Probabilistic Load Flow of Unbalanced Distribution Systems ...
3 LOAD FLOW METHOD FOR UNBALANCED SYSTEMS -...
Transcript of 3 LOAD FLOW METHOD FOR UNBALANCED SYSTEMS -...
CHAPTER - 3
LOAD FLOW METHOD FOR UNBALANCED SYSTEMS
3.1 INTRODUCTION
Load flow analysis is an important task for power system planning and operational
studies. Certain applications, particularly in distribution automation and optimization of a
power system, require repeated load flow solution and in these applications, it is very
important to solve the load flow problem as efficiently as possible. As the power distribution
networks become more and more complex, there is a higher demand for efficient and reliable
system operation. Consequently, the most important system analysis tool, load flow studies,
must have the capability to handle various system configurations with adequate accuracy and
speed. In many cases, it is observed that the radial distribution systems are unbalanced
because of single-phase, two-phase and three-phase loads. Thus, load flow solution for
unbalanced case, special treatment is required.
Conventional load flow methods cannot be directly applied to distribution systems as
discussed in previous chapter. Moreover, the techniques for three phase power flow analysis
for unbalanced systems cannot be developed by simply extending the single phase balanced
methods to three phase systems. A three phase load flow method has to address issues like
modeling of different types of component connections, determining starting point for three
phase power flow solution as there are phase shifts and transformation ratios for each phase
and at different buses. For untransposed lines and cables the balanced models are no longer
useful. The symmetrical component transformation can decouple the three phases. For three
phase networks an impedance matrix is to be obtained.
Chen et al. [24 - 26] have proposed a method to calculate power losses in unbalanced
radial distribution systems. Also proposed a method, how to model the transformer for power
flow analysis. Zimmerman and Chiang [39] have proposed Fast decoupled power flow
method for unbalanced radial distribution systems. This method orders the laterals instead of
buses into layers, thus reducing the problem size to the number of laterals. Using of lateral
variables instead of bus variables makes this method more efficient for a given system
topology, but it may add some difficulties if the network topology is changed regularly,
which is common in distribution systems because of switching operations. Thukaram et al.
[50] have proposed a method for solving three-phase radial distribution networks. This
method uses the forward and backward propagation to calculate branch currents and bus
voltages.
Garcia et al. [53] have proposed a method based on the Three-phase Current Injection
Method (TCIM), in which the current injection equations are written in rectangular
coordinates and is a full Newton method. Also it presents quadratic convergence properties
and convergence is obtained for all except some extremely ill conditioned cases. Lin and
Teng [54] have proposed a fast decoupled method which uses G-matrix for power flow based
on equivalent current injections. Teng [55] has proposed a method based on the Network
Topology which uses two matrices, viz. Bus Injection to Branch Current (BIBC) and Branch-
Current to Bus-Voltage (BCBV) matrices, to find out the solution. Kersting [56] has
proposed modeling of transformer and other components of distribution systems. Jen-Hao
Teng [78] has proposed direct method of load flow solution of unbalanced radial distribution
networks.
Mamdouh Abdel-Akher et al. [93] have proposed improved load flow method for
unbalanced RDS using sequence components. Peng Xiao et al. [96] have proposed a method
to model the different connections of transformer in as unbalanced radial distribution
networks. Subrahmanyam [100] has proposed simple three phase load flow method by
solving simple algebraic recursive expression of voltage magnitude. Many researchers [114,
127] have proposed different methods to solve load flow solution of unbalanced radial
distribution networks.
An efficient method for load flow analysis plays a critical role in automation
algorithms of RDS whose scope encompasses fault isolation, network reconfiguration and
service restoration. The ability of automation algorithms to handle these complex tasks that
require frequent topological changes in the RDS demands a dynamic topology processor
based on a well-defined data structure. In this chapter, a simple method of load flow
technique for unbalanced radial distribution system is proposed using data structure. The
proposed method involves the solution of simple algebraic equation of receiving end
voltages. However, most of the methods reported require a unique lateral branch and node
numbering method that needs to be pre-processed before the actual load flow can be carried
out using the recursive voltage equation. This unique numbering method is very essential in
obtaining the final solution.
