m WorleyParsons ËcoNomicS resources & energy KUWAIT OIL COMPANY 1 1 C897240-|C-SPC-001 0 Rev 0 15, October 2012 LOWER FARS HEAVY OIL DEVELOPMENT FEED WorleyParsons Canada Services Ltd. Calgary Division Heavy Oil Business Unit 540 - 12' Avenue SW Calgary, Alberta T2R OH4 Telephone: (403) 508-5300 Facsimile: (403)508-5301 www.worleyparsons.com ABN 6't 001 279812 @ Copyrlght 2010 WorleyParsons o .f $. :m uJl,-É¡¡+¡J ..trrr.d.ffi.ã- Project Specific Criteria To KOC Standard For Gontrol And Shut Down Valves (KOC-t-010) 9 B N4 ¿l e -// ,/,

Transcript of 11 c8972 00-ic-spc-0010-criteria to koc-i-010

Page 1: 11 c8972 00-ic-spc-0010-criteria to koc-i-010

m WorleyParsons ËcoNomicSresources & energy

KUWAIT OIL COMPANY

1 1 C897240-|C-SPC-001 0 Rev 0

15, October 2012

LOWER FARS HEAVY OIL DEVELOPMENT FEED

WorleyParsons Canada Services Ltd.Calgary Division Heavy Oil Business Unit540 - 12' Avenue SWCalgary, AlbertaT2R OH4

Telephone: (403) 508-5300Facsimile: (403)508-5301www.worleyparsons.comABN 6't 001 279812@ Copyrlght 2010 WorleyParsons

o.f$.

:muJl,-É¡¡+¡J..trrr.d.ffi.ã-

Project Specific Criteria To KOC StandardFor Gontrol And Shut Down Valves(KOC-t-010)

9BN4

¿l e -//,/,

Page 2: 11 c8972 00-ic-spc-0010-criteria to koc-i-010

m WorleyParsong ÉcoNomicSresources & eneÌgy

KUWAITOIL COMPANY

LOWER FARS HEAVY OIL DEVELOPMENT

PROJECT SPECIFIC GRITERIATO KOC STANDARD

FOR CONTROL AND SI{UT DOWN VALVES

SYNOPStSThis document presents the Project Specific Criteria To KOC Standard For ConlrolAnd Shut Down Valves(KOC-|-O10) for the Kuwait Oil Company Lower Fars Heavy Oil Development Feed Project.

Disclalmer

This document is conceptual in nature and represents the work of WorleyParsons performed to recognizedengineering principles and practices appropriate for conceptual engineering work and the terms of referencepovided by WorleyParsons' contractual Customer, Kuwait Oil Company (the "Customef). This document maynot be relied upon for detailed implementation or any other purposa not specifically identified within thisdocument. This document is confidential and prepared solely for the use of fhe Customer. The contents of thisdocument may not be usad or relied upon by any party other than the Customer, and neither WorleyParsons,ús sub consultants nor their respective employees assurne any liability for any reason, including, but notIímited to, negllgence, to any other party for any informatÌon or representation herein. The extent of anywamnty or guarantee of this document or the information contained therein in favour of the Cusfomer lslimited to the wananty or guarantee, if any, contained in the contract between the Customer andWorleyParsons.

DOC. NO. 11C8972-00-|C-SPC-0010 Rev 0 Proj Spec Criteria for KOC-|-O1O.docREV DESCRIFNON ORIGINATOR

11C8972-00.1C€PC-0010 Rev 0 Prcj Spæ Critoria lor KOC.|.010.dæ

4 10t15t2012

WORLEYPARSOI€APPROVAL DA-TE

CLIENTAPPROVAL DATE

É.R

<)<(

REVIEW

!ilAffie.au".¡W.dJJ-¡lrÂJã3.ãt12D- Pur(¡lllsu€d ForADoml G. Ellaschuk

N'A¡.¡ôr10- 2011t'- Púm¡llG. Ellsschuklsusd Fr Råvl6w

N/Aodfs.ältA Ft.r.h[kG,SæmilhH -qh.ñissuod ForSouãd Chðck

¡¡.

