The novatap and novaspout both use infrared technology ensuringmaximum hygiene and water efficiency.
Both taps have various flow rates to suit different applications suchas 3.5 litres per minute non-aerated specifically for healthcareapplications and the 5 litres per minute aerated for otherapplications. The taps have a programmable hygiene cycle toreduce the risk of legionellae.
1 IntroductionCistermiser’s infrared taps consist of the deck-mounted
novatap and the panel-mounted novaspout
0118 969 1611 | [email protected] | www.cistermiser.co.uk
installation guide
IR Range (Infrared Range)
supplied partsnovatap1 Spout body
2 Flexible hose
3 Spout gasket
4 Bracket gasket
5 Fixing bracket
6 Screw
7 Washer
8 Fixing nut
9 Mains adaptor
10 Battery case
11 Sticky pad
1
2
3
4
5
7
8
9
10
11
supplied partsnovaspout1 Basin spout
2 Solenoid valve
3 Anti-rotation washer
4 Lock nut
5 G3/4 backnut
6 Compression olive & nut
7 Lock ring
8 Screws
9 Sensor unit
10 Sensor gasket
11 Sensor fastening nut
12 Clamp plate
13 Screw packer
14 Mains adaptor
15 Battery case
16 Sticky pad
1
2
3
4
5
6
7
9
10
11
12
13
14
15
16
x 4
x 4
x 4
x 4
x 2
x 2
x 1
x 1
A
B
C
A
A
8
optional extras (Suitable for all Cistermiser IR Range products):Infrared configuration unit (ICU)Multi product power supply unit (PSUC)
6
0118 969 1611 | [email protected] | www.cistermiser.co.uk
2 Installation of the novatap
115mm125mm
450mm
Water supply
Isolating valve(not supplied)
10°
8mm AF Spanner
G3/8 (3/8” BSP) Female
The novatap can be mounted on any horizontalsurface up to 40mm thick. It requires a hole of32.5-36mm diameter.
Requires 4 x AA (LR6)alkaline batteries
Requires 1A fused spur
Multi product power supply unit (not supplied) (suitable for powering up to 20 units)
Power options
OR
OR
NOTE:Flush pipework prior to installationDo not install opposite a mirror
NOTE:When installing the inlet pipework it is goodplumbing practice to ensure that there is anaccessible service valve upstream of the spout.
Typically greater than 150mm
Typically 115mm
G1/2Compressionfitting
Alternativeorientation
Long: 200mm
Isolating valve(not supplied)
x 4
x 4
OR
Water supply
Requires 4 x AA (LR6)alkaline batteries
Requires 1A fused spur
Multi product power supply unit (not supplied) (suitable for powering up to 20 units)
Power options
OR
OR
NOTE:Flush pipework prior to installationDo not install opposite a mirror
3 Installation of the novaspout
0118 969 1611 | [email protected] | www.cistermiser.co.uk
Sensor
Ø38mm
3 – 15mm
Sensor nut (11)
Sensorgasket (10)
Sensorgasket (10)Apply
sanitarysiliconesealant
Applysanitarysiliconesealant
Applysanitarysiliconesealant
Thin wall Medium thickness wall
15 – 30mm
Ø44mm Ø38mm
Thick wall
31 – 36mm+
Clamp plate(reversible) (12)
Screw packer (13)
M4 screw
Sensor nut (11)
Spout
Ø27mm
3 – 8mm
G 3/4backnut (5) Apply
sanitarysiliconesealant
Thin wall
Large pan head screw (8 B)Applysanitarysiliconesealant
Medium thickness wall
8 – 36mm
Anti rotation washer (3)
Locknut (4)
Locking plate (7)
Rear view
Ø38mm
0118 969 1611 | [email protected] | www.cistermiser.co.uk
4 Power connectionsNOTE: Only one power source should beconnected at any time, either mains or batteries. It is not possible to connect both simultaneously.
If using the battery case, open it and fit 4 AlkalineAA (LR-6) batteries as indicated. Reseal and fasteninto place on panel using screws or with thesticky pads.
If using the mains adaptor, fasten into place onpanel in a dry location using screws or with thesticky pads and connect the un-terminated mainscable to a 50Hz 230V AC single phase supply viaa 1A fused spur (not supplied).
electrical connectionConnect the power connector from the spout tothe mains adaptor, or in the case of a batterypowered installation, the battery case.
