1. Test programme
Type test of a terminal cable lug (barrel & pin)
Type test (electrical part) including short circuit test (class A)
corresponding CD IEC 61238-3:2014 Annex J
IEH - Bereich Hochspannungsprüftechnik
Test report 2016-84/1
6 samples
Measuring of resistance factor k0
First heat cycle
Second heat cycle
Heat cycles 3 - 200
Measuring of resistance factor k2
Thermal short circuit
Measuring of resistance factor k3
Heat cycles 201 - 250
Measuring of resistance factor k4
Heat cycles 251 - 1000 with measuring of resistance factor kx
every 75 cycles
Type test of screened separable elbow
connector
Type test according to Cenelec EN IEC 61442 Ed. (03/2005) HD 629.1 S2
(02/2006) + A1 (09/2008)
Table 7 test sequence D1
ELABTest report 213 17 15
6 samples
DC withstand
AC withstand dry
Partial discharge @ ambient temp
Impulse withstand @ elevated temp
Heat cycles in air
Heat cycles in water
Disconnect - reconnect
Partial discharge @ elevated temp
Partial discharge @ ambient temp
Impulse withstand @ ambient temp
AC withstand dry
Examination
3
02/2018
2. Type test of the terminal cable lug2.1 Test arrangement
2.2 Results
Test description Criteria Results1 Resistance measurement after assembly Initial scatter δ ≤ 0.30 OK
δija = 0.18δijb = 0.04
2 Resistance measurement before short circuit test(after cycles 1 - 200)
Relative resistance factork/k0 ≤ 2.0
OKk/k0(ija) ≤ 1.2k/k0(ijb) ≤ 1.0
3 Resistance measurement after short circuit test Relative resistance factork/k0 ≤ 2.0
OKk/k0(ija) ≤ 1.4k/k0(ijb) ≤ 1.0
4 Maximum temperature during cycles (201 - 1000) Temperature of lug lower than linking pin (Θlinking pin = 134 °C) and reference conductor (Θref = 120 °C)
OKΘlug ≤ 119 °C
5 Statistical evaluation of resistance factors during cycles (201 - 1000) Scatter β ≤ 0.30
Change in resistance factor D ≤ 0.15Resistance factor ration λ ≤ 2.0
OKβija = 0.30 βijb = 0.04Dija ≤ 0.11 Dijb ≤ 0.10λija ≤ 1.6 λijb ≤ 1.1
All samples successfully passed the IEC 61238-3:2014 specifications.(Full test report 'IEH - Bereich Hochspannungsprüftechnik Test report 2016-84/1' available on request)
4
3. Type test of the screened separable connector3.1 Test arrangement
3.2 Results
Test description Criteria Results1 DC withstand voltage test
Apply 76 kV DC during 15 minutesNo breakdown or flashover shall occur OK
2 AC withstand voltage test, dry Apply 57 kV DC during 5 minutes
No breakdown or flashover shall occur OK
3 Partial discharge measurement at ambient temp Apply 28.2 kV for 1 min., measure at 25 kV
< 10 pC OK
4 Impulse voltage at elevated temp Conductor temp: 95 °C - 100 °C 10 positive and 10 negative impulses of 125 kV
No breakdown or flashover shall occur OK
5 Electrical heat cycling in air (63x) Apply 32 kV Heating current 2 h per 8 h: tref: 95 °C - 100 °C
No breakdown or flashover shall occur OK
6 Electrical heat cycling submersed in water (63x) Apply 32 kV Heating current 2 h per 8 h: tref: 95 °C - 100 °C
No breakdown or flashover shall occur OK
7 Disconnect and reconnect from bushing 5 times No damage to contact elements OK
8 Partial discharge measurement at elevated temp Conductor temp: 95 °C - 100 °C Apply 28.2 kV for 1 min., measure at 25 kV
< 10 pC OK
9 Partial discharge measurement at ambient temp Apply 28.2 kV for 1 min., measure at 25 kV
< 10 pC OK
10 Impulse voltage at ambient temp 10 positive and 10 negative impulses of 125 kV
No breakdown or flashover shall occur OK
11 AC withstand voltage test, dry Apply 57 kV DC during 5 minutes
No breakdown or flashover shall occur OK
12 Examination For information only Performed
All samples successfully passed the HD 629.1 S2 (02/2006) + A1 (09/2008) Table 7, D1 specifications.(Full test report 'Elab TE 213 17 15' available on request)
K400RTPA reducing tap plug
12/20 kV50 mm² Cu cableK200LR
K200LR
AFN20 termination
AFN20 termination
K400RTPA reducing tap plug
Current injection transformer
K400BE bushing extender
ELECTRICAL TESTING LABORATORY
Nexons Network Solutions N.V. - Div, EUROMOLDZUID lll, lnduslrieloon l2
B-932o EREMBODEGEM iAALST) (Site 2)
TEST CERTIFICATEThe test resulis of ihe pe#ormed
No. TE 2I3test series ore given in the iest report17 15 from ELAB
Requesior: Nexons Neiwork Soluiions N.V. - Div. Eurormo$d
Zuid lll - lndustrieloon l2B-9320 Erembodegem (Aolsr)
r---.'--TEST OBJECTTYPEAssembly instruction
Roied voltoge UolUHighesi system voltoge U*Roted curreniMqnufocturerCoble reference
Request number
Stori ond end dote Test specificstionIEC 61 442 Cd.2 (OS/2(m5): Test methods(02/2006]- + AI (09'l2(Hr8): Test requirements
Tqhle 7 test sequence Dn
Screened seporoble elbow connector - Enterfoce iype AK2OOLR/GlS9l746-ENG - 2001R/G-CW45 23Aq.6s$st 2017 - revision 0
12,7/22 kY
24 kV
250 ANexons Network Solutions N.V. - div- Eurnon'rold (NNS)lx50 mm2 Cv 12/2A kYFACAB 90104 N2XSY 1x50 RM/16 l2/20k\f2fi17 <VDE> 0276(code iniern: 1 xSOCvZA -429 1 6)
TRF 20',r7-052
CENETEC ENHD 629.1 52
Test series:1A/1 1 /2017 - 05/02/2018
TEST RESULT: the test obiecl successfully possed ihe ryibed test series.