The mathematical formulation of the proposed method is explained in the Section 3.2.
In this section, the modeling of different components of distribution system such as line, load
and transformer etc. are described. The steps of load flow algorithm are explained in Section
3.3. The effectiveness of the proposed method is tested with different examples of
distribution systems in Section 3.4 and the results are compared with the existing methods. In
Section 3.5, conclusions based on the solutions obtained by the proposed method are
presented.
3.2 MODELING OF UNBALANCED RADIAL DISTRIBUTION SYSTEM
Unbalanced radial distribution system can be modeled as a network of buses
connected by distribution lines (with or without voltage regulators), switches or transformers.
Each bus may also have a corresponding load, shunt capacitor and/or co-generator connected
to it. This model can be represented by a radial interconnection of copies of the basic building
block shown in Fig. 3.1. Since a given branch may be single-phase, two-phase, or three-
phase, each of the labeled quantities is respectively a complex scalar, 2 1 or 3 1 complex
vector.
Fig. 3.1 Basic building block of Distribution System
3.2.1 Distribution Systems Line Model
For the analysis of power transmission line, two fundamental assumptions are made,
namely:
Three-phase currents are balanced.
Transposition of the conductors to achieve balanced line parameters.
However, distribution systems do not lend themselves to either of the two
assumptions. Because of the dominance of single-phase loads, the assumption of balanced
three-phase currents is not applicable. Distribution lines are seldom transposed, nor can it be
assumed that the conductor configuration is an equilateral triangle. When these two
assumptions are invalid, it is necessary to introduce a more accurate method of calculating
the line impedance.
A general representation of a distribution system with N conductors can be formulated
by resorting to the Carson’s equations [56], leading to an N×N primitive impedance matrix.
For most application, the primitive impedance matrices containing the self and mutual
impedances of each branch need to be reduced to the same dimension. A convenient
representation can be formulated as a 3×3 matrix in the phase frame, consisting of the self
and mutual equivalent impedances for the three phases. The standard method used to form
this matrix is the Kron’s reduction [56], based on the Kirchhoff’s laws. For instance, a four-
wire grounded wye overhead distribution line shown in Fig. 3.2 results in a 4×4 impedance
matrix. The corresponding equations are
a
ijI aa
ijZ
b
ijI bb
ijZ ab
ijZ
a
iV
c
ijI
b
iV cc
ijZ
bc
ijZ ac
ijZ
an
ijZ b
jV
a
jV
c
iV nn
ijZ
cn
ijZ
bn
ijZ
c
jV
n
ijI
Fig. 3.2 Model of the three-phase four-wire distribution line
n
ij
c
ij
b
ij
a
ij
nn
ij
nc
ij
nb
ij
na
ij
cn
ij
cc
ij
cb
ij
ca
ij
bn
ij
bc
ij
bb
ij
ba
ij
an
ij
ac
ij
ab
ij
aa
ij
n
j
c
j
b
j
a
j
n
i
c
i
b
i
a
i
I
I
I
I
ZZZZ
ZZZZ
ZZZZ
ZZZZ
V
V
V
V
V
V
V
V
… (3.1)
It can also viewed in matrix form as
j-bus
i-bus
A B C N
A B C N
n
ij
abc
ij
nn
ij
Tn
ij
n
ij
abc
ij
n
j
abc
j
n
i
abc
i
I
I
ZZ
ZZ
V
V
V
V … (3.2)
If neutral is grounded, the voltages n
iV and n
jV are considered to be equal. Then from the first
row of Eqn. 3.2, the value of n
ijI can be obtained as
abc
ij
Tn
ij
1nn
ij
n
ij IZZI
… (3.3)
Substituting Eqn. (3.3) into Eqn. (3.2), the Kron’s reduction [56] of voltage equation reduces
to
abc
ij
abc
ij
abc
j
abc
i IZeVV … (3.4)
where,
cc
ij
cb
ij
ca
ij
bc
ij
bb
ij
ba
ij
ac
ij
ab
ij
aa
ijTn
ij
1nn
ij
n
ij
abc
ij
abc
ij
ZeZeZe
ZeZeZe
ZeZeZe
ZZZZZe
… (3.5)
3.2.2 Changing of phase impedances into sequence impedances
Phase components can be changed into sequence components as follows:
AZAZ abc
ij
1012
ij
… (3.6)
abc
i
1012
