity Capacity Capacity Capacity Capacity Capacity
Tot
79.2 37.7 76.4 36.8 72.7 35.7 68.6 34.3 64.1 32.9 60.7 31.773.3 46.7 69.7 45.5 65.5 44.0 61.2 42.4 56.6 40.7 53.3 39.466.2 55.1 62.3 53.3 58.5 51.5 54.5 49.4 50.6 46.5 48.3 44.463.0 57.9 60.2 55.3 57.1 52.5 54.0 49.7 50.6 46.6 48.3 44.480.2 38.9 77.4 38.2 73.9 37.2 69.9 36.1 65.2 34.6 61.8 33.574.6 49.3 71.1 48.3 67.0 45.3 57.6 43.6 54.3 42.367.9 58.8 64.0 57.0 60.0 55.2 56.4 51.9 52.9 48.7 50.5 46.466.0 60.7 62.9 57.8 59.8 55.0 56.4 51.8 52.9 48.7 50.5 46.4 8.280.9 40.0 78.2 39.5 4.7 38.7 70.8 37.7 66.0 36.3 62.6 35.275.5 51.7 72.1 50.9 68.1 49.8 63.4 48.1 58.5 46.3 55.1 45.069.2 62.0 65.6 60.3 61.9 57.0 58.5 53.8 54.9 50.5 52.3 48.168.3 62.8 5.3 60.1 61.9 57.0 58.4 53.7 54.9 50.5 52.3 48.1 8.5
Nom Cap.
MBtuh
Evaporator Air
CONDENSER AIR ENTERING Deg. F 75 85 95 105 115 120
CFM EWB
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen
48
1300
72 54.9 28.7 4.6 53.0 28.1 5.0 50.5 27.2 5.3 47.6 26.2 5.4 44.5 25.0 5.7 42.2 24.1 6.0 67 50.8 35.6 4.5 48.4 34.7 4.8 45.5 33.6 5.1 42.5 32.3 5.2 39.3 31.0 5.5 37.0 30.1 5.6 62 46.0 42.0 4.4 43.3 40.6 4.6 40.6 39.2 4.9 37.8 37.7 4.9 35.1 35.5 5.2 33.5 33.8 5.4 57 43.7 44.1 4.3 41.8 42.2 4.6 39.6 40.0 4.9 37.5 37.9 4.9 35.1 35.5 5.2 33.5 33.8 5.4
1500
72 55.7 29.7 4.7 53.8 29.1 5.1 51.3 28.4 5.4 48.5 27.5 5.5 45.2 26.4 5.9 42.9 25.5 6.1 67 51.8 37.6 4.6 49.3 36.8 4.9 46.5 35.8 5.3 43.3 34.5 5.3 39.5 33.2 5.6 37.7 32.2 5.8 62 47.1 44.8 4.5 44.4 43.4 4.8 41.6 42.0 5.1 39.1 39.5 5.1 36.7 37.1 5.4 35.0 35.4 5.6 57 45.8 46.2 4.4 43.7 44.1 4.8 41.5 41.9 5.1 39.1 39.5 5.1 36.7 37.1 5.4 35.0 35.4 5.6
1700
72 56.2 30.5 4.8 54.2 30.1 5.2 51.9 29.5 5.5 49.1 28.7 5.6 45.8 27.6 6.0 43.4 26.8 6.2 67 52.4 39.4 4.7 50.0 38.8 5.0 47.3 37.9 5.4 44.0 36.7 5.4 40.6 35.2 5.7 38.2 34.2 5.9 62 48.0 47.2 4.6 45.5 45.9 4.9 43.0 43.4 5.2 40.6 41.0 5.3 38.1 38.5 5.6 36.3 36.6 5.8 57 47.4 47.8 4.6 45.3 45.8 4.9 43.0 43.4 5.2 40.5 40.9 5.3 38.1 38.5 5.6 36.3 36.6 5.8
60
1450
72 67.1 32.3 5.7 64.7 31.6 6.1 61.6 30.6 6.5 59.4 29.5 6.6 55.5 28.2 7.1 52.5 27.2 7.3 67 62.1 40.1 5.5 59.1 39.1 5.9 55.6 37.8 6.3 52.9 36.4 6.4 49.0 34.9 6.7 46.1 33.8 6.9 62 56.1 47.3 5.4 52.9 45.8 5.7 49.6 44.2 6.1 47.1 42.4 6.1 43.8 39.9 6.4 41.8 38.1 6.6 57 53.4 49.7 5.3 51.0 47.5 5.7 48.4 45.1 6.0 46.7 42.6 6.1 43.8 40.0 6.4 41.8 38.1 6.6
1650
72 68.0 33.4 5.8 65.7 32.8 6.2 62.6 32.0 6.7 60.5 31.0 6.8 56.4 29.7 7.2 53.4 28.8 7.5 67 63.3 42.3 5.7 60.3 41.5 6.1 56.8 40.3 6.5 54.0 38.9 6.6 49.8 37.4 6.9 47.0 36.3 7.1 62 57.5 50.4 5.5 54.3 48.9 5.9 50.9 47.4 6.2 48.8 44.5 6.3 45.8 41.8 6.6 43.7 39.9 6.9 57 55.9 52.1 5.5 53.3 49.6 5.9 50.7 47.2 6.2 48.7 44.5 6.3 45.8 41.8 6.6 43.7 39.8 6.9
1850
72 68.6 34.4 5.9 66.3 33.9 6.4 63.3 33.2 6.8 61.2 32.4 6.9 57.1 31.1 7.4 54.1 30.2 7.6 67 64.0 44.3 5.8 61.1 43.7 6.2 57.7 42.7 6.6 54.8 41.3 6.7 50.5 39.7 7.1 47.6 38.6 7.3 62 58.7 53.2 5.7 55.6 51.7 6.0 52.5 48.9 6.4 50.5 46.1 6.5 47.5 43.3 6.9 45.2 41.3 7.1 57 57.9 53.9 5.6 55.4 51.6 6.0 52.5 48.9 6.4 50.5 46.1 6.5 47.5 43.3 6.9 45.2 41.3 7.1
