2291B1 3500 33 16

download 2291B1 3500 33 16

of 52

Transcript of 2291B1 3500 33 16

  • 8/18/2019 2291B1 3500 33 16

    1/52

     

    Operation and Maintenance Manual

    3500/33 16-Channel Relay Module

    Part Number 162291-01Rev. B (02/08)

  • 8/18/2019 2291B1 3500 33 16

    2/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    Copyright 2002. Bently Nevada LLC.

    All rights reserved. 

    The information contained in this document is subject to change without notice.

    The following are trademarks of General Electric Company in the United States and othercountries:

    Bently Nevada

    The following are trademarks of the legal entities cited:

    Velostat is a trademark of 3M Company.

    Contact Information

    The following contact information is provided for those times when you cannot contactyour local representative:

    Mailing Address 1631 Bently Parkway South

    Minden, Nevada USA 89423

    USATelephone 1.775.782.3611

    1.800.227.5514

    Fax 1.775.215.2873

    Internet www.ge-energy.com/bently 

    ii

    http://www.ge-energy.com/bentlyhttp://www.ge-energy.com/bently

  • 8/18/2019 2291B1 3500 33 16

    3/52

     

    Additional Information

    Notice: 

    This manual does not contain all the information required to operate and maintain

    the product. Refer to the following manuals for other required information.

    3500 Monitoring System Rack Installation and Maintenance Manual (PartNumber 129766-01) 

    • General description of a standard system.

    • Instructions for installing and removing the module from a 3500 rack.

    • Drawings for all cables used in the 3500 Monitoring System.

    3500 Monitoring System Rack Configuration and Utilities Guide (PartNumber 129777-01) 

    • Guidelines for using the 3500 Rack Configuration software for setting theoperating parameters of the module.

    • Guidelines for using the 3500 test utilities to verify that the input and outputterminals on the module are operating properly.

    3500 Monitoring System Computer Hardware and Software Manual (PartNumber 128158-01)

    • Instructions for connecting the rack to 3500 host computer.

    • Procedures for verifying communication.

    • Procedures for installing software.

    • Guidelines for using Data Acquisition / DDE Server and Operator Display Software.

    • Procedures and diagrams for setting up network and remote communications.

    3500 Field Wiring Diagram Package (Part Number 130432-01)

    • Diagrams that show how to hook up a particular transducer.

    • Lists of recommended wiring.

    iii

  • 8/18/2019 2291B1 3500 33 16

    4/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    Product Disposal Statement

    Customers and third parties, who are not member states of the European Union, who arein control of the product at the end of its life or at the end of its use, are solelyresponsible for the proper disposal of the product. No person, firm, corporation,association or agency that is in control of product shall dispose of it in a manner that is

    in violation of any applicable federal, state, local or international law. Bently Nevada LLCis not responsible for the disposal of the product at the end of its life or at the end of itsuse.

    iv

  • 8/18/2019 2291B1 3500 33 16

    5/52

     

    Contents

    1.  Receiving and Handling Instructions ..................................................... 1 1.1

     

    Receiving Inspection........................................................................................................................1 

    1.2 

    Handling and Storing Considerations......................................................................................1 

    2.  General Information.................................................................................. 3 2.1

     

    The 16-Channel Relay Module .................................................................................................... 3 

    2.2 

    Statuses................................................................................................................................................. 7 

    2.2.1 

    Module Statuses ...................................................................................................................... 7 

    2.2.2 

    Channel Status ......................................................................................................................... 8 

    2.3 

    LED Descriptions................................................................................................................................9 

    3.  Configuration Information ..................................................................... 11 3.1

     

    Hardware Considerations ...........................................................................................................11 

    3.2 

    Entering Alarm Drive Logic..........................................................................................................11 

    3.2.1 

    Relay Module Configuration Considerations ............................................................12 

    3.2.2 

    Relay Module Configuration Options............................................................................12 

    3.3 

    Software Switches ..........................................................................................................................14 

    3.3.1 

    Configuration Mode .............................................................................................................15 

    3.3.2 

    Bypass........................................................................................................................................15 

    4.  Output Module Description.................................................................... 17 4.1

     

    16-Channel Relay Output Module............................................................................................17 

    4.2 

    Wiring Euro Style Connectors ....................................................................................................19 

    5.  Maintenance ............................................................................................. 21 5.1

     

    Verifying a 3500 Rack - Relay Module ...................................................................................21 

    5.1.1 

    Choosing a Maintenance Interval..................................................................................21 

    5.1.2 

    Required Test Equipment...................................................................................................22 

    5.1.3 

    Typical Verification test setup .........................................................................................22 

    5.1.4 

    Using the Rack Configuration Software......................................................................23 

    5.1.5 

    Standard Relay Channels ..................................................................................................24 

    5.1.6 

    If a Channel Fails a Verification Test.............................................................................26 

    5.2 

    16-Channel Relay Firmware Upgrade Procedure ............................................................26 

    6.  Troubleshooting ....................................................................................... 28 

    v

  • 8/18/2019 2291B1 3500 33 16

    6/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    6.1  Self-test................................................................................................................................................28 6.2

     

    LED Fault Conditions......................................................................................................................29 

    6.3  System Event List Messages ......................................................................................................30 6.4  Alarm Event List Messages .........................................................................................................41 

    7.  Ordering Information...............................................................................42 

    7.1 

    16-Channel Relay Module ...........................................................................................................42 

    7.2 

    Spares...................................................................................................................................................42 

    8.  Specifications.............................................................................................43 8.1

     

    Relays ...................................................................................................................................................43 

    8.2 

    Environmental Limits.....................................................................................................................44 

    8.3 

    Mechanical.........................................................................................................................................44 

    8.4 

    Electromagnetic Compatibility..................................................................................................44 

    8.5 

    Approvals ............................................................................................................................................45 

    8.6 

    Physical ................................................................................................................................................46 

    8.6.1 

    Main Module............................................................................................................................46 

    8.6.2 

    Output Module........................................................................................................................46 8.7

     

    Rack Space Requirements ..........................................................................................................46 

    vi

  • 8/18/2019 2291B1 3500 33 16

    7/52

    Section 1 - Receiving and Handling Instructions

    1. Receiving and Handling Instructions

    1.1 Receiving Inspection

    Visually inspect the module for obvious shipping damage. If shipping damage isapparent, file a claim with the carrier and submit a copy to Bently Nevada LLC.

    1.2 Handling and Storing Considerations

    Circuit boards contain devices that are susceptible to damage when exposed toelectrostatic charges. Damage caused by obvious mishandling of the board willvoid the warranty. To avoid damage, observe the following precautions in theorder given.

