2012 Virginia Rehabilitation Code Overview · 2012 Virginia Rehabilitation Code Overview Learning...
Transcript of 2012 Virginia Rehabilitation Code Overview · 2012 Virginia Rehabilitation Code Overview Learning...
1
2012 Virginia
Rehabilitation Code
Overview
Learning Objectives
• Why do we have a VRC?
• When and how to apply the VRC
• Different compliance methods
• Prescriptive
• Work area
• Performance
• How to classify the Work
Learning Objectives
• Different methods for Alterations
• Level 1
• Level 2
• Level 3
• Change of Occupancy
• Additions
• And the rest . . .
2
FOCUS EYE!
• VCC/IBC vs. VRC/IEBC
• Percentages (50% of floor or building)
• Work areas
• Work area to floors below
• Work area and/or corridors and/or exits and/or stairways
• Entire floors / stories
• Entire floors / stories to floors below
• Entire floors / stories + corridors + exits + stairways
• Entire building
• Available to the site
• Available to the building or floor
Why a VRC? - Housing
Why a VRC? - Commercial / Urban
3
“Incentivize –
don’t penalize”
“It is as safe or safer today
than it was yesterday”
Why the VRC?
4
Change of Occupancy
VCC 103.3
Greater degree
Accessibility
Structural strength
Fire protection
Means of egress
Ventilation
Sanitation
Change of Occupancy
Greater degree
To Group I-2 or I-3
Apply for new CO
Cannot comply w/IBC, AHJ shall consider
modifications
Comply with VRC 1012.8
(accessibility)
Other than Group I-2 or I-3
Comply with VRC
Change of Occupancy
VRC 103.2
Other than Group I-2 or I-3
Apply for new CO
Cannot comply w/VRC,
AHJ shall consider modifications
5
Change of Occupancy
Compliance Methods
Prescriptive
VRC Section 407
Work Area
VRC Chapter 10
Performance
VRC Sections 1401.2.1 or
1401.2.2
Additions
VCC 103.4
VCC / IBC
IBC Chapters 5 and 9
Cannot lower current level of
safety
VRC / IEBC
VRC 102.2
Additions
Compliance Methods
Prescriptive
VRC Section 402
Work Area
VRC Chapter 11
Performance
VRC Section 1401.2.3
6
When to apply the VRC
• VCC 103.5 Reconstruction, alteration or repair in Group R-5 occupancies
• Exception 3 – Compliance with VRC shall be acceptable alternative
When to apply the VRC
• VCC 103.6 Reconstruction, alteration, and repair in other [than Group R-5] occupancies
• . . . shall comply with the VRC
When to apply the VRC
• VCC 103.7 Retrofit requirements
• . . . shall enforce the provisions of Section 1701 of the VRC
7
Basically a duplication of
2012 IBC
Section 3412 –
Compliance alternatives
How to apply the VRC
Prescriptive
Compliance
Method
Work Area
Compliance
Method
Performance
Compliance
Method
Chapter 4 Chapters 5-13 Chapter 14
Basically a duplication of
2012 IBC Sections
3401-3411
New concept
iCodes
VCC Chapter 1
VRC Chapters 1-3
How to apply the VRC
• Chapter 1 – Administration – Virginia amendment
• Chapter 2 – Definitions – with Virginia amendments
• Chapter 3 – Compliance Methods
• Chapter 4 – Prescriptive Compliance Method
• Chapter 5 – Classification of Work
• Chapter 6 – Repairs
• Chapter 7 – Alterations – Level 1
• Chapter 8 – Alterations – Level 2 – with Virginia amendments
• Chapter 9 – Alterations – Level 3
• Chapter 10 – Change of Occupancy
• Chapter 11 – Additions
• Chapter 12 – Historic Buildings – with Virginia amendments
• Chapter 13 – Relocated or Moved Buildings
• Chapter 14 – Performance Compliance Method – with Virginia amendments
• Chapter 15 – Construction Safeguards
• Chapter 16 – Referenced Standards – with Virginia amendments
• Chapter 17 – Retrofit Requirements – Virginia amendment
How to apply the VRC • VRC has very few changes to the 2012 IEBC
(other than Chapters 1 and 17)
Definitions Level 2 Historic
Performance
8
How to apply the VRC
Is this alteration more than 50% of the floor/story?
Is this a “work area”?
Does the means of egress section
apply?
Is this a Level 1, 2, or 3 alteration?
Is this a repair or alteration?
What are the limits of the
“work area”?
Do supplemental requirements
apply?
Does the VRC or VCC apply here?
Is this an existing building?
Is this a change of occupancy?
