2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ...

43
Fujian Longyan Zhicheng Ep Co., Ltd.

Transcript of 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ...

Page 1: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

Fujian Longyan Zhicheng Ep Co., Ltd.

Page 2: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

PROPER USE: 1. Please erect cables and connecting wires correctly according to the precautions in the

installation wiring diagram. Installation, commissioning and operation of this equipment can only be carried out by professional persons.

2. The earthing system must be checked strictly. The floor of plant power grid, the floor of high voltage control cabinet, the floor of rectifier transformer and the anode of electrostatic precipitator shall be connected with each other at the same point for earth connection. The shell of control cabinet, the shell of transformer and the shell of main body must be connected reliably before being connected with the earthing terminal. The resistance of earthing system must be ensured to be less than 2�.

3. A piece of multi-core copper cable with a cross section not less than 35mm2 must be arranged for the earthing terminal of each rectifier transformer and directly connected with the earthing busbar of the corresponding high voltage control cabinet, and the sharing of one piece of earthing wire on the control cabinet is not allowed for many rectifier transformers. N line must be led into each high voltage control cabinet, with a cross section not less than 2.5mm2.The secondary signal feedback wire and oil temperature signal feedback wire must be separately arranged with shielded wires respectively.

4. Before the no-load test, a megger must be used to carry out the insulation inspection on the rectifier transformer, and a false load (incandescent lamp) must be used to carry out the power-on test on the high voltage cabinet.

5. The high voltage safety interlocks, operating procedures and high voltage danger warning signs must be improved before the equipment is put into operation formally.

6. During the commissioning and repair of equipment, the operation must be carried out in accordance with the specifications, and the components and parts are strictly forbidden to be pulled out or inserted when they are live.

7. During the operation of equipment, in order to protect the equipment and personal safety, the live switch-over of high voltage isolation switch is strictly prohibited. Copyright statement:

1. All copyrights are the property of our company. Without our explicit written permission, it is not allowed to reproduce and transmit this manual or part of its contents and the violator must bear corresponding responsibilities.

2. For the reason of product improvement, the contents in this manual are subject to change without prior notice. We apologize for the inconvenience it may cause to you, and thank you for your understanding.

3. We have already verified the conformity between the contents of this manual and the hardware described. Because it is difficult of avoid errors, we cannot ensure complete conformity. If you find any unclear matter or error, please do not hesitate to contact us, and we welcome your valuable opinions. Our company reserves the right of final interpretation of this manual.

4. This product is provided with password activation and management functions. The consequence caused by system locking due to uncompleted commercial contract shall be borne by the defaulting party of commercial contract.

We will be with you in the future days. Providing you with top quality products and

services is our perpetual goal – Zhicheng Environmental Protection will create a good business together with you!

Page 3: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

1

Catalog

Chapter I General………………………………………..………………………..1

I. Product name, model and executive standard…………………………………………………..1

II. Product use, scope of application and features…………………………………………………1

Chapter II Main Technical Properties and Technical Parameters…….............4

I. Operating conditions of the product…………………………………………………………….4

II. Main technical parameters……………………………………………………………………..4

III. Product functions and features………………………………………………………………...5

Chapter III Main Structure and Operating Principle………….….…...............6

I. Product structure and outline dimensions……………………………………………………...6

II. Operating principle of primary circuit………………………………………………………...8

Chapter IV Equipment Installation and Use…………………………………...10

I. Equipment inspection and installation………………………………………………………...10

II. Simulation commissioning of equipment…………………………………………………….12

III. Equipment use………………………………………………………………………………..13

IV. Precautions for equipment use……………………………………………………………….16

Chapter V Analysis and Handling of Common Faults during the

OperationEquipment........................................................................….16

Chapter VI Equipment Maintenance and Service……………………….…….20

I. Service of high voltage control cabinet…………………………………………….………….20

II. Service of rectifier transformer……………………………………………………………….20

III. Measurement of earth resistance……………………………………………………………..20

IV. Active part inspection for rectifier transformer………………………………………………20

Chapter VII Product Integration and Spare Parts…………………………….23

Page 4: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

2

Chapter VIII Packing, Transportation and Open-package Inspection of

Product as well as Liability and Warranty Period for Equipment Damage…....23

Annex: Figures & Tables…………………………………………………….24

Table 1: parameter list of common component and parts for GGAj02-�A/�KV series high voltage

rectifier for electrostatic precipitator…………………………………………………....25

Table 2: parameter list of component and parts for GGAj02-�A/�KV series high voltage rectifier

for electrostatic precipitator……………………………………………….………….…27

Table 3: capacity list of GGAj02-�A/�KV series high voltage rectifier for electrostatic

precipitator…………………….…………………………………………………….…..29

Table 4: cross reference table for type selection of capacity of GGAj02-�A/�KV series high

voltage rectifier for electrostatic precipitator…………………………………………...31

Figure 1: wiring diagram for control system of GGAj02-�A/�KV series high voltage rectifier for

electrostatic precipitator…………………………………………………………...……32

Figure 2: schematic diagram for control system of GGAj02-�A/�KV series high voltage rectifier

for electrostatic precipitator (without the communication with a third party)………….33

Figure 3: schematic diagram for control system of GGAj02-�A/�KV series high voltage rectifier

for electrostatic precipitator (with the communication with a third party)……………..34

Figure 4: outline and structural diagram for GGAj02-�A/�KV series high voltage control

cabinet…………………………………………………………………………………..35

Figure 5: outline and structural diagram and parameter list for GGAj02-�A/�KV series high

voltage silicon rectifier transformer………………………………………………….….36

Figure 6: outline diagram for side entry bottom exit high voltage isolation switch cabinet……..37

Figure 7: outline diagram for safety earthing switch cylinder……………………………………38

Page 5: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

1

Chapter I General

I. Product name, model and executive standard

1. Product name: high voltage rectifier for electrostatic precipitator.

2. The model of this product is defined as follows:

G G A j 02 (ZC11) - �A / �kV - �

Silicon rectifier Derivative code

For high voltage Rated rectified voltage (kV)

Oil-immersed natural cooling Rated rectified current (A)

Voltage regulation by thyristor Design code

3. Executive standard: JB/T9688-2007 Crystal Brake Pipe Controlled High-Voltage Source for

Electric Dust Collector.

II. Product use, scope of application and features

1. Applicable scope of product

The basic function of this product is to transform the power frequency alternating current

power into high voltage direct current power for output. It can be used with proper selected

mechanical devices such as electrode, etc. to form a high voltage electrostatic precipitator, which is

applicable to various applications in the industrial departments such as dedusting, defogging,

dehydration, impurity separation as well as recovery of rare metals and other raw materials, etc. and

is an important piece of equipment for environmental protection, comprehensive development and

utilization. The specific scope of application is as follows:

Sector Use

Metallurgical

industry

To be used for smelting of black and nonferrous metals, dedusting, recovery

of raw materials for metal smelting and their comprehensive utilization

Building

material industry

To be used for dedusting and raw material recovery in the cement and

refractory industries

Electric power

industry To be used for flue gas dedusting of the boiler

Petroleum

industry

To be used for separation of salt, moisture or other impurities contained in

crude oil

Page 6: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

2

Chemical

industry

To be used for recovery of valuable constituents in flue gas and defogging

and dedusting, etc. in the acid production industry

Light and textile

industries To be used for recovery and dedusting in the paper and textile industries

Precision

machinery To be used for air purification and improvement of product quality

2. Product features:

As the high voltage power supply is a core product for electrostatic dedusting, we always pay

close attention to technical progress, seek innovation and improve strategies.

