19xr-7si

76
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53190008-01 Printed in U.S.A. Form 19XR-7SI Pg 1 1012 12-11 Replaces: 19XR-5SI Installation Instructions SAFETY CONSIDERATIONS Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design specifi- cations. When operating this equipment, use good judg- ment and safety precautions to avoid damage to equipment and property or injury to personnel. Be sure you understand and follow the procedures and safety precautions contained in the machine instruc- tions, as well as those listed in this guide. DANGER Failure to follow these procedures will result in severe per- sonal injury or death. DO NOT VENT refrigerant relief devices within a build- ing. Outlet from rupture disc or relief valve must be vented outdoors in accordance with the latest edition of ANSI/ ASHRAE 15 (American National Standards Institute/ American Society of Heating, Refrigerating and Air-Con- ditioning Engineers) (Safety Code for Mechanical Refrig- eration). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation. PROVIDE adequate ventilation in accordance with ANSI/ ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harm- ful and may cause heart irregularities, unconsciousness, or death. Intentional misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breath- ing. Product causes eye and skin irritation. Decomposition products are hazardous. DO NOT USE OXYGEN to purge lines or to pressurize a machine for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances. DO NOT USE air to leak test. Use only refrigerant or dry nitrogen. NEVER EXCEED specified test pressures. VERIFY the allowable test pressure by checking the instruction litera- ture and the design pressures on the equipment nameplate. DO NOT VALVE OFF any safety device. BE SURE that all pressure relief devices are properly installed and functioning before operating any machine. RISK OF INJURY OR DEATH by electrocution. High voltage is present on motor leads even though the motor is not running when a solid state or inside-delta mechanical starter is used. Open the power supply disconnect before touching motor leads or terminals. WARNING Failure to follow these procedures may result in personal injury or death. DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective gloves and gog- gles and proceed as follows: a. Shut off electrical power to unit. b. Recover refrigerant to relieve all pressure from sys- tem using both high-pressure and low pressure ports. c. Traces of vapor should be displaced with nitrogen and the work area should be well ventilated. Refrig- erant in contact with an open flame produces toxic gases. d. Cut component connection tubing with tubing cutter and remove component from unit. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to the system. e. Carefully unsweat remaining tubing stubs when nec- essary. Oil can ignite when exposed to torch flame. DO NOT USE eyebolts or eyebolt holes to rig machine sections or the entire assembly. DO NOT work on high-voltage equipment unless you are a qualified electrician. DO NOT WORK ON electrical components, including control panels, switches, starters, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid-state components. LOCK OPEN AND TAG electrical circuits during servic- ing. IF WORK IS INTERRUPTED, confirm that all cir- cuits are de-energized before resuming work. AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician. NEVER APPLY an open flame or live steam to a refriger- ant cylinder. Dangerous over pressure can result. When it is necessary to heat refrigerant, use only warm (110 F [43 C]) water. DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It is DANGEROUS AND ILLE- GAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar, and unscrew and discard the valve stem. DO NOT INCINERATE. CHECK THE REFRIGERANT TYPE before adding refrigerant to the machine. The introduction of the wrong refrigerant can cause machine damage or malfunction. (Warnings continued on next page.) EVERGREEN ® 19XR,XRV Hermetic Centrifugal Liquid Chillers with PIC II Controls and HFC-134a 50/60 Hz

Transcript of 19xr-7si

Page 1: 19xr-7si

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Catalog No. 04-53190008-01 Printed in U.S.A. Form 19XR-7SI Pg 1 1012 12-11 Replaces: 19XR-5SI

Installation InstructionsSAFETY CONSIDERATIONS

Centrifugal liquid chillers are designed to provide safeand reliable service when operated within design specifi-cations. When operating this equipment, use good judg-ment and safety precautions to avoid damage toequipment and property or injury to personnel.Be sure you understand and follow the procedures andsafety precautions contained in the machine instruc-tions, as well as those listed in this guide.

DANGER

Failure to follow these procedures will result in severe per-sonal injury or death.DO NOT VENT refrigerant relief devices within a build-ing. Outlet from rupture disc or relief valve must be ventedoutdoors in accordance with the latest edition of ANSI/ASHRAE 15 (American National Standards Institute/American Society of Heating, Refrigerating and Air-Con-ditioning Engineers) (Safety Code for Mechanical Refrig-eration). The accumulation of refrigerant in an enclosedspace can displace oxygen and cause asphyxiation.PROVIDE adequate ventilation in accordance with ANSI/ASHRAE 15, especially for enclosed and low overheadspaces. Inhalation of high concentrations of vapor is harm-ful and may cause heart irregularities, unconsciousness, ordeath. Intentional misuse can be fatal. Vapor is heavier thanair and reduces the amount of oxygen available for breath-ing. Product causes eye and skin irritation. Decompositionproducts are hazardous.DO NOT USE OXYGEN to purge lines or to pressurize amachine for any purpose. Oxygen gas reacts violently withoil, grease, and other common substances.DO NOT USE air to leak test. Use only refrigerant or drynitrogen.NEVER EXCEED specified test pressures. VERIFY theallowable test pressure by checking the instruction litera-ture and the design pressures on the equipment nameplate.DO NOT VALVE OFF any safety device.BE SURE that all pressure relief devices are properlyinstalled and functioning before operating any machine.RISK OF INJURY OR DEATH by electrocution. Highvoltage is present on motor leads even though the motor isnot running when a solid state or inside-delta mechanicalstarter is used. Open the power supply disconnect beforetouching motor leads or terminals.

WARNING

Failure to follow these procedures may result in personalinjury or death.DO NOT USE TORCH to remove any component. Systemcontains oil and refrigerant under pressure. To remove a component, wear protective gloves and gog-gles and proceed as follows:a. Shut off electrical power to unit.b. Recover refrigerant to relieve all pressure from sys-

tem using both high-pressure and low pressure ports.c. Traces of vapor should be displaced with nitrogen

and the work area should be well ventilated. Refrig-erant in contact with an open flame produces toxicgases.

d. Cut component connection tubing with tubing cutterand remove component from unit. Use a pan to catchany oil that may come out of the lines and as a gagefor how much oil to add to the system.

e. Carefully unsweat remaining tubing stubs when nec-essary. Oil can ignite when exposed to torch flame.

DO NOT USE eyebolts or eyebolt holes to rig machinesections or the entire assembly.DO NOT work on high-voltage equipment unless you are aqualified electrician.DO NOT WORK ON electrical components, includingcontrol panels, switches, starters, or oil heater until you aresure ALL POWER IS OFF and no residual voltage canleak from capacitors or solid-state components.LOCK OPEN AND TAG electrical circuits during servic-ing. IF WORK IS INTERRUPTED, confirm that all cir-cuits are de-energized before resuming work.AVOID SPILLING liquid refrigerant on skin or getting itinto the eyes. USE SAFETY GOGGLES. Wash any spillsfrom the skin with soap and water. If liquid refrigerantenters the eyes, IMMEDIATELY FLUSH EYES withwater and consult a physician.NEVER APPLY an open flame or live steam to a refriger-ant cylinder. Dangerous over pressure can result. When it isnecessary to heat refrigerant, use only warm (110 F [43 C])water.DO NOT REUSE disposable (nonreturnable) cylinders orattempt to refill them. It is DANGEROUS AND ILLE-GAL. When cylinder is emptied, evacuate remaining gaspressure, loosen the collar, and unscrew and discard thevalve stem. DO NOT INCINERATE.CHECK THE REFRIGERANT TYPE before addingrefrigerant to the machine. The introduction of the wrongrefrigerant can cause machine damage or malfunction.(Warnings continued on next page.)

EVERGREEN®

19XR,XRVHermetic Centrifugal Liquid Chillers

with PIC II Controls and HFC-134a50/60 Hz

Page 2: 19xr-7si

2

CONTENTSPage

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1,2INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Job Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-73Step 1 — Receive the Machine . . . . . . . . . . . . . . . . . . 2• INSPECT SHIPMENT• IDENTIFY MACHINE• INSTALLATION REQUIREMENTS• PROVIDE MACHINE PROTECTIONStep 2 — Rig the Machine . . . . . . . . . . . . . . . . . . . . . . . 3• RIG MACHINE ASSEMBLY• RIG MACHINE COMPONENTSStep 3 — Install Machine Supports . . . . . . . . . . . . . 33• INSTALL STANDARD ISOLATION• INSTALL ACCESSORY ISOLATION• INSTALL SPRING ISOLATIONStep 4 — Connect Piping . . . . . . . . . . . . . . . . . . . . . . . 35• INSTALL WATER PIPING TO HEAT

EXCHANGERS• INSTALL VENT PIPING TO

RELIEF VALVESStep 5 — Make Electrical Connections . . . . . . . . . 42• CONNECT CONTROL INPUTS• CONNECT CONTROL OUTPUTS• CONNECT STARTER• CARRIER COMFORT NETWORK INTERFACE• OPTIONAL UPC OPEN CONTROLLER WIRINGStep 6 — Install Field Insulation . . . . . . . . . . . . . . . . 73INSTALLATION START-UP REQUEST

CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1, CL-2

INTRODUCTION

General — The 19XR, 19XRV machine is factory assem-bled, wired, and leak tested. Installation (not by Carrier) con-sists primarily of establishing water and electrical services tothe machine. The rigging, installation, field wiring, field pip-ing, and insulation of waterbox covers are the responsibility ofthe contractor and/or customer. Carrier has no installationresponsibilities for the equipment.

Job DataNecessary information consists of:• job contract or specifications• machine location prints• rigging information• piping prints and details• field wiring drawings• starter manufacturer’s installation details• Carrier certified print

INSTALLATION

Step 1 — Receive the MachineINSPECT SHIPMENT

1. Inspect for shipping damage while machine is still onshipping conveyance. If machine appears to be damagedor has been torn loose from its anchorage, have itexamined by transportation inspectors before removal.

WARNING

Operation of this equipment with refrigerants other thanthose cited herein should comply with ANSI/ASHRAE 15(latest edition). Contact Carrier for further information onuse of this machine with other refrigerants.DO NOT ATTEMPT TO REMOVE fittings, covers, etc.,while machine is under pressure or while machine is run-ning. Be sure pressure is at 0 psig (0 kPa) before breakingany refrigerant connection.CAREFULLY INSPECT all relief valves, rupture discs,and other relief devices AT LEAST ONCE A YEAR. Ifmachine operates in a corrosive atmosphere, inspect thedevices at more frequent intervals.DO NOT ATTEMPT TO REPAIR OR RECONDITIONany relief valve when corrosion or build-up of foreignmaterial (rust, dirt, scale, etc.) is found within the valvebody or mechanism. Replace the valve.DO NOT install relief devices in series or backwards.USE CARE when working near or in line with a com-pressed spring. Sudden release of the spring can cause itand objects in its path to act as projectiles.

CAUTION

Failure to follow these procedures may result in damage toequipment.DO NOT STEP on refrigerant lines. Broken lines can whipabout and release refrigerant, causing personal injury.DO NOT climb over a machine. Use platform, catwalk, orstaging. Follow safe practices when using ladders.USE MECHANICAL EQUIPMENT (crane, hoist, etc.) tolift or move inspection covers or other heavy components.Even if components are light, use mechanical equipmentwhen there is a risk of slipping or losing your balance.BE AWARE that certain automatic start arrangementsCAN ENGAGE THE STARTER, TOWER FAN, ORPUMPS. Open the disconnect ahead of the starter, towerfan, and pumps. Shut off the machine or pump before ser-vicing equipment.USE only repaired or replacement parts that meet the coderequirements of the original equipment.DO NOT VENT OR DRAIN waterboxes containingindustrial brines, liquid, gases, or semisolids without thepermission of your process control group.DO NOT LOOSEN waterbox cover bolts until the water-box has been completely drained.DOUBLE-CHECK that coupling nut wrenches, dial indi-cators, or other items have been removed before rotatingany shafts.DO NOT LOOSEN a packing gland nut before checkingthat the nut has a positive thread engagement.PERIODICALLY INSPECT all valves, fittings, and pipingfor corrosion, rust, leaks, or damage.PROVIDE A DRAIN connection in the vent line near eachpressure relief device to prevent a build-up of condensateor rain water.DO NOT re-use compressor oil or any oil that has beenexposed to the atmosphere. Dispose of oil per local codesand regulations. DO NOT leave refrigerant system open to air any longerthan the actual time required to service the equipment. Sealcircuits being serviced and charge with dry nitrogen to pre-vent oil contamination when timely repairs cannot be com-pleted.

CAUTION

Do not open any valves or loosen any connections. The19XR, 19XRV machine may be shipped with a nitrogenholding charge in both modules. Damage to machine mayresult.

Page 3: 19xr-7si

3

Forward claim papers directly to transportation company.Manufacturer is not responsible for any damage incurredin transit.

2. Check all items against shipping list. Immediately notifythe nearest Carrier representative if any item is missing.

3. To prevent loss or damage, leave all parts in originalpackages until beginning installation. All openings areclosed with covers or plugs to prevent dirt and debrisfrom entering machine components during shipping. Afull operating oil charge is placed in the oil sump beforeshipment.

IDENTIFY MACHINE — The machine model number, seri-al number, and heat exchanger sizes are stamped on machineidentification nameplate (Fig. 1-3). Check this informationagainst shipping papers and job data.

INSTALLATION REQUIREMENTS — Prior to starting thechiller’s electrical installation, certain requirements should bechecked. Input power wire sizes, branch circuit protection, andcontrol wiring are all areas that need to be evaluated.Determine Wire Size Requirements — Wire size should bedetermined based on the size of the conduit openings, andapplicable local, national, and international codes (e.g., NEC

[National Electric Code]/CEC [California Energy Commis-sion] regulations). General recommendations are included inthe Carrier field wiring drawings.Conduit Entry Size — It is important to determine the size ofthe conduit openings in the enclosure power entry plate so thatthe wire planned for a specific entry point will fit through theopening. Do NOT punch holes or drill into the top surface ofstarter or drive if knockouts are provided on the side of the en-closure and not the top of the enclosure.Recommended Control and Signal Wire Sizes — The rec-ommended minimum size wire to connect I/O signals to thecontrol terminal blocks is 18 AWG (American Wire Gage).Recommended terminal tightening torque is 7 to 9 in.-lb(0.79 to 1.02 N-m).Recommended Airflow Clearances — Be sure there is ade-quate clearance for air circulation around the enclosure.A 6-in. (152.4 mm) minimum clearance is required wherevervents are located in the starter or drive enclosure.Verify Adequate Power Supply — It is important to verifythat the building power will meet the input power requirementsof the Machine Electrical Data nameplate input power rating.Be sure the input power to the chiller corresponds to the chill-er’s nameplate voltage, current, and frequency.PROVIDE MACHINE PROTECTION — Store machineand starter indoors, protected from construction dirt and mois-ture. Inspect under shipping tarps, bags, or crates to be sure thatwater has not collected during transit. Keep protective shippingcovers in place until machine is ready for installation.

If machine is exposed to freezing temperatures after watercircuits have been installed, open waterbox drains and removeall water from cooler and condenser. Leave drains open untilsystem is filled.

Step 2 — Rig the Machine — The 19XR, 19XRVmachine can be rigged as an entire assembly. It also has flangedconnections that allow the compressor, cooler, and condensersections to be separated and rigged individually.RIG MACHINE ASSEMBLY — See rigging instructions onlabel attached to machine. Refer to rigging guide (Fig. 4-6),physical data in Fig. 7, and Tables 1-8B. Lift machine only fromthe points indicated in rigging guide. Each lifting cable orchain must be capable of supporting the entire weight of themachine.Contractors are not authorized to disassemble any part of thechiller without Carrier's supervision. Any request otherwisemust be in writing from the Carrier Service Manager.NOTE: Carrier suggests that a structural engineer be consultedif transmission of vibrations from mechanical equipment is ofconcern.

SAFETY CODE CERTIFICATION

COMPRESSOR MOTOR DATA

R-

REFRIGERATION MACHINE

CARRIER CHARLOTTE

9701 OLD STATESVILLE ROAD

CHARLOTTE, NORTH CAROLINA 28269

MADE IN USA

PRODUCTION YEAR: 20XX

19XR05009801

A United Technologies CompanyTM

THIS UNIT IS DESIGNED,CONSTRUCTED,AND TESTED IN CONFORMANCE WITH ANSI/ASHRAE 15 (LATEST REVISION),

SPECIFICATION Z-415.IN ACCORDANCE WITH CARRIER AND OVERLOAD PROTECTION MUST BE THE COMPRESSOR MOTOR CONTROLLER REFRIGERATION.SAFETY CODE FOR MECHANICAL

TEST PRESSURE

DESIGN PRESSURE

CLR.WATER PRESSURE

COND.WATER PRESSURE

PSI

PSI

PSI

PSI

KPA

KPA

KPA

KPA

CAZTREH/ESAHP/STLOV

RL AMPS

OLT AMPS

LR AMPS Y-

LR AMPS D-

MAX FUSE/CIRCUIT BKR

MIN. CIRCUIT AMPACITY

LBS.

CHARGED

KGS.REFRIGERANT

MODEL NUMBER SERIAL NO.

MACHINE

COMP'R

COOLER

CONDENSER

ECON

STOR TANK

RATED iKW

RATED TONS

Fig. 1 — 19XR Refrigeration Machine Nameplate

a19-1881

WARNING

Lifting chiller module from points other than those speci-fied may result in serious damage to the machine or per-sonal injury. Rigging equipment and procedures must beadequate for maximum chiller module weight. See Fig. 4-6for maximum chiller module weights.

Page 4: 19xr-7si

4

Cooler Size10-12 (Frame 1 XR)15-17 (Frame 1 XR)20-22 (Frame 2 XR)30-32 (Frame 3 XR)35-37 (Frame 3 XR)40-42 (Frame 4 XR)45-47 (Frame 4 XR)50-54 (Frame 5 XR)5A-5C (Frame 5 XR)*55-59 (Frame 5 XR)5F-5H (Frame 5 XR)*5K-5R (Frame 5 XR)5T-5Z (Frame 5 XR)60-64 (Frame 6 XR)6K-6R (Frame 6 XR)65-69 (Frame 6 XR)6T-6Z (Frame 6 XR) 70-74 (Frame 7 XR)7K-7R (Frame 7 XR)75-79 (Frame 7 XR)7T-7Z (Frame 7 XR)80-84 (Frame 8 XR)8K-8R (Frame 8 XR)85-89 (Frame 8 XR)8T-8Z (Frame 8 XR)

Condenser Size10-12 (Frame 1 XR)15-17 (Frame 1 XR)20-22 (Frame 2 XR)30-32 (Frame 3 XR)35-37 (Frame 3 XR)40-42 (Frame 4 XR)45-47 (Frame 4 XR)50-54 (Frame 5 XR)55-59 (Frame 5 XR)60-64 (Frame 6 XR)65-69 (Frame 6 XR)70-74 (Frame 7 XR)75-79 (Frame 7 XR)80-84 (Frame 8 XR)85-89 (Frame 8 XR)

Compressor Code(First Digit Indicates Compressor Frame Size)**

Motor Code

Motor Efficiency CodeH — High EfficiencyS — Standard Efficiency

Motor Voltage CodeCode Volts-Phase-Hertz 60 — 200-3-60 61 — 230-3-60 62 — 380-3-60 63 — 416-3-60 64 — 460-3-60 65 — 575-3-60 66 — 2400-3-60 67 — 3300-3-60 68 — 4160-3-60 69 — 6900-3-60 50 — 230-3-50 52 — 400-3-50 53 — 3000-3-50 54 — 3300-3-50 55 — 6300-3-50 5A 5B 6A 6B

————

10000-3-5011000-3-5011000-3-6010000-3-60

Special Order Indicator– — StandardS — Special Order

Description19XR — High Efficiency Hermetic

Centrifugal Liquid Chiller19XRV — Ultra High Efficiency Variable Speed

Hermetic Centrifugal Liquid Chiller

Fig. 2 — Model Number Identification

a19-1940

* Refer to 19XR, 19XRV Computer Selection Program for details on these sizes.† Frame sizes with K-R and T-Z are with 1 in. OD evaporator tubing.** For Frame 4 compressors, second digit will be a letter (example 4G3) on units

equipped with split ring diffuser.††Refer to the 19XR, 19XRV Computer Selection Program for motor code details.

Page 5: 19xr-7si

5

34

18 19 20 21 22

23

31 30 29 28 27 26 25 2432

33 24

1

23

5

6

4

11

1213

16

15 14

17

7

910

8

Fig. 3 — Typical 19XR Components

LEGEND1 — Guide Vane Actuator2 — Suction Elbow3 — Chiller Visual Controller/ International Chiller

Visual Control (ICVC)4 — Chiller Identification Nameplate5 — Cooler, Auto Reset Relief Valves6 — Cooler Pressure Transducer7 — Condenser In/Out Temperature Thermistors8 — Condenser Waterflow Device (ICVC Inputs

available)9 — Cooler In/Out Temperature Thermistors

10 — Cooler Waterflow Device (ICVC Inputs available)11 — Refrigerant Pumpout Valve12 — Typical Flange Connection13 — Oil Drain Charging Valve14 — Oil Level Sight Glasses15 — Refrigerant Oil Cooler (Hidden)16 — Auxiliary Power Panel17 — Compressor Motor Housing

LEGEND18 — Condenser Auto. Reset Relief Valves19 — Compressor Motor Circuit Breaker20 — Solid-State Starter Control Display (optional)21 — Unit-Mounted Starter (Optional)

Solid-State Starter Shown22 — Motor Sight Glass23 — Cooler Return-End Waterbox Cover24 — ASME Nameplate (One Hidden)25 — Typical Waterbox Drain Port26 — Condenser Return-End Waterbox Cover27 — Refrigerant Moisture/Flow Indicator28 — Refrigerant Filter/Drier29 — Liquid Line Isolation Valve (Optional)30 — Linear Float Valve Chamber31 — Vessel Take-Apart Connector32 — Discharge Isolation Valve (Optional)33 — Charging Valve34 — Condenser Pressure Transducer

REAR VIEW

FRONT VIEW

a19-1533ef

a19-1534ef

Page 6: 19xr-7si

6

CHAIN "D"(SEE NOTE #2)

CHAIN "E"(SEE NOTE #2)

CHAIN "F"(SEE NOTE #2)

"A""B""C"

CHAIN MUST RUN THROUGHHOOK ON END COVER

VFDENCLOSURE

15’ - 0” (4572 mm) MIN 21’ - 0” (6401 mm) MAX HEIGHT ABOVE FLOOR

COMPFRAME

SIZE

HEATEXCHSIZE

MAXIMUM MACHINEWEIGHT

VESSELLENGTH DIM. “A” DIM. “B” DIM. “C”

CHAIN LENGTH

LF1 VFD or Unit-Mounted

Starter

LF2, Std Tier, or 575-v VFD “D” “E” “F”

lb kg lb kg ft mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm

2

10-12 18,590 8432 — — 10 3048 4- 7 1397 2-6 762 2-3 686 12-7 3835 13-0 3962 13-0 396215-17 19,140 8682 — — 12 3658 5- 9 1753 2-6 762 2-3 686 13-6 4115 13-2 4013 13-3 403920-22 19,610 8895 22,910 10392 10 3048 4- 7 1397 2-4 711 3-1 940 12-7 3835 13-0 3962 13-0 396230-32 21,210 9620 24,510 11118 12 3658 5- 9 1753 2-6 762 3-6 1067 13-6 4115 13-2 4013 13-3 403935-37 22,720 10306 26,020 11802 14 4267 7- 4 2235 2-6 762 3-6 1067 14-2 4318 13-4 4064 13-4 4064

3

30-32 21,210 9620 24,510 11118 12 3658 5- 9 1753 2-6 762 3-6 1067 13-6 4115 13-2 4013 13-3 403935-37 22,720 10306 26,020 11802 14 4267 7- 4 2235 2-6 762 3-6 1067 14-2 4318 13-4 4064 13-4 406440-42 29,930 13576 33,230 15073 12 3658 5- 9 1753 2-7 787 3-2 965 12-8 3861 12-8 3861 13-4 406445-47 32,040 14533 35,340 16030 14 4267 6-10 2083 2-7 787 3-2 965 13-1 3988 13-2 4013 13-8 416650-54 31,603 14335 34,103 15481 12 3658 5- 9 1753 2-7 787 3-2 965 12-7 3835 12-9 3886 13-5 40895K-5R 31,603 14355 34,103 15481 12 3658 5- 9 1753 2-7 787 3-2 965 12-7 3835 12-9 3886 13-5 408955-59 33,631 15255 36,131 16389 14 4267 6-10 2083 2-7 787 3-2 965 13-1 3988 13-3 4039 13-9 41915T-5Z 33,631 15255 36,131 16389 14 4267 6-10 2083 2-7 787 3-2 965 13-1 3988 13-3 4039 13-9 4191

4

50-54 32,933 14938 36,233 16435 12 3658 5- 9 1753 2-8 813 3-4 1016 13-1 3988 12-9 3886 13-4 40645K-5R 32,933 14938 36,233 16435 12 3658 5- 9 1753 2-8 813 3-4 1016 13-1 3988 12-9 3886 13-4 406455-59 34,661 15722 37,961 17219 14 4267 6- 2 1880 2-8 813 3-4 1016 13-7 4140 13-1 3998 14-4 43695T-5Z 34,661 15722 37,961 17219 14 4267 6- 2 1880 2-8 813 3-4 1016 13-7 4140 13-1 3998 14-4 436960-64 35,433 16072 38,733 17569 12 3658 5- 9 1753 2-8 813 3-4 1016 13-1 2988 12-9 3886 13-4 40646K-6R 35,433 16072 38,733 17569 12 3658 5- 9 1753 2-8 813 3-4 1016 13-1 3988 12-9 3886 13-4 406465-69 37,536 17026 40,836 18523 14 4267 6- 2 1880 2-8 813 3-4 1016 13-7 4140 13-1 3998 14-4 43696T-6Z 37,536 17026 40,836 18523 14 4267 6- 2 1880 2-8 813 3-4 1016 13-7 4140 13-1 3998 14-4 436970-74 40,929 18565 — — 14 4267 6- 6 1981 3-5 1041 4-4 1321 11-6 3505 12-5 3785 12-9 38867K-7R 40,929 18565 — — 14 4267 6- 6 1981 3-5 1041 4-4 1321 11-6 3505 12-5 3785 12-9 3886

MACHINE RIGGING GUIDENOTES:

1. Each chain must be capable of supporting the entire weight of the machine. Seechart for maximum weights.

2. Chain lengths shown are typical for 15 (4572 mm) lifting height. Some minoradjustments may be required.

3. Dimensions “A” and “B” define distance from machine center of gravity to tubesheet outermost surfaces. Dimension “C” defines distance from machine centerof gravity to floor.