What compliance method is being
proposed?
Is this an existing unsafe
condition?
Is this more than 50% of the building?
Is water available to the site / building /
floor?
“The single biggest problem
in communication . . .
. . . is the illusion that it has taken place”
- George Bernard Shaw
How to apply the VRC
• VRC supersedes “other” iCodes
• Regardless of stringency or specificity
• You only need to comply with the iCodes when the VRC sends you there
9
ADDITION
• Note: Definition is different between
• IBC
• VRC
ADDITION
10
• Any construction or renovation to an existing structure other than a repair or addition.
• Alterations are classified as Level 1, Level 2, and Level 3 (not included in IBC definition)
ALTERATION
“as described” Level 1 alterations
“as described” Level 2 alterations
11
“as described” Level 3 alterations
Work Area Method – Alterations
CHANGE OF OCCUPANCY
• Note: Definition is different between
• VCC (Virginia amendment)
• VRC
• SFPC (does not include level of activity)
12
• Note: Definition is different between
• IBC
• VRC
REPAIRS
Basically a duplication of
2012 IBC
Section 3412 –
Compliance alternatives
Compliance Methods
Prescriptive
Compliance
Method
Work Area
Compliance
Method
Performance
Compliance
Method
Chapter 4 Chapters 5-13 Chapter 14
Basically a duplication of
2012 IBC Sections
3401-3411
New concept
iCodes
VCC Chapter 1
VRC Chapters 1-3
13
Compliance Methods – there is a 4th!
VRC 301.1
Subject to the approval of . . .
Prescriptive Compliance Method
• Intended to be used in conjunction with the maintenance and prevention codes utilizing mostly provisions from all of the referenced iCodes
• If you are used to the IBC and want to keep it that way, this is probably the method for you
14
Prescriptive Compliance Method
• Basically duplicates the provisions from 2012 IBC Sections 3401-3411
• Additions (deleted by 2009 VCC and addressed in VCC Chapter 1)
• Alterations (deleted by 2009 VCC and addressed in VCC Chapter 1)
• Repairs (deleted by 2009 VCC and addressed in VCC Chapter 1)
• Fire escapes (deleted by 2009 VCC and addressed in VCC Chapter 1)
• Glass replacement
• Change of Occupancy (deleted by 2009 VCC and addressed in VCC Ch. 1)
• Historic Buildings
• Moved structures (deleted by 2009 VCC and addressed in VCC Ch. 1)
• Accessibility for Existing Buildings
Prescriptive Compliance Method
• Basically duplicates the provisions from 2012 IBC Sections 3401-3411
• Additions
• Alterations
• Repairs
• Fire escapes
• Glass replacement
• Change of Occupancy
• Historic Buildings
• Moved structures
• Accessibility for Existing Buildings
Prescriptive Compliance Method
• VRC Section 402 – Additions
• Comply with the IBC
• Alterations to the existing building together with the addition shall not be less conforming to the IBC than it was prior to the addition
• Together, they must comply with the height and area provisions of Chapter 5 of the IBC
• Gravity loads greater than 5% must comply with IBC
• Lateral loads greater than 10% must comply with IBC
• Smoke alarms shall be provided in existing buildings of Group R or I-1 occupancy when an addition is made to such buildings
15
Prescriptive Compliance Method
• VRC Section 403 – Alterations
• Comply with the IBC – except • Existing materials can remain
• New/replacement materials
• Like materials are permitted for repairs and alterations
• Otherwise, comply with the IBC
• Gravity loads greater than 5% must comply with IBC
• Lateral loads must comply with IBC
• Smoke alarms shall be provided in existing sleeping/dwelling units in Group R or I-1 occupancies when an addition is made to such buildings
Prescriptive Compliance Method
• VRC Section 404 – Repairs
• New/replacement materials • Like materials are permitted for repairs and alterations
• Routine maintenance, ordinary repairs exempt from permit, and wear due to normal use are outside of this code
• Substantial structural damage
• Less than substantial structural damage
Prescriptive Compliance Method
• VRC Section 405 – Fire escapes
• Existing can remain
• Permitted only where exterior stairways cannot be used due to lot lines
• Not allowed by IBC
16
Prescriptive Compliance Method
• VRC Section 407 – Change of occupancy
• Comply with the IBC for such change
• Such change shall be allowed without conforming to all of the requirements of this code provided the new or proposed use is less hazardous, based on life and fire risk, than the existing use
Prescriptive Compliance Method
• VRC Section 408 – Historic buildings
• The provisions of this code shall not be mandatory where such buildings do not constitute a distinct life safety hazard
Prescriptive Compliance Method
• VRC Section 410 – Accessibility
• Maintain accessibility during construction
• Cannot require greater degree than the IBC would require
• Cannot lower existing level of accessibility
• Complete change of occupancy • Comply with partial change and provide those 6 elements
• Partial change of occupancy • Comply with VRC 410.6 (Alterations), VRC 410.7 (Primary function), and
VRC 410.8 (specific alterations to elements for less than full compliance)
• Historic buildings • Allows for alternatives regarding site arrival, multilevel buildings,
entrances, and toilet facilities
17
Accessibility
Facility that is altered
VRC Sections 410.8.1 – 410.8.14
IBC Chapter 11
ICC A117.1
Do exceptions
apply? No
Technically infeasible?