    Application Advisory

    Machinery protection will be lost whenthis module is removed from the rack. 

    • Do not discharge static electricity onto the circuit board. Avoid tools orprocedures that would subject the circuit board to static damage. Somepossible causes include ungrounded soldering irons, nonconductiveplastics, and similar materials.

    • Personnel must be grounded with a suitable grounding strap (such as 3M

    Velostat®

     No. 2060) before handling or maintaining a printed circuit board.• Transport and store circuit boards in electrically conductive bags or foil.

    • Use extra caution during dry weather. Relative humidity less than 30%tends to multiply the accumulation of static charges on any surface.

    • When performed properly, you may install this module into or remove itfrom the rack while power is applied to the rack. Refer to the RackInstallation and Maintenance Manual (part number 129766-01) for theproper procedure.

    1

  • 8/18/2019 2291B1 3500 33 16

    8/52

  • 8/18/2019 2291B1 3500 33 16

    9/52

    Section 2 - General Information

    2. General InformationYou can use the 16-Channel Relay Module for most monitoring applications. Themodule uses a single relay to drive the output for each channel. See Section 2.1

    for additional information on the 16-Channel Relay Module.

    4

    5

    6

    7

    1 2 3

    NE

    NDE

    RELAY MODE

    NDE NE

     

    1. Relay module

    2. I/O module (front view)

    3. I/O module (left side view)

    4. LEDs indicating the module status.

    5. LEDs indicating the status of the Relay Channels.

    6. Terminals for connecting relay contacts to external devices.

    7. Switches that control how the relay contacts work.

    Figure 2-1: Views of 16-Channel Relay Module 

    2.1 The 16-Channel Relay Module

    The 3500/33 16-Channel Relay Module is a full-height module that provides 16

    relay outputs. You can place any number of these relay modules in any of theslots to the right of the Rack Interface Module (RIM).

    You can use AND and OR voting to fully program each relay output. The AlarmDrive Logic for each relay channel can use alarming inputs (Alert, Danger, Not OK,and individual channel parameters) from any monitor channel in the rack. Youprogram this Alarm Drive Logic using the Rack Configuration Software.

    3

  • 8/18/2019 2291B1 3500 33 16

    10/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    The three common configuration types of Alarm Drive Logic are:

    1) Bussed relays.  Bussed relays use an Alarm Drive Logic that ORs theAlerts or Dangers for all channels in the rack to drive a single relay.

    2) Individual relays.  Individual relays use Alarm Drive Logic that ORs theAlerts or Dangers for channel pairs (channel 1 and channel 2 or channel

    3 and channel 4) in a monitor to drive a single relay.

    3) Independent relays.  Independent relays use Alarm Drive Logic thatcause each alarm level (Alert and Danger) from a channel to drive aseparate relay channel.

    The following examples show the drive logic for these three types of logic .

    S = Monitor Slot A1 = Alert/Alarm 1

    C = Channel A2 = Danger/Alarm 2

    Example 1: Bussed Relays (Alert and Danger)

    ##A1 = Any Active Alert ##A2 = Any Active Danger

    ((S02C##A1) OR (S03C##A1) OR ... OR (S15C##A1))  Trip Relay Channel 1

    ((S02C##A2) OR (S03C##A2) OR … OR (S15C##A2))  Trip Relay Channel 2

    Figure 2-2: Bussed Relays Example

    4

  • 8/18/2019 2291B1 3500 33 16

    11/52

    Section 2 - General Information

    Example 2: Individual Relays (Alert and Danger)

    (S02C01A1) OR (S02C02A1)   Trip Relay Channel 1 (Alert Relay)

    (S02C01A2) OR (S02C02A2)   Trip Relay Channel 2 (Danger Relay)

    (S02C03A1) OR (S02C04A1)   Trip Relay Channel 3 (Alert Relay)

    (S02C03A2) OR (S02C04A2)   Trip Relay Channel 4 (Danger Relay)

    Figure 2-3: Individual Relays Example

    5

  • 8/18/2019 2291B1 3500 33 16

    12/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    Example 3: Independent Relays (Alert and Danger)

    (S02C01A1)   Trip Relay Module in slot 2 Channel 1 (Alert Relay)

    (S02C02A1)   Trip Relay Module in slot 2 Channel 2 (Alert Relay)

    (S02C03A1)   Trip Relay Module in slot 2 Channel 3 (Alert Relay)

    (S02C04A1)   Trip Relay Module in slot 2 Channel 4 (Alert Relay)

    (S02C01A2)   Trip Relay Module in slot 2 Channel 5 (Danger Relay)

    (S02C02A2)   Trip Relay Module in slot 2 Channel 6 (Danger Relay)

    (S02C03A2)   Trip Relay Module in slot 2 Channel 7 (Danger Relay)

    (S02C04A2)   Trip Relay Module in slot 2 Channel 8 (Danger Relay)

    Independent relays require one 16-Channel Relay Modules for each monitormodule.

    Figure 2-4: Independent Relays Example

    6

  • 8/18/2019 2291B1 3500 33 16

    13/52

    Section 2 - General Information

    2.2 Statuses

    The 16-Channel Relay Module will return both module and channel statuses. Thissection describes the available statuses and where you can find them.

    2.2.1 Module Statuses

    OK

    This indicates if the 16-Channel Relay Module is functioning correctly. Themodule returns a Not OK status under any of the following conditions:

    • Hardware Failure in the module

    • Node Voltage Failure

    • Configuration Failure

    • Slot ID Failure

    If the Module OK status goes Not OK, then the module will drive the system OKRelay on the Rack Interface I/O Module to a Not OK state.

    Configuration Fault

    This indicates if the 16-Channel Relay Module configuration is invalid.

    Bypass

    This indicates if some condition has caused the system to bypass any channelin the 16-Channel Relay Module. Any of the following conditions can cause

    the system to bypass the Relay Module:• A channel has never been configured

    • The Relay Module is in configuration mode

    • A Fatal error was found during self-test

    • Rack Alarm Inhibit has occurred

    • A channel has an invalid configuration

    • Any active channel is bypassed

    Alarm 1 Active

    This indicates that one or more channels of the 16-Channel Relay Module is inalarm.

    Table 2-1 shows where the you can find the module statuses.

    7

  • 8/18/2019 2291B1 3500 33 16

    14/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    Table 2-1: Location of Module Statuses

    StatusesComm.