5 Usage advice and specification
factory settings
electronic specification
Control classification: Independent
Maximum load: 7.5W 1.25A (6V DC)
EMC emissions: Tested at above load
Rated temperature range: 0-40° C
Action classification: Type 1.Y
Pollution classification: Degree 1
Range: ~18cm
Run-on time: 2 sec
Power requirements: Either 6V DC from 4 x alkaline AA (LR6) batteries or 6V DC regulated from mains adaptor. (1A fused spur required)
Battery life: 2 years in normal conditions with recommended batteries. A single red flashing of the LED indicates that the batteries are low and need to be replaced.
Cleaning: Clean only with soap and water only.
Lens care: Infrared lens can be polished with a soft cloth.
Minimum working pressure: 0.5 bar
Maximum working pressure: 6 bar
A
A
NOTE:Remove the label from the sensor BEFOREconnecting to the power. When the poweris first connected the LED in the sensorflashes amber. This is normal and lasts onlya few seconds.
0118 969 1611 | [email protected] | www.cistermiser.co.uk
6 Component dimensions
basin spout length
Short (NTP/SA, NTP/SN): 109mm
Medium (NTP/MA, NTP/MN): 159mm
Long (NTP/LA, NTP/LN): 209mm
140m
m80m
m
Flo
w R
ate
(lit
re/m
in)
Supply pressure (bar)
48m
m
26.5
mm
Basin spout length
5 litre per minute aerated
45mm
51mm
15mm
204mm
37m
m
27mm
48mm
87
2 3 4
654
32
510
1
flow rate chart
0
3.5 litre per minute non-aerated
0118 969 1611 | [email protected] | www.cistermiser.co.uk
7 Advanced setting guide
1 Disconnect power, wait for 2 seconds and reconnect
2 When flashing amber
If a hand is not placed over the sensor, it will go into normal operation mode.
Place hand 10cm from sensoruntil constant green
You are now in configuration mode
Sensing range adjustment
Wait for singlered flashing LEDto enter sensingrange mode
A Briefly place your hand in front of thesensor until the green LED flashedslowly. Range configuration modewill then be ready.
B
Move your hand to the distance from the sensor you would like toset as maximum range. Wait 8 seconds until constant green shows
C
Run-on time adjustment
Wait for doublered flashing LEDto enter refill time
A B
novatap & novaspout Carry out only if settings need to be changed
Sensor distanceis now set
When the water has run for the desired run-on time, move your hand out of the line of sight of the sensor. The water will cease and the run-on time will be set.
C
1 2
4 After configuration the unit will flash amber giving opportunity to re-enter configuration mode
During double red flashing brieflyplace your hand in front of the sensor, water will start running while a green flashingwill be seen. HOLD HAND STEADY
Additional configuration with Infrared Config Unit (ICU) remote control (sold separately)
• Hygiene rinse on/off: The installer is able to switch the 12hr hygiene rinse function on or off.
• Clean mode: The spouts can be disabled for a short period to allow for cleaning.
3
0118 969 1611 | [email protected] | www.cistermiser.co.uk
8 Infrared Configuration Unit (ICU) guide
inserting and replacing batteriesThe ICU uses 2 AAA or LR03 alkaline batteries,these must be installed before use. Always usenew batteries of the same type. Install as indicatedin the battery compartment on the rear of the ICU.
PLEASE NOTE: Batteries should be replacedwhen the signal of the ICU becomes weak and itbecomes difficult to activate either cleaning orconfiguration mode.
activating cleaning modeCleaning mode, disables normal operation forcleaning for a timed 30 seconds. In order toactivate cleaning mode with the ICU, it must bepointed at the sensor of the selected washroomproduct. Activation is most effective when theclean button is held down as the ICU is broughtclose to the sensor. It can take up to 3 secondsfor the product to sense the ICU.
When the washroom product is in Clean Mode, thesensor flashes green once a second.
activating ICU configuration modeIn order to activate ICU configuration mode with theICU, it must be pointed at the sensor of the selectedwashroom product. Activation is most effective whenthe configuration button is held down as the ICUis brought close to the sensor. It can take up to 3seconds for the product to sense the ICU.
The washroom product will return to normaloperation if there are no button presses for 30seconds.
infrared tapsThe ICU can adjust/activate the following settings onthe novatap and infrared taps: sensor range;
Run-on time; and 12hr hygiene cycle.
The product must always be put into ICUconfiguration mode before any setting can beconfigured.
Activates cleaning mode
Activates ICU configuration mode
Decreases setting
Increases setting
Checks the setting being altered
Saves changes and exits ICU configuration mode
Quits ICU configuration mode without saving changes
Configures sensor range
Configures hand wave
12 hour hygiene cycle activation
Resets to default factory settings
145
button descriptions
9
NOTE: Not supplied but available from Cistermiser or any major plumbing merchant.
configuring sensor rangePoint the ICU at the sensor and press the 1sensor range button (the sensor blinks green).