79.2 37.7 6.5 76.4 36.8 7.0 72.7 35.7 7.4 68.6 34.3 8.0 64.1 32.9 8.5 60.7 31.7 8.873.3 46.7 6.3 69.7 45.5 6.8 65.5 44.0 7.2 61.2 42.4 7.7 56.6 40.7 8.1 53.3 39.4 8.366.2 55.1 6.1 62.3 53.3 6.5 58.5 51.5 6.9 54.5 49.4 7.3 50.6 46.5
73.947.0 7.4
67.9 58.8 6.3 64.0 57.0 6.7 60.0 55.2 7.1 56.4 51.9 7.5 52.9 48.7 8.0 50.5 46.4 8.266.0 60.7 6.2 62.9 57.8 6.7 59.8 55.0 7.1 56.4 51.8 7.5 52.9 48.7 8.0 50.5 46.4 8.280.9 40.0 6.8 78.2 39.5 7.3 4.7 38.7 7.8 70.8 37.7 8.3 66.0 36.3 8.8 62.6 35.2 9.175.5 51.7 6.6 72.1 50.9 7.1 68.1 49.8 7.6 58.5 8.5 55.1 45.0 8.7
6.5 65.6 60.3 6.9 7.8 54.9 50.5 8.26.4 5.3 60.1 6.9 57.0 7.4 58.4 53.7 7.8 54.9 50.5 8.2 52.3 8.5
70
1300
72 79.2 37.7 6.5 76.4 36.8 7.0 72.7 35.7 7.4 68.6 34.3 8.0 64.1 32.9 8.5 60.7 31.7 8.8 67 73.3 46.7 6.3 69.7 45.5 6.8 65.5 44.0 7.2 61.2 42.4 7.7 56.6 40.7 8.1 53.3 39.4 8.3 62 66.2 55.1 6.1 62.3 53.3 6.5 58.5 51.5 6.9 54.5 49.4 7.3 50.6 46.5 7.7 48.3 44.4 7.9 57 63.0 57.9 6.1 60.2 55.3 6.5 57.1 52.5 6.8 54.0 49.7 7.3 50.6 46.6 7.7 48.3 44.4 8.0
1500
72 80.2 38.9 6.6 77.4 38.2 7.1 73.9 37.2 7.6 69.9 36.1 8.1 65.2 34.6 8.6 61.8 33.5 8.9 67 74.6 49.3 6.5 71.1 48.3 6.9 67.0 47.0 7.4 62.4 45.3 7.9 57.6 43.6 8.3 54.3 42.3 8.5 62 67.9 58.8 6.3 64.0 57.0 6.7 60.0 55.2 7.1 56.4 51.9 7.5 52.9 48.7 8.0 50.5 46.4 8.2 57 66.0 60.7 6.2 62.9 57.8 6.7 59.8 55.0 7.1 56.4 51.8 7.5 52.9 48.7 8.0 50.5 46.4 8.2
1700
72 80.9 40.0 6.8 78.2 39.5 7.3 74.7 38.7 7.8 70.8 37.7 8.3 66.0 36.3 8.8 62.6 35.2 9.1 67 75.5 51.7 6.6 72.1 50.9 7.1 68.1 49.8 7.6 63.4 48.1 8.0 58.5 46.3 8.5 55.1 45.0 8.7 62 69.2 62.0 6.5 65.6 60.3 6.9 61.9 57.0 7.4 58.5 53.8 7.8 54.9 50.5 8.2 52.3 48.1 8.5 57 68.3 62.8 6.4 65.3 60.1 6.9 61.9 57.0 7.4 58.4 53.7 7.8 54.9 50.5 8.2 52.3 48.1 8.5
38H
K/H
Q
13
Detailed Performance Data – Matching 38HK with Ceiling Cassette
Nom Cap.
Mbtuh
Evaporator Air
CONDENSER AIR ENTERING Deg. F 75 85 95 105 115 120
CFM EWB
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen
18
300
72 20.9 9.1 1.8 20.2 8.9 2.0 19.2 8.6 2.1 18.4 8.3 2.3 17.2 7.9 2.5 8.6 3.9 2.6 67 19.4 11.2 1.8 18.4 10.9 1.9 17.3 10.6 2.0 16.4 10.2 2.2 15.2 9.8 2.4 7.6 4.9 2.4 62 17.5 13.2 1.7 16.5 12.8 1.9 15.4 12.4 2.0 14.6 11.9 2.1 13.6 11.2 2.2 6.8 5.6 2.3 57 16.6 13.9 1.7 15.9 13.3 1.8 15.1 12.6 1.9 14.5 11.9 2.1 13.6 11.2 2.2 6.8 5.6 2.3
375
72 21.2 9.4 1.9 20.5 9.2 2.0 19.5 9.0 3.0 18.8 8.7 2.4 17.5 8.3 2.5 8.8 4.2 2.6 67 19.7 11.9 1.8 18.8 11.6 2.0 17.7 11.3 2.1 16.8 10.9 2.3 15.5 10.5 2.4 7.7 5.2 2.5 62 17.9 14.1 1.8 16.9 13.7 1.9 15.9 13.3 2.0 15.1 12.5 2.2 14.2 11.7 2.3 7.1 5.9 2.4 57 17.4 14.6 1.8 16.6 13.9 1.9 15.8 13.2 2.0 15.2 12.5 2.2 14.2 11.7 2.3 7.1 5.9 2.4
425
72 21.4 9.6 1.9 20.7 9.5 2.1 19.7 9.3 2.2 19.0 9.1 2.4 17.7 8.7 2.6 8.9 4.4 2.7 67 20.0 12.4 1.9 19.1 12.2 2.0 18.0 12.0 2.1 17.0 11.6 2.3 15.7 11.1 2.4 7.8 5.6 2.5 62 18.3 14.9 1.8 17.3 14.5 2.0 16.4 13.7 2.1 15.7 12.9 2.3 14.7 12.1 2.4 7.4 6.1 2.5 57 18.0 15.1 1.8 17.3 14.4 2.0 16.4 13.7 2.1 15.7 12.9 2.3 14.8 12.1 2.4 7.4 6.1 2.5
24
325
72 26.7 12.7 2.2 25.8 12.4 2.4 24.6 12.0 2.5 23.2 11.6 2.8 21.7 11.1 3.0 10.8 5.5 3.1 67 24.7 15.8 2.2 23.5 15.4 2.3 22.1 14.9 2.5 20.7 14.3 2.7 19.1 13.7 2.9 9.6 6.9 2.9 62 22.4 18.6 2.1 21.1 18.0 2.2 19.7 17.4 2.4 18.4 16.7 2.6 17.1 15.7 2.7 8.5 7.8 2.8 57 21.3 19.5 2.1 20.3 18.7 2.2 19.3 17.7 2.3 18.3 16.8 2.6 17.1 15.7 2.7 8.5 7.9 2.8
