18427996 Motor Starter Solutions 3

download 18427996 Motor Starter Solutions 3

of 1

Transcript of 18427996 Motor Starter Solutions 3

  • 7/27/2019 18427996 Motor Starter Solutions 3

    1/1

    1/2

    1

    General 1 TeSys motor starters 1Levels of service

    Type 1 and type 2 coordination according to the standardThe standard defines tests at different levels of current; the purpose of these tests is

    to place the equipment in extreme conditions.The standard defines 2 types of coordination, according to the condition of the

    components after testing:

    type 1,

    type 2.

    To determine the type of coordination, the standard requires that the behaviour of the

    equipment be tested under overload and short-circuit conditions for 3 fault current

    values, covering overload and short-circuit conditions.

    Type 1 coordination

    Type 1 coordination requires that in a short-circuit condition, the contactor or starter

    must not present any danger to personnel or installations and must not be able to

    resume operation without repair or the replacement of parts.

    1 Thermal overload relay curve.2 Fuse.

    3 Tripping of thermal overload relay only.

    4 Thermal limit of the circuit-breaker.

    5 Thermal overload relay limit.

    6 Current broken by the SCPD (1).

    7 Circuit breaker magnetic trip.

    Type 2 coordination

    Type 2 coordination requires that In a short-circuit condition, the contactor or s tartermust not present any danger to personnel or installations and must subsequently

    be able to resume operation. The risk of contact welding is permissible; in this case,

    the manufacturer must indicate measures to be taken regarding maintenance of the

    equipment.

    Type 2 coordination increases reliability of operation.

    Current valuesCurrent Ico (overload I < 10 In)

    The thermal overload relay associated with the contactor provides protection against

    this type of fault, up to a value Ico (see curve) defined by the manufacturer.

    Standard IEC 60947-4-1 specifies the 2 current values to be used for checking

    coordination between the thermal overload relay and the short-circuit protection

    device:b at 0.75 Ico only the thermal overload relay must trip,

    b at 1.25 Ico the short-circuit protection device must operate.

    Current r (low level short-circuit 10 < I < 50 In)

    The main cause of this type of fault is the deterioration of insulating materials.

    Standard IEC 60947-4-1 defines an intermediate short-circuit current r. This test

    current makes it possible to check whether the protection device is providing

    protection against low-level short-circuits.

    Operational current Ie (AC-3) (A) Current r (kA)

    Ie y16 1

    16 < Ie y63 363 < Ie y125 5125 < Ie y315 10

    315 < Ie y630 18

    630 < Ie y1000 30

    Current Iq (short-circuit > current r)

    This type of fault corresponds to a dead short and is relatively rare. It can be caused

    by a connection error during maintenance work. Short-circuit protection is provided

    by fast operating devices.

    Standard IEC 60947-4-1 defines a current Iq. The coordination tables supplied by

    Schneider Electric are based on a current Iq that is generally u 50 kA.

    (1) SCPD: short-circuit protection device.

    1 10 50

    In

    t

    0,75 Ico 1,25 Ico

    Ico

    Ir Iq

    1

    3 6

    7

    4

    5

    2

    ak In

    Overload zone Short-circuit zoneLow-levelshort-circuit zone