1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor...

25
LEGEND FA0.01 COVER SHEET THE COPYING OR RE-USE OF THIS DOCUMENT, OR PORTIONS THEREOF, FOR ANY REASON OTHER THAN THE ORIGINAL PROJECT OR THE PURPOSE ORIGINALLY INTENDED, WITHOUT THE CONSENT OF HUGHES ASSOCIATES, INC. IS PROHIBITED. HAI PROJECT NO. Revision No. Date 2551 San Ramon Valley Blvd, Suite 209 San Ramon, CA 94583 Phone (925)314-7910 Fax (925)314-9750 Scale: Graphics Project Description Design Drawing Title Drawing No. 4 3 2 1 1 2 3 4 A B C D Design: Drawn: Review: Date: Location: HUGHES ASSOCIATES, INC. Fire Science & Engineering 1RJW00050.002 CRA CRA RJW March 8, 2013 AC TRANSIT FIRE ALARM UPGRADE PROJECT IFB 2013-1247 1600 Franklin St. Oakland, CA A B C D Sheet: of 25 BID DESIGN SET 1 1600 FRANKLIN STREET FIRE ALARM REPLACEMENT IFB 2013-1247 SHEET LIST FA0.01 COVER SHEET FA1.13 PENTHOUSE FIRE ALARM LAYOUT FA0.02 RISER DIAGRAM BASEMENT - 5TH FLOOR FD1.01 BASEMENT & 1ST FLOOR DEMOLITION LAYOUT FA0.03 RISER DIAGRAM 6TH FLOOR - PENTHOUSE FD1.02 P3/P4 & 2ND FLOOR P5/P6 DEMOLITION LAYOUT FA0.04 FIRE ALARM AND SMOKE CONTROL OPERATION MATRIX FD1.03 3RD & 4TH FLOOR DEMOLITION LAYOUT FA0.05 SMOKE CONTROL PANEL LAYOUT FD1.04 5TH & 6TH FLOOR DEMOLITION LAYOUT FA1.01 BASEMENT FIRE ALARM LAYOUT FD1.05 7TH & 8TH FLOOR DEMOLITION LAYOUT FA1.02 1ST FLOOR FIRE ALARM LAYOUT AND P1/P2 FIRE ALARM LAYOUT FD1.06 9TH & 10TH FLOOR DEMOLITION LAYOUT FA1.03 2ND FLOOR FIRE ALARM LAYOUT AND P3/P4 FIRE ALARM LAYOUT FD1.07 PENTHOUSE DEMOLITION LAYOUT FA1.04 2ND FLOOR FIRE ALARM LAYOUT P5/P6 FIRE ALARM LAYOUT FA1.05 3RD FLOOR FIRE ALARM LAYOUT FA1.06 4TH FLOOR FIRE ALARM LAYOUT FA1.07 5TH FLOOR FIRE ALARM LAYOUT FA1.08 6TH FLOOR FIRE ALARM LAYOUT FA1.09 7TH FLOOR FIRE ALARM LAYOUT FA1.10 8TH FLOOR FIRE ALARM LAYOUT FA1.11 9TH FLOOR FIRE ALARM LAYOUT FA1.12 10TH FLOOR FIRE ALARM LAYOUT SCOPE OF WORK THE SCOPE OF THIS PROJECT IS TO INSTALL A NEW FIRE ALARM SYSTEM CONCURRENTLY WITH THE EXISTING SYSTEM AND UPON SYSTEM ACCEPTANCE, DEMOLISH THE EXISTING FIRE ALARM SYSTEM. EXISTING INITIATING AND NOTIFICATION DEVICES WILL BE DEMOLISHED. NEW INITIATING AND NOTIFICATION DEVICES WILL BE PROVIDED FOR THE NEW SYSTEM. THE FIRE ALARM SYSTEM REPLICATES THE EXISTING SMOKE CONTROL FUNCTIONALITY THROUGH RELAYS AND MONITOR MODULES. A FIREFIGHTER'S SMOKE CONTROL PANEL WILL BE PROVIDED AS PART OF THE PROJECT. BUILDING INFORMATION OCCUPANCY GROUP: 1600 FRANKLIN - "B" WIRING SURVIVABILITY AND CLASS VERTICAL RISERS = PATHWAY SURVIVABILITY LEVEL 1 HORIZONTAL WIRING = PATHWAY SURVIVABILITY LEVEL 0 SIGNALING LINE CIRCUIT (SLC) = CLASS B NOTIFICATION APPLIANCE CIRCUIT (NAC) = CLASS B INITIATING DEVICE CIRCUITS (IDC) = CLASS B GENERAL NOTES 1. ALL WORK TO BE PERFORMED IN ACCORDANCE WITH THE FOLLOWING CODES AND STANDARDS: 1.1. CALIFORNIA BUILDING CODE (CBC) 2010 1.2. CALIFORNIA FIRE CODE (CFC) 2010 1.3. CALIFORNIA ELECTRICAL CODE (CEC) 2010 1.4. OAKLAND FIRE DEPARTMENT REQUIREMENTS 1.5. NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE , 2010 EDITION 2. THE BUILDING SHALL REMAIN OCCUPIED THROUGHOUT THE CONSTRUCTION PERIOD. CONTRACTORS SHALL PERFORM WORK ON OFF HOURS AS NECESSARY. CONTRACTORS SHALL INCLUDE OFF HOURS WORK IN THE BASE BID. 3. ELECTRICAL CONTRACTOR SHALL PROVIDE RACEWAYS AND CONDUCTORS FOR FIRE ALARM SYSTEM INSTALLATION, INCLUDING DEDICATED POWER SUPPLY CONDUCTORS FOR CONTROL EQUIPMENT WITH LOCKING DEVICES ON DEDICATED CIRCUIT BREAKERS. 4. CONDUIT SIZE SHALL BE DETERMINED BY INSTALLING CONTRACTOR & SHALL NOT EXCEED 40% FILL CAPACITY (MINIMUM 3 4 ") IN ACCORDANCE WITH CHAPTER 9, TABLE 1 OF THE CEC. 5. ALL SLC AND IDC CIRCUITS SHALL BE INSTALLED IN METALLIC RACEWAY AS REQUIRED FOR SMOKE CONTROL SYSTEMS. SEPARATE 2 HOUR RATED SLC CIRCUITS SHALL BE RUN TO PROVIDE MONITORING AND CONTROL OF STAIR PRESSURIZATION FANS PER REQUIREMENTS OF THE CBC. 6. THE PRIMARY POWER SOURCE FOR THE FACP AND FCPS SHALL BE FROM DEDICATED CIRCUIT(S). THESE CIRCUITS SHALL BE LABELED AT BOTH THE ELECTRICAL SUB PANEL AND ON THE INSIDE OF THE FACP/FCPS DOOR AND PROVIDED WITH A CIRCUIT LOCK. 7. READILY VISIBLE SIGNS SHALL IDENTIFY THE LOCATION OF THE FIRE ALARM CONTROL PANEL AND REMOTE POWER SUPPLIES. SIGNS SHALL BE LOCATED AT DOOR(S) TO AREA(S) CONTAINING THE FACP AND FCPS. 8. SIGNALING LINE CIRCUIT (SLC) SHALL BE 16/2 TWISTED SHIELDED (U.O.N.) PLFA PER CEC. 9. NOTIFICATION APPLIANCE CIRCUIT (NAC) WIRING SHALL BE 14/2 TWISTED (U.O.N.) PLFA PER CEC. 10. EACH FLOOR CONNECTION TO THE SIGNALING LINE CIRCUIT SHALL HAVE AN ISOLATION DEVICE INSTALLED. NO MORE THAN 50 DEVICES SHALL BE INSTALLED PER ISOLATION BRANCH. 11. ALARM-SIGNALING DEVICES SHALL PRODUCE A DISTINCTIVE THREE-PULSE TEMPORAL PATTERN FIRE ALARM EVACUATION SIGNAL FOLLOWED BY A VOICE EVACUATION MESSAGE. AUDIBLE SIGNALS SHALL HAVE A SOUND LEVEL OF NOT LESS THAN 75dba AT 10' OR AT LEAST 15dba ABOVE THE AVERAGE AMBIENT SOUND LEVEL AS MEASURE 5' ABOVE THE FLOOR IN THE OCCUPIED AREA, WHICHEVER IS GREATER, BUT NO MORE THAN 120dba AT THE MINIMUM HEARING DISTANCE FROM THE AUDIBLE APPLIANCE. 12. ALL VISUAL DEVICES WITHIN A COMMON VIEW SHALL BE SYNCHRONIZED PER NFPA 72. IF VISUAL DEVICES ARE VISIBLE ON MULTIPLE FLOORS THOSE DEVICES SHALL BE SYNCHRONIZED. 13. UPON ACCEPTANCE OF THE WORK BY THE AHJ, A RECORD OF COMPLETION SHALL BE PROVIDED. 14. THE REQUIREMENTS OF TECHNICAL SPECIFICATION SECTION 283111, FIRE ALARM SYSTEM, ARE INCORPORATED IN THE REQUIREMENTS FOR THIS PROJECT AS IF FULLY PRESENTED IN THESE DRAWINGS. 1600 FRANKLIN STREET OAKLAND, CA 42"-48" MOUNTED NOT LESS THAN 80" AND NO GREATER THAN 96" ABOVE FINISHED FLOOR. COMBINATION AUDIBLE/VISUAL DEVICE CEILING LINE MANUAL PULL STATION MOUNTED NOT LESS THAN 80" AND NO GREATER THAN 96" ABOVE FINISHED FLOOR. VISUAL DEVICE FINISH FLOOR LINE SCALE: DEVICE MOUNTING ELEVATIONS NTS

