58
ControlNet Universal PCI Communication Interface Card 1784-PCIC, 1784-PCICS Series B Installation Instructions

Transcript of 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation...

Page 1: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

ControlNet Universal PCI Communication Interface Card1784-PCIC 1784-PCICS Series B

Installation Instructions

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (Publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwliteraturerockwellautomationcom) describes some important differences between solid state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable

In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment

The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams

No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual

Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited

Throughout this manual we use notes to make you aware of safety considerations

WARNINGIdentifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss

IMPORTANT Identifies information that is critical for successful application and understanding of the product

ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you

bull identify a hazard

bull avoid a hazard

bull recognize the consequence

SHOCK HAZARD Labels may be located on or inside the drive to alert people that dangerous voltage may be present

BURN HAZARD Labels may be located on or inside the drive to alert people that surfaces may be dangerous temperatures

Table of Contents

Chapter 1Install the 1784-PCIC or 1784-PCICS Communication Interface CardEuropean Hazardous Location Approval (1784-PCIC only) 1-3

European Zone 2 Certification 1-3North American Hazardous Location Approval 1-4Access the Computerrsquos PCI Local Bus Expansion Slots 1-5Insert the Card Into the Computer 1-6Connect to the Network 1-7Connect the Card Directly to the ControlNet Network 1-9Connect to a Device on the ControlNet Network 1-10

Chapter 2Install the Driver in Windows XP Install the Driver in Windows XP for the First Time 2-1Update the Existing Driver in Windows XP 2-3

Chapter 3Install the Driver in Windows 2000Install the Driver in Windows 2000 for the First Time 3-1Update the Existing Driver in Windows 2000 3-4

Chapter 4Install the Driver in Windows 98MeInstall the Driver in Windows 98Me for the First Time 4-1Install the Virtual Backplane Driver 4-3Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

ii Table of Contents

Chapter 5Once You Have Completed the InstallationRegister the EDS File 5-1Configure the ControlNet Communications Driver in RSLinx Software 5-2Connect a SoftLogix Controller to the ControlNet Network 5-4Go Online With RSNetWorx for ControlNet Software 5-7

Chapter 6Interpret the LED Indicators

Chapter 7SpecificationsIndex

Publication 1784-IN003D-EN-P - January 2006

Chapter 1

Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Before you install the card be certain that you

bull know how to install hardware in your computer

bull consult your computerrsquos documentation for hardware installation instructions

Refer to the following publications for more information

bull ControlNet Coax Media Planning and Installation publication CNET-IN002

bull ControlNet Communication Modules in Logix5000 Control Systems publication CNET-UM001

bull SoftLogix5800 System User Manual publication 1789-UM002

For Information On This Topic See Page

Access the Computerrsquos PCI Local Bus Expansion Slots 1-5

Insert the Card Into the Computer 1-6

Connect to the Network 1-7

Connect the Card Directly to the ControlNet Network 1-9

Connect to a Device on the ControlNet Network 1-10

TIP Installation instructions for both the 1784-PCIC and 1784-PCICS cards are exactly the same In most illustrations the 1784-PCIC card is shown

Publication 1784-IN003D-EN-P - January 2006

1-2 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment in overvoltage Category II applications (as defined in IEC publication 60664-1) at altitudes up to 2000 meters without derating

This equipment is considered Group 1 Class A industrial equipment according to IECCISPR Publication 11 Without appropriate precautions there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance

This equipment is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications

NOTE See NEMA Standards publication 250 and IEC publication 60529 as applicable for explanations of the degrees of protection provided by different types of enclosure Also see the appropriate sections in this publication as well as the Industrial Automation Wiring and Grounding Guidelines Allen-Bradley publication 1770-41 for additional installation requirements pertaining to this equipment

ATTENTION Prevent Electrostatic Discharge

This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when you handle this equipment

bull Touch a grounded object to discharge potential static

bull Wear an approved grounding wriststrap

bull Do not touch connectors or pins on component boards

bull Do not touch circuit components inside the equipment

bull Use a static-safe workstation if available

bull Store the equipment in appropriate static-safe packaging when not in use

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-3

European Hazardous Location Approval (1784-PCIC only)

European Zone 2 CertificationThe following applies when the product bears the EEx Marking

This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 949EC

The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres given in Annex II to this Directive The examination and test results are recorded in confidential report No 28 682 010

Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021

IMPORTANT This equipment is not resistant to sunlight or other sources of UV radiation

The secondary of a current transformer shall not be open-circuited when applied in Class I Zone 2 environments

Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I Zone 2 environments

This equipment shall be used within its specified ratings defined by Allen-Bradley

Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40 when applied in Class I Zone 2 environments

Publication 1784-IN003D-EN-P - January 2006

1-4 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

North American Hazardous Location ApprovalThe following information applies when operating this equipment in hazardous locations

Informations sur lrsquoutilisation de cet eacutequipement en environnements dangereux

Products marked CL I DIV 2 GP A B C D are suitable for use in Class I Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code When combining products within a system the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation

Les produits marqueacutes CL I DIV 2 GP A B C D ne conviennent qursquoagrave une utilisation en environnements de Classe I Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livreacute avec des marquages sur sa plaque drsquoidentification qui indiquent le code de tempeacuterature pour les environnements dangereux Lorsque plusieurs produits sont combineacutes dans un systegraveme le code de tempeacuterature le plus deacutefavorable (code de tempeacuterature le plus faible) peut ecirctre utiliseacute pour deacuteterminer le code de tempeacuterature global du systegraveme Les combinaisons drsquoeacutequipements dans le systegraveme sont sujettes agrave inspection par les autoriteacutes locales qualifieacutees au moment de lrsquoinstallation

WARNINGEXPLOSION HAZARD

bull Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous

bull Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this equipment by using screws sliding latches threaded connectors or other means provided with this product

bull Substitution of components may impair suitability for Class I Division 2

bull If this product contains batteries they must be changed only in an area known to be nonhazardous

AVERTISSEMENT RISQUE DrsquoEXPLOSION

bull Couper le courant ou srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher leacutequipement

bull Couper le courant ou sassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher les connecteurs Fixer tous les connecteurs externes relieacutes agrave cet eacutequipement agrave laide de vis loquets coulissants connecteurs fileteacutes ou autres moyens fournis avec ce produit

bull La substitution de composants peut rendre cet eacutequipement inadapteacute agrave une utilisation en environnement de Classe I Division 2

bull Srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de changer les piles

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-5

To install the card you need to

bull access the computerrsquos expansion slots

bull insert the card into the computer

Access the Computerrsquos PCI Local Bus Expansion SlotsTo install the card you must access the computerrsquos PCI local bus expansion slots Follow these general steps or refer to your computerrsquos user guide for further instructions

1 Shut down the host computer

2 Remove the computerrsquos cover

3 Select a vacant PCI local bus expansion slot

4 Loosen the screw (if present) on the back (rear bracket) of the computer

5 Remove the slotrsquos expansion cover

IMPORTANT The cardrsquos dimensions are shown below

42 in 107 cm

65 in 165 cm

31474-M

Publication 1784-IN003D-EN-P - January 2006

1-6 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Insert the Card Into the Computer

1 Handle the card so that you prevent electrostatic discharge

Refer to the Preface of this manual for more information

2 Insert the card into the edge connector and tighten the expansion slot screw (if present)

3 Replace the computer cover

4 Turn on the computer to be certain that it comes up correctly

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codesIf you insert or remove the card while host power is on an electrical arc can occur This could cause an explosion in hazardous location installationsBe sure that power is removed or the area is nonhazardous before proceeding

If the Computer Then

Turns on Go to to the next section Connect to the Network

Hangs up Either the card is not seated correctly in the PCI slot or you have a memory or IO conflict You should

bull remove and reinsert the card into the same PCI slot and try again

bull remove and reinsert the card into a different PCI slot and try again

bull remove all other non-essential cards and try again

If you continue to experience difficulty contact your local Rockwell Automation sales representative or distributor or call Rockwell Automation Technical Support at 4406465800

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-7

Connect to the Network

After you have installed the card you can connect it

bull directly to a ControlNet network which requires a tap (page 1-9)

bull to a device already connected to the ControlNet network (page 1-10)

See Figure 11 on page 1-8 for the connectors and indicators

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes

If you connect or disconnect the ControlNet cable with power applied to this module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations

Be sure that power is removed or the area is nonhazardous before proceeding

Publication 1784-IN003D-EN-P - January 2006

1-8 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 11 1784-PCIC or 1784-PCICS Card (1784-PCIC Card Shown)

ATTENTION Do not connect different ControlNet networks to this card If you attempt to connect a second network to this card your communication system will operate erratically

A

B

Network Access Port (NAP)RJ-45 connector for connecting programming terminals to devices on a ControlNet network

Channel A BNC connectors for connecting directly to ControlNet network

Channel B

Do not connect more than one ControlNet network to this card

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Allen-Bradley1784-PCICControlNet

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9

Connect the Card Directly to the ControlNet NetworkTo connect the card directly to a ControlNet network follow the instructions in these publications

bull ControlNet Coax Tap Installation Instructions publication 1786-IN007

bull ControlNet Coax Media Planning and Installation Manual publication CNET-IN002

Figure 12 Connect the Card Directly to the ControlNet Network

ATTENTION If you connect the product to a cable system that does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left unconnected If the cable system is redundant connect the product so that all devices on the network use the same cable for the same channel That is all channel A connectors connect to one cable all channel B connectors connect to the other cable

TIP If you use a non-redundant cable system all ControlNet devices must be on the same channel channel A

Desktop Host Computer

1784-PCIC or 1784-PCICS

1786-TPR -TPS -TPYR or -TPYS Tap

ControlNet Network

42200

Publication 1784-IN003D-EN-P - January 2006

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 2: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls (Publication SGI-11 available from your local Rockwell Automation sales office or online at httpwwwliteraturerockwellautomationcom) describes some important differences between solid state equipment and hard-wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable

In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment

The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams

No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual

Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited

Throughout this manual we use notes to make you aware of safety considerations

WARNINGIdentifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss

IMPORTANT Identifies information that is critical for successful application and understanding of the product

ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you

bull identify a hazard

bull avoid a hazard

bull recognize the consequence

SHOCK HAZARD Labels may be located on or inside the drive to alert people that dangerous voltage may be present

BURN HAZARD Labels may be located on or inside the drive to alert people that surfaces may be dangerous temperatures

Table of Contents

Chapter 1Install the 1784-PCIC or 1784-PCICS Communication Interface CardEuropean Hazardous Location Approval (1784-PCIC only) 1-3

European Zone 2 Certification 1-3North American Hazardous Location Approval 1-4Access the Computerrsquos PCI Local Bus Expansion Slots 1-5Insert the Card Into the Computer 1-6Connect to the Network 1-7Connect the Card Directly to the ControlNet Network 1-9Connect to a Device on the ControlNet Network 1-10

Chapter 2Install the Driver in Windows XP Install the Driver in Windows XP for the First Time 2-1Update the Existing Driver in Windows XP 2-3

Chapter 3Install the Driver in Windows 2000Install the Driver in Windows 2000 for the First Time 3-1Update the Existing Driver in Windows 2000 3-4

Chapter 4Install the Driver in Windows 98MeInstall the Driver in Windows 98Me for the First Time 4-1Install the Virtual Backplane Driver 4-3Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

ii Table of Contents

Chapter 5Once You Have Completed the InstallationRegister the EDS File 5-1Configure the ControlNet Communications Driver in RSLinx Software 5-2Connect a SoftLogix Controller to the ControlNet Network 5-4Go Online With RSNetWorx for ControlNet Software 5-7

Chapter 6Interpret the LED Indicators

Chapter 7SpecificationsIndex

Publication 1784-IN003D-EN-P - January 2006

Chapter 1

Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Before you install the card be certain that you

bull know how to install hardware in your computer

bull consult your computerrsquos documentation for hardware installation instructions

Refer to the following publications for more information

bull ControlNet Coax Media Planning and Installation publication CNET-IN002

bull ControlNet Communication Modules in Logix5000 Control Systems publication CNET-UM001

bull SoftLogix5800 System User Manual publication 1789-UM002

For Information On This Topic See Page

Access the Computerrsquos PCI Local Bus Expansion Slots 1-5

Insert the Card Into the Computer 1-6

Connect to the Network 1-7

Connect the Card Directly to the ControlNet Network 1-9

Connect to a Device on the ControlNet Network 1-10

TIP Installation instructions for both the 1784-PCIC and 1784-PCICS cards are exactly the same In most illustrations the 1784-PCIC card is shown

Publication 1784-IN003D-EN-P - January 2006

1-2 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment in overvoltage Category II applications (as defined in IEC publication 60664-1) at altitudes up to 2000 meters without derating

This equipment is considered Group 1 Class A industrial equipment according to IECCISPR Publication 11 Without appropriate precautions there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance

This equipment is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications

NOTE See NEMA Standards publication 250 and IEC publication 60529 as applicable for explanations of the degrees of protection provided by different types of enclosure Also see the appropriate sections in this publication as well as the Industrial Automation Wiring and Grounding Guidelines Allen-Bradley publication 1770-41 for additional installation requirements pertaining to this equipment

ATTENTION Prevent Electrostatic Discharge

This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when you handle this equipment

bull Touch a grounded object to discharge potential static

bull Wear an approved grounding wriststrap

bull Do not touch connectors or pins on component boards

bull Do not touch circuit components inside the equipment

bull Use a static-safe workstation if available

bull Store the equipment in appropriate static-safe packaging when not in use

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-3

European Hazardous Location Approval (1784-PCIC only)

European Zone 2 CertificationThe following applies when the product bears the EEx Marking

This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 949EC

The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres given in Annex II to this Directive The examination and test results are recorded in confidential report No 28 682 010

Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021

IMPORTANT This equipment is not resistant to sunlight or other sources of UV radiation

The secondary of a current transformer shall not be open-circuited when applied in Class I Zone 2 environments

Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I Zone 2 environments

This equipment shall be used within its specified ratings defined by Allen-Bradley

Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40 when applied in Class I Zone 2 environments

Publication 1784-IN003D-EN-P - January 2006

1-4 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

North American Hazardous Location ApprovalThe following information applies when operating this equipment in hazardous locations

Informations sur lrsquoutilisation de cet eacutequipement en environnements dangereux

Products marked CL I DIV 2 GP A B C D are suitable for use in Class I Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code When combining products within a system the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation

Les produits marqueacutes CL I DIV 2 GP A B C D ne conviennent qursquoagrave une utilisation en environnements de Classe I Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livreacute avec des marquages sur sa plaque drsquoidentification qui indiquent le code de tempeacuterature pour les environnements dangereux Lorsque plusieurs produits sont combineacutes dans un systegraveme le code de tempeacuterature le plus deacutefavorable (code de tempeacuterature le plus faible) peut ecirctre utiliseacute pour deacuteterminer le code de tempeacuterature global du systegraveme Les combinaisons drsquoeacutequipements dans le systegraveme sont sujettes agrave inspection par les autoriteacutes locales qualifieacutees au moment de lrsquoinstallation

WARNINGEXPLOSION HAZARD

bull Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous

bull Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this equipment by using screws sliding latches threaded connectors or other means provided with this product

bull Substitution of components may impair suitability for Class I Division 2

bull If this product contains batteries they must be changed only in an area known to be nonhazardous

AVERTISSEMENT RISQUE DrsquoEXPLOSION

bull Couper le courant ou srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher leacutequipement

bull Couper le courant ou sassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher les connecteurs Fixer tous les connecteurs externes relieacutes agrave cet eacutequipement agrave laide de vis loquets coulissants connecteurs fileteacutes ou autres moyens fournis avec ce produit

bull La substitution de composants peut rendre cet eacutequipement inadapteacute agrave une utilisation en environnement de Classe I Division 2

bull Srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de changer les piles

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-5

To install the card you need to

bull access the computerrsquos expansion slots

bull insert the card into the computer

Access the Computerrsquos PCI Local Bus Expansion SlotsTo install the card you must access the computerrsquos PCI local bus expansion slots Follow these general steps or refer to your computerrsquos user guide for further instructions

1 Shut down the host computer

2 Remove the computerrsquos cover

3 Select a vacant PCI local bus expansion slot

4 Loosen the screw (if present) on the back (rear bracket) of the computer

5 Remove the slotrsquos expansion cover

IMPORTANT The cardrsquos dimensions are shown below

42 in 107 cm

65 in 165 cm

31474-M

Publication 1784-IN003D-EN-P - January 2006

1-6 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Insert the Card Into the Computer

1 Handle the card so that you prevent electrostatic discharge

Refer to the Preface of this manual for more information

2 Insert the card into the edge connector and tighten the expansion slot screw (if present)

3 Replace the computer cover

4 Turn on the computer to be certain that it comes up correctly

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codesIf you insert or remove the card while host power is on an electrical arc can occur This could cause an explosion in hazardous location installationsBe sure that power is removed or the area is nonhazardous before proceeding

If the Computer Then

Turns on Go to to the next section Connect to the Network

Hangs up Either the card is not seated correctly in the PCI slot or you have a memory or IO conflict You should

bull remove and reinsert the card into the same PCI slot and try again

bull remove and reinsert the card into a different PCI slot and try again

bull remove all other non-essential cards and try again

If you continue to experience difficulty contact your local Rockwell Automation sales representative or distributor or call Rockwell Automation Technical Support at 4406465800

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-7

Connect to the Network

After you have installed the card you can connect it

bull directly to a ControlNet network which requires a tap (page 1-9)

bull to a device already connected to the ControlNet network (page 1-10)

See Figure 11 on page 1-8 for the connectors and indicators

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes

If you connect or disconnect the ControlNet cable with power applied to this module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations

Be sure that power is removed or the area is nonhazardous before proceeding

Publication 1784-IN003D-EN-P - January 2006

1-8 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 11 1784-PCIC or 1784-PCICS Card (1784-PCIC Card Shown)

ATTENTION Do not connect different ControlNet networks to this card If you attempt to connect a second network to this card your communication system will operate erratically

A

B

Network Access Port (NAP)RJ-45 connector for connecting programming terminals to devices on a ControlNet network

Channel A BNC connectors for connecting directly to ControlNet network

Channel B

Do not connect more than one ControlNet network to this card

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Allen-Bradley1784-PCICControlNet

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9

Connect the Card Directly to the ControlNet NetworkTo connect the card directly to a ControlNet network follow the instructions in these publications

bull ControlNet Coax Tap Installation Instructions publication 1786-IN007

bull ControlNet Coax Media Planning and Installation Manual publication CNET-IN002

Figure 12 Connect the Card Directly to the ControlNet Network

ATTENTION If you connect the product to a cable system that does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left unconnected If the cable system is redundant connect the product so that all devices on the network use the same cable for the same channel That is all channel A connectors connect to one cable all channel B connectors connect to the other cable

TIP If you use a non-redundant cable system all ControlNet devices must be on the same channel channel A

Desktop Host Computer

1784-PCIC or 1784-PCICS

1786-TPR -TPS -TPYR or -TPYS Tap

ControlNet Network

42200

Publication 1784-IN003D-EN-P - January 2006

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 3: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Table of Contents

Chapter 1Install the 1784-PCIC or 1784-PCICS Communication Interface CardEuropean Hazardous Location Approval (1784-PCIC only) 1-3

European Zone 2 Certification 1-3North American Hazardous Location Approval 1-4Access the Computerrsquos PCI Local Bus Expansion Slots 1-5Insert the Card Into the Computer 1-6Connect to the Network 1-7Connect the Card Directly to the ControlNet Network 1-9Connect to a Device on the ControlNet Network 1-10

Chapter 2Install the Driver in Windows XP Install the Driver in Windows XP for the First Time 2-1Update the Existing Driver in Windows XP 2-3

Chapter 3Install the Driver in Windows 2000Install the Driver in Windows 2000 for the First Time 3-1Update the Existing Driver in Windows 2000 3-4

Chapter 4Install the Driver in Windows 98MeInstall the Driver in Windows 98Me for the First Time 4-1Install the Virtual Backplane Driver 4-3Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

ii Table of Contents

Chapter 5Once You Have Completed the InstallationRegister the EDS File 5-1Configure the ControlNet Communications Driver in RSLinx Software 5-2Connect a SoftLogix Controller to the ControlNet Network 5-4Go Online With RSNetWorx for ControlNet Software 5-7

Chapter 6Interpret the LED Indicators

Chapter 7SpecificationsIndex

Publication 1784-IN003D-EN-P - January 2006

Chapter 1

Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Before you install the card be certain that you

bull know how to install hardware in your computer

bull consult your computerrsquos documentation for hardware installation instructions

Refer to the following publications for more information

bull ControlNet Coax Media Planning and Installation publication CNET-IN002

bull ControlNet Communication Modules in Logix5000 Control Systems publication CNET-UM001

bull SoftLogix5800 System User Manual publication 1789-UM002

For Information On This Topic See Page

Access the Computerrsquos PCI Local Bus Expansion Slots 1-5

Insert the Card Into the Computer 1-6

Connect to the Network 1-7

Connect the Card Directly to the ControlNet Network 1-9

Connect to a Device on the ControlNet Network 1-10

TIP Installation instructions for both the 1784-PCIC and 1784-PCICS cards are exactly the same In most illustrations the 1784-PCIC card is shown

Publication 1784-IN003D-EN-P - January 2006

1-2 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment in overvoltage Category II applications (as defined in IEC publication 60664-1) at altitudes up to 2000 meters without derating

This equipment is considered Group 1 Class A industrial equipment according to IECCISPR Publication 11 Without appropriate precautions there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance

This equipment is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications

NOTE See NEMA Standards publication 250 and IEC publication 60529 as applicable for explanations of the degrees of protection provided by different types of enclosure Also see the appropriate sections in this publication as well as the Industrial Automation Wiring and Grounding Guidelines Allen-Bradley publication 1770-41 for additional installation requirements pertaining to this equipment

ATTENTION Prevent Electrostatic Discharge

This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when you handle this equipment

bull Touch a grounded object to discharge potential static

bull Wear an approved grounding wriststrap

bull Do not touch connectors or pins on component boards

bull Do not touch circuit components inside the equipment

bull Use a static-safe workstation if available

bull Store the equipment in appropriate static-safe packaging when not in use

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-3

European Hazardous Location Approval (1784-PCIC only)

European Zone 2 CertificationThe following applies when the product bears the EEx Marking

This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 949EC

The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres given in Annex II to this Directive The examination and test results are recorded in confidential report No 28 682 010

Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021

IMPORTANT This equipment is not resistant to sunlight or other sources of UV radiation

The secondary of a current transformer shall not be open-circuited when applied in Class I Zone 2 environments

Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I Zone 2 environments

This equipment shall be used within its specified ratings defined by Allen-Bradley

Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40 when applied in Class I Zone 2 environments

Publication 1784-IN003D-EN-P - January 2006

1-4 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

North American Hazardous Location ApprovalThe following information applies when operating this equipment in hazardous locations

Informations sur lrsquoutilisation de cet eacutequipement en environnements dangereux

Products marked CL I DIV 2 GP A B C D are suitable for use in Class I Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code When combining products within a system the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation

Les produits marqueacutes CL I DIV 2 GP A B C D ne conviennent qursquoagrave une utilisation en environnements de Classe I Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livreacute avec des marquages sur sa plaque drsquoidentification qui indiquent le code de tempeacuterature pour les environnements dangereux Lorsque plusieurs produits sont combineacutes dans un systegraveme le code de tempeacuterature le plus deacutefavorable (code de tempeacuterature le plus faible) peut ecirctre utiliseacute pour deacuteterminer le code de tempeacuterature global du systegraveme Les combinaisons drsquoeacutequipements dans le systegraveme sont sujettes agrave inspection par les autoriteacutes locales qualifieacutees au moment de lrsquoinstallation

WARNINGEXPLOSION HAZARD

bull Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous

bull Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this equipment by using screws sliding latches threaded connectors or other means provided with this product

bull Substitution of components may impair suitability for Class I Division 2

bull If this product contains batteries they must be changed only in an area known to be nonhazardous

AVERTISSEMENT RISQUE DrsquoEXPLOSION

bull Couper le courant ou srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher leacutequipement

bull Couper le courant ou sassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher les connecteurs Fixer tous les connecteurs externes relieacutes agrave cet eacutequipement agrave laide de vis loquets coulissants connecteurs fileteacutes ou autres moyens fournis avec ce produit

bull La substitution de composants peut rendre cet eacutequipement inadapteacute agrave une utilisation en environnement de Classe I Division 2

bull Srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de changer les piles

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-5

To install the card you need to

bull access the computerrsquos expansion slots

bull insert the card into the computer

Access the Computerrsquos PCI Local Bus Expansion SlotsTo install the card you must access the computerrsquos PCI local bus expansion slots Follow these general steps or refer to your computerrsquos user guide for further instructions

1 Shut down the host computer

2 Remove the computerrsquos cover

3 Select a vacant PCI local bus expansion slot

4 Loosen the screw (if present) on the back (rear bracket) of the computer

5 Remove the slotrsquos expansion cover

IMPORTANT The cardrsquos dimensions are shown below

42 in 107 cm

65 in 165 cm

31474-M

Publication 1784-IN003D-EN-P - January 2006

1-6 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Insert the Card Into the Computer

1 Handle the card so that you prevent electrostatic discharge

Refer to the Preface of this manual for more information

2 Insert the card into the edge connector and tighten the expansion slot screw (if present)

3 Replace the computer cover

4 Turn on the computer to be certain that it comes up correctly

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codesIf you insert or remove the card while host power is on an electrical arc can occur This could cause an explosion in hazardous location installationsBe sure that power is removed or the area is nonhazardous before proceeding

If the Computer Then

Turns on Go to to the next section Connect to the Network

Hangs up Either the card is not seated correctly in the PCI slot or you have a memory or IO conflict You should

bull remove and reinsert the card into the same PCI slot and try again

bull remove and reinsert the card into a different PCI slot and try again

bull remove all other non-essential cards and try again

If you continue to experience difficulty contact your local Rockwell Automation sales representative or distributor or call Rockwell Automation Technical Support at 4406465800

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-7

Connect to the Network

After you have installed the card you can connect it

bull directly to a ControlNet network which requires a tap (page 1-9)

bull to a device already connected to the ControlNet network (page 1-10)

See Figure 11 on page 1-8 for the connectors and indicators

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes

If you connect or disconnect the ControlNet cable with power applied to this module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations

Be sure that power is removed or the area is nonhazardous before proceeding

Publication 1784-IN003D-EN-P - January 2006

1-8 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 11 1784-PCIC or 1784-PCICS Card (1784-PCIC Card Shown)

ATTENTION Do not connect different ControlNet networks to this card If you attempt to connect a second network to this card your communication system will operate erratically

A

B

Network Access Port (NAP)RJ-45 connector for connecting programming terminals to devices on a ControlNet network

Channel A BNC connectors for connecting directly to ControlNet network

Channel B

Do not connect more than one ControlNet network to this card

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Allen-Bradley1784-PCICControlNet

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9

Connect the Card Directly to the ControlNet NetworkTo connect the card directly to a ControlNet network follow the instructions in these publications

bull ControlNet Coax Tap Installation Instructions publication 1786-IN007

bull ControlNet Coax Media Planning and Installation Manual publication CNET-IN002

Figure 12 Connect the Card Directly to the ControlNet Network

ATTENTION If you connect the product to a cable system that does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left unconnected If the cable system is redundant connect the product so that all devices on the network use the same cable for the same channel That is all channel A connectors connect to one cable all channel B connectors connect to the other cable

TIP If you use a non-redundant cable system all ControlNet devices must be on the same channel channel A