Yes
Maximum extent
possible
Accessibility
• Conditions under which less than full compliance is required
• Entrances
• Elevators
• Platform lifts
• Ramps
• Dining areas
• Performance areas
• Jury boxes and witness stands
• Accessible units
• Type A units
• Toilet rooms
• Dressing, fitting and locker rooms
• Fuel dispensers
• Thresholds
• Extent of application
Primary function
When an alteration
affects the accessibility
to or contains
an area of primary function
the route to the primary
function shall be accessible
toilet facilities
drinking fountains
or
18
VRC 410.7 (and VRC 705.2), Exception 1: The costs of providing the accessible route
are not required to exceed 20% of the costs of the alterations
affecting the area of primary function.
20% Rule?
• Replacing existing HVAC ductwork and equipment throughout entire building
• Cost: $3,000,000
20% Rule?
• Renovating an auditorium to provide additional wheelchair seating (integration and dispersion), companion seats, designated aisle seats, and access to the stage (ramps and platform lift)
• Cost: $10,000,000
• Elsewhere in the building, there are no accessible routes to the classrooms and toilets
19
20% Rule
• Replacing existing football field press box , new sod at football field, and new press box at baseball fields
• Cost: $10,000,000
Accessibility in the 2012 VRC Scope of work
Prescriptive Compliance Method
Work Area Compliance Method
Performance Compliance Method
Repairs NA
605.1 (maintains the level provided)
NA
Alterations 410.6 705.1 1401.2.5 / 410.6
Alterations affecting accessibility to or contains an area of Primary Function
410.7 705.2 1401.2.5 / 410.7
Other alterations 410.8.1 – 410.8.14
705.1.1 – 705.1.14 (Level 1) / 806 (Level 2) / 906 (Level 3)
1401.2.5 / 410.8.1 – 410.8.14
Partial change of occupancy 410.4.1 1012.8.1 1401.2.5 / 410.4.1
Complete change of occupancy 410.4.2 1012.8.2 1401.2.5 / 410.4.2
Addition 410.5
1105.1 / 705 / 806 / 906
Driven by classification of the work
Historic building - alterations 410.9
1204.1 / 705 / 806 / 906
1401.2.5 / 410.9
Historic building – alterations: alternative requirements
410.9.1 – 410.9.4 1204.1.1 – 1204.9.4 1401.2.5 /
410.9.1 – 410.9.4
Historic building – change of occupancy
410.9 1205.15 1401.2.5 / 410.9
Historic building – change of occupancy: alternative requirements
410.9.1 – 410.9.4 1204.1.1 – 1204.9.4 1401.2.5 /
410.9.1 – 410.9.4
Moved building NA NA NA
Classification of Work
• Do not assume that because this chapter is called “Classification of Work,” that everything associated with this chapter must be a “work area” (italicized meaning a defined word)
• It does not say, “Classification of Work Areas”
20
Classification of Work
• Repairs (VRC Chapter 6)
• Alterations
• Level 1 (VRC Chapter 7)
• Level 2 (VRC Chapter 8 . . . and 7) • 1st time work area is introduced
• Might include work area(s) – otherwise, they would just be Level 2 alterations
• Level 3 (VRC Chapter 9 . . . and 8 . . . and 7) • Must include work area(s)
Classification of Work
• Change of Occupancy (VRC Chapter 10)
• Does not necessarily mean work area(s)
• Alteration-driven and change of occupancy-driven requirements
• Additions (VRC Chapter 11)
• Except for the affects on the existing building, must comply with the IBC
• Historic Buildings (VRC Chapter 12)
• Moved Buildings (VRC Chapter 13)
Repairs Level 1
Level 2
Level 3
Change of
occupancy
Additions New construction
(IBC)
Work Area Coompliance Method – Proportional approach
Work Area Method - VRC
Alterations
21
WORK AREA COMPLIANCE
METHOD
(next 9 chapters)
Repairs
• Confirm when you can use “like” materials versus IBC-compliant materials
• Glazing: new
• Electrical: like
• Mechanical: like • If it doesn’t make the system less conforming
• Plumbing: new
Fire Protection (maintain existing level of protection)
22
Means of egress (maintain existing level of protection)
Accessibility (maintain existing level of accessibility)
Structural
• Gets heavily into structural repairs
• Basically must comply with the IBC
• Structural and non-structural damage • Less than substantial
• Substantial
23
“as described” Level 1 alterations
Chapter 7 breakdown
• General
• Building elements and materials
• Fire protection
• Means of egress
• Accessibility
• Structural
• Energy conservation
Level 1 applies to ALL levels
24
Interior finishes
Materials and methods per the relevant iCode
Materials and methods per the relevant iCode
material standards
detail of installation & connections joints
penetrations continuity
25
Fire Protection (maintain existing level of protection)
What is fire protection?