4. Ensure that rigging cable is over the cable hook on the motor end cover beforelifting.

Fig. 4 — Machine Rigging Guide (Heat Exchanger Size 10 Through 7R)

a19-1992

Page 7: 19xr-7si

7

CHAIN "D"(SEE NOTE #2)

CHAIN "E"(SEE NOTE #2)

CHAIN "F"(SEE NOTE #2)

12’ - 0” (3658 mm) MIN14’ - 0” (4267 mm) MAXHEIGHT ABOVE FLOOR

HOOK FORCHAIN “D” TO TERMINATE HERE

"A""B"

"C"

COMPFRAME SIZE

HEATEXCHSIZE

MAXIMUM MACHINEWEIGHT

VESSELLENGTH DIM. “A” DIM. “B” DIM. “C”

CHAIN LENGTH

“D” “E” “F”

lb kg ft mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm

470-74 49,949 22656 14 4267 6- 5 1956 3-9 1143 4-9 1448 9- 8 2946 11-6 3505 11- 8 35567K-7R 49,949 22656 14 4267 6- 5 1956 3-9 1143 4-9 1448 9- 8 2946 11-6 3505 11- 8 3556

5

70-74 55,139 25011 14 4267 6- 2 1880 3-9 1143 4-9 1448 9-10 2997 11-4 3454 11- 6 35057K-7R 55,139 25011 14 4267 6- 2 1880 3-9 1143 4-9 1448 9-10 2997 11-4 3454 11- 6 350575-79 59,357 26294 16 4877 6-10 2083 3-9 1143 4-9 1448 10- 6 3200 12-8 3861 12-10 39127T-7Z 59,357 26294 16 4877 6-10 2083 3-9 1143 4-9 1448 10- 6 3200 12-8 3861 12-10 391280-84 64,866 29423 14 4267 6- 2 1880 3-9 1143 4-9 1448 9-10 2997 11-4 3454 11- 6 35058K-8R 64,866 29423 14 4267 6- 2 1880 3-9 1143 4-9 1448 9-10 2997 11-4 3454 11- 6 350585-89 68,839 31225 16 4877 6-10 2083 3-9 1143 4-9 1448 10- 6 3200 12-8 3861 12-10 39128T-8Z 68,839 31225 16 4877 6-10 2083 3-9 1143 4-9 1448 10- 6 3200 12-8 3861 12-10 3912

MACHINE RIGGING GUIDENOTES:

1. Each chain must be capable of supporting the entire weight ofthe machine. See chart for maximum weights.

2. Chain lengths shown are typical for 13 (3962 mm) lifting height.Some minor adjustments may be required.

3. Dimensions “A” and “B” define distance from machine center ofgravity to tube sheet outermost surfaces. Dimension “C”defines distance from machine center of gravity to floor.

4. Care must be taken to prevent damage to machine whilethreading chain “D” between drive, conduit, and piping.

Fig. 5 — Machine Rigging Guide (Heat Exchanger Size 70 Through 8Z)LF2, Std Tier, or 575-v VFD

a19-1990

Page 8: 19xr-7si

8

15’ - 0” (4572 mm) MIN 21’ - 0” (6401 mm) MAX HEIGHT ABOVE FLOOR

COMPFRAME

SIZE

HEATEXCHSIZE

MAXIMUM MACHINEWEIGHT

VESSELLENGTH DIM. “A” DIM. “B” DIM. “C”

CHAIN LENGTH

“D” “E” “F”

lb kg ft mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm

5

70-74 46,119 20919 14 4267 6- 2 1880 3-6 1067 4-7 1397 11- 6 3505 12-5 3785 12-9 38867K-7R 46,119 20919 14 4267 6- 2 1880 3-6 1067 4-7 1397 11- 6 3505 12-5 3785 12-9 388675-79 49,977 22669 16 4877 6-11 2108 3-6 1067 4-7 1397 11-11 3632 13-3 4039 13-7 41407T-7Z 49,977 22669 16 4877 6-11 2108 3-6 1067 4-7 1397 11-11 3632 13-3 4039 13-7 414080-84 55,981 25393 14 4267 6- 2 1880 3-6 1067 4-7 1397 11- 6 3505 12-5 3785 12-9 38868K-8R 55,981 25393 14 4267 6- 2 1880 3-6 1067 4-7 1397 11- 6 3505 12-5 3785 12-9 388685-89 59,564 27018 16 4877 6-11 2108 3-6 1067 4-7 1397 11-11 3632 13-3 4039 13-7 41408T-8Z 59,564 27018 16 4877 6-11 2108 3-6 1067 4-7 1397 11-11 3632 13-3 4039 13-7 4140

MACHINE RIGGING GUIDENOTES:

1. Each chain must be capable of supporting the entire weight ofthe machine. See chart for maximum weights.

2. Chain lengths shown are typical for 15 (4572 mm) lifting height.Some minor adjustments may be required.

3. Dimensions “A” and “B” define distance from machine center ofgravity to tube sheet outermost surfaces. Dimension “C”defines distance from machine center of gravity to floor.

Fig. 6 — Machine Rigging Guide (Heat Exchanger Size 70 Through 8Z)LF1 VFD or Unit-Mounted Starter

CG — Center of Gravity

a19-1312tf

Page 9: 19xr-7si

9

C

B

A

MOTOR SERVICECLEARANCE4'-0"- (1219 mm)

2'-6" MIN (762 mm)

2' MIN (610 mm)

SERVICE AREA

FRAME 2-4 COMPRESSOR 3'-0" (915 mm)RECOMMENDED OVERHEAD SERVICE CLEARANCEFRAME 5 COMPRESSOR 5'-0" (1524 mm)RECOMMENDED OVERHEAD SERVICE CLEARANCE

CLEARANCE FOR TUBE REMOVALSPACE FOREITHER END

10'-0" (3048 mm)(SIZES 10-12, 20-22)

12'-3 1/2" (3747 mm)(SIZES 15-17,30-32,40-42, 50-54, 5A-5C,5K-5R, 60-64, 6K-6R)

14'-0" (4267 mm)(SIZES 70-74, 7K-7R,80-84, 8K-8R)

14'-3" (4343 mm)(SIZES 35-37,45-47, 55-59,5F-5H, 5T-5Z,65-69, 6T-6Z)

16'-0" (4877 mm)(SIZES 75-79,7T-7Z, 85-89, 8T-8Z)

Fig. 7 — 19XR Dimensions (Refer to Tables 1 Through 3)

a19-1952

Page 10: 19xr-7si

10

Table 1 — 19XR Dimensions (Nozzle-In-Head Waterbox)

*Assumes both cooler and condenser nozzles on same end ofchiller.†Compressor frame size 2.**Compressor frame size 3.††Compressor frame size 4.***Compressor frame size 5.NOTES:

1. Service access should be provided per American Society ofHeating, Refrigerating, and Air Conditioning Engineers(ASHRAE) 15, latest edition, National Fire Protection Associa-tion (NFPA) 70, and local safety code.

2. Allow at least 3 ft (915 mm) overhead clearance for service rig-ging for frame 2-4 compressor. Overhead clearance for servicerigging frame 5 compressor should be 5 ft (1524 mm).

3. Dimensions are approximate. Certified drawings available uponrequest.

4. Marine waterboxes may add 6 in. to the width of the machine.See certified drawings for details.

5. ‘A’ length dimensions shown are for standard 150 psig designand victaulic connections. The 300 psig design and/or flangeswill add length. See certified drawings.

6. Not all waterbox/pass combinations are available with unit-mounted VFD. Check selection program and Drawing Managerfor availability.

7. 19XRV heights can vary depending on the configuration.Check 19XRV certified drawings for height information.

Table 2 — 19XR Nozzle Size

HEAT EXCHANGER SIZE

A (Length, with Nozzle-in-Head Waterbox) 19XRB (Width)

19XRC (Height)

19XRVB (Width)

19XRVC (Height)

1-Pass 2-Pass* 3-Passft-in. mm ft-in. mm ft-in. mm

SeeNote 7

ft-in. mm ft-in. mm ft-in. mm

10 to 12 11-11 3632 11-4 3464 11-11 3632 5- 27/8 1597 6- 11/4 1861 5-27/8 1597

15 to 17 14- 21/2 4331 13- 71/2 4163 14- 21/2 4331 5- 27/8 1597 6- 11/4 1861 5-27/8 1597

20 to 22 12- 01/2 3670 11- 51/8 3483 12- 01/2 3670 5- 67/16 1688 6- 31/4 1911 5-67/16 1688

30 to 32† 14- 4 4369 13- 85/8 4182 14- 4 4369 5- 73/16 1707 6- 95/8 2073 5-67/16 1688

30 to 32** 14- 4 4369 13- 85/8 4182 14- 4 4369 5- 73/16 1707 6- 95/8 2073 5-61/8 1680

35 to 37† 16- 01/2 4889 15- 51/8 4703 16- 01/2 4889 5- 73/16 1707 6- 95/8 2073 5-67/16 1688

35 to 37** 16- 01/2 4889 15- 51/8 4703 16- 01/2 4889 5- 73/16 1707 6- 95/8 2073 5-61/8 1680

40 to 42 14- 10 4521 14- 35/8 4360 14- 63/4 4439 6- 31/8 1908 7- 03/4 2153 6- 2 1880

45 to 47 16- 61/2 5042 16- 01/8 4880 16- 31/4 4959 6- 31/8 1908 7- 03/4 2153 6- 2 1880

50 to 52** 14-11 4546 14- 5 4395 14- 71/4 4451 6- 87/8 2054 7- 23/8 2194 6- 61/2 1994

50 to 54, 5K to 5R†† 14-11 4546 14- 5 4395 14- 71/4 4451 6- 87/8 2054 7- 23/8 2194 6- 77/8 2029

5A to 5C 14-11 4546 14- 5 4395 14- 71/4 4451 6- 87/8 2054 7- 23/8 2194 6- 87/8 2054

55 to 57** 16- 71/2 5067 16- 11/2 4915 16- 33/4 4972 6- 87/8 2054 7- 23/8 2194 6- 61/2 1994

55 to 59, 5T to 5Z†† 16- 71/2 5067 16- 11/2 4915 16- 33/4 4972 6- 87/8 2054 7- 23/8 2194 6- 77/8 2029

5F to 5H 16- 71/2 5067 16- 11/2 4915 16- 33/4 4972 6- 87/8 2054 7- 23/8 2194 6 - 87/8 2054

60 to 64, 6K to 6R 15- 0 4572 14- 53/4 4413 14- 73/4 4464 6- 05/8 2124 7- 43/8 2245 6- 105/8 2124

65 to 69, 6T to 6Z 16- 81/2 5093 16- 21/4 4934 16- 41/4 4985 6- 05/8 2124 7- 43/8 2245 6- 105/8 2124

70 to 74, 7K to 7R†† 17- 11/2 5219 16-111/2 5169 16-10 5131 7-111/2 2426 9- 91/2 2972 9- 13/8 2778

70 to 74, 7K to 7R*** 17- 11/2 5219 16-111/2 5169 16-10 5131 7-111/2 2426 9- 91/2 2972 9- 35/8 2835

75 to 79, 7T to 7Z 19- 11/2 5829 18-111/2 5779 18-10 5740 7-111/2 2426 9- 91/2 2972 9- 35/8 2835

80 to 84, 8K to 8R 17- 41/2 5296 17- 1 5207 16- 101/2 5143 8-103/4 2711 9- 111/4 3029 10- 09/16 3063

85 to 89, 8T to 8Z 19- 41/2 5905 19- 1 5817 18- 101/2 5753 8-103/4 2711 9- 111/4 3029 10- 09/16 3063

FRAMESIZE

NOZZLE SIZE (in.)(Nominal Pipe Size)

Cooler Condenser1-Pass 2-Pass 3-Pass 1-Pass 2-Pass 3-Pass

1 8 6 6 8 6 62 10 8 6 10 8 63 10 8 6 10 8 64 10 8 6 10 8 65 10 8 6 10 10 86 10 10 8 10 10 87 14 12 10 14 12 128 14 14 12 14 14 12

Page 11: 19xr-7si

11

Table 3 — 19XR Dimensions (Marine Waterbox)

*Assumes both cooler and condenser nozzles on same end of chiller.†1 or 3-pass length applies if cooler is a 1 or 3-pass design.NOTES:1. Service access should be provided per American Society of Heating,

Refrigerating, and Air Conditioning Engineers (ASHRAE) 15, latest edi-tion, National Fire Protection Association (NFPA) 70, and local safetycode.

2. Allow at least 3 ft (915 mm) overhead clearance for service rigging forframe 2-4 compressor. Overhead clearance for service rigging frame 5compressor should be 5 ft (1524 mm).

3. Dimensions are approximate. Certified drawings available upon request.4. Marine waterboxes may add 6 in., to the width of the machine. See certi-

fied drawings for details.5. ‘A’ length dimensions shown are for standard 150 psig design and victau-

lic connections. The 300 psig design and/or flanges will add length. Seecertified drawings.

6. 19XR,XRV height can vary depending on the configuration. Check 19XR,XRV certified drawings for height information.

7. Not all waterbox/pass combinations are available with unit-mounted VFD(variable frequency drive). Check selection program for availability.

Table 4 — 19XR Component Weights

*To determine compressor frame size, refer to 19XR,XRV Computer Selection Program.†Included in total cooler weight.

HEAT EXCHANGERSIZE

A (Length, Marine Waterbox) 19XRB WIDTH

19XRVB WIDTH 19XR,XRV

C HEIGHT2-Pass* 1 or 3-Pass†ft-in. mm ft-in. mm ft-in. mm ft-in. mm

10 to 12 NA NA NA NA NA NA NA NA

SeeNote 6

15 to 17 NA NA NA NA NA NA NA NA

20 to 22 12- 51/2 3797 14- 11/4 4299 6- 11/16 1856 6- 11/16 1856

30 to 32 14- 9 4496 16- 43/4 4997 6- 11/16 1856 6- 11/16 1856

35 to 37 16- 51/2 5017 18- 11/4 5518 6- 11/16 1856 6- 11/16 1856

40 to 42 15- 23/4 4642 16- 81/4 5086 6- 31/4 1911 6- 31/4 1911

45 to 47 16-111/4 5163 18- 43/4 5607 6- 31/4 1911 6- 31/4 1911

50 to 54, 5K to 5R 15- 31/2 4661 16- 81/2 5093 6- 87/8 2054 6- 87/8 2054

5A to 5C 15- 31/2 4661 16- 81/2 5093 6- 87/8 2054 6- 87/8 2054

55 to 59, 5T to 5Z 17- 0 5182 18- 5 5613 6- 87/8 2054 6- 87/8 2054

5F to 5H 17- 0 5182 18- 5 5613 6- 87/8 2054 6- 87/8 2054

60 to 64, 6K to 6R 15- 41/8 4677 16- 83/4 5099 6-113/4 2127 6- 113/4 2127

65 to 69, 6T to 6Z 17- 05/8 5197 18- 51/4 5620 6-113/4 2127 6- 113/4 2127

70 to 74, 7K to 7R 18- 35/8 5579 19- 93/4 6039 8- 81/8 2645 9- 63/8 2905

75 to 79, 7T to 7Z 20- 35/8 6188 21- 93/4 6649 8- 81/8 2645 9- 63/8 2905

80 to 84, 8K to 8R 18- 4 5583 19-101/2 6058 9- 55/8 2886 10- 5 3175

85 to 87, 8T to 8Z 20- 4 6198 21-101/2 6668 9- 55/8 2886 10- 5 3175

COMPONENTFRAME 2

COMPRESSOR*FRAME 3

COMPRESSOR*FRAME 4

COMPRESSOR*FRAME 5

COMPRESSOR*

lb kg lb kg lb kg lb kg

Suction Elbow 116 53 185 84 239 108 407 185

Discharge Elbow 100 45 125 57 157 71 325 147

Control Panel† 34 15 34 15 34 15 34 15

Optional Cooler Inlet Isolation Valve 8 4 13 6 20 9 24 11

Optional Discharge Isolation Valve 26 12 46 21 74 34 108 49

Std Tier VFD — 380, 400, and 460-v (335, 445 A) 650 295 650 295 — — — —

Std Tier VFD — 380, 400, and 460-v (485, 550 A) — — 1035 469 1035 469 — —

Std Tier VFD — 380, 400, and 460-v (605, 680, 765, 855, 960, 1070 A) — — 1600 726 1600 726 — —

Std Tier VFD — 380, 400, and 460-v (1275, 1530 A) — — 2800 1270 2800 1270

LiquiFlo™ 2 VFD — 380, 400, and 460-v (405 A / 608 A) 1600 726 1600 726 1600 726 — —

LiquiFlo 2 VFD — 380, 400, and 460-v (900 A) — — — — 2800 1270 2800 1270

LiquiFlo 2 VFD — 380, 400, and 460-v (1200 A) — — — — 2850 1293 2850 1293

LiquiFlo 2 VFD — 575-v (390 A) 2400 1089 2400 1089 — — — —

VFD Shelf — — — — 1049 476 1049 476

Page 12: 19xr-7si

12

Table 5A — 19XR Compressor and Motor Weights* — Compressor Frame Size 2†

*Total compressor weight is the sum of the compressor aerodynamic components (compressor weightcolumn), stator, rotor, and end bell cover weights.

†Compressor size number is the first digit of the compressor code. See Model Number Nomenclaturein Fig. 2.

**Compressor aerodynamic component weight only, motor weight not included. Applicable to standardcompressors only. For high lift compressors, contact Carrier Chiller Marketing for weights.

††Stator weight includes the stator and shell.

MOTOR CODE

ENGLISH SI

Compressor Weight**

(lb)

60 Hz 50 HzEnd Bell

CoverWeight

(lb)

Compressor Weight**

(kg)

60 Hz 50 HzEnd Bell

CoverWeight

(kg)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(kg)

Rotor Weight

(kg)

Stator Weight††

(kg)

Rotor Weight

(kg)

STANDARD-EFFICIENCY MOTORS / LOW VOLTAGE (200-575v)

BDS 2300 900 190 915 205 185 1043 408 86 415 93 84

BES 2300 915 200 965 220 185 1043 415 91 438 100 84

BFS 2300 975 215 1000 230 185 1043 442 98 454 104 84

BGS 2300 1000 230 1060 250 185 1043 454 104 481 113 84

BHS 2300 1030 240 1105 265 185 1043 467 109 501 120 84

BJS 2300 1105 265 — — 185 1043 501 120 — — 84

HIGH-EFFICIENCY MOTORS / LOW VOLTAGE (200-575v)

BDH 2300 1030 240 1030 240 185 1043 467 109 467 109 84

BEH 2300 1070 250 1070 250 185 1043 485 113 485 113 84

BFH 2300 1120 265 1120 265 185 1043 508 120 508 120 84

BGH 2300 1175 290 1175 290 185 1043 533 132 533 132 84

BHH 2300 1175 290 1175 290 185 1043 533 132 533 132 84

BJH 2300 1175 290 — — 185 1043 533 132 — — 84

JBH 2300 1003 226 1063 248 185 1043 455 103 482 112 84

JCH 2300 1063 248 1113 263 185 1043 482 112 505 119 84

JDH 2300 1113 263 1149 278 185 1043 505 119 521 126 84

JEH 2300 1149 278 1196 295 185 1043 521 126 542 134 84

JFH 2300 1196 295 — — 185 1043 542 134 — — 84

Page 13: 19xr-7si

13

Table 5B — 19XR Compressor and Motor Weights* — Compressor Frame Size 3†

*Total compressor weight is the sum of the compressor aerodynamic components (compressor weightcolumn), stator, rotor, and end bell cover weights.

†Compressor size number is the first digit of the compressor code. See Model Number Nomenclaturein Fig. 2.

**Compressor aerodynamic component weight only, motor weight not included. Applicable to standardcompressors only. For high lift compressors, contact Carrier Chiller Marketing for weights.

††Stator weight includes the stator and shell.