Transcript of 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor...

Page 1: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA0.01

COVER SHEET

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

1

1600 FRANKLIN STREET

FIRE ALARM REPLACEMENT

IFB 2013-1247

SHEET LIST

FA0.01 COVER SHEET FA1.13

PENTHOUSE FIRE ALARM

LAYOUT

FA0.02 RISER DIAGRAM BASEMENT - 5TH

FLOOR

FD1.01 BASEMENT & 1ST FLOOR

DEMOLITION LAYOUT

FA0.03 RISER DIAGRAM 6TH FLOOR -

PENTHOUSE

FD1.02 P3/P4 & 2ND FLOOR P5/P6

DEMOLITION LAYOUT

FA0.04 FIRE ALARM AND SMOKE CONTROL

OPERATION MATRIX

FD1.03 3RD & 4TH FLOOR DEMOLITION

LAYOUT

FA0.05 SMOKE CONTROL PANEL LAYOUT FD1.04 5TH & 6TH FLOOR DEMOLITION

LAYOUT

FA1.01 BASEMENT FIRE ALARM LAYOUT FD1.05 7TH & 8TH FLOOR DEMOLITION

LAYOUT

FA1.02 1ST FLOOR FIRE ALARM LAYOUT

AND P1/P2 FIRE ALARM LAYOUT

FD1.06 9TH & 10TH FLOOR DEMOLITION

LAYOUT

FA1.03 2ND FLOOR FIRE ALARM LAYOUT

AND P3/P4 FIRE ALARM LAYOUT

FD1.07 PENTHOUSE DEMOLITION

LAYOUT

FA1.04 2ND FLOOR FIRE ALARM LAYOUT

P5/P6 FIRE ALARM LAYOUT

FA1.05 3RD FLOOR FIRE ALARM LAYOUT

FA1.06 4TH FLOOR FIRE ALARM LAYOUT

FA1.07 5TH FLOOR FIRE ALARM LAYOUT

FA1.08 6TH FLOOR FIRE ALARM LAYOUT

FA1.09 7TH FLOOR FIRE ALARM LAYOUT

FA1.10 8TH FLOOR FIRE ALARM LAYOUT

FA1.11 9TH FLOOR FIRE ALARM LAYOUT

FA1.12 10TH FLOOR FIRE ALARM LAYOUT

SCOPE OF WORK

THE SCOPE OF THIS PROJECT IS TO INSTALL A NEW FIRE ALARM SYSTEM CONCURRENTLY

WITH THE EXISTING SYSTEM AND UPON SYSTEM ACCEPTANCE, DEMOLISH THE EXISTING

FIRE ALARM SYSTEM. EXISTING INITIATING AND NOTIFICATION DEVICES WILL BE

DEMOLISHED. NEW INITIATING AND NOTIFICATION DEVICES WILL BE PROVIDED FOR THE

NEW SYSTEM. THE FIRE ALARM SYSTEM REPLICATES THE EXISTING SMOKE CONTROL

FUNCTIONALITY THROUGH RELAYS AND MONITOR MODULES. A FIREFIGHTER'S SMOKE

CONTROL PANEL WILL BE PROVIDED AS PART OF THE PROJECT.

BUILDING INFORMATION

OCCUPANCY GROUP:

1600 FRANKLIN - "B"

WIRING SURVIVABILITY AND CLASS

VERTICAL RISERS = PATHWAY SURVIVABILITY LEVEL 1

HORIZONTAL WIRING = PATHWAY SURVIVABILITY LEVEL 0

SIGNALING LINE CIRCUIT (SLC) = CLASS B

NOTIFICATION APPLIANCE CIRCUIT (NAC) = CLASS B

INITIATING DEVICE CIRCUITS (IDC) = CLASS B

GENERAL NOTES

1. ALL WORK TO BE PERFORMED IN ACCORDANCE WITH THE FOLLOWING

CODES AND STANDARDS:

1.1. CALIFORNIA BUILDING CODE (CBC) 2010

1.2. CALIFORNIA FIRE CODE (CFC) 2010

1.3. CALIFORNIA ELECTRICAL CODE (CEC) 2010

1.4. OAKLAND FIRE DEPARTMENT REQUIREMENTS

1.5. NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE , 2010 EDITION

2. THE BUILDING SHALL REMAIN OCCUPIED THROUGHOUT THE

CONSTRUCTION PERIOD. CONTRACTORS SHALL PERFORM WORK ON OFF

HOURS AS NECESSARY. CONTRACTORS SHALL INCLUDE OFF HOURS

WORK IN THE BASE BID.