i VAV … (3.7)
abc
ij
1012
ij IAI … (3.8)
where A is symmetrical component transformation matrix given by
2
2
aa1
aa1
111
A and a= 01201
Now,
22
ij
21
ij
20
ij
12
ij
11
ij
10
ij
02
ij
01
ij
00
ijTn
ij
1nn
ij
n
ij
012
ij
012
ij
ZeZeZe
ZeZeZe
ZeZeZe
ZZZZZe
… (3.9)
The sequence voltage at the jth
bus can be obtained as:
012
ij
012
ij
012
i
012
j IZeVV
i.e.,
2
ij
1
ij
0
ij
22
ij
21
ij
20
ij
12
ij
11
ij
10
ij
02
ij
01
ij
00
ij
2
i
1
i
0
i
2
j
1
j
0
j
I
I
I
ZeZeZe
ZeZeZe
ZeZeZe
V
V
V
V
V
V
… (3.10)
3.2.3 Load Models
The different load models that have been considered are given below.
3.2.3.1 Lumped Load Model
In distribution systems loads can exist in one, two and three phase loads with wye or
delta connections. Also loads can be categorized into four types depending on the load
characteristics; constant power, constant impedance, constant current and complex loads. In
this chapter, the loads considered are of constant power type and can be mathematically
represented as follows
Wye connected loads
*
nph
i
nph
iph
iV
SIL
… (3.11)
where
ph
iIL = load current per phase at ith
bus
nph
iS = power per phase at ith
bus
nph
iV = phase to neutral voltage at ith
bus
Delta connected loads
*
phph
i
nph
iph
iV
SIL
… (3.12)
where
ph
iIL = load current per phase at ith
bus
nph
iS = power per phase at ith
bus
phph
iV = phase voltage at ith
bus
3.2.3.2 Distributed Load Model
Sometimes the primary feeder supplies loads through distribution transformers tapped
at various locations along line section. If every load point is modeled as a bus, then there will
be a large number of buses in the system. Hence these loads are represented as lumped loads:
At one-fourth length of line from sending end a dummy bus is created at which two
thirds of the load is assumed to be connected.
The remaining one-third load is assumed to be connected at the receiving end bus.
3.2.4 Transformer Model
The impact of the transformers in a distribution system is significant. Transformers
affect system loss, zero sequence current, method of grounding and protection strategy.
Three-phase transformer is represented by two blocks as shown in Fig. 3.3, one block
represents the per unit leakage admittance matrixabc
TY , and the other block models the core
loss as a function of voltage on the secondary side.
Fig. 3.3 General Three-phase Transformer Model
3.2.4.1 Core Loss
Core
Loss
Primary Secondary
The core loss of a transformer is approximated by shunt core loss functions on each
phase of the secondary terminal of the transformer. These core loss approximation functions
are based on the results of EPRI load modeling research which state that real and reactive
power losses in the transformer core can be expressed as functions of the terminal voltage of
the transformer. Transformer core loss functions represented in per unit at the system power
base [25] are:
2VC2
eBVABaseSystem
RatingKVA.u.pP
… (3.13)
2VF2
eEVDBaseSystem
RatingKVA.u.pQ
… (3.14)
where,
V is voltage magnitude in per unit.
It is to be noted that the coefficients A, B, C, D, E, and F are transformer dependent
constants.
3.2.4.2 Leakage Admittance Matrix: abc
TY
The admittance matrix part of the proposed three-phase transformer models follow the
methodology derived by [25, 56], for simplification, a single three-phase transformer is
approximated by three identical single-phase transformers connected appropriately. This
assumption is not essential; however, it simplifies the ensuing derivation and explanation.
Based upon this assumption, the characteristic sub matrices used in forming the three phase
transformer admittance matrices can be developed. The Table 3.1 shows the sub-matrices of
TY for the nine most common step-down transformer connection types. The Table 3.2 shows
the matrices for step-up transformer connection types.