    GatewayModule

    RackConfiguration

    Software

    OperatorDisplay

    Software

    3500/94 VGADisplay

    Module OK X X X

    Module Configuration Fault X

    Module Bypass X

    Module Alert/Alarm 1 Active X X X

    2.2.2 Channel Status

    OK

    This indicates that the associated channel of the 16-Channel Relay Modulehas detected no fault. If the Channel OK status goes not OK, then the modulewill drive the system OK Relay on the Rack Interface I/O Module to a Not OKstate.

    Bypass

    This indicates if some condition has caused the system to bypass theassociated 16-Channel Relay Module channel. Any of the following conditionscan cause the system to bypass the channel:

    • The channel has never been configured

    • The Relay Module is in configuration mode

    • A Fatal error was found during self-test

    • Rack Alarm Inhibit has occurred

    • The channel has an invalid configuration

    • The channel is bypassed using a software switch

    Channel Off

    This indicates if the associated 16-Channel Relay Module channel has beenturned off (not Active). You may turn off the Relay channels (inactivated) usingthe Rack Configuration Software.

    Alarm 1 Active

    This indicates if the associated 16-Channel Relay Module channel is in alarm.

    Table 2-2 shows where the you can find the channel statuses.

    8

  • 8/18/2019 2291B1 3500 33 16

    15/52

    Section 2 - General Information

    Table 2-2: Location of Channel Statuses

    StatusesComm.

    GatewayModule

    RackConfiguration

    Software

    OperatorDisplay

    Software

    3500/94 VGADisplay

    Channel OK X X X X

    Channel Bypass X X X X

    Channel Off X X X

    Channel Alert/Alarm 1 Active X X X

    2.3 LED Descriptions

    The LEDs on the front panel of the 16-Channel Relay Module indicate theoperating status of the module as shown in Figure 2-5.  Refer to Section 6.2 for allof the available LED conditions.

    1. OK LED: Indicates that the 16-Channel Relay Module and the 16-Channel Relay Output Module are operatingcorrectly.

    2. TX/RX LED: Flashes at the rate that messages are received.3. Channel Alarm LED: Indicates that an alarm condition has occurred with this relay.

    Figure 2-5: 3500/33 Front Panel LEDs

    9

  • 8/18/2019 2291B1 3500 33 16

    16/52

  • 8/18/2019 2291B1 3500 33 16

    17/52

    Section 3 - Configuration Information

    3. Configuration InformationYou configure 3500 relay modules through the 3500 Rack Configuration Software,by using the Relay Association screen to enter alarm drive logic for each relay

    channel and the Software Switches screen to set software switches. This sectiondefines the options on these configuration screens. The Rack Configuration andUtilities Guide (part number 129777-01) shows how to operate those screens.

    3.1 Hardware Considerations

    The slots in the 3500 rack are numbered from 0 to 15, counting from left to right.The power supplies go into slot 0 and the RIM goes into slot 1. Slots 2 through 15are called “monitoring positions”. You can install the 3500/33 module into any ofthe monitoring positions. However, if you will use the 3500/20 Rack InterfaceModule and Data Manager I/O to interface to DDIX, TDIX or TDXnet, refer to the

    3500/20 manual for slot restrictions that this may place on your configuration.

    3.2 Entering Alarm Drive Logic

    Use the Relay Association screen to define the alarm logic that will determinewhich alarms will cause the channels in the relay to drive the output.

    Figure 3-1:Relay Association Screen for a 16-Channel Relay Module

    11

  • 8/18/2019 2291B1 3500 33 16

    18/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    3.2.1 Relay Module Configuration Considerations

    • Add monitor modules to the rack configuration before configuring the RelayModule.

    • Activate only the Relay Module channels that will be used.

    • Note that only monitor modules may be used in the alarm drive logic.

    • Plan ahead to determine if you will configure any channels as channel pairs(DPDT).

    • Determine whether your application will need True AND or Normal AND votinglogic.

    • Consider using the Copy function if you configure several channels withsimilar logic or conditions.

    • Note that prior to downloading, the configuration software will determine if

    the number of instructions exceeds the limit of your relay module. Thesoftware limits the 16-Channel Relay module to 100 logical operations perchannel for each of the 16 channels.

    • Note that prior to exiting the Relay Association screen, the configurationsoftware will determine if there are errors in any channel alarm drive logic.The cursor will be placed at the location of the syntax error.

    3.2.2 Relay Module Configuration Options

    Available Monitors

    This field shows the monitors in the rack.

    Rack Type

    This specifies the type of RIM installed in the rack (Standard or TMR).

    Config ID

    This is a unique 6-character identifier that the software enters whendownloading a configuration to the 3500 rack.

    Relay Slot

    This indicates the location in the 3500 rack of the relay module you areconfiguring.

    Active

    This check box applies to the selected channel in the Channel Associationgroup. The relay channel drives the output only when this box is enabled (⌧)and the alarm drive logic for the channel is TRUE.

    12

  • 8/18/2019 2291B1 3500 33 16

    19/52

    Section 3 - Configuration Information

    Latching Relays

    When you select this option, the corresponding relay alarm channel will holdthe alarm state until it receives a rack reset or the relay is reconfigured.

    Relay Channel Pair (DPDT)

    Selecting this option will group the current channel with its channel pair, thusallowing both channels to have identical configurations and alarm logic.

    Standard Relay Channel Association

    This is a group for you to select the channel, or channel pair, you wish toconfigure and activate.

    Relay NE/NDE Switch Status

    This indicates the the relay hardware switch settings on the Relay OutputModule. This status is available only after you have uploaded the relay.

    Available Monitor Channels/Alarms

    When you select a monitor, this area shows all the alarms that are availablefor the relay module.

    Alarm Drive Logic

    This is the area in which you build the alarm drive logic using the availablemonitor alarms.

    AND Voting Setup

    This option determines the type of AND voting for a standard rack type.

    Figure 3-2: AND Voting Setup Screen

    13

  • 8/18/2019 2291B1 3500 33 16

    20/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    Normal AND Voting (Default)

    With you select this option, if an alarming parameter is Not OK or bypassed(due to either user selection or monitor failure), then the software will removethe parameter from the relay logic. Please note that the software will notremove a “Not-OK” alarming parameter (a parameter intended to alarm on aNot-OK condition) from the alarm logic equation.

    True AND Voting

    True AND logic causes alarming parameters that are Not OK or bypassed toremain in the relay logic. True AND logic will not drive an alarm if an alarmingparameter being ANDed is

    • Not OK (parameters are not intended to alarm on a Not-OKcondition), or

    • in bypass.