3. ELECTRICAL CONTRACTOR SHALL PROVIDE RACEWAYS AND CONDUCTORS

FOR FIRE ALARM SYSTEM INSTALLATION, INCLUDING DEDICATED POWER

SUPPLY CONDUCTORS FOR CONTROL EQUIPMENT WITH LOCKING DEVICES

ON DEDICATED CIRCUIT BREAKERS.

4. CONDUIT SIZE SHALL BE DETERMINED BY INSTALLING CONTRACTOR &

SHALL NOT EXCEED 40% FILL CAPACITY (MINIMUM

3

4

") IN ACCORDANCE

WITH CHAPTER 9, TABLE 1 OF THE CEC.

5. ALL SLC AND IDC CIRCUITS SHALL BE INSTALLED IN METALLIC RACEWAY AS

REQUIRED FOR SMOKE CONTROL SYSTEMS. SEPARATE 2 HOUR RATED

SLC CIRCUITS SHALL BE RUN TO PROVIDE MONITORING AND CONTROL OF

STAIR PRESSURIZATION FANS PER REQUIREMENTS OF THE CBC.

6. THE PRIMARY POWER SOURCE FOR THE FACP AND FCPS SHALL BE FROM

DEDICATED CIRCUIT(S). THESE CIRCUITS SHALL BE LABELED AT BOTH THE

ELECTRICAL SUB PANEL AND ON THE INSIDE OF THE FACP/FCPS DOOR

AND PROVIDED WITH A CIRCUIT LOCK.

7. READILY VISIBLE SIGNS SHALL IDENTIFY THE LOCATION OF THE FIRE

ALARM CONTROL PANEL AND REMOTE POWER SUPPLIES. SIGNS SHALL BE

LOCATED AT DOOR(S) TO AREA(S) CONTAINING THE FACP AND FCPS.

8. SIGNALING LINE CIRCUIT (SLC) SHALL BE 16/2 TWISTED SHIELDED (U.O.N.)

PLFA PER CEC.

9. NOTIFICATION APPLIANCE CIRCUIT (NAC) WIRING SHALL BE 14/2 TWISTED

(U.O.N.) PLFA PER CEC.

10. EACH FLOOR CONNECTION TO THE SIGNALING LINE CIRCUIT SHALL HAVE

AN ISOLATION DEVICE INSTALLED. NO MORE THAN 50 DEVICES SHALL BE

INSTALLED PER ISOLATION BRANCH.

11. ALARM-SIGNALING DEVICES SHALL PRODUCE A DISTINCTIVE THREE-PULSE

TEMPORAL PATTERN FIRE ALARM EVACUATION SIGNAL FOLLOWED BY A

VOICE EVACUATION MESSAGE. AUDIBLE SIGNALS SHALL HAVE A SOUND

LEVEL OF NOT LESS THAN 75dba AT 10' OR AT LEAST 15dba ABOVE THE

AVERAGE AMBIENT SOUND LEVEL AS MEASURE 5' ABOVE THE FLOOR IN

THE OCCUPIED AREA, WHICHEVER IS GREATER, BUT NO MORE THAN

120dba AT THE MINIMUM HEARING DISTANCE FROM THE AUDIBLE

APPLIANCE.

12. ALL VISUAL DEVICES WITHIN A COMMON VIEW SHALL BE SYNCHRONIZED

PER NFPA 72. IF VISUAL DEVICES ARE VISIBLE ON MULTIPLE FLOORS

THOSE DEVICES SHALL BE SYNCHRONIZED.

13. UPON ACCEPTANCE OF THE WORK BY THE AHJ, A RECORD OF

COMPLETION SHALL BE PROVIDED.

14. THE REQUIREMENTS OF TECHNICAL SPECIFICATION SECTION 283111, FIRE

ALARM SYSTEM, ARE INCORPORATED IN THE REQUIREMENTS FOR THIS

PROJECT AS IF FULLY PRESENTED IN THESE DRAWINGS.

1600 FRANKLIN STREET

OAKLAND, CA

42"-48"

MOUNTED NOT LESS

THAN 80" AND NO

GREATER THAN 96"

ABOVE FINISHED

FLOOR.

COMBINATION

AUDIBLE/VISUAL

DEVICE

CEILING

LINE

MANUAL PULL

STATION

MOUNTED NOT LESS THAN 80"

AND NO GREATER THAN 96"

ABOVE FINISHED FLOOR.

VISUAL

DEVICE

FINISH FLOOR

LINE

SCALE:

DEVICE MOUNTING ELEVATIONS

NTS

Page 2: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

FA0.02

RISER DIAGRAM

BASEMENT - 5TH FLOOR

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

2

SCALE:

SYSTEM RISER DIAGRAM

NTS

1

2

2

2

4

4

4

2

4

3

2

KEYED NOTES

1. SEPARATE 2 HOUR RATED SLC CIRCUITS

SHALL BE RUN TO PROVIDE MONITORING

AND CONTROL OF STAIR PRESSURIZATION

FANS.

2. AIR CONTROL DAMPER CONTROL FOR THE

SMOKE CONTROL SYSTEM SHALL CONSIST

OF A CONTROL RELAY FOR FORCE OPEN

AND FORCE SHUT AND TWO MONITOR

MODULES FOR END SWITCH POSITION

MONITORING.

3. SUPPLY FAN CONTROL FOR THE SMOKE

CONTROL SYSTEM SHALL CONSIST OF

CONTROL RELAYS TO CONTROL FAN

OPERATION, MONITOR MODULES TO

MONITOR AIRFLOW SPEEDS AND POWER

TO THE FAN AT THE SOURCE AND

MAINTENANCE DISCONNECT SWITCHES.

4. SUPPLY/EXHAUST FAN CONTROL, NOT FOR

SMOKE CONTROL USE, SHALL BE

PROVIDED WITH CONTROL RELAYS FOR

SHUTDOWN AND WITH MONITOR MODULES

FOR MONITORING OF POWER TO THE FAN

AT THE POWER DISCONNECT SWITCH.

MATCH LINE - SEE SHEET FA0.03 FOR CONTINUATION

Page 3: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

FA0.03

RISER DIAGRAM

6TH FLOOR - PENTHOUSE

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

3

SCALE:

SYSTEM RISER DIAGRAM

NTS

KEYED NOTES

1. SEPARATE 2 HOUR RATED SLC CIRCUITS

SHALL BE RUN TO PROVIDE MONITORING

AND CONTROL OF STAIR PRESSURIZATION

FANS.

2. AIR CONTROL DAMPER CONTROL FOR THE

SMOKE CONTROL SYSTEM SHALL CONSIST

OF A CONTROL RELAY FOR FORCE OPEN

AND FORCE SHUT AND TWO MONITOR

MODULES FOR END SWITCH POSITION

MONITORING.