Means of egress (maintain existing level of protection)
26
Accessibility (scoping w/ exceptions;
and addresses primary function)
Accessibility
Facility that is altered
VRC Sections 705.1.1 – 705.1.14
IBC Chapter 11
ICC A117.1
Do exceptions
apply? No
Technically infeasible?
Yes
Maximum extent
possible
Accessibility in the 2012 VRC Scope of work
Prescriptive Compliance Method
Work Area Compliance Method
Performance Compliance Method
Repairs NA
605.1 (maintains the level provided)
NA
Alterations 410.6 705.1 1401.2.5 / 410.6
Alterations affecting accessibility to or contains an area of Primary Function
410.7 705.2 1401.2.5 / 410.7
Other alterations 410.8.1 – 410.8.14
705.1.1 – 705.1.14 (Level 1) / 806 (Level 2) / 906 (Level 3)
1401.2.5 / 410.8.1 – 410.8.14
Partial change of occupancy 410.4.1 1012.8.1 1401.2.5 / 410.4.1
Complete change of occupancy 410.4.2 1012.8.2 1401.2.5 / 410.4.2
Addition 410.5
1105.1 / 705 / 806 / 906
Driven by classification of the work
Historic building - alterations 410.9
1204.1 / 705 / 806 / 906
1401.2.5 / 410.9
Historic building – alterations: alternative requirements
410.9.1 – 410.9.4 1204.1.1 – 1204.9.4 1401.2.5 /
410.9.1 – 410.9.4
Historic building – change of occupancy
410.9 1205.15 1401.2.5 / 410.9
Historic building – change of occupancy: alternative requirements
410.9.1 – 410.9.4 1204.1.1 – 1204.9.4 1401.2.5 /
410.9.1 – 410.9.4
Moved building NA NA NA
27
Structural (support of new equipment and materials)
Re-roofing and bracing
Energy conservation
28
Level 1 Alterations
Component VRC IBC
Interior finishes IBC IBC
Materials and methods IBC IBC
Fire protection Maintain existing Rated
Means of egress Maintain existing Full compliance
Structural IBC w/exceptions IBC
Energy conservation Only new components Full compliance w/IECC
Accessibility Limited / exceptions Entire facility / full
Chapter 8 breakdown
• General
• Special use and occupancy
• Building elements and materials
• Fire protection
• Means of egress
• Accessibility
• Structural
• Electrical
• Mechanical
• Plumbing
• Energy conservation
“as described” Level 2 alterations
29
Level 2 Alterations
• Work areas up to and including 50% of the aggregate area of the building
• Work areas over 50% would be considered a Level 3 alteration
≤50
>50
Level 2 Alterations
• Supplemental requirements apply when the work area exceeds 50% of the floor area on any floor
• Shaft enclosures
• Floor opening enclosures
• Stairways
• Interior finishes
• Sprinkler system
• Fire alarm system
• Door swings, door closing, panic hardware
• Corridor openings
• Means of egress lighting
• Exit signs
It becomes very critical to determine what
is and what
is not a work area
30
RECONFIGURED SPACE
• The floor area of a building where walls are proposed to be added, relocated, or removed.
RECONFIGURED SPACE
• The floor area of a building where walls are proposed to be added, relocated, or removed.
31
RECONFIGURED SPACE
• The floor area of a building where walls are proposed to be added, relocated, or removed.
RECONFIGURED SPACE
• The floor area of a building where walls are proposed to be added, relocated, or removed.
RECONFIGURED SPACE
• The floor area of a building where walls are proposed to be added, relocated, or removed.