GGAj02 series high voltage power supply takes the HVC-ZC11 intelligent controller for high

voltage power supply most recently researched and developed by our company as its kernel control

component. The HVC-ZC11 intelligent controller for high voltage power supply is a new generation

controller designed and manufactured by using modern electronic technology, which is focused on

four great objectives of “all-digital technical feature, high precision spark response and control,

ingenious control function and network-based design concept”, based on sufficient absorption of the

essence of DAVC controller product manufactured by American GE company and in combination

with many incisive control theories. The product has the following main technical features:

It selects the 32-bit ARM7 core based MCU as its central processing unit (CPU), which

can acquire relevant data in real time and calculate the electric field parameter and spark

parameter rapidly, thus controlling the trigger angle of silicon controlled rectifier accurately.

It has advantages such as rapid response speed, accurate control and high reliability, etc.

It selects 240×128 high-brightness blue-screen LCD for information display. Total Chinese

information display and advanced wizard push-key program make the man-machine

interface become very clear and easy for operation. It can be designed into multiple

language display according to needs so as to meet the requirements of export projects.

The advanced control program is provided with many operating modes, which can be

selected appropriately according to the use requirements in different industries and various

operating conditions on site so as to make the electrostatic precipitator reach the best

operating effect. Its dynamic spark tracing and detection technology can automatically

distinguish flashover in different intensities and carry out corresponding control, thus

Page 7: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

3

making the voltage of electric field recovered from flashover as fast as possible and

improving the efficiency of dust collection. Its perfect and reliable protective functions

make the electrostatic precipitator able to operate stably and reliably for a long period of

time.

With the photoelectric full isolation technology and switch power technology as well as the

circuit board designed and manufactured by adopting advanced surface mounting

technology (SMT), the product is featured with preeminent quality, high reliability, strong

anti-interference ability, etc. Meanwhile, the controller is mounted on the door plate with

advantages such as compact structure, convenient operation, etc.

The shutdown recording program can record the most recent fault as well as the operating

parameters and time when the fault occurs, which provides great convenience in the

troubleshooting. Meanwhile, the controller implements registration management and green

shade service, thus the user can obtain the best aftersales service.

With strong communication networking function, it can realize seamless communication

with the DCS system of our party or a third party.

a. It adopts the most common RS485 serial communication interface on site and

follows MODBUS communication protocol, thus it can conduct data exchange directly

with the PLC and DCS of any mainstream brand in the world; the operating data and

controlling parameters of each power supply can be uploaded to the host computer of DCS

through MODBUS communication protocol; alternatively, the high voltage data of several

electric fields can first be integrated to the PLC in the low voltage control system and then

be uploaded to the host computer through the communication interface (Ethernet or

MODBUS) on the PLC itself by utilizing the margin list, and the host computer manages,

regulates and controls each high voltage equipment indirectly through PLC.

b. It reserves CAN2.0 communication interface, which can realize the high speed

communication connection between up to 127 sets of high voltage power supplies and a

single PLC or host monitoring computer at the same time, build the required DCS work

station and realize data acquisition and exchange with the highest communication speed up

to 1MB/S (40M) and the maximum communication distance of a single node up to 10KM

(5KB/S). For the user who requires CAN2.0 communication, it only needs to change the

Page 8: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

4

communication module.

c. Besides being designed with RS485 and CAN2.0 full open communication

interfaces, the HVC-ZC11 intelligent controller for high voltage power supply is also

designed with hard wired communication interfaces, which can build non-open

communication connection conveniently with the DCS of a third party and realize the

function of remote startup and shutdown and voltage regulation of equipment.

Chapter II

Main Technical Properties and Technical Parameters

I. Operating conditions of the product

1. The altitude above sea level shall not exceed 1000m. If the altitude above sea level is

beyond 1000m, corresponding modification shall be conducted according to Annex B of

GB/T3859.2-1993.

2. For the control cabinet, the ambient temperature shall be -10 ~ +40 ; for the rectifier

transformer, the ambient temperature shall not be higher than +40 and shall not be lower than the

temperature of condensation point specified by the transformer oil.

3. The maximum relative humidity of air is 90% (corresponding to the air temperature of

20±5 ).

4. No violent vibration or impact is found, and the vertical inclination shall not be more than

5%.

5. There shall not be any conducting and explosive dust or any gas or steam which can corrode

metal and damage insulation at the operating place.

6. The frequency fluctuation of alternating current power supply shall not be more than ±2 .

7. The continuous fluctuation range of alternating current sinusoidal voltage amplitude shall

not exceed ±10 of rated alternating current sinusoidal voltage.

8. If the high voltage power supply is required to operate in special working conditions, then

the user shall put forward this requirement when placing an order and solve it through consultation

with the manufacturer.

II. Main technical parameters

1. Input and output parameters

For the input and output technical parameters of common series products for GGAj02 (ZC11)

Page 9: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

5

high voltage power supply, see attached table (3).

2. Output regulation range

Regulation range of output current: 0~100% of rated value;

Regulation range of output voltage: 0~100% of rated value.

3. Voltage regulation method

The voltage can be regulated at the net side of rectifier transformer with a thyristor, with

the regulation range of conduction angle of 0~179°.

4. Grade of load

The grade of load is “I" (100% of rated output current, continuous).

III. Product functions and features

1. Control function

The product is provided with many control modes, which can be selected by the user in

different operating conditions.

Manual control

Remote control

Spark tracing control

Maximum average voltage control

Intermittent power supply control

Constant voltage, constant current and constant conduction angle control

Other different control modes (e.g. critical spark control, constant spark rate control, back

corona detection control, etc.) can also be provided according to the user’s requirements.

2. Fault detection and protection function

The equipment is provided with the following protection functions. If any fault is found during

the operation of equipment, the controller will display the type of fault and automatically cut off the

power supply of primary circuit.

Load short-circuit protection

Load open-circuit protection

Primary overcurrent protection

Temperature sensor break-line protection

Dangerous oil temperature protection

Page 10: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

6

SCR short-circuit protection

Deflected excitation protection

Transformer overtemperature protection

Transformer gas protection (the control signal will be provided by the gas relay)

Other protection for switching signals provided from outside

3. Fault display and operating parameter display function

The panel of control cabinet is provided with a 240x128 liquid crystal display (LCD), which

can display operating parameters such as primary voltage, primary current, secondary voltage,

secondary current, transformer oil temperature, conduction angle, etc. When a trip occurs due to a

system fault or a system fault is self checked out, it will display the cause of fault.