MOTOR CODE

ENGLISH SI

Compressor Weight**

(lb)

60 Hz 50 HzEnd Bell

CoverWeight

(lb)

Compressor Weight**

(kg)

60 Hz 50 HzEnd Bell

CoverWeight

(kg)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(kg)

Rotor Weight

(kg)

Stator Weight††

(kg)

Rotor Weight

(kg)

STANDARD-EFFICIENCY MOTORS / LOW VOLTAGE (200-575v)

CBS 2816 1146 219 1188 236 274 1277 520 99 539 107 124

CCS 2816 1171 227 1196 242 274 1277 531 103 542 110 124

CDS 2816 1198 237 1258 255 274 1277 543 108 571 116 124

CES 2816 1207 240 1272 258 274 1277 547 109 577 117 124

CLS 2816 1247 249 1328 273 274 1277 566 113 602 124 124

CMS 2816 1270 257 1353 278 274 1277 576 117 614 126 124

CNS 2816 1321 266 1386 282 274 1277 599 121 629 128 124

CPS 2816 1334 269 1401 287 274 1277 605 122 635 130 124

CQS 2816 1353 276 1408 290 274 1277 614 125 639 132 124

CRS 2816 1259 321 — — 274 1277 571 146 — — 124CRS

(380v) 2816 1328 346 — — 274 1277 602 157 — — 124

STANDARD-EFFICIENCY MOTORS / MEDIUM VOLTAGE (2400-4160v)

CBS 2816 1154 236 1160 255 274 1277 523 107 526 116 124

CCS 2816 1182 243 1177 260 274 1277 536 110 534 118 124

CDS 2816 1220 252 1212 270 274 1277 553 114 550 122 124

CES 2816 1253 261 1259 281 274 1277 568 118 571 127 124

CLS 2816 1261 265 1271 284 274 1277 572 120 577 129 124

CMS 2816 1294 273 1318 293 274 1277 587 124 598 133 124

CNS 2816 1314 280 1357 303 274 1277 596 127 616 137 124

CPS 2816 1343 282 1413 308 274 1277 609 128 641 140 124

CQS 2816 1419 300 1522 336 274 1277 644 136 690 152 124

HIGH-EFFICIENCY MOTORS / LOW VOLTAGE (200-575v)

CBH 2816 1235 239 1290 254 274 1277 560 108 585 115 124

CCH 2816 1260 249 1295 259 274 1277 572 113 587 117 124

CDH 2816 1286 258 1358 273 274 1277 583 117 616 124 124

CEH 2816 1305 265 1377 279 274 1277 592 120 625 127 124

CLH 2816 1324 271 1435 292 274 1277 601 123 651 132 124

CMH 2816 1347 275 1455 298 274 1277 611 125 660 135 124

CNH 2816 1358 278 1467 301 274 1277 616 126 665 137 124

CPH 2816 1401 290 1479 304 274 1277 635 132 671 138 124

CQH 2816 1455 304 1479 304 274 1277 670 138 671 138 124

KBH 2816 1313 276 1353 285 274 1277 596 125 614 129 124

KCH 2816 1353 285 1381 291 274 1277 614 129 626 132 124

KDH 2816 1381 291 1417 307 274 1277 626 132 643 139 124

KEH 2816 1417 307 1441 313 274 1277 643 139 654 142 124

KFH 2816 1441 313 1470 320 274 1277 654 142 667 145 124

KGH 2816 1470 320 1505 333 274 1277 667 145 683 151 124

KHH 2816 1505 333 — — 274 1277 683 151 — — 124

Page 14: 19xr-7si

14

Table 5B — 19XR Compressor and Motor Weights* — Compressor Frame Size 3† (cont)

*Total compressor weight is the sum of the compressor aerodynamic components (compressor weightcolumn), stator, rotor, and end bell cover weights.

†Compressor size number is the first digit of the compressor code. See Model Number Nomenclaturein Fig. 2.

**Compressor aerodynamic component weight only, motor weight not included. Applicable to standardcompressors only. For high lift compressors, contact Carrier Chiller Marketing for weights.

††Stator weight includes the stator and shell.

MOTOR CODE

ENGLISH SI

Compressor Weight**

(lb)

60 Hz 50 HzEnd Bell

CoverWeight

(lb)

Compressor Weight**

(kg)

60 Hz 50 HzEnd Bell

CoverWeight

(kg)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(kg)

Rotor Weight

(kg)

Stator Weight††

(kg)

Rotor Weight

(kg)

HIGH-EFFICIENCY MOTORS / MEDIUM VOLTAGE (2400-4160v)

CBH 2816 1114 242 1156 255 274 1277 505 110 524 116 124

CCH 2816 1129 247 1163 257 274 1277 512 112 528 117 124

CDH 2816 1155 253 1190 263 274 1277 524 115 540 119 124

CEH 2816 1175 263 1236 276 274 1277 533 119 561 125 124

CLH 2816 1242 280 1305 296 274 1277 563 127 592 134 124

CMH 2816 1321 303 1305 296 274 1277 599 137 592 134 124

CNH 2816 1369 316 1386 316 274 1277 621 143 629 143 124

CPH 2816 1411 329 1386 316 274 1277 640 149 629 143 124

CQH 2816 1411 329 1428 329 274 1277 640 149 648 149 124

Page 15: 19xr-7si

15

Table 5C — 19XR Compressor and Motor Weights* — Compressor Frame Size 4†

*Total compressor weight is the sum of the compressor aerodynamic components (compressor weightcolumn), stator, rotor, and end bell cover weights.

†Compressor size number is the first digit of the compressor code. See Model Number Nomenclaturein Fig. 2.

**Compressor aerodynamic component weight only, motor weight not included. Applicable to standardcompressors only. For high lift compressors, contact Carrier Chiller Marketing for weights. For com-pressor frame size 4, two compressor weights are shown. The second value, 4211 lb (1910 kg), rep-resents the weight when the compressor is equipped with a Split Ring Diffuser (SRD).

††Stator weight includes the stator and shell.

MOTOR CODE

ENGLISH SI

Compressor Weight**

(lb)

60 Hz 50 HzEnd Bell

CoverWeight

(lb)

Compressor Weight**

(kg)

60 Hz 50 HzEnd Bell

CoverWeight

(kg)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(kg)

Rotor Weight

(kg)

Stator Weight††

(kg)

Rotor Weight

(kg)

STANDARD-EFFICIENCY MOTORS / LOW VOLTAGE (200-575v)

DBS 3425 / 4211 1570 324 1725 347 236 1554 / 1910 712 147 782 157 107

DCS 3425 / 4211 1580 326 1737 352 236 1554 / 1910 717 148 788 160 107

DDS 3425 / 4211 1595 329 1749 357 236 1554 / 1910 723 149 793 162 107

DES 3425 / 4211 1685 345 1762 365 236 1554 / 1910 764 156 799 166 107

DFS 3425 / 4211 1690 348 1801 372 236 1554 / 1910 767 158 817 169 107

DGS 3425 / 4211 1692 352 1858 386 236 1554 / 1910 767 160 843 175 107

DHS 3425 / 4211 1774 366 1904 398 236 1554 / 1910 805 166 864 181 107

DJS 3425 / 4211 — — 2020 401 318 1554 / 1910 — — 916 182 142

STANDARD-EFFICIENCY MOTORS / MEDIUM VOLTAGE (2400-4160v)

DBS 3425 / 4211 1524 296 1637 327 236 1554 / 1910 691 134 743 148 107

DCS 3425 / 4211 1569 307 1685 354 236 1554 / 1910 712 139 764 161 107

DDS 3425 / 4211 1588 313 1713 357 236 1554 / 1910 720 142 777 162 107

DES 3425 / 4211 1613 324 1746 360 236 1554 / 1910 732 147 792 163 107

DFS 3425 / 4211 1675 347 1811 381 236 1554 / 1910 760 157 821 173 107

DGS 3425 / 4211 1704 355 1998 422 236 (60 Hz)318 (50 Hz) 1554 / 1910 773 161 906 191 107 (60 Hz)

142 (50 Hz)

DHS 3425 / 4211 1737 361 2056 443 236 (60 Hz)318 (50 Hz) 1554 / 1910 788 164 933 201 107 (60 Hz)

142 (50 Hz)

DJS 3425 / 4211 1769 365 2101 464 236 (60 Hz)318 (50 Hz) 1554 / 1910 802 166 953 210 107 (60 Hz)

142 (50 Hz)STANDARD-EFFICIENCY MOTORS / MEDIUM VOLTAGE (6300-6900v)

DDS 3425 / 4211 1919 423 2069 458 318 1554 / 1910 870 192 938 208 142

DES 3425 / 4211 1939 428 2089 463 318 1554 / 1910 880 194 947 210 142

DFS 3425 / 4211 1989 448 2139 478 318 1554 / 1910 902 203 970 217 142

DGS 3425 / 4211 2054 473 — — 318 1554 / 1910 932 215 — — 142

DHS 3425 / 4211 2099 488 — — 318 1554 / 1910 952 221 — — 142

DJS 3425 / 4211 2159 508 — — 318 1554 / 1910 979 230 — — 142

HIGH-EFFICIENCY MOTORS / LOW VOLTAGE (200-575v)

DBH 3425 / 4211 1773 406 1827 406 318 1554 / 1910 804 184 829 184 142

DCH 3425 / 4211 1827 406 1827 414 318 1554 / 1910 829 184 829 188 142

DDH 3425 / 4211 1827 414 1881 422 318 1554 / 1910 829 188 853 191 142

DEH 3425 / 4211 1881 422 1881 422 318 1554 / 1910 853 191 853 191 142

DFH 3425 / 4211 1881 439 1963 439 318 1554 / 1910 853 199 890 199 142

DGH 3425 / 4211 1963 455 1963 455 318 1554 / 1910 890 206 890 206 142

DHH 3425 / 4211 1963 455 2050 463 318 1554 / 1910 890 206 930 210 142

DJH 3425 / 4211 — — 2050 471 318 1554 / 1910 — — 930 213 142

DKH 3425 / 4211 2050 471 — — 318 1554 / 1910 930 214 — — 142

Page 16: 19xr-7si

16

Table 5C — 19XR Compressor and Motor Weights* — Compressor Frame Size 4† (cont)

*Total compressor weight is the sum of the compressor aerodynamic components (compressor weightcolumn), stator, rotor, and end bell cover weights.

†Compressor size number is the first digit of the compressor code. See Model Number Nomenclaturein Fig. 2.

**Compressor aerodynamic component weight only, motor weight not included. Applicable to standardcompressors only. For high lift compressors, contact Carrier Chiller Marketing for weights. For com-pressor frame size 4, two compressor weights are shown. The second value, 4211 lb (1910 kg), rep-resents the weight when the compressor is equipped with a Split Ring Diffuser (SRD).

††Stator weight includes the stator and shell.

MOTOR CODE

ENGLISH SI

Compressor Weight**

(lb)

60 Hz 50 HzEnd Bell

CoverWeight

(lb)

Compressor Weight**

(kg)

60 Hz 50 HzEnd Bell

CoverWeight

(kg)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(kg)

Rotor Weight

(kg)

Stator Weight††

(kg)

Rotor Weight

(kg)

HIGH-EFFICIENCY MOTORS / LOW VOLTAGE (200-575v)

LBH 3425 / 4211 1873 364 1939 389 318 1554 / 1910 850 165 880 176 144

LCH 3425 / 4211 1939 389 2023 406 318 1554 / 1910 880 176 918 184 144

LDH 3425 / 4211 2023 406 2043 417 318 1554 / 1910 918 184 927 189 144

LEH 3425 / 4211 2043 417 2096 434 318 1554 / 1910 927 189 951 197 144

LFH 3425 / 4211 2096 434 2133 444 318 1554 / 1910 951 197 968 201 144

LGH 3425 / 4211 2133 444 2199 458 318 1554 / 1910 968 201 997 208 144

LHH 3425 / 4211 2199 458 2066 437 318 1554 / 1910 997 208 937 198 144

HIGH-EFFICIENCY MOTORS / MEDIUM VOLTAGE (2400-4160v)

DBH 3425 / 4211 1950 405 1950 405 318 1554 / 1910 885 184 885 184 144

DCH 3425 / 4211 1950 405 2025 429 318 1554 / 1910 885 184 919 195 144

DDH 3425 / 4211 1950 405 2025 429 318 1554 / 1910 885 184 919 195 144

DEH 3425 / 4211 2025 429 2100 452 318 1554 / 1910 919 195 953 205 144

DFH 3425 / 4211 2025 429 2100 452 318 1554 / 1910 919 195 953 205 144

DGH 3425 / 4211 2100 452 2200 480 318 1554 / 1910 953 205 998 218 144

DHH 3425 / 4211 2100 452 2320 575 318 1554 / 1910 953 205 1052 261 144

DJH 3425 / 4211 2100 452 2320 587 318 1554 / 1910 953 205 1052 266 144

DKH 3425 / 4211 2320 587 — — 318 1554 / 1910 1052 266 — — 144

HIGH-EFFICIENCY MOTORS / MEDIUM VOLTAGE (6300-6900v)

DDH 3425 / 4211 2150 536 2250 546 318 1554 / 1910 975 243 1021 248 144

DEH 3425 / 4211 2150 550 2250 550 318 1554 / 1910 975 249 1021 249 144

DFH 3425 / 4211 2250 575 2380 567 318 1554 / 1910 1021 261 1080 261 144

DGH 3425 / 4211 2250 599 2380 599 318 1554 / 1910 1021 272 1080 272 144

DHH 3425 / 4211 2380 604 2380 604 318 1554 / 1910 1080 274 1080 274 144

DJH 3425 / 4211 2380 614 2380 614 318 1554 / 1910 1080 279 1080 279 144

DKH 3425 / 4211 2380 614 — — 318 1554 / 1910 1080 279 — — 144

Page 17: 19xr-7si

17

Table 5D — 19XR Compressor and Motor Weights* — Compressor Frame Size 5†

*Total compressor weight is the sum of the compressor aerodynamic components (compressor weightcolumn), stator, rotor, and end bell cover weights.

†Compressor size number is the first digit of the compressor code. See Model Number Nomenclaturein Fig. 2.

**Compressor aerodynamic component weight only, motor weight not included. Applicable to standardcompressors only. For high lift compressors, contact Carrier Chiller Marketing for weights.

††Stator weight includes the stator and shell.

MOTOR CODE

ENGLISH SI

Compressor Weight**

(lb)

60 Hz 50 HzEnd Bell

CoverWeight

(lb)

Compressor Weight**

(kg)

60 Hz 50 HzEnd Bell

CoverWeight

(kg)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(kg)

Rotor Weight

(kg)

Stator Weight††

(kg)

Rotor Weight

(kg)

STANDARD-EFFICIENCY MOTORS / LOW VOLTAGE (200-575v)

EHS 7285 2843 741 2943 775 414 3304 1290 336 1335 352 188

EJS 7285 2826 741 2943 775 414 3304 1281 336 1335 352 188

EKS 7285 2943 775 2997 810 414 3304 1335 352 1359 367 188

ELS 7285 2932 775 2997 810 414 3304 1330 352 1359 367 188

EMS 7285 2986 810 3096 862 414 3304 1354 367 1404 391 188

ENS 7285 2986 810 3203 914 414 3304 1354 367 1453 415 188

EPS 7285 2986 810 3203 914 414 3304 1354 367 1453 415 188

EQS 7285 3013 621 — — 414 3304 1367 282 — — 188

STANDARD-EFFICIENCY MOTORS / MEDIUM VOLTAGE (2400-4160v)

EHS 7285 2744 706 2818 741 414 3304 1245 320 1278 336 188

EJS 7285 2816 741 2892 775 414 3304 1277 336 1312 352 188

EKS 7285 2816 741 2930 775 414 3304 1277 336 1329 352 188

ELS 7285 2808 741 3005 810 414 3304 1274 336 1363 367 188

EMS 7285 2892 775 3005 810 414 3304 1322 352 1363 367 188

ENS 7285 2997 775 3143 879 414 3304 1359 352 1426 399 188

EPS 7285 2967 810 3144 879 414 3304 1346 367 1426 399 188

STANDARD-EFFICIENCY MOTORS / MEDIUM VOLTAGE (6300-6900v)

EHS 7285 2773 735 2845 769 414 3304 1258 333 1290 349 188

EJS 7285 2855 769 2855 769 414 3304 1295 349 1295 349 188

EKS 7285 2919 803 2919 803 414 3304 1324 364 1324 364 188

ELS 7285 2908 803 3058 871 414 3304 1319 364 1387 395 188

EMS 7285 3029 854 3068 871 414 3304 1374 387 1392 395 188

ENS 7285 3023 854 3281 974 414 3304 1371 387 1488 442 188

EPS 7285 3068 871 3288 974 414 3304 1392 395 1491 442 188

HIGH-EFFICIENCY MOTORS / LOW VOLTAGE (200-575v)

EHH 7285 2939 776 2995 810 414 3304 1333 352 1359 367 188

EJH 7285 2944 776 3002 810 414 3304 1335 352 1362 367 188

EKH 7285 2992 810 3110 862 414 3304 1357 367 1411 391 188

ELH 7285 2299 810 3099 862 414 3304 1043 367 1406 391 188

EMH 7285 2965 810 3210 914 414 3304 1345 367 1456 415 188

ENH 7285 3015 855 3293 974 414 3304 1368 388 1494 442 188

EPH 7285 3029 855 3289 974 414 3304 1374 388 1492 442 188

EQH 7285 3162 664 — — 414 3304 1434 301 — — 188

Page 18: 19xr-7si

18

Table 5D — 19XR Compressor and Motor Weights* — Compressor Frame Size 5† (cont)

*Total compressor weight is the sum of the compressor aerodynamic components (compressor weightcolumn), stator, rotor, and end bell cover weights.

†Compressor size number is the first digit of the compressor code. See Model Number Nomenclaturein Fig. 2.

**Compressor aerodynamic component weight only, motor weight not included. Applicable to standardcompressors only. For high lift compressors, contact Carrier Chiller Marketing for weights.

††Stator weight includes the stator and shell.

MOTOR CODE

ENGLISH SI

Compressor Weight**

(lb)

60 Hz 50 HzEnd Bell

CoverWeight

(lb)

Compressor Weight**

(kg)

60 Hz 50 HzEnd Bell

CoverWeight

(kg)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(lb)

Rotor Weight

(lb)

Stator Weight††

(kg)

Rotor Weight

(kg)

Stator Weight††

(kg)

Rotor Weight

(kg)

HIGH-EFFICIENCY MOTORS / LOW VOLTAGE (200-575v)

MBH 7285 2795 645 2856 665 414 3304 1268 293 1295 302 188

MCH 7285 2873 672 2925 693 414 3304 1303 305 1327 314 188

MDH 7285 2906 684 3013 724 414 3304 1318 310 1367 328 188

MEH 7285 2956 704 3071 737 414 3304 1341 319 1392 334 188

MFH 7285 3034 724 3153 791 414 3304 1376 328 1430 359 188

MGH 7285 3071 737 — — 414 3304 1393 334 — — 188

HIGH-EFFICIENCY MOTORS / MEDIUM VOLTAGE (2400-4160v)

EHH 7285 2939 776 2997 810 414 3304 1333 352 1359 367 188

EJH 7285 2999 810 3108 862 414 3304 1360 367 1410 391 188

EKH 7285 2988 810 3102 862 414 3304 1355 367 1407 391 188

ELH 7285 2981 810 3065 872 414 3304 1352 367 1390 396 188

EMH 7285 3031 855 3077 872 414 3304 1375 388 1396 396 188

ENH 7285 3075 872 3260 974 414 3304 1395 396 1479 442 188

EPH 7285 3081 872 3298 974 414 3304 1398 396 1496 442 188

EQH 7285 3195 657 — — 414 3304 1449 298 — — 188

HIGH-EFFICIENCY MOTORS / MEDIUM VOLTAGE (6300-6900v)

EHH 7285 2998 810 3097 862 414 3304 1360 367 1405 391 188

EJH 7285 3029 855 3100 862 414 3304 1374 388 1406 391 188

EKH 7285 3049 855 3064 872 414 3304 1383 388 1390 396 188

ELH 7285 3068 872 3060 872 414 3304 1390 396 1388 396 188

EMH 7285 — — 3072 872 414 3304 — — 1393 396 188

ENH 7285 3075 872 3260 974 414 3304 1395 396 1479 442 188

EPH 7285 3081 872 3288 974 414 3304 1398 396 1491 442 188

EQH 7285 3195 657 — — 414 3304 1449 298 — — 188

HIGH-EFFICIENCY MOTORS / HIGH VOLTAGE (10000-11000v)

MCH 7285 — — 3956 678 414 3304 — — 1794 308 188

MDH 7285 — — 3956 678 414 3304 — — 1794 308 188

MFH 7285 — — 4062 719 414 3304 — — 1842 326 188

MGH 7285 3820 657 — — 414 3304 1733 298 — — 188

MHH 7285 3820 657 — — 414 3304 1733 298 — — 188

Page 19: 19xr-7si

19

Table 6A — 19XR Heat Exchanger Data — Drive End Entering Cooler Water

*Rigging weights are for standard tubes of standard wall thickness (0.025-in. [0.635 mm] wall).NOTES:

1. Cooler includes the control panel (ICVC), suction elbow, and 1/2 the distribution piping weight.2. Condenser includes float valve and sump, discharge elbow, and 1/2 the distribution piping weight.3. For special tubes refer to the 19XR/XRV Computer Selection Program.4. All weights for standard 2-pass NIH (nozzle-in-head) design.

CODE

ENGLISH METRIC (SI)Dry Rigging Weight

(lb)* Machine Charge Dry Rigging Weight(kg)* Machine Charge

CoolerOnly

CondenserOnly

RefrigerantWeight (lb)

Water Weight(lb) Cooler

OnlyCondenser

Only

Refrigerant Weight (kg)

Water Weight(kg)

Cooler Condenser Cooler Condenser Cooler Condenser Cooler Condenser10 2707 2704 328 226 283 348 1229 1228 149 103 128 15811 2777 2772 357 226 309 374 1261 1258 162 103 140 17012 2848 2857 387 226 335 407 1293 1297 176 103 152 18515 2969 2984 405 275 327 402 1348 1355 184 125 148 18316 3054 3068 441 275 359 435 1387 1393 200 125 163 19717 3141 3173 477 275 391 475 1426 1441 217 125 178 21620 3407 3373 416 252 402 398 1547 1531 189 114 183 18121 3555 3540 459 252 456 462 1614 1607 208 114 207 21022 3711 3704 505 252 514 526 1685 1682 229 114 233 23930 4071 3694 510 308 464 464 1848 1677 232 140 211 21131 4253 3899 565 308 531 543 1931 1770 257 140 241 24732 4445 4100 626 308 601 621 2018 1861 284 140 273 28235 4343 4606 577 349 511 513 1972 2091 262 158 232 23336 4551 4840 639 349 587 603 2066 2197 290 158 266 27437 4769 5069 709 349 667 692 2165 2301 322 158 303 31440 4908 5039 726 338 863 915 2228 2288 330 153 392 41541 5078 5232 783 338 930 995 2305 2375 355 153 422 45242 5226 5424 840 338 990 1074 2373 2462 381 153 449 48845 5363 5602 821 383 938 998 2435 2543 373 174 426 45346 5559 5824 874 383 1014 1088 2524 2644 397 174 460 49447 5730 6044 949 383 1083 1179 2601 2744 431 174 492 53550 5713 6090 897 446 1101 1225 2594 2765 407 202 500 55651 5940 6283 974 446 1192 1304 2697 2852 442 202 541 59252 6083 6464 1021 446 1248 1379 2762 2935 464 202 567 62653 6141 6529 1010 446 1277 1409 2788 2964 459 202 580 64054 6192 6591 987 446 1302 1439 2811 2992 448 202 591 65355 6257 6785 1014 504 1201 1339 2841 3080 460 229 545 60856 6517 7007 1101 504 1304 1429 2959 3181 500 229 592 64957 6682 7215 1154 504 1369 1514 3034 3276 524 229 622 68758 6751 7291 1143 504 1401 1550 3065 3310 519 229 636 70459 6811 7363 1116 504 1430 1583 3092 3343 507 229 649 7195A 5124 — 491 — 1023 — 2326 — 223 — 464 —5B 5177 — 510 — 1050 — 2350 — 232 — 477 —5C 5243 — 532 — 1079 — 2380 — 242 — 490 —5F 5577 — 553 — 1113 — 2532 — 251 — 505 —5G 5640 — 575 — 1143 — 2561 — 261 — 519 —5H 5716 — 600 — 1176 — 2595 — 272 — 534 —5K 4993 — 673 — 1067 — 2267 — 306 — 484 —5L 5090 — 706 — 1118 — 2311 — 321 — 508 —5M 5165 — 742 — 1162 — 2345 — 337 — 528 —5P 5041 — 641 — 1111 — 2289 — 291 — 504 —5Q 5131 — 678 — 1155 — 2329 — 308 — 524 —5R 5214 — 709 — 1206 — 2367 — 322 — 548 —5T 5425 — 768 — 1162 — 2463 — 349 — 528 —5U 5534 — 801 — 1220 — 2512 — 364 — 554 —5V 5620 — 843 — 1270 — 2551 — 383 — 577 —5X 5484 — 730 — 1212 — 2490 — 331 — 550 —5Y 5584 — 769 — 1262 — 2535 — 349 — 573 —5Z 5678 — 805 — 1320 — 2578 — 365 — 599 —60 6719 6764 1091 479 1400 1521 3050 3071 495 217 636 69161 6895 6949 1150 479 1470 1597 3130 3155 522 217 667 72562 7038 7130 1202 479 1527 1671 3195 3237 546 217 693 75963 7103 7199 1202 479 1559 1704 3225 3268 546 217 708 77464 7161 7264 1178 479 1587 1735 3251 3298 535 217 720 78865 7392 6782 1241 542 1530 1667 3356 3079 563 246 695 75766 7594 7894 1309 542 1610 1753 3448 3584 594 246 731 79667 7759 8102 1369 542 1674 1838 3523 3678 622 246 760 83468 7836 8182 1359 542 1711 1875 3558 3715 617 246 777 85169 7905 8258 1332 542 1743 1911 3589 3749 605 246 791 868

Page 20: 19xr-7si

20

Table 6A — 19XR Heat Exchanger Data — Drive End Entering Cooler Water (cont)

*Rigging weights are for standard tubes of standard wall thickness (0.025-in. [0.635 mm] wall).NOTES:

1. Cooler includes the control panel (ICVC), suction elbow, and 1/2 the distribution piping weight.2. Condenser includes float valve and sump, discharge elbow, and 1/2 the distribution piping weight.3. For special tubes refer to the 19XR/XRV Computer Selection Program.4. All weights for standard 2-pass NIH (nozzle-in-head) design.