Before After
32
Scope – Level 2 alterations
• VRC 801.1 Exception
• Buildings in which the reconfiguration is exclusively the result of compliance with the accessibility requirements of Section 705.2 shall be permitted to comply with Chapter 7
Chapter 7 (Level 1) also applies
Materials and methods per the relevant iCode
(w/ exceptions)
33
Scoping Requirements VRC Section 803 Building Elements & Materials
Limited to work areas in which Level 2 alterations are being performed and beyond where specified
34
Scoping for VRC Section 803
• Vertical openings
• In work areas only, or where specified
• Smoke barriers
• In Group I-2 only
• Interior finish
• In exits and corridors in any work area
• Guards
• In work areas only
Existing vertical openings
Interior existing vertical openings connecting 2 or more floors
shall be enclosed with not less than 1 hour rated construction
Exceptions
There are 14 exceptions
35
Scoping Requirements VRC Section 804 Fire Protection
Limited to work areas in which Level 2 alterations are being performed and beyond where specified
36
Automatic sprinkler systems
Grouped into four segments: High-rises
Bunch of Groups Windowless stories
Other buildings and areas
Bunch of Groups
Fire alarm and detection
• Provide in works areas of Groups E, I-1, I-2, I-3, R-2, and R-4; and in all R-1 occupancies as required by the IFC
37
Level 2 Alterations: Means of egress
How many conditions (prior to the first comma)
must be met before this provision applies?
Level 2 Alterations: Means of egress
2 3
4 5
1
otherwise . . .
38
Means of egress (maintain existing level of protection)
Level 2 Alterations: Means of egress – Virginia amendment
STOP HERE . . . unless you have non-conforming existing means of egress
Minimum number of exits
39
Exceptions
VRC 805.3.1.1 (one exit) is essentially 10 exceptions to VRC 805.3.1
Fire escapes
Egress doorways
• Occupant load and travel distance
• Work area, occupant load greater than 50, travel distance greater than 75 feet – with exceptions
• Door swing
• Work area, serving occupant load greater than 50
• Supplemental requirements – with exception
• Door closing
• Work area, opening onto exit passageway at grade, exit stair – with exceptions
40
Egress doorways
• Panic hardware
• Work area, egress path from work area to exit discharge, in buildings w/ Group A, w/ occupant load greater than 100, doors w/ latching devices
• Supplemental requirements – with exception
Openings in corridors
• Openings in corridor walls
• Work area with exception
• Corridor doors with exceptions
• Transoms
• Other openings w/ supplemental requirements and exceptions
Egress elements
• Dead-end corridors
• Work area with exceptions
• Means-of-egress lighting
• Work areas, supplemental requirements with exception
• Exit signs
• Work areas, supplemental requirements with exception
41
Egress elements
• Handrails
• Work area floor to and including the level of exit discharge
• Guards
• Work area floor to and including the level of exit discharge, but
• Confined to the egress path of any work area
Accessibility
• In addition to compliance with VRC Section 705 . . .
• Adding a stair and/or escalator
• IBC Sections 1104.4 and 1104.5
• Accessible (Type A and B) dwelling units and sleeping units
• IBC Section 1107 and IBC Chapter 9 (visible alarms)
Structural Structural alterations w/ Level 2 alterations
New structure
Existing structure -
gravity
Existing structure -
lateral
IBC Shall not reduce or prove can carry per
IBC
IBC
Do exceptions
apply?
VRC Section 706
Voluntary lateral
Not required to meet
IBC
Engineering analysis
42
Electrical
Electrical alterations w/in work areas only
New installations
Existing installations
Certain Residential
occupancies
VRC 702.4
Limited Groups
VRC 808.3.1-.7
VRC 702.4
Mechanical
Mechanical alterations
Reconfigured or converted spaces
Mechanically ventilated
spaces
New stuff that creates
bad stuff
IMC (work areas)
Altered, reconfigured, or extended
Local exhaust
5 CFM outdoor and 15 CFM ventilation;
or ASHRAE 62
VRC 809.2
(existing)
Minimum plumbing fixtures
43
Level 2 Alterations: Plumbing
• Existing occupant load (on that floor) = 100
• Increased occupant load by 20% = 20 occupants added
• Do I need to do anything?
• Increased occupant load by 24% = 24 occupants added
• Do I need to do anything?