4. Flashover control function

The HVC-ZC11 intelligent controller for high voltage power supply is provided with two

methods, i.e. by means of hardware and software to detect the flashover signal simultaneously.

Especially, its dynamic spark tracing and detection technology by means of software can

automatically calculate the turn-off half-wave number of thyristor according to the flashover energy

of electric field. Thus, it ensures that the electric field will gain the maximum average voltage in

case no arc discharge appears in the electric field, thus improving the dedusting efficiency.

5. Automatic recovery function

When the program cannot be performed due to factors such as external interference suffered by

the controller or sudden decrease in the supply voltage, etc., the processing unit will be reset

automatically within the set time and restore to the original working condition before interference.

Chapter III

Main Structure and Operating Principle

I. Product structure and outline dimensions

The complete set of high voltage rectifier for electrostatic precipitator is commonly composed

of high voltage control cabinet, rectifier transformer and damping resistor. If the user selects the

outdoor type (with the cable exit at the high voltage side) rectifier transformer, the high voltage

isolation switch cabinet can be provided according to the user’s requirements.

1. High voltage control cabinet

The high voltage control cabinet is of standard cold bent steel frame structure, with uniform

Page 11: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

7

outline dimensions of 600×600×2200. The color of cabinet frame is: GSB05-1426-2001 [light sea

(iron) blue], and the color of door plate is: GSB05-1426-2001 (sea grey). The cable entry mode is

divided into: top entry and bottom entry. If you have any special requirement for the outline

dimensions and colors, please put forward it when placing an order.

For the appearance of high voltage control cabinet, see attached figure (3).

2. Rectifier transformer

The rectifier transformer is an oil-immersed natural cooling type, including such two sections

as of alternating current booster and high voltage silicon bridge rectifier stack. The transformer

adopts the ri-shaped iron core (“ri” is a Chinese character), which is featured with small loss, low

temperature rise and small volume through computer-aided optimized design. The silicon rectifier

stack adopts avalanche components with long service lifetime, which can be recovered by itself

after instant breakdown and is mounted in the transformer container.

According to the series program recommended by the national standards, the rated output

direct current (average) of rectifier transformer is (unit: A): 0.05, 0.1, 0.2, 0.4, 0.6, 0.7, 0.8, 1.0, 1.2,

1.4, 1.6, 1.8 and 2.0, that is, thirteen grades altogether; and the rated output direct current voltage is

(unit: KV): 40, 50, 60, 66, 72, 80, 90, 100 and 120.

For the rated current and voltage beyond the above series program, we can provide them

according to the user’s requirements.

The structural type of rectifier transformer is high impedance rectifier transformer, which is

divided into the type of cable exit at the high voltage side (outdoor type) and the type of cable exit

at the top (indoor type).

For the outline drawing of rectifier transformer, see attached figure (4).

3. Damping resistor

The damping resistor is connected in series between the high voltage output end of rectifier

transformer and the cathode line of electrostatic precipitator, which is a protective component in the

electric circuit system of rectifier. It plays an important role in the suppression of flashover impact

current, absorption of higher harmonic wave and protection of control circuit during the operation.

For the outdoor type rectifier transformer (with cable exit at the high voltage side) provided

with high voltage isolation switch cabinet, the damping resistor is commonly mounted in the high

voltage isolation switch cabinet.

Page 12: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

8

The resistance and power of damping resistor shall be selected according to “Parameter List

for Main Components in the Primary Circuit” (attached table 2).

4. High voltage isolation switch and switch cabinet

The high voltage isolation switch is used to connect the high voltage incoming terminal in the

electric field of electrostatic precipitator with the high voltage output terminal of rectifier

transformer or the ground so as to ensure the personal safety during the repair of electrostatic

precipitator.

The high voltage isolation switch cabinet is generally used with the outdoor type rectifier

transformer and is placed between the rectifier transformer and temperature holding cabinet. The

flange of high voltage protective cover on the outdoor type rectifier transformer shall be joined to

the inlet flange of switch cabinet. The high voltage inlet and outlet directions of high voltage

isolation switch cabinet as well as the on-off operating direction of high voltage isolation switch

shall be determined by the user according to site arrangement.

II. Operating principle of primary circuit

For the electric schematic diagram, see attached figure (2).

The electric schematic diagram is mainly composed of primary circuit, operating control

circuit and auxiliary circuit (e.g. cooling fan), etc. The single phase alternating current 380V, 50 Hz

power supply is connected with the primary contactor KM1 through fuses FU1 and FU2. After the

control of primary contactor KM1, one output is connected with the input terminal A of transformer

through two silicon controlled rectifiers V1 and V2 in inverse parallel; the other output is connected

with the X1 terminal of transformer through the primary current transformer TA1. The phase-shifted

and voltage-regulated single phase alternating current power supply is output as the negative high

voltage after the voltage boosting and current rectification of transformer, and is supplied to the

electrostatic precipitator through the damping resistor. R7 and R6 are respectively the current

sampling resistor and voltage sampling resistor at the direct current high voltage side. The

secondary current and secondary voltage sampling signals are sent to the controller, which output

the conduction angle of trigger signal controlled thyristor (silicon controlled rectifier) after the

operation and processing of computer system. This automatic control system adopts the dual

closed-loop automatic control system with current inner loop feedback and voltage outer loop

feedback. The functions of other main components in the primary circuit are as follows:

Page 13: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

9

Alternating current voltmeter PV1: it displays the primary side voltage of rectifier transformer

after the voltage regulation of silicon controlled rectifier.

Alternating current ammeter PA1: it displays the primary side current of rectifier transformer.

Direct current voltmeter PV2: it displays the direct current voltage output by the equipment,

also called the secondary voltage.

Direct current ammeter PA2: it displays the direct current output by the equipment, also called

the secondary current.

R1 and C1 are resistance-capacitance absorption circuits.

Piezoresistors RV1-5: they absorb surge overvoltage.

Damping resistor R5: it buffers the spark discharge current and damps the parasitic oscillation

caused by LC distribution parameter in high voltage output circuit.

Resistor R4: it is a high voltage sampling dropping resistor.

Current transformer TA1: it provides the analog meter and controller with primary current

signal.

The power switch SA1 for control circuit: the on-off control for power supply of control circuit

and selection of local control/central control can be realized through SA1.

Isolation transformer T2: it provides the control circuit and remote control communication

board with AC 220V alternating current power supply after the isolation and voltage transformation

of single phase 380V, 50Hz power supply.

Safety interlock relay KA1: it realizes the safety interlock control of high voltage control

system. The system can be allowed to start up only after each safety interlock link is closed in

position and it is picked up.

Startup/shutdown control relay KA2: it realizes the startup and shutdown control of high

voltage control system. The control auxiliary contactor KM2 is energized after it is picked up, thus

controlling the pick-up of primary contactor KM1; and the control intermediate contactor KM2 and

the primary contactor KM1 are both de-energized and released after it is de-energized.

