34 OTM C Installation and operating instruction

36
Installation and operating instruction Motorized Change-Over Switches 34 OTM_C_

Transcript of 34 OTM C Installation and operating instruction

Page 1: 34 OTM C Installation and operating instruction

Installation and operating instruction

Motorized Change-Over Switches

34 OTM_C_

Page 2: 34 OTM C Installation and operating instruction
Page 3: 34 OTM C Installation and operating instruction

TABLE OF CONTENTS1 Introduction

1.1 Use of symbols..................................................................................4

2 Product overview

3 Quick start

3.1 Controlling the switch electrically (remote control) ..........................6

3.2 Controlling the switch manually (local operation) ............................7

4 Installation

4.1 Mounting the OTM_ motorized change-over switch ........................9

4.2 Mounting positions ..........................................................................14

5 Connecting the control circuit

6 Operating the OTM_motorized change-over switch

6.1 Electrical control ..............................................................................17

6.1.1 Impulse control ................................................................ 19

6.1.2 Continuous control .......................................................... 19

6.2 Manual operation.............................................................................20

6.3 Lockings...........................................................................................21

6.3.1 Locking electrical control................................................. 21

6.3.2 Locking manual operation............................................... 22

7 Technical data

7.1 Motor operator .................................................................................24

7.2 State information .............................................................................25

8 Accessories

8.1 Terminal clamp sets ........................................................................26

8.2 Bridging bars ...................................................................................27

8.3 Terminal shrouds .............................................................................28

8.4 Auxiliary contact blocks...................................................................30

8.5 UL standard switches......................................................................31

8.6 Barriers ............................................................................................33

2281 6527 Installation and operating instruction

TABLE OF CONTENTS

1SCC303002M9701

3

Page 4: 34 OTM C Installation and operating instruction

1 Introduction

This manual describes the installation and the basic operation of the OTM_ motorized change-overswitch. The instructive part is followed by a section on available accessories.

1.1 Use of symbols

Hazardous voltage: warns about a situation where a hazardous voltage may cause physical injury to aperson or damage to equipment.

General warning: warns about a situation where something other than electrical equipment maycause physical injury to a person or damage to equipment.

Caution: provides important information or warns about a situation that may have a detrimental effecton equipment.

Information: provides important information about the equipment.

1SCC303002M9701

4

Page 5: 34 OTM C Installation and operating instruction

2 Product overview

OTM_ motorized change-over switches are designed for diverse applications to secure power supply.You can operate the OTM_ motorized change-over switches either electrically using the motor operatoror manually using the handle.

6

11

5

10

43

1

2

8 97

S021

62A

Fig. 2-1 OTM_ motorized change-over switch

1 Motor operator

2 Switch panel

3 Motor/Manual selection

4 Terminals for locking state information

5 Handle for manual operation

6 Place for auxiliary terminals

7 Fuse (F1) of motor operator

8 Terminals for motor operator voltage supply

9 Terminals for push-buttons

10 Locking latch for releasing the handle and locking electrical control

11 Locking clip for locking manual operation

Installation and operating instruction

2 Product overview

1SCC303002M9701

5

Page 6: 34 OTM C Installation and operating instruction

3 Quick start

This is a quick guide meant for you who only need a reminder of how to operate the unit. For moredetailed instructions, see chapter 6

3.1 Controlling the switch electrically (remote control)

To control the switch electrically:

1. Remove the handle from the switch panel.You can remove the handle in any position.

2. Turn the Motor/Manual selector to the Motor (M) position to enable electrical control.

A00

308A

MM

Man.Man.

MM

Man.Man.

Fig. 3-1 Controlling the switch electrically

To disable electrical control, lock the locking latch with a padlock.

After the locking latch has been locked, the switch cannot be controlled electrically.

You can lock electrical control in any position (I, 0, II).