Desktop Host Computer

1784-PCIC or 1784-PCICS

1786-TPR -TPS -TPYR or -TPYS Tap

ControlNet Network

42200

Publication 1784-IN003D-EN-P - January 2006

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 4: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

ii Table of Contents

Chapter 5Once You Have Completed the InstallationRegister the EDS File 5-1Configure the ControlNet Communications Driver in RSLinx Software 5-2Connect a SoftLogix Controller to the ControlNet Network 5-4Go Online With RSNetWorx for ControlNet Software 5-7

Chapter 6Interpret the LED Indicators

Chapter 7SpecificationsIndex

Publication 1784-IN003D-EN-P - January 2006

Chapter 1

Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Before you install the card be certain that you

bull know how to install hardware in your computer

bull consult your computerrsquos documentation for hardware installation instructions

Refer to the following publications for more information

bull ControlNet Coax Media Planning and Installation publication CNET-IN002

bull ControlNet Communication Modules in Logix5000 Control Systems publication CNET-UM001

bull SoftLogix5800 System User Manual publication 1789-UM002

For Information On This Topic See Page

Access the Computerrsquos PCI Local Bus Expansion Slots 1-5

Insert the Card Into the Computer 1-6

Connect to the Network 1-7

Connect the Card Directly to the ControlNet Network 1-9

Connect to a Device on the ControlNet Network 1-10

TIP Installation instructions for both the 1784-PCIC and 1784-PCICS cards are exactly the same In most illustrations the 1784-PCIC card is shown

Publication 1784-IN003D-EN-P - January 2006

1-2 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment in overvoltage Category II applications (as defined in IEC publication 60664-1) at altitudes up to 2000 meters without derating

This equipment is considered Group 1 Class A industrial equipment according to IECCISPR Publication 11 Without appropriate precautions there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance

This equipment is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications

NOTE See NEMA Standards publication 250 and IEC publication 60529 as applicable for explanations of the degrees of protection provided by different types of enclosure Also see the appropriate sections in this publication as well as the Industrial Automation Wiring and Grounding Guidelines Allen-Bradley publication 1770-41 for additional installation requirements pertaining to this equipment

ATTENTION Prevent Electrostatic Discharge

This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when you handle this equipment

bull Touch a grounded object to discharge potential static

bull Wear an approved grounding wriststrap

bull Do not touch connectors or pins on component boards

bull Do not touch circuit components inside the equipment

bull Use a static-safe workstation if available

bull Store the equipment in appropriate static-safe packaging when not in use

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-3

European Hazardous Location Approval (1784-PCIC only)

European Zone 2 CertificationThe following applies when the product bears the EEx Marking

This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 949EC

The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres given in Annex II to this Directive The examination and test results are recorded in confidential report No 28 682 010

Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021

IMPORTANT This equipment is not resistant to sunlight or other sources of UV radiation

The secondary of a current transformer shall not be open-circuited when applied in Class I Zone 2 environments

Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I Zone 2 environments

This equipment shall be used within its specified ratings defined by Allen-Bradley

Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40 when applied in Class I Zone 2 environments

Publication 1784-IN003D-EN-P - January 2006

1-4 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

North American Hazardous Location ApprovalThe following information applies when operating this equipment in hazardous locations

Informations sur lrsquoutilisation de cet eacutequipement en environnements dangereux

Products marked CL I DIV 2 GP A B C D are suitable for use in Class I Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code When combining products within a system the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation

Les produits marqueacutes CL I DIV 2 GP A B C D ne conviennent qursquoagrave une utilisation en environnements de Classe I Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livreacute avec des marquages sur sa plaque drsquoidentification qui indiquent le code de tempeacuterature pour les environnements dangereux Lorsque plusieurs produits sont combineacutes dans un systegraveme le code de tempeacuterature le plus deacutefavorable (code de tempeacuterature le plus faible) peut ecirctre utiliseacute pour deacuteterminer le code de tempeacuterature global du systegraveme Les combinaisons drsquoeacutequipements dans le systegraveme sont sujettes agrave inspection par les autoriteacutes locales qualifieacutees au moment de lrsquoinstallation

WARNINGEXPLOSION HAZARD

bull Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous

bull Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this equipment by using screws sliding latches threaded connectors or other means provided with this product

bull Substitution of components may impair suitability for Class I Division 2

bull If this product contains batteries they must be changed only in an area known to be nonhazardous

AVERTISSEMENT RISQUE DrsquoEXPLOSION

bull Couper le courant ou srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher leacutequipement

bull Couper le courant ou sassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher les connecteurs Fixer tous les connecteurs externes relieacutes agrave cet eacutequipement agrave laide de vis loquets coulissants connecteurs fileteacutes ou autres moyens fournis avec ce produit

bull La substitution de composants peut rendre cet eacutequipement inadapteacute agrave une utilisation en environnement de Classe I Division 2

bull Srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de changer les piles

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-5

To install the card you need to

bull access the computerrsquos expansion slots

bull insert the card into the computer

Access the Computerrsquos PCI Local Bus Expansion SlotsTo install the card you must access the computerrsquos PCI local bus expansion slots Follow these general steps or refer to your computerrsquos user guide for further instructions

1 Shut down the host computer

2 Remove the computerrsquos cover

3 Select a vacant PCI local bus expansion slot

4 Loosen the screw (if present) on the back (rear bracket) of the computer

5 Remove the slotrsquos expansion cover

IMPORTANT The cardrsquos dimensions are shown below

42 in 107 cm

65 in 165 cm

31474-M

Publication 1784-IN003D-EN-P - January 2006

1-6 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Insert the Card Into the Computer

1 Handle the card so that you prevent electrostatic discharge

Refer to the Preface of this manual for more information

2 Insert the card into the edge connector and tighten the expansion slot screw (if present)

3 Replace the computer cover

4 Turn on the computer to be certain that it comes up correctly

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codesIf you insert or remove the card while host power is on an electrical arc can occur This could cause an explosion in hazardous location installationsBe sure that power is removed or the area is nonhazardous before proceeding

If the Computer Then

Turns on Go to to the next section Connect to the Network

Hangs up Either the card is not seated correctly in the PCI slot or you have a memory or IO conflict You should

bull remove and reinsert the card into the same PCI slot and try again

bull remove and reinsert the card into a different PCI slot and try again

bull remove all other non-essential cards and try again

If you continue to experience difficulty contact your local Rockwell Automation sales representative or distributor or call Rockwell Automation Technical Support at 4406465800

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-7

Connect to the Network

After you have installed the card you can connect it

bull directly to a ControlNet network which requires a tap (page 1-9)

bull to a device already connected to the ControlNet network (page 1-10)

See Figure 11 on page 1-8 for the connectors and indicators

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes

If you connect or disconnect the ControlNet cable with power applied to this module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations

Be sure that power is removed or the area is nonhazardous before proceeding

Publication 1784-IN003D-EN-P - January 2006

1-8 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 11 1784-PCIC or 1784-PCICS Card (1784-PCIC Card Shown)

ATTENTION Do not connect different ControlNet networks to this card If you attempt to connect a second network to this card your communication system will operate erratically

A

B

Network Access Port (NAP)RJ-45 connector for connecting programming terminals to devices on a ControlNet network

Channel A BNC connectors for connecting directly to ControlNet network

Channel B

Do not connect more than one ControlNet network to this card

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Allen-Bradley1784-PCICControlNet

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9

Connect the Card Directly to the ControlNet NetworkTo connect the card directly to a ControlNet network follow the instructions in these publications

bull ControlNet Coax Tap Installation Instructions publication 1786-IN007

bull ControlNet Coax Media Planning and Installation Manual publication CNET-IN002

Figure 12 Connect the Card Directly to the ControlNet Network

ATTENTION If you connect the product to a cable system that does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left unconnected If the cable system is redundant connect the product so that all devices on the network use the same cable for the same channel That is all channel A connectors connect to one cable all channel B connectors connect to the other cable

TIP If you use a non-redundant cable system all ControlNet devices must be on the same channel channel A

Desktop Host Computer

1784-PCIC or 1784-PCICS

1786-TPR -TPS -TPYR or -TPYS Tap

ControlNet Network

42200

Publication 1784-IN003D-EN-P - January 2006

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 5: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Chapter 1

Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Before you install the card be certain that you

bull know how to install hardware in your computer

bull consult your computerrsquos documentation for hardware installation instructions

Refer to the following publications for more information

bull ControlNet Coax Media Planning and Installation publication CNET-IN002

bull ControlNet Communication Modules in Logix5000 Control Systems publication CNET-UM001

bull SoftLogix5800 System User Manual publication 1789-UM002

For Information On This Topic See Page

Access the Computerrsquos PCI Local Bus Expansion Slots 1-5

Insert the Card Into the Computer 1-6

Connect to the Network 1-7

Connect the Card Directly to the ControlNet Network 1-9

Connect to a Device on the ControlNet Network 1-10

TIP Installation instructions for both the 1784-PCIC and 1784-PCICS cards are exactly the same In most illustrations the 1784-PCIC card is shown

Publication 1784-IN003D-EN-P - January 2006

1-2 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment in overvoltage Category II applications (as defined in IEC publication 60664-1) at altitudes up to 2000 meters without derating

This equipment is considered Group 1 Class A industrial equipment according to IECCISPR Publication 11 Without appropriate precautions there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance

This equipment is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications

NOTE See NEMA Standards publication 250 and IEC publication 60529 as applicable for explanations of the degrees of protection provided by different types of enclosure Also see the appropriate sections in this publication as well as the Industrial Automation Wiring and Grounding Guidelines Allen-Bradley publication 1770-41 for additional installation requirements pertaining to this equipment

ATTENTION Prevent Electrostatic Discharge

This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when you handle this equipment

bull Touch a grounded object to discharge potential static

bull Wear an approved grounding wriststrap

bull Do not touch connectors or pins on component boards

bull Do not touch circuit components inside the equipment

bull Use a static-safe workstation if available

bull Store the equipment in appropriate static-safe packaging when not in use

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-3

European Hazardous Location Approval (1784-PCIC only)

European Zone 2 CertificationThe following applies when the product bears the EEx Marking

This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 949EC

The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres given in Annex II to this Directive The examination and test results are recorded in confidential report No 28 682 010

Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021

IMPORTANT This equipment is not resistant to sunlight or other sources of UV radiation

The secondary of a current transformer shall not be open-circuited when applied in Class I Zone 2 environments

Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I Zone 2 environments

This equipment shall be used within its specified ratings defined by Allen-Bradley

Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40 when applied in Class I Zone 2 environments

Publication 1784-IN003D-EN-P - January 2006

1-4 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

North American Hazardous Location ApprovalThe following information applies when operating this equipment in hazardous locations

Informations sur lrsquoutilisation de cet eacutequipement en environnements dangereux

Products marked CL I DIV 2 GP A B C D are suitable for use in Class I Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code When combining products within a system the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation

Les produits marqueacutes CL I DIV 2 GP A B C D ne conviennent qursquoagrave une utilisation en environnements de Classe I Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livreacute avec des marquages sur sa plaque drsquoidentification qui indiquent le code de tempeacuterature pour les environnements dangereux Lorsque plusieurs produits sont combineacutes dans un systegraveme le code de tempeacuterature le plus deacutefavorable (code de tempeacuterature le plus faible) peut ecirctre utiliseacute pour deacuteterminer le code de tempeacuterature global du systegraveme Les combinaisons drsquoeacutequipements dans le systegraveme sont sujettes agrave inspection par les autoriteacutes locales qualifieacutees au moment de lrsquoinstallation

WARNINGEXPLOSION HAZARD

bull Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous

bull Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this equipment by using screws sliding latches threaded connectors or other means provided with this product

bull Substitution of components may impair suitability for Class I Division 2

bull If this product contains batteries they must be changed only in an area known to be nonhazardous

AVERTISSEMENT RISQUE DrsquoEXPLOSION

bull Couper le courant ou srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher leacutequipement

bull Couper le courant ou sassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher les connecteurs Fixer tous les connecteurs externes relieacutes agrave cet eacutequipement agrave laide de vis loquets coulissants connecteurs fileteacutes ou autres moyens fournis avec ce produit

bull La substitution de composants peut rendre cet eacutequipement inadapteacute agrave une utilisation en environnement de Classe I Division 2

bull Srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de changer les piles

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-5

To install the card you need to

bull access the computerrsquos expansion slots

bull insert the card into the computer

Access the Computerrsquos PCI Local Bus Expansion SlotsTo install the card you must access the computerrsquos PCI local bus expansion slots Follow these general steps or refer to your computerrsquos user guide for further instructions

1 Shut down the host computer

2 Remove the computerrsquos cover

3 Select a vacant PCI local bus expansion slot

4 Loosen the screw (if present) on the back (rear bracket) of the computer

5 Remove the slotrsquos expansion cover

IMPORTANT The cardrsquos dimensions are shown below

42 in 107 cm

65 in 165 cm

31474-M

Publication 1784-IN003D-EN-P - January 2006

1-6 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Insert the Card Into the Computer

1 Handle the card so that you prevent electrostatic discharge

Refer to the Preface of this manual for more information

2 Insert the card into the edge connector and tighten the expansion slot screw (if present)

3 Replace the computer cover

4 Turn on the computer to be certain that it comes up correctly

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codesIf you insert or remove the card while host power is on an electrical arc can occur This could cause an explosion in hazardous location installationsBe sure that power is removed or the area is nonhazardous before proceeding

If the Computer Then

Turns on Go to to the next section Connect to the Network

Hangs up Either the card is not seated correctly in the PCI slot or you have a memory or IO conflict You should

bull remove and reinsert the card into the same PCI slot and try again

bull remove and reinsert the card into a different PCI slot and try again

bull remove all other non-essential cards and try again

If you continue to experience difficulty contact your local Rockwell Automation sales representative or distributor or call Rockwell Automation Technical Support at 4406465800

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-7

Connect to the Network

After you have installed the card you can connect it

bull directly to a ControlNet network which requires a tap (page 1-9)

bull to a device already connected to the ControlNet network (page 1-10)