Fault alarm relay KA3: when any fault trip phenomenon appears in the system, it will act and

send out a sound and light alarm signal.

Primary contactor KM1: it controls the switch-on or cut-off of primary circuit.

Auxiliary contactor KM2: it controls the pick-up or release of primary contactor KM1.

Page 14: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

10

Chapter IV

Equipment Installation and Use

I. Equipment inspection and installation

1. Installation and inspection of transformer

(1) After the transformer is transported to the installation site, make sure to inspect if the

porcelain bush has any collision injury and if the sealing section has any oil permeation

phenomenon.

(2) The body of transformer is provided with four symmetrical lifting hooks, which are used to

lift or hoist the entire transformer. The lifting eyes on the tank cover are only be used for core lifting

(note: these lifting eyes cannot be used for lifting the entire transformer). During the lifting, the

angle between the transformer body and vertical line shall not exceed 30%. If this condition cannot

be satisfied, a special intermediate crossbeam can be used to lift the transformer.

(3) Insulation inspection

The insulation resistance of rectifier transformer can be checked and measured with a

1000V/2500V megger. Before the inspection, the secondary voltage/current sampling board shall be

dismantled. The readings of insulation resistance are as follows:

2. Installation of transformer

(1) When lifting the transformer, the wire cable with the diameter of 20~25mm shall be used to

Measurement

object

High voltage output

to earth

High voltage output to

current sampling

High voltage output to

voltage sampling

Resistance (M�) 2500

Reverse

direction

2500

Forward

direction

0.5

78

Measurement

object

High voltage output

to low voltage

terminal

Low voltage terminal to

earth

Resistance (M�) 2500 1000

Page 15: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

11

hook up the lifting eyes on the transformer tank body for lifting; if the lifting hooks are used for

lifting, then the diameter of lifting hooks shall not be more than 30mm so as to avoid damaging the

radiating fins due to compression. It is strictly forbidden the use the lifting eyes on the tank cover to

lift the entire transformer.

(2) When the high voltage rectifier transformer is installed in the isolation chamber, it shall be

kept more than 1m away from walls.

(3) After the installation and commissioning of high voltage rectifier transformer are finished

in position, the universal wheel shall be fixed at the bottom of transformer with channel steel so as

to prevent the displacement.

3. Installation of high voltage control cabinet

The high voltage control cabinet must be fixed with anchor bolts according to the requirement

of outline drawing.

4. Installation and arrangement of circuit

(1) Conduct wiring according to attached figure 1. Besides providing 380V alternating current

power supply, the power supply incoming line must also provide N line with a cross section not less

than 2.5mm2.

(2) According to relevant provisions of low voltage power distribution, select the specified

copper core cable to connect the power supply, high voltage control cabinet and silicon rectifier

transformer. The current and voltage feedback signal wires shall adopt RVVP4×1.5mm² shielded

cable, and the metal shielded layer shall have single end earthing within the controller or high

voltage control cabinet. When the equipment communicates with the PLC or host computer, it shall

adopt DJYPVP3×2×0.5 mm² triple twisted pair pairwise shielded cable.

Note: the secondary current and voltage sampling signals and the rectifier transformer oil

temperature sampling signal must be connected with the control cabinet through their respective

shielded cables, which cannot be replaced by common control cables.

(3) The earthing terminals of control cabinet, rectifier transformer and load shell must all be

grounded very reliably, with their earthing resistance not more than 2.0�. In order to prevent the

interference, the earthing terminals of high voltage control cabinet, rectifier transformer and load

(e.g. the anode of electrostatic precipitator) shall be connected with each other at the same point for

earth connection

Page 16: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

12

The detailed arrangement method for earthing wires is as follows: a piece of multi-strand

copper core wire with a cross section not less than 35mm2 shall be directly arranged from the

earthing terminal of each rectifier transformer to the earthing busbar of high voltage control cabinet.

Meanwhile, a piece of multi-strand copper core wire with a cross section not less than 16mm2 shall

be arranged from the earthing terminal of rectifier transformer to the earthing bolt on the

transformer shell, then a piece of multi-strand copper core wire with a cross section not less than

16mm2 shall be arranged from the earthing bolt to the anode of load (i.e. the shell of main body).

(4) The equipment wiring shall comply with relevant provisions of high voltage and low

voltage wiring specified by the country.

(5) In order to prevent the interference, during the cable arrangement, the power cable, signal

cable and communication cable shall be separately arranged so as to avoid mutual cross

interference.

II. Simulation commissioning of equipment

1. False-load test of the high voltage control cabinet

In order to ensure the safe reliability of equipment, before the first operation and reoperation

after the repair of the equipment, two pieces of power primary cables must be disconnected between

the high voltage control cabinet and rectifier transformer; two incandescent lamp bulbs with their

power not less than 100W shall be connected with each other in series and then be connected with

the power outlet terminal of high voltage control cabinet. Do voltage stepup test in manual

operating mode by using normal equipment starting method so as to ensure that the equipment will

be connected with the rectifier transformer to work at load only after the silicon controlled rectifier

can be triggered normally.

2. Fault alarm test of the equipment

(1) Oil temperature alarm: the rectifier transformer shall be equipped with a PT100

temperature sensor. When the transformer oil temperature reaches 85 , the controller will send out

a trip signal and give an alarm, and the display screen of controller will display the oil temperature

out-of-tolerance fault of transformer.

(2) High voltage safety interlock: after the installation of transformer, control cabinet and load,

it is necessary to interlock the high voltage output available switch with the startup operation of

control cabinet so as to ensure safe power supply. When the safety interlock is not available, it is not

Page 17: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

13

allowed to start the equipment, and the controller has the prompt for unavailable safety interlock.

(3) Load open-circuit/short-circuit protection: when the high voltage output of transformer is

open-circuited, the controller can trip for open circuit and meanwhile control the secondary voltage

does not exceed the rated value; when the high voltage output of transformer is short-circuited, the

controller can trip for short circuit and meanwhile control the secondary current does not exceed the

rated value.

III. Equipment use

1. Check and adjustment before the first startup

(1) Disconnect the power supply for entering the control cabinet;

(2) Check if the plug of controller is connected reliably;

(3) Check if all wires are correct and reliable;

(4) Check if all fuses are in good conditions and without looseness;

(5) Check the insulation of load (electric field of electrostatic precipitator) with a 2500V

megger, and its resistance value shall be above 100M� generally.

(6) Check if the secondary current and voltage sampling resistances comply with the

requirements with a multimeter. For the standard secondary current sampling resistance of the

equipment of various specifications, see attached table (2), and the secondary voltage sampling

resistance is 7.8K�.

2. Local startup of the equipment:

Close the circuit breaker QF1 of operating power supply, and the “power indicator” green lamp

HL1 will be lit. The master switch SA1 will be changed over to “local” position. The HVC-ZC11

high voltage intelligent controller for power supply will be energized for self-check and be rest by

itself. The display screen will display the salutatory interface, then enter the shutdown recording

interface. After the “confirmation” key is pressed, the system will enter the initial waiting interface.