Energy conservation
Level 2 Alterations
Component VRC IBC
Building elements and materials
Work area(s) only Entire building
Vertical openings 1-hour w/14 exceptions
1-, 2-, or 3-hour
44
Level 2 Alterations
Component VRC IBC
Interior finishes IBC w/exception (treated w/ coating)
Full compliance
Reduced corridor ratings
Sprinkler on floor and stairwell only
Entire building
Sprinkler system High-rise (work areas with corridors shared
by more than one tenant or serving more
than 30 occupants)
Entire building
Level 2 Alterations
Component VRC IBC
Sprinkler system Other (work area(s) with corridors shared
by more than one tenant or serving more
than 30 occupants – but only if required by IBC and work area exceeds 50% of floor area (fire pump exception – to
the floor)
Entire building (depending
on use group)
Standpipes Work area(s) with corridors shared by
more than one tenant - 50 feet above fire
department access (fire pump exception)
Entire building (30 feet above fire
department access)
Level 2 Alterations
Component VRC IBC
Fire alarm Work area(s) only (does not apply to
Groups A, B, F, H, M)
Entire building (all those Groups)
Means of egress Work area(s) with corridors shared by
more than one tenant within the work area
(otherwise, just maintain existing)
Entire building
45
Level 2 Alterations
Component VRC IBC
Single-exit 10 “exceptions” Very limited
Fire escapes Allowed Not allowed (except for helipads)
Doors in rated corridor Solid core doors (w/five exceptions
to being rated)
Rated doors
Dead-end corridors 35 feet (or 50 or 70 feet depending on Group
20 feet (or 50 depending on Group)
Handrails Allowed on one side Both sides
Accessibility Where dwelling or sleeping units are added, only those
added require visible alarms
All dwelling or sleeping units
Level 2 Alterations
Component VRC IBC
Accessibility Where more than 20 Type A dwelling or sleeping units are added, only those
added require visible alarms
All dwelling or sleeping units
Accessibility Where more than 4 Type B dwelling or sleeping units are added, only those
added require visible alarms
All dwelling or sleeping units
Structural loads No more than 5% Full compliance
Electrical Work area(s) only Entire building
Level 2 Alterations
Component VRC IBC
Mechanical Ventilation in work area(s) only
Heating and ventilation throughout entire
building
Energy conservation Only new components IECC
Plumbing Occupant load of each story increased
by more than 20%
IPC
46
Chapter 9 breakdown
• General
• Special use and occupancy
• Building elements and materials
• Fire protection
• Means of egress
• Accessibility
• Structural
• Energy conservation
“as described” Level 3 alterations
Level 3 Alterations (must comply with Chapters 7 & 8)
47
VRC Sections 803 (building elements and materials), 804 (fire protection), and 805 (means of egress)
. . . apply in work areas whether or not they include exits and corridors shared by more than one tenant and regardless of occupant load
Level 3 alterations
• VRC 901.2 Exception
• If the alterations affecting exits or shared egress access is exclusively the result of VRC Section 705.2 (primary function), then VRC Chapter 9 does not apply
Existing Stairways
Existing stairways
VRC Section 803.2.1
Highest work area floor to, and
including, level of exit discharge and all
floors below
Part of means of egress
Enclosed
Determine if
exceptions apply
VRC Section
803
VRC Section
702
Not less than 1-hour w/ opening
protectives
48
Work area
Stairway enclosure
(VRC 803.2.1 has 14 exceptions)
Interior finish
Interior finish
VRC Section 803.4
Between highest
work area floor to
floor of exit discharge
In exits
Serving the work
area
VRC Sections 702.1 – 702.3
Fire protection
Automatic sprinkler system
High-rise buildings
Rubbish and linen
chutes
Work areas only
VRC Section 804.2
49
Fire protection
Fire alarm and detection systems
Manual fire alarm systems
Automatic fire
detection
Work areas only
Where required by
IBC 907
Means of egress
VRC Section 905.1
VRC Section
805
Means-of-egress lighting
Exit signs
Work areas only
Highest work area
floor to floor of
exit discharge
Accessibility
VRC Section 906.1
VRC Sections 806 and 705
Type B units
IBC Section 1107 and
IBC Chapter 9
4 or more in various
Groups
50
Structural
Structural alterations
New structure
Existing structure -
gravity
Existing structure -
lateral
VRC Section 807.2
IBC and VRC Section
301.1.4.2
VRC Section 807.4
VRC Section 907.4
Do exceptions
apply?