Table 3.1 Sub-matrices of TY for common step-down transformer connections [96]
Transformer connection
Bus p Bus s
Self Admittance abc
ss
abc
pp YY
Mutual Admittance abc
sp
abc
ps YY
Table 3.2 Sub-matrices of TY for common step-up transformer connections [96]
where,
t
t
t
1
Y00
0Y0
00Y
Y ,
ttt
ttt
ttt
2
Y2YY
YY2Y
YYY2
3
1Y ,
tt
tt
tt
3
Y0Y
YY0
0YY
3
1Y
tY - Per-unit leakage admittance.
If the transformer has an off-nominal tap ratio α: β between the primary and
secondary windings, where α and β are tappings on the primary and secondary sides
respectively, then the sub-matrices are modified as follows:
Wye-G Wye-G 11 YY
11 YY
Wye-G Wye 22 YY
22 YY
Wye-G Delta 21 YY t
33 YY
Wye Wye-G 22 YY
22 YY
Wye Wye 22 YY
22 YY
Wye Delta 22 YY t
33 YY
Delta Wye-G 12 YY
3
t
3 YY
Delta Wye 22 YY t
33 YY
Delta Delta 22 YY
22 YY
Transformer connection
Bus p Bus s
Self Admittance abc
ss
abc
pp YY
Mutual Admittance abc
sp
abc
ps YY
Wye-G Wye-G 11 YY
11 YY
Wye-G Wye 22 YY
22 YY
Wye-G Delta 21 YY t
33 YY
Wye Wye-G 22 YY
22 YY
Wye Wye 22 YY
22 YY
Wye Delta 22 YY t
33 YY
Delta Wye-G 12 YY
3
t
3 YY
Delta Wye 22 YY
3
t
3 YY
Delta Delta 22 YY
22 YY
a) Divide the self admittance matrix of the primary by α2.
b) Divide the self admittance matrix of the secondary by β2.
c) Divide the mutual admittance matrices by αβ
With the nodal admittance matrix abc
TY , the transformer voltage-current relationship
can be expressed as:
abc
s
pabc
T
abc
s
P
V
VY
I
I
… (3.15)
where,
sssp
psppabc
T YY
YYY
The matrix abc
TY is divided into four 3×3 sub-matrices: Ypp, Yps, Ysp and Yss. Vp and
Vs are the line-to-neutral bus voltages and Ip and Is are injection currents at the primary and
secondary sides of the transformer respectively.
The sequence component of primary and secondary currents can be calculated as
abc
p
1012
p IAI
… (3.16)
abc
s
1012
s IAI … (3.17)
Then for three phase unbalanced system, the total current through branch k, abc
kI is
summation of current at bus j due to self load and the cumulative current of all the branches
connected to bus j.
The equation for 012
jV can be written as
012
k
012
k
012
i
012
j IZVV
… (3.18)
where
012
kI = sequence current vector in kth
branch = abc
k
1IA
012
iV and012
jV are the voltage vectors of ith
and jth
buses respectively.
AZAZ abc
k
1012
k
… (3.19)
where
cc
k
cb
k
ca
k
bc
k
bb
k
ba
k
ac
k
ab
k
aa
k
abc
k
ZZZ
ZZZ
ZZZ
Z
Then the phase voltages can be calculated as:
012abc AVV … (3.20)
These calculations are to be carried out till the bus voltages are converged within the
specified tolerance limits. Then the real and reactive power loss in branch k connected
between i and j buses can be expressed as:
)kSRe(kP abc
ij
abc
Loss … (3.21)
)kS(ImkQ abc
ij
abc
Loss … (3.22)
where
*abc
k
abc
j
abc
i
abc
ij IVVkS
kSabc
ij is a complex power loss in the branch, k connected between buses i and j
abc
iV andabc
jV are voltage at buses i and j respectively and
abc
kI is the current through branch k connected between buses i and j.
The total active power loss (TPL) and total reactive power loss (TQL) are calculated
by using the Eqns. (2.11) and (2.12) given in Chapter 2.