At this time, if the “automatic” key is pressed, then the controller will automatically control the

pick-up of primary contactor KM1. After that, the voltage will be increased slowly until it reaches a

set limit value. Then, it will operate around this value. When the “manual” key is pressed, it will

enter the manual waiting interface. At this time, the required operation can be selected according to

the menu. After the primary contactor KM1 is picked up, the “power indicator” green lamp HL1

will be turned out and the “system operating” red lamp HL2 will be lit, thus the system will enter

Page 18: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

14

the operating state.

Note: when starting the equipment for operation, if the controller has the prompt for

“unavailable safety interlock”, then it indicates that the high voltage isolation switch is not changed

over to the “operating” position or the interlock is connected virtually. At this time, the equipment is

unable to start up. Please try it again after confirming the position of high voltage isolation switch.

3. Local shutdown of the equipment:

After the “stop” key is pressed, the controller will first make the output voltage drop to zero,

then release the primary contactor KM1 and disconnect the primary circuit. At this time, the

“system operating” lamp HL2 is turned out and the “power indicator” lamp HL1 is lit, then it will

be alright after making the master switch SA1 change over to the “off” position. 4. Remote control

of the equipment:

When the equipment requires remote centralized control, first close the circuit breaker QF1 of

operating power supply, then make the master switch change over to the “central control” position.

At this time, the controller is unable to carry out operations such as startup, voltage step-up or

step-down, etc. The work of equipment startup, voltage step-up or step-down, etc. is completely

controlled by the remote PLC or DCS.

5. Operating instructions of the controller

The HVC-ZC11 intelligent controller is provided with a 240x128 high-brightness liquid crystal

display (LCD) and four thin-film keys as the man-machine dialogue window. Among four keys,

except that the reset key is a fixed key, other three keys are draw keys, with their current functions

to be determined by the wizard push-key program. The operator only needs to carry out operation

according to the prompt on the LCD, which is very straight and simple. Six commonly used display

interfaces are shown as follows:

Salutatory interface Shutdown recording interface

Record: the load has an open-circuit fault!

Primary voltage: 095V Secondary voltage: 072KV

Primary current: 005A Secondary current: 000mA

Conduction angle: 045° Mode of power supply:

continuous

Faith moves mountains

-- Welcome you to use the product manufactured by

Zhicheng Environmental Protection --

Rectifier transformer oil

Page 19: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

15

temperature: 028

Shutdown time: July 16, 2011-15:30:25

Commissioning Setting Confirmation

Reset Reset

Initial waiting interface Manual waiting interface

Prompt: the system is at the initial waiting state! Prompt: this cabinet is at the manual waiting state!

Primary voltage: 000V Secondary voltage: 000KV Primary voltage: 000V Secondary voltage: 000KV

Primary current: 000A Secondary current: 000mA Primary current: 000A Secondary current: 000mA

Conduction angle: 000 Mode of power supply:

continuous Conduction angle: 000

Mode of power supply:

continuous

Rectifier transformer

oil temperature: 000 Current limit: 800mA

Rectifier transformer oil

temperature: 000 Locking: conduction angle

Spark rate: 000 Spark rate: 000

15:35:56 Manual Automatic Setting 15:36:20 Return Startup Setting

Reset Reset

Automatic operating interface Parameter setting interface

Prompt: this cabinet is at the automatic voltage step-up state! Voltage limit: 072KV Turn-off wave number: 01

Primary voltage: 321V Secondary voltage: 066KV Current limit: 800mA Slow step-up rate: 05

Primary current: 198A Secondary current: 752mA Shortcut limit: current Recovery wave number: 06

Conduction angle: 126 Mode of power supply:

continuous

Initial value of fast

step-up: 40%

Peak value of fast

step-up: 95%

Rectifier transformer

oil temperature: 029 Current limit: 800mA Tracing time: 000 Intermittent ratio: 2:02

Spark rate: 000 Mode of power supply:

continuous

Voltage reduction by

rapping: 50%

15:38:25 Stop Step-down Limit Up � Down � Confirmation

Reset Reset

6. Fault trip:

Page 20: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

16

When the faults such as permanent short circuit, open circuit, primary overload, oil

temperature out-of-tolerance, heavy gas alarm, etc. occur in the electric field, the HVC-ZC11

controller will judge them automatically and output the trip signal. At this time, the startup and

shutdown control relay KA2 will be de-energized, the contacts KM2 and KM1 will be released to

disconnect the primary circuit, the fault alarm relay KA3 will be energized, and the fault alarm

buzzer HA1 will give a sound and light alarm. LCD will display the fault parameters and fault

causes. After the “confirmation” key is pressed, the fault alarm relay KA3 will be energized, stop

giving an alarm and return to the initial waiting interface.

IV. Precautions for equipment use

1. In order to ensure the equipment and personal safety, it is strictly forbidden to change over

the high voltage isolation switch or switch off the power supply switch directly when the equipment

is at operating state.

2. The current and voltage feedback signal wires between the rectifier transformer and control

cabinet must use metal shielded wires so as to prevent from the interference.

3. In order to ensure the personal safety, it is strictly forbidden to enter the high voltage

isolation chamber during the operation of equipment.

Chapter V Analysis and Handling of Common

Faults during the Operation of Equipment

Abnormal fault

phenomenon Cause analysis Handling method

1.Fault characteristics of

short circuit: very low

primary voltage, relatively

big primary current, nearly

zero secondary voltage and

very big secondary

current.

(1) The high voltage isolating knife is

grounded.

(2) The high voltage cable is breakdown or

the insulation of terminal connector is

damaged or breakdown, thus causing a

short circuit to earth.

(3) The ash hopper of electric field has a

serious ash accumulation, thus causing a

short circuit between the electric cathode

(1) Put the high voltage

isolating knife at the electric

field position.

(2) Handle or replace the

cable or terminal connector.

(3) Discharge the ash

accumulated in the ash

hopper.

(4) Shut down the boiler to

Page 21: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

17

and dust collecting electrode.

(4) The line of electric cathode is broken,

thus causing a short circuit.

(5) The ceramic rotating shaft on the

rapping device of electric cathode is

damaged or the ceramic shaft tank has a

serious ash accumulation, thus causing a

short circuit to earth.

(6) The damping resistor at the top of

electric field is dropped and grounded.

(7) The metallic foreign matters between

different electrodes causes a short circuit.

(8) The high voltage insulator is damaged

or the inner wall of quartz bush has dew

condensation, thus causing a short circuit

to earth.

(9) The ash discharging device has a fault

or the ash hopper has an ash accumulation,

thus causing a short circuit between two

electrodes.

handle the broken line.

(5) Replace the ceramic

rotating shaft or eliminate

the ash accumulation.

(6) Restore or replace the

damping resistor.

(7) Shut down the boiler to

handle and eliminate the

foreign matters.

(8) Replace the damaged

insulator, eliminate the ash

accumulation. Add a heating

device or increase the

heating temperature.

(9) Repair the ash

discharging device and

discharge the ash

accumulated in the ash

hopper.