See Figure 11 on page 1-8 for the connectors and indicators

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes

If you connect or disconnect the ControlNet cable with power applied to this module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations

Be sure that power is removed or the area is nonhazardous before proceeding

Publication 1784-IN003D-EN-P - January 2006

1-8 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 11 1784-PCIC or 1784-PCICS Card (1784-PCIC Card Shown)

ATTENTION Do not connect different ControlNet networks to this card If you attempt to connect a second network to this card your communication system will operate erratically

A

B

Network Access Port (NAP)RJ-45 connector for connecting programming terminals to devices on a ControlNet network

Channel A BNC connectors for connecting directly to ControlNet network

Channel B

Do not connect more than one ControlNet network to this card

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Allen-Bradley1784-PCICControlNet

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9

Connect the Card Directly to the ControlNet NetworkTo connect the card directly to a ControlNet network follow the instructions in these publications

bull ControlNet Coax Tap Installation Instructions publication 1786-IN007

bull ControlNet Coax Media Planning and Installation Manual publication CNET-IN002

Figure 12 Connect the Card Directly to the ControlNet Network

ATTENTION If you connect the product to a cable system that does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left unconnected If the cable system is redundant connect the product so that all devices on the network use the same cable for the same channel That is all channel A connectors connect to one cable all channel B connectors connect to the other cable

TIP If you use a non-redundant cable system all ControlNet devices must be on the same channel channel A

Desktop Host Computer

1784-PCIC or 1784-PCICS

1786-TPR -TPS -TPYR or -TPYS Tap

ControlNet Network

42200

Publication 1784-IN003D-EN-P - January 2006

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 6: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

1-2 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment in overvoltage Category II applications (as defined in IEC publication 60664-1) at altitudes up to 2000 meters without derating

This equipment is considered Group 1 Class A industrial equipment according to IECCISPR Publication 11 Without appropriate precautions there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance

This equipment is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications

NOTE See NEMA Standards publication 250 and IEC publication 60529 as applicable for explanations of the degrees of protection provided by different types of enclosure Also see the appropriate sections in this publication as well as the Industrial Automation Wiring and Grounding Guidelines Allen-Bradley publication 1770-41 for additional installation requirements pertaining to this equipment

ATTENTION Prevent Electrostatic Discharge

This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when you handle this equipment

bull Touch a grounded object to discharge potential static

bull Wear an approved grounding wriststrap

bull Do not touch connectors or pins on component boards

bull Do not touch circuit components inside the equipment

bull Use a static-safe workstation if available

bull Store the equipment in appropriate static-safe packaging when not in use

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-3

European Hazardous Location Approval (1784-PCIC only)

European Zone 2 CertificationThe following applies when the product bears the EEx Marking

This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 949EC

The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres given in Annex II to this Directive The examination and test results are recorded in confidential report No 28 682 010

Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021

IMPORTANT This equipment is not resistant to sunlight or other sources of UV radiation

The secondary of a current transformer shall not be open-circuited when applied in Class I Zone 2 environments

Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I Zone 2 environments

This equipment shall be used within its specified ratings defined by Allen-Bradley

Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40 when applied in Class I Zone 2 environments

Publication 1784-IN003D-EN-P - January 2006

1-4 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

North American Hazardous Location ApprovalThe following information applies when operating this equipment in hazardous locations

Informations sur lrsquoutilisation de cet eacutequipement en environnements dangereux

Products marked CL I DIV 2 GP A B C D are suitable for use in Class I Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code When combining products within a system the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation

Les produits marqueacutes CL I DIV 2 GP A B C D ne conviennent qursquoagrave une utilisation en environnements de Classe I Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livreacute avec des marquages sur sa plaque drsquoidentification qui indiquent le code de tempeacuterature pour les environnements dangereux Lorsque plusieurs produits sont combineacutes dans un systegraveme le code de tempeacuterature le plus deacutefavorable (code de tempeacuterature le plus faible) peut ecirctre utiliseacute pour deacuteterminer le code de tempeacuterature global du systegraveme Les combinaisons drsquoeacutequipements dans le systegraveme sont sujettes agrave inspection par les autoriteacutes locales qualifieacutees au moment de lrsquoinstallation

WARNINGEXPLOSION HAZARD

bull Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous

bull Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this equipment by using screws sliding latches threaded connectors or other means provided with this product

bull Substitution of components may impair suitability for Class I Division 2

bull If this product contains batteries they must be changed only in an area known to be nonhazardous

AVERTISSEMENT RISQUE DrsquoEXPLOSION

bull Couper le courant ou srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher leacutequipement

bull Couper le courant ou sassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher les connecteurs Fixer tous les connecteurs externes relieacutes agrave cet eacutequipement agrave laide de vis loquets coulissants connecteurs fileteacutes ou autres moyens fournis avec ce produit

bull La substitution de composants peut rendre cet eacutequipement inadapteacute agrave une utilisation en environnement de Classe I Division 2

bull Srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de changer les piles

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-5

To install the card you need to

bull access the computerrsquos expansion slots

bull insert the card into the computer

Access the Computerrsquos PCI Local Bus Expansion SlotsTo install the card you must access the computerrsquos PCI local bus expansion slots Follow these general steps or refer to your computerrsquos user guide for further instructions

1 Shut down the host computer

2 Remove the computerrsquos cover

3 Select a vacant PCI local bus expansion slot

4 Loosen the screw (if present) on the back (rear bracket) of the computer

5 Remove the slotrsquos expansion cover

IMPORTANT The cardrsquos dimensions are shown below

42 in 107 cm

65 in 165 cm

31474-M

Publication 1784-IN003D-EN-P - January 2006

1-6 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Insert the Card Into the Computer

1 Handle the card so that you prevent electrostatic discharge

Refer to the Preface of this manual for more information

2 Insert the card into the edge connector and tighten the expansion slot screw (if present)

3 Replace the computer cover

4 Turn on the computer to be certain that it comes up correctly

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codesIf you insert or remove the card while host power is on an electrical arc can occur This could cause an explosion in hazardous location installationsBe sure that power is removed or the area is nonhazardous before proceeding

If the Computer Then

Turns on Go to to the next section Connect to the Network

Hangs up Either the card is not seated correctly in the PCI slot or you have a memory or IO conflict You should

bull remove and reinsert the card into the same PCI slot and try again

bull remove and reinsert the card into a different PCI slot and try again

bull remove all other non-essential cards and try again

If you continue to experience difficulty contact your local Rockwell Automation sales representative or distributor or call Rockwell Automation Technical Support at 4406465800

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-7

Connect to the Network

After you have installed the card you can connect it

bull directly to a ControlNet network which requires a tap (page 1-9)

bull to a device already connected to the ControlNet network (page 1-10)

See Figure 11 on page 1-8 for the connectors and indicators

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes

If you connect or disconnect the ControlNet cable with power applied to this module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations

Be sure that power is removed or the area is nonhazardous before proceeding

Publication 1784-IN003D-EN-P - January 2006

1-8 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 11 1784-PCIC or 1784-PCICS Card (1784-PCIC Card Shown)

ATTENTION Do not connect different ControlNet networks to this card If you attempt to connect a second network to this card your communication system will operate erratically

A

B

Network Access Port (NAP)RJ-45 connector for connecting programming terminals to devices on a ControlNet network

Channel A BNC connectors for connecting directly to ControlNet network

Channel B

Do not connect more than one ControlNet network to this card

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Allen-Bradley1784-PCICControlNet

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9

Connect the Card Directly to the ControlNet NetworkTo connect the card directly to a ControlNet network follow the instructions in these publications

bull ControlNet Coax Tap Installation Instructions publication 1786-IN007

bull ControlNet Coax Media Planning and Installation Manual publication CNET-IN002

Figure 12 Connect the Card Directly to the ControlNet Network

ATTENTION If you connect the product to a cable system that does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left unconnected If the cable system is redundant connect the product so that all devices on the network use the same cable for the same channel That is all channel A connectors connect to one cable all channel B connectors connect to the other cable

TIP If you use a non-redundant cable system all ControlNet devices must be on the same channel channel A

Desktop Host Computer

1784-PCIC or 1784-PCICS

1786-TPR -TPS -TPYR or -TPYS Tap

ControlNet Network

42200

Publication 1784-IN003D-EN-P - January 2006

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 7: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-3

European Hazardous Location Approval (1784-PCIC only)

European Zone 2 CertificationThe following applies when the product bears the EEx Marking

This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 949EC

The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres given in Annex II to this Directive The examination and test results are recorded in confidential report No 28 682 010

Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021

IMPORTANT This equipment is not resistant to sunlight or other sources of UV radiation

The secondary of a current transformer shall not be open-circuited when applied in Class I Zone 2 environments

Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I Zone 2 environments

This equipment shall be used within its specified ratings defined by Allen-Bradley

Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40 when applied in Class I Zone 2 environments

Publication 1784-IN003D-EN-P - January 2006

1-4 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

North American Hazardous Location ApprovalThe following information applies when operating this equipment in hazardous locations

Informations sur lrsquoutilisation de cet eacutequipement en environnements dangereux

Products marked CL I DIV 2 GP A B C D are suitable for use in Class I Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code When combining products within a system the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation

Les produits marqueacutes CL I DIV 2 GP A B C D ne conviennent qursquoagrave une utilisation en environnements de Classe I Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livreacute avec des marquages sur sa plaque drsquoidentification qui indiquent le code de tempeacuterature pour les environnements dangereux Lorsque plusieurs produits sont combineacutes dans un systegraveme le code de tempeacuterature le plus deacutefavorable (code de tempeacuterature le plus faible) peut ecirctre utiliseacute pour deacuteterminer le code de tempeacuterature global du systegraveme Les combinaisons drsquoeacutequipements dans le systegraveme sont sujettes agrave inspection par les autoriteacutes locales qualifieacutees au moment de lrsquoinstallation

WARNINGEXPLOSION HAZARD

bull Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous

bull Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this equipment by using screws sliding latches threaded connectors or other means provided with this product

bull Substitution of components may impair suitability for Class I Division 2

bull If this product contains batteries they must be changed only in an area known to be nonhazardous

AVERTISSEMENT RISQUE DrsquoEXPLOSION

bull Couper le courant ou srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher leacutequipement

bull Couper le courant ou sassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher les connecteurs Fixer tous les connecteurs externes relieacutes agrave cet eacutequipement agrave laide de vis loquets coulissants connecteurs fileteacutes ou autres moyens fournis avec ce produit

bull La substitution de composants peut rendre cet eacutequipement inadapteacute agrave une utilisation en environnement de Classe I Division 2

bull Srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de changer les piles

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-5

To install the card you need to

bull access the computerrsquos expansion slots

bull insert the card into the computer

Access the Computerrsquos PCI Local Bus Expansion SlotsTo install the card you must access the computerrsquos PCI local bus expansion slots Follow these general steps or refer to your computerrsquos user guide for further instructions

1 Shut down the host computer

2 Remove the computerrsquos cover

3 Select a vacant PCI local bus expansion slot

4 Loosen the screw (if present) on the back (rear bracket) of the computer

5 Remove the slotrsquos expansion cover

IMPORTANT The cardrsquos dimensions are shown below

42 in 107 cm

65 in 165 cm

31474-M

Publication 1784-IN003D-EN-P - January 2006

1-6 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Insert the Card Into the Computer

1 Handle the card so that you prevent electrostatic discharge

Refer to the Preface of this manual for more information

2 Insert the card into the edge connector and tighten the expansion slot screw (if present)

3 Replace the computer cover

4 Turn on the computer to be certain that it comes up correctly

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codesIf you insert or remove the card while host power is on an electrical arc can occur This could cause an explosion in hazardous location installationsBe sure that power is removed or the area is nonhazardous before proceeding

If the Computer Then

Turns on Go to to the next section Connect to the Network

Hangs up Either the card is not seated correctly in the PCI slot or you have a memory or IO conflict You should

bull remove and reinsert the card into the same PCI slot and try again

bull remove and reinsert the card into a different PCI slot and try again

bull remove all other non-essential cards and try again

If you continue to experience difficulty contact your local Rockwell Automation sales representative or distributor or call Rockwell Automation Technical Support at 4406465800

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-7

Connect to the Network

After you have installed the card you can connect it

bull directly to a ControlNet network which requires a tap (page 1-9)

bull to a device already connected to the ControlNet network (page 1-10)

See Figure 11 on page 1-8 for the connectors and indicators

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes

If you connect or disconnect the ControlNet cable with power applied to this module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations

Be sure that power is removed or the area is nonhazardous before proceeding

Publication 1784-IN003D-EN-P - January 2006

1-8 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 11 1784-PCIC or 1784-PCICS Card (1784-PCIC Card Shown)

ATTENTION Do not connect different ControlNet networks to this card If you attempt to connect a second network to this card your communication system will operate erratically

A

B

Network Access Port (NAP)RJ-45 connector for connecting programming terminals to devices on a ControlNet network

Channel A BNC connectors for connecting directly to ControlNet network

Channel B

Do not connect more than one ControlNet network to this card

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Allen-Bradley1784-PCICControlNet

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9

Connect the Card Directly to the ControlNet NetworkTo connect the card directly to a ControlNet network follow the instructions in these publications

bull ControlNet Coax Tap Installation Instructions publication 1786-IN007

bull ControlNet Coax Media Planning and Installation Manual publication CNET-IN002

Figure 12 Connect the Card Directly to the ControlNet Network

ATTENTION If you connect the product to a cable system that does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left unconnected If the cable system is redundant connect the product so that all devices on the network use the same cable for the same channel That is all channel A connectors connect to one cable all channel B connectors connect to the other cable

TIP If you use a non-redundant cable system all ControlNet devices must be on the same channel channel A

Desktop Host Computer

1784-PCIC or 1784-PCICS

1786-TPR -TPS -TPYR or -TPYS Tap

ControlNet Network

42200

Publication 1784-IN003D-EN-P - January 2006

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 8: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