    Application Advisory

    Take care when selecting the AND voting to be used. Youshould consider the configuration settings for the channel youintend to use as an alarm parameter. Not OK Channel Defeat(single channel measurements), Not OK Channel Pair Defeat(paired channel measurements), Timed OK Channel Defeatand Latching vs. Non-Latching Not OK modes all affect the

    circumstances that cause a channel to be "Not OK" orbypassed.

    Note in particular that the following channel types have special scenarios thatyou must consider:

    Thrust Position: Monitor reports an Alarm (not a "Not OK" condition) to the relaymodule for a transducer not OK.

    Overspeed, Zero-Speed, Rotor Speed:

    These channel types have optional "OK Voltage Checks" that willdetermine if the monitor will or will not report a Not OK status tothe relay module due to a transducer voltage error.

    Eccentricity: "Direct Channel Above 600 RPM" affects bypass and Not OKstatus.

    3.3 Software Switches

    Software switches for relay modules let you temporarily bypass or inhibit therelay module and channel functions. Set these switches on the SoftwareSwitches screen under the Utilities Option on the main screen of the Rack

    14

  • 8/18/2019 2291B1 3500 33 16

    21/52

    Section 3 - Configuration Information

    Configuration Software. Switch settings take affect only after you press the Set button.

    3.3.1 Configuration Mode

    This module software switch allows you to configure the 16-Channel RelayModule (see Figure 3-3).

    Module Switch Number Switch Name

    1 Configuration Mode

    Figure 3-3: Module Software Switches Screen

    To configure a relay module, enable (⌧) this switch and set the key switch on thefront of the RIM to the PROGRAM position. When downloading a configurationfrom the Rack Configuration Software, this switch will automatically be enabledand disabled by the Rack Configuration Software. If the connection to the rack islost during the configuration process, use this switch to remove the module fromConfiguration Mode.

    The module switch number is used in the Communication Gateway Module.

    3.3.2 Bypass

    When enabled (⌧), the channel will be turned off and not allow alarming (seeFigure 3-4).

    Channel Switch Number Switch Name

    4 Bypass

    15

  • 8/18/2019 2291B1 3500 33 16

    22/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    Figure 3-4: Channel Software Switches Screen

    The channel switch number is used in the Communication Gateway Module.

    16

  • 8/18/2019 2291B1 3500 33 16

    23/52

    Section 4 - Output Module Description

    4. Output Module Description

    This section describes the output module that is associated with the 16-ChannelRelay Module. This section also describes how to use the connectors on the Relay

    Output Module and describes where to install each Output module.

    4.1 16-Channel Relay Output Module

    The 16-Channel Relay Output Module contains 16 sets of relay contacts (1 set foreach channel). You can set up the module so that each channel (in groups of 4channels) is Normally Energized or Normally De-energized. You must install the16-Channel Relay Output Module behind the 16-Channel Relay Module (in a RackMount or a Panel Mount rack) or above the 16-Channel Relay Module (in aBulkhead rack).

    NE

    NDE

    RELAY MODE

    NDE NE

    3

    4

    1 2

     

    1. I/O module (front view)2. I/O module (left side view)

    3. Terminals for connecting to the single-pole, double-throw (SPDT) relays.

    4. DIP switches for configuring the relays for Normally Energized (NE) or Normally De-Energized (NDE) operation. Thenumbers refer to relay channel groups. For example, CH1-4 corresponds to relay channels 1 through 4.

    Figure 4-1: 16-Channel Relay Output Module 

    17

  • 8/18/2019 2291B1 3500 33 16

    24/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    1

    2

    3

     1. Screwdriver

    2. Module cover

    3. DIP Switch 

    Figure 4-2: Configuring the Normally Energized and Normally De-Energized Relays

    CAUTION

    The output module can carry high voltageswhile installed in the rack with power applied to

    the rack. High voltages can shock or burnservice personnel and damage the output

    module during the relay configuration process.Remove power from the rack and remove theoutput module from rack before attempting to

    configure the relays.

    NOTE

    Relay contacts are marked NC (Normally

    Closed), NO (Normally Open), and ARM(Armature). NC and NO define the stateof the relay contacts with no power

    applied to the relay coil (de-energized,non-alarm state). 

    18

  • 8/18/2019 2291B1 3500 33 16

    25/52

    Section 4 - Output Module Description

    1

    2

    3

     1. No Power/ No Alarm (shelf state)

    2. With Power/ No Alarm

    3. With Power/ In Alarm 

    Figure 4-3: Normally Energized (NE) Relay States

    2

    3

    1

     1. No Power/ No Alarm (shelf state)

    2. With Power/ No Alarm 3. With Power/ In Alarm 

    Figure 4-4: Normally De-Energized (NDE) Relay States

    4.2 Wiring Euro Style Connectors

    To remove a terminal block from its base, loosen the screws attaching theterminal block to the base, grip the block firmly and pull, as shown in Figure 4-5. Do not pull the block out by its wires because this could loosen or damage thewires or connector.

    19

  • 8/18/2019 2291B1 3500 33 16

    26/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    Figure 4-5: Removing Terminal Block From a Typical 3500 Output Module

    DANGER

    High voltage may be present on the relaycontacts or relay wiring. High voltage

    can result in shock, burns, or death. Useproper isolation techniques and removeall power when working with the relays.

    Refer to the 3500 Field Wiring Diagram Package for the recommended wiring.

    Do not remove more than 6 mm (0.25 in) of insulation from the wires.

    Figure 4-6: Connnecting Wire to Relay Terminal Block

    20

  • 8/18/2019 2291B1 3500 33 16

    27/52

    Section 5 - Maintenance

    5. MaintenanceYou cannot repair the boards and components inside of 3500 modules in the field.3500 rack maintenance consists of testing module channels to verify that they

    are operating correctly. You should replace modules that are not operatingcorrectly with a spare.

    When performed properly, you may install the main module into or remove themodoule from the rack while power is applied to the rack. You should install orremove the relay output module only after removing the power to the rack. Referto the Rack Installation and Maintenance Manual (part number 129766-01) for theproper procedure.

    This section shows how to verify the operation of the 3500/33 16-Channel RelayModule.

    5.1 Verifying a 3500 Rack - Relay ModuleThe 3500 Monitoring System is a high precision instrument that requires nocalibration. You must, however, verify the functions of Relay Module channels atregular intervals. At each maintenance interval, we recommend that you use theprocedures in this section to verify the operation of all active channels in theRelay Module.