2.Fault characteristics of

open circuit: relatively

low primary voltage,

nearly zero primary

current, very high

secondary voltage and

zero secondary current.

(1) The high voltage isolating knife is not

in position.

(2) The damping resistor at the top of

electric field is blown out.

(1) Put the high voltage

isolating knife at the electric

field position.

(2) Replace the damping

resistor.

3.Fault characteristics:

normal primary voltage,

relatively low primary

(1) The rapping period of electric cathode

is too long, thus causing a serious ash

accumulation on the line of electric

(1) Adjust the rapping

period.

Page 22: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

18

current, relatively low

secondary voltage and

obviously reduced

secondary current.

cathode and generating a corona

obstruction.

(2) The rapping force of electric cathode is

not big enough.

(3) The rapping device for the line of

electric cathode has a fault.

(4) The flue dust concentration at the inlet

of electric field is too high.

(5) The dust specific resistance is too big,

thus causing a back corona (too high or too

low secondary current).

(2) Handle and improve the

rapping system.

(3) Handle the fault or shut

down the boiler to handle

the seized hammerhead, etc.

(4) Contact the boiler to

adjust the combustion and

calcined powder.

(5) Change the coal type.

4.Fault characteristics:

lower primary voltage,

lower primary current,

lower secondary voltage

and lower secondary

current. All of them have

vibration. The high voltage

rectifier transformer is

accompanied by abnormal

sound. With the increase of

current, the “puffing”

sound will be raised and

the oil temperature will be

increased.

(1) The trigger pulse circuit of silicon

controlled rectifier is not symmetric.

(2) A silicon controlled rectifier is

short-circuited, thus causing deflected

excitation operation.

(1) Replace the pulse trigger

plate.

(2) Replace the damaged

silicon controlled rectifier.

5. Fault characteristics:

normal primary voltage

and normal primary

current. No display on

the meter of secondary

(1) The meter is damaged.

Replace the meter.

Page 23: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

19

voltage or secondary

current, but normal

display on the

controller.

6. Fault characteristics:

when the “startup” key

is pressed, the fault type

displayed on the

controller is: “short

circuit alarm” or “open

circuit alarm”, and

meanwhile, measure the

output terminal with a

multimeter (wire size:

104, 108), which is as

big as power supply

voltage.

(1) The resistance-capacitance absorption

capacitor C1 or the resistance-capacitance

absorption resistor R1 is damaged.

(2) One or two silicon controlled rectifiers

are damaged.

Replace the fault

component.

7. Fault characteristics:

when the “step-up” key

is pressed, the primary

current, primary

voltage, secondary

current and secondary

voltage do not have any

reaction and are always

zero.

(1) The primary contactor has a fault or the

primary circuit is not formed.

(2) The controller or the pulse trigger plate

has a fault.

Replace the fault

component.

8. Fault characteristics:

once startup, the

equipment will trip. The

controller will display

(1) One or two silicon controlled rectifiers

are short-circuited.

(1) Replace the fault silicon

controlled rectifier.

Page 24: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

20

“primary overcurrent”

or “very big primary

current”, while the

secondary current and

secondary voltage are

almost zero.

(2) The primary side cable is breakdown or

short-circuited to earth.

(2) Replace the fault cable.

Chapter VI

Equipment Maintenance and Service

I. Service of high voltage control cabinet

Regularly check if there is any overheating, looseness or damage on the components and parts,

circuits and wires within the high voltage control cabinet; according to the ambient conditions on

the site, regularly clean and wipe the high voltage control cabinet to keep the cleanness in the high

voltage control cabinet and rectifier transformer bushing.

II. Service of rectifier transformer

1. Regularly check if the drying agent of rectifier transformer has any change in color. If any, it

shall be replaced promptly.

2. Regularly check if the oil level and temperature rise of rectifier transformer are normal. If

not, please handle them promptly.

3. Regularly wipe the shell of rectifier transformer and check if the shell has any rusting so as

to ensure the cleanness of rectifier transformer and soundness of protective paint on the shell.

4. The transformer oil test shall be conducted annually, which shall comply with the provisions

of GB/T7595-2000. The breakdown voltage shall not be less than 40KV/2.5mm, otherwise,

the oil shall be filtered again or replaced with new oil. The withstand voltage value of new oil

shall be more than 45KV/2.5mm.

III. Measurement of earth resistance

The earth resistance of system shall be measured annually, and the earth resistance value of

each point shall not be more than 2.0�.

IV. Active part inspection for rectifier transformer

Page 25: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

21

1. When it has any doubt about the interior after the rectifier transformer has any collision or

other events during the transportation or it needs to conduct repair after a fault occurs during the

operation, the active part inspection shall be conducted.

2. Active part operation for rectifier transformer

(1) Before the active part is lifted, first loosen the oil drain valve on the lower part of

transformer tank and discharge about 80KGS of transformer oil. Pay attention to ensure that the

discharged oil is contained and sealed in a clean vessel so as to prevent the transformer oil from

being polluted. Meanwhile, its storage time shall be as short as possible for fear of becoming damp

and reducing the dielectric strength.

(2) Remove all connecting bolts on the tank cover and tank body.

(3) Before the active part is lifted, for the outdoor type, first open the small cover plate and

stretch the hand into the oil tank. The lifting can be conducted only when the wires between the

high voltage output and porcelain insulator connecting terminal are released with a wrench. After

the active part inspection is finished, the active part shall be put into the oil tank and then restored to

its original condition.

(4) When the active part is lifted, pay attention to the balance of gravity center on the active

part. Four corners of the oil tank shall be monitored so as to prevent from the collision between the

active part and tank body and cause any damage.

(5) After the active part inspection is finished, put the active part into the oil tank and install

and fasten it in opposite direction. Connect the high voltage output wire and fill in the transformer

oil.

3. Main items in the active part inspection are as follows:

(1) If the coil has any collision injury and if the silicon rectifier stack has any crack;

(2) If the high voltage porcelain insulator has any damage and if all parts and fasteners have

any looseness phenomenon;

(3) The iron core shall be grounded reliably and only grounded at one point; for that with a

core-crossing screw stem, measure the insulation resistance between it and core with a 2500V

megger, and the resistance value must be more than 1000M�.

4. Precautions for the active part inspection for transformer:

(1) The lifting of active part shall be conducted in good weather conditions when it is dry

Page 26: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

22

without dust and moisture (the relative humidity shall not be more than 75%) and at a clean position.

Its lifting time shall be as short as possible so as to avoid from becoming damp or being polluted

and thus reducing the dielectricity. The active part inspection cannot be conducted in rainy days.

(2) When the lifted active part is exposed to the air, its continuous time for contacting with the

air outside shall not exceed the following provisions:

In dry air (the relative humidity of air shall not be more than 65%) � 3 hours.

In humid air (the relative humidity of air shall not be more than 75%) � 1 hours.

(3) After the rectifier transformer goes through the active part inspection, the power-on test can

be conducted only after the transformer oil is filled back and generally stands for 24 hours for fear

of high voltage discharge in bubbles.