400
72 27.1 13.1 2.3 26.2 12.9 2.4 25.0 12.6 2.6 23.6 12.2 2.9 22.0 11.7 3.1 11.0 5.8 3.2 67 25.2 16.6 2.2 24.0 16.3 2.4 22.6 15.9 2.5 21.1 15.3 2.8 19.5 14.7 2.9 9.7 7.3 3.0 62 22.9 19.8 2.2 21.6 19.2 2.3 20.3 18.6 2.4 19.0 17.5 2.7 17.9 16.4 2.8 8.9 8.2 2.9 57 22.3 20.5 2.1 21.2 19.5 2.3 20.2 18.5 2.4 19.1 17.5 2.7 17.9 16.4 2.8 8.9 8.2 2.9
450
72 27.3 13.5 2.3 26.4 13.3 2.5 25.2 13.0 2.7 23.9 12.7 2.9 22.3 12.2 3.1 11.1 6.1 3.2 67 25.5 17.4 2.3 24.4 17.2 2.4 23.0 16.8 2.6 21.4 16.2 2.8 19.7 15.6 3.0 9.9 7.8 3.1 62 23.4 20.9 2.2 22.1 20.3 2.4 20.9 19.2 2.5 19.7 18.1 2.8 18.5 17.0 2.9 9.3 8.5 3.0 57 23.1 21.2 2.2 22.1 20.3 2.4 20.9 19.2 2.5 19.8 18.1 2.8 18.6 17.0 2.9 9.3 8.5 3.0
Evap &
30 Cond
570
72 32.0 13.5 2.7 30.8 13.2 2.9 29.4 12.8 3.1 28.0 12.3 3.4 26.1 11.7 3.6 13.1 5.9 3.7 67 29.6 16.7 2.7 28.1 16.3 2.9 26.5 15.7 3.0 24.9 15.1 3.2 23.1 14.5 3.4 11.5 7.3 3.5 62 26.7 19.7 2.6 25.2 19.1 2.8 23.6 18.4 2.9 22.2 17.7 3.1 20.6 16.6 3.2 10.3 8.3 3.3 57 25.4 20.7 2.6 24.3 19.8 2.7 23.1 18.8 2.9 22.0 17.8 3.1 20.6 16.6 3.2 10.3 8.3 3.4
650
72 32.4 13.9 2.8 31.3 13.7 3.0 29.8 13.3 3.2 28.5 12.9 3.4 26.6 12.4 3.6 13.3 6.2 3.8 67 30.1 17.6 2.7 28.7 17.3 2.9 27.1 16.8 3.1 25.5 16.2 3.3 23.5 15.6 3.5 11.8 7.8 3.6 62 27.4 21.0 2.7 25.8 20.4 2.8 24.2 19.7 3.0 23.0 18.5 3.2 21.6 17.4 3.4 10.8 8.7 3.5 57 26.6 21.7 2.6 25.4 20.7 2.8 24.1 19.7 3.0 23.0 18.5 3.2 21.6 17.4 3.4 10.8 8.7 3.5
750
72 32.7 14.3 2.9 31.6 14.1 3.1 30.2 13.8 3.3 28.9 13.5 3.5 26.9 13.0 3.7 13.5 6.5 3.9 67 30.5 18.5 2.8 29.1 18.2 3.0 27.5 17.8 3.2 25.8 17.2 3.4 23.8 16.5 3.6 11.9 8.3 3.7 62 27.9 22.2 2.7 26.5 21.6 2.9 25.0 20.4 3.1 23.8 19.2 3.3 22.4 18.1 3.5 11.2 9.0 3.6 57 27.6 22.4 2.7 26.4 21.5 2.9 25.0 20.4 3.1 23.8 19.2 3.3 22.4 18.1 3.5 11.2 9.0 3.6
36 Evap
& 36
Cond
570
72 34.9 14.0 3.0 33.6 13.7 3.2 32.0 13.3 3.4 30.5 12.8 3.7 28.5 12.2 3.9 14.3 6.1 4.0 67 32.3 17.4 2.9 30.7 17.0 3.1 28.9 16.4 3.3 27.2 15.8 3.5 25.2 15.1 3.7 12.6 7.6 3.8 62 29.2 20.5 2.8 27.5 19.9 3.0 25.7 19.2 3.2 24.2 18.4 3.4 22.5 17.3 3.5 11.3 8.7 3.7 57 27.7 21.6 2.8 26.5 20.6 3.0 25.2 19.6 3.1 24.0 18.5 3.3 22.5 17.3 3.5 11.3 8.7 3.7
650
72 35.3 14.5 3.1 34.1 14.2 3.3 32.5 13.9 3.5 31.1 13.4 3.7 29.0 12.9 4.0 14.5 6.4 4.1 67 32.9 18.4 3.0 31.3 18.0 3.2 29.5 17.5 3.4 27.8 16.9 3.6 25.6 16.2 3.8 12.8 8.1 3.9 62 29.9 21.9 2.9 28.2 21.2 3.1 26.4 20.5 3.3 25.1 19.3 3.5 23.5 18.1 3.7 11.8 9.1 3.8 57 29.1 22.6 2.9 27.7 21.5 3.1 26.3 20.5 3.3 25.1 19.3 3.5 23.6 18.1 3.7 11.8 9.1 3.8
750
72 35.6 14.9 3.1 34.4 14.7 3.3 32.9 14.4 3.6 31.5 14.0 3.8 29.4 13.5 4.1 14.7 6.8 4.2 67 33.3 19.2 3.1 31.8 18.9 3.3 30.0 18.5 3.5 28.2 17.9 3.7 26.0 17.2 3.9 13.0 8.6 4.0 62 30.5 23.1 3.0 28.9 22.5 3.2 27.3 21.2 3.4 26.0 20.0 3.6 24.4 18.8 3.8 12.2 9.4 3.9 57 30.1 23.4 3.0 28.8 22.4 3.2 27.3 21.2 3.4 26.0 20.0 3.6 24.4 18.8 3.8 12.2 9.4 3.9
48 Evap
& 36
Cond
680