3.3 ALGORITHM FOR LOAD FLOW CALCULATION
Step 1 : Read line and load data of an unbalanced radial distribution system.
Step 2 : Initialize the bus voltages as 1p.u and bus voltage angles for phase – a,
phase - b and phase - c as000 120,120,0 respectively. Initialize TPL, TQL to zero.
Step 3 : Set iteration count =1 and tolerance = 0.0001.
Step 4 : Build BIM and Data Structure of the system using Section 2.3.
Step 5 : Convert phase component of voltages and impedances into sequence components
using Eqns. (3.6) – (3.7).
Step 6 : Calculate sequence component load currents at all buses.
Step 7 : Calculate Sequence voltages (V012
) at all buses using Eqn. (3.18). The phase voltages
(Vabc
) can be calculated using Eqn. (3.20).
Step 8 : Check for the convergence, if the difference between the voltage magnitudes in two
consecutive iterations is less than , then go to Step 9else set count = count+1 and
go to Step 6.
Step 9 : Calculate losses in each branch using Eqn. (3.21) and (3.22) and compute
TPL and TQL.
Step 10 : STOP.
3.4 FLOW CHART FOR THE PROPOSED METHOD
Read Distribution System.
Start
Assume bus voltages for phase system are , , .
Set iteration count (IC) =1, convergence criterion (ε) =0.0001, Initialize real and
reactive power losses to zero
Build Bus Incidence matrix (BIM)
Fig. 3.4 Flow chart of load flow method for unbalanced systems
3.5 ILLUSTRATIVE EXAMPLES
To illustrate the effectiveness of the proposed method is tested with two different
examples consisting of 25 and IEEE 37 bus unbalanced radial distribution systems.
3.5.1 Example – 1
The proposed algorithm is tested on 25-bus unbalanced radial distribution system
whose single line diagram is shown in Fig. 3.5. For the load flow the base voltage and base
MVA are chosen as 4.16 kV and 30 MVA respectively. The line and load data are given in
Appendix B (Table B.1). The voltage profile of the system obtained using load flow solution
is given in Table 3.3. The summary of load flow result of 25 bus system is given in Table 3.4.
Fig. 3.5 Single line diagram of 25 bus URDS
Table 3.3 Load flow result of 25 bus unbalanced radial distribution system
Bus
no.
Proposed method Existing method[127]
|Va|
(p.u.)
Angle
(Va)
(Deg)
|Vb|
(p.u.)
Angle
(Vb)
(Deg)
|Vc|
(p.u.)
Angle
(Vc)
(Deg)
|Va|
(p.u.)
|Vb|
(p.u.)
|Vc|
(p.u.)
1 1.0000 0.0000 1.0000 -2.0944 1.0000 2.0944 1.0000 1.0000 1.0000
2 0.9702 -0.0099 0.9711 -2.1016 0.9755 2.0824 0.9702 0.9711 0.9755
3 0.9632 -0.0122 0.9644 -2.1034 0.9698 2.0796 0.9632 0.9644 0.9698
4 0.9598 -0.0134 0.9613 -2.1043 0.9674 2.0783 0.9598 0.9613 0.9674
5 0.9587 -0.0133 0.9603 -2.1043 0.9664 2.0783 0.9587 0.9603 0.9664
6 0.955 -0.0097 0.9559 -2.1006 0.9615 2.082 0.955 0.9559 0.9615
7 0.9419 -0.0097 0.9428 -2.0997 0.9492 2.0816 0.9419 0.9428 0.9492
8 0.9529 -0.0097 0.9538 -2.1005 0.9596 2.082 0.9529 0.9538 0.9596
9 0.9359 -0.0097 0.9367 -2.0993 0.9438 2.0815 0.9359 0.9367 0.9438