5. Withstand voltage test for transformer oil

If the condition permits, the breakdown voltage shall be measured for transformer oil. The oil

sample shall be taken from the oil drain valve. At this time, the oil temperature shall not be lower

than +5 . The transformer oil must go through the withstand voltage test, and the average instant

breakdown voltage value of five tests shall be more than 35KV/2.5mm. If the breakdown voltage of oil

is lower than the required value, it can be used only when the causes are found out and it is handled

accordingly. In addition, if it needs to replenish oil, it is preferable to add the oil of same grade as far as

possible. In case the oil grade is different, then it can be mixed for use only after the chemical analysis is

conducted in advance.

6. Withstand voltage test for transformer

The rectifier transformer has already go through the induced voltage withstand test and applied

high voltage test before leaving the factory. If the high voltage test is required on the site, then it is

necessary to short circuit the high voltage set on the silicon rectifier stack, disassemble the high

voltage measuring resistor and current feedback outlet wire, put them into the oil again and stand

for 24 hours. Then the high voltage porcelain insulator shall go through the withstand voltage test to

earth. Otherwise, the applied high voltage test can not be conducted. For the silicon rectifier

transformer below 72KV, its test voltage shall be more than 1.1 times of rated voltage and less than

1.5 times of rated voltage.

Page 27: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

23

Chapter VII

Product Integration and Spare Parts

1. High voltage control cabinet 1 set

2. High voltage silicon rectifier transformer 1 set

3. PT100 temperature sensor for rectifier transformer 1 piece

4. Damping resistor 1 piece

5. Sampling board for transformer 1 piece

7. Operating instructions 1 copy

7. Factory inspection report of product 1 copy

8. Certificate of conformity of product 1 copy

Chapter VIII

Packing, Transportation and Open-package Inspection of Product as well

as Liability and Warranty Period for Equipment Damage

I. The manufacturer must deliver the equipment only after it is well packed according to the

provisions specified by the country. For any equipment damage during the transportation due to

improper packing, the manufacturer shall bear the liability for such damage.

II. After the equipment arrives in the site, the open-package inspection shall be conducted promptly,

and the contents of inspection shall include:

1. Any damage in the appearance and inside component and parts of equipment.

2. Conformity of installation and selection of inside component and parts with the design

requirements.

3. Any looseness or drop-off phenomenon of wire connectors.

4. Conformity of spare components and parts and technical documents with the list provided in

the operating manual.

III. If it is found that the equipment delivered does not conform to the purchase order (shortage in

quantity, incorrect specifications and models), the manufacturer shall quickly replace it

unconditionally.

IV. If the equipment is lost or damaged due to the carelessness of transportation department, the

manufacturer shall first meet the requirements in the production of the user in principle to solve the

Page 28: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

24

problems of missing and damage. After finding out the causes jointly, the responsible party shall

bear the responsibility and pay the amount dues to the manufacturer.

V. After the equipment arrives in the site, for any missing, damage, etc. of equipment purely due to

improper storage and use, all responsibilities shall be borne by the user itself.

VI. The warranty period of equipment shall be 12 months from the commencement date of

installation and commissioning or 18 months from the delivery date of equipment, whichever is

earlier.

Annex: Figures & Tables

Table 1: parameter list of common component and parts for GGAj02-�A/�KV series high voltage

rectifier for electrostatic precipitator

Table 2: parameter list of component and parts for GGAj02-�A/�KV series high voltage rectifier

for electrostatic precipitator

Table 3: capacity list of GGAj02-�A/�KV series high voltage rectifier for electrostatic precipitator

Table 4: cross reference table for type selection of capacity of GGAj02-�A/�KV series high voltage

rectifier for electrostatic precipitator

Figure 1: wiring diagram for control system of GGAj02-�A/�KV series high voltage rectifier for

electrostatic precipitator

Figure 2: schematic diagram for control system of GGAj02-�A/�KV series high voltage rectifier

for electrostatic precipitator (without the communication with a third party)

Figure 3: schematic diagram for control system of GGAj02-�A/�KV series high voltage rectifier

for electrostatic precipitator (with the communication with a third party)

Figure 4: outline and structural diagram for GGAj02-�A/�KV series high voltage control cabinet

Figure 5: outline and structural diagram and parameter list for GGAj02-�A/�KV series high voltage

silicon rectifier transformer

Figure 6: outline diagram for side entry bottom exit high voltage isolation switch cabinet

Figure 7: outline diagram for safety earthing switch cylinder

Page 29: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

25

Table 1: parameter list of common component and parts for GGAj02-�A/�KV series high voltage

rectifier for electrostatic precipitator

No. Position

No. Name Model Remarks

1 HL1 Equipment power

indicator lamp

ND16-22B/4

AC380V Green

2 HL2 Equipment operating

indicator lamp

ND16-22B/4

AC220V Red

3 HA1 Fault alarm buzzer NFM1-22/FS

AC220V Yellow

4 PV1 Primary voltage meter 6L2-450V

5 PV2 Secondary voltage meter 6C2-0.1MA-100KV

6 QF1 Power switch for

operating circuit DZ47-60 C6A/2P

7 QF2 Power switch for inside

illumination of cabinet DZ47-60 C1A/1P

8 M1/M2 Axial flow fan KA-1725HA(1)3 To be supplied for that

above 1.0A

9 T2 Isolation transformer 380/220V-60W

10 KA1 Safety interlock relay HF18FF/024-2Z1D With frame

11 KA2 Startup/shutdown control

relay HF18FF/024-2Z1D With frame

12 KA3 Fault alarm relay HF18FF/024-2Z1D With frame

13 KA4 Remote/local control

relay HF18FF/A220-2Z1D

To be supplied for that with

the communication with a

third party

14 KA5

Relay with reserved

interface for outside

signal

HF18FF/A220-2Z1D To be supplied as per the

user’s demand

15 RV1 Piezoresistor MY31-1000V/5KA

Page 30: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

26

16 RV2

RV3 Piezoresistor MY31-720V/5KA

17 U1 Signal sampling board of

transformer ZCHB01A Self-made

18 U2 Pulse trigger plate HVC-ZC12A Self-made

19 U3

Intelligent controller for

high voltage power

supply

HVC-ZC11 Self-made

20 U4 Remote control

communication board ZCHB02A

To be supplied for that with

the communication with a

third party

21 X3 Secondary outlet terminal IN13SBK-C

22 QS2 Door limit switch YBLX-JW2/11H/W1

23 HR1 Inside illumination lamp

of cabinet

7W energy-saving

lamp

Page 31: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

27

Table 2: parameter list of component and parts for GGAj02-�A/�KV series high voltage rectifier