1SCC303002M9701

6

Page 7: 34 OTM C Installation and operating instruction

A00

307A

2

1

Fig. 3-2 Locking electrical control

3.2 Controlling the switch manually (local operation)

To control the switch manually:

1. Turn the Motor/Manual selector to the Manual (Man.) position to enable manual operation and toprevent electrical operation.

2. Attach the handle to the switch panel.You can attach the handle in any position.

A00

309A

MM

Man.Man.

MM

Man.Man.

MM

Man.Man.

III

MM

Man.Man.

Fig. 3-3 Operating the switch manually

Installation and operating instruction

3 Quick start

1SCC303002M9701

7

Page 8: 34 OTM C Installation and operating instruction

To disable the manual (and electrical) operation, lift up the locking clip in position 0 and attach thepadlock to the handle.

A00

304A

Fig. 3-4 Locking the manual operation

The following chart shows the locking state information.

11

14 12

23

24

1112

14

1112

14

1112

14

1112

14

23 24 23 24 23 2423 24

Man.M MM

Man.Man.

MM

Man.Man.

1112

14

23 24

Fig. 3-5 Locking state information

1SCC303002M9701

8

Page 9: 34 OTM C Installation and operating instruction

4 Installation

4.1 Mounting the OTM_ motorized change-over switch

Use protection against direct contact.

A2

A1

III

3,5...4 Nm31...35.4 lb.in.

M5

MM

Man.Man.

MM

Man.Man.

A01

500A

Fig. 4-1 OTM160... 250_C

9,0134,5

127

A2

2065

A1130

162 A

B

25

122130

150

87,5323

16048,5 72

25

37

20

83 / 35,5

65

14100

A10

014A

Fig. 4-2 OTM160…250E-C-M

Installation and operating instruction

4 Installation

1SCC303002M9701

9

Page 10: 34 OTM C Installation and operating instruction

OTM160…250E-C-M

E3 E4

A 35 35

A1 116 116

A2 258 293

B 273 308

9,0134,5127

65A2

20

A1130

AB

25

170

122

150130

87,5323

160

25

83 / 35,5

65

14

37

2048,5 72

100

170

A10

005A

Fig. 4-3 OTM160...250_WCM

OTM160…250_WCM

E3 E4

A 43 43

A1 116 116

A2 282 325

B 297 340

9,00,35

134,55,30

1275,00

652,56

A2

200,79

A11305,12

A

B

250,98

1706,69

1224,80

1505,91

1305,12

87,53,4423

0,91 30,12

1606,30

250,98

83/35,53,27/1,40

652,56

140,55

371,46

200,7948,5

19,0972

2,83

1003,94

1706,69

A100

06A

Fig. 4-4 OTM200U_C_M

1SCC303002M9701

10

Page 11: 34 OTM C Installation and operating instruction

OTM200U_C_M

U3 U4

A 43/1,69 43/1,69

A1 116/4,57 116/4,57

A2 282/11,10 325/12,80

B 297/11,69 340/13,39

A2

A1

III

M53,5...4 Nm

31...35.4 lb.in.

MM

Man.Man.

MM

Man.Man.

A01

501A

Fig. 4-5 OTM315... 400_C

137,25 95

A225

A1156

A

B

11

160

150

31,25185,25

45635 87

192 43

32,5

20,5

126 / 51,5

95

17

120

185

A10

007A

Fig. 4-6 OTM315...400E_C_M

OTM315...400E_C_M

E3 E4

A 44 44

A1 142 142

A2 305 349

B 323 367

Installation and operating instruction

4 Installation

1SCC303002M9701

11

Page 12: 34 OTM C Installation and operating instruction

137,255,40

A2

953,74

250,98

A11566,14

1204,72

A

B

110,43

2208,66

1606,30

1505,91

31,251,23

195,257,69

40,16

562,20

351,38

873,43

1927,56

431,69

20,50,81

32,51,28

126 / 51,54,96 / 2,03

953,74

170,67

1857,28

A10

008A

Fig. 4-7 OTM400U_C_M

OTM400U_C_M

U3 U4

A 54/2,13 54/2,13

A1 142/5,59 142/5,59

A2 335/13,19 389/15,31

B 353/13,90 407/16,02

A2

A1

III

M6

MM

Man.Man.