CODE

ENGLISH METRIC (SI)Dry Rigging Weight

(lb)* Machine Charge Dry Rigging Weight(kg)* Machine Charge

CoolerOnly

CondenserOnly

RefrigerantWeight (lb)

Water Weight(lb) Cooler

OnlyCondenser

Only

Refrigerant Weight (kg)

Water Weight(kg)

Cooler Condenser Cooler Condenser Cooler Condenser Cooler Condenser6K 5716 — 760 — 1291 — 2595 — 345 — 586 —6L 5804 — 797 — 1341 — 2635 — 362 — 609 —6M 5894 — 828 — 1399 — 2676 — 376 — 635 —6P 5768 — 725 — 1338 — 2619 — 329 — 607 —6Q 5852 — 764 — 1385 — 2657 — 347 — 629 —6R 5938 — 798 — 1439 — 2696 — 362 — 653 —6T 6230 — 863 — 1405 — 2828 — 392 — 638 —6U 6330 — 905 — 1462 — 2874 — 411 — 664 —6V 6433 — 941 — 1528 — 2921 — 427 — 694 —6X 6293 — 823 — 1459 — 2857 — 374 — 662 —6Y 6388 — 868 — 1512 — 2900 — 394 — 686 —6Z 6487 — 906 — 1574 — 2945 — 411 — 715 —70 9942 10786 1409 840 2008 2225 4514 4897 640 381 912 101071 10330 11211 1539 840 2164 2389 4690 5090 699 381 982 108572 10632 11622 1646 840 2286 2548 4827 5276 747 381 1038 115773 10715 11737 1622 840 2328 2604 4865 5329 736 381 1057 118274 10790 11775 1584 840 2366 2622 4899 5346 719 381 1074 119075 10840 11859 1599 950 2183 2431 4921 5384 726 431 991 110476 11289 12345 1747 950 2361 2619 5125 5605 793 431 1072 118977 11638 12814 1869 950 2501 2801 5284 5818 849 431 1135 127278 11738 12949 1849 950 2548 2864 5329 5879 839 431 1157 130079 11828 12994 1806 950 2592 2885 5370 5899 820 431 1177 13107K 8728 — 1047 — 1948 — 3963 — 475 — 884 —7L 8959 — 1132 — 2094 — 4067 — 514 — 951 —7M 9161 — 1214 — 2229 — 4159 — 551 — 1012 —7P 8792 — 1002 — 2010 — 3992 — 455 — 913 —7Q 9023 — 1087 — 2156 — 4096 — 493 — 979 —7R 9229 — 1167 — 2295 — 4190 — 530 — 1042 —7T 9431 — 1194 — 2115 — 4282 — 542 — 960 —7U 9698 — 1292 — 2282 — 4403 — 587 — 1036 —7V 9932 — 1403 — 2436 — 4509 — 637 — 1106 —7X 9510 — 1142 — 2185 — 4318 — 518 — 992 —7Y 9777 — 1240 — 2352 — 4439 — 563 — 1068 —7Z 10016 — 1347 — 2511 — 4547 — 612 — 1140 —80 12664 12753 1700 836 2726 2977 5749 5790 772 380 1238 135281 12998 13149 1812 836 2863 3143 5901 5970 823 380 1300 142782 13347 13545 1928 836 3005 3309 6060 6149 875 380 1364 150283 13437 13872 1877 836 3053 3476 6100 6298 852 380 1386 157884 13523 14217 1840 836 3099 3651 6139 6455 835 380 1407 165885 13804 14008 1927 945 2951 3238 6267 6360 875 429 1340 147086 14191 14465 2054 945 3108 3428 6443 6567 933 429 1411 155687 14597 14923 2186 945 3271 3618 6627 6775 992 429 1485 164388 14705 15311 2142 945 3325 3608 6676 6951 972 429 1510 163889 14808 15721 2099 945 3378 4009 6723 7137 953 429 1534 18208K 11153 — 1385 — 2760 — 5063 — 629 — 1253 —8L 11400 — 1484 — 2926 — 5176 — 674 — 1328 —8M 11650 — 1589 — 3088 — 5289 — 721 — 1402 —8P 11219 — 1334 — 2830 — 5093 — 606 — 1285 —8Q 11470 — 1430 — 2999 — 5207 — 649 — 1362 —8R 11719 — 1535 — 3161 — 5320 — 697 — 1435 —8T 12069 — 1580 — 2991 — 5479 — 717 — 1358 —8U 12357 — 1694 — 3180 — 5610 — 769 — 1444 —8V 12645 — 1814 — 3365 — 5741 — 824 — 1528 —8X 12152 — 1522 — 3070 — 5517 — 691 — 1394 —8Y 12444 — 1632 — 3264 — 5650 — 741 — 1482 —8Z 12733 — 1752 — 3448 — 5781 — 795 — 1565 —

Page 21: 19xr-7si

21

Table 6B — 19XR Heat Exchanger Data — Compressor End Entering Cooler Water

*Rigging weights are for standard tubes of standard wall thickness (0.025-in. [0.635 mm] wall).NOTES:

1. Cooler includes the control panel (ICVC), suction elbow, and 1/2 the distribution piping weight.2. Condenser includes float valve and sump, discharge elbow, and 1/2 the distribution piping weight.3. For special tubes refer to the 19XR/XRV Computer Selection Program.4. All weights for standard 2-pass NIH (nozzle-in-head) design.

CODE

ENGLISH METRIC (SI)Dry Rigging Weight

(lb)* Machine Charge Dry Rigging Weight(kg)* Machine Charge

CoolerOnly

CondenserOnly

RefrigerantWeight (lb)

Water Weight(lb) Cooler

OnlyCondenser

Only

Refrigerant Weight (kg)

Water Weight(kg)

Cooler Condenser Cooler Condenser Cooler Condenser Cooler Condenser10 2707 2704 290 200 283 348 1228 1227 132 91 128 15811 2777 2772 310 200 309 374 1260 1257 141 91 140 17012 2848 2857 330 200 335 407 1292 1296 150 91 152 18515 2968 2984 320 250 327 402 1346 1354 145 113 148 18216 3054 3068 340 250 359 435 1385 1392 154 113 163 19717 3141 3173 370 250 391 475 1425 1439 168 113 177 21520 3407 3373 345 225 402 398 1545 1530 156 102 182 18121 3555 3540 385 225 456 462 1613 1606 175 102 207 21022 3711 3704 435 225 514 526 1683 1680 197 102 233 23930 4071 3694 350 260 464 464 1847 1676 159 118 210 21031 4253 3899 420 260 531 543 1929 1769 191 118 241 24632 4445 4100 490 260 601 621 2016 1860 222 118 273 28235 4343 4606 400 310 511 513 1970 2089 181 141 232 23336 4551 4840 480 310 587 603 2064 2195 218 141 266 27437 4769 5069 550 310 667 692 2163 2299 249 141 303 31440 4908 5039 560 280 863 915 2226 2286 254 127 391 41541 5078 5232 630 280 930 995 2303 2373 286 127 422 45142 5226 5424 690 280 990 1074 2370 2460 313 127 449 48745 5363 5602 640 330 938 998 2433 2541 290 150 425 45346 5559 5824 720 330 1014 1088 2522 2642 327 150 460 49447 5730 6044 790 330 1083 1179 2599 2742 358 150 491 53550 5713 6090 750 400 1101 1225 2591 2762 340 181 499 55651 5940 6283 840 400 1192 1304 2694 2850 381 181 541 59152 6083 6464 900 400 1248 1379 2759 2932 408 181 566 62653 6141 6529 900 400 1277 1409 2788 2964 409 182 580 64054 6192 6591 900 400 1302 1439 2811 2992 409 182 591 65355 6257 6785 870 490 1201 1339 2838 3078 395 222 545 60756 6517 7007 940 490 1304 1429 2956 3178 426 222 591 64857 6682 7215 980 490 1369 1514 3031 3273 445 222 621 68758 6751 7291 980 490 1401 1550 3065 3310 445 222 636 70459 6811 7363 980 490 1430 1583 3092 3343 445 222 649 7195A 5124 — 500 — 1023 — 2324 — 227 — 464 —5B 5177 — 520 — 1050 — 2348 — 236 — 476 —5C 5243 — 550 — 1079 — 2378 — 249 — 489 —5F 5577 — 550 — 1113 — 2530 — 249 — 505 —5G 5640 — 570 — 1143 — 2558 — 259 — 518 —5H 5716 — 600 — 1176 — 2593 — 272 — 533 —5K 4993 — 673 — 1067 — 2267 — 306 — 484 —5L 5090 — 706 — 1118 — 2311 — 321 — 508 —5M 5165 — 742 — 1162 — 2345 — 337 — 528 —5P 5041 — 641 — 1111 — 2289 — 291 — 504 —5Q 5131 — 678 — 1155 — 2329 — 308 — 524 —5R 5214 — 709 — 1206 — 2367 — 322 — 548 —5T 5425 — 768 — 1162 — 2463 — 349 — 528 —5U 5534 — 801 — 1220 — 2512 — 364 — 554 —5V 5620 — 843 — 1270 — 2551 — 383 — 577 —5X 5484 — 730 — 1212 — 2490 — 331 — 550 —5Y 5584 — 769 — 1262 — 2535 — 349 — 573 —5Z 5678 — 805 — 1320 — 2578 — 365 — 599 —60 6719 6764 940 420 1400 1521 3048 3068 426 191 635 69061 6895 6949 980 420 1470 1597 3128 3152 445 191 667 72462 7038 7130 1020 420 1527 1671 3192 3234 463 191 693 75863 7103 7199 1020 420 1559 1714 3225 3268 463 191 708 77864 7161 7264 1020 420 1587 1735 3251 3298 463 191 720 78865 7392 7682 1020 510 1530 1667 3353 3484 463 231 694 75666 7594 7894 1060 510 1610 1753 3445 3581 481 231 730 79567 7759 8102 1090 510 1674 1838 3519 3675 494 231 759 83468 7836 8182 1090 510 1711 1875 3558 3715 495 232 777 85169 7905 8258 1090 510 1743 1911 3589 3749 495 232 791 868

Page 22: 19xr-7si

22

Table 6B — 19XR Heat Exchanger Data — Compressor End Entering Cooler Water (cont)

*Rigging weights are for standard tubes of standard wall thickness (0.025-in. [0.635 mm] wall).NOTES:

1. Cooler includes the control panel (ICVC), suction elbow, and 1/2 the distribution piping weight.2. Condenser includes float valve and sump, discharge elbow, and 1/2 the distribution piping weight.3. For special tubes refer to the 19XR/XRV Computer Selection Program.4. All weights for standard 2-pass NIH (nozzle-in-head) design.

CODE

ENGLISH METRIC (SI)Dry Rigging Weight

(lb)* Machine Charge Dry Rigging Weight(kg)* Machine Charge

CoolerOnly

CondenserOnly

RefrigerantWeight (lb)

Water Weight(lb) Cooler

OnlyCondenser

Only

Refrigerant Weight (kg)

Water Weight(kg)

Cooler Condenser Cooler Condenser Cooler Condenser Cooler Condenser6K 5716 — 760 — 1291 — 2595 — 345 — 586 —6L 5804 — 797 — 1341 — 2635 — 362 — 609 —6M 5894 — 828 — 1399 — 2676 — 376 — 635 —6P 5768 — 725 — 1338 — 2619 — 329 — 607 —6Q 5852 — 764 — 1385 — 2657 — 347 — 629 —6R 5938 — 798 — 1439 — 2696 — 362 — 653 —6T 6230 — 863 — 1405 — 2828 — 392 — 638 —6U 6330 — 905 — 1462 — 2874 — 411 — 664 —6V 6433 — 941 — 1528 — 2921 — 427 — 694 —6X 6293 — 823 — 1459 — 2857 — 374 — 662 —6Y 6388 — 868 — 1512 — 2900 — 394 — 686 —6Z 6487 — 906 — 1574 — 2945 — 411 — 715 —70 9942 10782 1220 780 2008 2223 4510 4891 553 354 911 100871 10330 11211 1340 780 2164 2389 4686 5085 608 354 982 108472 10632 11612 1440 780 2286 2544 4823 5267 653 354 1037 115473 10715 11737 1440 780 2328 2604 4865 5329 654 354 1057 118274 10790 11775 1440 780 2366 2622 4899 5346 654 354 1074 119075 10840 11854 1365 925 2183 2429 4917 5377 619 420 990 110276 11289 12345 1505 925 2361 2619 5121 5600 683 420 1071 118877 11638 12803 1625 925 2501 2796 5279 5807 737 420 1134 126878 11738 12949 1625 925 2548 2864 5329 5879 738 420 1157 130079 11828 12994 1625 925 2592 2885 5370 5899 738 420 1177 13107K 8728 — 1047 — 1948 — 3963 — 475 — 884 —7L 8959 — 1132 — 2094 — 4067 — 514 — 951 —7M 9161 — 1214 — 2229 — 4159 — 551 — 1012 —7P 8792 — 1002 — 2010 — 3992 — 455 — 913 —7Q 9023 — 1087 — 2156 — 4096 — 493 — 979 —7R 9229 — 1167 — 2295 — 4190 — 530 — 1042 —7T 9431 — 1194 — 2115 — 4282 — 542 — 960 —7U 9698 — 1292 — 2282 — 4403 — 587 — 1036 —7V 9932 — 1403 — 2436 — 4509 — 637 — 1106 —7X 9510 — 1142 — 2185 — 4318 — 518 — 992 —7Y 9777 — 1240 — 2352 — 4439 — 563 — 1068 —7Z 10016 — 1347 — 2511 — 4547 — 612 — 1140 —80 12664 12753 1500 720 2726 2977 5744 5785 680 327 1236 135081 12998 13149 1620 720 2863 3143 5896 5964 735 327 1299 142682 13347 13545 1730 720 3005 3309 6054 6144 785 327 1363 150183 13437 13872 1730 720 3053 3476 6100 6298 785 327 1386 157884 13523 14217 1730 720 3099 3651 6139 6455 785 327 1407 165885 13804 14008 1690 860 2951 3238 6261 6354 767 390 1339 146986 14191 14465 1820 860 3108 3428 6437 6561 826 390 1410 155587 14597 14923 1940 860 3271 3618 6621 6769 880 390 1484 164188 14705 15311 1940 860 3325 3808 6676 6951 881 390 1510 172989 14808 15721 1940 860 3378 4009 6723 7137 881 390 1534 18208K 11153 — 1385 — 2760 — 5063 — 629 — 1253 —8L 11400 — 1484 — 2926 — 5176 — 674 — 1328 —8M 11650 — 1589 — 3088 — 5289 — 721 — 1402 —8P 11219 — 1334 — 2830 — 5093 — 606 — 1285 —8Q 11470 — 1430 — 2999 — 5207 — 649 — 1362 —8R 11719 — 1535 — 3161 — 5320 — 697 — 1435 —8T 12069 — 1580 — 2991 — 5479 — 717 — 1358 —8U 12357 — 1694 — 3180 — 5610 — 769 — 1444 —8V 12645 — 1814 — 3365 — 5741 — 824 — 1528 —8X 12152 — 1522 — 3070 — 5517 — 691 — 1394 —8Y 12444 — 1632 — 3264 — 5650 — 741 — 1482 —8Z 12733 — 1752 — 3448 — 5781 — 795 — 1565 —

Page 23: 19xr-7si

23

Table 7 — 19XR Additional Data for Marine Waterboxes*

*Add to heat exchanger data for total weights or volumes.NOTE: For the total weight of a vessel with a marine waterbox, add these values to the heat exchanger weights (or volumes).

HEAT EXCHANGER FRAME, PASS

ENGLISH SI

psigRigging Weight (lb) Water Volume (gal)

kPaRigging Weight (kg) Water Volume (L)

Cooler Condenser Cooler Condenser Cooler Condenser Cooler CondenserFRAME 2, 1 AND 3 PASS

150

730 — 84 —

1034

331 — 318 —FRAME 2, 2 PASS 365 365 42 42 166 166 159 159FRAME 3, 1 AND 3 PASS 730 — 84 — 331 — 318 —FRAME 3, 2 PASS 365 365 42 42 166 166 159 159FRAME 4, 1 AND 3 PASS 1888 — 109 — 856 — 412 —FRAME 4, 2 PASS 944 989 54 54 428 449 205 205FRAME 5, 1 AND 3 PASS 2445 — 122 — 1109 — 462 —FRAME 5, 2 PASS 1223 1195 61 60 555 542 231 226FRAME 6, 1 AND 3 PASS 2860 — 139 — 1297 — 524 —FRAME 6, 2 PASS 1430 1443 69 69 649 655 262 262FRAME 7, 1 AND 3 PASS 3970 — 309 — 1801 — 1170 —FRAME 7, 2 PASS 1720 1561 155 123 780 708 585 465FRAME 8, 1 AND 3 PASS 5048 — 364 — 2290 — 1376 —FRAME 8, 2 PASS 2182 1751 182 141 990 794 688 532FRAME 2, 1 AND 3 PASS

300

860 — 84 —

2068

390 — 318 —FRAME 2, 2 PASS 430 430 42 42 195 195 159 159FRAME 3, 1 AND 3 PASS 860 — 84 — 390 — 318 —FRAME 3, 2 PASS 430 430 42 42 195 195 159 159FRAME 4, 1 AND 3 PASS 2162 — 109 — 981 — 412 —FRAME 4, 2 PASS 1552 1641 47 47 704 744 178 178FRAME 5, 1 AND 3 PASS 2655 — 122 — 1204 — 462 —FRAME 5, 2 PASS 1965 1909 53 50 891 866 199 190FRAME 6, 1 AND 3 PASS 3330 — 139 — 1510 — 524 —FRAME 6, 2 PASS 2425 2451 58 58 1100 1112 218 218FRAME 7, 1 AND 3 PASS 5294 — 309 — 2401 — 1170 —FRAME 7, 2 PASS 4140 4652 146 94 1878 2110 553 356FRAME 8, 1 AND 3 PASS 6222 — 364 — 2822 — 1376 —FRAME 8, 2 PASS 4952 4559 161 94 2246 2068 609 355

Page 24: 19xr-7si

24

Table 8A — 19XR Waterbox Cover Weights — English (lb)

LEGEND

NOTE: Weight for NIH 2-pass cover, 150 psig, is included in the heat exchanger weights shown in Tables 6A and 6B.

FRAMES 1, 2, AND 3 — COOLER

WATERBOX DESCRIPTIONFrame 1 Frame 2 Frame 3

Standard Nozzles Flanged Standard

Nozzles Flanged Standard Nozzles Flanged

NIH, 1 Pass Cover, 150 psig 177 204 320 350 320 350

NIH, 2 Pass Cover, 150 psig 185 218 320 350 320 350

NIH, 3 Pass Cover, 150 psig 180 196 310 340 310 340

NIH Plain End Cover, 150 psig 136 136 300 300 300 300

MWB End Cover, 150 psig — — 300 300 300 300

MWB Return Cover, 150 psig — — 243 243 243 243

NIH, 1 Pass Cover, 300 psig 248 301 411 486 411 486

NIH, 2 Pass Cover, 300 psig 255 324 411 518 411 518

NIH, 3 Pass Cover, 300 psig 253 288 433 468 433 468

NIH Plain End Cover, 300 psig 175 175 400 400 400 400

MWB End Cover, 300 psig — — 400 400 400 400

MWB Return Cover, 300 psig — — 445 445 445 445

FRAMES 1, 2, AND 3 — CONDENSER

WATERBOX DESCRIPTIONFrame 1 Frame 2 Frame 3

Standard Nozzles Flanged Standard

Nozzles Flanged Standard Nozzles Flanged

NIH, 1 Pass Cover, 150 psig 177 204 320 350 320 350

NIH, 2 Pass Cover, 150 psig 185 218 320 350 320 350

NIH, 3 Pass Cover, 150 psig 180 196 310 310 310 340

NIH Plain End Cover, 150 psig 136 136 300 300 300 300

MWB End Cover, 150 psig — — 300 300 300 300

MWB Return Cover, 150 psig — — 225 225 225 225

NIH, 1 Pass Cover, 300 psig 248 301 411 486 411 486

NIH, 2 Pass Cover, 300 psig 255 324 411 518 411 518

NIH, 3 Pass Cover, 300 psig 253 288 433 468 433 468

NIH Plain End Cover, 300 psig 175 175 400 400 400 400

MWB End Cover, 300 psig — — 400 400 400 400

MWB Return Cover, 300 psig — — 359 359 359 359

NIH — Nozzle-in-HeadMWB — Marine Waterbox

Page 25: 19xr-7si

25

Table 8A — 19XR Waterbox Cover Weights — English (lb) (cont)

LEGEND

NOTE: Weight for NIH 2-pass cover, 150 psig, is included in the heat exchanger weights shown in Tables 6A and 6B.

FRAMES 4, 5, AND 6 — COOLER

WATERBOX DESCRIPTION

Frame 4 Frame 5 Frame 6

Standard Nozzles Flanged Standard

Nozzles Flanged Standard Nozzles Flanged

NIH, 1 Pass Cover, 150 psig 148 185 168 229 187 223

NIH, 2 Pass Cover, 150 psig 202 256 224 298 257 330

NIH, 3 Pass Cover, 150 psig 473 489 629 655 817 843

NIH Plain End Cover, 150 psig 138 138 154 154 172 172

MWB End Cover, 150 psig 317 317 393 393 503 503

MWB Return Cover, 150 psig 138 138 154 154 172 172

NIH, 1 Pass Cover, 300 psig 593 668 764 839 959 1035

NIH, 2 Pass Cover, 300 psig 594 700 761 878 923 1074

NIH, 3 Pass Cover, 300 psig 621 656 795 838 980 1031

NIH/MWB End Cover, 300 psig 569 569 713 713 913 913

FRAMES 4, 5, AND 6 — CONDENSER

WATERBOX DESCRIPTIONFrame 4 Frame 5 Frame 6

Standard Nozzles Flanged Standard

Nozzles Flanged Standard Nozzles Flanged

NIH, 1 Pass Cover, 150 psig 148 185 168 229 187 223

NIH, 2 Pass Cover, 150 psig 202 256 224 298 257 330

NIH, 3 Pass Cover, 150 psig 473 489 629 655 817 843

NIH Plain End Cover, 150 psig 138 138 154 154 172 172

MWB End Cover, 150 psig 317 317 393 393 503 503

MWB Return Cover, 150 psig 138 138 154 154 172 172

NIH, 1 Pass Cover, 300 psig 593 668 764 839 959 1035

NIH, 2 Pass Cover, 300 psig 594 700 761 878 923 1074

NIH, 3 Pass Cover, 300 psig 621 656 795 838 980 1031

NIH/MWB End Cover, 300 psig 569 569 713 713 913 913

NIH — Nozzle-in-HeadMWB — Marine Waterbox

Page 26: 19xr-7si

26

Table 8A — 19XR Waterbox Cover Weights — English (lb) (cont)

LEGEND

NOTE: Weight for NIH 2-pass cover, 150 psig, is included in the heat exchanger weights shown in Tables 6A and 6B.