Decrease or increase the sensor range by pressingthe and buttons respectively. The sensor blinksred when the min or max value is reached.
Press the button to check the sensor rangesetting - the sensor displays the current setting byflashing green, see table.
Save setting and exit ICU configuration mode bypressing the button.
Exit without saving by pressing the button.
configuring run on timePoint the ICU at the sensor and press the 4 run-on time button (the sensor blinks green).
Decrease or increase the run-on time by pressingthe and buttons respectively. The sensor blinksred when the min or max value is reached.
Press the button to check the run-on time setting- the sensor displays the current setting by flashinggreen, see table.
Save setting and exit ICU configuration code bypressing the button.
Exit without saving by pressing the button.
configuring the 12hr hygiene rinse cyclePoint the ICU at the sensor and press the 5 run-on time button (the sensor blinks green).
Decrease or increase the hygiene rinse time bypressing the and buttons respectively. Thesensor blinks red when the min or max value isreached.
Press the button to check the hygiene rinse timesetting - the sensor displays the current setting byflashing green, see table.
Save setting and exit ICU configuration mode bypressing the button.
Exit without saving by pressing the button.
reset to factory settingsPoint the ICU at the sensor and press the 9 resetbutton (the sensor blinks green). This sets all settingsto the default factory settings.
Save setting and exit ICU configuration mode bypressing the button.
Exit without saving by pressing the button.
Number of flashes 1 2 3 4 5
Range (cm approx) 8 11 14 16 18
Number of flashes 1 2 3 4 5 6 7 8
Run-on-time (sec.) 1 2 3 4 5 10 20 30
Number of flashes 1 2 3 4 5 6
Hygiene rinse time (sec.) 0 5 10 15 30 60
0118 969 1611 | [email protected] | www.cistermiser.co.uk
9 Frequently asked questions
The sensor is flashing red Low battery. Change batteries. once a second
The sensor is not flashing No power. Change batteries if battery powered. Ensure power is at all when hands are in switched on and is reaching the tap. Check all electrical sensing range. connections.
Water supply. Ensure water supply has been turned on and thereis good working pressure. Minimum working pressure 0.5 bar.
Filter blockage (Novatap). Ensure flexible connector has not been twisted. Ensure filter in the flexible connector is not blocked. Ensure the spout is clear.
no water from tap / spout
The sensor is flashing green Filter or aerator is blocked with scale or debris.once a second when hands Remove aerator using key supplied, clean and reinstall. are in sensing range. Check filters prior to the aerator i.e. TMV (Novatap check filter
within the flexible connector).
water flow diminishes
The sensor is not flashing at all No power. The power has failed whilst the solenoid tap is open.when hands are in sensing Change batteries if battery powered. Ensure power is switched onrange and is reaching the tap, check all electrical connections.
Water supply. Ensure water pressure is not above maximum working pressure of 6 bar or below minimum working pressure of0.5 bar.NovatapDebris or scale in diaphragm/solenoid. Remove aerator using key supplied then place hands in sensing range and let water flow forapproximately 2-3 minutes, this should clear any debris. (The flowwill automatically shut off after 1 minute; when this happens, removehand and reactivate).If this does not solve the problem contact Cistermiser Technical Department.NovaspoutDebris or scale in diaphragm. Isolate water supply to the valve.Remove wires attached to solenoid. Undo 4 screws and remove.You will have access to the diaphragm (note orientation for whenreinstalling) flush under cold water and visually inspect. Reinstall Diaphragm has been damaged by debris. Call Cistermiser for further advice.
continuous flow of water or dripping from the tap
The sensor is flashing greenonce a second when hands are in sensing range but there is no water.
The sensor is flashing greenonce a second when hands are in sensing range
0118 969 1611 | [email protected] | www.cistermiser.co.uk
IRT_A-01
9 Frequently asked questions
DDA
The sensor is flashing green TMV/water pressure issue. Ensure TMV is operating correctly andonce a second when hands are water pressures are suitable for TMVs installed.in sensing range
water flow as expected and then diminishes immediately
The sensor is flashing green TMV/hot water plumbing issue. Ensure TMV is set up correctly; hotonce a second when hands are water-runs in buildings can sometimes be lengthy. There may be ain sensing range short delay until hot water is dispensed from the tap.
water is always cold
Double red flash Faulty wiring. Check wiring.Faulty solenoid. Call Cistermiser for advice.
Red flash once every second Low battery power. Change batteries.Red flash twice every Sensor covered or heavily scratched. Uncover sensor or polish three seconds. out scratches.
other alarms