MM

Man.Man.

A01

502A

Fig. 4-8 OTM600... 800_C

1SCC303002M9701

12

Page 13: 34 OTM C Installation and operating instruction

145

17

200

160

A1

147,5

A2

198

210250

212,5 A

B

47,5

15

25,5

39

45

132,6

110,5

564,1

256

43299

138,6

61,513,5

Fig. 4-9 OTM630... 800E_C_M

OTM630-800E-C-M

U02 U03 U04

A 65 65 65

A1 180 180 180

A2 325 390 455

B 346 411 476

200

A1

1606,30

147,5

A2

198

210

250

212,5 A

B

47,5

15

25,5

39 13,5

45

132,65

64,1

256

400

43

299

mmin

5,81

1,54 0,53

7,87

0,59

1,008,37

1,87

7,80

8,27

9,84

50920,04

15,75

2,52

0,20 5,22

10,08

1,77

1,69

11,77

145

170,67

5,7

Fig. 4-10 OTM600U_C_M

Installation and operating instruction

4 Installation

1SCC303002M9701

13

Page 14: 34 OTM C Installation and operating instruction

OTM600U-C-M

U02 U03 U04

A 65/2,56 65/2,56 65/2,56

A1 180/7,09 180/7,09 180/7,09

A2 325/12,8 390/15,35 455/17,91

B 436/13,62 411/16,18 476/18,74

4.2 Mounting positions

The recommended mounting positions for OTM_ motorized change-over switches are horizontal, wallmounted or table mounted.

Do not install the OTM_ change-over switches in any other position than those described above.

1SCC303002M9701

14

Page 15: 34 OTM C Installation and operating instruction

5 Connecting the control circuit

The electrical installation and maintenance of OTM_motorized change-over switches may beperformed only by an authorized electrician. Do not attempt any installation or maintenance actionswhen an OTM_motorized change-over switch is connected to the electrical mains. Before starting thework, make sure that the switch is de-energized.

III

MM

Man.Man.

A00

298A

11

14 12

23

24

3

1 2

MM

Man.Man.

II I 0

24Vdc

PE N L

F2

cUi>250V_

Fig. 5-1 OTM_motorized change-over switch terminals

1. Terminals for motor operator voltage supply

2. Control terminal (push-buttons)

3. Terminals for state information of locking

Installation and operating instruction

5 Connecting the control circuit

1SCC303002M9701

15

Page 16: 34 OTM C Installation and operating instruction

Do not couple power for the control terminal. See the correct terminal for the power supply in Figure5-1.

The control voltage (output C = 24Vdc) on the control terminal is non-isolated, see box 2 in Figure5-1.

The maximum cable length to ensure faultless operation of the push-buttons, see table 7-1

When relay outputs are used with inductive loads (such as relays, contactors and motors), they mustbe protected from voltage spikes using varistors, RC-protectors (AC current) or DC current diodes(DC current).

1SCC303002M9701

16

Page 17: 34 OTM C Installation and operating instruction

6 Operating the OTM_motorized change-over switch

Never open any covers on the product. There may be dangerous external control voltages inside theOTM_ motorized change-over switch even if the voltage is turned off.

Never handle control cables when the voltage of the OTM_ motorized change-over switch or externalcontrol circuits is connected.

Exercise sufficient caution when handling the unit.

6.1 Electrical control

You can control the switch electrically by using the push-buttons or a similar control concept.

To control the switch electrically:

1. Release the handle from the switch panel by pressing down the locking latch under the switch paneland pulling the handle off, see Figure 6-1.

Installation and operating instruction

6 Operating the OTM_motorized change-over switch

1SCC303002M9701

17

Page 18: 34 OTM C Installation and operating instruction

21

A00

305A

Fig. 6-1 Releasing the handle

Electrical control is disabled if the handle is attached to the switch panel.