FRAMES 7 AND 8 — COOLER

WATERBOX DESCRIPTIONFRAME 7 FRAME 8

Standard Nozzles Flanged Standard Nozzles Flanged

NIH, 1 Pass Cover, 150 psig 329 441 417 494

NIH, 2 Pass Cover, 150 psig 426 541 531 685

NIH, 3 Pass Cover, 150 psig 1202 1239 1568 1625

NIH Plain End Cover, 150 psig 315 315 404 404

MWB End Cover, 150 psig 789 789 1339 1339

MWB Return Cover, 150 psig 315 315 404 404

NIH, 1 Pass Cover, 300 psig 1636 1801 2265 2529

NIH, 2 Pass Cover, 300 psig 1585 1825 2170 2499

NIH, 3 Pass Cover, 300 psig 1660 1741 2273 2436

NIH/MWB End Cover, 300 psig 1451 1451 1923 1923

FRAMES 7 AND 8 — CONDENSER

WATERBOX DESCRIPTIONFrame 7 Frame 8

StandardNozzles Flanged Standard

Nozzles Flanged

NIH, 1 Pass Cover, 150 psig 329 441 417 494

NIH, 2 Pass Cover, 150 psig 426 541 531 685

NIH, 3 Pass Cover, 150 psig 1113 1171 1438 1497

NIH Plain End Cover, 150 psig 315 315 404 404

MWB End Cover, 150 psig 703 703 898 898

Bolt On MWB End Cover, 150 psig 700 700 1307 1307

MWB Return Cover, 150 psig 315 315 404 404

NIH, 1 Pass Cover, 300 psig 1472 1633 1860 2015

NIH, 2 Pass Cover, 300 psig 1410 1644 1735 2044

NIH, 3 Pass Cover, 300 psig 1495 1613 1883 1995

NIH/MWB End Cover, 300 psig 1440 1440 1635 1635

NIH — Nozzle-in-HeadMWB — Marine Waterbox

Page 27: 19xr-7si

27

Table 8B — 19XR Waterbox Cover Weights — SI (kg)

LEGEND

NOTE: Weight for NIH 2-pass cover, 1034 kPa, is included in the heat exchanger weights shown in Tables 6A and 6B.

FRAMES 1, 2, AND 3 — COOLER

WATERBOX DESCRIPTIONFRAME 1 FRAME 2 FRAME 3

Standard Nozzles Flanged Standard

Nozzles Flanged Standard Nozzles Flanged

NIH, 1 Pass Cover, 1034 kPa 80 92 145 159 145 159

NIH, 2 Pass Cover, 1034 kPa 84 99 145 159 145 159

NIH, 3 Pass Cover, 1034 kPa 82 88 141 154 141 154

NIH Plain End Cover, 1034 kPa 61 62 136 136 136 136

MWB End Cover, 1034 kPa — — 136 136 136 136

MWB Return Cover, 1034 kPa — — 110 110 110 110

NIH, 1 Pass Cover, 2068 kPa 112 137 186 220 186 220

NIH, 2 Pass Cover, 2068 kPa 116 147 186 235 186 235

NIH, 3 Pass Cover, 2068 kPa 115 131 196 212 196 212

NIH Plain End Cover, 2068 kPa 79 79 181 181 181 181

MWB End Cover, 2068 kPa — — 181 181 181 181

MWB Return Cover, 2068 kPa — — 202 202 202 202

FRAMES 1, 2, AND 3 — CONDENSER

WATERBOX DESCRIPTIONFrame 1 Frame 2 Frame 3

Standard Nozzles Flanged Standard

Nozzles Flanged Standard Nozzles Flanged

NIH, 1 Pass Cover, 1034 kPa 80 92 145 159 145 159

NIH, 2 Pass Cover, 1034 kPa 84 99 145 159 145 159

NIH, 3 Pass Cover, 1034 kPa 82 88 141 154 141 154

NIH Plain End Cover, 1034 kPa 61 62 136 136 136 136

MWB End Cover, 1034 kPa — — 136 136 136 136

MWB Return Cover, 1034 kPa — — 102 102 102 102

NIH, 1 Pass Cover, 2068 kPa 112 137 186 220 186 220

NIH, 2 Pass Cover, 2068 kPa 116 147 186 235 186 235

NIH, 3 Pass Cover, 2068 kPa 115 131 196 212 196 212

NIH Plain End Cover, 2068 kPa 79 79 181 181 181 181

MWB End Cover, 2068 kPa — — 181 181 181 181

MWB Return Cover, 2068 kPa — — 163 163 163 163

NIH — Nozzle-in-HeadMWB — Marine Waterbox

Page 28: 19xr-7si

28

Table 8B — 19XR Waterbox Cover Weights — SI (kg) (cont)

LEGEND

NOTE: Weight for NIH 2-pass cover, 1034 kPa, is included in the heat exchanger weights shown in Tables 6A and 6B.

FRAMES 4, 5, AND 6 — COOLER

WATERBOX DESCRIPTIONFrame 4 Frame 5 Frame 6

Standard Nozzles Flanged Standard

Nozzles Flanged Standard Nozzles Flanged

NIH, 1 Pass Cover, 1034 kPa 67 84 76 104 85 101

NIH, 2 Pass Cover, 1034 kPa 92 116 102 135 117 150

NIH, 3 Pass Cover, 1034 kPa 215 222 285 297 371 382

NIH Plain End Cover, 1034 kPa 63 63 70 70 78 78

MWB End Cover, 1034 kPa 144 144 178 178 228 228

MWB Return Cover, 1034 kPa 63 63 70 70 78 78

NIH, 1 Pass Cover, 2068 kPa 269 303 347 381 435 479

NIH, 2 Pass Cover, 2068 kPa 269 318 345 393 419 487

NIH, 3 Pass Cover, 2068 kPa 282 298 361 376 495 468

NIH/MWB End Cover, 2068 kPa 258 258 323 298 414 414

FRAMES 4, 5, AND 6 — CONDENSER

WATERBOX DESCRIPTIONFrame 4 Frame 5 Frame 6

Standard Nozzles Flanged Standard

Nozzles Flanged Standard Nozzles Flanged

NIH, 1 Pass Cover, 1034 kPa 67 84 76 104 85 101

NIH, 2 Pass Cover, 1034 kPa 92 116 102 135 117 150

NIH, 3 Pass Cover, 1034 kPa 215 222 285 297 371 382

NIH Plain End Cover, 1034 kPa 63 63 70 70 78 78

MWB End Cover, 1034 kPa 144 144 178 178 228 228

MWB Return Cover, 1034 kPa 63 63 70 70 78 78

NIH, 1 Pass Cover, 2068 kPa 269 303 347 381 435 469

NIH, 2 Pass Cover, 2068 kPa 269 318 345 393 419 487

NIH, 3 Pass Cover, 2068 kPa 282 298 361 376 445 468

NIH/MWB End Cover, 2068 kPa 258 258 323 298 414 414

NIH — Nozzle-in-HeadMWB — Marine Waterbox

Page 29: 19xr-7si

29

Table 8B — 19XR Waterbox Cover Weights — SI (kg) (cont)

LEGEND NOTE: Weight for NIH 2-pass cover, 1034 kPa, is included in theheat exchanger weights shown in Tables 6A and 6B.

RIG MACHINE COMPONENTS — Refer to instructionsbelow, Fig. 8-11, and Carrier Certified Prints for machine com-ponent disassembly.

.

NOTE: If the cooler and condenser vessels must be separated,the heat exchangers should be kept level by placing a supportplate under the tube sheets. The support plate will also help tokeep the vessels level and aligned when the vessels are boltedback together.

NOTE: Wiring must also be disconnected. Label each wirebefore removal (see Carrier Certified Prints). In order to dis-connect the starter from the machine, remove wiring for the oilpump, oil heater, control wiring at the power panel, and themain motor leads at the starter lugs.

Remove all transducer and sensor wires at the sensor. Clipall wire ties necessary to pull heat exchangers apart.To Separate Cooler and Condenser:

1. Place a support plate under each tube sheet to keep eachvessel level (Fig. 8, Item 6).

2. Cut the refrigerant motor cooling line at the locationshown (Fig. 8, Item 7).

3. Disconnect the compressor discharge elbow at the com-pressor (Fig. 9, Item 6).

4. Cut the hot gas bypass line at the location shown (Fig. 8,Item 1).

5. Unbolt the cooler liquid feed line at the location shown(Fig. 8, Item 10).

6. Cover all openings.7. Disconnect all wires and cables that cross from the cooler

side of the machine to the condenser side, including:a. temperature sensor cable at the waterbox (Fig. 11,

Item 5)

FRAMES 7 AND 8 — COOLER

WATERBOX DESCRIPTION

Frame 7 Frame 8

StandardNozzles Flanged Standard

Nozzles Flanged

NIH, 1 Pass Cover, 1034 kPa 149 200 189 224

NIH, 2 Pass Cover, 1034 kPa 193 245 241 311

NIH, 3 Pass Cover, 1034 kPa 545 562 711 737

NIH Plain End Cover, 1034 kPa 143 143 183 183

MWB End Cover, 1034 kPa 358 358 607 607

MWB Return Cover, 1034 kPa 143 143 183 183

NIH, 1 Pass Cover, 2068 kPa 742 817 1027 1147

NIH, 2 Pass Cover, 2068 kPa 719 828 984 1134

NIH, 3 Pass Cover, 2068 kPa 753 790 1031 1105

NIH/MWB End Cover, 2068 kPa 658 658 872 872

FRAMES 7 AND 8 — CONDENSER

WATERBOX DESCRIPTIONFRAME 7 FRAME 8

StandardNozzles Flanged Standard

Nozzles Flanged

NIH, 1 Pass Cover, 1034 kPa 149 200 189 224

NIH, 2 Pass Cover, 1034 kPa 193 245 241 311

NIH, 3 Pass Cover, 1034 kPa 505 531 652 679

NIH Plain End Cover, 1034 kPa 143 143 183 183

MWB End Cover, 1034 kPa 319 319 407 407

Bolt On MWB End Cover, 1034 kPa 318 318 593 593

MWB Return Cover, 1034 kPa 143 143 183 183

NIH, 1 Pass Cover, 2068 kPa 668 741 844 914

NIH, 2 Pass Cover, 2068 kPa 640 746 787 927

NIH, 3 Pass Cover, 2068 kPa 678 732 859 905

NIH/MWB End Cover, 2068 kPa 653 653 742 742

NIH — Nozzle-in-HeadMWB — Marine Waterbox

IMPORTANT: Only a qualified service technician shouldperform this operation.

WARNING

Do not attempt to disconnect flanges while the machine isunder pressure. Failure to relieve pressure can result in per-sonal injury or damage to the unit.

CAUTION

Before rigging the compressor, disconnect all wires enter-ing the power panel.

Page 30: 19xr-7si

30

b. waterside transducer cables at the transducer(Fig. 11, Item 4)

c. condenser transducer cable at the transducer(Fig. 11, Item 7)

d. motor power wires at the starter (Fig. 8, Item 4)e. wires and cable housings at the power panel that

cross from the starter to the power panel (Fig. 9,Item 2).

8. Disconnect the rabbet-fit connectors on the tube sheets(Fig. 8, Item 5).

9. Rig the vessels apart.To Separate the Compressor from the Cooler:

1. Unbolt the compressor suction elbow at the cooler flange(Fig. 8, Item 2).

2. Cut the refrigerant motor cooling line at the locationshown (Fig. 8, Item 7).

3. Disconnect the motor refrigerant return line (Fig. 8,Item 8).

4. Disconnect the following:a. compressor oil sump temperature sensor cable

(Fig. 10, Item 4)b. bearing temperature sensor cable (Fig. 10, Item 2)c. motor temperature sensor cable (Fig. 10, Item 1)d. wires and cable housings that cross from the power

panel to the starter and control panel (Fig. 9,Item 2)

e. discharge temperature sensor cable (Fig. 10, Item6)

f. compressor oil sump pressure cable (Fig. 10,Item 3)

g. compressor oil discharge pressure cable (Fig. 10,Item 5)

h. guide vane actuator cable (Fig. 9, Item 1)i. diffuser actuator cable (Frame 5 compressor and

Frame 4 units with split ring diffuser) — split ringdiffuser not shown (Fig. 11, Item 2)

j. diffuser pressure cable (Frame 5 compressor andFrame 4 units with split ring diffuser) (Fig. 10,Item 8).

5. Disconnect the flared fitting for the oil reclaim line(Fig. 8, Item 3).

6. Unbolt the compressor discharge elbow (Fig. 9, Item 6).7. Cover all openings.8. Disconnect motor power cables at the starter lugs (Fig. 8,

Item 4).9. Unbolt the compressor mounting from the cooler (Fig. 8,

Item 9).To Rig Compressor:NOTE: The motor end of the 19XR compressor is heavy andwill tip backwards unless these directions are followed:

1. Cut two 4 in. x 6 in. wooden beams to the same length asthe compressor.

2. Drill holes into the beams and bolt them to the base of thecompressor.

Additional Notes1. Use silicon grease on new O-rings when refitting.2. Use gasket sealant on new gaskets when refitting.3. Cooler and condenser vessels may be rigged vertically.

Rigging should be fixed to all 4 corners of the tube sheet.

CONDENSER

COOLER

COMPRESSOR (SEE PAGE 10)

1 — Optional Hot Gas Bypass (Cut)2 — Compressor Suction Elbow (Unbolt)3 — Oil Reclaim Line (Unbolt)4 — Starter Connector (Unbolt)5 — Vessel Connectors (Unbolt)

6 — Tube Sheet7 — Refrigerant Motor Cooling Line (Cut)8 — Motor Drain (Unbolt)9 — Compressor Mounting (Unbolt)

10 — Cooler Liquid Feed Line (Unbolt)

Fig. 8 — Cooler, Side View

a19-2005

Page 31: 19xr-7si

31

1 — Guide Vane Actuator Cable2 — Power Panel3 — Communication Cable4 — Water Sensor Cables5 — Motor Winding Temperature Cable

6 — Compressor Discharge Elbow Joints7 — Condenser Pressure Cable8 — Cooler Pressure Connection9 — Water Sensor Cables

Fig. 9 — 19XR Chiller Top View

9

8

1 2 3

4

567

a19-1391ef

1 — Motor Temperature Sensor Cable2 — Bearing Temperature Sensor Cable

Connection (Inside Box)3 — Compressor Oil Sump Pressure Cable4 — Compressor Oil Sump Temperature

Sensor Cable

5 — Compressor Oil Discharge Pressure Cable6 — Discharge Temperature Sensor Cable7 — Guide Vane Actuator Cable8 — Diffuser Pressure and Actuator Cable

(Frame 5 Compressor Only, Optional for Frame 4)

Fig. 10 — Compressor Detail

a19-1390tf

Page 32: 19xr-7si

32

1 — Guide Vane Actuator Cables2 — Diffuser Actuator (Frame 5 Compressor, Frame 4 Optional)3 — Hot Gas Bypass Line (Optional)4 — Condenser Leaving Water Pressure Cable

(Optional for ICVC Units)5 — Condenser Leaving Water Temperature Cable6 — Condenser Entering Water Temperature Cable7 — Condenser Entering Water Pressure Cable

(Optional for ICVC Units)8 — Vessel Take-Apart Connectors

9 — Cooler Entering Water Temperature Cable10 — Cooler Entering Water Pressure Cable

(Optional for ICVC Units)11 — Cooler Leaving Water Temperature Cable12 — Cooler Leaving Water Pressure Cable

(Optional for ICVC Units)13 — Chiller Visual Controller (CVC) or International Chiller Visual

Controller (ICVC)14 — Guide Vane Actuator

Fig. 11 — Chiller End View

12

1 2

11

10

9 8

6

5

4

3

7

13

14

a19-1495ef

Page 33: 19xr-7si

33

Step 3 — Install Machine SupportsINSTALL STANDARD ISOLATION — Figures 12 and 13show the position of support plates and shear flex pads, whichtogether form the standard machine support system.

INSTALL ACCESSORY ISOLATION (if required) — Un-even floors or other considerations may dictate the use ofaccessory soleplates (supplied by Carrier for field installation)and leveling pads. Refer to Fig. 12 and 14.

Level machine by using jacking screws in isolation sole-plates. Use a level at least 24-in. (600 mm) long.

For adequate and long lasting machine support, propergrout selection and placement is essential. Carrier recommendsthat only pre-mixed, epoxy type, non-shrinking grout be usedfor machine installation. Follow manufacturer’s instructions inapplying grout.

1. Check machine location prints for required groutthickness.

2. Carefully wax jacking screws for easy removal fromgrout.

3. Grout must extend above the base of the soleplate andthere must be no voids in grout beneath the plates.

4. Allow grout to set and harden, per manufacturer’s in-structions, before starting machine.

5. Remove jacking screws from leveling pads after grouthas hardened.

IMPORTANT: Chiller housekeeping pad, anchor bolts, andattachment points that are designed by others must be inaccordance with all applicable national and local codes.

Fig. 12 — 19XR,XRV Machine Footprint

a19-1547tf

19XR,XRV HEAT EXCHANGER

SIZE

DIMENSIONS (ft-in.)

A B C D E F G

10-12 10- 71/4 4-101/4 0-1 0-35/8 1- 13/4 0-9 0-1/215-17 12-103/4 4-101/4 0-1 0-35/8 1- 13/4 0-9 0-1/220-22 10- 71/4 5- 41/4 0-1 0-35/8 1- 13/4 0-9 0-1/230-32 12-103/4 5- 41/4 0 0-35/8 1- 13/4 0-9 0-1/235-37 14- 71/4 5- 41/4 0 0-35/8 1- 1 3/4 0-9 0-1/240-42 12-103/4 6- 0 0-11/2 0-35/8 1- 13/4 0-9 0-1/245-57 14- 71/4 6- 0 0-11/2 0-35/8 1- 13/4 0-9 0-1/2

50-54, 5A-5C, 5K-5R 12-103/4 6- 51/2 0- 1/2 0-35/8 1- 13/4 0-9 0-1/255-59, 5F-5H, 5T-5Z 14- 71/4 6- 51/2 0- 1/2 0-35/8 1- 13/4 0-9 0-1/2

60-64, 6K-6R 12-103/4 6- 91/2 0- 1/2 0-35/8 1- 13/4 0-9 0-1/265-69, 6T-6Z 14- 71/4 6- 91/2 0- 1/2 0-35/8 1- 13/4 0-9 0-1/270-74, 7K-7R 15- 17/8 7-101/2 0- 1/4 0-615/16 1-10 1-4 0-3/475-79, 7T-7Z 17- 17/8 7-101/2 0- 1/4 0-615/16 1-10 1-4 0-3/480-84, 8K-8R 15- 17/8 8- 93/4 0- 15/16 0-615/16 1-10 1-4 0-1/16

85-89, 8T-8Z 17- 17/8 8- 93/4 0- 15/16 0-615/16 1-10 1-4 0-1/16

Page 34: 19xr-7si

34

INSTALL SPRING ISOLATION — Spring isolation maybe purchased as an accessory from Carrier for field installation.It may also be field supplied and installed. Spring isolators maybe placed directly under machine support plates or located un-der machine soleplates. See Fig. 15. Consult job data for spe-cific arrangement. Low profile spring isolation assemblies can

be field supplied to keep the machine at a convenient workingheight.

Obtain specific details on spring mounting and machineweight distribution from job data. Also, check job data formethods to support and isolate pipes that are attached to springisolated machines.

NOTES:1. Dimensions in ( ) are in millimeters.2. Isolation package includes 4 shear flex pads.

Fig. 13 — Standard Isolation

VIEW Y-Ya23-46tf

18.25 in.(463.6 mm)

21.25 in.(539.8 mm)

7 in.(177.8 mm)

10 in.(254 mm)

1.5 in.(38.1 mm)

1.5 in.(38.1 mm)

7/8-9UNC-4 HOLES FORJACKING SCREWS

25 in.(635 mm)

28 in.(711.2 mm)

14 in.(355.6 mm)

17 in.(431.8 mm)

1.5 in.(38.1 mm)

1.5 in.(38.1 mm)

7/8-9UNC-2B HOLES FORJACKING SCREWS

Fig. 14 — Accessory Isolation

LEGEND

NOTES:1. Dimensions in ( ) are in millimeters.2. Accessory (Carrier supplied, field installed) soleplate package includes 4 soleplates, 16 jacking screws and leveling pads.3. Jacking screws to be removed after grout has set.4. Thickness of grout will vary, depending on the amount necessary to level chiller. Use only pre-mixed non-shrinking grout, Masterflow 648

CP-Plus or Chemrex Embeco 636 Plus Grout, 1½ in. (38.1 mm) to 2¼ in. (57.2 mm) thick.

HRS — Hot Rolled Steel

VIEW X-X

ACCESSORY SOLEPLATE DETAIL

a19-1110tf

a19-2002

a19-2003

SOLEPLATE DIMENSIONSHEAT EXCHANGER FRAME SIZE

1 THROUGH 6

SOLEPLATE DIMENSIONSHEAT EXCHANGER FRAME SIZE

7 AND 8

Page 35: 19xr-7si

35

Step 4 — Connect PipingINSTALL WATER PIPING TO HEAT EXCHANGERS —Refer to Table 9 for nozzle sizes. Install piping using job data,piping drawings, and procedures outlined below. A typical pip-ing installation is shown in Fig. 16.

1. Offset pipe flanges to permit removal of waterbox coverfor maintenance and to provide clearance for pipecleaning. No flanges are necessary with marine waterboxoption; however, water piping should not cross in front ofthe waterbox or access will be blocked.

2. Provide openings in water piping for required pressuregages and thermometers. For thorough mixing and tem-perature stabilization, wells in the leaving water pipeshould extend inside pipe at least 2 in. (50 mm).

3. Install air vents at all high points in piping to remove airand prevent water hammer.

4. Install pipe hangers where needed. Make sure no weightor stress is placed on waterbox nozzles or flanges.

5. Water flow direction must be as specified in Fig. 17-20.NOTE: Entering water is always the lower of the 2 noz-zles. Leaving water is always the upper nozzle for cooleror condenser.

6. Install waterbox vent and drain piping in accordance withindividual job data. All connections are 3/4-in. FPT.

7. Install waterbox drain plugs in the unused waterboxdrains and vent openings.

8. Install optional pumpout system or pumpout system andstorage tank as shown in Fig. 21-24.

Fig. 15 — 19XR Accessory Spring Isolation (Shown with Accessory Soleplates)

NOTE: The accessory spring isolators are supplied by Carrier for installation in the field.

a19-1521tf

CAUTION

Factory-supplied insulation is not flammable but can bedamaged by welding sparks and open flame. Protect insu-lation with a wet canvas cover.

CAUTION

To prevent damage to sensors, remove chilled and con-denser water temperature sensors before welding connect-ing piping to water nozzles. Refer to Fig. 9. Replacesensors after welding is complete.

CAUTION

When flushing the water systems, isolate the chiller fromthe water circuits to prevent damage to the heat exchangertubes.

Fig. 16 — Typical Nozzle Piping

a19-1395tf

Page 36: 19xr-7si

36

NOZZLE-IN HEAD WATERBOXES

FRAMES 1, 2, AND 3

FRAMES 4, 5, AND 6

NOZZLE ARRANGEMENT CODES FOR ALL 19XR NOZZLE-IN-HEAD WATERBOXES

Fig. 17 — Piping Flow Data (NIH, Frames 1 Through 6)

*Refer to certified drawings.

PASSCOOLER WATERBOXES

In Out ArrangementCode*

18 5 A5 8 B

27 9 C4 6 D

37 6 E4 9 F

PASSCONDENSER WATERBOXES

In Out ArrangementCode*

111 2 P

2 11 Q

210 12 R

1 3 S

310 3 T

1 12 U

a19-1370tf

a19-1243tf

Page 37: 19xr-7si

37

CONDCOOLER

CLCL CL

CL CONDCOOLER

DRIVE END COMPRESSOR END

10

11 12 9

8

7 4

5

6 3 2

1

NOZZLE-IN HEAD WATERBOXES

FRAMES 7 AND 8

NOZZLE ARRANGEMENT CODES FOR ALL 19XR NOZZLE-IN-HEAD WATERBOXES

Fig. 18 — Piping Flow Data (NIH, Frames 7 and 8)*Refer to certified drawings.

