Q19928 - 2711-NC21 and 2711-NC22 cables for the PanelView
Last Modified: 07/16/2002
Previously Released as #13911
The 2711-NC21 and NC22 cables are 9 pin to 8 pin mini-din cables designed originally to
connect a PV300 Keypad or a xxx5, xxx9 or xxx16 terminal directly to a ML1000, 1200 or
1500 processor.
They only differ by the length: The NC21 is 16.4ft (5 meter) The NC22 is 49 ft (15 meter)
The pinout of this cable is: PV AIC+, ML1000 9 pin 8 pin (Rt. Angle) DCD 1 -------- 5 DCD TXD 2 -------- 4 RXD RXD 3 -------- 7 TXD GND 5 -------- 2 GND 4 ---| 6 ---| RTS 7 -------- 3 RTS ; RTS/CTS are not crossed. They must be crossed when used with a
Belden network. CTS 8 -------- 6 CTS
Problem: The problem is when the NC21/NC22 is connected to an AIC+ and a Belden cable is also
connected. The handshaking pins are required in this setup and the handshaking pins not
crossed. They are required to be crossed for handshaking to occur with the Belden cable.
If Belden is not used, the handshaking pins are not required.
Alternatives: Use a 1761-CBL-PM02 or a 2711-CBL-PM05 with a null modem adapter.
Or, add a 9 to 9 pin adapter to the NC21 cable with pins 7 and 8 crossed. But don't re-
cross pins 2 and 3, they are already crossed.
May 2002: New cables that correct the handshaking pins are available as Ser A Rev B.
Documentation
General Category: s EOIProduct(s): PanelViewCatalog #: 2711ND3
Series / Revision:Subject
(Keyphrases):Summary of
Technote Information:
Page 1 of 2Documentation Technote: 2711-NC21 and 2711-NC22 cables for the PanelView
6/29/2006http://domino.automation.rockwell.com/applications/kb/RAKB.nsf/0/A4350EB6186504DF852...
The new pinout of this cable is: PV AIC+, ML1000 9 pin 8 pin (Rt. Angle) DCD 1 -------- 5 DCD TXD 2 -------- 4 RXD RXD 3 -------- 7 TXD GND 5 -------- 2 GND 4 ---| 6 ---| RTS 7 -------- 6 CTS ; RTS/CTS are now crossed with a Ser A Rev B cable. CTS 8 -------- 3 RTS
Related Links:
DISCLAIMER This knowledge base web site is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this web site is not intended to constitute application, design, software or other professional engineering advice or services. Before making any decision or taking any action, which might affect your equipment, you should consult a qualified professional advisor. ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES. ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.
Copyright © 2006 Rockwell Automation. All rights reserved.
Close Print this Page
Page 2 of 2Documentation Technote: 2711-NC21 and 2711-NC22 cables for the PanelView
6/29/2006http://domino.automation.rockwell.com/applications/kb/RAKB.nsf/0/A4350EB6186504DF852...