No
VRC Section 807.5
VRC Section 301.1.4.2
VRC Section 301.1.4.2
Substantial alterations
Limited alterations
Wall anchors
Bracing Evaluation & analysis
VRC Section 706
Energy conservation
Level 3 Alterations
Component VRC IBC
Stairways From highest work area floor to level of exit
discharge
Entire height
51
Level 3 Alterations
Component VRC IBC
Interior finishes In exits serving work area(s) between highest work area floor to level
of exit discharge
Entire height
Attached dwelling separation
Not continuous: Materials consistent
with existing wall
Compliant materials
Sprinkler system High-rise (work areas with sufficient water
supply to the site)
Entire building
Manual fire alarm (pull station)
Work area(s) only Throughout entire building
Level 3 Alterations
Component VRC IBC
Means of egress VCC amendment (compliance with code
under which it was constructed)
Entire building
Energy conservation Only new components Full compliance w/IECC
Sections 1007 through 1011
Chapters 9, 8, 7
Section 1012
Change of Occupancy
Change in occupancy (no alterations or
repairs)
Repair or alteration
Alteration-driven
Change of occupancy-driven
No change of occupancy classification
Change of occupancy classification
Chapters 9, 8, 7, 6
The requirements of this section overlay those
of Chapters 7-9
Work area requirements apply only if
you have a work area
Generally must comply with
IBC, IMC, IPC, and
NFPA 70/NEC
Work area requirements apply only if
you have a work area
and
52
Portion without separation
Section 1012 Change of Occupancy Classification – Alteration-driven
Change of Occupancy Classification
Throughout building
Only that portion
Chapter 9 (8 and 7)
Portion with separation
Based on most restrictive occupancy classification
from adjacent spaces with fire barriers
Chapter 9 (8 and 7)
Change to a higher hazard
Section 1012 Change of Occupancy Classification – COOC-driven
Change of Occupancy Classification
IBC Deemed acceptable or comply with VRC
Means of egress, height & area, exterior wall exposure
Change to an equal or lower
hazard
Sprinklers, fire alarm and
detection, interior finishes,
accessibility (partial COOC)
Throughout building
Only where the COOC occurs
Vertical shafts, accessibility
(complete COOC)
IBC
Change of Occupancy
• The work area concept does not apply to change of occupancy classification – unless such changes meet the definition of work area
• In other words, just because an entire building is undergoing a change of occupancy does not mean the entire building is automatically a work area
53
Change of Occupancy
• VRC 1001.1 Scope
• Change of occupancy classification (A1 to A2)
• Occupancy group designation changes (E to B)
• Occupancy classification is not changed (A-3 to A-3)
• Change of purpose or level of activity
• A-3
• Library
• Art Gallery
• Gymnasium
• Large lecture Halls
• A-2
• Restaurant to night club
Change of Occupancy Classification
• VRC 1012.1.3 Change of occupancy classification based on hazard category
• Occupancy groups were evaluated in which the degree of inherent hazards of an occupancy group differ
• Like results were grouped and then assigned a rating number, 1 through 4 or 5
• The lower the number, the higher the hazard
• Tables are used to determine whether a change of occupancy classification is to a higher, lower, or equivalent occupancy classification
Change of Occupancy Classification: Means of Egress
• What about R-5?
• Will be taught to consider like R-3
54
Change of Occupancy Classification: Means of Egress
• VRC 1012.4.1 Change to higher hazard category
• Must comply with the IBC Chapter 10 • There are seven (7) exceptions
Change of Occupancy Classification: Means of Egress
• VRC 1012.4.2 Change to equal or lower hazard category
• Existing elements of the means of egress shall comply with VRC Chapter 9 for the new occupancy classification
• Newly constructed or configured means of egress shall comply with the IBC Chapter 10
Change of Occupancy Classification: Heights and areas
• R-5 = R-3
55
Change of Occupancy Classification: Heights and areas
• VRC 1012.5.1 Change to higher hazard category
• Must comply with the IBC Chapter 5 • Fire wall alternative
• In other than Groups H, F-1 and S-1, in lieu of fire walls, use of fire barriers having a fire-resistance rating of not less than that specified in the IBC, shall be permitted in buildings protected throughout with an automatic sprinkler system
Eiffel Tower 1889 - 984 FT
The Gherkin 2004 – 590 FT
Empire State Building 1931 – 1,454 FT
Taipei 101 2004 – 1,677 FT
Burj Khalifa 2010 – 2,717 FT
Nakheel Tower Never built – 4,593 FT
High-rise 75FT
• VRC 1012.5.2
Change to equal
or lower hazard
category • The height and
area of the
existing building
shall be deemed
acceptable
Change of Occupancy Classification: Heights and areas
Change of Occupancy Classification: Enclosure of vertical shafts
• Stairways
• To a higher hazard • IBC
• 3 exceptions
• Other than stairways
• To a higher hazard • IBC
• 2 exceptions
56
Change of Occupancy Classification: Accessibility