2. Turn the Motor/Manual selection switch to the Motor (M) position, see Figure 6-2.

A00

299A

MM

Man.Man.

MM

Man.Man.

Fig. 6-2 Motor/Manual selection in the Motor (M) position

3. Control the OTM_ motorized change-over switch with the push-buttons via impulse control orcontinuous control.

The switch can be operated from position I to position II (or from II to I) without stopping it in position0. For example, if switch I is closed and you press the push-button (II), the control unit first runs switchI in the open position and then the control unit runs switch II from the open to the closed position.

1SCC303002M9701

18

Page 19: 34 OTM C Installation and operating instruction

The motor operator is protected from overloading by a fuse (F1) under the motor operator, see Figure2-1. Only use the same type of fuse that is described on the label close to the fuse.

6.1.1 Impulse control

When using impulse control, the switch is controlled by electric impulses. When you press the controlbutton, the switch is driven to the corresponding position (I, 0 or II). The control impulse must last morethan 100ms to take effect. A new command cannot be given until the switch has reached the position ofthe previous command. Figure 6-3 shows the operation of the switch with impulse control.

If a new command is given before the switch has reached the position of the previous command, thefuse (F1) may operate.

I - function

0 - function

II - function

I II 0

A00

301A

I - command II - command 0 - command

Fig. 6-3 Impulse control

6.1.2 Continuous control

When using continuous control, the control command is supplied to the switch continuously. When youpress the control button, the switch is driven to the corresponding position (I, 0 or II). Control ofposition 0 will over-run control of the other positions; that is, if you simultaneously give the 0 commandand another command, the switch is driven to position 0. Figure 6-4 shows the operation of the switchwith continuous control.

Installation and operating instruction

6 Operating the OTM_motorized change-over switch

1SCC303002M9701

19

Page 20: 34 OTM C Installation and operating instruction

The continuous control command can be given with push buttons, cam switches or with relaysincorporated in PLC equipment or with other suitable contacts.

I - position

0 - position

II - position

A00

302A

I - command II - command

0 - command

0 - command

Fig. 6-4 Continuous control

6.2 Manual operation

You can control the switch manually using the handle that is included in the delivery.

To control the switch manually:

1. Turn the Motor/Manual selector to the Manual (Man.) position, see Figure 6-5. The motor operator isswitched off and electrical control is prevented.

A00

300A

MM

Man.Man.

MM

Man.Man.

Fig. 6-5 Motor/Manual selection in the Man. position

2. Attach the handle by pressing it to the switch panel until it clicks into place. You can attach thehandle in all positions, see Figure 6-6.

1SCC303002M9701

20

Page 21: 34 OTM C Installation and operating instruction

A00

303A

MM

Man.Man.

III

MM

Man.Man.

Fig. 6-6 Attaching the handle

Electrical control is prevented when the handle is attached to the switch panel.

3. Control the OTM_ motorized change-over switch by turning the handle to the required position (I, 0,II).

6.3 Lockings

You can lock the OTM_motorized change-over switch to a specific position.

6.3.1 Locking electrical control

You can lock the electrical control to any position (I, 0, II).

To lock electrical control:

1. Pull up the locking latch under the switch panel.

2. Place the padloc k under the latc h, see Figure 6-7 .

Installation and operating instruction

6 Operating the OTM_motorized change-over switch

1SCC303002M9701

21

Page 22: 34 OTM C Installation and operating instruction

A00

307A

2

1

Fig. 6-7 Locking electrical control

You cannot attach the handle when electrical control is locked.

6.3.2 Locking manual operation

By default, manual operation can only be locked to position 0. Locking to positions I and II is optionaland possible only with modifications to the switch panel.

To lock manual operation:

1. Turn the handle to the required position.

2. Pull out the clip from the handle and place the padloc k on the hand le, see Figure 6-8 .

1SCC303002M9701

22

Page 23: 34 OTM C Installation and operating instruction

A00

304A

Fig. 6-8 Locking manual operation

The handle cannot be removed when padlocked to position 0.