3. SUPPLY FAN CONTROL FOR THE SMOKE

CONTROL SYSTEM SHALL CONSIST OF

CONTROL RELAYS TO CONTROL FAN

OPERATION, MONITOR MODULES TO

MONITOR AIRFLOW SPEEDS AND POWER

TO THE FAN AT THE SOURCE AND

MAINTENANCE DISCONNECT SWITCHES.

4. SUPPLY/EXHAUST FAN CONTROL, NOT FOR

SMOKE CONTROL USE, SHALL BE

PROVIDED WITH CONTROL RELAYS FOR

SHUTDOWN AND WITH MONITOR MODULES

FOR MONITORING OF POWER TO THE FAN

AT THE POWER DISCONNECT SWITCH.

1

3

2

3

4

4

2

2

2

2

3

2

MATCH LINE - SEE SHEET FA0.02 FOR CONTINUATION

4

Page 4: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

FA0.04

FIRE ALARM AND SMOKE CONTROL

OPERATION MATRIX

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

4

SCALE:

SMOKE CONTROL MATRIX

NTS

MANUAL PULL STATION

1ST FLOOR ELEV LOBBY

SMOKE DETECTORS

SH

UT

DO

WN

F

AN

RE

CA

LL E

LE

VA

TO

RS

T

O

2N

D F

LO

OR

RE

CA

LL E

LE

VA

TO

RS

T

O

1S

T F

LO

OR

SH

UT

F

IR

E D

OO

RS

SU

PE

RV

IS

OR

Y S

IG

NA

L A

T

FA

CP

TR

OU

BLE

S

IG

NA

L A

T F

AC

P

ALA

RM

S

IG

NA

L A

T F

AC

P

OPEN AREA SMOKE

DETECTORS

FLOOR AIR CONTROL

DAMPER DUCT DETECTOR

BASEMENT, 2-10 ELEVATOR

LOBBY SMOKE DETECTORS

GE

NE

RA

TE

E

VA

CU

AT

IO

N

TO

NE

IN

G

AR

AG

E A

RE

A

OF

F-S

IT

E A

LA

RM

S

IG

NA

L

OF

F-S

IT

E S

UP

ER

VIS

OR

Y

SIG

NA

L

OF

F-S

IT

E T

RO

UB

LE

S

IG

NA

L

SH

UT

F

IR

E D

AM

PE

RS

SPRINKLER WATER FLOW

SPRINKLER VALVE TAMPER

FIRE ALARM SYSTEM

AC FAIL

ELEVATOR MACHINE ROOM

HEAT DETECTOR

SCALE:

SYSTEM OPERATION MATRIX

NTS

OU

TP

UT

S

INPUTS

HALON PANEL ALARM

HALON PANEL TROUBLE

PREACTION PANEL ALARM

PREACTION PANEL

TROUBLE

PREACTION PANEL

SUPERVISORY

GE

NE

RA

TE

E

VA

CU

AT

IO

N T

ON

E

TH

RO

UG

HO

UT

B

UILD

IN

G

FIRE PUMP ENGINE

RUNNING

FIRE RESERVOIR FULL

FIRE RESERVOIR TEMP

MONITOR SWITCH

BM

S N

OT

IF

IC

AT

IO

N

UN

LO

CK

S

EC

UR

IT

Y D

OO

RS

AIR HANDLING UNIT DUCT

DETECTOR

FIRE PUMP CONTROLLER

TROUBLE

FIRE PUMP CONTROLLER

OFF

FIRE PUMP COMMON

TROUBLE

FIRE ALARM SYSTEM

GROUND FAULT

FIRE ALARM SYSTEM

CIRCUIT FAULT

FIRE ALARM SYSTEM

COMMUNICATION FAULT

Page 5: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

FIREFIGHTER'S CONTROL

CLOSEOPEN AUTO FAULTNORMAL

SUPPLY FANSP-4

STAIR #2

AC TRANSIT SMOKE CONTROL PANEL

4TH FLOOR

5TH FLOOR

6TH FLOOR

7TH FLOOR

8TH FLOOR

9TH FLOOR

10TH FLOOR

ROOF

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

SU

PP

LY D

AM

PE

RS

RE

TUR

N D

AM

PE

RS

AUTO

NORMAL FAULT

ON OFF

STAIR #1

STAIR #2

AUTO

NORMAL FAULT

ON OFF

SMOKE CONTROL

SUPPLY - SF-1B, -1E

AUTO

NORMAL FAULT

ON OFF

SMOKE

SX-1EXHAUST FAN

BASEMENT

1ST FLOOR

2ND FLOOR

LAMP TEST

FAULT/TROUBLE/

OFF/CLOSED/ALARM

ON/OPEN/RUNNING

LEGEND

SUPERVISORY/LOW FUEL/

NORMAL

PHASE REVERSAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

SUPPLY FANSP-1

STAIR #1

AUTO

OFFON

NORMAL FAULT

SUPPLY FANSP-2

STAIR #1

AUTO

NORMAL FAULT

ON OFF

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

CLOSEOPEN AUTO FAULTNORMAL

SUPPLY FANSP-3

STAIR #2

AUTO

OFFON

NORMAL FAULT

AUTO

NORMAL FAULT

OFF

NON SMOKE CONTROL

RETURN - RF-1A, -1B, -1C, -1D FANS

SUPPLY - SF-1A, -1C, -1D, -1F

FANS

AHU-1

OFFONNORMAL

OFFONNORMAL

OFFONNORMAL

AUTO

AUTO

AUTO

OFFONNORMAL AUTO

OFFONNORMAL AUTO

P5

P4

P3

P2

P1

E-17

PARKING LEVELS

E-16OFFONNORMAL AUTO

E-15

E-14

E-12

E-10

OFFONNORMAL AUTO

E-13OFFONNORMAL AUTOE-5

OFFONNORMAL AUTOE-11

OFFONNORMAL AUTOS-5

ELEVATOR #5 MACHINE ROOM, LEVEL P3

OFFONNORMAL AUTO

E-2OFFONNORMAL AUTO

S-2

ROOMS B1, B2, B4, B16, B16A, B17, B17AOFFONNORMAL AUTO

S-6OFFONNORMAL AUTO

E-6

EMERGENCY GENERATOR ROOMOFFONNORMAL AUTO

E-7

BOILER ROOM

E-1

TOILET EXHAUST FAN

AUTO

NORMAL

ON OFF

3RD FLOOR

MAIN FAN PURGE SWITCH

AUTO

NORMAL FAULT

ON OFF

Note: This door will be hinged on the left/lock on the right.

PENTHOUSE/

4'-4 7/8"

3'-4 7/8"

ENABLE

DISABLE

PANEL

FA0.05

SMOKE CONTROL PANEL

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

5

SCALE:

SMOKE CONTROL PANEL

1:2

GENERAL NOTES

1. FIRE ALARM CONTRACTOR TO PROVIDE REQUIRED MONITORING POINTS

FOR ALL EQUIPMENT COMPRISING OF THE SMOKE CONTROL SYSTEM.