10 0.9315 -0.0097 0.9319 -2.099 0.9395 2.0813 0.9315 0.9319 0.9395
11 0.9294 -0.0097 0.9296 -2.0989 0.9376 2.0813 0.9294 0.9296 0.9376
12 0.9284 -0.0097 0.9284 -2.0988 0.9366 2.0814 0.9284 0.9284 0.9366
13 0.9287 -0.0097 0.9287 -2.0989 0.9368 2.0814 0.9287 0.9287 0.9368
14 0.9359 -0.0096 0.937 -2.0992 0.9434 2.0814 0.9359 0.937 0.9434
15 0.9338 -0.0096 0.9349 -2.099 0.9414 2.0814 0.9338 0.9349 0.9414
16 0.9408 -0.0097 0.9418 -2.0996 0.9483 2.0816 0.9408 0.9418 0.9483
17 0.9347 -0.0096 0.936 -2.0991 0.942 2.0815 0.9347 0.936 0.942
18 0.9573 -0.0122 0.9586 -2.103 0.9643 2.0795 0.9573 0.9586 0.9643
19 0.9548 -0.0122 0.9563 -2.1029 0.962 2.0795 0.9524 0.9544 0.96
20 0.9535 -0.0122 0.9547 -2.1028 0.9603 2.0795 0.9548 0.9563 0.962
21 0.9538 -0.0121 0.9549 -2.1029 0.9605 2.0797 0.9537 0.9549 0.9605
22 0.9518 -0.0121 0.9525 -2.1028 0.9585 2.0799 0.9518 0.9525 0.9585
23 0.9565 -0.0133 0.9584 -2.1043 0.9648 2.0783 0.9565 0.9584 0.9648
24 0.9544 -0.0133 0.9565 -2.1043 0.9631 2.0782 0.9544 0.9565 0.9631
25 0.952 -0.0132 0.9547 -2.1044 0.9612 2.0783 0.952 0.9547 0.9612
From the results the minimum voltages in phases a, b and c are 0.9284 p.u., 0.9284
p.u. and 0.9366 p.u. respectively. Total active power losses are observed as 52.7 kW, 55.41
kW and 41.83 kW in phases a, b and c respectively. Total Reactive power losses are as
58.2048 kVAr, 53.2694 kVAr and 55.6711 kVAr in phases a, b and c respectively. The
voltage regulation is 7.16%, 7.16% and 6.34% in phases a, b and c respectively. The solution
obtained by the proposed method is compared with solution obtained by the existing method
[127] and results are confirmed exactly. The total demand in each phase also can be observed
in Table 3.4.
Table 3.4 Summary of load flow result of 25 bus system
Description Proposed method Existing method [127]
Phase phase A phase B phase C phase A phase B phase C
Total Real power
loss in kW 52.7 55.41 41.83 52.82 55.44 41.86
Total Reactive
power loss in kVAr 58.2048 53.2694 55.6711 58.32 53.29 55.69
Total Real power
demand in kW 1126.000 1138.7102 1125.1284 1126.12 1138.74 1125.16
Total Reactive
power demand in
kVAr 850.2048 854.2695 855.6711 850.32 854.29 855.69
Minimum Voltage
in p.u. 0.9284 0.9284 0.9366 0.9284 0.9284 0.9366
3.5.2 Example – 2
The proposed algorithm is tested on IEEE 37-bus unbalanced radial distribution
system whose single line diagram is shown in Fig. 3.6. For the load flow the base voltage and
base MVA are chosen as 4.8 kV and 100 MVA respectively. The line and load data are given
in Appendix B (Table B.2 to B.6). The voltage profile of the system obtained using load flow
solution is given in Table 3.5. The summary of load flow result of 25 bus system is given in
Table 3.6.
Fig. 3.6 Single line diagram of IEEE 37 bus URDS
Table 3.5 Load flow result of 37 bus unbalanced radial distribution system
Bus
no.