72 37.2 16.2 3.1 35.9 15.8 3.3 34.2 15.3 3.5 33.2 14.8 3.9 31.0 14.1 4.1 15.5 7.1 4.3 67 34.4 20.1 3.0 32.7 19.6 3.2 30.8 18.9 3.4 29.6 18.2 3.7 27.4 17.5 3.9 13.7 8.7 4.0 62 31.1 23.7 2.9 29.3 22.9 3.1 27.5 22.1 3.3 26.4 21.2 3.5 24.5 20.0 3.7 12.2 10.0 3.9 57 29.6 24.9 2.9 28.3 23.8 3.1 26.8 22.6 3.3 26.2 21.4 3.5 24.5 20.0 3.7 12.3 10.0 3.9
830
72 37.7 16.7 3.2 36.4 16.4 3.4 34.7 16.0 3.6 33.8 15.5 3.9 31.6 14.9 4.2 15.8 7.4 4.3 67 35.1 21.2 3.1 33.4 20.8 3.3 31.5 20.2 3.5 30.2 19.5 3.8 27.9 18.7 4.0 14.0 9.4 4.1 62 31.9 25.3 3.0 30.1 24.5 3.2 28.2 23.7 3.4 27.3 22.3 3.7 25.6 20.9 3.9 12.8 10.5 4.0 57 31.0 26.1 3.0 29.6 24.9 3.2 28.1 23.6 3.4 27.3 22.3 3.7 25.6 20.9 3.9 12.8 10.5 4.0
975
72 38.0 17.2 3.2 36.7 17.0 3.5 35.1 16.6 3.7 34.3 16.2 4.0 31.9 15.6 4.3 16.0 7.8 4.4 67 35.5 22.2 3.2 33.9 21.9 3.4 32.0 21.4 3.6 30.7 20.7 3.9 28.3 19.9 4.1 14.1 9.9 4.2 62 32.5 26.6 3.1 30.8 25.9 3.3 29.1 24.5 3.5 28.3 23.1 3.8 26.6 21.7 4.0 13.3 10.9 4.1 57 32.08 26.99 3.06 30.70 25.83 3.28 29.11 24.49 3.51 28.31 23.11 3.78 26.59 21.71 4.00 13.30 10.86 4.13
36 Evap
&
38H
K/H
Q
Notes:1. Net Capacities shown include a deduction for evaporator fan motor heat.2. Formulas: Leaving db= Entering - Sensible Heat Cap./(1.09 x CFM)
Leaving wb= wb corresponding to air leaving coil (hwb)h wb leaving = hwb entering - Total Cap(Btuh)/(4.5 X CFM) 3. Direct Interpolation Permissible. Do not extrapolate.
14
Detailed Performance Data – Matching 38HK with Ceiling Cassette
Evaporator CONDENSER AIR ENTERING Deg. FNom Cap. Air 75 85 95 105 115 120
Mbtuh CFM EWB Cap. Tot Cap. MBtuh Tot Cap. MBtuh Tot Cap. MBtuh Tot Cap. MBtuh Tot Cap. TotSysTot Sen Sys Tot Sen Sys Tot Sen Sys Tot Sen Sys Tot Sen Sys Tot Sen
72 47.3 20.8 3.6343.7 25.9 3.5439.5 30.5 3.4437.6 32.1 3.40
45.6 20.4 3.9141.6 25.2 3.8037.2 29.5 3.6635.9 30.6 3.62
43.4 19.7 4.1739.1 24.4 4.0534.9 28.5 3.8734.1 29.1 3.83
41.0 19.0 4.4636.5 23.4 4.3032.5 27.4 4.0832.3 27.5 4.07
38.3 18.2 4.7633.8 22.5 4.5330.2 25.7 4.3230.2 25.8 4.32
36.4 17.3 4.9432.1 21.4 4.6628.7 24.5 4.4528.7 24.5 4.46
680 676257
48 Evap& 48
Cond830
72 47.9 21.5 3.7244.5 27.3 3.6340.5 32.5 3.5339.4 33.6 3.50
46.2 21.2 3.9842.4 26.7 3.8938.2 31.5 3.7737.6 32.0 3.75
44.1 20.6 4.2640.0 26.0 4.1535.8 30.5 3.9835.7 30.4 3.98
41.7 20.0 4.5637.3 25.1 4.4333.7 28.7 4.2233.7 28.7 4.22
38.9 19.2 4.8534.4 24.1 4.6431.6 26.9 4.4631.6 26.9 4.46
37.0 18.2 5.0232.7 22.9 4.7630.0 25.6 4.6030.0 25.6 4.60
676257
975
72 48.3 22.1 3.8145.1 28.6 3.7241.3 34.3 3.6240.8 34.7 3.60
46.7 21.9 4.0743.1 28.1 3.9639.1 33.4 3.8639.0 33.2 3.86
44.6 21.4 4.3540.7 27.5 4.2437.0 31.5 4.1337.0 31.5 4.13
42.3 20.9 4.6537.8 26.6 4.5034.9 29.7 4.3634.9 29.8 4.36
39.4 20.1 4.9434.9 25.6 4.7532.8 27.9 4.6132.8 27.9 4.61
37.4 19.1 5.1233.2 24.3 4.8931.1 26.5 4.7731.2 26.5 4.77
676257
Notes:1. Net Capacities shown include a deduction for evaporator fan motor heat.2. Formulas: Leaving db= Entering - Sensible Heat Cap./(1.09 x CFM)
Leaving wb= wb corresponding to air leaving coil (hwb)h wb leaving = hwb entering - Total Cap(Btuh)/(4.5 X CFM) 3. Direct Interpolation Permissible. Do not extrapolate.
38H
K/H
Q
15
Detailed Performance Data – Matching 38HK with Free Stand
Nom Cap.