1-4 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

North American Hazardous Location ApprovalThe following information applies when operating this equipment in hazardous locations

Informations sur lrsquoutilisation de cet eacutequipement en environnements dangereux

Products marked CL I DIV 2 GP A B C D are suitable for use in Class I Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code When combining products within a system the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation

Les produits marqueacutes CL I DIV 2 GP A B C D ne conviennent qursquoagrave une utilisation en environnements de Classe I Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livreacute avec des marquages sur sa plaque drsquoidentification qui indiquent le code de tempeacuterature pour les environnements dangereux Lorsque plusieurs produits sont combineacutes dans un systegraveme le code de tempeacuterature le plus deacutefavorable (code de tempeacuterature le plus faible) peut ecirctre utiliseacute pour deacuteterminer le code de tempeacuterature global du systegraveme Les combinaisons drsquoeacutequipements dans le systegraveme sont sujettes agrave inspection par les autoriteacutes locales qualifieacutees au moment de lrsquoinstallation

WARNINGEXPLOSION HAZARD

bull Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous

bull Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this equipment by using screws sliding latches threaded connectors or other means provided with this product

bull Substitution of components may impair suitability for Class I Division 2

bull If this product contains batteries they must be changed only in an area known to be nonhazardous

AVERTISSEMENT RISQUE DrsquoEXPLOSION

bull Couper le courant ou srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher leacutequipement

bull Couper le courant ou sassurer que lrsquoenvironnement est classeacute non dangereux avant de deacutebrancher les connecteurs Fixer tous les connecteurs externes relieacutes agrave cet eacutequipement agrave laide de vis loquets coulissants connecteurs fileteacutes ou autres moyens fournis avec ce produit

bull La substitution de composants peut rendre cet eacutequipement inadapteacute agrave une utilisation en environnement de Classe I Division 2

bull Srsquoassurer que lrsquoenvironnement est classeacute non dangereux avant de changer les piles

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-5

To install the card you need to

bull access the computerrsquos expansion slots

bull insert the card into the computer

Access the Computerrsquos PCI Local Bus Expansion SlotsTo install the card you must access the computerrsquos PCI local bus expansion slots Follow these general steps or refer to your computerrsquos user guide for further instructions

1 Shut down the host computer

2 Remove the computerrsquos cover

3 Select a vacant PCI local bus expansion slot

4 Loosen the screw (if present) on the back (rear bracket) of the computer

5 Remove the slotrsquos expansion cover

IMPORTANT The cardrsquos dimensions are shown below

42 in 107 cm

65 in 165 cm

31474-M

Publication 1784-IN003D-EN-P - January 2006

1-6 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Insert the Card Into the Computer

1 Handle the card so that you prevent electrostatic discharge

Refer to the Preface of this manual for more information

2 Insert the card into the edge connector and tighten the expansion slot screw (if present)

3 Replace the computer cover

4 Turn on the computer to be certain that it comes up correctly

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codesIf you insert or remove the card while host power is on an electrical arc can occur This could cause an explosion in hazardous location installationsBe sure that power is removed or the area is nonhazardous before proceeding

If the Computer Then

Turns on Go to to the next section Connect to the Network

Hangs up Either the card is not seated correctly in the PCI slot or you have a memory or IO conflict You should

bull remove and reinsert the card into the same PCI slot and try again

bull remove and reinsert the card into a different PCI slot and try again

bull remove all other non-essential cards and try again

If you continue to experience difficulty contact your local Rockwell Automation sales representative or distributor or call Rockwell Automation Technical Support at 4406465800

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-7

Connect to the Network

After you have installed the card you can connect it

bull directly to a ControlNet network which requires a tap (page 1-9)

bull to a device already connected to the ControlNet network (page 1-10)

See Figure 11 on page 1-8 for the connectors and indicators

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes

If you connect or disconnect the ControlNet cable with power applied to this module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations

Be sure that power is removed or the area is nonhazardous before proceeding

Publication 1784-IN003D-EN-P - January 2006

1-8 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 11 1784-PCIC or 1784-PCICS Card (1784-PCIC Card Shown)

ATTENTION Do not connect different ControlNet networks to this card If you attempt to connect a second network to this card your communication system will operate erratically

A

B

Network Access Port (NAP)RJ-45 connector for connecting programming terminals to devices on a ControlNet network

Channel A BNC connectors for connecting directly to ControlNet network

Channel B

Do not connect more than one ControlNet network to this card

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Allen-Bradley1784-PCICControlNet

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9

Connect the Card Directly to the ControlNet NetworkTo connect the card directly to a ControlNet network follow the instructions in these publications

bull ControlNet Coax Tap Installation Instructions publication 1786-IN007

bull ControlNet Coax Media Planning and Installation Manual publication CNET-IN002

Figure 12 Connect the Card Directly to the ControlNet Network

ATTENTION If you connect the product to a cable system that does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left unconnected If the cable system is redundant connect the product so that all devices on the network use the same cable for the same channel That is all channel A connectors connect to one cable all channel B connectors connect to the other cable

TIP If you use a non-redundant cable system all ControlNet devices must be on the same channel channel A

Desktop Host Computer

1784-PCIC or 1784-PCICS

1786-TPR -TPS -TPYR or -TPYS Tap

ControlNet Network

42200

Publication 1784-IN003D-EN-P - January 2006

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 9: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-5

To install the card you need to

bull access the computerrsquos expansion slots

bull insert the card into the computer

Access the Computerrsquos PCI Local Bus Expansion SlotsTo install the card you must access the computerrsquos PCI local bus expansion slots Follow these general steps or refer to your computerrsquos user guide for further instructions

1 Shut down the host computer

2 Remove the computerrsquos cover

3 Select a vacant PCI local bus expansion slot

4 Loosen the screw (if present) on the back (rear bracket) of the computer

5 Remove the slotrsquos expansion cover

IMPORTANT The cardrsquos dimensions are shown below

42 in 107 cm

65 in 165 cm

31474-M

Publication 1784-IN003D-EN-P - January 2006

1-6 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Insert the Card Into the Computer

1 Handle the card so that you prevent electrostatic discharge

Refer to the Preface of this manual for more information

2 Insert the card into the edge connector and tighten the expansion slot screw (if present)

3 Replace the computer cover

4 Turn on the computer to be certain that it comes up correctly

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codesIf you insert or remove the card while host power is on an electrical arc can occur This could cause an explosion in hazardous location installationsBe sure that power is removed or the area is nonhazardous before proceeding

If the Computer Then

Turns on Go to to the next section Connect to the Network

Hangs up Either the card is not seated correctly in the PCI slot or you have a memory or IO conflict You should

bull remove and reinsert the card into the same PCI slot and try again

bull remove and reinsert the card into a different PCI slot and try again

bull remove all other non-essential cards and try again

If you continue to experience difficulty contact your local Rockwell Automation sales representative or distributor or call Rockwell Automation Technical Support at 4406465800

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-7

Connect to the Network

After you have installed the card you can connect it

bull directly to a ControlNet network which requires a tap (page 1-9)

bull to a device already connected to the ControlNet network (page 1-10)

See Figure 11 on page 1-8 for the connectors and indicators

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes

If you connect or disconnect the ControlNet cable with power applied to this module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations

Be sure that power is removed or the area is nonhazardous before proceeding

Publication 1784-IN003D-EN-P - January 2006

1-8 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 11 1784-PCIC or 1784-PCICS Card (1784-PCIC Card Shown)

ATTENTION Do not connect different ControlNet networks to this card If you attempt to connect a second network to this card your communication system will operate erratically

A

B

Network Access Port (NAP)RJ-45 connector for connecting programming terminals to devices on a ControlNet network

Channel A BNC connectors for connecting directly to ControlNet network

Channel B

Do not connect more than one ControlNet network to this card

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Allen-Bradley1784-PCICControlNet

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9

Connect the Card Directly to the ControlNet NetworkTo connect the card directly to a ControlNet network follow the instructions in these publications

bull ControlNet Coax Tap Installation Instructions publication 1786-IN007

bull ControlNet Coax Media Planning and Installation Manual publication CNET-IN002

Figure 12 Connect the Card Directly to the ControlNet Network

ATTENTION If you connect the product to a cable system that does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left unconnected If the cable system is redundant connect the product so that all devices on the network use the same cable for the same channel That is all channel A connectors connect to one cable all channel B connectors connect to the other cable

TIP If you use a non-redundant cable system all ControlNet devices must be on the same channel channel A

Desktop Host Computer

1784-PCIC or 1784-PCICS

1786-TPR -TPS -TPYR or -TPYS Tap

ControlNet Network

42200

Publication 1784-IN003D-EN-P - January 2006

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 10: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

1-6 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Insert the Card Into the Computer

1 Handle the card so that you prevent electrostatic discharge

Refer to the Preface of this manual for more information

2 Insert the card into the edge connector and tighten the expansion slot screw (if present)

3 Replace the computer cover

4 Turn on the computer to be certain that it comes up correctly

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codesIf you insert or remove the card while host power is on an electrical arc can occur This could cause an explosion in hazardous location installationsBe sure that power is removed or the area is nonhazardous before proceeding

If the Computer Then

Turns on Go to to the next section Connect to the Network

Hangs up Either the card is not seated correctly in the PCI slot or you have a memory or IO conflict You should

bull remove and reinsert the card into the same PCI slot and try again

bull remove and reinsert the card into a different PCI slot and try again

bull remove all other non-essential cards and try again

If you continue to experience difficulty contact your local Rockwell Automation sales representative or distributor or call Rockwell Automation Technical Support at 4406465800

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-7

Connect to the Network

After you have installed the card you can connect it

bull directly to a ControlNet network which requires a tap (page 1-9)

bull to a device already connected to the ControlNet network (page 1-10)

See Figure 11 on page 1-8 for the connectors and indicators

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes

If you connect or disconnect the ControlNet cable with power applied to this module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations

Be sure that power is removed or the area is nonhazardous before proceeding

Publication 1784-IN003D-EN-P - January 2006

1-8 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 11 1784-PCIC or 1784-PCICS Card (1784-PCIC Card Shown)

ATTENTION Do not connect different ControlNet networks to this card If you attempt to connect a second network to this card your communication system will operate erratically

A

B

Network Access Port (NAP)RJ-45 connector for connecting programming terminals to devices on a ControlNet network

Channel A BNC connectors for connecting directly to ControlNet network

Channel B

Do not connect more than one ControlNet network to this card

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Allen-Bradley1784-PCICControlNet

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9

Connect the Card Directly to the ControlNet NetworkTo connect the card directly to a ControlNet network follow the instructions in these publications

bull ControlNet Coax Tap Installation Instructions publication 1786-IN007

bull ControlNet Coax Media Planning and Installation Manual publication CNET-IN002

Figure 12 Connect the Card Directly to the ControlNet Network

ATTENTION If you connect the product to a cable system that does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left unconnected If the cable system is redundant connect the product so that all devices on the network use the same cable for the same channel That is all channel A connectors connect to one cable all channel B connectors connect to the other cable

TIP If you use a non-redundant cable system all ControlNet devices must be on the same channel channel A

Desktop Host Computer

1784-PCIC or 1784-PCICS

1786-TPR -TPS -TPYR or -TPYS Tap

ControlNet Network

42200

Publication 1784-IN003D-EN-P - January 2006

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 11: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-7

Connect to the Network

After you have installed the card you can connect it

bull directly to a ControlNet network which requires a tap (page 1-9)

bull to a device already connected to the ControlNet network (page 1-10)

See Figure 11 on page 1-8 for the connectors and indicators

WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes

If you connect or disconnect the ControlNet cable with power applied to this module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations

Be sure that power is removed or the area is nonhazardous before proceeding

Publication 1784-IN003D-EN-P - January 2006

1-8 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 11 1784-PCIC or 1784-PCICS Card (1784-PCIC Card Shown)

ATTENTION Do not connect different ControlNet networks to this card If you attempt to connect a second network to this card your communication system will operate erratically

A

B

Network Access Port (NAP)RJ-45 connector for connecting programming terminals to devices on a ControlNet network

Channel A BNC connectors for connecting directly to ControlNet network

Channel B

Do not connect more than one ControlNet network to this card

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Allen-Bradley1784-PCICControlNet

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9

Connect the Card Directly to the ControlNet NetworkTo connect the card directly to a ControlNet network follow the instructions in these publications

bull ControlNet Coax Tap Installation Instructions publication 1786-IN007

bull ControlNet Coax Media Planning and Installation Manual publication CNET-IN002

Figure 12 Connect the Card Directly to the ControlNet Network

ATTENTION If you connect the product to a cable system that does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left unconnected If the cable system is redundant connect the product so that all devices on the network use the same cable for the same channel That is all channel A connectors connect to one cable all channel B connectors connect to the other cable

TIP If you use a non-redundant cable system all ControlNet devices must be on the same channel channel A

Desktop Host Computer

1784-PCIC or 1784-PCICS

1786-TPR -TPS -TPYR or -TPYS Tap

ControlNet Network

42200

Publication 1784-IN003D-EN-P - January 2006

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 12: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

1-8 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 11 1784-PCIC or 1784-PCICS Card (1784-PCIC Card Shown)

ATTENTION Do not connect different ControlNet networks to this card If you attempt to connect a second network to this card your communication system will operate erratically

A

B

Network Access Port (NAP)RJ-45 connector for connecting programming terminals to devices on a ControlNet network

Channel A BNC connectors for connecting directly to ControlNet network

Channel B

Do not connect more than one ControlNet network to this card

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Allen-Bradley1784-PCICControlNet

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9

Connect the Card Directly to the ControlNet NetworkTo connect the card directly to a ControlNet network follow the instructions in these publications

bull ControlNet Coax Tap Installation Instructions publication 1786-IN007

bull ControlNet Coax Media Planning and Installation Manual publication CNET-IN002

Figure 12 Connect the Card Directly to the ControlNet Network

ATTENTION If you connect the product to a cable system that does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left unconnected If the cable system is redundant connect the product so that all devices on the network use the same cable for the same channel That is all channel A connectors connect to one cable all channel B connectors connect to the other cable