• VRC 1012.8.1 Partial
• That portion shall comply with VRC Sections 705, 806, and 906, as applicable
• VRC 1012.8.2 Complete
• Entire building shall comply with VRC Section 1012.8.1 and the following:
Additions
• Addition(s) must comply with the VCC
• Existing building
• Impact from addition: VRC
• “New” work w/in building: VRC
Additions
• VRC 1102.1 Height limitations
• No addition shall increase the height of an existing building beyond that permitted under the IBC
• Addition + Existing = IBC Chapter 5
• Based on lowest construction type
• VRC 1102.2 Area limitations
• No addition shall increase the area of an existing building beyond that permitted under the IBC, unless fire separation is provided per IBC
• Addition + Existing = IBC Chapter 5
• Based on lowest construction type
57
Additions
• VRC 1102.3 Fire protection systems
• If an addition increases an existing building’s fire area or areas to a level that is required to have fire protection systems by Chapter 9 of the IBC, those fire areas must comply with IBC Chapter 9 requirements, both in the addition and the existing building
• The VRC provides no exceptions to the sprinkler threshold limits given in Chapter 9 of the IBC
• Existing area is below sprinkler threshold (e.g., 4,000 SF)
• Add SF that exceeds the threshold (e.g., added 2,000 SF and threshold is 5,000 SF)
• Must sprinkle both the existing and new area (all 6,000 SF) – not just the new area
Additions: Structural
• VRC 1103.2 Additional gravity loads
• Existing structural elements supporting any additional gravity loads as a result of additions shall comply with the IBC
• Exception: Structural elements whose stress is not increased by more than 5%
• Lateral-force-resisting system
• Vertical addition
• Horizontal addition
• Addition of structural elements to improve existing
• Snow drifts
• Flood hazard areas
Historic Buildings
• VRC provides a means for the preservation of historic buildings
• Allows for a departure from full compliance with the I-Codes, without compromising the minimum standards for fire prevention and life safety features
58
Historic Buildings
Relocated or Moved Buildings
• Safe for human occupancy
• Per IFC and VMC
• Location on lot
• Per IBC / IRC
• Foundation
• Per IBC / IRC
• Wind loads
• Per IBC / IRC
• Seismic loads
• Per IBC / IRC
• Snow loads
• Per IBC / IRC
• Flood hazard
• Per IBC Section 1612
• Inspection and repairs
• Structural elements and connections
Performance Compliance Methods
• VRC 1401.6 Evaluation process
• Basically duplicates 2012 IBC Section 3412.5
• Must evaluate all listed categories in terms of • Fire safety
• Means of egress
• General safety
59
Performance Compliance Methods
IEBC VRC
Performance Compliance Methods
• Categories
• Building height
• Building area
• Compartmentation
• Corridor walls
• Tenant and dwelling unit separations
• Vertical openings
• HVAC systems
• Automatic fire detection
• Fire alarm systems
• Smoke control
• Means-of-egress capacity and number
• Dead ends
• Elevator control
• Means-of-egress emergency lighting
• Mixed occupancies
• Automatic sprinklers
• Standpipes
• Incidental uses
Performance Compliance Methods
• VRC 1401.7 Building score
• Enter into “Summary Sheet”
60
Performance Compliance Methods
• VRC 1401.8 Mandatory safety scores
Performance Compliance Methods
• VRC 1401.9 Evaluation of building safety
• Mandatory safety scores subtracted from building score for each category
Retrofit requirements
• Basically duplicates 2009 VCC 3413
• Since these retrofit requirements have been around for a few code cycles, it is anticipated that the effect of these requirements should be limited • Smoke detectors
• Fire detection system
• Fire suppression (sprinklers)
• Fire extinguishers
• Replacement glass
• Posting of occupant loads in assembly spaces
61
What compliance method?
• Prescriptive
• The traditional way of dealing with existing buildings (basically the old IBC Chapter 34)
• Intended to be used in conjunction with the maintenance and fire prevention codes utilizing mostly provisions from all of the referenced iCodes
• If you are used to the IBC and want to keep that way, this is the method for you
What compliance method?
• Work area
• Intended to be a proportional approach that gains compliance with the iCodes over a period of time
• “Upgrades” are generally triggered by the type and extent of the work
• Recognized as enhancing the level of safety but is not equal to that found in the iCodes
• Less stringent than the iCodes and therefore, potentially less costly
What compliance method?
• Performance
• Basically, the “compliance alternative” way of dealing with existing buildings (the old IBC Section 3412)
• Recognizes that most buildings that would utilize this method were built prior to any comprehensive building codes being adopted and are often not equipped with the types of systems and features that “modern” building codes require
62
What compliance method?
• VRC 301.1, Exception
• Appropriate for certain scopes of work – but only for alterations