    Section

    Number

    Topic Page

    Number

    5.1.1 Choosing a Maintenance Interval 21

    5.1.2 Required Test Equipment 22

    5.1.3 Typical Verification Test Setup 22

    5.1.4 Using the Rack Configuration Software 23

    5.1.5 Standard Relay Channels 24

    5.1.1 Choosing a Maintenance Interval

    Use the following approach to choose a maintenance interval:

    • Start with an interval of one year and then shorten the interval if either ofthe following conditions apply:

    - The monitored machine is classified as critical.

    21

  • 8/18/2019 2291B1 3500 33 16

    28/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    - The 3500 rack is operating in a harsh environment, such as inextreme temperature, high humidity, or in a corrosive atmosphere.

    • At each interval, use the results of the previous verifications and ISOProcedure 10012-1 1992(E) to adjust the interval.

    5.1.2 Required Test Equipment

    The test equipment you will need to simulate the inputs for the relay channel willdepend on the type of monitor providing inputs to the Relay Alarm Drive Logic.You can identify this equipment under “Required Test Equipment” in theMaintenance section of the specific monitor manual.

    5.1.3 Typical Verification test setup

    The following figure shows the typical test setup for verifying a Relay Module. Thetest equipment is used to simulate the transducer signal to selected monitors andthe laptop computer is used to observe the output from the rack.

    1. 3500 Rack

    2. Test Equipment

    3. RS-232 communications

    4. Laptop Computer

    Figure 5-1: Typical Test Setup

    You can connect transducers to a 3500 rack in a number of ways. Depending onthe wiring option for the I/O module of your monitor, connect the test equipmentto the Monitor Module and Relay Module using one of the following methods:

    22

  • 8/18/2019 2291B1 3500 33 16

    29/52

    Section 5 - Maintenance

    1. Connect test equipment here.

    2. Inputs

    3. Monitor I/O Module (Internal Termination)

    4. External Termination Block (Euro Style Connectors)

    5. External Termination Block (Terminal Strip Connectors)

    Figure 5-2: Test Setup Wiring Methods 

    1. Outputs

    Figure 5-3: 16-Channel Relay Output Module

    5.1.4 Using the Rack Configuration Software

    The laptop computer that is part of the test setup uses the Rack ConfigurationSoftware to display output from the rack and to reset certain operating

    23

  • 8/18/2019 2291B1 3500 33 16

    30/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    parameters in the rack. To perform the test procedures in this section you mustbe familiar with the following features of the Rack Configuration Software to

    • upload and save configuration files

    • display the Verification screen

    The Rack Configuration and Test Utilities Guide (part number 129777-01) explainshow to perform these operations.

    NOTE

    Save the original rack configurationbefore doing any maintenance or

    troubleshooting procedures.

    The Verification screen displays relay channel output from a 3500 rack as shownin Figure 5-4.  Information such as Alarm Drive Logic, Channel Alarm State andChannel OK State are used to verify relay channels.

    Figure 5-4: 3500 Rack Configuration Software Verification Screen

    5.1.5 Standard Relay Channels

    Verify relay channels by forcing alarms from the monitors that provide inputs forthe Relay Alarm Drive Logic. When the logic is true, the Channel Alarm State willchange to Alarm on the Verification screen and the alarm relay and front panelLED for that channel will change state. Verify only those channels that are activeand configured.

    To verify that a 16-Channel Relay channel is working correctly.

    24

  • 8/18/2019 2291B1 3500 33 16

    31/52

    Section 5 - Maintenance

    1. Run the Rack Configuration Software on the test computer.

    2. Choose Verification from the Utilities menu. A screen prompting for theslot and channel number of the relay to be tested will appear.

    3. Choose the proper Slot number and Channel number and then click on theVerify button. The Verification screen will appear.

    4. Verify that the Channel OK State status on the Relay Verification screenreads OK.

    5. Use the Relay Verification screen to determine what inputs must besimulated.

    6. Simulate the required Alarm Drive Logic inputs to cause the relay tochange states.

    For example, for a 3500 Rack with the following configuration:

    Slot Number Module Type

    1 Rack Interface Module

    2 3500/42 – 4 Channel Monitor

    3 3500/42 – 4 Channel Monitor

    4 3500/42 - 4 Channel Monitor

    5 3500/33 - 16-Channel Relay

    and a relay channel with the following Alarm Drive Logic:

    ( S02C01A1 * S03C01A1 ) + S04C01A2send test signals to the monitors in the rack to cause Slot 2 Channel 1 ANDSlot 3 Channel 1 to be in Alert OR cause Slot 4 Channel 1 to be in Danger.

    7. Verify that the Channel Alarm State status on the Relay Verification screenchanges to Alarm. Verify that the relay contacts change state and thefront panel LED illuminates.

    8. If the Relay channel does not respond correctly, check the inputs to ensurethey meet the Alarm Drive Logic requirements. If the module still does notmeet specifications, go to Section 5.1.6 (If a Channel Fails a Verification

    Test).

    9. Select the next channel to be tested by using the Channel drop down liston the Verification screen. Repeat steps 4 through 8 to test the next relaychannel.

    25

  • 8/18/2019 2291B1 3500 33 16

    32/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    5.1.6 If a Channel Fails a Verification Test

    When handling or replacing circuit boards always be sure to adequately protectagainst damage from Electrostatic Discharge (ESD). Always wear a proper wriststrap and work on a grounded, conductive work surface.

    1. Use the Rack Configuration Software to save the configuration for the

    module.

    2. Replace the module with a spare. Refer to the installation section in the3500 Monitoring System Rack Installation and Maintenance Manual (partnumber 129766-01).

    3. Return the faulty module to Bently Nevada LLC for repair.

    4. Use the Rack Configuration Software to download the configuration forthe spare module.

    5. Verify the operation of the spare.

    5.2 16-Channel Relay Firmware Upgrade Procedure

    Occasionally you may need to upgrade the original firmware that ships with the3500/33 16-Channel Relay Module. The following instructions describe how toupgrade the existing firmware using the 3500 Configuration software. You mustuse the 3500 Rack Configuration Software to reconfigure the module afterupgrading its firmware.

    Application Advisory

    During the following procedure youmust not not interrupt power to the rack

    or remove the monitor that you areupgrading from the rack. Either of thse

    events may cause the monitor tobecome inoperable.

    1. Start the 3500 Configuration software and connect to the rack.

    2. Upload and save the current configuration of the monitor, the upgradeprocess will erase any configuration in the monitor.

    3. Under the Utilities menu option select Upgrade Firmware.

    26

  • 8/18/2019 2291B1 3500 33 16

    33/52

    Section 5 - Maintenance

    4. Select the module you wish to update and click on the OK button.

    5. The software will request you to download the file. Select the file and clickon the Open button.

    6. The software will now download the file.

    7. After the download completes, reload the configuration to the monitor. Ifthe process fails (simultaneous flashing alarm LEDs), depending on thefailure mode, the module may revert to its old code. See Section 6.2, “LEDFault Conditions” for an explanation of the failure mode. Under no

    circumstances should you remove the module until it the downloadprocess finishes.