TIP If you use a non-redundant cable system all ControlNet devices must be on the same channel channel A

Desktop Host Computer

1784-PCIC or 1784-PCICS

1786-TPR -TPS -TPYR or -TPYS Tap

ControlNet Network

42200

Publication 1784-IN003D-EN-P - January 2006

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 13: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-9

Connect the Card Directly to the ControlNet NetworkTo connect the card directly to a ControlNet network follow the instructions in these publications

bull ControlNet Coax Tap Installation Instructions publication 1786-IN007

bull ControlNet Coax Media Planning and Installation Manual publication CNET-IN002

Figure 12 Connect the Card Directly to the ControlNet Network

ATTENTION If you connect the product to a cable system that does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left unconnected If the cable system is redundant connect the product so that all devices on the network use the same cable for the same channel That is all channel A connectors connect to one cable all channel B connectors connect to the other cable

TIP If you use a non-redundant cable system all ControlNet devices must be on the same channel channel A

Desktop Host Computer

1784-PCIC or 1784-PCICS

1786-TPR -TPS -TPYR or -TPYS Tap

ControlNet Network

42200

Publication 1784-IN003D-EN-P - January 2006

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 14: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

1-10 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Connect to a Device on the ControlNet NetworkThe 1786-CP cable (Figure 13) connects a host computer to another ControlNet device It has two RJ-45 8-pin connectors

Figure 13 1786-CP cable

See Tables 11 and 12 for the wiring for the 1786-CP cable

ATTENTION Use only the 1786-CP cable when you connect a programming terminal to the network through the Network Acces Port (NAP) If you use a different cable it could result in possible network failures or product damage

Table 11 Wiring For 1786-CP Cable (Connector 1)

Connector 1

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTTX-H Transmit Data High

4 PTTX-L Transmit Data Low

5 PTRX-L Receive Data Low

6 PTRX-H Receive Data High

7 NC No Connection

8 ISO-GND Isolated Ground

RJ-45 8-pin Connectors

1786-CP Cable

30124-m

Connector 1 Connector 2

Publication 1784-IN003D-EN-P - January 2006

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 15: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Install the 1784-PCIC or 1784-PCICS Communication Interface Card 1-11

When you use the RJ-45 connector you can connect the card to a ControlNet network without a tap through the Network Access Port (or NAP) of a programmable controller IO adapter or other ControlNet compliant devices

See Figure 14 and Figure 15

Table 12 Wiring For 1786-CP Cable (Connector 2)

Connector 2

Wire Number Signal Mnemonic Signal Name

1 ISO-GND Isolated Ground

2 NC No Connection

3 PTRX-H Receive Data High

4 PTRX-L Receive Data Low

5 PTTX-L Transmit Data Low

6 PTTX-H Transmit Data High

7 NC No Connection

8 ISO-GND Isolated Ground

Publication 1784-IN003D-EN-P - January 2006

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 16: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

1-12 Install the 1784-PCIC or 1784-PCICS Communication Interface Card

Figure 14 Connect a Programming Terminal to a ControlNet Network Through Another ControlNet Device

Figure 15 Connect a Portable Host Computer to the ControlNet Network Through the 1784-PCIC or 1784-PCICS Card

ATTENTION If a SoftLogix5800 processor is running on the computer containing the 1784-PCIC or 1784-PCICS card do not use the 1786-CP cable to connect the card to the ControlNet network Instead connect the card directly to the ControlNet network as shown in Figure 12

1 The 1786-CP cable can be plugged into any ControlNet productrsquos NAP to provide programming capability on the ControlNet network When you connect a programming terminal through this cable it is counted as a node and must have a unique address

ControlNet Network

Programming Terminal

1784-PCIC or 1784-PCICS 1786-CP Cable1

ControlNet Product

42199

Portable Host Computer

1784-PCIC or 1784-PCICS1784-PCC

Desktop Host Computer

1784-PCC1 Cable

ControlNet Network

42198

Publication 1784-IN003D-EN-P - January 2006

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 17: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Chapter 2

Install the Driver in Windows XP

Install the Driver in Windows XP for the First TimeFollow these steps to install the driver for the first time on a personal computer running Windows XP

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

For Information On This Topic See Page

Install the Driver in Windows XP for the First Time 2-1

Update the Existing Driver in Windows XP 2-3

Publication 1784-IN003D-EN-P - January 2006

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 18: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

2-2 Install the Driver in Windows XP

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

4 Select the Install from a list or specific location (Advanced) radio button

5 Click Next

6 On the screen that appears click the Search for the best driver in these locations radio button

7 Check the Include this location in the search checkbox

8 Uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 19: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Install the Driver in Windows XP 2-3

9 Click Browse

10 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

11 Click OK

12 Click Next

13 Click Finish

The driver is now ready to use Go on to Chapter 5

Update the Existing Driver in Windows XPFollow these steps to update the existing device driver on a personal computer running Windows XP

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

IMPORTANT If prompted to overwrite existing files click Yes

IMPORTANT During the update procedure communication through the card will be disrupted

Publication 1784-IN003D-EN-P - January 2006

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 20: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

2-4 Install the Driver in Windows XP

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Update Driver

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 21: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Install the Driver in Windows XP 2-5

The Hardware Update Wizard appears

9 Select the Install from a list or specific location (Advanced) radio button

10 Click Next

11 On the screen that appears click the Donrsquot search I will choose the best driver to install radio button

12 Click Next

13 Click Have Disk

14 Click Browse

Publication 1784-IN003D-EN-P - January 2006

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 22: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

2-6 Install the Driver in Windows XP

15 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

16 Click Open

17 Click OK

18 Select A-B 1784-PCIC(S) to highlight it

19 Click Next

20 Click Finish

21 Close the Device Manager screen

22 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 23: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Chapter 3

Install the Driver in Windows 2000

Install the Driver in Windows 2000 for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 2000

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Found New Hardware Wizard

For Information On This Topic See Page

Install the Driver in Windows 2000 for the First Time 3-1

Update the Existing Driver in Windows 2000 3-4

Publication 1784-IN003D-EN-P - January 2006

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 24: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

3-2 Install the Driver in Windows 2000

4 Click Next

5 Click the Search for a suitable driver for my device (recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 25: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Install the Driver in Windows 2000 3-3

8 Click Next

9 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

10 Click Open

11 Click OK

12 Click Next to install the new driver

13 Click Finish to close the Found New Hardware Wizard

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 26: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

3-4 Install the Driver in Windows 2000

Update the Existing Driver in Windows 2000Follow these steps to update the existing device driver on a personal computer running Windows 2000

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click Manage

4 In the left window pane click the + to the left of System Tools to open it

5 Under System Tools click Device Manager

6 In the right window pane click the + to the left of A-B Virtual Backplane to expand it

7 Right-click A-B 1784-PCIC(S)

8 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 27: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Install the Driver in Windows 2000 3-5

9 Click the Driver tab

10 Click Update Driver

The Upgrade Device Driver Wizard appears

11 Click Next

12 Click the Display a list of the known drivers for this device so I can choose a specific driver radio button

Publication 1784-IN003D-EN-P - January 2006

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 28: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

3-6 Install the Driver in Windows 2000

13 Click Next

14 Click Have Disk

15 Click Browse

16 Navigate to the folder that contains the installation files

The installation files can be found in the DriversWin2K_WinXP folder on the 1784-PCIC(S) Driver CD-ROM

17 Click Open

18 Click OK

19 Select A-B 1784-PCIC(S) to highlight it

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 29: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Install the Driver in Windows 2000 3-7

20 Click Next

21 Click Next to install the new driver

22 Click Finish

23 Close the A-B 1784-PCIC(S) Properties screen

24 Close the Device Manager screen

25 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 30: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

3-8 Install the Driver in Windows 2000

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 31: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Chapter 4

Install the Driver in Windows 98Me

Install the Driver in Windows 98Me for the First Time Follow these steps to install the driver for the first time on a personal computer running Windows 98Me

1 Shut down the computer

2 Insert the 1784-PCIC or 1784-PCICS card into an unused PCI slot

Refer to Chapter 1 for installation information

3 Restart the computer

After the computer restarts the operating system detects the new PCI card and displays the Add New Hardware wizard

For Information On This Topic See Page

Install the Driver in Windows 98Me for the First Time 4-1

Install the Virtual Backplane Driver 4-3

Update the Existing Driver in Windows 98Me 4-5

Publication 1784-IN003D-EN-P - January 2006

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 32: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

4-2 Install the Driver in Windows 98Me

4 Click Next

5 Click the Search for the best driver for your device (Recommended) radio button

6 Click Next

7 Check the Specify a location checkbox and uncheck the remaining checkboxes

8 Click Browse and navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 33: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Install the Driver in Windows 98Me 4-3

9 Click OK

10 Click Next

11 Click Next

12 Click Finish

Install the Virtual Backplane DriverSo that the 1784-PCICS drivers work properly after you install them for the first time you must install the Virtual Backplane Driver Follow this procedure to install the Virtual Backplane Driver

1 Select Start rArrSettings rArrControl Panel

2 Double-click Add New Hardware

You see the Add New Hardware Wizard

3 Click Next

Windows searches for the new Plug and Play devices

4 Click Next

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 34: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

4-4 Install the Driver in Windows 98Me

5 Click the No I want to select the hardware from a list radio button

6 Click Next

7 Select A-B Virtual Backplane from the list of hardware types

8 Click Next

9 Select A-B Virtual Backplane from the list of models

10 Click Next

11 Click Finish

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 35: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Install the Driver in Windows 98Me 4-5

Update the Existing Driver in Windows 98MeFollow these steps to update the existing device driver on a personal computer running Windows 98Me

1 If you are browsing with RSLinx software close RSWho

2 Right-click My Computer

3 Click on the Device Manager tab

4 In the left window pane click the + to the left of A-B Virtual Backplane to expand it

5 Right-click on A-B 1784-PCIC(S)

6 Click Properties

IMPORTANT During the update procedure communication through the card will be disrupted

TIP If you see more than one A-B 1784-PCIC(S) entry perform the update on only one of the entries

Publication 1784-IN003D-EN-P - January 2006

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 36: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

4-6 Install the Driver in Windows 98Me

7 Click the Driver tab

8 Click Update Driver

9 Click Next

10 Click the Display a list of all the drivers in a specific location so you can select the driver you want radio button

Publication 1784-IN003D-EN-P - January 2006

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 37: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Install the Driver in Windows 98Me 4-7

11 Click Next

12 Click Have Disk

13 Click Browse then navigate to the folder that contains the installation files

The installation files can be found in the DriversWin98 folder on the 1784-PCIC(S) Driver CD-ROM

14 Click OK

15 Click OK

16 Select A-B 1784-PCIC(S) to highlight it

17 Click Next

18 Click Next

19 Click Next

20 Click Finish

IMPORTANT If prompted to overwrite existing files click Yes

Publication 1784-IN003D-EN-P - January 2006

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 38: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

4-8 Install the Driver in Windows 98Me

21 Close the A-B 1784-PCIC(S) Properties screen

22 Close the System Properties screen

23 Shut down and restart the computer

The driver is now ready to use Go on to Chapter 5

Publication 1784-IN003D-EN-P - January 2006

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 39: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Chapter 5

Once You Have Completed the Installation

Once you have installed the drivers you can do the following

Register the EDS FileThe EDS files can be found in the EDS Files folder on the 1784-PCIC(S) Driver CD-ROM or they can be downloaded from httpwwwabcomnetworkseds

Use the EDS wizard in either RSLinx or RSNetWorx for ControlNet software to register these EDS files for the 1784-PCIC or 1784-PCICS card

bull In Windows select Start rArrPrograms rArrRockwell Software rArrRSLinx Tools rArrEDS Hardware Installation Tool

bull In RSNetWorx for ControlNet software select Tools rArrEDS Wizard

For Information On This Topic See Page

Register the EDS File 5-1

Configure the ControlNet Communications Driver in RSLinx Software 5-2

Connect a SoftLogix Controller to the ControlNet Network 5-4

Go Online With RSNetWorx for ControlNet Software 5-7

Catalog Number EDS File

1784-PCIC 0001000C00490400eds

1784-PCICS 0001000C003F0400eds

Publication 1784-IN003D-EN-P - January 2006

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 40: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

5-2 Once You Have Completed the Installation

Configure the ControlNet Communications Driver in RSLinx SoftwareFollow this procedure to configure the ControlNet communication driver

1 Install RSLinx software version 24200 or later on your computer

2 In RSLinx software select Configure Drivers

3 Select a driver for ControlNet devices

IMPORTANT Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller For information on configuring the ControlNet card for use with SoftLogix5800 controllers refer to page 5-4

A Click Communications

B Click Configure Drivers

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 41: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Once You Have Completed the Installation 5-3

In the example below we chose the 1784-PCICS card

4 Name the new ControlNet driver

A Use the pull-down menu to select the ControlNet driver

B Click Add New

A Name the driver This example shows the default name (AB_PCIC-1) that RSLinx software uses

B Click OK

Publication 1784-IN003D-EN-P - January 2006

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 42: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

5-4 Once You Have Completed the Installation

5 After you create the driver configure it to correspond to the ControlNet module within your computer

The driver is now available in RSLinx software You can browse the network by expanding ControlNet port on the desired 1784-PCIC or 1784-PCICS communication card

Connect a SoftLogix Controller to the ControlNet NetworkThe SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows 2000 or Windows XP environment When using this controller you must install the SoftLogix5800 Chassis monitor a virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers

Before you can connect the SoftLogix system to the ControlNet network you must create the 1784-PCIC or 1784-PCICS card as part of the SoftLogix chassis

1 In the SoftLogix chassis monitor create a New Module

A If multiple cards are located in your computer choose the correct one

B Make sure you use the correct Network Address

C Click OK

A Click Slot

B Click Create Module

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 43: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Once You Have Completed the Installation 5-5