POINTS SHALL INCLUDE:

1.1. STAIR PRESSURIZATION FANS

1.2. SMOKE CONTROL SUPPLY AND RETURN FANS

1.3. NON-SMOKE CONTROL SUPPLY AND RETURN FANS

1.4. TOILET EXHAUST FANS

1.5. AIR CONTROL DAMPER POSITION END SWITCHES

2. PURGE FAN OPERATION - "MAIN FAN PURGE SWITCH" SHALL SEND A

SIGNAL TO BMS EQUIPMENT TO SUPPLY 100% FRESH AIR AND EXHAUST

ALL AIR OUT OF THE BUILDING. ALL DAMPERS SHALL BE IN THE "OPEN"

POSITION.

3. SMOKE CONTROL PANEL SHOWN IS PER KIRKLAND SPECIFICATIONS.

EQUIVALENT PANELS MAY BE SUBMITTED FOR REVIEW AND ACCEPTANCE

IN ACCORDANCE WITH THE FIRE ALARM SPECIFICATION AS AN APPROVED

EQUAL.

Page 6: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA1.01

BASEMENT FIRE ALARM LAYOUT

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

BASEMENT FIRE ALARM LAYOUT

1/8" = 1'-0"

6

NOTES

1. FIRE ALARM EQUIPMENT USED FOR THE PURPOSES OF SMOKE CONTROL

ARE SHOWN IN PROXIMITY TO THE UNITS BEING SERVED. FIELD

VERIFICATION WILL BE NECESSARY FOR PROPER INSTALLATION.

2. MOTOR CONTROL CENTER EQUIPMENT USED FOR SMOKE CONTROL THAT

IS NOT PROVIDED WITH CONTACTS FOR POWER MONITORING SHALL BE

PROVIDED WITH VOLTAGE-SENSING RELAYS TO MONITOR FOR THE

PRESENCE OF POWER. MCCS USED FOR SMOKE CONTROL FANS SHALL

HAVE TWO ADJUSTABLE CT SWITCHES (ON AND OFF) TO MONITOR FOR

ELECTRICAL CURRENT DRAW DURING FAN OPERATION.

KEYED NOTES

1. FIRE WATER TANK - TWO MONITOR MODULES REQUIRED FOR TANK FILL

AND WATER TEMPERATURE.

2. DIESEL GENERATOR POWERED FIRE PUMP CONTROLLER LOCATIONS.

TWO CONTROLLERS ARE PRESENT.

3. FIRE PUMP VALVE TAMPERS - PROVIDE INDIVIDUAL MONITORING OF EACH

TAMPER SWITCH.

4. LOCATION OF THE MOTOR CONTROL CENTER FOR SP-1 AND SP-3 STAIR

PRESSURIZATION FANS FOR SMOKE CONTROL USE. MODULES LOCATED

AT THIS CONTROL EQUIPMENT INCLUDE.

4.1. FORCE ON - CONTROL MODULE

4.2. FORCE OFF - CONTROL MODULE

4.3. POWER MONITOR - MONITOR MODULE

4.4. ON STATUS - MONITOR MODULE

4.5. OFF STATUS - MONITOR MODULE

5. LOCATION OF CONTROL EQUIPMENT FOR NON-SMOKE CONTROL SUPPLY

FANS. EACH FAN CONTROL SHALL BE PROVIDED WITH THE FOLLOWING:

5.1. FORCE ON - CONTROL MODULE

5.2. FORCE OFF - CONTROL MODULE

5.3. ON STATUS - MONITOR MODULE

6. LOCATION OF CONTROL EQUIPMENT FOR NON-SMOKE CONTROL EXHAUST

FANS. EACH FAN CONTROL SHALL BE PROVIDED WITH THE FOLLOWING

DEVICES.

6.1. FORCE ON - CONTROL MODULE

6.2. FORCE OFF - CONTROL MODULE

6.3. ON STATUS - MONITOR MODULE

7. LOCATION OF SMOKE CONTROL STAIR PRESSURIZATION FAN. A MONITOR

MODULE SHALL BE PROVIDED AT THE MAINTENANCE DISCONNECT FOR

ON-POSITION MONITORING.

1

2

3

5

7

6

6

5

6

4

4

Page 7: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA1.02

1ST FLOOR FIRE ALARM LAYOUT,

AND P1/P2 FIRE ALARM LAYOUT

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

7

SCALE:

1ST FLOOR FIRE ALARM LAYOUT

1/8" = 1'-0"

NOTES

1. FIRE ALARM EQUIPMENT USED FOR THE PURPOSES OF SMOKE CONTROL

ARE SHOWN IN PROXIMITY TO THE UNITS BEING SERVED. FIELD

VERIFICATION WILL BE NECESSARY FOR PROPER INSTALLATION.

2. ALL DEVICES INSTALLED IN THE GARAGE AREA ARE TO BE

WEATHERPROOF DEVICES.

KEYED NOTES

1. CONTROL MODULE SHALL INTERLOCK WITH THE SECURITY PANEL

INTERFACE SHALL UNLOCK REQUIRED EGRESS DOORS AND OPEN

SECURITY GATES WHERE NECESSARY AS SPECIFIED BY THE OAKLAND

FIRE DEPARTMENT.

2. FIRE ALARM REMOTE ANNUNCIATOR PANEL LOCATED BEHIND THE GUARD

DESK.

3. LOCATION OF SMOKE CONTROL STAIR PRESSURIZATION FAN. A MONITOR

MODULE SHALL BE PROVIDED AT THE MAINTENANCE DISCONNECT FOR

ON-POSITION MONITORING.

4. LOCATION OF CONTROL EQUIPMENT FOR NON-SMOKE CONTROL EXHAUST

FANS. EACH FAN CONTROL SHALL BE PROVIDED WITH THE FOLLOWING

DEVICES.

4.1. FORCE ON - CONTROL MODULE

4.2. FORCE OFF - CONTROL MODULE

4.3. ON STATUS - MONITOR MODULE

5. MONITOR MODULES SHALL BE PLACED AT THE FIRE ALARM TERMINAL

CABINET TO MONITOR THE TERMINALS CONNECTED TO THE END

SWITCHES AT EACH DAMPER LOCATION. AC TRANSIT ASSUMES

RESPONSIBILITY FOR THE CONTINUITY OF THE WIRE FROM THE TERMINAL

CABINET TO THE DAMPER LOCATION. TWO (2) MONITOR MODULES WILL BE

REQUIRED FOR EACH OF THE TWO (2) DAMPERS, RESULTING IN FOUR (4)

MODULES REQUIRED.

6. TWO (2) CONTROL MODULES SHALL BE PLACED NEXT TO THE 24V/120V

POWER SUPPLY FOR FORCE OPEN AND FORCE CLOSED CONDITIONS.

1

2

3

4

4

65

Page 8: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA1.03

P3/P4 FLOOR FIRE ALARM LAYOUT

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

P3/P4 FIRE ALARM LAYOUT

1/8" = 1'-0"

8

NOTES

1. FIRE ALARM EQUIPMENT USED FOR THE PURPOSES OF SMOKE CONTROL

ARE SHOWN IN PROXIMITY TO THE UNITS BEING SERVED. FIELD

VERIFICATION WILL BE NECESSARY FOR PROPER INSTALLATION.

