Fire Alarm System Design & Maintenance
Lee Daly
Total Fire Alarm & Security Inc.
11/08/16
![Page 2: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/2.jpg)
Agenda
• History of Fire Alarm Systems / Original & Current State Fire Codes pertaining to Multi-Housing in MN
• Typical Fire Alarm System Design – (3) Basic Types of Facilities for Multi-Housing
• Residential Space vs. Common Area
• Typical Sprinkler System Design
• Maintenance & Annual Inspections
![Page 3: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/3.jpg)
History of Fire Alarm System Requirements for Multi-Housing
Facilities in Minnesota
Original State Fire Codes: • Manual Activation Only (1960’s – 1970’s) • Automatic Heat Detection (1970’s – 1980’s) • Automatic Smoke Detection (Mid 1980’s) • ADA Requirements – Strobes (1990’s) International Fire Code (IFC): • Sprinkler System Exceptions (Mid 2000’s)
![Page 4: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/4.jpg)
Early Fire Alarm Systems
![Page 5: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/5.jpg)
No Alarm System - Yell Fire!
![Page 6: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/6.jpg)
Manual Activation Only (60’s – 70’s)
![Page 7: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/7.jpg)
Automatic Heat Detection (70’s)
![Page 8: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/8.jpg)
Automatic Smoke Detection (80’s)
![Page 9: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/9.jpg)
Transition from Bells to Horns & Speakers for High-Rises (80’s)
![Page 10: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/10.jpg)
ADA Legislation – Strobes (90’s)
![Page 11: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/11.jpg)
75 Db Requirement - Mini-Horns in Living Rooms/Bedrooms (90’s)
![Page 12: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/12.jpg)
Addressable Technology (90’s)
• Manual Pull Stations, Smoke/Heat Detectors, & Sprinkler Devices are all identified on a per point basis
• Verses the Traditional Zoned System (typically by Floor or Area of Building)
![Page 13: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/13.jpg)
MN Adopts International Fire Code – IFC (early 2000’s)
• Sprinkler System Exception – Allows Manual Pull Stations & Smoke Detectors to be Eliminated in Buildings with 100% Sprinkler System (New Construction)
• (1) Manual Pull Station only at Main Panel
• Smoke Detectors only at Elevator Lobbies (elevator capture) & Door Holder Control
![Page 14: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/14.jpg)
Present Fire Alarm System Design Requirements - Basic R-2 Occupancy
• Fire Alarm Systems required for any building 16 units or larger or 3 occupied levels or more
• 24/7 Fire Monitoring is required for all buildings with Sprinkler Systems regardless of size - Townhomes, etc.
• Independent Residential Smoke Detectors are required in Residents Living Space (not to be connected to central Fire Alarm System)
![Page 15: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/15.jpg)
Non-Sprinklered R-2 Occupancy
• Manual Pull Stations at all exits
• Heat Detectors in boiler rooms, laundry rooms, storage rooms, & parking garages
• Smoke Detectors 30’ on center in all common corridors, at elevator lobbies, & door holders
• Horns & Strobes required in all common areas (corridors, restrooms, laundry rooms, etc.)
• Mini-Horns required in all resident bedrooms
![Page 16: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/16.jpg)
Fully Sprinklered R-2 Occupancy
• Manual Pull Stations at exits (1) Only
• Heat Detectors in boiler rooms, laundry rooms, storage rooms, & parking garages (Sprinkler Heads monitored by Fire Panel)
• Smoke Detectors 30’ on center in all common corridors, at elevator lobbies, & door holders
• Horns & Strobes required in all common areas
• (corridors, restrooms, laundry rooms, etc)
• Mini-Horns required in all resident bedrooms
![Page 17: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/17.jpg)
Typical Fire Alarm System & Design by Building Type
![Page 18: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/18.jpg)
Building Type 1 - Townhomes R-2
Separate Resident Entrances & No Common Corridors or Areas
Sprinkler System with 24/7 Fire Monitoring Panel Required Only
![Page 19: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/19.jpg)
Typical Townhome Outside Entrance to Sprinkler Room & Monitoring Panel
![Page 20: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/20.jpg)
Building Type 2 – Low-Rise R-2
Common Entrance & Corridors to Resident Units (Typically 3 – 5 Floors)
Central Fire Alarm System Required per State IFC
![Page 21: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/21.jpg)
Low-Rise R-2 – Non Sprinklered
![Page 22: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/22.jpg)
Low-Rise R2 – Sprinklered Low Frequency Horns in Bedrooms
![Page 23: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/23.jpg)