2 Select the 1784-PCIC or 1784-PCICS card

3 Select the serial number of the 1784-PCIC or 1784-PCICS card you want

If you previously configured the card that you selected by serial number the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot)

4 Configure the card

A Select the ControlNet card

B Specify the virtual backplane slot number

C Click OK

A If multiple cards are located in your computer choose the serial number of the correct one

B Click Next

A Specify the node address on the ControlNet network

B Enter the label name for the card (this is the name you wrote on the label of the card to help you identify the card from others in the same computer)

C Click Finish

Publication 1784-IN003D-EN-P - January 2006

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 44: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

5-6 Once You Have Completed the Installation

You can specify any slot number greater than 0 for the communication card RSLinx software resides in slot 0

By creating the card in the virtual chassis you configure the communication driver information needed by the SoftLogix controller Do not use RSLinx software to install the ControlNet communication driver to the same card installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix chassis monitor

Instead configure a Virtual Backplane driver in RSLinx software

5 Select Communications rArrConfigure Drivers

6 Under Available Driver Types select Virtual Backplane (SoftLogix 58xx)

7 Click Add New

8 Enter a name for the driver

9 Click OK

10 Click on Close

The Virtual Backplane driver is now ready to use

After you add the card to the chassis monitor and configure a Virtual Backplane driver you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired 1784-PCIC or 1784-PCICS communication card Browsing the ControlNet network through the Virtual Backplane driver provides the same functionality as the RSLinx driver

Publication 1784-IN003D-EN-P - January 2006

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 45: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Once You Have Completed the Installation 5-7

Go Online With RSNetWorx for ControlNet SoftwareWhen going online with RSNetWorx for ControlNet software via the 1784-PCIC or 1784-PCICS card select Port A ControlNet under the card in the Virtual Chassis

Do not select AB-PCIC-1 ControlNet

Publication 1784-IN003D-EN-P - January 2006

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 46: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

5-8 Once You Have Completed the Installation

Notes

Publication 1784-IN003D-EN-P - January 2006

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 47: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Chapter 6

Interpret the LED Indicators

The LED indicators on the card give you information about the card and the network when yoursquore connected via the BNC connectors Table 61 outlines the states and explains what each state means to you and the action you should take if any to correct that state

IMPORTANT When you connect the module to a ControlNet network using only the Network Acces Port (NAP) the LEDs are meaningless

A

B

Redundant Media BNC Connectors

Diagnostic Status Indicators

42281

Publication 1784-IN003D-EN-P - January 2006

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 48: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

6-2 Interpret the LED Indicators

bull Steady - indicator is on continuously in the defined state

bull Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together) The two indicators are always in opposite states out of phase

bull Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other) If both indicators flash they must flash together in phase

Table 61 ControlNet status interpretation

A and BCause Action

Off bull No power bull None or apply power to the personal computer

bull 1784-PCIC or 1784-PCICS driver not started

bull Start RSLinx software

bull Verify that the 1784-PCIC or 1784-PCICS driver has been configured properly in RSLinx software

bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Publication 1784-IN003D-EN-P - January 2006

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 49: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Interpret the LED Indicators 6-3

Steady red bull Faulted card bull Check operating system event log for details of fault (if the personal computerrsquos operating system supports an event log)

bull Cycle power to the computer

bull Verify that you have firmly inserted the 1784-PCIC or 1784-PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened

bull If fault persists contact your Rockwell Automation representative or distributor

Alternating redgreen bull Self-test

bull Incorrect channel configuration

bull None

bull Verify that the ControlNet network is connected to the correct channel of the 1784-PCIC or 1784-PCICS card (for example if the ControlNet network is configured for channel A only then the card must be connected to the network via channel A)

Alternating redoff bull Incorrect node configuration

bull Duplicate ControlNet node address

bull Check 1784-PCIC or 1784-PCICS node address and other ControlNet configuration parameters

A or BCause Action

Off bull Channel disabled bull Use RSNetWorx for ControlNet sofware to configure the ControlNet network for redundant media if required

Steady green bull Normal operation bull None

Flashing greenoff bull Temporary network errors

bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Flashing redoff bull Media fault bull Check media for broken cables loose connectors or missing terminators

bull If condition persists refer to the ControlNet Media Planning and Installation Manual publication CNET-IN002

Table 61 ControlNet status interpretation

A and BCause Action

Publication 1784-IN003D-EN-P - January 2006

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 50: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

6-4 Interpret the LED Indicators

A or BCause Action

Flashing redoff bull No other nodes present on network

bull Add other nodes to the network

Flashing redgreen bull Incorrect node address

bull Change 1784-PCIC or 1784-PCICS node address so that it is less than or equal to

UMAX(1)

bull Stop and restart the 1784-PCIC or 1784-PCICS driver in RSLinx software

bull Incorrect network configuration

bull Use RSNetWorx for ControlNet software to reconfigure the ControlNet network so that

UMAX(1) is greater than or equal to the 1784-PCIC or 1784-PCICS node address

(1) UMAX is the highest node address on a ControlNet network that can transmit data

Publication 1784-IN003D-EN-P - January 2006

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 51: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Chapter 7

Specifications

PCI local bus Compliant to PCI revision 22 The 1784-PCIC and 1784-PCICS cards are compatible with 5V and 33V PCI slots 32-bit and 64-bit PCI slots and PCI-X slots Attention The 1784-PCIC and 1784-PCICS cards are not compatible with PCI Express and should not be inserted into a PCI Express slot

Mechanical form factor H x L Universal PCI 32-bit short card 107 cm (42 in) x 165 cm (65 in) L

Driver compatibility Microsoft Windows XP with Service Pack 1 or higher Microsoft Windows 2000 with Service Pack 4 or higher Microsoft Windows 98 Microsoft Windows Me

Software compatibility Rockwell Software RSLinx software version 24200 or later

Operational temperature IEC 60068-2-1 (Test Ad Operating Cold) IEC 60068-2-2 (Test Bd Operating Dry Heat) IEC 60068-2-14 (Test Nb Operating Thermal Shock) 055 deg C (32131 deg F) The operating parameters describe the environment within the PCI slot Refer to the documentation for your computer for environmental requirements This card should not exceed those specifications

Storage temperature IEC 60068-2-1 (Test Ab Unpackaged Nonoperating Cold) IEC 60068-2-2 (Test Bb Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na Unpackaged Nonoperating Thermal Shock) -4085 deg C (-40185 deg F)

Relative humidity IEC 60068-2-30 (Test Db Un-packaged Nonoperating Damp Heat) 595 noncondensing

Vibration IEC 60068-2-6 (Test Fc Operating) 2g 10500Hz

Operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 30 g

Non-operating shock IEC 60068-2-27 (Test Ea Unpackaged Shock) 50 g

Emissions CISPR 11 Group 1 Class A

ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3 10Vm with 1 k Hz sine-wave 80AM from 80 MHz2000 MHz 10Vm with 200 Hz 50 pulse 100AM at 900 MHz 10Vm with 200 Hz 50 pulse 100AM at 1890 MHz

Publication 1784-IN003D-EN-P - January 2006

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 52: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

7-2 Specifications

EFTB immunity IEC 61000-4-4 plusmn 2 kV at 5 kHz on communications ports

Surge transient immunity IEC 61000-4-5 plusmn 2 kV line-earth (CM) on communications ports

Conducted RF immunity IEC 61000-4-6 10Vrms with 1 kH sine-wave 80 AM from 150kHz80MHz

Enclosure type rating None (open-style)

Power requirements In US this equipment must be powered from UL Listed Information Technology Equipment or UL Listed Industrial Control Equipment In Canada this equipment must be powered by an SELV source CSA Certified Information Technology Equipment or CSA Certified Process Control Equipment 5V dc 700 mA max Class 2

Power dissipation 35 W

Isolation voltage (continuous-voltage withstand rating)

50V continuous Tested to withstand 600V for 60 s

Wiring category(1) 2 - on communications ports

Certifications (when product is marked)(2) UR UL Recognized Component Industrial Control Equipment CSA CSA Accepted Component for Process Control Equipment CSA Accepted Component for Process Control Equipment in Class I Division 2 Group ABCD Hazardous Locations CE European Union 89336EEC EMC Directive compliant with EN 50082-2 Industrial Immunity EN 61326 MeasControlLab Industrial Requirements EN 61000-6-2 Industrial Immunity EN 61000-6-4 Industrial Emissions C-tick Australian Radiocommunications Act compliant with ASNZS CISPR 11 Industrial Emissions EEx (1784-PCIC only) European Union 949EC ATEX Directive compliant with EN 50021 Potentially Explosive Atmospheres Protection ldquonrdquo (Zone 2) CI ControlNet International conformance tested to ControlNet specifications

(1) Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770-41

(2) See the Product Certification link at wwwabcom for Declarations of Conformity Certificates and other certification details

Publication 1784-IN003D-EN-P - January 2006

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 53: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Index

Ccard install 1-1configure ControlNet communications driver

in RSLinx 5-2 5-7connect

a SoftLogix controller to the ControlNet net-work 5-4

the card directly to the ControlNet network 1-9

to a device on the ControlNet network 1-10ControlNet network

connect to 1-9connect to a device on 1-10

Ddriver

install in Windows 2000 for the first time 3-1install in Windows 98Me 4-1install in Windows 98Me for the first time

4-1install in Windows XP 2-1install in Windows XP for the first time 2-1update the existing driver in Windows 2000

3-4update the existing driver in Windows 98Me

4-5update the existing driver in Windows XP 2-3

Iinstall the 1784-PCIC and 1784-PCICS

Communication Interface Cards 1-1

install the driverin Windows 2000 3-1in Windows 98Me 4-1in Windows XP 2-1

install the Virtual Backplane Driver 4-3

LLEDs

status indicator 6-1

RRSLinx

configure ControlNet communications driver 5-2 5-7

Sspecifications 7-1status indicator LEDs 6-1

Uupdate the existing driver

in Windows 2000 3-4in Windows 98Me 4-5in Windows XP 2-3

VVirtual Backplane Driver

install 4-3

Publication 1784-IN003D-EN-P - January 2006

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 54: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

2 Index

Notes

Publication 1784-IN003D-EN-P - January 2006

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 55: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

How Are We DoingYour comments on our technical publications will help us serve you better in the futureThank you for taking the time to provide us feedbackYou can complete this form and mail (or fax) it back to us or email us at

RADocumentCommentsrarockwellcom

Publication CIG-CO521C-EN-P ndash May 2003 PN 957782-91

Where applicable please rank the feature (1=needs improvement 2=satisfactory 3=outstanding)

Pub TitleType ControlNet Universal PCI Communication Interface Card

Cat No 1784-PCIC 1784-PCICS Series B

Pub No 1784-IN003D-EN-P Pub Date January 2006 Part No 953002-33

Overall Usefulness 1 2 3 How can we make this publication more useful for you

Completeness 1 2 3 Can we add more information to help you

(all necessary information is provided)

procedurestep illustration feature

example guideline other

explanation definition

Technical Accuracy 1 2 3 Can we be more accurate

(all information is correct)

text illustration

Clarity 1 2 3 How can we make things clearer

(all information is easy to understand)

Other Comments You can add additional comments on the back of this form

Your Name LocationPhone

Your TitleFunction

Would you like us to contact you regarding your comments

___No there is no need to contact me ___Yes please email me at __________________________

___Yes please call me ___Yes please contact me via ________________________

Return this form toRockwell Automation Technical Communications 1 Allen-Bradley Dr Mayfield Hts OH 44124-9705

Fax 440-646-3525 Email RADocumentCommentsrarockwellcom

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 56: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Other Comments

PLEASE FOLD HERE

1 ALLEN-BRADLEY DR

PLEASE FASTEN HERE (DO NOT STAPLE)

NO POSTAGE NECESSARY IF MAILED

IN THE UNITED STATES

BUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO 18235 CLEVELAND OH

POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 57: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Publication 1784-IN003D-EN-P - January 2006 PN 953002-33Supersedes Publication 1784-IN003C-EN-P - October 2004 Copyright copy 2006 Rockwell Automation Inc All rights reserved Printed in USA

Rockwell Automation SupportRockwell Automation provides technical information on the web to assist you in using our products At httpsupportrockwellautomationcom you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools

For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect Support programs For more information contact your local distributor or Rockwell Automation representative or visit httpsupportrockwellautomationcom

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation please review the information thats contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running

New Product Satisfaction Return

Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned

United States 14406463223Monday ndash Friday 8am ndash 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues

United States Contact your distributor You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process

Outside United States

Please contact your local Rockwell Automation representative for return procedure

  • Publication 1784-IN003D-EN-P ControlNet Universal PCI Communication Interface Card Installation Instructions
  • Table of Contents
  • 1 - Install the 1784-PCIC or 1784-PCICS Communication Interface Card
    • European Hazardous Location Approval (1784-PCIC only)
      • European Zone 2 Certification
        • North American Hazardous Location Approval
        • Access the Computerrsquos PCI Local Bus Expansion Slots
        • Insert the Card Into the Computer
        • Connect to the Network
        • Connect the Card Directly to the ControlNet Network
        • Connect to a Device on the ControlNet Network
          • 2 - Install the Driver in Windows XP
            • Install the Driver in Windows XP for the First Time
            • Update the Existing Driver in Windows XP
              • 3 - Install the Driver in Windows 2000
                • Install the Driver in Windows 2000 for the First Time
                • Update the Existing Driver in Windows 2000
                  • 4 - Install the Driver in Windows 98Me
                    • Install the Driver in Windows 98Me for the First Time
                    • Install the Virtual Backplane Driver
                    • Update the Existing Driver in Windows 98Me
                      • 5 - Once You Have Completed the Installation
                        • Register the EDS File
                        • Configure the ControlNet Communications Driver in RSLinx Software
                        • Connect a SoftLogix Controller to the ControlNet Network
                        • Go Online With RSNetWorx for ControlNet Software
                          • 6 - Interpret the LED Indicators
                            • Interpret the LED Indicators
                              • 7 - Specifications
                              • Index
                              • How Are We Doing
                              • Back Cover
                                • Introduction_Catagory Types