    27

  • 8/18/2019 2291B1 3500 33 16

    34/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    6. TroubleshootingThis section describes how to use the module self-test, the LEDs, and SystemEvent List to troubleshoot a problem with the 16-Channel Relay Module or the

    Output module.

    6.1 Self-test

    To perform a self-test:

    1. Connect a computer running the Rack Configuration Software to the 3500rack (if needed).

    2. Select Utilities from the main screen of the Rack Configuration Software.

    3. Select System Events/Module Self-test from the Utilities menu.

    4. Press the Module Self-test button on the System Events screen.

    Application Advisory

    Machinery protection will be lost whilethe module performs its self-test.

    5. Select the slot that contains the relay module and press the OK button.The relay module will perform a full self-test and the software will displaythe System Events screen. Note that the list will not contain the results ofthe self-test.

    6. Wait 30 seconds for the module to run a full self-test.

    7. Press the Latest Events button. The software will update the SystemEvents screen to include results of the self-test.

    8. Verify if the relay module passed self-test. If the module failed the self test,

    refer to Section 6.3. 

    28

  • 8/18/2019 2291B1 3500 33 16

    35/52

    Section 6 - Troubleshooting

    6.2 LED Fault Conditions

    The following table shows how to use the LEDs to diagnose and correct problemswith the 16-Channel Relay Module.

    Table 6-1: OK and TX/RX LED Fault Condition Diagnostics

    OK LED TX/RX Condition Solution

    1 Hz 1 Hz Relay Module is not configured. Reconfigure the Relay Module.

    5 HzNot

    applicable

    Relay Module or the Relay OutputModule has detected an internalfault and are not OK.

    Check the System Event List.

    ON FlashingRelay Module and the Relay OutputModule are operating correctly.

    No action is required.

    OFFNot

    applicableRelay Module is not operatingcorrectly.

    Replace the Relay Module.

    Notapplicable

    Notflashing

    Relay Module is not

    communicating correctly or theRelay Module is not associated withany monitors in the rack that arecommunicating.

    Check the System Event List orconfigure the alarm logic of at leastone active relay channel.

    Table 6-2: Alarm LED Fault Condition Diagnostics

    Alarm LED Condition Solution

    ON Channel is in Alarm. No action is required.

    OFF Channel is not in Alarm. No action is required.

    All LEDs Flashing (5flashes in 3 seconds) Failed firmware download dueto a recoverable error. Re-attempt firmware download.

    All LEDs Flashing at (5flashes in 5 seconds)

    Failed firmware download dueto a non-recoverable error.

    Replace the relay module with a spare.Return the relay module to a BentlyNevada service center for repair.

    29

  • 8/18/2019 2291B1 3500 33 16

    36/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    6.3 System Event List Messages

    This section describes the System Event List Messages that are entered by the16-Channel Relay Module. Table 6-3 is an example of a System Event ListMessage.

    Table 6-3: Example of a System Event List Message

    SequenceNumber

    EventInformation

    EventNumber

    ClassEvent Date(DDMMYY)

    Event TimeEvent

    SpecificSlot

    0000000123EEPROM Memory

    Failure13 1 02/01/90 12:24:31:99 5

    Sequence Number: This is the number of the event in the System Event List (forexample 123).

    Event Information: This provides the name of the event (for example EEPROMMemory Failure).

    Event Number: This identifies the specific event that occurred.

    Class: This indicates the severity of the event. The followingclasses are available:

    Table 6-4: System Event List Classes

    Class Value Classification

    0 Severe/fatal event

    1 Potential problem event

    2 Typical logged event

    3 Reserved

    Event Date: This specifies the date that the event occurred.

    Event Time: This specifies the time that the event occurred.

    Event Specific: Provides additional information for the events that use thisfield.

    Slot: This identifies the module with which the event isassociated. If the module is a half-height module in theupper slot or a full-height module, this field will be 0 to 15. Ifthe module is a half-height module in the lower slot thenthis field will be 0L to 15L. For example, this field wouldidentify a half-height module in the lower position of slot 5as 5L.

    30

  • 8/18/2019 2291B1 3500 33 16

    37/52

    Section 6 - Troubleshooting

    The 16-Channel Relay module may place following System Event List Messages,which are listed in numerical order. Events marked with a star (*)will not driverelays on the 16-Channel Relay Output Module. If you are unable to solve anyproblems contact your nearest Bently Nevada LLC office.

    Flash Memory Failure

    Event Number: 11

    Event Classification: Potential Problem

    Action: Replace the Relay Module as soon as possible.

    * Internal Network Failure 

    Event Number: 30

    Event Classification: Severe/Fatal Event

    Action: Replace the Relay Module immediately.

    Resync Internal Network

    Event Number: 31

    Event Classification: Severe/Fatal Event

    Action: Replace the Relay Module immediately.

    Device Not Communicating 

    Event Number: 32

    Event Classification: Potential ProblemAction: Determine whether one of the following components is faulty:

    • the Relay Module

    • the rack backplane

    Device Is Communicating 

    Event Number: 33

    Event Classification: Potential Problem

    Action: Determine whether one of the following components is faulty:

    • the Relay Module

    • the rack backplane

    31

  • 8/18/2019 2291B1 3500 33 16

    38/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    Fail Relay Coil Sense 

    Event Number: 55

    Event Classification: Potential Problem

    Action: Verify that the Relay Output Module is installed. If installed,

    determine whether one of the following components is faulty:• the Relay Module

    • the Relay Output Module

    Pass Relay Coil Sense 

    Event Number: 56

    Event Classification: Potential Problem

    Action: Determine whether one of the following components is faulty:

    • the Relay Module

    • the Relay Output Module

    I/O Module Mismatch

    Event Number: 62

    Event Classification: Potential Problem

    Action: Determine whether one of the following components is faulty:

    • the Relay Module

    • the Relay Output Module

    I/O Module Compatible

    Event Number: 63

    Event Classification: Potential Problem

    Action: Determine whether one of the following components is faulty:

    • the Relay Module

    • the Relay Output Module

    Fail I/O Jumper Check (Fail read I/O module ID) 

    Event Number: 64

    32

  • 8/18/2019 2291B1 3500 33 16

    39/52

    Section 6 - Troubleshooting

    Event Classification: Potential Problem

    Action: Determine whether one of the following components is faulty:

    • the Relay Module

    • the Relay Output Module

    Pass I/O Jumper Check (Pass read I/O module ID) 

    Event Number: 65

    Event Classification: Potential Problem

    Action: Determine whether one of the following components is faulty:

    • the Relay Module

    • the Relay Output Module

    Fail Main Board +5V-A  (Fail Main Board +5V - upper Power Supply)

    Event Number: 100

    Event Classification: Potential Problem

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, Determine whether one ofthe following components is faulty:

    • the Relay Module

    • the Power Supply installed in the upper slot

    Pass Main Board +5V-A  (Pass Main Board +5V - upper Power Supply)

    Event Number: 101

    Event Classification: Potential Problem

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    • the Relay Module

    • the Power Supply installed in the upper slot

    Fail Main Board +5V-B  (Fail Main Board +5V - lower Power Supply)

    Event Number: 102

    33

  • 8/18/2019 2291B1 3500 33 16

    40/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    Event Classification: Potential Problem

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    • the Relay Module

    • the Power Supply installed in the lower slot

    Pass Main Board +5V-B  (Pass Main Board +5V - lower Power Supply)

    Event Number: 103

    Event Classification: Potential Problem

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    • the Relay Module

    • the Power Supply installed in the lower slot

    * Fail Main Board +5V-AB  (Fail Main Board +5V - upper and lower PowerSupplies)

    Event Number: 104

    Event Classification: Severe / Fatal Event

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    • the Relay Module

    • the Power Supply installed in the lower slot

    • the Power Supply installed in the upper slot

    Pass Main Board +5V-AB  (Pass Man Board +5V - upper and lower PowerSupplies)

    Event Number: 105

    Event Classification: Severe / Fatal Event

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    34

  • 8/18/2019 2291B1 3500 33 16

    41/52

    Section 6 - Troubleshooting

    • the Relay Module

    • the Power Supply installed in the lower slot

    • the Power Supply installed in the upper slot

    * Fail Main Board +3.3V  (Fail Main Board +3.3V Supply)

    Event Number: 162

    Event Classification: Severe / Fatal Event

    Action: Verify that noise from the power source is not causing theproblem. If the problem is not caused by noise, determine whetherone of the following components is faulty:

    • the Relay Module

    • the Power Supply installed in the lower slot

    • the Power Supply installed in the upper slot

    Pass Main Board +3.3V  (Pass Man Board +3.3V Supply)

    Event Number: 163

    Event Classification: Severe / Fatal Event

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    • the Relay Module

    • the Power Supply installed in the lower slot

    • the Power Supply installed in the upper slot

    Device Configured

    Event Number: 300

    Event Classification: Typical logged event

    Action: No action required.

    * Configuration Failure

    Event Number: 301

    Event Classification: Severe/Fatal Event

    35

  • 8/18/2019 2291B1 3500 33 16

    42/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    Action: Replace the Relay Module immediately.

    Configuration Failure 

    Event Number: 301

    Event Classification: Potential Problem

    Action: Download a new configuration to the Relay Module. If the problemstill exists, replace the Relay Module as soon as possible.

    * Module Entered Cfig Mode

    Event Number: 305

    Event Classification: Typical logged event

    Action: No action required. 

    Software Switches Reset

    Event Number: 305

    Event Classification: Potential Problem

    Action: Download the software switches to the Relay Module. If thesoftware switches are not correct. replace the Relay Module assoon as possible.

    Fail I/O Board +5V-AB  (Fail OUTPUT Board +14V Supply)

    Event Number: 390

    Event Classification: Potential Problem

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    • the Relay OUTPUT Module

    • the Relay Module

    • the Power Supply installed in the lower slot

    • the Power Supply installed in the upper slot

    Pass I/O Board +5V-AB  (Pass OUTPUT Board +14V Supply)

    Event Number: 391

    Event Classification: Potential Problem

    36

  • 8/18/2019 2291B1 3500 33 16

    43/52

    Section 6 - Troubleshooting

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    • the Relay Output Module

    • the Relay Module

    • the Power Supply installed in the lower slot

    • the Power Supply installed in the upper slot

    Fail I/O Board +14V-AB  (Fail OUTPUT Board +14V Supply)

    Event Number: 396

    Event Classification: Potential Problem

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of the

    following components is faulty:

    • the Relay OUTPUT Module

    • the Relay Module

    • the Power Supply installed in the lower slot

    • the Power Supply installed in the upper slot

    Pass I/O Board +14V-AB  (Pass OUTPUT Board +14V Supply)

    Event Number: 397

    Event Classification: Potential Problem

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    • the Relay Output Module

    • the Relay Module

    • the Power Supply installed in the lower slot

    • the Power Supply installed in the upper slot

    Fail I/O Module DIP Sw  (Fail Output Module DIP switch)

    Event Number: 398

    37

  • 8/18/2019 2291B1 3500 33 16

    44/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    Event Classification: Potential Problem

    Action: Verify that the Relay Output Module is installed. If the Relay OutputModule is installed, replace the Relay Output Module as soon aspossible.

    I/O Module Detect Fault  (Pass Output Module DIP switch – there was a

    detected fault that is no longer present)

    Event Number: 399

    Event Classification: Potential Problem

    Action: Verify that the Relay Output Module is installed. If the Relay OutputModule is installed, replace the Relay Output Module as soon aspossible.

    Pass Module Self-test

    Event Number: 410

    Event Classification: Typical Logged Event

    Action: No action required.

    Enabled Ch Bypass  (Enabled Channel Bypass)

    Event Number: 416

    Event Classification: Typical logged event

    Event Specific: Ch x

    Action: No action required.Disabled Ch Bypass  (Disabled Channel Bypass)

    Event Number: 417

    Event Classification: Typical logged event

    Event Specific: Ch x

    Action: No action required.

    Invalid Alm Drive Logic (Invalid Alarm Drive Logic)

    Event Number: 451

    Event Classification: Severe/Fatal Event

    38

  • 8/18/2019 2291B1 3500 33 16

    45/52

    Section 6 - Troubleshooting

    Action: Download a new configuration to the Relay Module. If the problemstill exists, replace the Relay Module as soon as possible.