2. ALL DEVICES INSTALLED IN THE GARAGE AREA ARE TO BE

WEATHERPROOF DEVICES.

KEYED NOTES

1. PROVIDE HEAT DETECTORS WITHIN 2' OF EACH SPRINKLER HEAD.

2. PROVIDE THREE (3) RELAYS AND ONE (1) MONITOR MODULE FOR

ELEVATOR SERVICE CONNECTIONS.

3. LOCATION OF CONTROL EQUIPMENT FOR NON-SMOKE CONTROL SUPPLY

FANS. EACH FAN CONTROL SHALL BE PROVIDED WITH THE FOLLOWING:

3.1. FORCE ON - CONTROL MODULE

3.2. FORCE OFF - CONTROL MODULE

3.3. ON STATUS - MONITOR MODULE

4. LOCATION OF CONTROL EQUIPMENT FOR NON-SMOKE CONTROL EXHAUST

FANS. EACH FAN CONTROL SHALL BE PROVIDED WITH THE FOLLOWING

DEVICES.

4.1. FORCE ON - CONTROL MODULE

4.2. FORCE OFF - CONTROL MODULE

4.3. ON STATUS - MONITOR MODULE

1

1

2

3

4

4

4

4

4

Page 9: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA1.04

2ND FLOOR FIRE ALARM LAYOUT

AND P5/P6 FIRE ALARM LAYOUT

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

9

SCALE:

2ND FLOOR FIRE ALARM LAYOUT

1/8" = 1'-0"

NOTES

1. FIRE ALARM EQUIPMENT USED FOR THE PURPOSES OF SMOKE CONTROL

ARE SHOWN IN PROXIMITY TO THE UNITS BEING SERVED. FIELD

VERIFICATION WILL BE NECESSARY FOR PROPER INSTALLATION.

2. ALL DEVICES INSTALLED IN THE GARAGE AREA ARE TO BE

WEATHERPROOF DEVICES.

KEYED NOTES

1. LOCATION OF CONTROL EQUIPMENT FOR NON-SMOKE CONTROL EXHAUST

FANS. EACH FAN CONTROL SHALL BE PROVIDED WITH THE FOLLOWING

DEVICES.

1.1. FORCE ON - CONTROL MODULE

1.2. FORCE OFF - CONTROL MODULE

1.3. ON STATUS - MONITOR MODULE

2. MONITOR MODULES SHALL BE PLACED AT THE FIRE ALARM TERMINAL

CABINET TO MONITOR THE TERMINALS CONNECTED TO THE END

SWITCHES AT EACH DAMPER LOCATION. AC TRANSIT ASSUMES

RESPONSIBILITY FOR THE CONTINUITY OF THE WIRE FROM THE TERMINAL

CABINET TO THE DAMPER LOCATION. TWO (2) MONITOR MODULES WILL BE

REQUIRED FOR EACH OF THE TWO (2) DAMPERS, RESULTING IN FOUR (4)

MODULES REQUIRED.

3. TWO (2) CONTROL MODULES SHALL BE PLACED NEXT TO THE 24V/120V

POWER SUPPLY FOR FORCE OPEN AND FORCE CLOSED CONDITIONS.

3

2

1

Page 10: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA1.05

3RD FLOOR FIRE ALARM LAYOUT

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

3RD FLOOR FIRE ALARM LAYOUT

1/8" = 1'-0"

10

NOTES

1. FIRE ALARM EQUIPMENT USED FOR THE PURPOSES OF SMOKE CONTROL

ARE SHOWN IN PROXIMITY TO THE UNITS BEING SERVED. FIELD

VERIFICATION WILL BE NECESSARY FOR PROPER INSTALLATION.

KEYED NOTES

1. MONITOR MODULES SHALL BE PLACED AT THE FIRE ALARM TERMINAL

CABINET TO MONITOR THE TERMINALS CONNECTED TO THE END

SWITCHES AT EACH DAMPER LOCATION. AC TRANSIT ASSUMES

RESPONSIBILITY FOR THE CONTINUITY OF THE WIRE FROM THE TERMINAL

CABINET TO THE DAMPER LOCATION. TWO (2) MONITOR MODULES WILL BE

REQUIRED FOR EACH OF THE TWO (2) DAMPERS, RESULTING IN FOUR (4)

MODULES REQUIRED.

2. TWO (2) CONTROL MODULES SHALL BE PLACED NEXT TO THE 24V/120V

POWER SUPPLY FOR FORCE OPEN AND FORCE CLOSED CONDITIONS.

1

2

Page 11: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA1.06

4TH FLOOR FIRE ALARM LAYOUT

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

11

SCALE:

4TH FLOOR FIRE ALARM LAYOUT

1/8" = 1'-0"

NOTES

1. FIRE ALARM EQUIPMENT USED FOR THE PURPOSES OF SMOKE CONTROL

ARE SHOWN IN PROXIMITY TO THE UNITS BEING SERVED. FIELD

VERIFICATION WILL BE NECESSARY FOR PROPER INSTALLATION.

KEYED NOTES

1. MONITOR MODULES SHALL BE PLACED AT THE FIRE ALARM TERMINAL

CABINET TO MONITOR THE TERMINALS CONNECTED TO THE END

SWITCHES AT EACH DAMPER LOCATION. AC TRANSIT ASSUMES

RESPONSIBILITY FOR THE CONTINUITY OF THE WIRE FROM THE TERMINAL

CABINET TO THE DAMPER LOCATION. TWO (2) MONITOR MODULES WILL BE

REQUIRED FOR EACH OF THE TWO (2) DAMPERS, RESULTING IN FOUR (4)

MODULES REQUIRED.

2. TWO (2) CONTROL MODULES SHALL BE PLACED NEXT TO THE 24V/120V

POWER SUPPLY FOR FORCE OPEN AND FORCE CLOSED CONDITIONS.

1

2

Page 12: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA1.07

5TH FLOOR FIRE ALARM LAYOUT

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

5TH FLOOR FIRE ALARM LAYOUT

1/8" = 1'-0"

12

NOTES

1. FIRE ALARM EQUIPMENT USED FOR THE PURPOSES OF SMOKE CONTROL

ARE SHOWN IN PROXIMITY TO THE UNITS BEING SERVED. FIELD

VERIFICATION WILL BE NECESSARY FOR PROPER INSTALLATION.

KEYED NOTES

1. MONITOR MODULES SHALL BE PLACED AT THE FIRE ALARM TERMINAL

CABINET TO MONITOR THE TERMINALS CONNECTED TO THE END

SWITCHES AT EACH DAMPER LOCATION. AC TRANSIT ASSUMES

RESPONSIBILITY FOR THE CONTINUITY OF THE WIRE FROM THE TERMINAL

CABINET TO THE DAMPER LOCATION. TWO (2) MONITOR MODULES WILL BE

REQUIRED FOR EACH OF THE TWO (2) DAMPERS, RESULTING IN FOUR (4)

MODULES REQUIRED.

2. TWO (2) CONTROL MODULES SHALL BE PLACED NEXT TO THE 24V/120V

POWER SUPPLY FOR FORCE OPEN AND FORCE CLOSED CONDITIONS.