*

Pä96 2 of 7

ú

Page 3: 11 c8972 00-ic-spc-0010-criteria to koc-i-010

WorleyParsons EcoNomicSresources & energy

KUWAIT OIL COMPANY

LOWER FARS HEAVYOIL DEVELOPMENT

PROJECT SPEC¡FIC CRITERIATO KOC STANDARD

FOR CONTROL AND SHUT DOWN VALVES (KOC.TOIO)

The following Project Specific Criteria shall apply to KOC Standard for Control and Shutdown Valves

(KOC-|-O10, Rev 1).

Section 3.0 - TERMINOLOGY

Sub-Section 3.2

r Add the following:

MOV Motor Operated Valve

Section a.0 - REFERENGE ,9ODES ANR,.STANDARDS,

Sub-Section 4.2.2

Add the following:

tsA 75.08.06: Face-to-Face Dimensions for lntegral Flanged Globe Style Control

Valve Bodies (Classes 900, 1500 and 2500).

Valve lnspection and Testing

Specification for Pipeline Valves

APt 598:

API 6D:

Rewrite as follows:

ISA 75.01 to:

lsA 75.03

ISA 75.01.01: Flow Equations for Sizing Control Valves

ISA 75.08.01: Face-to-Face Dimensions for lntegral Flanged Globe

Style Control Valve Bodies (Classes 125, 150, 250, 300 and ô00).

ISA 75.08.02: Face-to-Face Dimensions for Flangeless Control

Valves (Classes 150, 300 and 600).

NACE MR0175/lSO 15156 Petroleum and naturalgas industries-Materials for use in H2S-containing environments in oil and gas

production

¡sA 75.04

NACE MRO175

Sub-Sectlon 4.2.3

I 1C8072{0-|C-SPC{010 R€v 0 Prcl spoc Crit*h for

4 ßt15m12

ffi

I

o{1r

*

Page 3 ol 7

rl,

Page 4: 11 c8972 00-ic-spc-0010-criteria to koc-i-010

m WorleyParsons €coNomicS ffiresou¡ces & ener8y

KUWAITOIL COMPAI,IY

LOWER FARS HEAVY OIL DEVELOPMENT

PROJECT SPECIFIC CRITERIA TO KOC STANDARD

FOR CONTROL AND SHUT DOWN VALVES (KOC-I-OIO)

a Add the following:

KOC-E-O13: KOC Standard for Motor Operated Vafve Actuators

11C8972-00-EL-SPC-0005: ProjectSpecificCriteria-KOC Recommended

Practice for Selection, lnstallation and Maintenance of Electrical

Equipment ln Hazardous Areas: Part 1: General Requirements(KOC-E-004 Part 1)

11C8972-00-EL-SPC-0006: ProjectSpecificCriteria-KOC Recommended

Practice for Selection, lnstallation and Maintenance of Electrical

Equipment ln Hazardous Areas: Part 2: Flameproof Enclosure'D'(KOC-E-004 Paft2)

11C8972-00-EL-SPC-0007: ProjectSpecilicCriteria-KOCRecommendedPractice for Selaction, lnstallation and Maintenance of Electrical

Equipment ln Hazardous Areas: Part 3: lntrinsic Safety'l'(KOC-E-004 Part 3)

11C8972-00-lC-SPC-1903: Addendum To KOC Specification General lnstruments(015 JH 1e03)

Sub-Section 4.2.4

¡ Add the following nsw sub-section 4.2.4,015 Series of KOC Specificationr

015-JH-1903 Generallnstruments

KOC-I-004 KOC Standard for Shutdown systems

Sub-Section 4.2.5

Add the following new sub-section 4,2.5, General:

ln any document where reference is made to a Standard or Specification, lhen the

reference automatically includes lhe contents of the addendum or criteria of that

specification (where an addendum or criteria has been issued).

Where specific standards have been withdrawn, superseded or made obsolete, the

latest replacement standards shall be used. Whenever the specifications are

referenced, they include the addendum as indicated in the Project Tender Work Scope.