Proposed method Existing method [132]
|Va| (p.u) |Vb|
(p.u)
|Vc| (p.u) |Va| (p.u) |Vb|
(p.u)
|Vc| (p.u)
1 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000
2 0.9863 0.9855 0.9817 0.9863 0.9855 0.9817
3 0.9781 0.9772 0.9719 0.9781 0.9772 0.9719
4 0.9709 0.9715 0.9645 0.9709 0.9715 0.9645
5 0.9652 0.9667 0.9588 0.9652 0.9667 0.9588
6 0.9634 0.9651 0.9571 0.9634 0.9651 0.9571
7 0.9607 0.9631 0.9547 0.9607 0.9631 0.9547
8 0.9582 0.9621 0.9527 0.9582 0.9621 0.9527
9 0.9547 0.9606 0.9494 0.9547 0.9606 0.9494
10 0.9512 0.9596 0.9472 0.9512 0.9596 0.9472
11 0.9501 0.9592 0.9461 0.9501 0.9592 0.9461
12 0.9498 0.9590 0.9451 0.9498 0.9590 0.9451
13 0.9497 0.9589 0.9448 0.9497 0.9589 0.9448
14 0.9763 0.9749 0.9697 0.9763 0.9749 0.9697
15 0.9740 0.9718 0.9672 0.9740 0.9718 0.9672
16 0.9727 0.9683 0.9647 0.9727 0.9683 0.9647
17 0.9726 0.9679 0.9646 0.9726 0.9679 0.9646
18 0.9725 0.9675 0.9645 0.9725 0.9675 0.9645
19 0.9761 0.9746 0.9701 0.9761 0.9746 0.9701
20 0.9757 0.9738 0.9699 0.9757 0.9738 0.9699
21 0.9697 0.9709 0.9635 0.9697 0.9709 0.9635
22 0.9690 0.9705 0.9631 0.9690 0.9705 0.9631
23 0.9686 0.9704 0.9630 0.9686 0.9704 0.9630
24 0.9634 0.9651 0.9571 0.9634 0.9651 0.9571
25 0.9632 0.9642 0.9569 0.9632 0.9642 0.9569
26 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000
27 0.9542 0.9595 0.9478 0.9542 0.9595 0.9478
28 0.9541 0.9593 0.9473 0.9541 0.9593 0.9473
29 0.9497 0.9588 0.9445 0.9497 0.9588 0.9445
30 0.9737 0.9717 0.9671 0.9737 0.9717 0.9671
31 0.9723 0.9714 0.9667 0.9723 0.9714 0.9667
32 0.9709 0.9629 0.9631 0.9709 0.9629 0.9631
33 0.9707 0.9624 0.9629 0.9707 0.9624 0.9629
34 0.9705 0.9619 0.9629 0.9705 0.9619 0.9629
35 0.9686 0.9701 0.9627 0.9686 0.9701 0.9627
36 0.9536 0.9578 0.9475 0.9536 0.9578 0.9475
37 0.9751 0.9737 0.9691 0.9751 0.9737 0.9691
From the results the minimum voltages in phases a, b and c are 0.9497 p.u., 0.9588
p.u. and 0.9445p.u. respectively. Total active power losses are observed as 31.5612 kW,
23.6734 kW and 30.4408 kW in phases a, b and c respectively. Total reactive power losses
are as 24.0121 kVAr, 22.3235 kVAr and 29.1918 kVAr in phases a, b and c respectively. The
voltage regulation is 5.03%, 4.12% and 5.55% in phases a, b and c respectively. The solution
obtained by the proposed method is compared with solution obtained by the existing method
[132] and results are confirmed exactly. The total demand in each phase also can be observed
in Table 3.6.
Table 3.6 Summary of load flow result of 37 bus unbalanced radial distribution
system
Description Proposed method Existing method [132]
Phase phase A phase B phase C phase A phase B phase C
Total Real power
loss in kW 31.5612 23.6734 30.4408 31.56 23.67 30.44
Total Reactive
power loss in
kVAr 24.0121 22.3235 29.1918 24.01 22.32 29.19
Total Real power
demand in kW 885.56 789.67 1163.44 885.56 789.67 1163.44
Total Reactive
power demand in
kVAr 442.01 397.32 521.81 442.01 397.32 521.81
Minimum Voltage
in p.u. 0.9497 0.9588 0.9445 0.9497 0.9588 0.9445
3.6 CONCLUSIONS
In this chapter, the implementation of Data structures for bus identification and load
flow solution for Unbalanced Radial distribution systems has been presented. The modeling
of major components such as line, transformer and load related to unbalanced radial
distribution system is presented. The proposed method is demonstrated with the two different
three phase unbalanced radial distribution systems and the results obtained are compared with
results of existing method.