Building Type 3 – High-Rise R2
More Than 75 Feet Above Street Level (or Fire Dept. Access)
![Page 24: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/24.jpg)
High-Rise R2 – Sprinklered Speakers in Bedrooms
![Page 25: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/25.jpg)
Self-Contained Smoke Detectors Required in Residential Space
![Page 26: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/26.jpg)
Ionization & Photoelectric Types
![Page 27: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/27.jpg)
Typical Layout of Residential Self-Contained Smoke Detectors
New Construction
![Page 28: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/28.jpg)
Residential Smoke Requirements
• New Construction – 120VAC with battery backup Interconnected & located in Hallways outside Bedrooms & in each Bedroom
• Existing Buildings (after 8/1/89) – 120VAC with battery backup & located in Hallways outside Bedrooms (No Interconnection)
• Existing Buildings (before 8/1/89) – Battery Operated OK & located in Hallways outside Bedrooms (No Interconnection)
![Page 29: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/29.jpg)
Replacement Requirements for Residential Smoke Detectors
• If they Fail to Respond when Tested
• When they exceed 10 Years from the date of manufacture
• Must be replaced with same type of device:
120VAC with Battery
Battery Only
Interconnected
![Page 30: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/30.jpg)
CO Detectors Required for Gas Appliances In Residential Space
![Page 31: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/31.jpg)
CO Detector Exception
• In Buildings with centrally located gas appliances (boiler room, laundry rooms, etc.)
• CO Detectors can be installed at the location of the gas appliances only and not in each residential unit
• CO Detectors must be connected to the building fire alarm system and be monitored 24/7 by and outside monitoring service
![Page 32: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/32.jpg)
Mini-Horns or Speakers required in Bedrooms of Residential Space
![Page 33: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/33.jpg)
Typical Sprinkler Systems in Multi-Housing Buildings
Required to be connected to the Central Fire Alarm System
with 24/7 Monitoring
![Page 34: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/34.jpg)
Wet Sprinkler System (Common Areas & Residential Space)
![Page 35: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/35.jpg)
Dry Sprinkler System (Unheated Garages & Attics)
![Page 36: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/36.jpg)
Typical Sprinkler Riser Room (Fire Pump for High-Rises)
![Page 37: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/37.jpg)
Maintenance & Annual Inspections
![Page 38: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/38.jpg)
State IFC Requires Annual Inspections of Fire Alarm & Sprinkler Systems
• 100% Inspection of all Systems Devices: Smoke Detectors, Heat Detectors, Manual Pull Stations, Door Holders, & other Associated Equipment. Sprinkler Wet & Dry Systems.
• Fire Pumps (April – October in MN)
• Horns & Strobes must be activated
• Main Panel & Remote Panels Battery Load Test
• Monitoring Signals Verified with Central Station
![Page 39: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/39.jpg)
Maintenance Items that should be included during Annual Inspection
• Smoke Detectors should be cleaned & tested for sensitivity levels (if addressable system)
• Batteries should be replaced if they fail the required load test (5-Year Replacement Plan)
• Main Panel should be tested for all alarm, trouble, supervisory, reset, & silence functions
• Main Panel should have manufacturers firmware upgrades installed
![Page 40: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/40.jpg)
Smoke Detectors are the most active device = Problems if not Maintained
![Page 41: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/41.jpg)
Protect Smoke Detectors Temporarily Construction/Garage Cleaning
![Page 42: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/42.jpg)
City Fire Inspector Variances on Maintenance & Inspections
• Generally Cities in MN enforce the State IFC and NFPA Testing Standards
• Some may require more than State IFC
• UL Certificates have been initiated by some Fire Marshals in the Metro Area
• UL requires more Documentation/ 1 Hour Alarm Response/ 4 Hour Trouble Response
• Higher Monitoring/Service Contract Costs
![Page 43: Fire Alarm System Design & Maintenance - … · Typical Layout of Residential Self-Contained Smoke Detectors New Construction . Residential Smoke Requirements ... of Fire Alarm &](https://reader031.fdocuments.us/reader031/viewer/2022021718/5b7c84867f8b9aa74b8e825c/html5/thumbnails/43.jpg)
UL Certificate/Monitoring Cities
Brooklyn Center Coon Rapids
Brooklyn Park Eden Prairie
Burnsville Golden Valley
Chanhassen Maple Grove
Chaska Plymouth
Shakopee