for electrostatic precipitator

Name &

specification

of

components

and parts

Equipment

model

Primary

contactor

KM1

Common

fuse

HDLRTO

Silicon

controlled

rectifier

V1/V2 KP

series

Resistor

R1

RX20

Capacitor

U1~3

CJ48B-2

-500V

Current

transformer

TA1/TA2

BH-0.66

Alternating

current

ammeter

A1 6L2-A

Direct

current

ammeter

A2 6C2 -

0.1MA

Damping

resistor

R5 ZG12

Current

sampling

resistor

R7

RX20

A KV A A A W/� UF A A MA W/K� W/�

60

66

72

0.1

80 50/5 50

60

66

72 0.2

80

250 20/30

60 75

66

72

200 0.3

80

20/20 0.47 20/20

60

100 100/5 100

66

72

150

0.4

80

500

500/2

20/15

60

125

66

72

150/5 150

0.5

80 200/5 200

20/12

60

200

300 50/20

150/5 150

66

160

72 0.6

80 200

250 500 50/20

1.0

200/5 200

800 1200/1

20/10

Page 32: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

28

60

66

72

0.7

80

250/5 250

30/8.6

60 200/5 200

66

72 0.8

80

1000 30/7.5

60

250 300

250/5 250

66

72 300/5 300 1.0

80

500

400/5 400

30/6

60

66

72

315

300/5 300 1.1

80 400/5 400

30/5.5

60

350

300/5 300

66

72 1.2

80

30/5

60

400

66

72

400

400/5 400

1.4

80 500/5 500

1500

50/4.3

60

66 400/5 400

72 1.5

80

50/4

60

450

66

72 1.6

80

2800/

700�

50/3.75

60

66

72

500

500

800

500/5 500

1.8

80 600/5 600

2000

50/3.4

60 500/5 500

66

72

550

2.0

80

630

600

1000

2.0

600/5 600 2500

3000/

500�

50/3

Page 33: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

29

Table 3: capacity list of GGAj02-�A/�KV series high voltage rectifier for electrostatic precipitator

Equipment

model

Alternating

current

input

voltage

Alternating

current

input

current

Alternating

current

input power

Direct

current

output

voltage

Direct

current

output

current

Direct

current

output

power A KV V A KVA KV A KW

60 23 9 60 6

66 25 10 66 7

72 27 10 72 7

80 30 11 80 8

0.1

150 56 21 150

15

60 45 17 60 12

66 50 19 66 13

72 54 21 72 14

80 60 23 80 16

0.2

150 113 43 150

0.2

30

60 68 26 60 18

66 74 28 66 20

72 81 31 72 22 0.3

80 90 34 80

0.3

24

60 90 34 60 24

66 99 38 66 26

72 108 41 72 29 0.4

80 121 46 80

0.4

32

60 113 43 60 30

66 124 47 66 33

72 135 51 72 36 0.5

80 151 57 80

0.5

40

60 135 51 60 36

66 149 57 66 40

72 163 62 72 43 0.6

80 180 68 80

0.6

48

60 158 60 60 42

66 174 66 66 46

72 190 72 72 50 0.7

80

211 80 80

0.7

56

Page 34: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

30

60 180 68 60 48

66

199 76 66 53

72 217 82 72 58 0.8

80 241 92 80

0.8

64

60 226 86 60 60

66 248 94 66 66

72 271 103 72 72 1.0

80 301 115 80

1.0

80

60 248 94 60 66

66 273 104 66 73

72 298 113 72 79 1.1

80 331 126 80

1.1

88

60 271 103 60 72

66 298 113 66 79

72 325 124 72 86 1.2

80 361 137 80

1.2

96

60 322 122 60 84

66 351 133 66 92

72 378 144 72 101 1.4

80 420 160 80

1.4

112

60 338 128 60 90

66 372 141 66 99

72 406 154 72 108 1.5

80 451 171 80

1.5

120

60 361 137 60 96

66 397 151 66 106

72 433 165 72 115 1.6

80 481 183 80

1.6

128

60 406 154 60 108

66 447 170 66 119

72 487 185 72 130 1.8

80 541 206 80

1.8

144

60 451 171 60 120

66 496 188 66 132

72 541 206 72 144 2.0

80

380/220

602 229 80

2.0

160

Page 35: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

31

Table 4: cross reference table for type selection of capacity of GGAj02-�A/�KV series high voltage

rectifier for electrostatic precipitator

Due to difference in the body structure and operation site of equipment, the secondary current

of equipment will vary from each other. For specific type selection, the type selected by the design

institute shall govern, and this table is only for reference

No. Equipment

specification

Cross section of

electrostatic

precipitator

Area of

electrode

plate

Corona wire

length

Spacing of same

electrodes

1 0.01/100 1.0-2 30-40 60-80 450-550

2 0.02/100 1.5-2.5 60-80 120-160 450-550

3 0.03/100 2-3 80-100 160-200 450-550

4 0.05/100 4-6 120-150 240-300 450-550

5 0.1/100 6-10 250-300 500-600 450-550

6 0.1/72 6-10 250-300 500-600 300-400

7 0.2/72 15-20 500-600 1000-1200 300-400

8 0.3/72 25-30 750-900 1200-2200 300-400

9 0.4/72 30-40 1000-1200 2000-2800 300-400

10 0.5/72 40-50 1250-1500 2500-3000 300-400

11 0.6/72 50-60 1500-1800 3000-3600 300-400

12 0.7/72 55-70 1750-2100 3500-4200 300-400

13 0.8/72 60-80 2000-2500 4000-5000 300-400

14 1.0/72 80-100 2500-2800 5000-5600 300-400

15 1.1/72 90-110 2800-3200 5600-6400 300-400

16 1.2/72 105-120 3000-3600 6000-7200 300-400

17 1.5/72 130-150 3800-4200 7500-8300 300-400

18 1.6/72 140-160 4200-5000 8000-10000 300-400

19 1.8/72 150-180 4500-5500 9200-11000 300-400

20 2.0/72 160-200 5000-6000 10000-12000 300-400

Page 36: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU
Page 37: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU
Page 38: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU
Page 39: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU
Page 40: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU
Page 41: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU
Page 42: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU
Page 43: 2SHUDWLQJ ,QVWUXFWLRQV )RU - fjzchb.comfjzchb.com/images/upfile/GGAJ02E.pdf · 2SHUDWLQJ ,QVWUXFWLRQV )RU **$- 6HULHV +LJK 9ROWDJH 6LOLFRQ 5HFWLILHU )RU (OHFWURVWDWLF 3UHFLSLWDWRU

Scope Of Business ★ GGAJ02 Series Single-Phase High Voltage Rectifier For Electrostatic Precipitator;

★ GGAJ06 Series Three-Phase High Voltage Rectifier For Electrostatic Precipitator;

★ HF Series High Frequency, High Voltage Power Supply For Electrostatic Precipitator;

★ Low Voltage Control System And Complete Project For Electrostatic Precipitator And

Bag Dust Collector, Desulphurization, Denitrification And Pneumatic Ash Handling.

★ Industrial Automatic Control System And Complete Project;

★ Development Of Application Software.

Address: Dongbao Industrial Concentrated Area, Longzhou Industrial Park, Fujian Province

Tel.: +86-597-2337888

Fax: +86-597-2303182

E-Mail: [email protected]

Postal Code: 364000