Mbtuh
Evaporator Air
CONDENSER AIR ENTERING Deg. F 75 85 95 105 115 120
CFM EWB Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw
Capacity MBtuh
Tot Sys Kw Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen
36
600
72 41.3 19.4 3.2 39.8 18.9 3.5 37.9 18.4 3.7 36.4 17.7 3.9 34.0 16.9 4.2 17.0 8.5 4.4 67 38.2 24.0 3.1 36.3 23.4 3.4 34.2 22.7 3.6 32.4 21.8 3.8 30.0 20.9 4.0 15.0 10.5 4.1 62 34.5 28.3 3.0 32.5 27.4 3.2 30.5 26.5 3.4 28.9 25.4 3.6 26.8 23.9 3.8 13.4 12.0 3.9 57 32.8 29.8 3.0 31.4 28.5 3.2 29.8 27.0 3.4 28.7 25.6 3.6 26.8 24.0 3.8 13.4 12.0 3.9
700
72 41.8 20.0 3.3 40.4 19.7 3.5 38.5 19.2 3.8 37.1 18.6 4.0 34.6 17.8 4.3 17.3 8.9 4.4 67 38.9 25.4 3.2 37.0 24.9 3.4 34.9 24.2 3.7 33.1 23.3 3.9 30.6 22.4 4.1 15.3 11.2 4.2 62 35.4 30.2 3.1 33.4 29.3 3.3 31.3 28.4 3.5 29.9 26.7 3.7 28.1 25.1 3.9 14.0 12.5 4.1 57 34.4 31.2 3.1 32.8 29.8 3.3 31.2 28.3 3.5 29.9 26.7 3.7 28.1 25.1 3.9 14.0 12.5 4.1
800
72 42.2 20.6 3.4 40.7 20.3 3.6 38.9 19.9 3.8 37.5 19.4 4.1 35.0 18.7 4.4 17.5 9.3 4.5 67 39.4 26.6 3.3 37.6 26.2 3.5 35.5 25.6 3.7 33.6 24.8 4.0 31.0 23.8 4.2 15.5 11.9 4.3 62 36.1 31.9 3.2 34.2 31.0 3.4 32.3 29.3 3.7 31.0 27.7 3.9 29.1 26.0 4.1 14.6 13.0 4.2 57 35.6 32.3 3.2 34.1 30.9 3.4 32.3 29.3 3.7 31.0 27.7 3.9 29.1 26.0 4.1 14.6 13.0 4.2
48
700
72 50.9 21.5 3.7 49.1 21.0 4.0 46.8 20.4 4.3 42.4 19.6 4.6 39.6 18.7 4.9 19.8 9.4 5.1 67 47.1 26.7 3.7 44.8 26.0 3.9 42.1 25.1 4.2 37.8 24.2 4.4 35.0 23.2 4.7 17.5 11.6 4.8 62 42.6 31.4 3.6 40.1 30.4 3.8 37.6 29.4 4.0 33.7 28.2 4.2 31.3 26.6 4.5 15.6 13.3 4.6 57 40.5 33.0 3.5 38.7 31.6 3.7 36.7 30.0 3.9 33.4 28.3 4.2 31.3 26.6 4.5 15.6 13.3 4.6
800
72 51.6 22.2 3.8 49.8 21.8 4.1 47.5 21.2 4.4 43.2 20.6 4.7 40.3 19.7 5.0 20.1 9.9 5.2 67 48.0 28.1 3.7 45.7 27.6 4.0 43.1 26.8 4.3 38.6 25.9 4.6 35.6 24.8 4.8 17.8 12.4 4.9 62 43.6 33.5 3.6 41.2 32.5 3.9 38.6 31.5 4.1 34.8 29.6 4.3 32.7 27.8 4.6 16.3 13.9 4.7 57 42.4 34.6 3.6 40.5 33.0 3.9 38.4 31.4 4.1 34.8 29.6 4.3 32.7 27.8 4.6 16.4 13.9 4.7
900
72 52.1 22.8 3.9 50.3 22.5 4.2 48.0 22.1 4.5 43.7 21.5 4.8 40.8 20.7 5.1 20.4 10.3 5.3 67 48.6 29.5 3.8 46.4 29.0 4.1 43.8 28.4 4.4 39.1 27.5 4.6 36.1 26.4 4.9 18.0 13.2 5.0 62 44.5 35.4 3.7 42.2 34.4 4.0 39.8 32.5 4.3 36.1 30.7 4.5 33.9 28.8 4.8 17.0 14.4 4.9 57 43.9 35.8 3.7 42.0 34.3 4.0 39.8 32.5 4.3 36.1 30.7 4.5 33.9 28.8 4.8 17.0 14.4 4.9
60
1000
72 63.9 30.6 5.0 61.7 29.9 5.4 58.7 29.0 5.8 54.1 27.9 6.0 50.6 26.7 6.4 25.3 13.4 6.7 67 59.2 38.0 4.9 56.3 37.0 5.3 52.9 35.8 5.6 48.2 34.4 5.8 44.6 33.1 6.1 22.3 16.5 6.3 62 53.5 44.8 4.8 50.3 43.3 5.1 47.2 41.8 5.4 43.0 40.2 5.5 39.9 37.8 5.8 20.0 18.9 6.0 57 50.9 47.1 4.7 48.6 45.0 5.0 46.1 42.7 5.3 42.6 40.4 5.5 39.9 37.8 5.8 20.0 18.9 6.0
1250
72 64.8 31.7 5.2 62.5 31.1 5.5 59.7 30.3 5.9 55.1 29.3 6.2 51.4 28.1 6.6 25.7 14.1 6.8 67 60.2 40.1 5.0 57.4 39.3 5.4 54.1 38.2 5.8 49.2 36.9 6.0 45.5 35.4 6.3 22.7 17.7 6.4 62 54.8 47.8 4.9 51.7 46.3 5.2 48.4 44.9 5.5 44.5 42.2 5.7 41.8 39.6 6.0 20.9 19.8 6.2 57 53.3 49.3 4.9 50.8 47.0 5.2 48.3 44.7 5.5 44.5 42.2 5.7 41.8 39.6 6.0 20.9 19.8 6.2
1500
72 65.4 32.5 5.3 63.1 32.1 5.7 60.3 31.4 6.0 55.8 30.6 6.3 52.0 29.5 6.7 26.0 14.7 6.9 67 61.0 42.0 5.2 58.2 41.4 5.5 55.0 40.4 5.9 50.0 39.1 6.1 46.1 37.6 6.4 23.0 18.8 6.6 62 55.9 50.4 5.0 52.9 49.0 5.4 50.0 46.3 5.7 46.1 43.7 5.9 43.3 41.0 6.2 21.6 20.5 6.4 57 55.1 51.0 5.0 52.8 48.8 5.4 50.0 46.3 5.7 46.1 43.7 5.9 43.3 41.1 6.2 21.7 20.5 6.4
38H
K/H
Q
Typical Wiring Schematic 38HK 18-36- 60Hz
220-240V/1Ph 24V Control
220-240V/1Ph 220V Control
16
Typical Wiring Schematic 38HK- 48-70- 60Hz
220V/1Ph 24V Control
220V/1Ph 220V Control
38H
K/H
Q
17
38H
K/H
Q
Typical Wiring Schematic 38HK- 48-70- 60Hz – Cont
220V/3Ph 24V Control
220V/3Ph 220V Control
18
Typical Wiring Schematic Heat Pump 38HQ18-24
38H
K/H
Q
19
38H
K/H
Q
Application data Unit selectionSelect equipment to match or be slightly less than anticipated peak load. This provides betterhumidity control, fewer unit cycles, and less part-load operation.For units used in spaces with high sensible loads,base equipment selection on unit sensible load,not on total anticipated load. Adjust foranticipated room wet bulb temperature to avoidunder sizing equipment.When selecting equipment that has outdoor airintroduced into the unit, determine the mixconditions of room air and outdoor air at designconditions. The cooling capacity tables in thisliterature are based on 80 F edb. To select the proper equipment, adjust for actual dry-bulb andwet-bulb conditions with the required outdoorair.