1

2

Page 13: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA1.08

6TH FLOOR FIRE ALARM LAYOUT

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

13

SCALE:

6TH FLOOR FIRE ALARM LAYOUT

1/8" = 1'-0"

NOTES

1. FIRE ALARM EQUIPMENT USED FOR THE PURPOSES OF SMOKE CONTROL

ARE SHOWN IN PROXIMITY TO THE UNITS BEING SERVED. FIELD

VERIFICATION WILL BE NECESSARY FOR PROPER INSTALLATION.

KEYED NOTES

1. MONITOR MODULES SHALL BE PLACED AT THE FIRE ALARM TERMINAL

CABINET TO MONITOR THE TERMINALS CONNECTED TO THE END

SWITCHES AT EACH DAMPER LOCATION. AC TRANSIT ASSUMES

RESPONSIBILITY FOR THE CONTINUITY OF THE WIRE FROM THE TERMINAL

CABINET TO THE DAMPER LOCATION. TWO (2) MONITOR MODULES WILL BE

REQUIRED FOR EACH OF THE TWO (2) DAMPERS, RESULTING IN FOUR (4)

MODULES REQUIRED.

2. TWO (2) CONTROL MODULES SHALL BE PLACED NEXT TO THE 24V/120V

POWER SUPPLY FOR FORCE OPEN AND FORCE CLOSED CONDITIONS.

2

1

Page 14: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA1.09

7TH FLOOR FIRE ALARM LAYOUT

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

7TH FLOOR FIRE ALARM LAYOUT

1/8" = 1'-0"

14

NOTES

1. FIRE ALARM EQUIPMENT USED FOR THE PURPOSES OF SMOKE CONTROL

ARE SHOWN IN PROXIMITY TO THE UNITS BEING SERVED. FIELD

VERIFICATION WILL BE NECESSARY FOR PROPER INSTALLATION.

KEYED NOTES

1. MONITOR MODULES SHALL BE PLACED AT THE FIRE ALARM TERMINAL

CABINET TO MONITOR THE TERMINALS CONNECTED TO THE END

SWITCHES AT EACH DAMPER LOCATION. AC TRANSIT ASSUMES

RESPONSIBILITY FOR THE CONTINUITY OF THE WIRE FROM THE TERMINAL

CABINET TO THE DAMPER LOCATION. TWO (2) MONITOR MODULES WILL BE

REQUIRED FOR EACH OF THE TWO (2) DAMPERS, RESULTING IN FOUR (4)

MODULES REQUIRED.

2. TWO (2) CONTROL MODULES SHALL BE PLACED NEXT TO THE 24V/120V

POWER SUPPLY FOR FORCE OPEN AND FORCE CLOSED CONDITIONS.

1

2

Page 15: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA1.10

8TH FLOOR FIRE ALARM LAYOUT

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

15

SCALE:

8TH FLOOR FIRE ALARM LAYOUT

1/8" = 1'-0"

NOTES

1. FIRE ALARM EQUIPMENT USED FOR THE PURPOSES OF SMOKE CONTROL

ARE SHOWN IN PROXIMITY TO THE UNITS BEING SERVED. FIELD

VERIFICATION WILL BE NECESSARY FOR PROPER INSTALLATION.

KEYED NOTES

1. MONITOR MODULES SHALL BE PLACED AT THE FIRE ALARM TERMINAL

CABINET TO MONITOR THE TERMINALS CONNECTED TO THE END

SWITCHES AT EACH DAMPER LOCATION. AC TRANSIT ASSUMES

RESPONSIBILITY FOR THE CONTINUITY OF THE WIRE FROM THE TERMINAL

CABINET TO THE DAMPER LOCATION. TWO (2) MONITOR MODULES WILL BE

REQUIRED FOR EACH OF THE TWO (2) DAMPERS, RESULTING IN FOUR (4)

MODULES REQUIRED.

2. TWO (2) CONTROL MODULES SHALL BE PLACED NEXT TO THE 24V/120V

POWER SUPPLY FOR FORCE OPEN AND FORCE CLOSED CONDITIONS.

1

2

Page 16: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA1.11

9TH FLOOR FIRE ALARM LAYOUT

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

9TH FLOOR FIRE ALARM LAYOUT

1/8" = 1'-0"

16

NOTES

1. FIRE ALARM EQUIPMENT USED FOR THE PURPOSES OF SMOKE CONTROL

ARE SHOWN IN PROXIMITY TO THE UNITS BEING SERVED. FIELD

VERIFICATION WILL BE NECESSARY FOR PROPER INSTALLATION.

KEYED NOTES

1. MONITOR MODULES SHALL BE PLACED AT THE FIRE ALARM TERMINAL

CABINET TO MONITOR THE TERMINALS CONNECTED TO THE END

SWITCHES AT EACH DAMPER LOCATION. AC TRANSIT ASSUMES

RESPONSIBILITY FOR THE CONTINUITY OF THE WIRE FROM THE TERMINAL

CABINET TO THE DAMPER LOCATION. TWO (2) MONITOR MODULES WILL BE

REQUIRED FOR EACH OF THE TWO (2) DAMPERS, RESULTING IN FOUR (4)

MODULES REQUIRED.

2. TWO (2) CONTROL MODULES SHALL BE PLACED NEXT TO THE 24V/120V

POWER SUPPLY FOR FORCE OPEN AND FORCE CLOSED CONDITIONS.

3. PREACTION PANEL SHALL BE MONITORED FOR ALARM, SUPERVISORY, AND

TROUBLE CONDITIONS. PREACTION PANEL TO REMAIN.

4. HALON RELEASING PANEL SHALL BE MONITORED FOR ALARM AND

TROUBLE CONDITIONS. HALON PANEL TO REMAIN.

5. LOCATION OF PREACTION HARDWARE (CONTROLLED BY PREACTION

PANEL, FOR INFORMATION ONLY).

1

4

4

3

2

Page 17: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA1.12

10TH FLOOR FIRE ALARM LAYOUT

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

17

SCALE:

10TH FLOOR FIRE ALARM LAYOUT

1/8" = 1'-0"

NOTES

1. FIRE ALARM EQUIPMENT USED FOR THE PURPOSES OF SMOKE CONTROL

ARE SHOWN IN PROXIMITY TO THE UNITS BEING SERVED. FIELD

VERIFICATION WILL BE NECESSARY FOR PROPER INSTALLATION.

KEYED NOTES

1. MONITOR MODULES SHALL BE PLACED AT THE FIRE ALARM TERMINAL

CABINET TO MONITOR THE TERMINALS CONNECTED TO THE END

SWITCHES AT EACH DAMPER LOCATION. AC TRANSIT ASSUMES

RESPONSIBILITY FOR THE CONTINUITY OF THE WIRE FROM THE TERMINAL

CABINET TO THE DAMPER LOCATION. TWO (2) MONITOR MODULES WILL BE

REQUIRED FOR EACH OF THE TWO (2) DAMPERS, RESULTING IN FOUR (4)

MODULES REQUIRED.