Installation and operating instruction

6 Operating the OTM_motorized change-over switch

1SCC303002M9701

23

Page 24: 34 OTM C Installation and operating instruction

7 Technical data

7.1 Motor operator

Table 7-1 General technical data of motor operators

Motor operator Value

Rated operational voltage Ue 220 - 240 VAC

Operating voltage range 0,85... 1,1 x Ue

Operating angle 90° 0-I, I-0, 0-II, II-0; 180° I-0-II

Operating time See Table 7-2

Protection degree IP 20

Voltage supply PE N L

Cable of the push-buttons (no SELV) C II I 0

Cross section; solid/stranded 1.,5… 2,5 mm2

Maximum cable length 100 m

State information of locking (no SELV)

Handle attached or motor operator locked 11-12-14 (C/O)

Locking motor operator 23-24 (NO)

Rated impulse withstand voltage Uimp

Between terminals 4 kV

Between state information contacts 4 kV

Operating temperature -5... +40 °C

Transportation and storage temperature -40... +70 °C

Altitude Max. 2000m

Table 7-2 Specified technical data of motor operators

Type Voltage Ue[V]

Nominalcurrent aIn[A]

CurrentInrush [A]

Operatingtime I-0,0-I, 0-II, II-0 [s]

Operatingtime I-0-II,II-0-I [s]

OFF-timewhenoperatingI-II or II-I[s]

OTM160...250_C 230VAC 0,2 1,8 0,4-0,8 1,1-1,5 0,4-0,8

110V

OTM315...400_C 230VAC 0,5 3,5 0,4-0,8 1,1-1,5 0,4-0,8

110V

OTM600…800_C 230VAC

110VaUnder nominal conditions

1SCC303002M9701

24

Page 25: 34 OTM C Installation and operating instruction

7.2 State information

Table 7-3 State information

Measurement Value

Handle attached or motor operator locked 11-12-14 (C/O): 4A / 250V / cosφ=1

Locking motor operator 23-24 (NO): 4A / 250V / cosφ=1

Installation and operating instruction

7 Technical data

1SCC303002M9701

25

Page 26: 34 OTM C Installation and operating instruction

8 Accessories

8.1 Terminal clamp sets

III

OT 200, OT 250

OZXB1LOZXB2OZXB2LOZXB8OZXB9

OT 200U

OZXA-200_OZXA-206_

A00

074A

III

MM

Man.Man.

MM

Man.Man.

Fig. 8-1 OTM 160...250_C

III

II

OT 315, OT 400

OZXB2LOZXB3OZXB4OZXB7OZXB7LOZXB8OZXB9

A00

083A

OT 400U

OZXA-400_OZXA-406_

II

MM

Man.Man.

MM

Man.Man.

Fig. 8-2 OTM 315...400_C

1SCC303002M9701

26

Page 27: 34 OTM C Installation and operating instruction

OT 630, OT 800

A00

151A

OT 800U

III

OZXB3OZXB4OZXB5OZXB6 *OZXB7L

OZXA-800_OZXA-806_

* max. 1 pcs / side

II

MM

Man.Man.

MM

Man.Man.

Fig. 8-3 OTM 600...800_C

8.2 Bridging bars

A00

087A

1

OTZC_

3II

I

2

MM

Man.Man.MM

Man.Man.

Fig. 8-4 OTM160…400_C

Installation and operating instruction

8 Accessories

1SCC303002M9701

27

Page 28: 34 OTM C Installation and operating instruction

A00

154A

III

OTZC_

2

1

3

800 A 630 A

MM

Man.Man.MM

Man.Man.

Fig. 8-5 OTM600...800_C

8.3 Terminal shrouds

1

1

OTS250 1SGT

OTS250 1LGT

2

2

A01

504A

III

34

M

M

M8 15...22Nm 5/6DIA IN. 133-195LB.IN.OTS250 1S

GT

OTS250 1LGT

III

MM

Man.Man.

MM

Man.Man.