Unit mounting Unit leveling — For reliable operation, unitsshould be level in all planes.Clearance — Provide adequate clearance forairflow. See dimensional drawings for proper clearances. The condensing units are designedfor free-blow application. Air inlets and outletsshould not be restricted. Outdoor fan externalstatic pressure available is less than 0.1 in. wg.Unit location —Units may be wall mounted, padmounted at ground level, roof mounted, or mounted on or under a deck or patio. Be surethat water from roof does not drain directly ontothe unit. If 38 Series condensing units aremounted near a wall, the condenser air shoulddischarge away from the wall. This will provideinherent coil protection and the best possiblesound and airflow performance.Winter start — The use of a winter start controlmay extend the operation range (generally to 35F or 40 F). Winter start bypasses the low-pressure switch for 3 minutes.Crankcase heater — Units with low ambientcontrol should be equipped with crankcaseheaters to prevent refrigerant migration duringcompressor off cycle.
Refrigerant lines General refrigerant line sizing: 1. All charges, line sizing, and capacities are based on runs of 25 ft. For runs over 25 ft, consult the appendix A. NOTE: The minimum line length should be 10 ft.
MAXIMUM LINE LENGTHS
UNITMAXIMUM
EQUIVALENTFT
MAXIMUM LIFT— FAN COIL
BELOWCONDENSING
UNIT
MAXIMUM LIFT — FAN COIL
ABOVECONDENSING
UNIT38HK 50 30* 30*
*Maximum distance permitted is 30 ft from lowestsystem component to highest system component. Forlonger line application please refer to appendix A.
2. Refrigerant lines should not be buried in theground. If it is necessary to bury the lines, not more than 36 in. should be buried. Provide a minimum 6 in. vertical rise to the service valvesto prevent refrigerant migration.3. The refrigerant lines must be insulated. Use a minimum of 1/2-in. thick insulation. Closed-cellinsulation is recommended in all applications.4. Special consideration should be given toisolating interconnecting tubing from the buildingstructure. Isolate the tubing so that vibration ornoise is not transmitted into the structure.5. The 38 Series system charge is based on ratedperformance and 25 ft of line.6. For the supply and return lines, check physicaldata.
SYSTEM OPERATING CONDITIONS OPERATING LIMITS
TEMPERATURE CONDITIONS LIMITSMaximum Cooling Ambient (F) Minimum Cooling Ambient (F) (withoutaccessory low-ambient kit)Minimum Cooling ambient (F) (with accessorylow-ambient kit)
125
55
35
Saturated Suction Temperature RangeMinimum (F) Maximum (F) 20 55
Saturated Condensing Temperature RangeMinimum (F) Maximum (F) 60 150
Maximum Compressor DischargeTemperature (F)Minimum Discharge Superheat (F)
275
60NOTE: For system controls see Electrical Data.
20
ControlsThe indoor blower starts according to thenormal fan coil unit sequence of operation.The control relay (in the outdoor unit) initiatesoperation of a cooling cycle for thecompressor. As the set point at the fan coil issatisfied, its individual signal to the 38HK unitstops.38 Series outdoor condensing unit — Theoutdoor unit is equipped with a control thatmonitors the indoor fan coil cooling request.Unit malfunction — Each unit is equippedwith a high-pressure switch (HPS), a lowpressure switch (LPS), Compressor over current protection is achieved by an internal line break overload,which automatically resets when the motortemperature cools to a satisfactory level.
38H
K/H
Q
21
Unit operation NOTE: AUTO fan mode is used as the unit operation example for ALL fan coil units in this section. Contact your local Carrier dealer for operation information in other fan modes. Fan coil units — Duct free fan coil units have a self-contained control system that determines the set point for fan coil operation, fan mode operation, and heating mode operation (if provided). The un-ducted fan coil and ducted fan coil units are equipped with a thermostat. For ducted fan coils the field installed thermostat determines the set point for fan mode operation, and electric heat operation (if provided). On a call for cooling operation by a single fan coil unit, a signal is sent to the 38H outdoor unit and energizes a control relay.
38H
K/H
Q
Appendix Long-Line Guideline.
Reference: Catalog No. 513-868
22
LONG-LINE GUIDELINE
Table 1 – REQUIRED FIELD INSTALLED ACCESSORIES FOR AIR CONDITIONERS AND HEAT PUMP
ACCESSORYREQUIRED FOR
LOW-AMBIENT APPLICATIONS(BELOW 55°F)
REQUIRED FOR LONG-LINE
APPLICATIONS*(OVER 50 FT)
REQUIRED FORSEA COAST
APPLICATIONS(WITHIN 2 MILES)
Crankcase Heater Yes Yes NoEvaporator Freeze Thermostat Yes No No
Winter Start Control Yes† No NoAccumulator No No No
Compressor Start AssistCapacitor and Relay Yes Yes No
Low Ambient Controller,MotorMaster™ Control,
orLow-Ambient Pressure Switch
Yes No No
Wind Baffle See Low-Ambient Instructions No NoCoastal Filter No No YesSupport Feet Recommended No Recommended
Liquid-Line Solenoid Valveor
Hard-Shutoff TXVNo
See Long-LineApplicationGuideline
No
Ball-Bearing Fan Motor Yes‡ No NoIsolation Relay Yes** No No
38H
K/H
Q
*For tubing line sets between 50 and 175 ft, refer to Residential Split-System Long-Line Application Guideline.†Only when low-pressure switch is used.‡Required for Low-Ambient Controller (full modulation feature) and MotorMaster™ control only.** Required on Heat Pumps only.