2. TWO (2) CONTROL MODULES SHALL BE PLACED NEXT TO THE 24V/120V

POWER SUPPLY FOR FORCE OPEN AND FORCE CLOSED CONDITIONS.

3. CONTROL MODULE SHALL INTERFACE WITH THE DOOR SECURITY PANEL

LOCATED IN THE ELECTRICAL ROOM. LOCATIONS OF CARD READERS ARE

SHOWN. COORDINATE WITH SECURITY.

4. NEW WIRE/CONDUIT FOR MAGNETIC DOOR RELEASE IS REQUIRED.

DEMOLISH THE EXISTING EQUIPMENT.

1

3

3

3

4

2

Page 18: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FA1.13

PENTHOUSE/ROOF FIRE ALARM

LAYOUT

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

PENTHOUSE/ROOF FIRE ALARM LAYOUT

1/8" = 1'-0"

18

NOTES

1. FIRE ALARM EQUIPMENT USED FOR THE PURPOSES OF SMOKE CONTROL

ARE SHOWN IN PROXIMITY TO THE UNITS BEING SERVED. FIELD

VERIFICATION WILL BE NECESSARY FOR PROPER INSTALLATION.

2. CONDUIT INSTALLATION ON THE ROOF DECK WILL NOT BE PERMITTED.

COORDINATE WITH THE OWNER FOR ACCEPTABLE PATHWAYS FOR

CONDUIT ROUTING TO EQUIPMENT.

3. MOTOR CONTROL CENTER EQUIPMENT THAT IS NOT PROVIDED WITH

CONTACTS FOR POWER MONITORING SHALL BE PROVIDED WITH CT

SWITCHES TO MONITOR FOR THE PRESENCE OF ELECTRICAL CURRENT

DURING FAN OPERATION.

KEYED NOTES

1. PROVIDE HEAT DETECTORS WITHIN 2' OF EACH SPRINKLER HEAD.

2. LOCATION OF RISER PENETRATION TO PENTHOUSE.

3. LOCATION OF CONTROL EQUIPMENT FOR SMOKE CONTROL SUPPLY FANS.

EACH FAN CONTROL SHALL BE PROVIDED WITH THE FOLLOWING DEVICES

AT THE MCC. FANS CONTROLLED ARE SP-2, SP-4, SX-1, SF-1B, AND SF-1E.

3.1. FORCE ON - CONTROL MODULE

3.2. FORCE OFF - CONTROL MODULE

3.3. POWER MONITOR - MONITOR MODULE

3.4. ON STATUS - MONITOR MODULE

3.5. OFF STATUS - MONITOR MODULE

4. LOCATION OF CONTROL EQUIPMENT FOR NON-SMOKE CONTROL SUPPLY

FANS. EACH FAN CONTROL SHALL BE PROVIDED WITH THE FOLLOWING:

4.1. FORCE ON - CONTROL MODULE

4.2. FORCE OFF - CONTROL MODULE

4.3. OFF STATUS - MONITOR MODULE

5. LOCATION OF CONTROL EQUIPMENT FOR NON-SMOKE CONTROL EXHAUST

FANS. EACH FAN CONTROL SHALL BE PROVIDED WITH THE FOLLOWING

DEVICES.

5.1. FORCE ON - CONTROL MODULE

5.2. FORCE OFF - CONTROL MODULE

5.3. OFF STATUS - MONITOR MODULE

6. TOILET EXHAUST FAN E-1. RELOCATE CONTROL WIRING TO NEW JUNCTION

BOX.

7. FIRE SMOKE DAMPER INTERFACE

7.1. FORCE CLOSE - CONTROL MODULE

7.2. OPEN STATUS - MONITOR MODULE

7.3. CLOSED STATUS - MONITOR MODULE

8. LOCATION OF SMOKE CONTROL STAIR PRESSURIZATION FAN. A MONITOR

MODULE SHALL BE PROVIDED AT THE MAINTENANCE DISCONNECT FOR

ON-POSITION MONITORING.

1

1

1 1

1

1

11

11 1

2

5

5

7

3

4

8

8

7

7

6

3

Page 19: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FD1.01

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

BASEMENT DEMOLITION LAYOUT

3/32" = 1'-0"

19

SCALE:

1ST FLOOR DEMOLITION LAYOUT

3/32" = 1'-0"

NOTES

Page 20: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FD1.02

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

P3/P4 DEMOLITION LAYOUT

3/32" = 1'-0"

20

SCALE:

2ND FLOOR DEMOLITION LAYOUT

3/32" = 1'-0"

NOTES

Page 21: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FD1.03

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

3RD FLOOR DEMOLITION LAYOUT

3/32" = 1'-0"

21

SCALE:

4TH FLOOR DEMOLITION LAYOUT

3/32" = 1'-0"

NOTES

Page 22: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FD1.04

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

5TH FLOOR DEMOLITION LAYOUT

3/32" = 1'-0"

22

SCALE:

6TH FLOOR DEMOLITION LAYOUT

3/32" = 1'-0"

NOTES

Page 23: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FD1.05

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

7TH FLOOR DEMOLITION LAYOUT

3/32" = 1'-0"

23

SCALE:

8TH FLOOR DEMOLITION LAYOUT

3/32" = 1'-0"

NOTES

Page 24: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FD1.06

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

9TH FLOOR DEMOLITION LAYOUT

3/32" = 1'-0"

24

SCALE:

10TH FLOOR DEMOLITION LAYOUT

3/32" = 1'-0"

NOTES

KEYED NOTES

Page 25: 1600 FRANKLIN STREET - AC Transit · fa1.01 basement fire alarm layout fd1.05 7th & 8th floor demolition layout fa1.02 1st floor fire alarm layout and p1/p2 fire alarm layout fd1.06

LEGEND

FD1.07

THE COPYING OR RE-USE OF THIS DOCUMENT,

OR PORTIONS THEREOF, FOR ANY REASON

OTHER THAN THE ORIGINAL PROJECT OR THE

PURPOSE ORIGINALLY INTENDED, WITHOUT

THE CONSENT OF HUGHES ASSOCIATES, INC.

IS PROHIBITED.

HAI PROJECT NO.

RevisionNo. Date

2551 San Ramon Valley Blvd, Suite 209

San Ramon, CA 94583

Phone (925)314-7910

Fax (925)314-9750

Scale:

Grap

hics

Pro

ject D

escrip

tio

nD

esig

nD

raw

in

g T

itle

Draw

in

g N

o.

4321

1 2 3 4

A

B

C

D

Design:

Drawn:

Review:

Date:

Location:

HUGHES ASSOCIATES, INC.

Fire Science & Engineering

1RJW00050.002

CRA

CRA

RJW

March 8, 2013

AC TRANSIT

FIRE ALARM

UPGRADE PROJECT

IFB 2013-1247

1600 Franklin St.

Oakland, CA

A

B

C

D

Sheet:of 25

BID DESIGN SET

SCALE:

PENTHOUSE DEMOLITION LAYOUT

3/32" = 1'-0"

25

KEYED NOTESNOTES