                                  Print Spec Sheet

                                  JIT Printing Specifications RA-QR005D-EN-P - 4032009
                                  Printing Specification YOUR DATA HERE Instructions NO
                                  (required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
                                  (required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
                                  (required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
                                  Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
                                  Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
                                  Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
                                  (required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
                                  (required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
                                  BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
                                  (required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
                                  Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
                                  Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
                                  Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
                                  Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
                                  Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
                                  Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
                                  Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
                                  Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
                                  Comments C2
                                  Part Number 953002-33 JIT POD
                                  D1
                                  D2
                                  D3
                                  D4
                                  D5
                                  D6
                                  D7
                                  D8
                                  D9
                                  This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
                                  Publication Type and Print Category
                                  Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
                                  AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
                                  AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
                                  AR NA NA ArticleEditorialByline NA NA Presale Internal
                                  News Release (press releases should not be checked into DocMan or printed)
                                  AT B3 B4 D5 Application Techniques 5 100 Presale External
                                  BR A2 Primary A1 NA Brochures 5 100 Presale External
                                  CA C2 Primary C1 NA Catalogue 1 50 Presale External
                                  CG NA NA Catalogue Guide 1 50 Presale External
                                  CL NA NA Collection 5 50 Presale External
                                  CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
                                  CP E-only E-only D5 Competitive Information 5 50 NA Confidential
                                  DC E-only E-only Discount Schedules NA NA Presale Internal
                                  DI A1 A3 NA Direct Mail 5 100 Presale Internal
                                  DM NA NA Product Demo 5 50 Presale Internal
                                  DS B3 D5 Dimensions Sheet 1 5 Post External
                                  DU B3 D5 Document Update 1 5 Post External
                                  GR B2 D6 Getting Results 1 5 Post External
                                  IN B3 D5 Installation instructions 1 5 Post External
                                  LM NA NA Launch KitMaterials 5 50 Presale Internal
                                  PC B3 D5 Packaging Contents
                                  PL E-only Primary B3 E-only Price List 5 50 Presale Internal
                                  PM B2 D6 Programming Manual 1 5 Post External
                                  PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
                                  QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
                                  QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
                                  RM B2 D5 D6 Reference Manual 1 5 Post External
                                  RN B3 D5 Release Notes 1 5 Post External
                                  SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
                                  SG B2 D5 D6 Selection Guide BW 5 100 Presale External
                                  SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
                                  SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
                                  TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
                                  TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
                                  UM B2 Primary B4 D6 User Manual BW 1 5 Post External
                                  WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
                                  WP B3 Primary B5 D5 White Paper 5 100 Presale External
                                  Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
                                  A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
                                  A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
                                  A4 2 color 80 gloss cover 80 gloss text
                                  170gsm Silk ndash 120gsm Silk
                                  A5 2 color 80 gloss cover 80 matt sheet text
                                  170gsm Silk ndash 120gsm Silk
                                  A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
                                  A7 4 color cover 10 Point Cover C2S
                                  2 color text Category being deleted 50 matte sheet text
                                  Selection Guide
                                  A8 4 color cover Category being deleted 50 matte sheet text self cover
                                  2 color text
                                  Selection Guide
                                  A9 2 color 100gsm bond 50 matte sheet text self cover
                                  Selection Guide
                                  Post Sale Technical Communication
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
                                  2 color text 50 matte sheet text
                                  B2 1 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B3 1 color 50 matte sheet text self cover
                                  100gsm bond
                                  B4 2 color 60 Cover
                                  160gsm Colortech amp 100gsm Bond 50 matte sheet text
                                  B5 2 color 50 matte sheet text self cover
                                  100gsm bond
                                  Catalogs
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
                                  4 color text 45 Coated Sheet
                                  C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
                                  2 color text 32-33 Coated Sheet
                                  JIT POD
                                  Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
                                  D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
                                  D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
                                  D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
                                  D4 1 color 160gsm tab 90 index
                                  D5 1 color 80gsm bond 20 bond self cover
                                  D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D7 2 color 160gsm tab 90 index
                                  D8 2 color 80gsm bond 20 bond self cover
                                  D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
                                  D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 58: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Introduction_Catagory Types

Print Spec Sheet

JIT Printing Specifications RA-QR005D-EN-P - 4032009
Printing Specification YOUR DATA HERE Instructions NO
(required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
(required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
(required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
(required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
(required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
(required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
Comments C2
Part Number 953002-33 JIT POD
D1
D2
D3
D4
D5
D6
D7
D8
D9
This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printingFind your publication type in the first section below Use the assigned Printing Category information to determine the standard print specifications for that document type The Printing Categories are defined below the Publication Type section Note there may be slightly different print specifications for the categories depending on the region (EMEA or Americas)For more information on Global Sales and Marketing Printing Standards see publication RA-CO004 in DocMan
Publication Type and Print Category
Publication Type Off Set Print Category Spec (See table below) JIT Spec (See table below) Description Order Min Order Max Life Cycle Usage Release Option
AD NA - Puttman NA Advertisement Reprint Colour NA NA Presale Internal
AP A3 D2 Application Solution or Customer Success Story 5 100 Presale External
AR NA NA ArticleEditorialByline NA NA Presale Internal
News Release (press releases should not be checked into DocMan or printed)
AT B3 B4 D5 Application Techniques 5 100 Presale External
BR A2 Primary A1 NA Brochures 5 100 Presale External
CA C2 Primary C1 NA Catalogue 1 50 Presale External
CG NA NA Catalogue Guide 1 50 Presale External
CL NA NA Collection 5 50 Presale External
CO A5 A6 A9 D5 Company Confidential Information NA NA NA Confidential
CP E-only E-only D5 Competitive Information 5 50 NA Confidential
DC E-only E-only Discount Schedules NA NA Presale Internal
DI A1 A3 NA Direct Mail 5 100 Presale Internal
DM NA NA Product Demo 5 50 Presale Internal
DS B3 D5 Dimensions Sheet 1 5 Post External
DU B3 D5 Document Update 1 5 Post External
GR B2 D6 Getting Results 1 5 Post External
IN B3 D5 Installation instructions 1 5 Post External
LM NA NA Launch KitMaterials 5 50 Presale Internal
PC B3 D5 Packaging Contents
PL E-only Primary B3 E-only Price List 5 50 Presale Internal
PM B2 D6 Programming Manual 1 5 Post External
PP A3 D1 Product Profile NOTE Application Solutions are to be assigned the AP pub type 5 100 Presale External
QR B2 Primary B3 B5 D5 D6 Quick Reference 1 5 Post External
QS B2 Primary B3 B5 D5 D6 Quick Start 1 5 Post External
RM B2 D5 D6 Reference Manual 1 5 Post External
RN B3 D5 Release Notes 1 5 Post External
SG B1 Primary B4 D5 D6 Selection Guide Colour 5 100 Presale External
SG B2 D5 D6 Selection Guide BW 5 100 Presale External
SP A1 A2 A3 A4 NA Service ProfileSales Promotion NOTE Service profiles are to be assigned the PP pub type 5 100 Presale Internal
SR B2 B3 D5 D6 Specification Rating Sheet 5 100 Presale External
TD B2 Primary B3 B4 B5 D5 D6 Technical Data 5 100 Presale External
TG B2 B3 D6 Troubleshooting Guide 1 5 Post External
UM B2 Primary B4 D6 User Manual BW 1 5 Post External
WD B3 D5 Wiring Diagrams Dwgs 1 5 Post Internal
WP B3 Primary B5 D5 White Paper 5 100 Presale External
Pre-sale Marketing All paper in this category is White Brightness 85 or better Opacity 87 or better
Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
A1 4 color 170gsm 2pp 100 gloss cover 100 gloss text
A2 4 color 170gsm folded 4pp 100 gloss cover 80 gloss text
A3 4 color Cover 170gsm with Body 120gsm gt 4pp 80 gloss cover 80 gloss text
A4 2 color 80 gloss cover 80 gloss text
170gsm Silk ndash 120gsm Silk
A5 2 color 80 gloss cover 80 matt sheet text
170gsm Silk ndash 120gsm Silk
A6 1 color 170gsm Silk ndash 120gsm Silk 80 gloss cover 80 matt sheet text
A7 4 color cover 10 Point Cover C2S
2 color text Category being deleted 50 matte sheet text
Selection Guide
A8 4 color cover Category being deleted 50 matte sheet text self cover
2 color text
Selection Guide
A9 2 color 100gsm bond 50 matte sheet text self cover
Selection Guide
Post Sale Technical Communication
Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
B1 4 color cover 270gsm Gloss 100gsm bond 10 Point Cover C2S
2 color text 50 matte sheet text
B2 1 color 60 Cover
160gsm Colortech amp 100gsm Bond 50 matte sheet text
B3 1 color 50 matte sheet text self cover
100gsm bond
B4 2 color 60 Cover
160gsm Colortech amp 100gsm Bond 50 matte sheet text
B5 2 color 50 matte sheet text self cover
100gsm bond
Catalogs
Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
C1 4 color cover 270gsm Gloss 90gsm silk 10 Point Cover C2S
4 color text 45 Coated Sheet
C2 4 color cover 270gsm Gloss 80gsm silk 10 Point Cover C2S
2 color text 32-33 Coated Sheet
JIT POD
Category Color Options AP EMEA Paper Requirements Canada LA US Paper Requirements
D1 4 color 170gsm white silk 80 gloss cover coated 2 sides
D2 4 color 120gsm white silk 80 gloss text coated 2 sides self cover
D3 4 color Cover 170gsm with Body 120gsm 80 gloss cover 80 gloss text coated 2 sides
D4 1 color 160gsm tab 90 index
D5 1 color 80gsm bond 20 bond self cover
D6 1 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
D7 2 color 160gsm tab 90 index
D8 2 color 80gsm bond 20 bond self cover
D9 2 color Cover 160gsm tab with Body 80gsm bond 90 index 20 bond
D10 Combination 4 color cover with 2 color body Cover 160gsm with Body 80gsm 90 index 20 bond
Page 59: 1784-PCIC, 1784-PCICS Series B - Rockwell …...1784-PCIC, 1784-PCICS Series B Installation Instructions Important User Information Solid state equipment has operational characteristics

Print Spec Sheet

JIT Printing Specifications RA-QR005D-EN-P - 4032009
Printing Specification YOUR DATA HERE Instructions NO
(required) Category D5 Select Print Category ABC or D from category list on Introduction_Catagory Types tab 11rdquo x 17rdquo LOOSE -Loose Leaf YES Pre-sale Marketing TOP
(required) Finished Trim Size Width 55rdquo x 85rdquo (half-size) 85rdquo x 11rdquo PERFECT - Perfect Bound A1 LEFT
(required) Publication Number 1784-IN003D-EN-P Sample 2030-SP001B-EN-P 3rdquo x 5rdquo SADDLE - Saddle Stitch A2 RIGHT CORNER
Use Legacy Number NO YES or NO 18rdquo x 24rdquo Poster PLASTCOIL - Plastic Coil (Coil Bound) A4 BOTTOM SIDE
Legacy Number if applicable Sample Legacy Number 0160-533 24rdquo x 36rdquo Poster STAPLED1 -1 position A3
Publication Title ControlNet Universal PCI Communication Interface Card Sample ElectroGuard Selling Brief 36rdquo x 24rdquo Poster STAPLED1B - bottom 1 position A5
(required) Business Group Marketing Commercial As entered in DocMan 4rdquo x 6rdquo STAPLED2 - 2 positions A6
(required) Cost Center 19021 As entered in DocMan - enter number only no description Example - 19021 CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 19105 475rdquo x 7rdquo (slightly smaller half-size) THERMAL - Thermal bound (Tape bound) A7
BindingStitching SADDLE - Saddle Stitch Review key on right Saddle-Stitch Items All page quantities must be divisible by 420 sheets max on 20 (text and cover) 20 sheets = 80-page pub16 sheets max on 20 (text) and 90 (cover) 16 sheets = 64-page pubPerfect Bound Items475 sheets max on 20 no cover 475 sheets = 950-page pub470 sheets max wcover 90 index unless indicated otherwise) 470 sheets = 940-page pubCoil Bound Items400 sheets max of 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 400 sheets = 800-page pubTape Bound Items125 sheets max on 20 no cover 125 sheets = 250-page pub120 sheets max wcover (90 index unless indicated otherwise) 120 sheets = 240-page pubDouble Wire Bound Items250 sheets max on 20 (if adding cover deduct equivalent number of pages to equal cover thickness) (90 index unless indicated otherwise) 250 sheets = 500-page pub 475rdquo x 775rdquo THERMALO - Thermal Bound (Tape bound - offline) A8
(required) Page Count of Publication 58 Total page count including cover 55rdquo x 85rdquo (half-size) Wire O - Double Wire Bound (offline) A9
Paper Stock Color White White is assumed For color options contact your vendor 6rdquo x 4rdquo Post Sale Technical Communication
Number of Tabs Needed 5 tab in stock at RR Donnelley 7385rdquo x 9rdquo (RSI Std) B1
Stitching Location Blank Corner or Side 825rdquo x 10875rdquo B2
Drill Hole YESNO NO All drilled publications use the 5-hole standard 516 inch-size hole and a minimum of frac14 inch from the inner page border 825rdquo x 11rdquo (RA product profile std) B3
Glue Location on Pad Glue location on pads 8375rdquo x 10875 B4
Number of Pages per Pad Average sheets of paper 25 50 75100 Max 9rdquo x 12rdquo (Folder) B5
Ink Color One color assumes BLACK 4 color assume CMYK Indicate PMS number herehellip A4 (8 frac14rdquo x 11 frac34rdquo) (210 x 297 mm) Catalogs
Used in Manufacturing YES A5 (583rdquo x 826rdquo) (148 x 210 mm) C1
Comments C2
Part Number 953002-33 JIT POD
D1
D2
D3
D4
D5
D6
D7
D8
D9