This Long-Line Application Guideline appliesto all Carrier residential air conditioner andheat pump split systems that have a nominalcapacity of 18,000 to 60,000 Btuh. Thisguideline provides required system changesand accessories necessary for any residentialproduct having piping requirements greaterthan 50 ft or installations where indoor unit is located above outdoor unit.This guideline is intended to cover applicationsoutside the standard Installation Instructions.This guideline is for standard, single-speedproducts. For applications involving 2-speedproducts, refer to Step 6 first.NOTE: The presale literature for outdoor unitmust be referred to in conjunction with thisguideline.
Step 1—Approved SystemsAny residential indoor/outdoor unitcombination listed in the outdoor unit presaleliterature is an approved system, EXCEPT thefollowing:• Indoor coils with capillary-metering devices• All equipment less than nominal 18,000 Btuh
• All 1/4-in. and 3/16–in. liquid-lineapplications• Any indoor furnace coil/fan coil not listed inoutdoor unit presale literature• Any application which has interconnectingtubing with an equivalent length greater than175 ft
Step 2—Interconnecting Tubing SizingTable 2 lists recommended interconnectingvapor-line diameters for equivalent total-linelengths. All residential split systems installedin long-line applications must use only 3/8-in.liquid lines. Equivalent line length equals thelinear length (measured) of interconnectingvapor tubing plus losses due to elbows. (SeeTable 3 and Fig. 3.) Liquid lines larger than3/8-in. OD greatly increase charge quantity ofthe system. Excessive charge increases risk of migration and compressor damage. Table 2 provides the estimated percentage of nominalcooling-capacity losses based on the standard,required vapor line size versus what is selectedfor the long-line application. Since the vaporline is the discharge line in heating mode,losses are minimal.
23
38H
K/H
Q
Calculate the linear length of vapor tuberequired, adding any losses for the totalnumber of elbows for application. (See Table6.) Using this equivalent length, select desiredvapor-line size from Table 2. Subtract thenominal percentage loss from outdoor-unitpresale-literature Detailed Cooling Capacitiesdata for the given indoor/outdoor combination.Reference all notes of Table 2.NOTE: When specifying vapor-lineinsulation, be aware of the following standardpractice:All standard accessory-tubing kits are suppliedwith 3/8-in. insulation on vapor line.For minimal capacity loss in long-lineapplication, 1/2-in. insulation should be specified.For reference only, the close cell insulationmaterial specified for accessory tubing kits is acompound of vinyl, neoprene, or nitrile blendsof these polymers. Performance requirementsinclude thermal range of 0° F to 200°F (-17.8°C to 93° C) and a maximum thermalconductivity of 0.28.NOTE: Special consideration must be given toisolating interconnecting tubing from buildingstructure. Isolate tubing so that vibration ornoise is not transmitted into structure.
Step 3—Metering Device Sizing The metering device for a long-line applicationmust be flexible enough to compensate forfrictional losses due to long refrigerant linesand installed system design (indoor coil aboveor below outdoor unit.) The piston or TXVprovides such flexibility.The piston should be changed for both indoorcoil and outdoor heat pump unit, depending onsystem configuration and line length. Tables 4 and 5 provide necessary changes for a givenapplication.Use Tables 4 and 5 when selecting correctpiston size. Outdoor unit presale literaturemust be consulted to determine meteringdevices specified for standard applications.After determining standard application pistonsize(s), refer to Tables 4 and 5 as they relate to system design (outdoor unit above or belowindoor unit) per equivalent length of tubing.NOTE: If total equivalent horizontal length is100 ft or longer, both indoor and outdoorpistons must be increased 1 full piston size, in addition to changes required by Tables 4 and 5.After finding appropriate change in pistonsize, add or subtract the change from original piston number. If piston size is decreased,round new piston number down to nearestcommon piston number found in Table 6. Ifpiston size is increased, round new piston
number up to nearest common piston numberfound in Table 6.
EXAMPLE:An 042 size heat pump is 75 ft above an 042 sizefan coil. The 042 size heat-pump presale literaturespecifies a size 80 indoor piston and size 63 outdoorpiston. To establish correct indoor piston size for a75 ft vertical separation, refer to Table 4. For a 75 ft equivalent line length, the piston change is -5.Therefore subtract 5 from the original indoor piston size of 80: 80 – 5 = 75 Table 6 provides common piston sizes. In thisinstance, 75 is not listed, therefore round DOWN to next piston size, which would be 74. To establishcorrect outdoor piston size for a 75 ft verticalseparation, refer to Table 5. For a 75 ft equivalentline length, the piston change is +4. Therefore add 4 to the original outdoor piston size of 63: 63 + 4 = 67Since 67 is listed in Table 6, that is the piston whichshould be used. If a 67 size piston were not listed, itwould be necessary to round UP to next piston size.
Step 4—Liquid-Line Solenoid AndTubing ConfigurationThere are 2 types of liquid-line solenoids: 1 forsingle-flow applications and the other for bi-flow applications. The purpose of having 2 solenoids is to minimize the valve internal-pressure drop in accordance with refrigerant flow direction and liquid migration to the compressor. The bi-flow solenoid is designedto have minimal refrigerant-pressure drop ineither flow direction, which makes it suitablefor heat pump usage. Refer to Table 7 forliquid-line solenoid kit part numbers.NOTE: When installing a liquid-line solenoid,the system may require a minimum 60-va low-voltage transformer.Each type of solenoid has an indicator flowarrow stamped on the valve body. Whensolenoid is closed (not energized) and pressureis applied in direction of flow arrow, completeshutoff occurs. If pressure is applied againstdirection of flow arrow, leakage through valveoccurs. When determining proper installationof valve within liquid line, 2 considerationsmust be made:1. Direction of flow arrow2. Where solenoid is installed in system.TXVs can only be substituted for liquid-linesolenoids in singleflow air conditioningsystems. Bi-flow TXVs allow liquid migrationto coldest point during off cycles, which couldallow liquid into compressor. Fig. 2 through 5detail proper installation of liquid-line solenoidand provide applications where TXVs may besubstituted. Reference all notes of the appropriate figures.