PASSCOOLER WATERBOXES

In Out Arrangement Code*

18 5 A5 8 B

27 9 C4 6 D

37 6 E4 9 F

PASSCONDENSER WATERBOXES

In Out Arrangement Code*

111 2 P

2 11 Q

210 12 R

1 3 S

310 3 T

1 12 U

a19-1548ef

MARINE WATERBOXES

FRAMES 2 AND 3*

NOZZLE ARRANGEMENT CODES

PASSCOOLER WATERBOXES CONDENSER WATERBOXES

In Out Arrangement Code In Out Arrangement Code

18 5 A — — —

5 8 B — — —

27 9 C 10 12 R

4 6 D 1 3 S

37 6 E — — —

4 9 F — — —

Fig. 19 — Piping Flow Data (MWB, Frames 2 and 3)

*There is no Frame 1 marine waterbox.

a19-1245tf

Page 38: 19xr-7si

38

MARINE WATERBOXES

FRAMES 4, 5, AND 6

FRAMES 7 AND 8

Fig. 20 — Piping Flow Data (MWB, Frames 4 Through 8)

NOZZLE ARRANGEMENT CODES

PASSCOOLER WATERBOXES CONDENSER WATERBOXES

In Out ArrangementCode In Out Arrangement

Code

19 6 A — — —

6 9 B — — —

27 9 C 10 12 R

4 6 D 1 3 S

37 6 E — — —

4 9 F — — —

NOZZLE ARRANGEMENT CODES

PASSCOOLER WATERBOXES CONDENSER WATERBOXES

In Out ArrangementCode In Out Arrangement

Code

18 5 A — — —

5 8 B — — —

27 9 C 10 12 R

4 6 D 1 3 S

37 6 E — — —

4 9 F — — —

a19-1245tf

a19-1247tf

Page 39: 19xr-7si

39

Table 9 — 19XR Waterbox Nozzle Sizes

FRAMESIZE

PRESSUREpsig (kPa) PASS

NOMINAL PIPE SIZE (in.) ACTUAL PIPE ID (in.)Cooler Condenser Cooler Condenser

1 150/300(1034/2068)

1 8 8 7.981 7.9812 6 6 6.065 6.0653 6 6 6.065 6.065

2 150/300(1034/2068)

1 10 10 10.020 10.0202 8 8 7.981 7.9813 6 6 6.065 6.065

3 150/300(1034/2068)

1 10 10 10.020 10.0202 8 8 7.981 7.9813 6 6 6.065 6.065

4 150/300(1034/2068)

1 10 10 10.020 10.0202 8 8 7.981 7.9813 6 6 6.065 6.065

5 150/300(1034/2068)

1 10 10 10.020 10.0202 8 10 7.981 10.0203 6 8 6.065 7.981

6 150/300(1034/2068)

1 10 10 10.020 10.0202 10 10 10.020 10.0203 8 8 7.981 7.981

7

150(1034)

1 14 14 13.250 13.2502 12 12 12.000 12.0003 10 12 10.020 12.000

300(2068)

1 14 14 12.500 12.5002 12 12 11.376 11.7503 10 12 9.750 11.750

8

150(1034)

1 14 14 13.250 13.2502 14 14 13.250 13.2503 12 12 12.000 12.000

300(2068)

1 14 14 12.500 12.5002 14 14 12.500 12.5003 12 12 11.376 11.376

Page 40: 19xr-7si

40

LEVEL GAGE

0' - 5 1/2"[140mm]

PRESSURE GAGE

3/8" MALE FLARERELIEF VALVE CONN.

1/2" DIA. K.O.ELECTRICAL CONN.(PUMPOUT POWER)

1' - 7 "[483mm]

0' - 5 7/8 "[149mm]

(2) 1" NPT RELIEFVALVE OUTLET (SEE FIELDINSTALLATION NOTES)

0' - 9 "[229mm]TYPICAL

B

T

R

E

D

W

0'- 9 7/8" [249mm]

1" NPTLIQUID CONN. 0'- 9"

[229mm]TYPICAL

VAPOR

3/4" NPTPUMPOUT CONDENSERWATER INLET CONN.

1/2" MALE FLAREVAPOR CONN. 3/4" NPT

PUMPOUT CONDENSERWATER OUTLET CONN.

ELECTRICAL SERVICEACCESS SPACE20 3/4" X 8 3/4" X 4 1/2"(BOTH SIDES)

V

U

N

A

GM

J

K

L

F

1'-0 3/4" [324mm]

3/8" MALE FLARERELIEF VALVE CONN.

1/2" DIA. K.O.ELECTRICAL CONN.(PUMPOUT POWER)(FAR SIDE)

0'- 3 1/4" [83mm]0'- 10"

[254mm]

0'- 2 3/4" [70mm]

0'- 7 15/16" [202mm]

(FARSIDE)

C

P

S

H

DIMENSIONSENGLISH (ft-in.)

SI (mm)

TANKSIZE A B C D E F G H J K

0428 10- 5 9-10 4-41/4 2-43/4 1-23/8 3-11/4 6-43/16 3-113/8 3-47/8 2-99/16

0452 14-111/4 14- 41/2 4-81/4 2-81/2 1-41/4 3-41/2 7-21/4 4- 31/4 3-83/4 3-17/16

TANKSIZE L M N P R S T U V W

0428 3-45/8 0-31/2 4- 91/2 1-77/8 2-03/8 3-9 5-01/4 2-5 2-97/8 2-53/4

0452 3-81/2 0-33/8 6-115/8 1-83/4 2-05/8 4-1 5-01/2 2-51/4 2-101/8 2-6

TANKSIZE A B C D E F G H J K

0428 3175 2997 1327 730 365 946 1935 1203 1038 8520452 4553 4381 1429 826 413 1029 2191 1302 1137 951

TANKSIZE L M N P R S T U V W

0428 1032 89 1451 505 619 1143 1530 737 860 7560452 1130 86 2124 527 625 1225 1537 742 867 762

NOTES:

1. Denotes center of gravity.

2. Dimensions in [ ] are inmillimeters.

3. The weights and center ofgravity values given are for anempty storage tank.

4. For additional information onthe pumpout unit, see certifieddrawings.

5. Conduit knockout is locatedon the side of the control box.

6. 28 cubic ft storage tankweight: 2334 lb (1059 kg).

7. 52 cu ft storage tank weight:3414 lb (1549 kg).

Fig. 21 — Optional Pumpout Unit and Storage Tank

TOP VIEW

LEFT SIDE VIEW

FRONT VIEW

AVAILABLE CONDUITKNOCKOUT SIZES

TRADE SIZE QTY LOCATION

1/2 1 TOP3/4 1 BOTTOM1 1 MIDDLE

11/4 1 MIDDLE

a23-1541

a23-1542

a23-1543

Page 41: 19xr-7si

41

RATED DRY WEIGHT AND REFRIGERANT CAPACITY)

ENGLISH (lb) SI (kg)

TANKSIZE

TANK OD(in.)

DRYWEIGHT*

(lb)

MAXIMUM REFRIGERANT CAPACITY (lb) TANKSIZE

TANK OD(mm)

DRYWEIGHT*

(kg)

MAXIMUM REFRIGERANT CAPACITY (kg)

ANSI/ASHRAE 15 UL 1963 ANSI/ASHRAE 15 UL 19630428 24.00 2334 1860 1716 0428 610 1059 844 7780452 27.25 3414 3563 3286 0452 692 1549 1616 1491

LEGEND

*The above dry weight includes the pumpout condensing unit weight of 164 lb (75 kg).

ANSI — American National Standard InstituteASHRAE — American Society of Heating, Refrigerating, and Air Conditioning EngineersOD — Outside DiameterUL — Underwriters Laboratories

Fig. 21 — Optional Pumpout Unit and Storage Tank (cont)

STORAGETANK LIQUIDVALVE

OILSEPARATOR

PUMPOUTCONDENSERWATER SUPPLYAND RETURN

PUMPOUTCONDENSER

STORAGE TANKVAPOR VALVE

2 3

4 5

PRESSURERELIEF SAFETY VALVE

PUMPOUTCOMPRESSOR

TEE FORCHARGING

REFRIGERANTCHARGING VALVE

COOLERREFRIGERANTISOLATIONVALVE

LIQUID LINESERVICEVALVE

CHILLERCONDENSERVESSEL

CHILLERCOOLERVESSEL

6

7

11

1a

1b

SERVICE VALVE ONPUMPOUT UNIT

= SERVICE VALVE ONCHILLER (FIELDSUPPLIED)

=

= MAINTAIN AT LEAST 2 FT (610mm) CLEARANCE AROUNDSTORAGE TANK FOR SERVICE AND OPERATION WORK.

REFRIGERANTCHARGING VALVE

10

OILSEPARATOR

PUMPOUTCONDENSERWATER SUPPLYAND RETURN

PUMPOUTCONDENSER

2 3

4 5

PRESSURERELIEF SAFETY VALVE

PUMPOUTCOMPRESSOR

COOLERREFRIGERANTISOLATIONVALVE

REFRIGERANTCHARGING VALVE

CHILLERCONDENSERVESSEL

CHILLERCOOLERVESSEL

7

11

1a

1b

SERVICE VALVE ONPUMPOUT UNIT

= SERVICE VALVE ONCHILLER

=

LIQUID LINESERVICEVALVE

REFRIGERANTCHARGING VALVE

Fig. 22 — Optional Pumpout System Piping Schematic with Storage Tank

Fig. 23 — Optional Pumpout System Piping Schematic without Storage Tank

a19-1690

a19-1691

Page 42: 19xr-7si

42

INSTALL VENT PIPING TO RELIEF VALVES — The19XR, 19XRV chiller is factory equipped with relief valves onthe cooler and condenser shells. Refer to Fig. 25 and Tables 10and 11 for size and location of relief devices. Vent reliefdevices to the outdoors in accordance with ANSI/ASHRAE 15(latest edition) Safety Code for Mechanical Refrigeration andall other applicable codes.

1. If relief devices are manifolded, the cross-sectional areaof the relief pipe must at least equal the sum of the areasrequired for individual relief pipes.

2. Provide a pipe plug near outlet side of each relief devicefor leak testing. Provide pipe fittings that allow vent

piping to be disconnected periodically for inspection ofvalve mechanism.

3. Piping to relief devices must not apply stress to the de-vice. Adequately support piping. A length of flexible tub-ing or piping near the device is essential on spring-isolated machines.

4. Cover the outdoor vent with a rain cap and place a con-densation drain at the low point in the vent piping to pre-vent water build-up on the atmospheric side of the reliefdevice.

Step 5 — Make Electrical Connections — Fieldwiring must be installed in accordance with job wiring dia-grams and all applicable electrical codes.

Wiring diagrams in this publication (Fig. 26-35) are for ref-erence only and are not intended for use during actual installa-tion; follow job specific wiring diagrams.

CONNECT CONTROL INPUTS — Wiring may be speci-fied for a spare safety switch, and a remote start/stop contactcan be wired to the starter terminal strip. Additional spare sen-sors and Carrier Comfort Network modules may be specifiedas well. These are wired to the machine control panel as indi-cated in Fig. 26. The PIC II control panel optional wiring andpower panel component layout is shown in Fig. 27.

Table 10 — Relief Valve Locations

NOTE: All valves relieve at 185 psi (1275 kPa).

Table 11 — Cooler/Relief Valve Arrangement

DANGER

Refrigerant discharged into confined spaces can displaceoxygen and cause asphyxiation.

COMPRESSOR

OILSEPARATOR

CONDENSER LEAVINGWATER

ENTERINGWATER

VALVE5

VALVE4

VALVE2

CONTROLPANEL

FRAMEASSEMBLY

OILHEATER

VALVE3

OIL FILLFITTING

Fig. 24 — Pumpout Unit

a19-1546

CAUTION

Do not run 120-v wiring into the control cabinet. The con-trol cabinet should only be used for additional extra-lowvoltage wiring (50 v maximum). Damage to machine couldresult.

CAUTION

Do not attempt to start compressor or oil pump (even for arotation check) or apply test voltage of any kind whileeither chiller module is under dehydration vacuum. Motorinsulation breakdown and serious damage may result.

LOCATION FRAMESIZE

RELIEF VALVEOUTLET SIZE

QUANTITY OF RELIEF VALVES

With Discharge andCooler Inlet Isolation

Without Discharge

andCooler

Inlet Isolation

Cooler1, 2 1 NPT FEMALE CONNECTOR 1 23-6 11/4 NPT FEMALE CONNECTOR 1 27,8 11/4 NPT FEMALE CONNECTOR 2 4

Condenser1, 2 1 NPT FEMALE CONNECTOR 2 23-6 11/4 NPT FEMALE CONNECTOR 2 2

HEAT EXCHANGERFRAME SIZE

COMPRESSORFRAME SIZE ISOLATION VALVES COOLER ARRANGEMENT

SEE FIGURE NO.CONDENSER ARRANGEMENT

SEE FIGURE NO.

2 2Yes 25A 25ENo 25C 25E

3 2Yes 25A 25ENo 25C 25E

3, 4, 5 3Yes 25A 25ENo 25C 25E

5, 6 4Yes 25A 25ENo 25C 25E

7 4Yes 25B 25FNo 25D 25F

7, 8 5Yes 25B 25FNo 25D 25F

Page 43: 19xr-7si

43

COOLER

CONDENSER

COOLER

CONDENSER

Fig. 25 — Relief Valve Arrangements

WITH OPTIONAL ISOLATION OF DISCHARGE AND COOLER (Fig. A, B)

WITHOUT ISOLATION OPTION OF DISCHARGE AND COOLER (Fig. C, D)

FIG. A FIG. B

FIG. DFIG. C

CONDENSER RELIEF VALVE ARRANGEMENT — WITH OR WITHOUT OPTIONAL ISOLATION (Fig. E, F)

FIG. E FIG. F

FRAME 1-6 FRAMES 7, 8

FRAME 1-6 FRAME 7, 8

FRAME 1-6 FRAME 7, 8

a19-1497ef a19-1496ef

a19-1498ef a19-1499ef

a19-1500efa19-1501ef

Page 44: 19xr-7si

44

19X

R C

HIL

LER

S

LEG

EN

D1

—C

arrie

r C

omfo

rt N

etw

ork

(CC

N)

Inte

rfac

e2

—C

ircui

t Bre

aker

s3

—C

ontr

ol P

anel

Inte

rnal

Vie

w4

—C

hille

r C

ontr

ol M

odul

e (C

CM

)Fa

ctor

y W

iring

Fie

ld W

iring

NO

TE

: Fie

ld s

uppl

ied

term

inal

str

ip m

ust b

e lo

cate

d in

con

trol

pan

el.

Fig

. 26

— C

CN

Co

mm

un

icat

ion

Wir

ing

fo

r M

ult

iple

Ch

iller

s (T

ypic

al)

a19-1502tf

Page 45: 19xr-7si

45

CA

RR

IER

CO

MF

OR

T N

ET

WO

RK

(CC

N)

INT

ER

FAC

E

CH

ILLE

R D

ISP

LAY

(CV

C/IC

VC

)

Fig

. 27

— P

IC II

Co

ntr

ol P

anel

Op

tio

nal

Wir

ing

an

d P

ow

er P

anel

Co

mp

on

ent

Lay

ou

t

a19-1943

Page 46: 19xr-7si

46

CONNECT CONTROL OUTPUTS — Connect auxiliaryequipment, chilled and condenser water pumps, and sparealarms as required and indicated on job wiring drawings.CONNECT STARTER — The 19XR chiller is available witha unit-mounted, factory-installed starter or VFD (variable fre-quency drive) (Fig. 28-30) or a free-standing, field-installedstarter or VFD (Fig. 32-35).Unit-Mounted, Factory-Installed Starter or VFD — Attachpower leads by connecting them from inside the starter cabinetto the line side circuit breaker terminals. See Fig. 28-31.

Machines with electro-mechanical starters (wye-delta) willhave a top hat shipped with the machine if the RLA (rated loadamps) is greater than 935 amps. If the machine is equipped

with a solid-state starter, a top hat is provided if the RLAexceeds 740 amps. The top hat is shipped in the knocked-downposition and must be assembled and installed on top of thestarter cabinet, over the line side circuit breaker. Duringassembly, remove the access plate and use it as the cover pieceof the top hat. The top hat provides additional wire bendingspace to attach line side power leads to the circuit breakerwithin the starter.

IMPORTANT: Be sure to ground the power circuit inaccordance with the National Electrical Code (NEC),applicable local codes, and job wiring diagrams. Also,make sure correct phasing is observed for proper rotation.

3

7

8

LEGEND1 — Disconnect (Fused on VFD only) NOT by Carrier2 — Unit-Mounted Starter or VFD3 — Control Panel4 — Power Panel5 — Vents6 — Pressure Gages7 — Chilled Water Pump8 — Condenser Water Pump9 — Chilled Water Pump Starter

10 — Condensing Water Pump Starter11 — Cooling Tower Fan Starter

NOTES:1. All wiring must comply with applicable codes.2. Refer to Carrier System Design Manual for details regarding

piping techniques.3. Wiring not shown for optional devices such as:

• remote start-stop• remote alarm• optional safety device• 4 to 20 mA (1 to 5 VDC) resets• optional remote sensors• kW output• head pressure reference

IMPORTANT: Wiring and piping shown are for general point-of-connection only and are not intended to show details for aspecific installation. Certified field wiring and dimensional dia-grams are available on request.

PipingControl WiringPower Wiring

Fig. 28 — 19XR with Unit-Mounted Starter or VFD (LF1)

a19-1536ef

Page 47: 19xr-7si

47

LEGEND FOR FIG. 2919XR with Unit-Mounted Starter

See Notes on page 50.

REFERENCENUMBER EXPLANATION

1

3 Phase Under/Over VoltagePhase Loss/Imbalance/Reversal Motor Overload ProtectionFrequency ShiftkW Transducer/kW Hours/Demand kWSingle Cycle DropoutMotor/Starter OvercurrentControl Power Transformer (3KVA) (Integral)Controls and Oil Heater Circuit Breaker (integral)Oil Pump Circuit Breaker (Integral)4-20ma Head Pressure Reference Output3 Phase Analog Volts/Amps Meter PackagePower Factor Correction PackageLightning/Surge Arrestor PackagePhase to Phase to Ground Fault DetectionPhase to Ground Fault Detection

2 Compressor Motor Starter Branch DisconnectA Evaporator Liquid Pump Starter DisconnectB Evaporator Liquid Pump Motor StarterC Condenser Liquid Pump Starter DisconnectD Condenser Liquid Pump Motor StarterE Cooling Tower Fan Motor Starter Disconnect (Low Fan/#1)F Cooling Tower Fan Motor Starter (Low Fan/#1)G Cooling Tower Fan Motor Starter Disconnect (High Fan/#2)H Cooling Tower Fan Motor Starter (High Fan/#2)J Spare Safety Devices [N.C.] See Note 3.1 K Remote Start/Stop Device [N.O] See Note 3.1L Remote Alarm See Note 3.3M Remote Annunciator See Note 3.3N Lug Adapters See Note 2.1P Ice Build Start/Terminate Device See Note 3.1

Page 48: 19xr-7si

48

Fig. 29 — 19XR Typical Field Wiring with Unit-Mounted Starter

a19-2006NOTE: See Legend on page 48.

Page 49: 19xr-7si

49

Fig. 29 — 19XR Typical Field Wiring with Unit-Mounted Starter (cont)

a19-1504ef

Page 50: 19xr-7si

50

NOTES FOR FIG. 2919XR with Unit-Mounted Starter

I. GENERAL1.0 Starters shall be designed and manufactured in accordance

with Carrier Engineering Requirement Z-415.1.1 All field-supplied conductors, devices, and the field-

installation wiring, and termination of conductors anddevices, must be in compliance with all applicable codesand job specifications.

1.2 The routing of field-installed conduit and conductors andthe location of field-installed devices must not interfere withequipment access or the reading, adjusting, or servicing ofany component.

1.3 Equipment installation and all starting and control devices,must comply with details in equipment submittal drawingsand literature.

1.4 Contacts and switches are shown in the position they wouldassume with the circuit de-energized and the chiller shutdown.

1.5 WARNING — Do not use aluminum conductors.1.6 Installer is responsible for any damage caused by improper

wiring between starter and machine.II. POWER WIRING TO STARTER

2.0 Provide a means of disconnecting power to starter.2.1 Power conductor rating must meet minimum unit nameplate

voltage and compressor motor FLA (minimum circuitampacity).

2.2 Lug adapters may be required if installation conditions dic-tate that conductors be sized beyond the minimum ampac-ity required. Breaker lugs will accommodate the quantity (#)and size (MCM) cables (per phase) as indicated in tablesbelow.

2.3 Power conductors to starter must enter through top ofenclosure. Flexible conduit should be used for the last fewfeet to the enclosure to provide unit vibration isolation.

2.4 Compressor motor and controls must be grounded by usingequipment grounding lugs provided inside unit-mountedstarter enclosure.

2.5 Starters with “Rated Load Amps” (RLA) greater than 433Arequire the assembly and the installation of a “Top Hat”(located inside enclosure) to provide the required wirebending space for incoming power leads.

2.6 Metering current transformers (CTs), if present, have aninner diameter of 23/4 in. Caution should be taken whenselecting power wiring so that all power cables can passthrough the CTs.

III. CONTROL WIRING3.0 Field supplied control conductors to be at least 18 AWG or

larger.3.1 Ice build start/terminate device contacts, remote start/stop

device contacts and spare safety device contacts (devicesnot supplied by Carrier), must have 24 VAC rating. MAXcurrent is 60 mA, nominal current is 10 mA. Switches withgold plated bifurcated contacts are recommended.

3.2 Remove jumper wire between J2-1 and J2-2 before con-necting auxiliary safeties between these terminals.

3.3 Each integrated contact output can control loads (VA) forevaporator pump, condenser pump, tower fan low, tower fanhigh, and alarm annunciator devices rated 5 amps at 115VAC and up to 3 amps at 277 VAC.

Do not use control transformers in the control center as thepower source for external or field-supplied contactor coils,actuator motors or any other loads.

3.4 If one single speed fan is used, connect fan control leadsJ9-13 and -14, jumper ISM J9-13 to -11, and jumper J9-14to -12. This will allow the fan to be actuated by closure ofeither “low fan” or “high fan” ISM channel contact.

3.5 Do not route control wiring carrying 30 v or less within aconduit which has wires carrying 50 v or higher or alongside wires carrying 50 v or higher.

3.6 Control wiring between starter and power panel must be sepa-rate shielded cables with minimum rating of 600 v, 80 C.Ground shield at starter.

3.7 Spare 4-20 mA output signal is designed for controllers with anon-grounded 4-20 mA input signal and a maximum inputimpedance of 500 ohms.

3.8 Flow devices to confirm evaporator or condenser pump floware not required. However; if flow devices are used, wire asshown in diagram below. Remove jumper installed at theseterminals and wire in a 4.3 K resistor in its place. The flowdevice and resistor must be installed in parallel at these termi-nals such that the resistor provides a signal when the flowdevice is open.

CAUTION

To prevent damage to machine, do NOT punch holes or drill intothe top surface of the starter enclosure for field wiring. Knock-outs are provided on the side of the starter enclosure for fieldwiring connections.