1 1C8972{0-lc-SPC{o10 Rw 0 Proi SpEc Critorla for KOCJ4Io.doc

a

É,,RN¡

4 1Q115t2012o<(

*

4ot7

r/,

Page 5: 11 c8972 00-ic-spc-0010-criteria to koc-i-010

llllorleyParsonsresources & energy

KUWAIT OIL COMPANY

LOWER FARS HEAVY OIL DEVELOPMENT

PROJECT SPECIFIC CRITERIATO KOC STANDARD

FOR CONTROL AND SHUT DOWN VALVES (KOC'|-010)

EcoNomicS ,ffi

Section 7.0 - SERVICE CONDITIONS

Sub-Sectlon 7.1.2

Rewrite as follows:

'NACE 0175" "NACE MR0175/|SO 150156"

Se,ction 8.0 - ÇoNIRoL VALVES

Sub-Section 8.2.4

o Rewrite as follows:

ISA 75.03 as ISA 75.08.01 and ISA 75.04 as ISA 75.08.02

Sub-Section 8.2.5

¡ Add the following:

Control Valve body material shall also be in accordance with the material required by

the line specification (Piping Glass).

Sub-Section 8.3.7

¡ Rewrite as follows:

'NACE 0175" "NACE MR0175/tSO 150156',.

Section 9.0 - CONTROL VALVE ACTUATORS

Sub-Section 9.4.3

Rewrite as followsl

"NACE 0175' 'NACE MR0175/|SO 150156".

Sub-Sectlon 9.6

a Append:

11C8972.00-|C€PC.0010 Rw 0 Proispæ crüêrlå ftrI 10t1il2412

a

a

*

oÍ7

tu

Page 6: 11 c8972 00-ic-spc-0010-criteria to koc-i-010

M WorleyParsonE ÊcoNomicS mresoutces & energy

KUWAITOIL COMPAT¡Y

LOWER FARS HEAVY OIL DEVELOPMENT

PROJECT SPECIFIC CRITERIATO KOC STANDARD

FOR CONTROL AND SHUT DOWN VALVES {KOC.I.O1O)

Electric actuated MOVs are covered by KOC Standard for Motor Operated Valve

Actuators, KOC-E-013 and its project specific crileria (Document Number:

1 1 C8972-00-EL-SPC-oo1 9).

Sgction 10.0.- ÇONTRO-,L VALVE AÇGESSOR¡ES

Sub-Ssction 10.1 - Valve Positioners

Sub-Sectlon 10.1.4

r Replace item b.):

Positioners shall be SMART with Foundation Fieldbus communicalion protocol.

Sub-Section 10.7 - Solenoid Valves

Sub-Section 10.7.1

Add the followingi

Three-way direct acting Solenoid Valves which have top mounted vents shall have

their vents piped so that moisture/sand does not entor the valve. Solenoid vents shall

have bug screens.

secrion 11.2 - FLASHING.J$ND CAVITATION

Sub.Sectlon ll.2.l

a

a Add the following at the end:

ln any case, whenever either flashing or cavitation is expected, hardened material for

valve trim including seat and plug shall be specified.

Sect¡on 12.0 - SH!''ITPQWN V.A*LY*ES

Sub-Section 12.4.6

11C097240.1C€PC{010 R€v 0 PojSpæ Crltsrlá tor

4 1011512012 o

c*

Pago ô ol 7

rl,

Page 7: 11 c8972 00-ic-spc-0010-criteria to koc-i-010

@ WorleyParsona ËcoNomicSresources & energy

KUWAIT OIL COMPANY

LOWER FARS HEAVY OIL DEVELOPMENT

PROJECT SPECIFIC GRITERIATO KOC STANDARD

FOR CONTROLAND SHUT DOWN VALVES (KOC-|-010)

r Replace'switches with'transmitters'

Sub-Section 12.5.1

¡ Add the following:

All limit switches shall be equipped with line break resistors.

Sub-Section 12.5.3

. Add the following:

Limit switches shall be completely wired to a Junction Box installed on the valves and

shall meet the electrical hazardous area classification.

Sub-Sectlon 12.7

o Add the following:

- Pushbutton for Partial Stroke Testing of Shutdown Valves

- Tripped/ Available Status lndication of Shutdown Valves

Sub-Section 12.9

a Add the following new Sub-Section 12.9 Partial Stroke

Hardware and software to perform partial stroke testing shall be provided on ESD

valves, if required, by safety review to improve availability of valve. Positioner withpartial stroke testing functionality shall use SMART HART communication protocol

11C8972{0íC-SPC{010 R€v 0 Pþl Sp€c Crilerie for Kocl.o1o,doc4 t0/'1512012

ffi

f.R

d,