24
Step 5—Charging InformationWeigh in appropriate refrigerant charge, thenuse the standard practices of superheat-charging method for piston applications and subcooling-charging method for TXVapplications to confirm correct charge. Thestandard charging methods can be found onoutdoor unit-information plate, in unitInstallation Instructions, or in the ServiceManual. Since total system charge is increasedfor long-line applications, it may be necessaryto calculate the additional refrigerant charge.Since long-line applications only involve 3/8-in. liquid lines, the additional refrigerantcharge required is 0.6 oz of Refrigerant 22 (R-22) per ft of 3/8-in. liquid line over 15 ft.
EXAMPLE:To calculate additional charge required for a 25–ftline set: 25 ft – 15 ft= 10 ft X 0.6 oz/ft = 6 oz of additional charge
The rating-plate charge of a given outdoor unitis for a standard application of 15 ft of interconnecting tubing. The rating-plate chargecan be found on outdoor unit-rating plate or inoutdoor unit-presale literature. Long-lineapplications do not require additional oilcharge. 38
HK
/HQ
Table 2 —Estimated Percentage of Nominal Cooling-Capacity Losses*UNIT NOMINAL
SIZE (BTUH)LONG-LINE
VAPOR-LINEDIAMETER (IN.)**
EQUIVALENT LINE LENGTH (FT)
50 75 100 125 150 175
18,000 5/8 5 7 9 12 12 143/4 1 3 4 5 5 7
24,000 5/8 6 9 13 16 19 223/4 0 1 1 2 3 4
30,000 5/8 6 8 10 13 15 173/4 2 3 4 5 6 7
36,000 3/4 7 10 14 17 21 NR7/8 2 4 6 8 10 113/4 7 10 13 17 20 23
42,000 7/8 3 4 6 7 8 101-1/8 0 0 1 1 2 23/4 10 14 18 22 NR NR
48,000 7/8 4 6 7 9 11 131-1/8 0 0 1 1 2 2
60,000 7/8 7 9 11 14 16 191-1/8 1 2 2 3 3 4
*The estimated percentage of cooling capacity that must be subtracted from the Detailed Cooling Capacities data specified in outdoorunit-presale literature for any given indoor/outdoor combination.**Vapor-line diameter that may be selected for a long-line application. If smaller vapor lines are selected but not specified within thetable, large capacity losses will occur and defrost capabilities will be reduced. If larger vapor lines are selected but not specified withinthe table, refrigerant oil return will be impaired due to velocity losses.N/R—Not recommended due to excessive loss of capacity.
Step 6—2–Speed Applications Vapor tube diameter for the 036 and 048 is 7/8Outdoor units may be connected to indoor in.; 060 is 1–1/8section using accessory tubing package or Vapor refrigerant connection diameter for allfield-supplied refrigerant grade tubing or sizes is 7/8 in. correct size and condition. In long-line DO NOT INSTALL EQUIVALENTapplications, 2–speed units are handled INTERCONNECTING TUBING LENGTHSbasically the same way as the single-speed GREATER THAN 100 FT.units. There are 2 major differences: 2. Do not increase or decrease tubing sizes.1. For tubing up to 100 ft: Liquid tube For other applications see the previous sectionsdiameters and refrigerant connection diameters under Long-Line Guidelines.for all sizes are 3/8 in.
25
38H
K/H
Q
B
90° STD
A
C
45° STD
Fig.1—Tube Bend Losses
Table 3—Fitting Losses in Equivalent FtTUBE SIZE OD
(IN.)REFERENCE DIAGRAM IN FIG. 1
A B C5/8 1.6 1.0 0.83/4 1.8 1.2 0.97/8 2.0 1.4 1.0
1-1/8 2.6 1.7 1.3
26
Table 4 - Calculation of Indoor Piston No.OUTDOOR UNIT ABOVE INDOOR
FT0-25
26-5051-75
76-100101-125126-150
PISTON CHANGE0-3-5-7-9
-10OUTDOOR UNIT BELOW INDOOR
FT PISTON CHANGE0-25 0
26-50 +4
Table 5 — Calculation of Outdoor Piston No. OUTDOOR UNIT ABOVE INDOOR
38H
K/H
Q
FT0-50
51-7576-100
101-125126-150
PISTON CHANGE0
+4+6+8
+10OUTDOOR UNIT BELOW INDOOR
FT PISTON CHANGE0-50 0
Table 6 — Common Piston SizesACCURATER™ CHATLEFF ACCURATER™ CHATLEFF
— 32 65 65— 33 67 6735 35 — 68— 36 70 70— 37 — 7138 38 73 73— 39 — 7440 40 76 76— 41 78 7842 42 80 80— 43 — 81— 45 82 8246 — 84 84— 47 86 8649 49 88 8851 51 — 8952 52 90 90— 53 — 9255 55 93 9357 57 96 9659 59 98 9861 61 101 101— 62 104 10463 63 109 —
Table 7—Liquid-Line Solenoid Kit Part NumbersTYPE OF VALVE PART NO.
Single Flow KAALS0101LLSBi-Flow KHALS0101LLS
27
38H
K/H
Q
175' MAX.
GROUND LEVEL
BASEMENT
Note: For Rotary Compressor,maximum length is 105'.
Fig. 2—Application with Air Conditioner Installed in a Horizontal Configuration
175' MAX.
GROUND LEVEL
BASEMENT
Note: For Rotary Compressor,maximum length is 105'.
Fig. 3—Application with Heat Pump Installed in a Horizontal Configuration
28
38H
K/H
Q
HEAT PUMP ONLY
50' MAX.
GROUND LEVEL
TRAP
Note: For Rotary Compressor,maximum height is 30'.
Fig. 4-Application with Air Conditioner or Heat Pump Installed with Indoor Unit above Outdoor Unit
29
38H
K/H
Q
HEAT PUMP ONLY
150' MAX. Note: For Rotary Compressor,maximum height is 90'.
Fig. 5—Application with Air Conditioner or Heat Pump Installed Above Indoor Unit
30
Notes
38H
K/H
Q
31
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations 38HK-03 PD 60HZ 2011