18427996 Motor Starter Solutions 3
Transcript of 18427996 Motor Starter Solutions 3
-
7/27/2019 18427996 Motor Starter Solutions 3
1/1
1/2
1
General 1 TeSys motor starters 1Levels of service
Type 1 and type 2 coordination according to the standardThe standard defines tests at different levels of current; the purpose of these tests is
to place the equipment in extreme conditions.The standard defines 2 types of coordination, according to the condition of the
components after testing:
type 1,
type 2.
To determine the type of coordination, the standard requires that the behaviour of the
equipment be tested under overload and short-circuit conditions for 3 fault current
values, covering overload and short-circuit conditions.
Type 1 coordination
Type 1 coordination requires that in a short-circuit condition, the contactor or starter
must not present any danger to personnel or installations and must not be able to
resume operation without repair or the replacement of parts.
1 Thermal overload relay curve.2 Fuse.
3 Tripping of thermal overload relay only.
4 Thermal limit of the circuit-breaker.
5 Thermal overload relay limit.
6 Current broken by the SCPD (1).
7 Circuit breaker magnetic trip.
Type 2 coordination
Type 2 coordination requires that In a short-circuit condition, the contactor or s tartermust not present any danger to personnel or installations and must subsequently
be able to resume operation. The risk of contact welding is permissible; in this case,
the manufacturer must indicate measures to be taken regarding maintenance of the
equipment.
Type 2 coordination increases reliability of operation.
Current valuesCurrent Ico (overload I < 10 In)
The thermal overload relay associated with the contactor provides protection against
this type of fault, up to a value Ico (see curve) defined by the manufacturer.
Standard IEC 60947-4-1 specifies the 2 current values to be used for checking
coordination between the thermal overload relay and the short-circuit protection
device:b at 0.75 Ico only the thermal overload relay must trip,
b at 1.25 Ico the short-circuit protection device must operate.
Current r (low level short-circuit 10 < I < 50 In)
The main cause of this type of fault is the deterioration of insulating materials.
Standard IEC 60947-4-1 defines an intermediate short-circuit current r. This test
current makes it possible to check whether the protection device is providing
protection against low-level short-circuits.
Operational current Ie (AC-3) (A) Current r (kA)
Ie y16 1
16 < Ie y63 363 < Ie y125 5125 < Ie y315 10
315 < Ie y630 18
630 < Ie y1000 30
Current Iq (short-circuit > current r)
This type of fault corresponds to a dead short and is relatively rare. It can be caused
by a connection error during maintenance work. Short-circuit protection is provided
by fast operating devices.
Standard IEC 60947-4-1 defines a current Iq. The coordination tables supplied by
Schneider Electric are based on a current Iq that is generally u 50 kA.
(1) SCPD: short-circuit protection device.
1 10 50
In
t
0,75 Ico 1,25 Ico
Ico
Ir Iq
1
3 6
7
4
5
2
ak In
Overload zone Short-circuit zoneLow-levelshort-circuit zone