Fig. 8-6 OTM160…250_C

1SCC303002M9701

28

Page 29: 34 OTM C Installation and operating instruction

OTS400 1SGT

OTS400 1LGT

A01

505A

M

M

M10 30...44Nm 266-390 LB.IN.

III

OTS400 1SGT

OTS400 1LGT

II

MM

Man.Man.

MM

Man.Man.

Fig. 8-7 OTM315…400_C

III

OTS800 1SGT

OTS800 1LGT

A01

506A

1

2

1

2

OTS800 1SGT

OTS800 1LGT

M

M

M12 50...75Nm 433-664 LB.IN.

34

II

MM

Man.Man.

MM

Man.Man.

Fig. 8-8 OTM600…800_C

Installation and operating instruction

8 Accessories

1SCC303002M9701

29

Page 30: 34 OTM C Installation and operating instruction

8.4 Auxiliary contact blocks

Man.

MM

Man.Man.

Man.

MM

Man.Man.

A00

077A

II

I

1112

1314

2122

2324

1112

1314

2122

2324

3

11

37

21

13

II

I

12

OA 1G10 OA 3G01I

OII

OA 1G10 OA 3G01I

OII

I

II MAX 2+2

MAX 2+2

Fig. 8-9 OTM160…800_C

1SCC303002M9701

30

Page 31: 34 OTM C Installation and operating instruction

8.5 UL standard switches

F

A01

509A

Fig. 8-10 OTM200U_C

Height Width Depth

406 mm 305 mm 203 mm

16 inch 12 inch 8 inch

F

D

D

A01

510A

Fig. 8-11 OTM400U_C

Height Width Depth

610 mm 356 mm 254 mm

24 inch 14 inch 10 inch

Installation and operating instruction

8 Accessories

1SCC303002M9701

31

Page 32: 34 OTM C Installation and operating instruction

F

E

A

E

B

A01

511A

Fig. 8-12 OTM600U_C

Height Width Depth

600 mm 700 mm 400 mm

24 inch 28 inch 16 inch

Table 8-4 Measurements of the OTM_ motorized change-over switch

A 0

B 13mm 0,5inch

C Cable sizeAWG/MCM

4-3 2 1 1/0 2/0 3/0-4/0

250 300

100mm

100mm

100mm

125mm

150mm

175mm

200mm

250mm

4inch

4inch

4inch

5inch

6inch

7inch

8inch

10inch

D Cable sizeAWG/MCM

2 1 1/0 2/0 3/0-4/0

250 300 350

100mm

100mm

150mm

150mm

175mm

200mm

250mm

300mm

4inch

4inch

5inch

6inch

7inch

8inch

10inch

12inch

E Cable sizeAWG/MCM

2 1 1/0 2/0 3/0-4/0

250 300 350 400 500 600

100mm

100mm

150mm

150mm

175mm

200mm

250mm

300mm

330mm

356mm

381mm

4inch

4inch

5inch

6inch

7inch

8inch

10inch

12inch

13inch

14inch

15inch

F 13mm 0,5inch

1SCC303002M9701

32

Page 33: 34 OTM C Installation and operating instruction

8.6 Barriers

If the conductors are wider than 39 mm (1.54 inch), barriers of type 68838 or shrouds must be usedon OTM600U_C to maintain a clearance of 1 inch.

A01

508A

III

III

110

173

118

3

12

II

MM

Man.Man.

MM

Man.Man.

II

MM

Man.Man.

MM

Man.Man.

Fig. 8-13 OTM600U_C

Installation and operating instruction

8 Accessories

1SCC303002M9701

33

Page 34: 34 OTM C Installation and operating instruction
Page 35: 34 OTM C Installation and operating instruction
Page 36: 34 OTM C Installation and operating instruction

ABB OyLow Voltage ProductsP.O Box 622FI-65101 VAASA, FinlandTelephone +358 10 22 11Telefax +358 10 22 45708http://www.abb.com/lvswitches

Publicatio

n:1SCC303002M9701