    Fail Slot Id Test

    Event Number: 461

    Event Classification: Severe/Fatal EventAction: Verify that the Relay Module is fully inserted in the rack. If the Relay

    Module is installed correctly, determine whether one of thefollowing components is faulty:

    • the Relay Module

    • the rack backplane

    Pass Slot Id Test

    Event Number: 462

    Event Classification: Severe/Fatal Event

    Action: Verify that the Relay Module is fully inserted in the rack. If the RelayModule is installed correctly, determine whether one of thefollowing components is faulty:

    • the Relay Module

    • the rack backplane

    Fail I/O Board +15V-A  (Fail Output Board +15V - upper Power Supply)

    Event Number: 554

    Event Classification: Potential Problem

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    • the Relay Output Module

    • the Relay Module

    the Power Supply installed in the upper slotPass I/O Board +15V-A  (Pass Output Board +15V - upper Power Supply)

    Event Number: 555

    Event Classification: Potential Problem

    39

  • 8/18/2019 2291B1 3500 33 16

    46/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    • the Relay Output Module

    • the Relay Module

    • the Power Supply installed in the upper slot

    Fail I/O Board +15V-B  (Fail Output Board +15V - lower Power Supply)

    Event Number: 556

    Event Classification: Potential Problem

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    • the Relay Output Module

    • the Relay Module

    • the Power Supply installed in the lower slot

    Pass I/O Board +15V-B  (Pass OUTPUT Board +15V - lower Power Supply)

    Event Number: 557

    Event Classification: Potential Problem

    Action: Verify that noise from the power source is not causing the problem.

    If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    • the Relay OUTPUT Module

    • the Relay Module

    • the Power Supply installed in the lower slot

    Fail I/O Board +15V-AB  (Fail OUTPUT Board +15V - upper and lower PowerSupplies)

    Event Number: 558Event Classification: Potential Problem

    40

  • 8/18/2019 2291B1 3500 33 16

    47/52

    Section 6 - Troubleshooting

    Action: Verify that noise from the power source is not causing the problem.If the problem is not caused by noise, determine whether one of thefollowing components is faulty:

    • the Relay OUTPUT Module

    • the Relay Module

    • the Power Supply installed in the lower slot

    • the Power Supply installed in the upper slot

    Pass I/O Board +15V-AB  (Pass Output Board +15V - upper and lower PowerSupplies)

    Event Number: 559

    Event Classification: Potential Problem

    Action: Verify that noise from the power source is not causing the problem.

    If the problem is not caused by noise determine whether one of thefollowing components is faulty:

    • the Relay Output Module

    • the Relay Module

    • the Power Supply installed in the lower slot

    • the Power Supply installed in the upper slot

    6.4 Alarm Event List Messages

    The 16-Channel Relay Module may place the following messages in the AlarmEvent List.

    Table 6-5: Alarm Event List Messages and Their Causes

    Alarm Event List Message When the message will occur

    Entered Not OK Module went Not OK

    Left Not OK Module returned to the OK state

    Relay Activated Condition for driving the relay channel met

    Relay Deactivated Condition for driving the relay channel no longer met

    41

  • 8/18/2019 2291B1 3500 33 16

    48/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    7. Ordering InformationThis section contains the ordering information for the 3500/33 16-Channel RelayModule.

    7.1 16-Channel Relay ModulePart number 3500/33- AXX - BXX

    A: Output Module

    0 1  16-Channel Relay Output Module

    B: Agency Approval Option 

    0 0  None

    0 1  CSA-NRTL/C

    7.2 Spares 

    149968

    16-Channel Relay Control Module

    149992-01

    16-Channel Relay Output Module

    00580453

    Connector Header, 16-position

    162291-01

    3500/33 Relay Module Manual

    04425545

    Grounding Wrist Strap (single use only)

    42

  • 8/18/2019 2291B1 3500 33 16

    49/52

    Section 8 - Specifications

    8. SpecificationsThis section contains the specifications for the 3500/33 16-Channel Relay Module.

    8.1 Relays

    Type

    Single-pole, double-throw (SPDT) relays

    Environmental sealing

    Epoxy-sealed

    Arc suppressors 

    250 Vrms, installed as standard.

    Contact Ratings(resistive load)

    Max switched power

    DC: 160 W

    AC: 1500 VA

    Min switchedcurrent

    100 mA @ 12 Vdc

    Max switchedcurrent

    6 A

    Max switchedvoltage

    DC: 300 VdcAC: 400 Vac

    Contact Life

    100,000 @ 5 A, 24 Vdc or 250 Vac

    43

  • 8/18/2019 2291B1 3500 33 16

    50/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    Operation

    Groups of four channels are switch selectable forNormally De-energized or Normally Energized.

    8.2 Environmental LimitsTemperature

    -30 ºC to 65 ºC (-22 ºF to 150 ºF) operating

    -40 ºC to 85 ºC (-40 ºC to 185 ºC) storage

    Humidity

    95% non-condensing

    8.3 MechanicalImpact

    10 g’s for 11 ms

    Shipping

    Per mil Std 81D – Category G Equipment

    Vibration

    Sinusoidal, 3 g at 5 to 100 Hz

    8.4 Electromagnetic Compatibility

    EN50081-2

    Radiated Emissions

    EN 55011, Class A

    ConductedEmissions

    EN 55011, Class A

    44

  • 8/18/2019 2291B1 3500 33 16

    51/52

    Section 8 - Specifications

    EN50082-2

    ElectrostaticDischarge

    EN 61000-4-2, Criteria B

    RadiatedSusceptibility

    ENV 50140, Criteria A

    ConductedSusceptibility

    ENV 50141, Criteria A

    Electrical FastTransient

    EN 61000-4-4, Criteria B

    Surge Capability

    EN 61000-4-5, Criteria B

    Magnetic Field

    EN 61000-4-8, Criteria A

    Power Supply Dip

    EN 61000-4-11, Criteria B

    Radio Telephone

    ENV 50204, Criteria B

    Low Voltage Directives

    SafetyRequirements

    EN61010-01

    8.5 Approvals

    CSA-NRTL/C

    Class I, Division 2, Groups A through D

    45

  • 8/18/2019 2291B1 3500 33 16

    52/52

    3500/33 16 Channel Relay Module Operation and Maintenance Manual

    LCIE

    Zone 2

    CE Mark

    8.6 Physical

    8.6.1 Main Module

    Dimensions (Height xWidth x Depth)

    241 mm x 24.4 mm x 242 mm

    (9.50 in x 0.96 in x 9.52 in)

    Weight

    0.7 kg (1.6 lbs)

    8.6.2 Output Module

    Dimensions (Height xWidth x Depth)

    241 mm x 24.4 mm x 99.1 mm.

    (9.50 in x 0.96 in x 3.90 in)

    Weight

    0.4 kg (1.0 lbs)

    8.7 Rack Space Requirements

    Main Module

    1 full-height front slot

    Output Module

    1 full-height rear slot