ALLEN BRADLEY (WYE-DELTA)

StarterRLA

Lug Capacity (Per Phase)# Conductors Conductor Range

186-207A 1 3 AWG — 350 MCM208-296A 2 2/0 AWG — 250 MCM297-444A 2 250 — 350 MCM445-606A 2 1 AWG — 500 MCM607-888A 4 4/0 AWG — 500 MCM889-1316A 4 500 — 1000 MCM

BENSHAW (SOLID-STATE)

StarterRLA

Lug Capacity (Per Phase)

# Conductors Conductor Range FrameSize

95-200A 1 6 AWG — 350 MCM 2, 3201-480A 2 3/0 AWG — 500 MCM 2, 3481-640A 3 1/0 AWG — 500 MCM 2, 3641-739A 4 250 — 500 MCM 2, 3740-979A 5 6 AWG — 350 MCM 4, 5

980-1390A 2 3/0 AWG — 500 MCM 4, 5

BENSHAW (WYE-DELTA)

StarterRLA

Lug Capacity (Per Phase)Circuit Breaker or Terminal Block (Option)

# Conductors Conductor Range FrameSize

112-185A 1 6 AWG — 350 MCM 2, 3186-474A 2 3/0 AWG — 500 MCM 2, 3475-606A 3 1/0 AWG — 500 MCM 2, 3607-775A 4 250 — 500 MCM 4776-804A 4 250 — 500 MCM 4, 5

805-1138A 5 300 — 600 MCM 4, 51139-1151 5 300 — 600 MCM 4, 5

CUTLER-HAMMER (WYE-DELTA)

StarterRLA

Lug Capacity (Per Phase)# Conductors Conductor Range

112-185A 1 4 AWG — 350 MCM186-296A 2 2/0 AWG — 250 MCM297-444A 2 250 — 350 MCM445-606A 2 1 AWG — 500 MCM607-888A 4 4/0 AWG — 500 MCM889-1316A 4 500 — 1000 MCM

CAUTION

Control wiring for Carrier to start pumps and tower fan motorsand establish flows must be provided to assure machine protec-tion. If primary pump, tower fan, and flow control is by othermeans, also provide parallel means for control by Carrier. Fail-ure to do so could result in machine freeze-up or overpressure.

CCMJ3 (LOWER)

312

Page 51: 19xr-7si

51

LEGEND FOR FIG. 3019XR with Unit-Mounted LF1 VFD

See Notes on page 54.

REFERENCENUMBER EXPLANATION

1

3 Phase Under/Over Voltage (Line Side)Phase Loss/Imbalance/Reversal (Line Side)Frequency Shift (Line Side)kW Transducer/kW Hours/Demand kWOver CurrentControl Power Transformer (3KVA)Controls and Oil Heater Fused Disconnect (FU2)Oil Pump Circuit Fused Disconnect (FU1)Phase to Ground Fault Protection3 Phase Analog Volts/Amps Meter Package

1A Line Reactor (See Fig. 31)

1B Compressor VFD/Motor Branch Fused Disconnect or Equivalent Circuit Breaker (Required)

2 System Feeder (Short Circuit, Ground Fault and Protection)A Evaporator Liquid Pump Starter DisconnectB Evaporator Liquid Pump Motor StarterC Condenser Liquid Pump Starter DisconnectD Condenser Liquid Pump Motor StarterE Cooling Tower Fan Motor Starter Disconnect (Low Fan/#1)F Cooling Tower Fan Motor Starter (Low Fan/#1)G Cooling Tower Fan Motor Starter Disconnect (High Fan/#2)H Cooling Tower Fan Motor Starter (High Fan/#2)J Spare Safety Devices [N.C.] See Note 3.1 K Remote Start/Stop Device [N.O] See Note 3.1L Remote Alarm See Note 3.3M Remote Annunciator See Note 3.3N Lug Adapters See Note 2.3P Ice Build Start/Terminate Device See Note 3.1

Page 52: 19xr-7si

52

Fig. 30 — 19XR Typical Wiring with Unit-Mounted LF1 Variable Frequency Drive

a19-1948

NOTE: See Legend on page 52.

Page 53: 19xr-7si

53

Fig. 30 — 19XR Typical Wiring with Unit-Mounted LF1Variable Frequency Drive (cont)

a19-1714

Page 54: 19xr-7si

54

NOTES FOR FIG. 3019XR with Unit-Mounted LF1 VFD

I. GENERAL1.0 Variable Frequency Drive (VFD) Starters shall be designed

and manufactured in accordance with Carrier EngineeringRequirement Z-416.

1.1 All field-supplied conductors, devices, and the fieldinstallation wiring, and termination of conductors anddevices, must be in compliance with all applicable codesand job specifications.

1.2 The routing of field-installed conduit and conductors andthe location of field-installed devices must not interfere withequipment access or the reading, adjusting, or servicing ofany component.

1.3 Equipment installation and all starting and control devices,must comply with details in equipment submittal drawingsand literature.

1.4 Contacts and switches are shown in the position they wouldassume with the circuit de-energized and the chiller shutdown.

1.5 WARNING — Do not use aluminum conductors.1.6 Installer is responsible for any damage caused by improper

wiring between VFD and machine.1.7 All field-installed wiring is field-supplied.

II. POWER WIRING TO VFD2.0 Provide a local means of disconnecting power to VFD.

Provide short circuit protection for the chiller andinterconnecting wire at the branch feeder. The short circuitprotection shall be fused type or equivalent circuit breaker.

2.1 Metal conduit must be used for the power wires from VFD tobranch feeder.

2.2 Line side power conductor rating must meet the VFDnameplate voltage and chiller full load amps (minimum cir-cuit ampacity).

2.3 Lug adapters may be required if installation conditionsdictate that conductors be sized beyond the minimumampacity required. Disconnect lugs will accommodate thequantity (#) and size (MCM) cables (per phase) as indicatedin table below. If larger lugs are required, the lugs can bepurchased from Cutler-Hammer.

2.4 Compressor motor and controls must be grounded by usingequipment grounding lugs provided inside unit-mountedVFD enclosure.

2.5 Metering current transformers (CTs), if present, have aninner diameter of 23/4 in. Caution should be taken whenselecting power wiring so that all power cables can passthrough the CTs.

III. CONTROL WIRING3.0 Field supplied control conductors to be at least 18 AWG or

larger.3.1 Ice build start/terminate device contacts, remote start/stop

device contacts and spare safety device contacts (devicesnot supplied by Carrier), must have 24 VAC rating. MAXcurrent is 60 mA, nominal current is 10 mA. Switches withgold plated bifurcated contacts are recommended.

3.2 Remove jumper wire between J2-1 and J2-2 before con-necting auxiliary safeties between these terminals.

3.3 Each integrated contact output can control loads (VA) forevaporator pump, condenser pump, tower fan low, tower fanhigh, and alarm annunciator devices rated 5 amps at 115VAC and up to 3 amps at 277 VAC.

Do not use control transformers in the control center as thepower source for external or field-supplied contactor coils,actuator motors or any other loads.

3.4 Do not route control wiring carrying 30 v or less within aconduit which has wires carrying 50 v or higher or alongside wires carrying 50 v or higher.

3.5 Spare 4-20 mA output signal is designed for controllers with anon-grounded 4-20 mA input signal and a maximum inputimpedance of 500 ohms.

3.8 Flow devices to confirm evaporator or condenser pump floware not required. However; if flow devices are used, wire asshown in diagram below. Remove jumper installed at theseterminals and wire in a 4.3 K resistor in its place. The flowdevice and resistor must be installed in parallel at these termi-nals such that the resistor provides a signal when the flowdevice is open.

CAUTION

To prevent damage to machine, do NOT punch holes or drill intothe top surface of the VFD enclosure for field wiring. Knockoutsare provided on the side of the VFD enclosure for field wiringconnections.

Drive Frame

Incoming Connection Component

Incoming Cable Lug Size

Cutler-Hammer Lug Part No.

FactoryInstalled

0400(575 v)

Terminal Block (STD) (2) 4/0 — 500 MCM N/A YES

Circuit Breaker (2) 3/0 — 350 MCM TA602LDJKCW YES

(2) 400 — 500 MCM 3TA603LDKCW NO

0414

Terminal Block (STD) (2) 4/0 — 500 MCM N/A YES

Circuit Breaker (2) 3/0 — 350 MCM TA602LDJKCW YES

(2) 400 — 500 MCM 3TA603LDKCW NO

0500

Terminal Block (STD) (2) 4/0 — 500 MCM N/A YES

Circuit Breaker (2) 3/0 — 350 MCM TA602LDJKCW YES

(2) 400 — 500 MCM 3TA603LDKCW NO

0643

Terminal Block (STD) (4) 4/0 — 600 MCM N/A YES

Circuit Breaker

(3) 3/0 — 400 MCM TA1000NB1 YES

(4) 4/0 — 500 MCM TA1200NB1 NO

(3) 500 — 750 MCM TA1201NB1 NO

CAUTION

Control wiring for Carrier to start pumps and tower fan motorsand establish flows must be provided to assure machine protec-tion. If primary pump, tower fan, and flow control is by othermeans, also provide parallel means for control by Carrier. Fail-ure to do so could result in machine freeze-up or overpressure.

CCMJ3 (LOWER)

312

Page 55: 19xr-7si

55

Fig

. 31

— 1

9XR

V O

pti

on

al L

ine

Rea

cto

r P

hys

ical

Dim

ensi

on

s an

d F

ield

Wir

ing

fo

r U

nit

-Mo

un

ted

LF

1 V

FD

Ap

plic

atio

ns

a19-1512ef

Page 56: 19xr-7si

56

Free-Standing, Field-Installed Starter or VFD — Assembleand install compressor terminal box in desired orientation, andcut necessary conduit openings in conduit support plates. SeeFig. 32-35. Attach power leads to compressor terminals in ac-cordance with job wiring drawings, observing caution label interminal box. Use only copper conductors. The motor must begrounded in accordance with NEC (National Electrical Code),applicable local codes, and job wiring diagrams. Installer is re-sponsible for any damage caused by improper wiring betweenstarter and compressor motor.

Insulate Motor Terminals and Lead Wire Ends — Insulatecompressor motor terminals, lead wire ends, and electricalwires to prevent moisture condensation and electrical arcing.For low-voltage units (up to 600 v), obtain insulation materialfrom machine shipping package consisting of 3 rolls of insula-tion putty and one roll of vinyl tape.

1. Insulate each terminal by wrapping with one layer of in-sulation putty.

2. Overwrap putty with 4 layers of vinyl tape.High Voltage Units — High-voltage units require special ter-minal preparation. Follow local electrical codes for high-volt-age installation. Vinyl tape is not acceptable; a high voltageterminal method must be used.

IMPORTANT: Do not insulate terminals until wiringarrangement has been checked and approved by Carrierstart-up personnel. Also, make sure correct phasing is fol-lowed for proper motor rotation.

LEGEND1 — Disconnect2 — Free-Standing Compressor Motor Starter or VFD3 — Compressor Motor Terminal Box4 — Chiller Power Panel5 — Control Panel6 — Vents7 — Pressure Gages8 — Chilled Water Pump9 — Condenser Water Pump

10 — Chilled Water Pump Starter11 — Condensing Water Pump Starter12 — Cooling Tower Fan Starter13 — Disconnect14 — Oil Pump Disconnect (see Note 4)

NOTES:1. All wiring must comply with applicable codes.2. Refer to Carrier System Design Manual for details regarding

piping techniques.3. Wiring not shown for optional devices such as:

• remote start-stop• remote alarm• optional safety device• 4 to 20 mA (1-5 VDC) resets• optional remote sensors• kW output• head pressure reference

4. Oil pump disconnect may be located within the enclosure ofItem 2 — Free-Standing Compressor Motor Starter.

IMPORTANT: Wiring and piping shown are for general point-of-connection only and are not intended to show details for a spe-cific installation. Certified field wiring and dimensional diagramsare available on request.

PipingControl WiringPower Wiring

Fig. 32 — 19XR with Free-Standing Starter or VFD

a19-1535ef

Page 57: 19xr-7si

57

LEGEND FOR FIG. 3319XR with Free-Standing Starter (Low Voltage)

See Notes on page 60.

REFERENCENUMBER EXPLANATION

1

3 Phase Under/Over VoltagePhase Loss/Imbalance/ReversalMotor Overload ProtectionFrequency ShiftkW Transducer/kW Hours/Demand kWSingle Cycle DropoutMotor/Starter OvercurrentControl Power Transformer (3KVA) (Integral)Controls and Oil Heater Circuit Breaker (integral)Oil Pump Circuit Breaker3 Phase Analog Volts/Amps Meter PackagePower Factor Correction PackageLightning/Surge Arrestor PackageAuxiliary Run Status Contacts N.O./N.C.Run Indicating LightEmergency Stop SwitchPhase to Phase to Fault DetectionPhase to Ground Fault Detection

2 Compressor Motor Starter Branch DisconnectA Evaporator Liquid Pump Starter DisconnectB Evaporator Liquid Pump Motor StarterC Condenser Liquid Pump Starter DisconnectD Condenser Liquid Pump Motor StarterE Cooling Tower Fan Motor Starter Disconnect (Low Fan/#1)F Cooling Tower Fan Motor Starter (Low Fan/#1)G Cooling Tower Fan Motor Starter Disconnect (High Fan/#2)H Cooling Tower Fan Motor Starter (High Fan/#2)J Spare Safety Devices [N.C.] See Note 3.1 K Remote Start/Stop Device [N.O] See Note 3.1L Remote Alarm See Note 3.3M Remote Annunciator See Note 3.3N Lug Adapters See Note 2.1P Ice Build Start/Terminate Device See Note 3.1Q Lead Connectors See Note 4.0R 6 Lead to 3 Lead Jumpers See Note 4.0

Page 58: 19xr-7si

58

Fig. 33 — 19XR Typical Field Wiring with Free-Standing Starter (Low Voltage)

a19-2007NOTE: See Legend on page 58.

Page 59: 19xr-7si

59

Fig. 33 — 19XR Typical Field Wiring with Free-Standing Starter (Low Voltage) (cont)

a19-1506ef

(SEE NOTE 3.8)

Page 60: 19xr-7si

60

NOTES FOR FIG. 3319XR with Free-Standing Starter (Low Voltage)

I. GENERAL1.0 Starters shall be designed and manufactured in accordance

with Carrier Engineering Requirement Z-415.1.1 All field-supplied conductors, devices, and the field

installation wiring, termination of conductors and devices,must be in compliance with all applicable codes and jobspecifications.

1.2 The routing of field-installed conduit and conductors andthe location of field-installed devices must not interfere withequipment access or the reading, adjusting, or servicing ofany component.

1.3 Equipment installation and all starting and control devices,must comply with details in equipment submittal drawingsand literature.

1.4 Contacts and switches are shown in the position they wouldassume with the circuit de-energized and the chiller shut-down.

1.5 WARNING — Do not use aluminum conductors.1.6 Installer is responsible for any damage caused by improper

wiring between starter and machine.1.7 All field-installed wiring is field-supplied.

II. POWER WIRING TO STARTER2.0 Provide a means of disconnecting power to starter.2.1 Lug adapters may be required if installation conditions

dictate that conductors be sized beyond the minimumampacity required. Contact starter supplier for luginformation.

2.2 Compressor motor and controls must be grounded by usingequipment grounding lug provided inside starter enclosure.

III. CONTROL WIRING3.0 Field supplied control conductors to be at least 18 AWG or

larger.3.1 Ice build start/terminate device contacts, remote start/stop

device contacts and spare safety device contacts (devicesnot supplied by Carrier), must have 24 VAC rating. MAXcurrent is 60 mA, nominal current is 10 mA. Switches withgold plated bifurcated contacts are recommended.

3.2 Feed 24 VAC power to safety input terminals. ReferenceMX3 electrical drawings.

3.3 Each integrated contact output can control loads (VA) forevaporator pump, condenser pump, tower fan low, tower fanhigh, and alarm annunciator devices rated 5 amps at 115VAC and up to 3 amps at 277 VAC.

Do not use control transformers in the control center as thepower source for external or field-supplied contactor coils,actuator motors or any other loads.

3.4 Do not route control wiring carrying 30 v or less within aconduit which has wires carrying 50 v or higher or alongside wires carrying 50 v or higher.

3.5 Control wiring between starter and power panel must beseparate shielded cables with minimum rating 600 v, 80 C.Ground shield at starter.

3.6 If optional pumpout/oil pump circuit breaker is not suppliedwithin the starter enclosure, it must be located within sight ofmachine with wiring routed to suit.

3.7 When providing conductors for oil pump motor and oilheater power, refer to sizing data on label located on thechiller power panel, equipment submittal documentation orequipment product data catalog.

3.8 Spare 4-20 mA output signal is designed for controllers with anon-grounded 4-20 mA input signal and a maximum inputimpedance of 500 ohms.

IV. POWER WIRING BETWEEN FREE-STANDING STARTERAND COMPRESSOR MOTOR4.0 Low voltage (600 v or less) compressor motors have (6)

5/8 in. terminal studs (lead connectors not suppliedby Carrier). Either 3 or 6 conductors must be run betweencompressor motor and starter, depending on the size of theconductors or the type of motor starter employed. If only 3leads are utilized, jumper motor terminals as follows: 1 to 6,2 to 4, 3 to 5. Center to center distance between terminalsis 3-5/32 in. Compressor motor starter must have nameplatestamped as to conforming with Carrier Engineering require-ment “Z-415.”

4.1 Power conductor rating must meet minimum unit nameplatevoltage and compressor motor RLA. Refer to the labellocated on the side of the chiller control panel, equipmentsubmittal documentation or equipment product data catalogfor conductor sizing data. (Conductor as defined below maybe a single lead or multiple smaller ampacity leads in paral-lel for the purpose of carrying the equivalent or higher cur-rent of a single larger lead.)When (3) conductors are used:Minimum ampacity per conductor = 1.25 x compressor RLA When (6) conductors are used:Minimum ampacity per conductor = 0.721 x compressorRLA

4.2 When more than one conduit is used to run conductorsfrom starter to compressor motor terminal box, an equalnumber of leads from the following phases (conductor)must be installed in each conduit to prevent excessiveheating.Inside delta starters: 1, 3, or multiples of 3 conduits arerequired. (For example: conductors to motor terminals 1, 2,3, 4, 5 and 6 in a single conduit or conductors to motorterminals 1 and 4 in one conduit, conductors to motorterminals 2 and 5 in one conduit and conductors to motorterminals 3 and 6 in one conduit.)For all other starters: 1, 2, or multiples of 2 are required.(For example: conductors to motor terminals 1, 2, and 3 inone conduit, and conductors to motor terminals 4, 5, and 6in one conduit).

4.3 Compressor motor power conductors may enter terminalbox through top, left side or bottom left using holes cut bycontractor to suit conduit. Flexible conduit should be usedfor the last few feet to the terminal box for unit vibration iso-lation. Use of stress cones or 12 conductors larger than 500MCM may require an oversize (special) motor terminal box(not supplied by Carrier). Lead connections between 3-phase motors and their starters must not be insulated untilCarrier personnel have checked compressor and oil pumprotations.

4.4 Compressor motor frame to be grounded in accordancewith the National Electrical Code (NFPA-70) and applicablecodes. Means for grounding compressor motor is pressureconnector for #4 AWG to 500 MCM wire, supplied andlocated in the lower left side corner of the compressormotor terminal box.

4.5 Do not allow motor terminals to support weight of wirecables. Use cable supports and strain reliefs as required.

4.6 Use backup wrench when tightening lead connectors tomotor terminal studs. Torque to 45 lb-ft max.

CAUTION

To prevent damage to machine, do NOT punch holes or drill intothe top surface of the starter enclosure for field wiring. Knock-outs are provided on the side of the starter enclosure for fieldwiring connections.

CAUTION

Control wiring for Carrier to start pumps and tower fan motorsand establish flows must be provided to assure machine protec-tion. If primary pump, tower fan, and flow control is by othermeans, also provide parallel means for control by Carrier. Fail-ure to do so could result in machine freeze-up or overpressure.

Page 61: 19xr-7si

61

LEGEND FOR FIG. 3419XR with Free-Standing Starter (Medium Voltage)

See Notes on page 64.

REFERENCENUMBER EXPLANATION

1

3 Phase Under/Over VoltagePhase Loss/Imbalance/ReversalMotor Overload ProtectionFrequency ShiftkW Transducer/kW Hours/Demand kWSingle Cycle DropoutMotor/Starter OvercurrentControl Power Transformer (3KVA) (Integral)Controls and Oil Heater Circuit Breaker (integral)Oil Pump Circuit BreakerOil Pump Circuit Breaker with Transformer3 Phase Analog Volts/Amps Meter PackagePower Factor Correction PackageLightning/Surge Arrestor PackageAuxiliary Run Status Contacts N.O./N.C.Run Indicating LightEmergency Stop SwitchPhase to Ground Fault Detection

2 Compressor Motor Starter Branch DisconnectA Evaporator Liquid Pump Starter DisconnectB Evaporator Liquid Pump Motor StarterC Condenser Liquid Pump Starter DisconnectD Condenser Liquid Pump Motor StarterE Cooling Tower Fan Motor Starter Disconnect (Low Fan/#1)F Cooling Tower Fan Motor Starter (Low Fan/#1)G Cooling Tower Fan Motor Starter Disconnect (High/#2)H Cooling Tower Fan Motor Starter (High Fan/#2)J Spare Safety Devices [N.C.] See Note 3.1 K Remote Start/Stop Device [N.O] See Note 3.1L Remote Alarm See Note 3.3M Remote Annunciator See Note 3.3N Lug Adapters See Note 2.1P Ice Build Start/Terminate Device See Note 3.1Q Lead Connectors See Note 4.0R 6 Lead to 3 Lead Jumpers See Note 4.0

Page 62: 19xr-7si

62

Fig. 34 — 19XR Typical Field Wiring with Free-Standing Starter (Medium Voltage)

a19-2008NOTE: See Legend on page 62.

Page 63: 19xr-7si

63

Fig. 34 — 19XR Typical Field Wiring with Free-Standing Starter (Medium Voltage) (cont)

a19-1508ef

(SEE NOTE 3.8)

Page 64: 19xr-7si

64

NOTES FOR FIG. 3419XR with Free-Standing Starter (Medium Voltage)

I. GENERAL1.0 Starters shall be designed and manufactured in accordance

with Carrier Engineering Requirement Z-415.1.1 All field-supplied conductors, devices, and the field

installation wiring, termination of conductors and devices,must be in compliance with all applicable codes and jobspecifications.

1.2 The routing of field-installed conduit and conductors andthe location of field-installed devices must not interfere withequipment access or the reading, adjusting, or servicing ofany component.

1.3 Equipment installation and all starting and control devices,must comply with details in equipment submittal drawingsand literature.

1.4 Contacts and switches are shown in the position they wouldassume with the circuit de-energized and chiller shutdown.

1.5 WARNING — Do not use aluminum conductors.1.6 Installer is responsible for any damage caused by improper

wiring between starter and machine.1.7 All field-installed wiring is field-supplied.

II. POWER WIRING TO STARTER2.0 Provide a means of disconnecting power to starter.2.1 Lug adapters may be required if installation conditions dic-

tate that conductors be sized beyond the minimum ampac-ity required. Contact starter supplier for lug information.

2.2 Compressor motor and controls must be grounded by usingequipment grounding lug provided inside starter enclosure.

III. CONTROL WIRING3.0 Field supplied control conductors to be at least 18 AWG or

larger.3.1 Ice build start/terminate device contacts, remote start/stop

device contacts and spare safety device contacts (devicesnot supplied by Carrier), must have 24 VAC rating. MAXcurrent is 60 mA, nominal current is 10 mA. Switches withgold plated bifurcated contacts are recommended.

3.2 Remove jumper wire between J2-1 and J2-2 before con-necting auxiliary safeties between these terminals.

3.3 Each integrated contact output can control loads (VA) forevaporator pump, condenser pump, tower fan low, tower fanhigh, and alarm annunciator devices rated 5 amps at 115VAC and up to 3 amps at 277 VAC.

Do not use control transformers in the control center as thepower source for external or field-supplied contactor coils,actuator motors or any other loads.

3.4 Do not route control wiring carrying 30 v or less within aconduit which has wires carrying 50 v or higher or alongside wires carrying 50 v or higher.

3.5 Control wiring between starter and power panel must beseparate shielded cables with minimum rating 600 v, 80 C.Ground shield at starter.

3.6 If optional pumpout/oil pump circuit breaker is not suppliedwithin the starter enclosure, it must be located within sight ofmachine with wiring routed to suit.

3.7 When providing conductors for oil pump motor and oilheater power, refer to sizing data on label located on thechiller power panel, equipment submittal documentation orequipment product data catalog.

3.8 Spare 4-20 mA output signal is designed for controllers with anon-grounded 4-20 mA input signal and a maximum inputimpedance of 500 ohms.

IV. POWER WIRING BETWEEN FREE-STANDING STARTERAND COMPRESSOR MOTOR4.0 Medium voltage (over 600 volts) compressor motors have

(3) terminals. Connections are 9/16-in. threaded stud. Acompression lug with a single 9/16-in. diameter hole can beconnected directly to the stud or 3 adapters are supplied forconnecting a NEMA lug. Use suitable connectors and insu-lation for high voltage alternating current cable terminations(these items are not supplied by Carrier). Compressormotor starter must have nameplate stamped as to conform-ing with Carrier Engineering requirement “Z-415.”

4.1 Power conductor rating must meet minimum unit nameplatevoltage and compressor motor RLA. Refer to the labellocated on the side of the chiller control panel, equipmentsubmittal documentation or equipment product data catalogfor conductor sizing data. (Conductor as defined below maybe a single lead or multiple smaller ampacity leads in paral-lel for the purpose of carrying the equivalent or higher cur-rent of a single larger lead.)When (3) conductors are used:Minimum ampacity per conductor = 1.25 x compressor RLA

4.2 When more than one conduit is used to run conductorsfrom starter to compressor motor terminal box, an equalnumber of leads from each phase (conductor) must be ineach conduit to prevent excessive heating. (For example,conductors to motor terminals 1, 2, and 3 in one conduit,and those to 4, 5, and 6 in another).

4.4 Compressor motor power conductors may enter terminalbox through top, left side or bottom left using holes cut bycontractor to suit conduit. Flexible conduit should be usedfor the last few feet to the terminal box for unit vibration iso-lation. Use of stress cones may require an oversize (spe-cial) motor terminal box (not supplied by Carrier).

4.3 Compressor motor frame to be grounded in accordancewith the National Electrical Code (NFPA-70) and applicablecodes. Means for grounding compressor motor is a #4AWG to 500 MCM pressure connector, supplied andlocated in the lower left side corner of the compressormotor terminal box.

4.5 Do not allow motor terminals to support weight of wirecables. Use cable supports and strain reliefs as required.

4.6 Use backup wrench when tightening lead connectors tomotor terminal studs. Torque to 30-35 ft-lb max.

CAUTION

To prevent damage to machine, do NOT punch holes or drill intothe top surface of the starter enclosure for field wiring. Knock-outs are provided on the side of the starter enclosure for fieldwiring connections.

CAUTION

Control wiring for Carrier to start pumps and tower fan motorsand establish flows must be provided to assure machine protec-tion. If primary pump, tower fan, and flow control is by othermeans, also provide parallel means for control by Carrier. Fail-ure to do so could result in machine freeze-up or overpressure.

Page 65: 19xr-7si

65

LEGEND FOR FIG. 3519XR with Free-Standing VFD

See Notes on page 68.

REFERENCENUMBER EXPLANATION

1

3 Phase Under/Over VoltagePhase Loss/Imbalance/ReversalMotor Overload ProtectionFrequency ShiftkW Transducer/kW Hours/Demand kWSingle Cycle DropoutMotor/Starter OvercurrentControl Power Transformer (3KVA) (Integral)Controls and Oil Heater Circuit Breaker (integral)Oil Pump Circuit Breaker (Integral)Phase to Ground Fault Protection3 Phase Analog Volts/Amps Meter PackagePower Factor Correction PackageLightning/Surge Arrestor PackageLine Reactor (See Fig. 31)Passive Line Filter 12 Pulse Input SectionRun Indicating LightEmergency Stop Switch

2 Compressor Motor Starter Branch DisconnectA Evaporator Liquid Pump Starter DisconnectB Evaporator Liquid Pump Motor StarterC Condenser Liquid Pump Starter DisconnectD Condenser Liquid Pump Motor StarterE Cooling Tower Fan Motor Starter Disconnect (Low Fan/#1)F Cooling Tower Fan Motor Starter (Low Fan/#1)G Cooling Tower Fan Motor Starter Disconnect (High Fan/#2)H Cooling Tower Fan Motor Starter (High Fan/#2)J Spare Safety Devices [N.C.] See Note 3.1 K Remote Start/Stop Device [N.O] See Note 3.1L Remote Alarm See Note 3.3M Remote Annunciator See Note 3.3N Lug Adapters See Note 2.1P Ice Build Start/Terminate Device See Note 3.1Q Lead Connectors See Note 4.0R 6 Lead to 3 Lead Jumpers See Note 4.0

Page 66: 19xr-7si

66

Fig. 35 — 19XR Typical Field Wiring with Free-Standing VFD

a19-1949NOTE: See Legend on page 66.

Page 67: 19xr-7si

67

Fig. 35 — 19XR Typical Field Wiring with Free-Standing Starter VFD (cont)

a19-1508ef(SEE NOTE 3.8

Page 68: 19xr-7si

68

NOTES FOR FIG. 3519XR with Free-Standing VFD

I. GENERAL1.0 Variable Frequency Drive (VFD) shall be designed and

manufactured in accordance with Carrier EngineeringRequirement Z-416.

1.1 All field-supplied conductors, devices, and the field-installation wiring, termination of conductors and devices,must be in compliance with all applicable codes and jobspecifications.

1.2 The routing of field-installed conduit and conductors andthe location of field-installed devices must not interfere withequipment access or the reading, adjusting, or servicing ofany component.

1.3 Equipment installation and all starting and control devices,must comply with details in equipment submittal drawingsand literature.

1.4 Contacts and switches are shown in the position they wouldassume with the circuit de-energized and the chiller shutdown.

1.5 WARNING — Do not use aluminum conductors.1.6 Installer is responsible for any damage caused by improper

wiring between VFD and machine.1.7 All field-installed wiring is field-supplied.

II. POWER WIRING TO VFD2.0 Provide a local means of disconnecting power to VFD.2.1 Lug adapters may be required if installation conditions dic-

tate that conductors be sized beyond the minimum ampac-ity required. Refer to VFD dimensional drawings for luginformation.

2.2 Compressor motor and controls must be grounded by usingequipment grounding lugs provided inside VFD enclosure.

III. CONTROL WIRING3.0 Field supplied control conductors to be at least 18 AWG or

larger.3.1 Optional ice build start/terminate device contacts, optional

remote start/stop device contacts and optional spare safetydevice contacts, must have 24 VAC rating. MAX current is60 mA, nominal current is 10 mA. Switches with gold platedbifurcated contacts are recommended.

3.2 Remove jumper wire between J2-1 and J2-2 before con-necting auxiliary safeties between these terminals.

3.3 Each integrated contact output can control loads (VA) forevaporator pump, condenser pump, tower fan low, tower fanhigh, and alarm annunciator devices rated 5 amps at 115VAC and up to 3 amps at 277 VAC.

Do not use control transformers in the control center as thepower source for external or field-supplied contactor coils,actuator motors or any other loads.

3.4 Do not route control wiring carrying 30 v or less within aconduit which has wires carrying 50 v or higher or alongside wires carrying 50 v or higher.

3.5 Control wiring between VFD and power panel must be sep-arate shielded cables with minimum rating 600 v, 80 C.Ground shield at VFD.

3.6 If optional pumpout/oil pump circuit breaker is not suppliedwithin the starter enclosure, it must be located within sight ofmachine with wiring routed to suit.

3.7 When providing conductors for oil pump motor and oilheater power, refer to sizing data on label located on thechiller power panel, equipment submittal documentation orequipment product data catalog.

3.8 Spare 4-20 mA output signal is designed for controllers with anon-grounded 4-20 mA input signal and a maximum inputimpedance of 500 ohms.

IV. POWER WIRING BETWEEN FREE-STANDING VFD ANDCOMPRESSOR MOTOR4.0 Low voltage (600 v or less) compressor motors have (6)

5/8 in. terminal studs with 19XR frame 2 and 3 compressoror (6) 7/8 -in. terminal studs with 19XR frame 4 and 5 com-pressor (lead connectors not supplied by Carrier). Either 3or 6 leads must be run between compressor motor andVFD, depending on the size of the conductors or the type ofmotor starter employed. If only 3 leads are utilized, jumpermotor terminals as follows: 1 to 6, 2 to 4, 3 to 5. Center tocenter distance between frame 2 and 3 compressor termi-nals is 3-5/32 in. Center to center distance between frame 4and 5 compressor terminals is 4-13/16 in. Compressor motorVFD must have nameplate stamped as to conforming withCarrier Engineering requirement “Z-416.”

4.1 Power conductor rating must meet minimum unit nameplatevoltage and compressor motor RLA. Refer to the labellocated on the side of the chiller control panel, equipmentsubmittal documentation or equipment product data catalogfor conductor sizing data. (Conductor as defined below maybe a single lead or multiple smaller ampacity leads in paral-lel for the purpose of carrying the equivalent or higher cur-rent of a single larger lead.)When (3) conductors are used:Minimum ampacity per conductor = 1.25 x compressor RLA When (6) conductors are used:Minimum ampacity per conductor = 1.25 x compressorRLA / 2.

4.2 When more than one conduit is used to run conductorsfrom VFD to compressor motor terminal box, an equal num-ber of leads from each phase (conductor) must be in eachconduit to prevent excessive heating. (For example, con-ductors to motor terminals 1, 2, and 3 in one conduit, andconductors to motor terminals 4, 5, and 6 in another).

4.3 Compressor motor power conductors may enter terminalbox through top, left side or bottom left using holes cut bycontractor to suit conduit. Flexible conduit should be usedfor the last few feet to the terminal box for unit vibration iso-lation. Use of stress cones or 12 conductors larger than500 MCM may require an oversize (special) motor terminalbox (not supplied by Carrier). Lead connections between3-phase motors and VFD must not be insulated until Carrierpersonnel have checked compressor and oil pumprotations.

4.4 Compressor motor frame to be grounded in accordancewith the National Electrical Code (NFPA-70) and applicablecodes. Means for grounding compressor motor is a pres-sure connector for #4 AWG to wire, supplied and located inthe lower left side corner of the compressor motor terminalbox.

4.5 Do not allow motor terminals to support weight of wirecables. Use cable supports and strain reliefs as required.

4.6 Use backup wrench when tightening lead connectors tomotor terminal studs. Torque to 45 lb-ft max.

4.7 Do not exceed 100 ft. maximum power cable lengthbetween the VFD and motor terminals without consultingCarrier for special requirements.

CAUTION

To prevent damage to machine, do NOT punch holes or drill intothe top surface of the VFD enclosure for field wiring. Knockoutsare provided on the side of the VFD enclosure for field wiringconnections.

CAUTION

Control wiring for Carrier to start pumps and tower fan motorsand establish flows must be provided to assure machine protec-tion. If primary pump, tower fan, and flow control is by othermeans, also provide parallel means for control by Carrier. Fail-ure to do so could result in machine freeze-up or overpressure.

Page 69: 19xr-7si

69

Connect Power Wires to Oil Pump Starter — See Fig. 36.Connect power wires to oil pump starter mounted in machinepower panel. Use separate fused disconnect or circuit breakeras shown on job wiring diagrams and Fig. 36. Check thatpower supply voltage agrees with oil pump voltage. Followcorrect phasing for proper motor rotation.

Connect Power Wires to Oil Heater Contactor — Connectcontrol power wiring between the oil heater contactor termi-nals and terminals LL1 and LL2 on the field wiring strip in thecompressor motor starter. Refer to Fig. 37 and wiring label onthe machine power panel for units without split ring diffuser.Refer to Fig. 38 for units with split ring diffuser.

Connect Wiring from Starter to Power Panel — Connect con-trol wiring from main motor starter to the machine powerpanel. All control wiring must use shielded cable. Also, con-nect the communications cable. Refer to the job wiring dia-grams for cable type and cable number. Make sure the controlcircuit is grounded in accordance with applicable electricalcodes and instructions on machine control wiring label.CARRIER COMFORT NETWORK INTERFACE — TheCarrier Comfort Network® (CCN) communication bus wiringis supplied and installed by the electrical contractor. It consistsof shielded, 3-conductor cable with drain wire.

The system elements are connected to the communicationbus in a daisy chain arrangement. The positive pin of each sys-tem element communication connector must be wired to thepositive pins of the system element on either side of it. Thenegative pins must be wired to the negative pins. The signalground pins must be wired to the signal ground pins. SeeFig. 26 for location of the CCN network connections on the ter-minal strip labelled CCN.NOTE: Conductors and drain wire must be 20 AWG (Ameri-can Wire Gage) minimum stranded, tinned copper. Individualconductors must be insulated with PVC, PVC/nylon, vinyl,Teflon, or polyethylene. An aluminum/polyester 100% foilshield and an outer jacket of PVC, PVC/nylon, chrome vinyl,or Teflon with a minimum operating temperature range of –4 Fto 140 F (–20 C to 60 C) is required. See table below for cablesthat meet the requirements.

When connecting the CCN communication bus to a systemelement, a color code system for the entire network is recom-mended to simplify installation and checkout. The followingcolor code is recommended:

If a cable with a different color scheme is selected, a similarcolor code should be adopted for the entire network.

CAUTION

Do not punch holes or drill into the top surface of eitherpower panel. Knockouts are provided in the bottom of thepower panels for wiring connections. Damage to machinecould result.

WARNING

Voltage to terminals LL1 and LL2 (of each circuit) comesfrom a control transformer in a starter built to Carrier speci-fications. Do not connect an outside source of controlpower to the compressor motor starter (terminals LL1 andLL2 of each circuit). An outside power source will producedangerous voltage at the line side of the starter, becausesupplying voltage at the transformer secondary terminalsproduces input level voltage at the transformer primary ter-minals. Severe injury could result.

LEGEND

Factory Wiring

Field Wiring

Oil Pump Terminal

Power Panel Component Terminal

Fig. 36 — Oil Pump Wiring

a19-638tf

LEGEND

Field Wiring

Power Panel Component Terminal

Fig. 37 — Oil Heater and Control Power Wiring (Units without Split Ring Diffuser)

a19-1311tf

MANUFACTURER CABLE NO.Alpha 2413 or 5463

American A22503Belden 8772

Columbia 02525

SIGNAL TYPE

CCN BUS CONDUCTORINSULATION

COLOR

CCN NETWORKINTERFACE

(Control Panel)

+ Red +Ground White G

– Black –

(WHT)

(WHT)

(BLK)(BLK)

(BLK)(WHT)(BLK)

COMPRESSOR OIL HEATERWIRING FOR 346V, 400V, 416V,460V, 480V, & 575V OIL PUMP

COMPRESSOR OIL HEATERWIRING FOR 200V & 230V

OIL PUMP

22 21

2C 1C

TO TB-G**

(BLK)

(WHT)

(WHT)

(WHT)

(BLK)21

11

1C

2C(BLK)

11

2C

21

LEGEND

Field Wiring

Power Panel Component Terminal

Fig. 38 — Oil Heater and Control Power Wiring (Units with Split Ring Diffuser)

a19-1527ef

Page 70: 19xr-7si

70

At each system element, the shields of its communicationbus cables must be tied together. If the communication bus isentirely within one building, the resulting continuous shieldmust be connected to ground at only one single point. SeeFig. 26. If the communication bus cable exits from one build-ing and enters another, the shields must be connected to groundat the lightening suppressor in each building where the cableenters or exits the building (one point only).

To connect the 19XR chiller to the network, proceed as fol-lows (see Fig. 26):

1. Route wire through knockout in back of control panel.2. Strip back leads.3. Crimp one no. 8 size spring spade terminal on each

conductor.4. Attach red to “+” terminal and white to “G” terminal and

black to “–” terminal of CCN Network interface locatedin the control panel.

OPTIONAL UPC OPEN CONTROLLER WIRING — Theoptional UPC Open controller communicates using BACnet*on an MS/TP network segment communications at 9600 bps,19.2 kbps, 38.4 kbps, or 76.8 kbps.

Wire the controllers on an MS/TP network segment in a dai-sy-chain configuration. Wire specifications for the cable are22 AWG (American Wire Gage) or 24 AWG, low-capacitance,twisted, stranded, shielded copper wire. The maximum lengthis 2000 ft.

Install a BT485 terminator on the first and last controller ona network segment to add bias and prevent signal distortionsdue to echoing. See Fig. 39-41.

To wire the UPC Open controller to the BAS network:1. Pull the screw terminal connector from the controller's

BAS Port.2. Check the communications wiring for shorts and

grounds.3. Connect the communications wiring to the BAS port’s

screw terminals labeled Net +, Net -, and Shield.NOTE: Use the same polarity throughout the networksegment.

4. Insert the power screw terminal connector into the UPCOpen controller's power terminals if they are not current-ly connected.

5. Verify communication with the network by viewing amodule status report. To perform a module status reportusing the BACview keypad/display unit, press and holdthe “FN” key then press the “.” Key.

To install a BT485 terminator, push the BT485, on to theBT485 connector located near the BACnet connector.NOTE: The BT485 terminator has no associated polarity.

To order a BT485 terminator, consult Commercial Productsi-Vu® Open Control System Master Prices.MS/TP Wiring Recommendations — Recommendations areshown in Tables 12 and 13. The wire jacket and UL tempera-ture rating specifications list two acceptable alternatives. TheHalar specification has a higher temperature rating and atougher outer jacket than the SmokeGard specification, and it isappropriate for use in applications where the user is concernedabout abrasion. The Halar jacket is also less likely to crack inextremely low temperatures. NOTE: Use the specified type of wire and cable for maximumsignal integrity.

Fig. 39 — UPC Open Controller

876

54 321

09

876

54 321

09

BACNETBAUD RATEDIP SWITCHES

ADDRESSROTARYSWITCHES

POWER LED

RUN LED

ERROR LED

BACNETCONNECTION(BAS PORT)

BT485TERMINATOR

Tx2 LED

Rx2 LED

Tx1 LED

Rx1 LED

EIA-485JUMPERS

* Sponsored by ASHRAE (American Society of Heating,Refrigerating and Air-Conditioning Engineers).

Page 71: 19xr-7si

71

Fig. 40 — Network Wiring

Fig. 41 — BT485 Terminator Installation

Page 72: 19xr-7si

72

Table 12 — MS/TP Wiring Recommendations

LEGEND

Table 13 — Open System Wiring Specifications and Recommended Vendors

LEGEND

SPECIFICATION RECOMMENDATIONCable Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable

Conductor 22 or 24 AWG stranded copper (tin plated) Insulation Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.

Color Code Black/White Twist Lay 2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal Shielding Aluminum/Mylar shield with 24 AWG TC drain wire

Jacket SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D. Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.

DC Resistance 15.2 Ohms/1000 feet (50 Ohms/km) nominal Capacitance 12.5 pF/ft (41 pF/meter) nominal conductor to conductor

Characteristic Impedance 100 Ohms nominal Weight 12 lb/1000 feet (17.9 kg/km)

UL Temperature Rating SmokeGard 167°F (75°C) Halar -40 to 302°F (-40 to 150°C)

Voltage 300 Vac, power limited Listing UL: NEC CL2P, or better

AWG — American Wire GageCL2P — Class 2 Plenum CableDC — Direct CurrentFEP — Fluorinated Ethylene PolymerNEC — National Electrical CodeO.D. — Outside DiameterTC — Tinned CopperUL — Underwriters Laboratories

WIRING SPECIFICATIONS RECOMMENDED VENDORS AND PART NUMBERS

Wire Type Description Connect AirInternational Belden RMCORP Contractors

Wire and Cable

MS/TPNetwork (RS-485)

22 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam FEP, plenum rated. See MS/TP Installation Guide for specifications.

W221P-22227 — 25160PV CLP0520LC

24 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam FEP, plenum rated. See MS/TP Installation Guidefor specifications.

W241P-2000F 82841 25120-OR —

Rnet 4 conductor, unshielded, CMP, 18 AWG, plenum rated. W184C-2099BLB 6302UE 21450 CLP0442

AWG — American Wire GageCL2P — Class 2 Plenum CableCMP — Communications Plenum RatedFEP — Fluorinated Ethylene PolymerTC — Tinned Copper

Page 73: 19xr-7si

73

Step 6 — Install Field Insulation

When installing insulation at the jobsite, insulate the follow-ing components:• compressor motor

• cooler shell• cooler tube sheets• suction piping• motor cooling drain • oil reclaim piping• oil cooler refrigerant side tubing• refrigerant liquid line to coolerNOTE: Insulation of the waterbox covers is applied only at thejobsite by the contractor. When insulating the covers, makesure there is access for removal of waterbox covers for servic-ing. See Fig. 42.

CAUTION

Protect insulation from weld heat damage and weld splat-ter. Cover with wet canvas cover during water pipinginstallation.

Fig. 42 — 19XR Insulation Area

a19-1393ef

a19-1374ef

Page 74: 19xr-7si

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Catalog No. 04-53190008-01 Printed in U.S.A. Form 19XR-7SI Pg 74 1012 12-11 Replaces: 19XR-5SI

Copyright 2011 Carrier Corporation

Page 75: 19xr-7si

CL-1

INSTALLATION START-UP REQUEST CHECKLIST

Machine Model Number: 19XR Serial Number:

To:

Attn:

Date

Project Name

Carrier Job Number

The following information provides the status of the chiller installation.

YES/NO DATE TO BE(N/A) COMPLETED

1. The machine is level.2. The machine components are installed and connected in

accordance with the installation instructions.3. The isolation package and grouting (if necessary)

are installed.4. The relief valves are piped to the atmosphere.5. All piping is installed and supported. Direction of flow

is indicated in accordance with the installation instructionsand job prints.a. Chilled water pipingb. Condenser water pipingc. Waterbox drain pipingd. Pumpout unit condenser piping (if installed)e. Other

6. Gages are installed as called for on the job prints requiredto establish design flow for the cooler and condenser.a. Water pressure gages IN and OUTb. Water temperature gages IN and OUT

7. The machine’s starter wiring is complete. The wiring isinstalled per installation instructions and certified prints.a. Power wiring to compressor motor. (Motor leads will

not be taped until the Carrier technician megger teststhe motor.)

b. Oil pump wiringc. Oil heater/control wiringd. Carrier controls can independently energize water

pumps and tower fan.e. Line side voltage is within ±10% of chiller nameplate

voltage.f. Other

8. The motor starter has not been supplied by Carrier. Ithas been installed according to the manufacturer’sinstructions.

9. The motor starter has not been supplied by Carrier and ithas been checked for proper operation.

Page 76: 19xr-7si

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Catalog No. 04-53190008-01 Printed in U.S.A. Form 19XR-7SI Pg CL-2 1012 12-11 Replaces: 19XR-5SI

Copyright 2011 Carrier Corporation

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- --

- -

- -

- -

- -

- -

- -

- -

- -

- -

-

CU

T A

LON

G D

OT

TE

D L

INE

CU

T A

LON

G D

OT

TE

D L

INE

COMMENTS:

TESTING YES/NO DATE TO BECOMPLETED

1. The cooling tower fan has been checked for blade pitch andproper operation.

2. The chilled water and condenser water lines have been:a. Filledb. Testedc. Flushedd. Ventede. Strainers cleaned

3. The chilled water and condenser water pumps have beenchecked for proper rotation and flow.

4. The following cooling load will be available for start-up:a. 25%b. 50%c. 75%d. 100%

5. The refrigerant charge is at the machine.6. Services such as electrical power and control air will be available

at start-up.7. The electrical and mechanical representatives will be available

to assist in commissioning the machine.8. The customer’s operators will be available to receive instructions

for proper operation of the chiller after start-up.

Concerns about the installation/request for additional assistance:

I am aware that the start-up time for a Carrier chiller can take between 2 and 6 days depending on the model of the machine and theoptions and accessories used with it.

Your contact at the jobsite will be _______________________________________________________________________________

Phone number ______________________________________________________________________________________________

Pager/cell number ____________________________________________________________________________________________

Fax number ________________________________________________________________________________________________

In accordance with our contract, we hereby request the services of your technician to render start-up services per contract terms for thisjob on (Date). I understand that the technician’s time will be charged as extra services due to correcting items in thischecklist that are incomplete.

Signature of Purchaser ________________________________________________________________________________________

Signature of Jobsite Supervisor _________________________________________________________________________________